architects 24 Ryerson Avenue, Suite 206 Toronto, Ontario M5T 2P3 www.garchitects.ca | 647.727.8860 Project Address Project Number Owner Issue Issue Date Project Plot Date 20170503 ISSUED FOR TENDER Baycrest Geriatric Care Dentistry Alterations 3560 Bathurst St. Toronto, ON M6A 2E1 16084 Baycrest Hospital 20170503
Transcript
  • architects24 Ryerson Avenue, Suite 206Toronto, Ontario M5T 2P3 www.garchitects.ca | 647.727.8860

    Project Address

    Project Number

    Owner

    Issue

    Issue Date

    Project

    Plot Date

    20170503

    ISSUED FOR TENDER

    Baycrest Geriatric Care Dentistry Alterations

    3560 Bathurst St. Toronto, ON M6A 2E1

    16084

    Baycrest Hospital

    20170503

  • TEAM DIRECTORY

    OWNER

    ARCHITECT

    MECHANICAL & ELECTRICAL ENGINEER

    Baycrest Health Sciences3560 Bathurst St. Toronto, ON, M6A 2E1

    G architects24 Ryerson Ave. Suite 206, Toronto, ON, M5T 2P3

    H. H. Angus & Associates Ltd.1127 Leslie St. Toronto, ON, M3C 2J6

    GENERAL NOTES:

    1. Drawings are not to be scaled. Contractor will verify all existing conditions and dimensions required to perform the Work and willreport any discrepancies with the Contract Documents to the Architect before commencing work.

    2. The Architectural Drawings are to be read in conjunction with all other Contract Documents including the Project Manuals and theStructural, Mechanical and Electrical Drawings. In cases of difference between the Consultants' documents with respect to thequantity, sizes or scope of work, the greater shall apply.

    3. Positions of exposed or finished Mechanical or Electrical devices, fittings and fixtures are indicated on the Architectural Drawings.Locations shown on the Architectural Drawings shall govern over Mechanical and Electrical Drawings. Mechanical and Electricalitems not clearly located will be located as directed by the Architect.

    4. Site verify all dimensions, conditions, and levels on site prior to fabrications é installations.

    5. All discrepancies between conditions shown and site conditions are to be reported to the architect.

    6. The architect has not been retained for supervision of construction and assumes no responsibility for means, methods and techniques ofconstruction.

    7. These documents are not to be used for construction unless specifically noted for such purpose.

    BAYCREST A

    VE.

    KHED

    IVE AVE.

    BA

    THU

    RS

    T ST.

    WASDALE C

    RESCENT

    BROOKE AV

    E.

    OLD ORC

    HARD

    GROVE

    NOT IN SCOPE

    CONSULTANT DRAWING LIST

    MECHANICAL

    M001 MECHANICAL LEGEND & DRAWING LIST

    M101 BASEMENT PART FLOOR PLAN WEST - PLUMBING DEMOLITION

    M102 GROUND FLOOR PART FLOOR PLAN WEST - PLUMBING DEMOLITION

    M103 GROUND FLOOR PART FLOOR PLAN WEST - PLUMBING NEW

    M104 GROUND FLOOR PART FLOOR PLAN EAST - PLUMBING NEW

    M105 BASEMENT PART FLOOR PLAN WEST - PLUMBING NEW

    M106 BASEMENT PART FLOOR PLAN EAST - PLUMBING NEW

    M107 SECOND FLOOR ROOF PART PLAN - PLUMBING NEW

    M201 GROUND FLOOR PART FLOOR PLAN WEST - HEATING DEMOLITION

    M202 GROUND FLOOR PART FLOOR PLAN WEST - HEATING NEW

    M301 GROUND FLOOR PART FLOOR PLAN WEST - VENTILATION DEMOLITION

    M302 GROUND FLOOR PART FLOOR PLAN WEST - VENTILATION NEW

    M303 NOT IN USE

    M304 NOT IN USE

    M305 SECOND FLOOR ROOF PART PLAN - VENTILATION NEW

    M401 GROUND FLOOR PART FLOOR PLAN EAST - FIRE PROTECTION DEMOLITION

    M402 GROUND FLOOR PART FLOOR PLAN EAST - FIRE PROTECTION NEW

    M403 NOT IN USE

    M501 GROUND FLOOR PART FLOOR PLAN WEST - MEDICAL GASES DEMOLITION

    M502 GROUND FLOOR PART FLOOR PLAN WEST - MEDICAL GASES NEW

    M503 GROUND FLOOR PART FLOOR PLAN EAST - MEDICAL GASES NEW

    M504 BASEMENT PART FLOOR PLAN EAST - MEDICAL GASES NEW

    M601 MECHANICAL DETAILS SHEET #1

    M602 MECHANICAL DETAILS SHEET #2

    M603 MECHANICAL DETAILS SHEET #3

    M701 MECHANICAL SCHEDULES

    ELECTRICAL

    E-000

    E-100

    E-101

    E-300

    E-301

    E-302

    E-303

    E-400

    LEGEND AND DRAWING LIST

    DEMOLITION LIGHTING

    DEMOLITION POWER & SYSTEMS

    NEW LIGHTING

    NEW POWER

    NEW SYSTEMS

    NEW BASEMENT POWER, LIGHTING AND SYSTEMS

    DETAILS

    All drawing andspecifications are theproperty of the architect.The contractor shall verifyall dimensions andinformation on site andreport any discrepancy toarchitect before proceeding.

    24 Ryerson Avenue, Suite 206. Toronto, ON M5T 2P3www.garchitects.ca | 647.727.8860 | [email protected]

    scale:

    drawn by:

    reviewed by:

    job number:

    plot date:

    drawing number:

