applied sciences Article Basic Chemical Tests of Concrete during the Assessment of Structure Suitability—Discussion on Selected Industrial Structures Jacek Hulimka and Marta Kalu˙ za * Faculty of Civil Engineering, Silesian University of Technology, 44-100 Gliwice, Poland; [email protected] * Correspondence: [email protected]; Tel.: +48-32-237-20-37 Received: 12 November 2019; Accepted: 28 December 2019; Published: 3 January 2020 Abstract: Making a decision to perform an overhaul of a damaged reinforced concrete structure should be preceded by an analysis of the real durability of that structure after the repair in connection with the anticipated service life. One of the basic problems is the avoidance of further corrosion of concrete and steel after the repair, which depends on the degree of concrete contamination with harmful chemical factors. It is particularly important to determine the content of chloride and sulfate ions which cause corrosion. Concrete pH is equally significant because it conditions eective passivation of the reinforcement. The paper presents the basic issues related to the main chemical threats, including the main sources of their origin as well as their limit values. It emphasizes the importance of conducting the chemical tests of concrete, which should be treated as one of the methods of determining structure suitability for an overhaul, especially in the context of subsequent durability. This seems obvious to an experienced specialist, but in practice, such studies are often ignored. Those considerations are backed up with selected examples of reinforced concrete industrial structures exposed to aggressive chemicals during their operation. The text shows the correlation between their technical condition and chemical test results as well as the influence of those results on making decisions concerning eective overhauls. Keywords: reinforced concrete; durability; chemical tests; diagnostic; industrial structures; corrosion 1. Introduction Given the present development of construction chemistry, the thesis that nearly every reinforced concrete (RC) structure can be repaired even if its technical condition is very bad can be proposed. By technical condition, the authors understand the actual condition of the RC element, taking into account its original manufacturing defects, mechanical damage, and chemical pollution—in relation to a new, properly made element. A repair is defined herein as restoration of original features of the structure, especially its load-bearing capacity and rigidity. The proposed thesis is true to a certain extent, but it requires answering the following questions. Is the repair cost-eective from an economic point of view? Does the scope of the necessary repair works actually cover the replacement of substantial parts of the structure (which would be reconstruction or modernization rather than a repair)? What will the real structure durability be after the repair and is it satisfactory concerning the anticipated further service life of the facility? Certainly, the above questions do not cover all the doubts. This paper discusses the real durability of repaired RC structures from which a relatively long period of further service life is required. Appl. Sci. 2020, 10, 358; doi:10.3390/app10010358 www.mdpi.com/journal/applsci
Transcript

applied sciences

Article

Basic Chemical Tests of Concrete during theAssessment of Structure Suitability—Discussion onSelected Industrial Structures

Jacek Hulimka and Marta Kałuza *

Faculty of Civil Engineering, Silesian University of Technology, 44-100 Gliwice, Poland; [email protected]* Correspondence: [email protected]; Tel.: +48-32-237-20-37

Received: 12 November 2019; Accepted: 28 December 2019; Published: 3 January 2020�����������������

Abstract: Making a decision to perform an overhaul of a damaged reinforced concrete structureshould be preceded by an analysis of the real durability of that structure after the repair in connectionwith the anticipated service life. One of the basic problems is the avoidance of further corrosionof concrete and steel after the repair, which depends on the degree of concrete contamination withharmful chemical factors. It is particularly important to determine the content of chloride andsulfate ions which cause corrosion. Concrete pH is equally significant because it conditions effectivepassivation of the reinforcement. The paper presents the basic issues related to the main chemicalthreats, including the main sources of their origin as well as their limit values. It emphasizes theimportance of conducting the chemical tests of concrete, which should be treated as one of themethods of determining structure suitability for an overhaul, especially in the context of subsequentdurability. This seems obvious to an experienced specialist, but in practice, such studies are oftenignored. Those considerations are backed up with selected examples of reinforced concrete industrialstructures exposed to aggressive chemicals during their operation. The text shows the correlationbetween their technical condition and chemical test results as well as the influence of those results onmaking decisions concerning effective overhauls.

Keywords: reinforced concrete; durability; chemical tests; diagnostic; industrial structures; corrosion

1. Introduction

Given the present development of construction chemistry, the thesis that nearly every reinforcedconcrete (RC) structure can be repaired even if its technical condition is very bad can be proposed. Bytechnical condition, the authors understand the actual condition of the RC element, taking into accountits original manufacturing defects, mechanical damage, and chemical pollution—in relation to a new,properly made element. A repair is defined herein as restoration of original features of the structure,especially its load-bearing capacity and rigidity. The proposed thesis is true to a certain extent, but itrequires answering the following questions.

• Is the repair cost-effective from an economic point of view?• Does the scope of the necessary repair works actually cover the replacement of substantial parts

of the structure (which would be reconstruction or modernization rather than a repair)?• What will the real structure durability be after the repair and is it satisfactory concerning the

anticipated further service life of the facility?

Certainly, the above questions do not cover all the doubts. This paper discusses the real durabilityof repaired RC structures from which a relatively long period of further service life is required.

Appl. Sci. 2020, 10, 358; doi:10.3390/app10010358 www.mdpi.com/journal/applsci

Appl. Sci. 2020, 10, 358 2 of 16

Examples presented in the paper include RC support structures of power boilers and trestle bridgesunder industrial systems. In those cases, industrial devices are fairly often replaced entirely—thisraises a question concerning the possibility of performing an overhaul of the RC support structure andusing it further. This is caused both by the willingness to save money and the time pressure related tothe performed works. However, the economic aspect is usually less important because repairing aseverely damaged structure is quite costly as well—which results from the cost analysis of repairs ofreal objects that the authors performed during their many years of practice in evaluating and planningvarious overhauls of RC structures. The willingness to save time is more significant—demolition andreconstruction of an RC structure last much longer than its repair. Therefore, an investor relativelyoften forces a repair of RC support structures even if their technical condition is very bad.

Both object owners, as well as designers dealing with such repairs, often think that appropriatelyapplied repair materials allow restoring the original features of a damaged structure. In principle, sucha stance is justified if one takes into account a period lasting a few years. However, the service lifeof new power boilers, process pipelines, and other industrial devices is defined as 20–30 years andsometimes even more. Thus, the use of support structures should be planned for the same period.This creates a problem of assessing the suitability of a damaged structure for repairs guaranteeingreliable operation throughout an anticipated long period. From a practical point of view, it is importantthat the assessment method should be relatively quick and cheap and does not require specializedequipment or examination techniques.

This study investigated the influence of basic concrete chemical tests on RC structure suitability foran overhaul through literature review and case-studies verification. The basic threats to RC structuredurability, with particular reference to chemical factors, are presented and discussed. This stems fromthe fact that any mechanical damage can be repaired because its causes are usually temporary—as anexample, damage to the hall’s supporting column as a result of being hit by a forklift [1]. On the otherhand, chemical agents usually cause permanent changes that hinder durable repairs or reinforcementsand sometimes even make those impossible—as shown in this paper. The main thesis of this paperthat the factor determining the possibility of effective and durable repairs of a corroded RC structure isits chemical condition is discussed and confirmed by actual cases of damaged industrial structures.

