[BACKUP METHOD OF SYSTEM PARAMETERS] November 5, 2014
Kohzu Precision Co., Ltd | Backup method of system parameters 1
Backup method of system parameters
Using Chamonix
Kohzu Precision Co., Ltd
1. Backup method of system parameters ........................................................... 2
2. Preparation for backup of system parameters .................................................. 2
2.1. Download the installer ............................................................................... 3
2.2. Install Chamonix ...................................................................................... 4
3. Start Chamonix ........................................................................................ 6
3.1. Select a port ........................................................................................... 6
3.2. Connect to SC controller ............................................................................ 8
4. Backup system parameters ......................................................................... 9
4.1. Start system parameters ............................................................................ 9
4.2. Save, print and send system parameters ...................................................... 11
4.3. Configuration of XML file .......................................................................... 13
5. Reset system parameters with Chamonix ..................................................... 14
6. Revision History ..................................................................................... 16
Figure 1 RS-232C cable ............................................................................ 2
Figure 2 The download screen in the Web site of our company ........................... 3
Figure 3 Folder after unzipped .................................................................... 4
Figure 4 InstallShield wizard screen ............................................................. 5
Figure 5 Main form when COM is not specified correctly .................................... 6
Figure 6 Starting the communication settings form ........................................... 7
Figure 7 Main form after connecting to SC controller (SC-410) ............................ 8
Figure 8 Start System Parameters of PM1 ..................................................... 9
Figure 9 Setting window of "PM1 System Parameters" .................................... 10
Figure 10 Open, Save, Print, and Send buttons ............................................. 11
Figure 11 Operation method of System Parameters ...................................... 12
Figure 12 Example when a saved XML file is opened ...................................... 13
Figure 13 Command button ..................................................................... 14
Figure 14 Send RST command ................................................................. 15
November 5, 2014 [BACKUP METHOD OF SYSTEM PARAMETERS]
2 Backup method of system parameters | Kohzu Precision Co., Ltd
1. Backup method of 1system parameters
This instruction manual describes the backup procedure using Chamonix, the standard
control software made by our company. Chamonix is available without fee from the Web
site of our company.2
2. Preparation for backup of system parameters
Chamonix communicates with a SC controller using 3RS-232C (Figure 1). The
communication baud rate of Chamonix is 115200 baud by default. Since the baud rate of a
SC controller is 38400 baud by default, it is necessary to change the setting of Chamonix.
The changing method of baud rate is also described next. If the DIP switch of the
controller's back is changed from default, return to the original position4.
Figure 1 RS-232C cable
1 System parameters saved in a SC controller may be referred to as system settings on control software of our company and old version of documents for SC controllers, etc. When referring to these documents, please regard system parameters in this manual as system settings. 2 Please read the terms and conditions for use of "Chamonix". 3 "SC controller" in this manual refers to SC-200, SC-200K, SC-200T, SC-400, SC-800, SC-210, and SC-410. A part of special custom-made products is excluded. 4 For details, refer to the instruction manual of corresponding SC controller.
RS-232C cable (cross)
•For details, refer to "2-3 Connecting Method" of the SC controller and "2-3 Connection Method" in the instruction manual of Chamonix respectively.
[BACKUP METHOD OF SYSTEM PARAMETERS] November 5, 2014
Kohzu Precision Co., Ltd | Download the installer 3
2.1. Download the installer
Figure 2 The download screen in the Web site of our company
Download from http://www.kohzu.co.jp/downloads/application/ (Figure 2).
The download file is compressed with ZIP format.
November 5, 2014 [BACKUP METHOD OF SYSTEM PARAMETERS]
4 Install Chamonix | Kohzu Precision Co., Ltd
2.2. Install Chamonix
Unzip the downloaded file to get the folder as shown in Figure 3. Execute "setup (.exe)"
with administrative privilege.
For details, refer to Chamonix User's Guide (ChamoniUsersGuide.pdf) in the unzipped
folder.
Figure 3 Folder after unzipped
The "Welcome to Chamonix InstallShield" wizard (Figure 4) is displayed. Follow the
instruction of the wizard to install5.
5 For details on installation, refer to "Chamonix User's Guide".
[BACKUP METHOD OF SYSTEM PARAMETERS] November 5, 2014
Kohzu Precision Co., Ltd | Install Chamonix 5
Figure 4 InstallShield wizard screen
November 5, 2014 [BACKUP METHOD OF SYSTEM PARAMETERS]
6 Start Chamonix | Kohzu Precision Co., Ltd
3. Start Chamonix
3.1. Select a port
When Chamonix is started, the following main form screen is displayed (Figure 5). This is
because a correct port to which the SC controller is connected is not selected correctly. If
the error dialog does not open, it connects to the SC controller automatically.
Figure 5 Main form when COM is not specified correctly
[BACKUP METHOD OF SYSTEM PARAMETERS] November 5, 2014
Kohzu Precision Co., Ltd | Select a port 7
Right click "Connect" in "Chamonix" to open the communication settings menu.
Figure 6 Starting the communication settings form
Select the port to which the SC controller is connected from "COM port" in the opened
menu and baud rate (default is 38400 baud), and click "Connect" in the menu or push the
"Connect" button in the main form.