    architects

    As indicated

    PROJECT INFORMATION

    16084

    Baycrest Geriatric Care Dentistry Alterations

    CL, DS

    MG

    20170503

    A0.01

    3560 Bathurst St. Toronto, ON M6A 2E1

    DRAWING LIST

    Sheet No. Drawing Name

    A0.01 SERIES - PROJECT INFORMATION

    A0.01 PROJECT INFORMATION

    A0.02 SERIES - ARCHITECTURAL INFO

    A0.02 ARCHITECTURAL INFO

    A0.05 SERIES - CODE INFORMATION

    A0.05 CODE INFORMATION

    A1.20 SERIES - DEMOLITION

    A1.21 LEVEL 1 - DEMOLITION PLAN

    A1.31 LEVEL 1 - DEMOLITION RCP

    A2.00 SERIES - ROUTING DIAGRAMS

    A2.00 ROUTING DIAGRAM - BASEMENT & LEVEL 1

    A2.10 SERIES - FRAMING FLOOR PLANS

    A2.10 BASEMENT - FLOOR PLAN

    A2.11 LEVEL 1 - FLOOR PLAN

    A3.00 SERIES - FRAMING REFLECTED CEILING PLANS

    A3.01 LEVEL 1 - REFLECTED CEILING PLAN

    A9.00 SERIES - DOORS & SCREENS

    A9.00 DOOR SCHEDULE, SCREEN TYPES, MILLWORK

    1 : 1000

    CONTEXT PLAN

    1 : 3251

    LEVEL 1 - KEY PLAN

    1 : 3252

    BASEMENT - KEY PLAN

    # date: revision: by:

    1 20161130 ISSUED FOR PERMIT G

    2 20170503 ISSUED FOR TENDER G

  • TYPICAL MOUNTING HEIGHTS

    SWITCH NURSE CALL

    RECEPTACLES

    THERMOSTAT

    TH

    SW NC

    DU

    1500

    1100

    1150

    350

    SYMBOL

    FIRERESISTANCE

    RATINGCONSTRUCTION DESCRIPTION

    60 MIN ULCU419

    STCRATING

    NOTES

    INTERIOR PARTITION ASSEMBLIES

    STUD SIZE

    FIRE RESISTANCE RATING

    P1xA

    A92

    60

    PARTITION ASSEMBLY TAG

    HEAD CONDITION

    ACOUSTIC ASSEMBLY

    STUD SIZE REFER TO ASSEMBLY LEGEND

    HEAD CONDITION 'A' EXTEND PARTITION TO U/S OFSTRUCTURE ABOVE

    'B' EXTEND PARTITION TO U/S OFCEILING ABOVE

    'C' EXTEND PARTITION TO XXmm

    ACOUSTIC ASSEMBLY 'A' DENOTES ACOUSTICASSEMBLY REFER TOASSEMBLY LEGEND

    FIRE RESISTANCE RATING REFER TO ASSEMBLY LEGEND

    P2-

    A 60

    92

    P3-

    A -

    92

    124

    125

    16MM GWB TYPE 'X'92MM METAL STUD FRAMING

    ACOUSTIC BATT INSULATION INFILL16MM GWB TYPE 'X'

    16MM GWB.8MM MEDICAL GRADE LEAD (500MM AFF TO

    2000MM AFF MIN)92MM METAL STUD FRAMING

    ACOUSTIC BATT INSULATION INFILL16MM GWB

    -

    -

    SMOKE SEAL AT ALL JOINTS

    F3-

    - -

    64 - -

    16MM GWB64MM METAL STUDS

    F4-

    - -

    - - -

    16MM GWB LAMINATED TO EXGSTRUCTURE

    16

    F2-

    - -

    152- -

    16MM GWB152MM METAL STUDS

    80

    P5-

    A -

    92

    16MM FULL HEIGHT LEAD LINED GWB W/50MM WIDE LEAD STRIPS AT SEAMSAND 3/8" LEAD DISCS OVER FASTENERS

    92MM METAL STUD FRAMINGACOUSTIC BATT INSULATION INFILL

    16MM GWB

    -

    P4-

    A -

    152

    185

    16MM GWB.8MM MEDICAL GRADE LEAD (500MM AFF TO

    2000MM AFF MIN)152MM METAL STUD FRAMING

    ACOUSTIC BATT INSULATION INFILL16MM GWB

    -

    P6-

    A -

    152

    16MM FULL HEIGHT LEAD LINED GWB W/50MM WIDE LEAD STRIPS AT SEAMSAND 3/8" LEAD DISCS OVER FASTENERS

    152MM METAL STUD FRAMINGACOUSTIC BATT INSULATION INFILL

    16MM GWB

    -

    F1-

    A -

    152

    16MM GWB.8MM MEDICAL GRADE LEAD (500MM AFF TO

    2000MM AFF MIN)152MM METAL STUD FRAMING

    ACOUSTIC BATT INSULATION INFILL

    -

    P7-

    A -

    92

    124

    16MM GWB92MM METAL STUD FRAMING

    ACOUSTIC BATT INSULATION INFILL16MM GWB

    -

    171

    LEADED ASSEMBLY

    LEADED ASSEMBLY

    LEADED ASSEMBLY

    LEADED ASSEMBLY

    LEADED ASSEMBLY

    F5-

    - -

    64- -

    16MM GWB.8MM MEDICAL GRADE LEAD (500MM AFF TO

    2000MM AFF MIN)64MM METAL STUDS

    81

    F6-

    - -

    64 - -

    16MM FULL HEIGHT LEAD LINED GWB W/50MM WIDE LEAD STRIPS AT SEAMSAND 3/8" LEAD DISCS OVER FASTENERS

    64MM METAL STUDS

    83

    H1-

    - -

    64- -

    16MM GYPSUM6mil POLYETHYLENE SHEETING FOR

    DUST CONTROL64MM METAL STUDS

    80

    TEMPORARY HOARDING ASSEMBLY

    SYMBOL

    FIRERESISTANCE

    RATINGCONSTRUCTION DESCRIPTION

    STCRATING

    NOTES

    CLGS

    2700

    GWB

    METAL FRAMING SUSPENDEDFROM STRUCTURE ABOVE

    22mm METAL HAT CHANNEL16mm GWB

    METAL FRAMING SUSPENDEDFROM STRUCTURE ABOVE

    16mm ACOUSTIC CEILING TILECLGS

    2700

    ACT

    186

    126

    -

    -

    -

    -

    -

    -

    LEADED ASSEMBLY

    LEADED ASSEMBLY

    168

    F7-

    - -

    64 - -

    16MM GWB22MM RESILIENT CHANNELS64MM METAL STUDS

    ACOUSTIC BATT INSULATION INFILL

    102

    EXTERIOR ELEVATION TAG

    INTERIOR ELEVATION TAG

    BUILDING SECTION TAG

    WALL SECTION TAG

    DETAIL SECTION TAG

    CALLOUT TAG

    ROOM TAG

    CEILING TAG

    INTERIOR WALL TAG

    INTERIOR DOOR TAG

    A101

    1 Ref

    1

    Ref

    1

    Ref

    1 Ref

    A101

    1 Ref

    1

    Ref

    1

    Ref

    1 Ref

    01

    A101

    REF

    1

    A101

    Ref

    ANNOTATION SYMBOLS

    ROOM NAME101150 m³

    Ref1

    A101

    Ref1

    A101

    P1xA

    A92

    60

    D001A 90

    CLG3500

    ACT S

    CEILING TYPE

    HEIGHT ABOVE FINISHED FLOOR

    CEILING ASSEMBLY

    HEAD CONDITION

    FIRE RESISTANCE RATING

    STUD SIZE

    ACOUSTIC ASSEMBLY

    WALL ASSEMLY TAG

    FIRE RESISTANCE RATING

    UNIQUE DOOR NUMBER

    DIMENSIONS ARE F.O. GWB SUBSTRATE OR STRUCTUREUNLESS OTHERWISE NOTED

    CRITICAL CLEAR DIMENSIONS ARE NOTED AS "CLEAR"

    DIMENSION DIMENSION

    1

    DIMENSIONING NOTES

    *ALERT CONSULTANT OF ANY DESCREPANCY IN DIMENSIONS.DO NOT SCALE DRAWINGS.