2. Basic Threats to RC Structure Durability—Short Literature Review

Reinforced concrete is a durable structural material and the steel reinforcement inside it is safefrom corrosion. The above is true under the condition that the concrete and the reinforcing steelis well-protected against corrosion beforehand. In the case of relatively new concrete with correctcomposition and structure (high pH), the reinforcing steel surface is passivated and effectively protectedagainst corrosion [2]. However, concrete surface pH decreases in time, which makes the concretegradually lose its protective properties. Simultaneously, the threat of concrete contamination withaggressive chemical agents increases as they penetrate the concrete near the reinforcement. Concretecontamination is both aggressive ions (chloride, sulfate, nitrogen) from the environment, as well ascarbon dioxide causing carbonation. If a structure is continuously exposed to aggressive chemicalfactors, this process becomes progressive. Corrosion processes can be significantly delayed by usingvarious types of concrete surface protection against the penetration of aggressive factors [3–5] or theuse of low absorption concrete [6].

Very simplified divisions group factors threatening RC structure durability into mechanical,atmospheric, biological, and chemical ones [7]. In practice, it is sometimes hard to distinguish betweenseparate risk factors because their effects are often strongly interrelated (e.g., chemical aggressioncauses steel corrosion; then, swelling corrosion products burst concrete, which is a mechanical action).The selected examples presented below are aimed at depicting their influence on the possibility of adurable and effective structure repair.

Purely mechanical damage often results from impact or other action which are incidental [1].In such cases, the usefulness of the damaged element for repair must be determined by the size of

Appl. Sci. 2020, 10, 358 3 of 16

the damage and the cost-effectiveness of the repair in relation to the costs of replacing a part of thestructure. Another type of mechanical damage is concrete surface abrasion by a stream of liquid orgas—this does not influence structure suitability for an overhaul, either. A specific group is mechanicaldamage resulting from repeated repetitive fatigue loads. Reinforced concrete crane beams are a goodexample here. In this case, the occurrence of mechanical damage usually prevents effective repairs,because the structure of concrete and reinforcing steel is damaged.

Most cases of atmospheric damage have the form of frost corrosion. Therefore, those donot preclude durable repairs, even though they do result in cover thinning, thus facilitatingchemical aggression.

Many biological factors also come down to mechanical action, for example when plant rootsburst concrete. Sometimes the organisms living on the concrete surface are chemically aggressive aswell. For example, lichens can cause chemical decomposition of concrete and pollute it with sulfurcompounds. The activity of bacteria is equally detrimental as they can also pollute concrete with sulfurcompounds [8–10].

Still, chemical agents form the most significant group of impact factors causing corrosion of concreteand reinforcement. Some of them are present in the atmosphere—an example is carbon dioxide whichcauses carbonation in concrete [7,11]. Other typical corrosion factors are sulfur compounds, whichform gypsum in concrete (through the reaction of sulfate ions with portlandite) and, in the subsequentphase, ettringite which can be, or not, expansive. Sulfur compounds are present, among other things,in the so-called industrial atmosphere and in a part of groundwater [7,12]. The abovementionedbiological corrosion is also a source of concrete contamination with sulfur compounds. Publication [13]contains an interesting overview covering the territory of Germany. The authors undermine, to acertain extent, the classical idea of a sulfate attack caused by the migration of sulfate ions from soil orwater and highlight the detrimental influence of gypsum.

Another widespread corrosion agent is sodium chloride, found naturally in seawater and a partof the groundwater. Its significant concentrations are also transferred to the environment duringthe deicing of communication surfaces. Chlorides react with cement hydration products (calciumhydroxide i.e., portlandite, C-S-H phase), destroy the passivation layer and directly cause steelcorrosion [12,14,15]. A specific source of chlorides is also coal mine water, a huge volume of whichis discharged to surface waters. In the years 1995–1998, the daily discharge of Cl− and SO4

2− saltsto the upper drainage basin of the Odra and Vistula Rivers was approximately 7000 tons [16]. Forexample, water from the level of 665 m in the “Wesoła” coal mine contains more than 35 g/dm3 ofchloride ions [17]; in extreme cases, that content reaches 200 g/dm3 [16]. That water often comes intocontact with industrial structures, introducing chloride ions into the concrete. Such a situation wasdescribed in the paper [18] where, among others, the corrosion of the RC silo caused by coal minewater led to extensive structural failure.

Certain effects of chemical aggression also exert a mechanical impact. This happens in three ways:

• New chemical compounds forming in concrete increase their volume and burst the surroundingmaterial (ettringite, gypsum, thaumazite, Candlot salt, calcium carbonate, expansive calciumchloride, and expansive magnesium chloride);

• Similarly, swelling products of reinforcing steel corrosion burst the concrete cover (ion oxides andhydroxides);

• Soluble compounds forming in concrete discharge a portion of the matter beyond the concreteelement (acid calcium carbonate).

The abovementioned factors are not an exhaustive list of the enormous number of chemicalsubstances aggressive for concrete, but they are the most common and relatively easy to examine ones.The latter part of the paper describes the results of basic laboratory tests concerning the assessmentof concrete pollution with the typical chemical factors as well as relates the obtained results to thepossibility and justifiability of industrial support structure repairs.

Appl. Sci. 2020, 10, 358 4 of 16

Due to the nature of the paper, a chemical description of corrosive processes is not included hereinbecause the content and aim of the paper are different. Such descriptions can be found in a number ofreferences [7,19–21].

The article also omits issues related to the use of typical non-destructive tests [22] andnon-destructive electrochemical techniques to evaluate the corrosion of steel reinforcement—includingthe examination of the corrosion potential of steel and the corrosion rate of steel [23–25]. Such testsare extremely helpful in assessing the risk of steel corrosion in RC; however, their main advantage isdetermining the level of steel corrosion without disturbing the continuity of concrete cover. Meanwhile,the article describes the cases of constructions in which the degree of corrosion damage was sosignificant that the use of advanced non-destructive methods was unnecessary—most of the corrosiondamage was clearly visible.

3. Chemical Tests

3.1. Need for Chemical Tests

An analysis of numerous technical studies concerning repairs of RC structures after many yearsof operation shows that the most frequently recommended works are those consisting in the removalof visible damage to concrete and reinforcement. Therefore, the recommendations come down to anumber of activities which, assuming a certain simplification, can be described as follows: Hacking off

damaged or weakened concrete, cleaning the surface of concrete and the uncovered reinforcement,supplementation of significant reinforcement losses, application of a bonding layer (in some systemspreceded by application of corrosion inhibitors on rebars), filling of deep losses, filling of shallowlosses (patching), and (not always) application of protective layers. Typical polymer cement concrete(PCC) repair systems are usually recommended here.

The range and scope of necessary repairs with the relevant requirements have been described indetail in a group of Polish standards PN-EN 1504—Products and systems for the protection and repairof concrete structures (part 1 to 10) [26].

Such an approach leads to the restoration of the original geometry of the element (and restorationof reinforcement, if necessary). However, the success may be ostensible if the original concrete instructure is strongly carbonated or contaminated with harmful ions retained in the deeper layers. Insuch a case, the original concrete and the reinforcement are exposed to corrosion which starts virtuallyright after repair completion. The application of appropriate corrosion inhibitors does slowdown thatprocess, but it progresses much faster than in new concrete anyway.

One must also remember that supplementing the corroded reinforcement so that the originalamount is restored, which is often done in practice, may prove insufficient. First, the deformations ofthe original and new reinforcement are not compatible. Second, the yield strength of corroded rebars islowered [27]. The latter aspect is also related to chemical contamination of concrete and the possibilityof a durable repair of the structure.

