DES
DRN
CKD
APPD
SCALE
ISSUED
ALL DIM. IN mm
AMDTDRAFTING STANDARD TO A.S.1100 CAD PRODUCT - DO NOT AMEND MANUALLY
DESCRIPTION
AMENDMENTS
NO DRN DATE CKD APPD
POWER STANDARD DRAWING
MAR'2011
N.T.S.
A.TAYLOR
A.TAYLOR
J.COPPINS
A.TAYLOR
7
3 J.C. MAR'11 A.T. S.C.
SF6 GAS LOAD BREAK SWITCH
FOR UNIVERSAL POLE CONSTRUCTION
ASSEMBLIES
2
10 4
8 1
7 1
6 6
5 1
4 1
3 2
2 6
1 6
ITEM QTY DESCRIPTION STOCK CODE
MATERIAL SCHEDULE
S01-1-4-10
22KV STRAIN INSULATOR ASSEMBLY S01-1-3-09
FIBREGLASS CROSSARM SHACKLE PLATE S01-1-4-37
S01-1-2-10FIBREGLASS HV TERMINATION CROSSARM
400813
S01-1-4-19HV SURGE ARRESTORS
400812
LINE POLE
FLAT CROSSARM BRACES 298687 S01-2-1-49
2
AR
12
1
AR
AR
22KV POST TOP INSULATOR 300467 S01-1-3-10
22KV POST TOP INSULATOR STUD 300517 S01-1-4-44
300368 S02-1-1-34
BELL MOUTHED LUGS FOR 150 SQMM FLEX CABLE 402692 S02-1-2-11
150 SQMM EPR INSULATED FLEXABLE COPPER CABLE
402362
2.5 SQMM LV INSULATED CABLE FOR POWER SUPPLY 2725 S02-1-1-14
4036
70 SQMM YELLOW/GREEN INSULATED COPPER CABLE 401059 S02-1-1-23
BATTERY CHARGER, RADIO AND 10M OF CONTROL CABLE
NGK GBS CONTROL ENCLOSURE, INCLUDES BATTERY,
DWG
DISCONNECT TEE 2295
AR
G.L. G.L.
12
00
800
HV SURGE
DIVERTERS
HV SURGE
DIVERTERS
ELECTRODE ELECTRODE
COPPER CABLE
70 SQMM Y/GR INSULATED
GBS
NGK
EARTHING SINGLE LINE DIAGRAM
ELEVATION "B"ELEVATION "A"
COPPER CABLE
INSULATED
70 SQMM Y/GR
EARTH
VT
EARTH
BOX
CONTROL
TO CONTROL BOX
ON OPPOSITE SIDE
VT TO BE MOUNTED
IN COMING TRAFFIC.
OPPOSITE SIDE TO
TO BE MOUNTED ON
CONTROL BOX
1 2 3
4
5
6
8
20
10
11
B A
ELEVATION KEY
ISOMETRIC VIEW
17
16
7
21
GBS CONTROL CABLE
1200
1200
VT POWER CABLE
POWER SUPPLY ARANGEMENT UPDATED
S01-2-7-11_2
14
23
22
24
NOTES
4 C.C. SEP'11 B.C. S.C.
ITEM 3, 4 CHANGED
ITEMS 22, 23, 24 AND NOTE 1 ADDED,
5 A.T. NOV'11 B.C. S.C.ITEMS 4, 17 UPDATED, NOTE 3 ADDED
6 A.T. JUL'13 B.C. B.C.ITEM 18 REMOVED, NOTE 3 CHANGED
25
1 VOLTAGE TRANSFORMER 406940 S01-1-6-16
11
12
13
14
15
16
17
18
19
20
2 SURGE ARRESTOR MOUNT21 413103
NGK GBS HANGING BRACKET
22 AR 402707
23 4 402689
24 1 406941
35SQMM FLEX INSULATED CABLE, HV POWER SUPPLY TO VT S02-1-1-34
COMPRESSION LUG, BELL MOUTH FOR 35SQMM FLEX CABLE S02-1-2-11
VT MOUNTING ADAPTOR BRACKET S01-1-6-16
414398
406938
S01-1-6-17
S01-1-6-17
S01-1-6-17
20MM DIAMETER CONDUIT FOR POWER SUPPLY CABLE
- - -
ATTACHMENT POINT
POLE EARTHING
125 MANUAL OPERATION NGK GBS (REFER NOTE 4)
REMOTE OPERATED NGK GBS (REFER NOTE 4)
-
-
- -
-
-
-
MANUAL OPERATION NGK GBS FOR NEW INSTALLATIONS.
IS PUT ON HOLD UNTIL FURTHER NOTICE. USE ITEM 25
THE USE OF ITEM 7 REMOTE NGK GBS AND CONTROL BOX 4.
FOR ALL OTHER NOTES REFER TO SHEET 1.3.
SWITCH.
VT SHALL BE CONNECTED TO THE SOURCE SIDE OF THE 2.
22, 23, AND 24 ARE NOT REQUIRED
FOR A NON-AUTOMATED INSTALLATION, ITEMS 15, 16, 17, 20, 1.
NOTE 4
REFER
DRAWINGNUMBERA3NORTHERN TERRITORY
7 I.B. JUL'17 B.C. B.C.
'B' AMENDED
ITEM 25 & NOTE 4 ADDED, ELEVATION
PR
OP
ER
TY
SID
E
RO
AD
SID
E
400823 S01-1-6-17
DES
DRN
CKD
APPD
SCALE
ISSUED
ALL DIM. IN mm
DRAWINGNUMBER
AMDT
A3
DRAFTING STANDARD TO A.S.1100 CAD PRODUCT - DO NOT AMEND MANUALLY
DESCRIPTION
AMENDMENTS
NO DRN DATE CKD APPDNORTHERN TERRITORY
POWER STANDARD DRAWING
PR
OP
ER
TY
SID
E
RO
AD
SID
E
G.L.