November 5, 2014 [BACKUP METHOD OF SYSTEM PARAMETERS]
8 Connect to SC controller | Kohzu Precision Co., Ltd
3.2. Connect to SC controller
When connection to the SC controller is successful, the main form as shown in Figure 7 is
displayed. The figure shows the screen when connected to SC-410. For SC-020, 021, SC-
200, SC-200K, and SC-200T, only 2 axes are displayed.
Figure 7 Main form after connecting to SC controller (SC-410)
When the connection is conducted correctly, "Connected to SC (model name)" is displayed
in the status tool bar at the bottom of the main form. Please check the message is
displayed.
[BACKUP METHOD OF SYSTEM PARAMETERS] November 5, 2014
Kohzu Precision Co., Ltd | Backup system parameters 9
4. Backup system parameters
4.1. Start system parameters
When the "System" button of each axis is pushed, the pushed button turns ON in green as
shown in Figure 8, and the setting window of "System Parameters" as shown in Figure 9 is
displayed. In these figures, the "System Parameters" setting window of PMI axis is
displayed.
Figure 8 Start System Parameters of PM1
When the "System Parameters" setting window is opened, system parameters of the axis
are extracted from the controller. In the example shown in Figure 9, the parameters of PM1
axis only are extracted.
In Chamonix, it is required to save backup per axis of the SC controller. Please
note that it does not mean to save backup of all axes as a batch.
November 5, 2014 [BACKUP METHOD OF SYSTEM PARAMETERS]
10 Start system parameters | Kohzu Precision Co., Ltd
Figure 9 Setting window of "PM1 System Parameters"
[BACKUP METHOD OF SYSTEM PARAMETERS] November 5, 2014
Kohzu Precision Co., Ltd | Save, print and send system parameters 11
4.2. Save, print and send system parameters
The values of "System Parameters" in each axis can be saved as binary format (*.bin) or
XML format 6file. The saved file can be imported as the parameters of a displayed axis by
pushing the "Open" button. For the position of each button, refer to Figure 10.
Figure 10 Open, Save, Print, and Send buttons
Push the "Print" button to print parameters. Push the "Send" button to apply edited system
parameters as parameters of the axis in the SC controller.
In Chamonix, it is required to save backup per axis of the SC controller. Please
note that it does not mean to save backup of all axes as a batch.
6 XML1.1 (JIS X 4159:2005) format is used.
November 5, 2014 [BACKUP METHOD OF SYSTEM PARAMETERS]
12 Save, print and send system parameters | Kohzu Precision Co., Ltd
Figure 11 Operation method of System Parameters
Values saved in a CSV file is imported to the form when "Open" is executed.
Always push the "Send" button to actually apply them to the SC controller.
• Push the "Save" button to save system parameters of the SC controller in binary format or XML format.
Save
• Push the "Open" button to import system parameters saved in binary format or XML format to Chamonix.
Open• Push the "Print" button to
print system parameters of the SC controller.
• Push the "Send" button to apply the values displayed in the form to the SC controller.
Send
[BACKUP METHOD OF SYSTEM PARAMETERS] November 5, 2014
Kohzu Precision Co., Ltd | Configuration of XML file 13
4.3. Configuration of XML file
Saved XML file is shown in Figure 12. The file is configured with such variables as a model
of the controller, display resolutions inside Chamonix, each parameter and speed table.
Though each variable is editable, the order of variables cannot be changed. If the order of
variables is changed, it may not be read correctly.
Figure 12 Example when a saved XML file is opened
Our company does not recommend modifying a backup file with anything but
Chamonix. From the standpoint, it is recommended to save as a binary file.
November 5, 2014 [BACKUP METHOD OF SYSTEM PARAMETERS]
14 Reset system parameters with Chamonix | Kohzu Precision Co., Ltd
5. Reset system parameters with Chamonix
SC-020 and SC-021 do not have a front panel. Therefore, reset should be performed by
sending RST command with control software like Chamonix or by setting SYS No.36 of the
system parameters to 1 with the optional product, RC-10 (production has finished). The
reset method of system parameters using Chamonix is described.
Figure 13 Command button
As shown in Figure 13, push the Command button at the top part of the main form.
"Chamonix Command Control" opens. As shown in Figure 14, enter "RST" in the sending
box at the bottom part, and push the "Enter" key to send the RST command to the SC
controller. As shown in the figure, the reply from the SC controller is displayed as "→C RST" that indicates the system parameters are successfully reset.
When system parameters are reset, the values of all system parameters become the default values. Always perform backup before execution.
[BACKUP METHOD OF SYSTEM PARAMETERS] November 5, 2014
Kohzu Precision Co., Ltd | Reset system parameters with Chamonix 15
Figure 14 Send RST command
November 5, 2014 [BACKUP METHOD OF SYSTEM PARAMETERS]
16 Revision History | Kohzu Precision Co., Ltd
6. Revision History
Date Version Person
in charge
Remarks
2013/11/29 Rev.1.0 Okui
2014/11/05 Rev.2.0 Okui Changed software to Chamonix.
[BACKUP METHOD OF SYSTEM PARAMETERS] November 5, 2014
Kohzu Precision Co., Ltd | Revision History 17