Meanwhile, there is a simple and cheap method of determining the potential effectiveness of RCrepairs throughout a longer period. In each case, one should conduct at least random examinationsof the basic chemical features of the original concrete, including pH and the content of chloride andsulfate ions. Depending on the obtained results, the structure may:

• Be repaired without additional treatment;• Undergo additional treatment (e.g., re-alkalization or electrochemical chloride extraction ECE) if

the results point to a corrosion threat, but the condition of concrete can be improved;• Not be qualified for repair due to a significant threat to durability.

Unfortunately, the last option is rarely applied in practice. Examples of the effects of such conductshall be shown in the next chapter.

The authors argue that in the case of every RC structure used for a long period or in conditionsthreatening it with concrete penetration by chlorine or sulfur compounds, the decision to repair the

Appl. Sci. 2020, 10, 358 5 of 16

corrosive damage should be determined by conducting basic chemical examinations of concrete. Thoseexaminations are relatively cheap and do not take much time. Their results, if interpreted correctly,allow one to make an informed decision about repairing the RC structure with its durability in mind.

3.2. Typical Methods of Chemical Testing

3.2.1. Determination of the Chloride and Sulfate Ions

Generally, chloride and sulfate ions content tests should be carried out on powdered samplesof concrete taken during drilling or from core drilling or other concrete fragments obtained from thestructure. Test samples should be taken from representative places (in concrete cover, especially at thereinforcement surface) where there is a risk of pollution. It is recommended that samples be taken fromdifferent depths. The minimum required amount of sample is 1 g, however, when collecting powderedsamples it is recommended to collect about 20 g of the material, so as to ensure the representativenessof all concrete components. The test drilling should have a diameter of 30 to 50 mm; they can be cutinto slices or crushed at different depths.

There are two similar chemical laboratory tests that allow direct determination of chloride contentin a concrete sample (mass percentage of chloride referred to total concrete or to binder)—the Mohror Fajans method [28,29]. In both cases, the principle of the method is the reaction of precipitationfrom a solution containing Cl− ions (concrete power) of sediment (AgCl) using a silver nitrate solution(AgNO3) of an exactly known concentration. In the first method, potassium chromate (K2CrO4) isused as an indicator, which causes the solution to become reddish–brown. The test environmentmust be neutral or weakly alkaline (pH from 7 to 10.5). In the case of the Fajans method, a differentindicator is used. This is fluorescein in the form of an aqueous solution of fluorescein sodium, whichis an adsorption indicator. This causes color changes that are observed, not in the solution (as inthe Mohr method), but on the surface of the sediment. In this method, the chlorides can only bedetermined in neutral solutions. To calculate the chloride content, an equation is used that is identicalin both methods.

There is also a standard way of determining the chloride content in hardened concrete describedin the PN-EN 14629:2008—Products and systems for the protection and repair of concrete structures;Test methods—determination of chloride content in hardened concrete [30]. The procedure for thedetermination of chloride ions by the Volhard method (Method A) and the potentiometric method(Method B) are described here. Method A is quite similar to the described above two (Mohr or Fajans)with a different type of indicator. This is an iron–ammonium alum, which forms a red complex withthe first drop of excess thiocyanate solution. Method B is based on potentiometric titration [31] ofa silver nitrate solution (AgNO3). The test consists of adding small multiples of the solution to thepowered concrete sample, recording potential changes, and determining the first derivatives from theobtained data. In both cases (Methods A and B), the standard provides a formula for calculating thechloride content as a percentage of chloride ions in relation to the sample mass. The Volhard method isthe most commonly used in practice for the determination of the chloride content in concrete [32]. Themain Rilem recommendations are based on this method [33,34].

To determine the content of sulfate ions in the concrete sample, a typical chemical laboratorytest—the gravimetric method [28]—is used. The determination is based on the precipitation of sulfatesfrom the concrete power (on hot) in acidic solution (HCl), using barium chloride (BaCl2). Then, thehardly soluble barium sulfate (BaSO4) is precipitated, which after roasting is weighed and convertedinto the content of SO4

2− ions.

3.2.2. Carbonation—Determination of the pH Value

There are two typical methods to determine the pH value of hardened concrete. The first one isthe laboratory method and the second one uses the indicator, which is sprayed onto the surface of theconcrete breakthrough.

Appl. Sci. 2020, 10, 358 6 of 16

The first method is very precise and is made using a pH-meter. The pH value is measured inwater extracts obtained after the treatment of the crushed concrete sample with boiling water. Theweight ratio here is 1 part concrete to 10 parts water. In this method, it is important to separately testsamples from individual layers (depths) of concrete, because a test made of a too deep part of theconcrete cover gives an average result.

The indicator methods are simplified, which can be used also as in-situ tests. They consist ofspraying on the fresh concrete breakthrough the appropriate indicator preparation and reading the pHvalue from the available range. The following types of tests can be used.

• Phenolphthalein or thymolphthalein test.

The first one complies with the PN-EN 14630:2007 standard [35]. The indicator here is an alcoholsolution of phenolphthalein, which is colored on red–purple only at pH values higher than 8.5 ÷9.5. This is quite a rough estimate of the pH value. A more accurate estimate can be obtained byusing the second test, where the indicator is thymolphthalein. The concrete surface is colored innavy blue, at pH values higher than pH 9.3 ÷ 10.5

• Rainbow test.

This test is the most accurate of the indicator tests available [22]. It allows the assessment of theintensity of the carbonation process, due to the dyeing of the concrete breakthrough in variouscolors in the range from pH 5 to pH 13.

Figure 1 shows the colors obtained for the appropriate pH value at the above indicator tests. Thecolor, and thus the pH value, also identifies the level of carbonation.

Appl. Sci. 2020, 10, x FOR PEER REVIEW 6 of 16

3.2.2. Carbonation—Determination of the pH Value

There are two typical methods to determine the pH value of hardened concrete. The first one is the laboratory method and the second one uses the indicator, which is sprayed onto the surface of the concrete breakthrough.

The first method is very precise and is made using a pH-meter. The pH value is measured in water extracts obtained after the treatment of the crushed concrete sample with boiling water. The weight ratio here is 1 part concrete to 10 parts water. In this method, it is important to separately test samples from individual layers (depths) of concrete, because a test made of a too deep part of the concrete cover gives an average result.

The indicator methods are simplified, which can be used also as in-situ tests. They consist of spraying on the fresh concrete breakthrough the appropriate indicator preparation and reading the pH value from the available range. The following types of tests can be used.

• Phenolphthalein or thymolphthalein test. The first one complies with the PN-EN 14630:2007 standard [35]. The indicator here is an alcohol solution of phenolphthalein, which is colored on red–purple only at pH values higher than 8.5 ÷ 9.5. This is quite a rough estimate of the pH value. A more accurate estimate can be obtained by using the second test, where the indicator is thymolphthalein. The concrete surface is colored in navy blue, at pH values higher than pH 9.3 ÷ 10.5

• Rainbow test. This test is the most accurate of the indicator tests available [22]. It allows the assessment of the intensity of the carbonation process, due to the dyeing of the concrete breakthrough in various colors in the range from pH 5 to pH 13.

Figure 1 shows the colors obtained for the appropriate pH value at the above indicator tests. The color, and thus the pH value, also identifies the level of carbonation.

Figure 1. The colors used to determine the pH value of concrete and its carbonation level.