12
00
800
ELEVATION "A" ELEVATION "B"
B A
ELEVATION KEY
ISOMETRIC VIEW
SHOWN FOR CLARITY
CONTROL CABLE NOT
13 2
12 1
11 1
10
9
8 1
7 1
6 6
5 1
4 1
3 2
2 6
1 6
ITEM QTY DESCRIPTION STOCK CODE
MATERIAL SCHEDULE
S01-1-4-10
22KV STRAIN INSULATOR ASSEMBLY S01-1-3-09
FIBREGLASS CROSSARM SHACKLE PLATE S01-1-4-37
S01-1-2-10FIBREGLASS HV TERMINATION CROSSARM
400813
S01-1-4-19HV SURGE ARRESTORS
REMOTE OPERATED NGK GBS 400812
S01-2-1-03LV INSULATOR PINS TYPE LP AND LPN
S01-2-1-49
4 WIRE LV CROSSARM 298562 S01-1-2-11
LV SERVICE FUSE HOLDER 241109 S01-1-4-49
214
AR15
1216
117
18
19
120
22KV POST TOP INSULATOR 300467 S01-1-3-10
22KV POST TOP INSULATOR STUD 300517 S01-1-4-44
300368 S02-1-1-34
BELL MOUTHED LUGS FOR 150 SQMM FLEX CABLE 402692 S02-1-2-11
150 SQMM EPR INSULATED FLEXABLE COPPER CABLE
402362
21
63 AMP SERVICE FUSE 10322
70 SQMM YELLOW/GREEN INSULATED COPPER CABLE 401059 S02-1-1-23
DWG
DISCONNECT TEE 2295
AR
ITEM QTY DESCRIPTION STOCK CODE DWG
2 SURGE ARRESTOR MOUNT22 413103
1
2 3
4
5
125x125x1200x6 SHS DURAGAL GBS HANGING BRACKET
6
7
8
LINE POLE WELDED TYPE
4
13
2
10
11
12
9
1516
17
18 19
123 150x150x1480x6 SHS DURAGAL HV RISER DETAIL "C"
DETAIL "C"
1630
50
600
150 SHS DURAGAL
{2 x 26Ø
DIVERTERS DIVERTERS
ELECTRODE ELECTRODE
COPPER CABLE
70 SQMM Y/GR INSULATED POLE EARTHING ATTACHMENT POINT
GBS
NGK
COPPER CABLE
70 SQMM Y/GR INSULATED
LINE DIAGRAM
EARTHING SINGLE
EARTH
BOX
CONTROL
HV SURGEHV SURGE
NOTES
SF6 GAS LOAD BREAK SWITCH
FOR WELDED POLE CONSTRUCTION
ASSEMBLIES
S01-2-7-11_3MAR’2011
N.T.S.
A.TAYLOR
A.TAYLOR
J.COPPINS
A.TAYLOR
0 ISSUED FOR CONSTRUCTION J.C. APR’11 A.T. S.C.
TOP OF POLE
RISER TO BE FULLY 6mm WELDED TO
1200
60
03
60
{
2 x 26Ø
DETAIL "C"
2
1 A.T. AUG’11 B.N. S.C.NOTE 6 ADDED
414398
406938
S01-1-6-17
S01-1-6-17
12
00
CROSSARM ANGLE BRACES 400815
S01-1-6-17
LV INSULATED CABLE FOR POWER SUPPLY
-
-
BATTERY CHARGER, RADIO, CONTROL AND POWER CABLE
NGK GBS CONTROL ENCLOSURE, INCLUDES BATTERY,
20
ANACONDA CONDUIT FOR POWER SUPPLY CABLE
IN COMING TRAFFIC
OPPOSITE SIDE TO
BE MOUNTED ON
CONTROL BOX MUST
2 A.T. NOV’11 B.C. S.C.
SHALL BE POINTING TOWARDS THE GROUND.
SECURED WITH HALF SADDLES TO THE POLE AT 1000MM INTERVALS. ALL OPEN ENDS OF CONDUITS
CONTROL BOX POWER SUPPLY CABLE SHALL BE PROTECTED BY 20MM DIAMETER ANACONDA CONDUIT9.
SOURCE LV POWER SUPPLY FROM A TRANSFORMER UPSTREAM OF THE SWITCH.8.
FOR DETIALS ON SCADA AND COMMUNICATIONS REQUIREMENTS REFER TO S01-2-7-16.7.
FOR A NON-AUTOMATD INSTALLATION, ITEMS 12, 17, 18, 19 AND 20 ARE NOT REQUIRED.6.
CABLE TO BE LOOPED NEAR THE SWITCH.
RUN THE CONTROL CABLE UP THE MIDDLE OF THE POLE, EXCESS CONTROL 5.
REFER TO SHEET 2 FOR ALTERNATIVE POWER SUPPLY ARRANGEMENTS.4.
FIT SERVICE FUSE HOLDER WITH 63A FUSE.3.
INSULATED COPPER CABLE.
BOND SWITCH EARTH TO NEAREST SURGE ARRESTOR EARTH STUD VIA 70 SQMM YELLOW/GREEN2.
NEEDS TO BE ASSESSED IN ACCORDANCE WITH EG0/AS7000.
EARTHING RESISTANCE EXCEEDS 30 OHMS WITH ALL CMEN/MEN CONNECTIONS REMOVED, THE POLE
REFER TO S01-2-3-11, S01-2-3-12 OR S01-2-3-13 FOR UNDERGROUND EARTHING DETAILS. IF 1.
ITEM 4, 19 UPDATED, NOTE 8, 9 ADDED