    CLEAR

    DIMENSION

    ACACTADDADHAFFALUMANODAPAPPROXARCHASPHAUTOAVB

    BOBOSBSBHBHDBLDGBLKBOTBPLBR

    CLCIPCBCGCJCLNGCLRCMUCOCO-ORDCOLCONCCONSTCONTCONTRCORRCPTCRSCTCW

    DAMPGDCDETLDIADIMDIVDLDEMODPDWDWG(S)

    EOSEAELEELECELEVEPXEQEXISTEXPEXTREXTEWS

    FOFAFCPFDNFEFFEFHCFINFL DRFLRFPFRFRRFTFTG

    GAGALVGBGBLKGLGRGRNDGSGYPGWB

    HBHDHDWRHMHORHPHSSHVAC

    IDINDNINSULINSUL GLINTINVT

    JANJT

    KP

    LAMLAMGLLBRLHLLLONG

    ALTERNATING CURRENTACCOUTIC TILEADDENDUMADHESIVEABOVE FINISHED FLOORALUMINIUMANODIZEDACCESS PANELAPPROXIMATEARCHITECTURALASPHALTAUTOMATICAIR/VAPOUR BARRIER

    BOTTOM OFBOTTOM OF SLABBOTH SIDESBOREHOLEBULKHEADBUILDINGBLOCKBOTTOMBASE PLATEBRICK

    CENTRE LINECAST IN PLACECATCH BASINCORNER GUARDCONTROL JOINTCEILINGCOLOURCONCRETE BLOCKCLEAN OUTCO-ORDINATECOLUMNCONCRETECONSTRUCTIONCONTINUOUSCONTRACTORCORRIDORCARPETCOURSESCERAMIC TILECURTAIN WALL

    DAMP-PROOFINGDIRECT CURRENTDETAILDIAMETERDIMENSIONDIVISIONDEAD LOADDEMOLITIONDUPLEX RECEPTACLEDISHWASHERDRAWING(S)

    EDGE OF SLABEACHELEVATORELECTRICALELEVATIONEPOXYEQUALEXISTINGEXPOSEDEXTRUDEDEXTERIOREYEWASH STATION

    FACE OFFIRE ALARMFIRE CONTROL PANEL / ANNUNCIATORFOUNDATIONFIRE EXTINGUISHERFINISH FLOOR ELEVATIONFIRE HOSE CABINETFINISHFLOOR DRAINFLOORFIRE PULLREFRIDGERATORFIRE RESISTANCE RATINGFEETFOOTING

    GAUGEGALVANIZEDGRAB BARGLAZED BLOCKGLASSGRILLEGROUNDGALVANIZED STEELGYPSUMGYPSUM WALLBOARD

    HOSE BIBHAND DRYERHARDWAREHOLLOW METALHORIZONTALHIGH POINTHOLLOW STRUCTURAL SECTIONHEATING VENTILATING AND AIR CONDITIONING

    INSIDE DIAMETERINDUCTIONINSULATIONINSULATING GLASSINTERIORINVERT

    JANITORJOINT

    KICK PLATE

    LAMINATELAMINATED GLASSLUMBERLEFT HANDLIVE LOADLONGITUDINAL

    MATMAXMDFMECHMTLMFRMHMINMISCMMBMOMRMSNRYMTDMWMWP

    NGASNICNONOMNSNTS

    OCODOHOHDOPNGOPP

    PLPLAMPLGLPLTPLYPOLPORPPTPRECASTPREFABPROJPSFPSIPTPTDPTNPVC

    RORARADRBRCPRDRECREFREINFRENOREQREVRGRHRIRMRWL

    SOGSSSSTLSAMSCHEDSCONCSNDISPOSESNDISPENSESECTSFLSGLSHTHGSHGLSHTSIMSLSLNTSMFSPECSPNSTNSTDSTLSTNSTRSTRUCTSUSPSUSPD

    TOTOSTBTEMPTEMPGLTHKTMBRTPDTRTOPTYP

    USUNOUNFIN

    VBVFLVERTVOL

    WOW/WSWBWDWDFWGLWMWPFWWT

    MATERIALMAXIMUMMEDIUM DENSITY FIBREBOARDMECHANICALMETALMANURACTURERMANHOLEMINIMUMMISCELLANEOUSMEMBRANEMASONRY OPENINGMIRRORMASONRYMOUNTEDMICROWAVEMEMBRANE WATERPROOFING

    NEOPRENE GASKETNOT IN CONTRACTNUMBERNOMINALNON-SLIPNOT TO SCALE

    ON CENTREOUTSIDE DIAMETEROVERHEADOVERHEAD DOOROPENINGOPPOSITE

    PLASTERPLASTIC LAMINATEPLATE GLASSPLATEPLYWOODPOLISHEDPORCELAIN TILEPRIME PAINTEDPRECAST CONCRETEPREFABRICATEDPROJECTIONPOUNDS PER SQUARE FOOTPOUNDS PER SQUARE INCHPAINTPAPER TOWEL DISPENSERPARTITIONPOLYVINYL CHLORIDE

    ROUGH OPENINGROOF ANCHORRADIATORRUBBER BASEREFLECTED CEILING PLANROOF DRAINRECESSEDREFERENCEREINFORCEDRENOVATIONREQUIREDREVISIONRANGERIGHT HANDRIGID INSULATIONROOMRAIN WATER LEADER/ DOWNSPOUT

    SLAB ON GRADESOLID SURFACESTAINLESS STEELSELF ADHERED MEMBRANESCHEDULESEALED CONCRETESANITARY NAPKIN DISPOSALSANITARY NAPKIN DISPENSERSECTIONSEAMLESS FLOORINGSAFETY GLASSSHEATHINGSHEET GLASSSHEETSIMILARSLABSEALANTSPRAYED MINERAL FIREPROOFINGSPECIFICATIONSPANDRELSTONESTEEL DECKSTEELSTAINSTAIRSTRUCTURALSUSPENDSUSPENDED