3.3. Permissible Values of Tested Parameters

The recommendations contained in the European standards and the model standard, fib-Model Code 2010, concerning concrete durability in relation to corrosion factors are described in detail in [21] and other publications. In general, the design of an overhaul or modernization of an RC structure has to be based on the recommendations contained in the standards (in the scope of the permissible content of harmful ions) and utilize generally accepted, examination-based pH values.

The conducted chemical examinations focused on three basic parameters: The content of chloride ions (Cl−) and of sulfate ions (SO42−), as well as the concrete reaction connected to the carbonation process.

Under PN-EN 206+A1. Concrete—Specification, performance, production and conformity [36], the maximal content of chloride ions (Cl−) in concrete in relation to the cement mass (including type

Figure 1. The colors used to determine the pH value of concrete and its carbonation level.

3.3. Permissible Values of Tested Parameters

The recommendations contained in the European standards and the model standard, fib-ModelCode 2010, concerning concrete durability in relation to corrosion factors are described in detail in [21]and other publications. In general, the design of an overhaul or modernization of an RC structurehas to be based on the recommendations contained in the standards (in the scope of the permissiblecontent of harmful ions) and utilize generally accepted, examination-based pH values.

The conducted chemical examinations focused on three basic parameters: The content of chlorideions (Cl−) and of sulfate ions (SO4

2−), as well as the concrete reaction connected to the carbonation process.Under PN-EN 206+A1. Concrete—Specification, performance, production and conformity [36],

the maximal content of chloride ions (Cl−) in concrete in relation to the cement mass (including typeII additives) is: 0.1% or 0.2% in structures with prestressing steel reinforcement; 0.2% or 0.4% instructures with ordinary steel reinforcement; 1.0% in structures without reinforcement. Such strictrequirements (as well as their differentiation depending on the presence and type of reinforcement)

Appl. Sci. 2020, 10, 358 7 of 16

stem from the fact that chloride ions do not only cause concrete corrosion, but also—or actually firstand foremost—corrosion of steel reinforcement and other elements [7,14]. Determination of chloridecontent in relation to cement is convenient because it allows obtaining reproducible results and presentsthe proportions between the aggressive action of chlorides and the inhibiting effect of cement [37].At the same time, the literature contains a number of author’s concepts concerning critical chloridecontent as well as chloride content examination methods [38–40]; unfortunately, some of them lead tocertain interpretation contradictions, thus hindering assessment of results. It should be highlightedthat under PN-EN 197-1:2012 standard [41] chloride content in cement as the construction materialmust not exceed 0.1%.

The maximal content of sulfate ions (SO42−) is 0.5% of the concrete mass. Given the cement content

of 300 kg/m3 of concrete mixture, this means approx. 3% in relation to binder mass. This value isrelatively high, but one must be aware that a certain amount of sulfur compounds is already containedin cement and their excessive amount that penetrates the material comes from the surroundings ofthe structure.

The concrete reaction is not regulated by provisions of standards, but numerous tests conductedallow to state certain universal recommendations. In the first phase of material existence, the reactionis strongly basic—a pH of more than 12. The reaction of carbon dioxide with calcium hydroxidecreates calcium carbonate, which initially has a good influence on the structure because it seals thestructure surface [11]. At the next stage, calcium carbonate is transformed into soluble bicarbonate ionswhich are then washed out from the structure. This process lowers concrete reaction and deterioratesconcrete structure. It is a progressive phenomenon, both in terms of concrete reaction lowering ina given layer and the depth at which it takes place. If concrete pH is lowered to approx. 11.8, thepassivation layer on the reinforcement is damaged for the first time, which initiates corrosion processes.Further pH decrease results in the complete destruction of the passivation layer and a risk of seriouscorrosive damage to the reinforcement. Long-lasting carbonation may lower concrete pH even to8.3 [42], causing the anti-corrosive properties of the cover to disappear completely.

4. Discussion Based on Practical Examples

4.1. A Short Description of the Structures

To back up the above descriptions with practical examples, the paper cites the results of the basicchemical tests of concrete in selected industrial support structures. The cited results are comparedwith the actual technical condition of the structures in question.

All the structures were built in the second half of the 20th century and their age (and operationperiod) at the time of the examinations was 45–55 years.

The first case was a support structure of a WR-25 power boiler. The structure consisted of a bottomslab (on piles) and a spatial frame resting on it. The frame consisted of nine columns and a top gridtied with a plate with openings. This structure is hereinafter referred to as A.

In the second case, the analysis covered the support structures of four power boilers—three of theWLM-5 type and one of the WR-10 type. Each of the identical support structures of WLM-5 boilersconsisted of a bottom slab with two flat frames fixed in it. Each frame consisted of two columns joinedby a lock with brackets and the locks were joined by a plate. Those structures are hereinafter referredto as B1, B2, and B3. The support structure of the WR-10 boiler was similar, but each frame containedthree columns. This one is hereinafter referred to as B4.

In the third case, the analysis covered two identical foundations of WLM-25 boilers which weregeometrically similar to the first foundation (A), but their dimensions were different. Those structuresare hereinafter referred to as C1 and C2.

The fourth case was slightly different in terms of construction because it was a pipeline supportsystem in a steel plant. The trestle bridge was designed and built as an RC one, structurally joined withan open water channel. In structural terms, the trestle was an RC spatial frame consisting of two-level

Appl. Sci. 2020, 10, 358 8 of 16

columns joined by longitudinal and transverse locks; the top tier beams were joined by a plate. At anunknown time, the top longitudinal beams were confined in a steel sheet housing. In the past, thecolumns were additionally concreted and confined in steel elements; those reinforcements did notreach the foundation level. Most of the structural elements bore traces of past repairs made using PCCmaterials. The structure is marked as D.

All the presented facilities are RC monolithic structures operated in industrial conditions, includingexposure to process water. All those structures can also be divided into an underground part and apart above the ground. This division is very important here because it distinguishes between twozones characterized by varying exposure to the external corrosive impact.

4.2. Structural Materials

To determine concrete strength, core samples were tested. That was supplemented with asclerometric test and the correlation coefficient was determined each time. The obtained results arepresented in Table 1, including the class to which the concrete corresponds. The design values obtainedfrom the original design documentation (wherever available) are in the original units.

Table 1. Concrete classes—designed and applied (tested).

Structure Designed ConcreteActual Concrete (Tested)

Foundation Columns Beams Slabs

A Rw = 170 kG/cm2 - C16/20 C16/20 -B1–B3 Rw = 170 kG/cm2 - C12/15 C12/15 -

B4 Rw = 170 kG/cm2 - C12/15 C12/15 -C1–C2 - C20/25 C20/25 C16/20 -

D - - C16/20 C16/20 -

The steel grade was determined based on ribbing (Table 2). St0 was assumed for smooth steel.The access to the individual types of rebars was obtained by performing core drilling or uncovering orby utilizing the areas where the corrosion processes had already uncovered the rebar surface.

Table 2. Designed and applied (tested) reinforcing steel.

