Page 1: AXIAL MADRID - RC-Clima€¦ · Type of compressor Scroll Nº of compressors ud 2 2 2 2 2 Nº of circuits ud 1 1 1 1 2 OUTDOOR FANS Type AC Axial Air flow m ³/h 8.300 14.500 14.300

AXIAL MADRID

MAD

ENG

Page 2: AXIAL MADRID - RC-Clima€¦ · Type of compressor Scroll Nº of compressors ud 2 2 2 2 2 Nº of circuits ud 1 1 1 1 2 OUTDOOR FANS Type AC Axial Air flow m ³/h 8.300 14.500 14.300

In RC Clima, we are not just offering a high-quality product, we also provide our costumers with a premium after sales and technical support

TOTA

L SU

PPORT

Technical support directly from RC Clima engineersCommisioning and maintenance programsOriginal spare parts

ENGIN

EERI

NG &

CUS

TOM

ISAT

ION

Engineered tailor-made solutionsGuidance to select the right option

TRAI

NING

HVAC training and courses

Dedicated training on RC Clima units, commisioning and maintenance operations

RC CLIMA AFTERSALES, 100% Technical support

Page 3: AXIAL MADRID - RC-Clima€¦ · Type of compressor Scroll Nº of compressors ud 2 2 2 2 2 Nº of circuits ud 1 1 1 1 2 OUTDOOR FANS Type AC Axial Air flow m ³/h 8.300 14.500 14.300

on/off compressor

Inverter compressor

AXIAL MAD is an efficient and reliable condensing unit for air handling purposes, available in heat pump or cooling only. The units are designed to be installed outdoor and connected through refrigeration pipework to an indoor unit which shall be ducted for air conditioning of medium and large areas, such as manufacturing plants, malls crowded shops, supermarkets...

The cooling and heating capacity cover from 25kW up to 80kW with a large range of options to give the right solution to every single installation.

The units use refrigerant R410A and are available with R134a as an option for high ambient applications.

The Inverter compressor makes it possible to precisely adjust the capacity of the equipment to the thermal demand of the installation, consuming only the electrical power needed at any time.

OPTIONALLY: INVE TE

PRECISION, EFFICIENCY AND RELIABILITY

Inverter equipment is the most economical option when considering seasonal operating costs.

COMPRESSOR POWER %

TEMPERATURE

ECOErP

Page 4: AXIAL MADRID - RC-Clima€¦ · Type of compressor Scroll Nº of compressors ud 2 2 2 2 2 Nº of circuits ud 1 1 1 1 2 OUTDOOR FANS Type AC Axial Air flow m ³/h 8.300 14.500 14.300

4

STANDARD FEATURES AND OPTIONS

Standard*Options

Galvanised sheet metal coated with an epoxy baked powder paint

Panel handlers for easy access

Thermo-acoustic fire resistant insulation foam

Compact and optimised design

• Customized design to meet special requirements

ENVE

LOPE

Scroll compressors

Compressors Crankcase heaters

Compressor discharge temperature protection

• Compressors jacket for lower sound levels• Compressor soft start

COM

PRES

SORS

Optimised coils manufactured from copper tube and aluminium fins

• Fins coating protection (Epoxi, Blygold©,…)

HEAT

EXC

HANG

ERS

REFR

IGER

ATIO

N CI

RCUI

T 1 or 2 refrigeration circuits

Tandem of scroll compressors per circuit

Thermostatic expansion valves (TEV)

Filter dryer

Full operating charge of R410 refrigerant

Binder points

Non-return valves

4 way valve for heat pump mode

High and low pressure switch

• Outside analogue pressure gauges• R-134a refrigerant for high ambient temperatures

VENT

ILAT

ION AC axial fans (2 speeds)

Low sound levels

High efficiency

Large airflow with mínimum sound levels

EC plug fans for further efficiency and high external static pressure, constant Air Flow, flexibility to adapt to the installation pressure drop with the minimum power input to always maintain the required air flow

• Axial EC fans with stepless head pressure control (PID)• EC Return fans• Upgraded fans for higher External Static Pressure (available for supply and return fans)

In accordance with EN-60204-1

Door interlocking electric isolator

Air Flow switch

Phase rotation protection

Fuse protection

Compressor starter contactors

Transformer

Sub circuit protection

Wired to the latest European standards and codes of practice

• Head pressure control (with 2 speeds)• Magnetothermal protection• Energy manager to monitor energy consumption.

ELEC

TRIC

AL C

OM

PONE

NTS

Category G4 air filter

• Category M5, M6, F7, F8, F9 • Filter change pressure switch

AIR

FILT

RATION

Page 5: AXIAL MADRID - RC-Clima€¦ · Type of compressor Scroll Nº of compressors ud 2 2 2 2 2 Nº of circuits ud 1 1 1 1 2 OUTDOOR FANS Type AC Axial Air flow m ³/h 8.300 14.500 14.300

Axial MADHigh efficiency and ecodesign at your service

• Free cooling (based on temperature or enthalpy), of 2 or 3 dampersEN

ERGY

SAVI

NGS

• Electric heating (1 or 2 stages) for additional heating• Low pressure hot water coil for additional heating• Air quality sensors (VOC and CO2)• Fire and smoke detector

OTH

ERS

1 or 2 refrigeration circuits

Tandem of scroll compressors per circuit

Thermostatic expansion valves (TEV)

Filter dryer

Full operating charge of R410 refrigerant

Binder points

Non-return valves

4 way valve for heat pump mode

High and low pressure switch

• Outside analogue pressure gauges• R-134a refrigerant for high ambient temperatures