    TOP OFTOP OF SLABTIMBERTEMPERATURETEMPERED GLASSTHICKTHERMAL BARRIERTOILET PAPER DISPENSERTRIMTOPPINGTYPICAL

    UNDERSIDEUNLESS NOTED OTHERWISEUNFINISHED

    VAPOUR BARRIERVINYL FLOORINGVERTICALVOLUME

    WHERE OCCURSWITHWEATHER-STRIPPINGWINDOW BLINDWOODWOOD FLOORWIRED GLASSWIRE MESHWATERPROOF / WATERPROOFINGWINDOW WASHING TRACK

    ABBREVIATIONS

    FLOOR FINISH SCHEDULE

    SYMBOL DESCRIPTION MANUFACTURER MODEL COLOUR/ FINISH

    VINYL PLANKFLOOR

    ARMSTRONG D2418 GOLDEN GROVEF1

    VINYL SHEETFLOOR

    POLYFLOR 9855 WARM CONCRETEF2

    BASE FINISH SCHEDULE

    SYMBOL DESCRIPTION MANUFACTURER MODEL COLOUR/ FINISH

    INTEGRAL COVE - - -B2

    RUBBER BASEB1 JOHNSONITE 50 WHITE

    WALL FINISH SCHEDULE

    SYMBOL DESCRIPTION MANUFACTURER MODEL COLOUR/ FINISH

    PAINT BENJAMIN MOORE CLOUD WHITEPT-1

    PT-2

    CC40

    PT-3

    PAINT

    PAINT

    SHERWIN WILLIAMS HIGH STRUNGSW 6705

    SHERWIN WILLIAMS BLUE MOSQUESW 6789

    AFF115

    WALL FINISH(TO EXTEND 50MMBELOW RUBBER BASE)

    STAINLESS STEELCOVE CAP

    VINYL SHEET BASE

    32MM RADIUS COVE W/CONTINUOUS FILLERSTRIP

    VINYL SHEETFLOOR FINISH

    50

    TYPICAL BARRIER-FREE DOOR

    600 MIN

    300 MIN

    1500X1500 CLEAR

    1200X1200 CLEAR

    PULL SIDE

    PUSH SIDE

    100

    WALL FINISH(TO EXTEND 50MMBELOW RUBBER BASE)

    RUBBER BASE

    FLOOR FINISH

    AFF115

    50

    TRANSITION STRIP - VINYLFLOOR REDUCER

    NEW VINYL PLANK FLOOR (F1)NEW VINYL SHEET FLOOR (F2)

    EXISTING FINISHED FLOOR

    FINISHED FLOOR

    EXISTING FLOOR

    VINYL TRANSITION STRIP

    NEW VINYL SHEET FLOOR

    NEW VINYL PLANK FLOOR

    FINISHED FLOOR

    EXISTING FLOOR

    ROOM FINISH SCHEDULE

    ROOM NO. ROOM NAME FLOORFINISH

    BASE

    1C01A

    1C01B

    1C02A

    1C02B

    OPERATORY

    OFFICE

    WORKSPACE

    PAN

    OPERATORY

    RECOVERY

    CLEAN

    SOILED

    OPERATORY

    WALL FINISH

    1C02C

    1C02D

    1C02E

    1C02F

    1C02G

    CORRIDOR1C02

    B2 * PT

    B2

    B2

    B2

    B2

    B2

    B1

    B2

    B2

    B1

    F1

    F1

    F2

    F2

    F2

    F2

    F2

    F2

    F2

    F2

    * PT

    * PT

    * PT

    * PT

    * PT

    * PT

    * PT

    * PT

    * PT

    * WITH P2/P3 ACCENT WALL. TBD BY OWNER

    BA03 MECH EXISTING EXISTINGEXISTING

    CLG FINISH

    PT-1

    PT-1

    PT-1

    PT-1

    PT-1

    PT-1

    PT-1

    PT-1

    PT-1

    PT-1

    1C03A

    1C04

    OPITHAL

    PODIATRY F2

    F2 B2

    B2

    * PT

    * PT

    PT-1

    PT-1

    REFLECTED CEILING PLAN LEGEND

    CEILING TYPE

    CEILING ASSEMBLY

    HEIGHT ABOVE FINISHED FLOOR

    CLG3500

    ACT S

    All drawing andspecifications are theproperty of the architect.The contractor shall verifyall dimensions andinformation on site andreport any discrepancy toarchitect before proceeding.

    24 Ryerson Avenue, Suite 206. Toronto, ON M5T 2P3www.garchitects.ca | 647.727.8860 | [email protected]

    scale:

    drawn by:

    reviewed by:

    job number:

    plot date:

    drawing number:

    architects

    As indicated

    ARCHITECTURAL INFO

    16084

    Baycrest Geriatric Care Dentistry Alterations

    CL, DS

    MG

    20170503

    A0.02

    3560 Bathurst St. Toronto, ON M6A 2E1

    1 : 22

    B2 COVE WALL BASE TYPE

    1 : 21

    B1 RUBBER BASE

    1 : 23

    TR1 VINYL PLANK FLOOR & TR-2 VINYL SHEET FLOOR

    1 : 24

    TR2 VINYL SHEET TO VINYL PLANK FLOOR

    NOTE: PT-2 & PT-3 CLIENT TO SELECT ACCENT WALL LOCATIONS

    PARTITION TYPES

    CEILING ASSEMBLIES

    # date: revision: by:

    1 20161130 ISSUED FOR PERMIT G

    2 20170503 ISSUED FOR TENDER G

  • 1045

    0MM

    TRA

    VEL D

    ISTA

    NCE

    1 HR

    1 HR

    1 HR

    1 HR

    1245

    0MM

    TRA

    VEL

    DIS

    TANC

    E

    1700

    0MM

    TR

    AV

    EL

    DIS

    TAN

    CE

    EXIT

    EX

    IT

    EXIT

    EX

    IT

    1 HR

    1 HR

    1 HR

    1 HR

    OPERATORY

    1C02C

    OPERATORY

    1C02D

    PAN

    1C02G

    WORK AREA

    1C02F

    OPERATORY

    1C02B

    FUTURE OPERATORY

    1C02A

    OFFICE

    1C02E

    CLEAN

    1C01B

    SOILED

    1C01A

    CORRIDOR1C02

    CORRIDOR

    1C52

    OBC MATRIX LEGEND

    XXXXMM TRAVEL DISTANCE

    1100

    BARRIER FREE PATH OF TRAVEL

    EXIT EXIT SIGN

    1HR FRR

    2HR FRR

    2 HR 2 HR

    2 HR

    PUMP ROOM

    BA03A

    CORRDIOR

    All drawing andspecifications are theproperty of the architect.The contractor shall verifyall dimensions andinformation on site andreport any discrepancy toarchitect before proceeding.