StructureDesigned Steel Steel Found in the Uncovered Areas

Foundation Columns Beams Slabs Foundation Columns Beams Slabs

A 18G2/St0 18G2/St0 18G2/St0 St0 - 18G2/St0 18G2/St0 St0B1–B3 St0 St0 St0 St0 St0 34GS/St0 34GS/St0 St0

B4 - - - - - 34GS/St0 34GS/St0 34GSC1–C2 - - - - 34GS/St0 34GS/St0 34GS/St0 St0

D - - - - - St0 St0 St0

4.3. Results of Chemical Tests

Concrete samples were collected for examinations from each of the structures. Some samplescame from core drills, while others were collected independently by hacking off a cover fragment. Theobtained examination results are presented in Table 3. In the case of a greater number of examinations,extreme values are presented. Each of the tests was done using a selected method described inSection 3.2.1.

Appl. Sci. 2020, 10, 358 9 of 16

Table 3. Results of chemical tests.

StructureChloride Ion Content * [%]

Foundation Columns Beams Slabs

A - 3.4 1.1–4.3 3.4B1–B3 0.2–0.7 0.1–0.4 0.1–0.5 0.1–0.4

B4 - 0.3 0.2–0.5 0.2C1–C2 0.1–0.4 0.2–1.2 0.2–2.1 0.6–1.9

D - 2.9 3.3–7.5 6.5

StructureSulfate Ion Content * [%]

Foundation Columns Beams Slabs

A - 3.9 2.9–3.6 0.9B1–B3 3.4–3.9 2.2–3.2 1.7–4.0 1.7–2.2

B4 - 1.9 2.4–3.6 3.3C1–C2 2.2–2.9 3.7–4.9 4.4–8.9 4.0–6.1

D - 4.4 0.1–0.5 1.8

StructurepH

Foundation Columns Beams Slabs

A - 8.8 9.2–9.9 10.1B1–B3 11.4–11.5 10.8–11.4 10.6–11.2 10.8

B4 - 10.4 10.2–11.4 10.9C1–C2 11.2–11.8 10.0–10.8 9.1–10.9 8.8–10.6

D - 8.3 10.1–11.0 10.9

* in relation to binder mass.

4.4. Technical Condition of the Structures—Correlation with Chemical Examination Results

The technical condition of all analyzed structures was defined independently for underground andabove-ground elements. Three situations were identified—only after external inspections—determiningthe intensity of observed damage. The technical condition was found as: satisfactory, bad, and verybad, which is summarized in Table 4.

Table 4. Results of identified technical condition.

Structure Underground Parts Ground Parts

A - very badB1–B3 satisfactory satisfactory

B4 - satisfactoryC1–C2 satisfactory bad/very bad

D - very bad

The total assessment of the technical condition, given in Table 4, was based on a number of factors.In terms of this article, the main determinant of technical condition should be the chemical conditionof concrete associated with the risk of corrosion. However, the general condition of structure was alsoinfluenced by: Area of significant corrosion damage, the actual amount of reinforcement, conditions ofuse (both in the past and during the expected further operation), and the expected period of furtheruse. Therefore, it is difficult to determine the unambiguous quantitative criteria for the classificationof a structure to a given technical condition, because each time it was a combination of the factordescribed. The author’s experience, which is difficult to quantify and based on many years of researchand observations of similar structures played an important role in this identification of the technicalcondition. This, an attempt to quantify the condition of the structure, for example in the form ofintervals of the number of points given in individual aspects and added up for the whole structure, can

Appl. Sci. 2020, 10, 358 10 of 16

be very misleading because determining such a score and adopting appropriate weights will alwaysbe subjective.

During the inspections, corrosion intensity, damage of concrete (including mechanical ones),and different surface deposits were assessed and classified. In particular, the condition of structuresobserved was caused by corrosive damage to concrete (20 - 80% of the surface of structural elements)as well as corrosion of reinforcing steel (from surface concrete to through practically the entire rebar) ofvarying intensity.

In general, a good correlation between the chemical test results and the structure technicalcondition was observed.

The best condition was demonstrated by all the elements from group B both in underground andabove-ground parts. The corrosive damage to rebars was present only in the areas of original defectsof the concrete cover which decreased its thickness (Figure 2a,b). The corrosion was visible mostlyon the surface, with only small, isolated pitting spots. As shown in Table 3, the pH of all elements ofthose structures was at least 10.6 which indicates only a partial loss of the protective ability of concrete.Also, the content of chlorine and sulfate ions exceeded the permissible values only in certain areas.Interestingly, those foundations were made of concrete of the lowest class (C12/15), so it could beexpected that their corrosion would be the highest. One of the reasons for the high ion concentration isthe low density of concrete, which can be identified with its low class. However, the pH value wasrelatively high and pointed to only a small carbonation of the concrete. It is worth noting that thepower boilers supported by group B structures were supplied with imported coal with a very lowcontent of sulfur compounds and hardly any contact with mine water.

Appl. Sci. 2020, 10, x FOR PEER REVIEW 10 of 16

During the inspections, corrosion intensity, damage of concrete (including mechanical ones), and different surface deposits were assessed and classified. In particular, the condition of structures observed was caused by corrosive damage to concrete (20 - 80% of the surface of structural elements) as well as corrosion of reinforcing steel (from surface concrete to through practically the entire rebar) of varying intensity.

In general, a good correlation between the chemical test results and the structure technical condition was observed.

The best condition was demonstrated by all the elements from group B both in underground and above-ground parts. The corrosive damage to rebars was present only in the areas of original defects of the concrete cover which decreased its thickness (Figure 2a,b). The corrosion was visible mostly on the surface, with only small, isolated pitting spots. As shown in Table 3, the pH of all elements of those structures was at least 10.6 which indicates only a partial loss of the protective ability of concrete. Also, the content of chlorine and sulfate ions exceeded the permissible values only in certain areas. Interestingly, those foundations were made of concrete of the lowest class (C12/15), so it could be expected that their corrosion would be the highest. One of the reasons for the high ion concentration is the low density of concrete, which can be identified with its low class. However, the pH value was relatively high and pointed to only a small carbonation of the concrete. It is worth noting that the power boilers supported by group B structures were supplied with imported coal with a very low content of sulfur compounds and hardly any contact with mine water.

(a)

(b)

Figure 2. Examples of corrosive damage: (a,b) corrosion of steel rebars in defected concrete cover.

The test results for elements from structures A, C1, and C2 were much worse. The pH value was as low as 10 or even less (except the foundation in structures C). The chloride ion content was enormous—it exceeded the permissible values several times. The worst situation was in all elements from structure A. The same applies to sulfate ion content. The permissible values in the parts of structures C1 and C2 above the ground were drastically exceeded. The underground parts of structures C1 and C2 were an exception because their pH exceeded 11 and the content of chloride and sulfate ions fell within the permissible range. The above was caused by tight flooring which did not let harmful agents come into contact with the concrete surface. The technical condition of the facilities determined on the basis of a visual assessment of the structures (Table 4) perfectly corresponds to the abovementioned test results—all the elements above the ground showed extensive corrosive damage to concrete and rebars; corrosion reduced the original cross-section of some rebars by as much as 50% or more (Figures 3a,b and 4a,b).

Simultaneously, the concrete in the underground parts of structures C1 and C2 retained its original structure and no reinforcement corrosion was found in the uncovered areas (the technical condition was found as satisfactory). The boilers on foundations A, C1, and C2 were supplied with

Figure 2. Examples of corrosive damage: (a,b) corrosion of steel rebars in defected concrete cover.

