UniMix air insulated medium voltage switchgear
� BA PTMV BU Switchgear
� Product Marketing
� Manuel Salvi
©A
BB
-P
age
2
Compliant with new IEC 62271-200(ex 60298) that classifies reliability and operating risks.
Classified by IEC 62271-200 as:metal-enclosedpartition metallic (compartments segregation) LSC2A
Loss of Continuity: Feeder Service: Compartment
Is compliant with IEC 60129 for indications.
UniMix Standards Compliance
©A
BB
-P
age
3UniMix characteristics
Maximum Flexibility up to 24kV
Interchangeable SF6/vacuum CBs
Sensors/DIN CT’s/Ring CT’s
Compact dimensions (375/500/750mm)
Wall standing
Bus bars CTs & VTs (W>375mm)
Full Int.Arc Proof 16kAx1s (0.5s for
W=375mm)
All earthed metal segregation
Welded tank
Short delivery time
©A
BB
-P
age
4
Maximum safety during maintenance and operations in the cable or fuse compartment even with bus bars energized.
Reduced risk of short circuit between phases or between the two insulators of the same phase
UniMix Characteristics
EARTHED metallic segregation between bus bar and feeder compartments
©A
BB
-P
age
5
Rated insulation voltage kV 12 17 24
Test Voltage (50-60 Hz/1 min) kV 28 38 50
Impulse withstand voltage kV 75 95 125
Rated frequency Hz 50/60 50/60 50/60
Rated main busbar current A 630/1250
Rated feeder current A 630/1250
Max. short-time current kA 25x1s 25x1s 25x1s
Max. making capacity kA 62.5x1s 62.5x1s 62.5x1s
SHS2 Gas absolute pressure (20 °C; SF6 350g) kPa 125
LBS motor kit Available
UniMix Characteristics
Electrical Data
©A
BB
-P
age
6UniMix Internal Arc Proof
Internal arc proof withstand current
500/750mm width units16kA for 1 second
20kA for 0.5 second
Tranne P1E e P1A
375mm width units12.5kA for 1 second
16kA for 0.5 second
“Light” version12.5kA for 1 second
©A
BB
-P
age
7
Arc-proof testaccording to IEC 298 standards, appendix AA, class A, criteria 1 to 5 / IEC 62271-200
Criteria:1 Correctly secured doors, covers do not open.2 Parts which may cause a hazard do not fly off.3 No holes in the freely accessible external parts
of the enclosure.4 Horizontally and vertically arranged indicators
do not ignite.5 Earthing connections are still effective.
Test
ing
setu
p
Infr
ared
cam
era
UniMix Internal Arc Proof
©A
BB
-P
age
8UniMix
SHS2 type Switch disconnector
SF6 insulated
Stainless steel enclosure
3 position: LINE – OPEN – EARTH
Making capacity Earthing Switch
Separate slots for SD and ES
IEC 60129 for indications
Motor operated mechanism on request
©A
BB
-P
age
9
2
SHS2 basic structure
Legend:1. Switching shaft - 2. Isolators - 3. Enclosure - 4. Fixed contacts - 5. Moving Contacts6. Earthing contacts - 7. Operating mechanism - 8. Rupture disk
2
4
7
14
5
68
2
3
2
7
UniMix
©A
BB
-P
age
10UniMix
SHS2: Three positions SD
OPENEARTH
LINE
©A
BB
-P
age
11
SHS2: Accessories
Caption:1 Line key locks2 Earth key locks3 Auxiliary contacts (2+2) 4 Opening coil5 Voltage indicators
3
4 5
1
2
3
3
1
UniMix
©A
BB
-P
age
12UniMix
Circuit breakers 230mm pole distance
On board PR521 relay and sensors
SF6 pressure switch on request
Motorised on request
©A
BB
-P
age
13UniMix
Protection & Control
REF542 Plus
PR521 & dedicated current sensors on
board of CB
PR512 & ring core type CTs
DIN 43625 Fuses
©A
BB
-P
age
14UniMix
Instrument transformers
Current and voltage transformers
Ring core type
DIN 42600DIN 42600
Combisensor
©A
BB
-P
age
15UniMix
New Units: P1/A
Rated insulation voltage kV 24
Test Voltage (50-60 Hz/1 min) kV 50
Impulse withstand voltage kV 125
Rated frequency Hz 50/60
Rated main busbar current A 630/1250
Rated feeder current A 400/630
Max. short-time current kA 16x1s
Max. making capacity kA 62.5x1s (ES excluded)
Maintenance of CB (opening of door) keeping MV cables enegised
©A
BB
-P
age
16UniMix
New Units: P1/E
Rated insulation voltage kV 24
Test Voltage (50-60 Hz/1 min) kV 50
Impulse withstand voltage kV 125
Rated frequency Hz 50/60
Rated main busbar current A 630/1250
Rated feeder current A 630/1250
Max. short-time current kA 25x1s
Max. making capacity kA 62.5x1s
Internal arc proof kA 16x1S
Withdrawable Circuit Breaker with front operating mechanism
Feeder current up to 1250A
DIN CTs and DIN VTs can be both housed in the feeder unit
©A
BB
-P
age
17UniMix
New Units: P1/E
©A
BB
-P
age
18
Unit P3 – Switch disconnector
UniMix
Opening coil
Motor operated mechanism
Bus Tie Unit
Available for 500 mm width units:
- DIN CTs (2 or 3)
- DIN VTs
- Busbars DIN CTs
- Busbars DIN VTs
©A
BB
-P
age
19
Unit P2 – Fused Switch disconnector
UniMix
Opening coil
Bus Tie Unit
Available for 500 mm width units:
- Busbars DIN CTs
- Busbars DIN VTs
©A
BB
-P
age
20
Unit P1/F – Circuit breaker
UniMix
DIN CTs (2 or 3)
DIN VTs
On board current sensors for PR521
Bus Tie unit
©A
BB
-P
age
21
Unit ASR – Switched Incoming
UniMix
Bus Tie unit
Available for 500 mm width units:
- DIN CTs (2 or 3)
- DIN VTs
- Busbars DIN CTs
- Busbars DIN VTs
©A
BB
-P
age
22
Unit A – Direct Incoming
UniMix
Available for 500 mm width units:
- DIN CTs (2 or 3)
- DIN VTs
©A
BB
-P
age
23
Unit R - Riser
UniMix
Available for 500mm width units:
- DIN CTs (2 or 3)
- DIN VTs
©A
BB
-P
age
24
Unit Rac – Direct cable Incoming
UniMix
Available for 500mm width units:
- DIN CTs (2 or 3)
- DIN VTs
©A
BB
-P
age
25
Unit M – Measure
UniMix
Busbars DIN CTs
DIN VTs
©A
BB
-P
age
26Secondary Distribution typical applications
Manufacturing industry
Secondary substations
Shopping centres
Airports
Undergrounds
Windmills
Production = 9’000 units/year
©A
BB
-P
age
27
Workshop : sqm. 5300Offices : sqm. 400
LoretoAprutino
Unimix factory and Production process
©A
BB
-P
age
28UniMix on inside.abb.com
General information
Documents download
Service and supportTraining & Technical Support
Audit & Consulting
Retrofit & Upgrades