    24 Ryerson Avenue, Suite 206. Toronto, ON M5T 2P3www.garchitects.ca | 647.727.8860 | [email protected]

    scale:

    drawn by:

    reviewed by:

    job number:

    plot date:

    drawing number:

    architects

    1 : 50

    CODE INFORMATION

    16084

    Baycrest Geriatric Care Dentistry Alterations

    CL

    MG

    20170503

    A0.05

    3560 Bathurst St. Toronto, ON M6A 2E1

    1 : 502

    LEVEL 1 - CODE INFORMATION 1 : 50

    1BASEMENT - CODE INFORMATION

    # date: revision: by:

    1 20161130 ISSUED FOR PERMIT G

    2 20170503 ISSUED FOR TENDER G

  • HEAD NURSE1C05

    PHYSICIAN1D11B

    OPER. OFFICE1C02D

    LAB WORKROOM

    10020

    DENTAL OFFICE

    1C02B

    OFFICE1C02A

    OPERATORIES1C02

    ENT

    1C01

    ELEC

    1B18

    C DE F

    1

    2

    3

    XRAY

    1C02C

    PODIATRY

    1C04

    OPITHAL1C03A

    3690 1525 2545 3520

    15155

    8665

    1805

    670

    1760

    2525

    2525

    2465

    2295 2360 4010

    1174

    0

    3465

    2830

    1850

    855

    2745

    1905

    1174

    0

    1

    1

    1

    1

    1

    1

    1

    1 1

    1

    1

    11

    1

    1

    1

    1

    1

    1

    2

    2

    2

    2

    2

    2

    3

    3

    3

    3

    3

    3 4

    43

    3

    4

    4

    4

    4

    5

    6

    6

    6

    6

    6

    6 6

    7 7

    8

    8

    9

    B

    WAITING ROOM CLINICS

    1C44

    2

    5

    10

    A

    SPECIMENT COLLECTION

    1C3

    11

    51 m² (548 ft²)

    CORRIDOR

    1C52

    964

    DEMO

    DE

    MO

    EX

    G

    EXG

    2100

    2100

    H1-

    A64

    -

    H1-

    A64

    -

    H1-

    A64

    -

    12

    12

    13

    13

    EXG DEMO

    EXG DEMO

    DEMO

    EXG

    DEMO

    EXG

    EXG

    EXG

    980

    380

    1

    EXISTING TO REMAIN

    TO BE DEMOLISHED

    NOT IN SCOPE

    PROPOSED PARTITION

    PHASING LEGEND

    HOARDING

    AREA OF WORK

    KEY PLAN

    LEVEL 1

    All drawing andspecifications are theproperty of the architect.The contractor shall verifyall dimensions andinformation on site andreport any discrepancy toarchitect before proceeding.

    24 Ryerson Avenue, Suite 206. Toronto, ON M5T 2P3www.garchitects.ca | 647.727.8860 | [email protected]

    scale:

    drawn by:

    reviewed by:

    job number:

    plot date:

    drawing number:

    architects

    1 : 50

    LEVEL 1 - DEMOLITION PLAN

    16084

    Baycrest Geriatric Care Dentistry Alterations

    DS, CL

    MG

    20170503

    A1.21

    3560 Bathurst St. Toronto, ON M6A 2E1

    KEYNOTES - DEMOLITION

    Key Value Keynote Text

    1 EXISTING PARTITIONS TO BE DEMOLISHED.

    2 EXISTING DOORS AND FRAMES TO BE DEMOLISHED.

    3 EXISTING MILLWORK TO BE DEMOLISHED. ANY EXISTING ELEMENTS TO REMAIN AFFECTED BYWORK TO BE PATCHED AND MADE GOOD OVERLAY.

    4 EXISTING PLUMB FIXTURES TO BE DEMOLISHED. EXISTING MECH/ELEC SERVICES TO BE CAPPED.

    5 PROVIDE NEW OPENING IN EXISTING PARTITION. PREPARE TO RECEIVE NEW DOOR AND FRAME.

    6 EXISTING FLOOR FINISH TO BE DEMOLISHED AND PREPPED FOR NEW FLOOR FINISH.

    7 EXISTING CARPET (INCLUDING WALL BASE) & UNDERLAYMENT TO BE DEMOLISHED. SUBFLOOR TOBE PREPPED FOR NEW FLOOR FINISH.

    8 EXISTING TILE (INCLUDING WALL BASE) & UNDERLAYMENT TO BE DEMOLISHED. SUBFLOOR TO BEPREPPED FOR NEW FLOOR FINISH.

    9 EXISTING DOOR & FRAME TO BE DEMOLISHED. OPENING TO BE INCREASED IN SIZE TO RECEIVENEW DOOR.

    10 PROVIDE EQUIPMENT NEW OPENING (2235H X 775W) IN EXISTING PARTITION. COORDINATE WITHPASS THROUGH WASHER REQUIREMENTS.

    11 REFER TO MECH / ELEC DOCUMENTS.

    12 PREP SLAB FOR INFLOOR POWER. REFER TO ELEC.

    13 EXISTING MILLWORK TO BE DEMOLISHED.

    DEMOLITION NOTES:

    1. ALL DEMOLITION WORK TO BE COORDINATED WITH HAZARDOUS MATERIALS ASSESSMENT REPORT FUNISHED BY OWNER PRIOR TO COMMENCEMENT OF DEMOLITIONACTIVITIES.

    2. ALL DEMOLITION WORK TO BE COORDINATED WITH THE DEMOLITION WORK OF ALL OTHER DISCIPLINES FORMING PART OF THE CONTRACT DOCUMENTS PRIOR TOCOMMENCEMENT OF DEMOLITION ACTIVITIES.

    3. INTERIOR PARTITIONS TO BE DEMOLISHED ARE ASSUMED TO BE GWB ON METAL STUD FRAMING WITH FIBERGLASS BATT INSULATION TO UNDERSTIDE OF STRUCTURE ABOVEUNLESS OTHERWISE NOTED. NOTIFY CONSULTANT OF ALL FOUND CONDITIONS WHICH DIFFER FROM THIS ASSUMPTIONS BEFORE PROCEEDING WITH DEMOLITION.

    4. WHERE DEMO PARTITION INTERSECTS WITH EXG PARTITION TO REMAIN: DEMOLISH EXG INTERIOR PARTITION AND WALL BASE REPAIR / PATCH / SKIM EXG GWB WALL TOREMAIN TO ACCEPT NEW WALL AND BASE FINISH MATERIALS.