The test results for elements from structures A, C1, and C2 were much worse. The pH valuewas as low as 10 or even less (except the foundation in structures C). The chloride ion content wasenormous—it exceeded the permissible values several times. The worst situation was in all elementsfrom structure A. The same applies to sulfate ion content. The permissible values in the parts ofstructures C1 and C2 above the ground were drastically exceeded. The underground parts of structuresC1 and C2 were an exception because their pH exceeded 11 and the content of chloride and sulfateions fell within the permissible range. The above was caused by tight flooring which did not letharmful agents come into contact with the concrete surface. The technical condition of the facilitiesdetermined on the basis of a visual assessment of the structures (Table 4) perfectly corresponds to theabovementioned test results—all the elements above the ground showed extensive corrosive damageto concrete and rebars; corrosion reduced the original cross-section of some rebars by as much as 50%or more (Figure 3a,b and Figure 4a,b).

Appl. Sci. 2020, 10, 358 11 of 16

Appl. Sci. 2020, 10, x FOR PEER REVIEW 11 of 16

Polish coal with a high content of sulfur compounds; in the case of A, the coal was supplied directly from the mine and was damp due to contact with water containing sodium chloride. In both cases, the RC structural elements were also very damp and had contact with solid products of combustion.

(a)

(b)

Figure 3. Examples of steel damage in one of the structure C: (a) corrosion of steel rebars with concrete damage, (b) locally interrupted reinforcement.

(a)

(b)

Figure 4. Examples of corrosive damage in A facility: (a) concrete and steel corrosion, (b) traces of completely corroded stirrups.

The support structure of pipelines (D) showed relatively diversified results, but in all cases, the condition of structural elements was bad or very bad. In terms of pH value, a high threat of corrosion, especially concerning the columns was observed. The sulfate ion content was exceeded only in the columns, but the chloride ion content was drastically exceeded in all structural elements. The above was perfectly visible as enormous damage to concrete, reinforcing steel and additional steel elements (Figure 5a,b).

Figure 3. Examples of steel damage in one of the structure C: (a) corrosion of steel rebars with concretedamage, (b) locally interrupted reinforcement.

Appl. Sci. 2020, 10, x FOR PEER REVIEW 11 of 16

Polish coal with a high content of sulfur compounds; in the case of A, the coal was supplied directly from the mine and was damp due to contact with water containing sodium chloride. In both cases, the RC structural elements were also very damp and had contact with solid products of combustion.

(a)

(b)

Figure 3. Examples of steel damage in one of the structure C: (a) corrosion of steel rebars with concrete damage, (b) locally interrupted reinforcement.

(a)

(b)

Figure 4. Examples of corrosive damage in A facility: (a) concrete and steel corrosion, (b) traces of completely corroded stirrups.

The support structure of pipelines (D) showed relatively diversified results, but in all cases, the condition of structural elements was bad or very bad. In terms of pH value, a high threat of corrosion, especially concerning the columns was observed. The sulfate ion content was exceeded only in the columns, but the chloride ion content was drastically exceeded in all structural elements. The above was perfectly visible as enormous damage to concrete, reinforcing steel and additional steel elements (Figure 5a,b).

Figure 4. Examples of corrosive damage in A facility: (a) concrete and steel corrosion, (b) traces ofcompletely corroded stirrups.

Simultaneously, the concrete in the underground parts of structures C1 and C2 retained its originalstructure and no reinforcement corrosion was found in the uncovered areas (the technical conditionwas found as satisfactory). The boilers on foundations A, C1, and C2 were supplied with Polish coalwith a high content of sulfur compounds; in the case of A, the coal was supplied directly from the mineand was damp due to contact with water containing sodium chloride. In both cases, the RC structuralelements were also very damp and had contact with solid products of combustion.

The support structure of pipelines (D) showed relatively diversified results, but in all cases, thecondition of structural elements was bad or very bad. In terms of pH value, a high threat of corrosion,especially concerning the columns was observed. The sulfate ion content was exceeded only in thecolumns, but the chloride ion content was drastically exceeded in all structural elements. The abovewas perfectly visible as enormous damage to concrete, reinforcing steel and additional steel elements(Figure 5a,b).

Appl. Sci. 2020, 10, 358 12 of 16Appl. Sci. 2020, 10, x FOR PEER REVIEW 12 of 16

(a)

(b)

Figure 5. Damage of varying intensity: (a) damage of concrete and steel corrosion of rebars and profiles, (b) strong corrosion of steel elements used as the strengthening of concrete beams.

In many cases, the concrete burst by swelling corrosion products (Figure 6a). The structure columns were embedded in concrete and confined in an external skeleton made of steel sections approximately 20 years ago. That concrete was strongly damaged (Figure 6b), which proves that the repairs had been conducted in conditions that had not ensured their effectiveness. Similarly, the repairing layers on the beams, made using one of the PCC systems, were destroyed. It must be mentioned that the sodium chloride source was processed water in the open channels under the support structure.

(a)

(b)

Figure 6. The very bad condition of structural elements: (a) swelling steel rebars caused damage of the concrete cover, (b) damaged steel strengthening and concrete of columns.

4.5. Discussion on the Possibility of Repair

The classification of damage (described above) and the decision to undertake repairs is not always strict, because it depends on a number of factors with difficult to determine weights. An external visual inspection of the structure allowing assessment of the level of damage is not a clear premise for making a decision about the ability of the structure to carry out effective and durable repairs. Despite this, in many cases, only on this basis decisions are made about the further fate (in terms of repair or dismantling) of the object.

Figure 5. Damage of varying intensity: (a) damage of concrete and steel corrosion of rebars and profiles,(b) strong corrosion of steel elements used as the strengthening of concrete beams.

In many cases, the concrete burst by swelling corrosion products (Figure 6a). The structurecolumns were embedded in concrete and confined in an external skeleton made of steel sectionsapproximately 20 years ago. That concrete was strongly damaged (Figure 6b), which proves thatthe repairs had been conducted in conditions that had not ensured their effectiveness. Similarly,the repairing layers on the beams, made using one of the PCC systems, were destroyed. It mustbe mentioned that the sodium chloride source was processed water in the open channels under thesupport structure.

Appl. Sci. 2020, 10, x FOR PEER REVIEW 12 of 16

(a)

(b)

Figure 5. Damage of varying intensity: (a) damage of concrete and steel corrosion of rebars and profiles, (b) strong corrosion of steel elements used as the strengthening of concrete beams.

In many cases, the concrete burst by swelling corrosion products (Figure 6a). The structure columns were embedded in concrete and confined in an external skeleton made of steel sections approximately 20 years ago. That concrete was strongly damaged (Figure 6b), which proves that the repairs had been conducted in conditions that had not ensured their effectiveness. Similarly, the repairing layers on the beams, made using one of the PCC systems, were destroyed. It must be mentioned that the sodium chloride source was processed water in the open channels under the support structure.

(a)

(b)

Figure 6. The very bad condition of structural elements: (a) swelling steel rebars caused damage of the concrete cover, (b) damaged steel strengthening and concrete of columns.

4.5. Discussion on the Possibility of Repair

The classification of damage (described above) and the decision to undertake repairs is not always strict, because it depends on a number of factors with difficult to determine weights. An external visual inspection of the structure allowing assessment of the level of damage is not a clear premise for making a decision about the ability of the structure to carry out effective and durable repairs. Despite this, in many cases, only on this basis decisions are made about the further fate (in terms of repair or dismantling) of the object.

Figure 6. The very bad condition of structural elements: (a) swelling steel rebars caused damage of theconcrete cover, (b) damaged steel strengthening and concrete of columns.