Unity Software: Dedicated RC CLIMA software

All parameters and alarms can be monitored from the display

Scan cycling of 40ms

Time zone programming

Data logging and alarms log

BMS port communication via Modbus RTU

User Terminal Th-Tune

EC fans controlled via Modbus

Dedicated cuting-edge technology controller

• BMS Communication cards available (Bacnet, Modbus, Ethernet) • pGD Graphic Display

SOFT

WAR

E &

CONT

ROL

ECOErP

MODEL MAD025 MAD035 MAD045 MAD050 MAD065

COOLING MODETotal cooling capacity kW 25,5 36.5 43,1 49,0 65,4

Sensible cooling capacity 19,5 28,0 34,0 38,9 51,9

Input power in cooling kW 8,2 12,8 15,4 15,9 21,5

EER W/W 3,12 2,85 2,80 3,08 3,04

HEATING MODETotal heating capacity kW 24,9 36,0 42,8 48,0 64,1

Input power in heating kW 7,6 12,1 14,2 14,8 20,2

COP W/W 3,29 2,97 3,00 3,23 3,17

COMPRESSORSType of compressor Scroll

Nº of compressors ud 2 2 2 2 2

Nº of circuits ud 1 1 1 1 2

OUTDOOR FANSType AC Axial

Air flow m³/h 8.300 14.500 14.300 18.000 18.400

External static pressure Pa 50 50 60 55 55

INDOOR FANSType Centrífugo EC

Air flow m³/h 4.800 7.000 7.900 9.700 12.000

External static pressure Pa 437 412 178 257 636

GENERAL DATAMains incoming supply 400V-III+N-50Hz

Refrigerant R410A

TECHNICAL DATA*

Cooling capacity and input power at nominal conditions. Indoor temperature of DBT= 27ºC, WBT = 19ºC and outdoor temperature of DBT = 35ºC, in accordance with UNE-EN 14511 standard. Heating capacity and input power at nominal conditions. Indoor temperature of DBT = 20ºC, WBT = 15ºC max., And outdoor temperature of DBT = 7ºC, WBT = 6ºC, in accordance with UNE-EN 14511 standard.

*The information in this document is subject to change without previous notification. RC Clima does not accept liability for any error or omission.

Page 6: AXIAL MADRID - RC-Clima€¦ · Type of compressor Scroll Nº of compressors ud 2 2 2 2 2 Nº of circuits ud 1 1 1 1 2 OUTDOOR FANS Type AC Axial Air flow m ³/h 8.300 14.500 14.300

OPERATING LIMITS

¹ Down to 0ºC ambient with head pressure control

² For higher temperatures, contact RC-Clima for an R134a version

DIMENSIONS _ Condensing unit

MODE COOLING HEATING

INDOOR AIR DBT WBT DBT WBTMinimum 19ºC 14ºC 10ºC -Maxim 35ºC 24ºC 27ºC -

OUTDOOR AIR DBT WBT DBT WBTMinimum 18ºC1 - -10ºC -10ºCMaxim 48ºC2 - 24ºC 15ºC

H

AP

MAD – C MODEL MAD025 MAD035 MAD045 MAD050 MAD065

Width (W) mm 1470 1470 1470 2000 2000

Depth (D) mm 1000 1000 1000 1380 1380

Height (H) mm 1700 1700 1700 1500 1500

DIMENSIONS _Evaporator unitHorizontal PARIS

A

P

H

A

P

H

DIMENSIONS _Evaporator unitVertical NEW YORK

PAR – E MODEL PAR025 - E PAR030 - E

Width (W) mm 1675 1890

Depth (D) mm 785 820

Height (H) mm 565 620

NYC – E MODEL NYC020 - E NYC025 - E NYC035 - E NYC045 - E NYC050 - E NYC065 - E

Width (W) mm 1480 1480 1780 1780 2700 2700

Depth (D) mm 880 880 944 944 970 970

Height (H) mm 755 755 835 835 850 850

6

Page 7: AXIAL MADRID - RC-Clima€¦ · Type of compressor Scroll Nº of compressors ud 2 2 2 2 2 Nº of circuits ud 1 1 1 1 2 OUTDOOR FANS Type AC Axial Air flow m ³/h 8.300 14.500 14.300

A SOLUTION FOR EACH CHALLENGE

ROOFTOP BARCELONAThe perfect compact solution for large areas

HORIZONTAL PARISThe invisible solution for indoor installation in ceilings with a ductwork

VERTICAL NEW YORKAn invisible solution for installation in basements and machinery rooms with a ductwork

AXIAL MADRIDCondensing outdoor unit to be matched with an indoor unit.

OUTDOOR UNIT CONFIGURATIONS Condensing unit

INDOOR PAR MATCHING CONFIGURATIONSEvaporator unit _ideal for ceiling applications

INDOOR NYC MATCHING CONFIGURATIONSEvaporator unit

I

I

R

R

1 2

I

I

I I

R

R

RR

5 6

3 4

A

Axial MADHigh efficiency and ecodesign at your service

Page 8: AXIAL MADRID - RC-Clima€¦ · Type of compressor Scroll Nº of compressors ud 2 2 2 2 2 Nº of circuits ud 1 1 1 1 2 OUTDOOR FANS Type AC Axial Air flow m ³/h 8.300 14.500 14.300

High efficiency and ecodesign at your service

Polígono Industrial SkolCarretera Batllòria, Nave E

17451, Sant Feliu de BuixalleuGirona, España

[email protected]

Polígono Industrial GaseransCalle Ter, Parcela 6A

17451, Sant Feliu de BuixalleuGirona, España

[email protected]

14.05.101.006 V02


Recommended