    5. MAINTAIN INTEGRITY OF ALL EXISTING FRR ASSEMBLIES NOTED TO REMAIN. NOTIFY CONSULTANT IF DAMAGE OCCURS. REPAIR DAMAGE TO FRR ASSEMBLIES AS DIRECTEDBY CONSULTANT. REFER TO DWG A0.05 FOR LOCATION OF FRR ASSEMBLIES.

    # date: revision: by:

    1 20161130 ISSUED FOR PERMIT G

    2 20170503 ISSUED FOR TENDER G

  • C DE

    F

    1

    2

    3

    L1

    L1

    L1

    L1

    L1

    L1

    L1

    L1

    L1L1

    L1 L1L1L1

    L1L1

    L1L1

    L1

    L1

    L1

    L1

    L1

    L1

    L1

    L1

    L1 L1

    SA2

    SP1

    ES1 SD1

    SA2

    SA1

    SA1

    RA2

    ES1

    SP1

    ES1

    SP1

    RA1

    ES1

    ES1

    SA2

    SP1

    ES1

    SP1

    SA2 ES1

    SP1

    ES1

    SA2

    RA2

    RA1

    ES1

    SA2 RA2 SA2

    RA2

    ES1

    SA2

    RA2

    SP1

    SP1

    ES1

    SP1SA2

    ES1

    ES1

    SA2

    SA2

    SP1SP1

    SA2SA2

    RA2RA2L1

    B

    SA2

    ES1

    L1

    G2

    ES1

    L1

    SP1

    L1

    ES1

    G2

    1 1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    2

    2

    2 2

    22

    3

    3

    2

    2

    2

    2

    3

    2 2

    3

    2

    2

    3 2

    2

    2

    3

    4

    4

    4

    4

    4

    4

    4

    44

    4

    4

    4

    4 4 4

    4

    42 23 4

    22

    4

    22

    2

    2

    3

    3

    3

    4

    22

    35

    3

    4 42 2 2

    4 4

    3

    4

    A

    6

    6

    6

    6

    6

    6

    6

    66

    6

    6

    L1

    L1

    L1

    AREA OF WORK

    KEY PLAN

    LEVEL 1

    EXISTING TO REMAIN

    TO BE DEMOLISHED

    NOT IN SCOPE

    PROPOSED PARTITION

    PHASING LEGEND

    HOARDING

    All drawing andspecifications are theproperty of the architect.The contractor shall verifyall dimensions andinformation on site andreport any discrepancy toarchitect before proceeding.

    24 Ryerson Avenue, Suite 206. Toronto, ON M5T 2P3www.garchitects.ca | 647.727.8860 | [email protected]

    scale:

    drawn by:

    reviewed by:

    job number:

    plot date:

    drawing number:

    architects

    1 : 50

    LEVEL 1 - DEMOLITION RCP

    16084

    Baycrest Geriatric Care Dentistry Alterations

    DS

    MG

    20170503

    A1.31

    3560 Bathurst St. Toronto, ON M6A 2E1

    KEYNOTES - DEMOLITION

    Key Value Keynote Text

    1 EXISTING SPEAKER TO BE DEMOLISHED.

    2 EXISTING LIGHT FIXTURES TO BE DEMOLISHED.

    3 EXISTING SPRINKLER LAYOUT TO BE RECONFIGURED, COORDINATE WITHMECHANICAL ENGINEER.

    4 EXISTING SUPPLY/RETURN GRILLE TO BE DEMOLISHED.

    5 EXISTING SMOKE DETECTOR TO BE DEMOLISHED.

    6 EXISTING CEILING TO BE DEMOLISHED.

    # date: revision: by:

    1 20161130 ISSUED FOR PERMIT G

    2 20170503 ISSUED FOR TENDER G

  • 3

    A2.00

    1

    1

    1

    1

    1

    PROVIDE BULKHEAD ASREQUIRED AROUNDMECHANICAL SERVICES

    AREA OF WORK

    AREA OF HVAC ROUTING - PATCHING TO CEILING AS REQUIRED

    FURRING AS REQUIRED. COORD W/ MECH

    F3-

    A64

    -

    All drawing andspecifications are theproperty of the architect.The contractor shall verifyall dimensions andinformation on site andreport any discrepancy toarchitect before proceeding.

    24 Ryerson Avenue, Suite 206. Toronto, ON M5T 2P3www.garchitects.ca | 647.727.8860 | [email protected]

    scale:

    drawn by:

    reviewed by:

    job number:

    plot date:

    drawing number:

    architects

    As indicated

    ROUTING DIAGRAM - BASEMENT & LEVEL 1

    16084

    Baycrest Geriatric Care Dentistry Alterations

    CL

    MG

    20170503

    A2.00

    3560 Bathurst St. Toronto, ON M6A 2E1

    1 : 2502

    LEVEL 1 ROUTING DIAGRAM

    1 : 2501

    BASEMENT ROUTING DIAGRAM

    1 : 103

    LEVEL 1 ROUTING DIAGRAM - Callout 1

    KEYNOTES - DEMOLITION

    Key Value Keynote Text

    1 REMOVE AND REINSTALL ACT CEILING, TILES, AND GRID AS REQUIRED TO FACILIATE MECH/ELEC WORK.

    # date: revision: by:

    1 20161130 ISSUED FOR PERMIT G

    2 20170503 ISSUED FOR TENDER G

  • PUMP ROOMBA03A

    REFER TO MECHANICAL DRAWINGSFOR SCOPE OF WORK

    AREA OF WORK

    KEY PLAN

    EXISTING TO REMAIN

    TO BE DEMOLISHED

    NOT IN SCOPE

    PROPOSED PARTITION

    PHASING LEGEND

    HOARDING

    All drawing andspecifications are theproperty of the architect.The contractor shall verifyall dimensions andinformation on site andreport any discrepancy toarchitect before proceeding.