4.5. Discussion on the Possibility of Repair

The classification of damage (described above) and the decision to undertake repairs is not alwaysstrict, because it depends on a number of factors with difficult to determine weights. An externalvisual inspection of the structure allowing assessment of the level of damage is not a clear premise formaking a decision about the ability of the structure to carry out effective and durable repairs. Despitethis, in many cases, only on this basis decisions are made about the further fate (in terms of repair ordismantling) of the object.

Appl. Sci. 2020, 10, 358 13 of 16

In the authors’ opinion, the results of chemical tests served as an argument in the discussion aboutthe final and responsible qualification of the structure for repairs or the decision to demolish it. Itcan be assumed, based on the authors’ many years of experience, that the combination of very strongconcrete contamination with harmful ions and a low pH was a clear premise for the demolition of thestructure—especially if the expected lifetime exceeded 10 years.

In the general case, it is also necessary to take into account the possibility of liquidation of a givenstructure due to the continuity of technological processes in the industrial plant—in some specific casessuch processes are continuous and it is impossible to stop them (e.g., operation of a blast furnace in asteel plant). In such cases, renovation may be necessary even if the condition of the structure actuallyprecludes the sense of such activities.

In the presented case studies, the decision on further use of the facilities took into account allfactors, including the results of chemical tests. In each case, the lifetime of the structures was foreseenfor the next 25–30 years. All the structures from group B, despite having a weak concrete (C12/15)showed a low level of chemical contamination and relatively high pH value indicating a small lossof the protective capacity of concrete. This allowed the structure to be qualified for repair, and alsoguaranteed its effective and durable performance. The elements were repaired—since that time, theyhave been operated for nearly 15 years without signs of corrosion. Concerning the structures A andD, which indicated the worst technical condition, the decision ordered the dismantling of the partsabove the floor or ground level (structure D). The chemical contamination of those structures was veryhigh, which did not provide effective repairs, especially that the area where they had to be made wasvery extensive (structure D). The repair of the underground parts has been approved on conditionthat their appropriate condition was proved, including via chemical tests—the latter was not availableat the time of conducting the evaluation. The entire part above the floor level of the structures C1and C2 were also qualified for dismantling. Despite the fact that this structure was made of relativelygood concrete, with a satisfactory pH value (partially carbonized concrete), the intensity of damageobserved as well as very high chemical contamination of concrete disqualified it from continued use.The technical condition of the underground foundation slabs was good, so it was decided to order therepair and reuse of them.

5. Summary

Reinforced concrete industrial structures operated for several decades often show extensivedamage to concrete and reinforcing steel. Such technical condition necessitates overhauls aimed atextending the structure service life. That approach is certainly right if a given RC structure cannotbe put out of operation, including the cases where it is a support structure of a device which cannotbe disassembled. However, the operation time of the device itself is usually limited, so the repairedreinforced concrete structure is also going to be used for a relatively short period.

A different situation concerns a replaced device resting on an RC structure when the latter isanticipated to be used as a support element for a new device. In such a case, the RC support structure inquestion has to work without breakdowns for the next several decades because such is the anticipatedoperation time of most industrial systems. In such a situation, support structure durability becomes thebasic criterion, but it is limited by the condition of that structure stemming from its previous operationperiod. In the case of RC, one of the most important factors is the chemical condition of the concrete,including its pH and contamination with chloride and sulfate ions. Those factors directly translate intothe conditions of anti-corrosive protection of reinforcement and into the threat of concrete and steelcorrosion. Therefore, it is justified to perform tests of concrete in this scope before deciding that anoverhaul is justified.

The presented practical examples show a clear correlation between chemical pollution of concreteand the technical condition of an RC structure (both concrete and rebars). Thus, they confirm the thesisproposed herein that correct identification of selected chemical values in concrete allows one to assessboth the condition of the structure and its behavior after a possible repair. It should not be clearly

Appl. Sci. 2020, 10, 358 14 of 16

equated to a bad condition of an RC structure with the presence of high contamination with harmfulchemical substances. However, it is certain that a high content of harmful ions and a decreased pHresult in a bad technical condition and, in some cases, ineffective repairs.

The paper presents selected examples of industrial support structures, in the case of which theresults of chemical tests of concrete were one of the reasons why it was decided either to performa facility overhaul or demolish that facility and build a new one. Moreover, one of the examplesshows that separating a structure fragment (a bottom slab of the foundation) from the direct actionof corrosive factors results in a much better technical condition and acceptable values of chemicalcontamination. Consequently, the element in question was admitted for an overhaul and preservedas a part of a new support structure. The paper also demonstrates a visible correlation between thetechnical condition of structural elements and the results of the chemical test of concrete.

Author Contributions: Conceptualization of the paper, J.H.; presentation of the problem, J.H.; methodology ofchemical test, M.K.; description and analysis of practical cases, J.H.; writing—original draft preparation, J.H. andM.K.; editing of the paper, M.K.; revision, J.H. and M.K. All authors have read and agreed to the published versionof the manuscript.

Funding: This publication was performed with financial support from “Funds to maintain research potential” atthe Silesian University of Technology.

Conflicts of Interest: The authors declare no conflict of interest.

References

1. Hulimka, J.; Skwarek, M. Failure of supporting structure of conveyor belt as result of impact bytruck. In Awarie Budowlane. Zapobieganie, Diagnostyka, Naprawy, Rekonstrukcje; Wydawnictwo UczelnianeZachodniopomorskiego Uniwersytetu Technicznego: Szczecin, Poland, 2015; pp. 509–516.

2. Barkey, D.P. Corrosion of steel reinforcement in concrete adjacent to surface repairs. ACI Mater. J. 2004, 101,266–272.

3. Al-Kheetan, M.J.; Rahman, M.M.; Chamberlain, D.A. Moisture evaluation of concrete pavement treated withhydrophobic surface impregnants. Int. J. Pavement Eng. 2019, 1–9. [CrossRef]

4. Swamy, R.; Tanikawa, S. An external surface coating to protect concrete and steel from aggressiveenvironments. Mater. Struct. 1993, 26, 465–478. [CrossRef]

5. Elnaggar, E.; Elsokkary, T.; Shohide, M.; Sabbagh, B.; Abdel-Gawwad, H. Surface protection of concrete bynew protective coating. Constr. Build. Mater. 2019, 220, 245–252. [CrossRef]

6. Al-Kheetan, M.J.; Ghaffar, S.H.; Madyan, O.A.; Rahman, M.M. Development of low absorption andhigh-resistant sodium acetate concrete for severe environmental conditions. Constr. Build. Mater. 2020,230, 117057. [CrossRef]

7. Bonic, Z.; Toplicic-Curcic, G.; Davidovic, N.; Savic, J. Damage of Concrete and Reinforcement ofReinforced-Concrete Foundations Caused by Environmental Effects. Procedia Eng. 2015, 117, 411–418.[CrossRef]

8. Sand, W.; Bock, E. Biodeterioration of mineral materials by microorganisms-biogenic sulfuric and nitric acidcorrosion of concrete and natural stone. Geomicrobiol. J. 1991, 9, 129–138. [CrossRef]

9. Wei, S.; Sanchez, M.; Trejo, D.; Gillis, C. Microbial mediated deterioration of reinforced concrete structures.Int. Biodeterior. Biodegrad. 2010, 64, 748–754. [CrossRef]

10. O’Connell, M.; McNally, C.; Richardson, M.G. Biochemical attack on concrete in wastewater applications: Astate of the art review. Cem. Concr. Compos. 2010, 32, 479–485. [CrossRef]

11. Woyciechowski, P. Model of Concrete Carbonation; Series: Scientific Works. Buildings; Warsaw University ofTechnology: Warsaw, Poland, 2013.