    24 Ryerson Avenue, Suite 206. Toronto, ON M5T 2P3www.garchitects.ca | 647.727.8860 | [email protected]

    scale:

    drawn by:

    reviewed by:

    job number:

    plot date:

    drawing number:

    architects

    1 : 50

    BASEMENT - FLOOR PLAN

    16084

    Baycrest Geriatric Care Dentistry Alterations

    Author

    Checker

    20170503

    A2.10

    3560 Bathurst St. Toronto, ON M6A 2E1

    # date: revision: by:

    1 20161130 ISSUED FOR PERMIT G

    2 20170503 ISSUED FOR TENDER G

  • C DE

    F

    1

    2

    3

    2820 3650 2195 3580

    3375

    4145

    4140

    3285

    2195

    1235

    1840

    720

    4275 4390

    OPERATORY

    1C02C

    OPERATORY1C02D

    OPERATORY

    1C02B

    FUTURE OPERATORY

    1C02A

    SOILED

    1C01A

    OFFICE1C02E

    PAN1C02G

    WORK AREA

    1C02F

    CORRIDOR1C02

    ELEC. ROOM1B18

    S S S

    S

    NC

    PASSTHROUGHWASHER

    CLEAN1C01B

    B

    WAITING ROOM CLINICS

    1C44

    CLEAR

    1100

    NC

    XR

    AY

    D01 45D02 45D03 45

    D04 -

    D11 -

    D10 -

    D05 -

    D07 -

    D09 -

    D08 45D06 -

    F2 F2

    F2

    F2

    F1

    F2

    F2

    F1 F2F2

    P4A

    A152

    -

    P3A

    A92

    -

    P4A

    A152

    -

    P4A

    A152

    -

    F5-

    A64

    -

    P6A

    A152

    -

    P5A

    A92

    -

    P7A

    A92

    60

    P8A

    A92

    -

    P8A

    A92

    -

    P7A

    A92

    60

    F4-

    --

    -

    F4-

    --

    -

    F4-

    --

    -

    1

    S01 -

    1

    1

    EXG EXG

    TR-1

    XRAYXRAY

    XRAY

    XRAY

    WP

    S04 -

    CG-1

    CG-1

    CG-1 CG-1

    TR-2

    TR-3

    TR-2

    TR-2

    TR-2TR-2

    P2A

    A92

    60F1

    A

    A152

    -

    CLEAR

    1100

    NC

    CG-1

    DOUBLESINK

    SINK

    A

    SPECIMENT COLLECTION

    1C45

    460

    NC NC

    460

    2820 2935 2825

    2540

    2905 1455

    COORD W/ DESK

    2195 2195

    8665

    9270

    1905

    1174

    0

    P2A

    A92

    60

    P3A

    A92

    -

    P3A

    A92

    -

    WP

    WP

    PC

    PC

    PC

    PC

    PC

    PB

    51 m² (548 ft²)

    CORRIDOR

    1C52

    D13 -

    WP

    12245 15055

    NC

    TR-2

    P5A

    A92

    -

    F1A

    A152

    -

    F6-

    A64

    -

    F5-

    A64

    -

    F5-

    A64

    -

    F5-

    A64

    -

    F5-

    A64

    -

    2

    COORD W/ FURN

    915

    F3-

    A64

    -

    F5-

    A64

    -

    F3-

    A64

    -

    460

    3

    3

    4

    4

    4 4

    MILLWORK MW-01 - REFER TODETAIL ON A9.00

    F7A

    A64

    -

    F2

    F2

    PODIATRY

    1C04

    OPITHAL

    1C03A

    1615 V.I.F.

    2945

    V.I.

    F.

    MILLWORK MW-01 - REFER TODETAIL ON A9.00

    V.I.

    F.

    900

    450

    610

    610

    F2EXG

    TR-1F2EXG

    TR-1F2EXG

    TR-1F1

    EXG

    TR-1F1

    TR-1F1

    EXG

    EXG

    F1

    6001040

    600

    D12 -

    610

    CLE

    AR

    1100

    610

    CLE

    AR

    1100

    CLE

    AR

    1000

    AREA OF WORK

    KEY PLAN

    LEVEL 1

    NC NURSE CALL

    S SECURITY ACCESS SWIPE PANEL

    XRAY XRAY TRIGGER

    WP WALL PHONE

    PC POLYCOM

    PB PUSH BUTTON - DOOR OPERATOR

    SYMBOL LEGEND

    NEW HAND WASH SINK

    NEW WORKROOM SINK

    EXISTING TO REMAIN

    TO BE DEMOLISHED

    NOT IN SCOPE

    PROPOSED PARTITION

    PHASING LEGEND

    All drawing andspecifications are theproperty of the architect.The contractor shall verifyall dimensions andinformation on site andreport any discrepancy toarchitect before proceeding.

    24 Ryerson Avenue, Suite 206. Toronto, ON M5T 2P3www.garchitects.ca | 647.727.8860 | [email protected]

    scale:

    drawn by:

    reviewed by:

    job number:

    plot date:

    drawing number:

    architects

    1 : 50

    LEVEL 1 - FLOOR PLAN

    16084

    Baycrest Geriatric Care Dentistry Alterations

    DS

    MG

    20170503

    A2.11

    3560 Bathurst St. Toronto, ON M6A 2E1

    KEYNOTES - PROPOSED

    Key Value Keynote Text

    1 INFILL WALL TO MATCH EXISTING WALL. PATCH AND MAKE GOOD ANYDAMAGE TO EXISTING WALL.

    2 .080 ALUMINUM SIGNAGE WITH BAKED ENAMEL FINISH TO READ "WARNING.FLAMMABLE MATERIALS. NO OPEN FLAME".

    3 IN FLOOR POWER INSTALLED. REFER TO ELEC.

    4 BLOCKING IN PARTITION FOR XRAY. REFER TO DENATL DRAWING DETAILS.

    # date: revision: by:

    1 20161130 ISSUED FOR PERMIT G

    2 20170503 ISSUED FOR TENDER G

  • C DE

    F

    1

    2

    3

    B

    RELIANCE

    MIDMARSTERILIZERS

    CART

    CURING LIGHT

    XRAY SYSTEM

    CURING LIGHTXRAY SYSTEM XRAY SYSTEM

    CURING LIGHT

    PAN

    FORMING VACUUM

    SANDBLAST / DUST COLLECTOR

    ULTRASONIC CLEANER

    LATHE

    UNDER COUNTER:DENTAL KAVO (STORAGE)HANDPIECES (STORAGE)HS AMALGAMSCAVOR

    SOILED

    1C01A

    OPERATORY

    1C02C

    OPERATORY1C02D

    OPERATORY1C02B

    FUTURE OPERATORY1C02A

    OFFICE1C02E

    PAN1C02G

    WORK AREA

    1C02F

    CORRIDOR

    1C02

    ELEC. ROOM

    1B18

    CLEAN

    1C01B

    WAITING ROOM CLINICS

    1C44

    450MM SHELVING

    MOUNTED ARM W/LIGHTING ABOVE

    UNDER COUNTER:DENTAL (KAVO)

    HANDPIECESHIGH SPEED AMALGAM

    SCALER

    UNDER COUNTER:DENTAL (KAVO)HANDPIECESHIGH SPEED AMALGAMSCALER

    UNDER COUNTER:MASTER SWITCHWET VACUUM SYSTEMAMALAGAM SEPARATORWATER SOLENOID

    PASSTHROUGHWASHER

    MOUNTED ARM W/LIGHTING ABOVE

    DENTAL CHAIR W/ MOUNTEDARM & LIGHTING ABOVE.