12. Kurdowski, W. Cement and Concrete Chemistry; Scientific Publisher PWN: Warsaw, Poland; Association ofCement Producers: Cracow, Poland, 2010.

13. Bellmann, F.; Erfurt, W.; Ludwig, H.-M. Field performance of concrete exposed to sulphate and low pHconditions from natural and industrial sources. Cem. Concr. Compos. 2012, 34, 86–93. [CrossRef]

14. Barberon, F.; Bouny, V.B.; Zanni, H.; Bresson, B.; Caillerie, J.B.; Malosse, L.; Zehong, G. Interactions betweenchloride and cement-paste materials. Magn. Reson. Imaging 2005, 23, 267–272. [CrossRef] [PubMed]

Appl. Sci. 2020, 10, 358 15 of 16

15. Broomfield, J.P. Corrosion of Steel in Concrete: Understanding, Investigation and Repair; CRC Press: Boca Raton,FL, USA, 2006.

16. Smolinski, A. The economy of saline mine waters (in Polish). Min. Environ. 2006, 1, 5–15.17. Turek, M.; Dydo, P.; Surma, A. Zero discharge utilization of saline waters from “Wesola” coal-mine.

Desalination 2005, 185, 275–280. [CrossRef]18. Hulimka, J.; Kałuza, M. A history of failure and repairs of the reinforced concrete raw coal silo. Eng. Fail.

Anal. 2019, 104, 657–672. [CrossRef]19. Glasser, F.P.; Marchand, J.; Samson, E. Durability of concrete-Degradation phenomena involving detrimental

chemical reactions. Cem. Concr. Res. 2008, 38, 226–246. [CrossRef]20. Piasta, W. Analysis of carbonate and sulphate attack on concrete structures. Eng. Fail. Anal. 2017, 79, 606–614.

[CrossRef]21. Zych, T. Durability of contemporary concrete in European Standards. Tech. Trans. Archit. 2011, 108, 317–326.22. Hoła, J.; Bien, J.; Sadowski, Ł.; Schabowicz, K. Non-destructive and semi-destructive diagnostics of concrete

structures in assessment of their durability. Bull. Pol. Acad. Sci. Tech. Sci. 2015, 63, 87–96. [CrossRef]23. Elsener, B.; Andrade, C.; Gulikers, J.; Polder, R.; Raupach, M. Half-cell potential measurements—Potential

mapping on reinforced concrete structures. Mater. Struct. 2003, 36, 461–471. [CrossRef]24. Andrade, C.; Alonso, C. Test methods for on-site corrosion rate measurement of steel reinforcement in

concrete by means of the polarization resistance method. Mater. Struct. 2004, 37, 623–643. [CrossRef]25. Jasniok, M.; Jasniok, T. Measurements on Corrosion Rate of Reinforcing Steel under various Environmental

Conditions, Using an Insulator to Delimit the Polarized Area. Procedia Eng. 2017, 193, 431–438. [CrossRef]26. PN-EN 1504. Part 1÷10. Products and Systems for the Protection and Repair of Concrete Structures; Standard;

Polish Committee for Standardization: Warsaw, Poland, 2006–2017.27. Taha, N.A.; Morsy, M. Study of the behavior of corroded steel bar and convenient method of repairing.

HBRC J. 2016, 12, 107–113. [CrossRef]28. Harvey, D. Analytical Chemistry 2.0—An Open-Access Digital Textbook. Anal. Bioanal. Chem. 2011, 399,

149–152. [CrossRef] [PubMed]29. Park, B. A statistical comparison of the gravimetric, Mohr, and Fajans methods for chloride. J. Cehmical Educ.

1958, 35, 516. [CrossRef]30. PN-EN 14629:2008. Products and Systems for the Protection and Repair of concrete structures. Test Methods-Determination

of Chloride Content in Hardened Concrete; Standard; Polish Committee for Standardization: Warsaw, Poland, 2008.31. Climent, M.A.; de Vera, G.; Viqueira, E.; López-Atalaya, M.M. Generalization of the possibility of eliminating

the filtration step in the determination of acid-soluble chloride content in cement and concrete bypotentiometric titration. Cem. Concr. Res. 2004, 34, 2291–2295. [CrossRef]

32. Castellote, M.; Andrade, C. Round-Robin test on chloride analysis in concrete—Part I: Analysis of totalchloride content. Mater. Struct. 2001, 34, 532–549. [CrossRef]

33. RILEM TC 178-TMC RILEM TC 178-TMC: ’Testing and modelling chloride penetration in concrete’Analysisof total chloride content in concrete. Mater. Struct. 2002, 35, 583–585. [CrossRef]

34. Vennesland, Ø.; Climent, M.A.; Andrade, C.; RILEM Technical Committee 178-TMC (Carmen Andrade).Recommendation of RILEM TC 178-TMC: Testing and modelling chloride penetration in concrete: Methodsfor obtaining dust samples by means of grinding concrete in order to determine the chloride concentrationprofile. Mater. Struct. 2013, 46, 337–344.

35. PN-EN 14630:2007. Products and Systems for the Protection and Repair of Concrete Structures. TestMethods-Determination of Carbonation Depth in Hardened Concrete by the Phenolphthalein Method; Standard;Polish Committee for Standardization: Warsaw, Poland, 2007.

36. PN-EN 206+A1:2016-12. Concrete—Specification, Performance, Production and Conformity; Standard; PolishCommittee for Standardization: Warsaw, Poland, 2016.

37. Ann, K.Y.; Song, H.-W. Chloride threshold level for corrosion of steel in concrete. Corros. Sci. 2007, 49,4113–4133. [CrossRef]

38. Angst, U.; Elsener, B.; Larsen, C.K.; Vennesland, Ø. Critical chloride content in reinforced concrete—A review.Cem. Concr. Res. 2009, 39, 1122–1138. [CrossRef]

39. Shi, X.; Xie, N.; Fortune, K.; Gong, J. Durability of steel reinforced concrete in chloride environments:An overview. Constr. Build. Mater. 2012, 30, 125–138. [CrossRef]

Appl. Sci. 2020, 10, 358 16 of 16

40. Torres-Luque, M.; Bastidas-Arteaga, E.; Schoefs, F.; Sánchez-Silva, M.; Osma, J.F. Non-destructive methodsfor measuring chloride ingress into concrete: State-of-the-art and future challenges. Constr. Build. Mater.2014, 68, 68–81. [CrossRef]

41. PN-EN 197-1:2012. Cement—Part 1. Composition, Specifications and Conformity Criteria for Common Cements;Standard; Polish Committee for Standardization: Warsaw, Poland, 2012.

42. Papadakis, V.G.; Fardis, M.N.; Vayenas, C.G. Effect of composition, environmental factors and cement-limemortar coating on concrete carbonation. Mater. Struct. 1992, 25, 293–304. [CrossRef]

© 2020 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open accessarticle distributed under the terms and conditions of the Creative Commons Attribution(CC BY) license (http://creativecommons.org/licenses/by/4.0/).