    DOCTOR'S & ASSISTANT'SSTOOLS ADJACENT

    TRIMMER

    DOUBLE SINK

    SINK

    A

    SPECIMENT COLLECTION

    1C45

    EQ EQ

    WORKSTATION

    ADJ DESK

    AD

    J D

    ES

    K

    AD

    J D

    ES

    K

    SYSTEM1

    EYEWASH STATION

    EYEWASH STATION

    ULTRASONIC X2 CLEANER

    All drawing andspecifications are theproperty of the architect.The contractor shall verifyall dimensions andinformation on site andreport any discrepancy toarchitect before proceeding.

    24 Ryerson Avenue, Suite 206. Toronto, ON M5T 2P3www.garchitects.ca | 647.727.8860 | [email protected]

    scale:

    drawn by:

    reviewed by:

    job number:

    plot date:

    drawing number:

    architects

    1 : 50

    LEVEL 1 - FURNISHING & EQUIPMENT

    16084

    Baycrest Geriatric Care Dentistry Alterations

    CL

    MG

    20170503

    A2.21

    3560 Bathurst St. Toronto, ON M6A 2E1

    NOTE: EQUIPMENT & FURNITURE TO BE OWNERSUPPLIED, VENDOR INSTALLED

    # date: revision: by:

    1 20161130 ISSUED FOR PERMIT G

    2 20170503 ISSUED FOR TENDER G

  • C DE

    F

    1

    2

    3

    CLG2700

    GWB S

    CLG2700

    GWB S

    CLG2700

    GWB S

    CLG2700

    GWB S

    L1

    L1

    L1

    L1

    L1

    L1

    L1 L1

    B

    L1

    CLG2700

    GWB S

    A

    CLG2700

    GWB S

    665 1480

    665

    860 860

    1115

    1185

    800

    1525

    1065 1065

    1000 1455 1000

    EQ

    EQ

    L1

    1475

    1475

    CLG2700

    GWB S

    CLG2700

    GWB S

    1200

    2355

    1000

    EQ EQ

    EQ EQ

    1000

    1535

    1000

    L1

    L1

    L1

    L1

    SA1

    RA1

    SA1

    RA1

    SA1

    RA1 SA1

    RA1

    RA1

    SA2

    RA1

    RA1

    SA2SA2

    SA1

    RA1

    SA1

    SA1

    SA1RA1

    RA1

    SP1

    SP1

    SP1

    SP1

    SP1SP1

    SP1

    SP1SP1

    SP1

    SP1

    SP1

    SP1

    SP1

    SP1

    EQ

    EQ

    CLG2700

    GWB S

    EQ EQ

    SA2

    SA2

    RA1

    SP1

    SP1

    CLG2700

    GWB S

    1242 1241

    L1

    EQ

    EQ

    A C T

    CLG2700

    GWB SA C T

    SP1

    SA2

    SP1

    SA2

    RA1

    A C T

    A C T

    SA2 SA2

    SP1SP1

    RA1

    CLG2700

    GWB SA C T

    L2 L2

    L2 L2

    L2 L2

    L2 L2

    L2

    L2

    L2

    L2

    L2

    L2

    L2

    L2

    10

    A9.00

    TYP

    1

    1

    1 1

    F3

    F3

    LD LD LD

    LD

    ELECTRICAL FIXTURES

    LIGHTING FIXTURES

    L2L1

    610 x 610 FIXTURE610 x 1220 FIXTURE

    SPEAKER (CIRCULAR)

    SP1

    MECHANICAL FIXTURES

    RECESSED SPRINKLERSMOKE / HEAT DETECTORSURFACE MOUNTED

    305X305 CEILING MOUNTEDRETURN AIR DIFFUSER

    305X305 CEILING MOUNTEDSUPPLY AIR DIFFUSER

    HEATING, VENTILATION & AIR CONDITIONING

    SA1 RA1

    SECURITY

    FIRE PROTECTION

    305X610 CEILING MOUNTEDRETURN AIR DIFFUSER

    610X610 CEILING MOUNTEDSUPPLY AIR DIFFUSER

    SA2 RA2

    610X610 CEILING MOUNTEDRETURN AIR DIFFUSER

    RA3

    CAMERA

    UNDERCABINET LIGHTS1

    TRAC LIGHTF3

    AREA OF WORK

    KEY PLAN

    LEVEL 1

    EXISTING TO REMAIN

    TO BE DEMOLISHED

    NOT IN SCOPE

    PROPOSED PARTITION

    PHASING LEGEND

    All drawing andspecifications are theproperty of the architect.The contractor shall verifyall dimensions andinformation on site andreport any discrepancy toarchitect before proceeding.

    24 Ryerson Avenue, Suite 206. Toronto, ON M5T 2P3www.garchitects.ca | 647.727.8860 | [email protected]

    scale:

    drawn by:

    reviewed by:

    job number:

    plot date:

    drawing number:

    architects

    1 : 50

    LEVEL 1 - REFLECTED CEILING PLAN

    16084

    Baycrest Geriatric Care Dentistry Alterations

    DS

    MG

    20170503

    A3.01

    3560 Bathurst St. Toronto, ON M6A 2E1

    KEYNOTES - PROPOSED

    Key Value Keynote Text

    1 ADDITIONAL STRUCTURAL SUPPORT IN CEILING. REFER TO DENTALDRAWINGS.

    # date: revision: by:

    1 20161130 ISSUED FOR PERMIT G

    2 20170503 ISSUED FOR TENDER G

  • SCHEDULE - DOORS

    DOOR FRAME

    DOOR NO. CONDITION TYPE WIDTH HEIGHT MATERIAL FINISH MATERIAL FINISHFIRE

    RATING NOTES

    D01

    D02

    D03

    D04 -

    D06

    D11

    D05 NEW -

    -

    -

    D07

    D08

    D09

    NEW

    NEW

    NEW

    D1

    965 2050

    2700

    2050

    2700

    45 MIN

    TYPE

    D10

    -

    NEW

    NEW

    NEW

    NEW

    NEW

    NEW

    D1 965

    965

    1100

    965

    1200

    1000

    1200

    1200

    1200

    2700

    2700

    2700

    2050

    2050

    2050 HM

    HM

    SOLID COREWD

    HM

    LEADED

    LEADED

    F1 HM

    HM

    HM

    HM

    OPEN

    OPEN

    OPEN

    OPEN

    OPEN

    -

    -

    45 MIN

    45 MIN

    SECURITY ACCESS SWIPE PANEL. VERIFYOPENING AND DOOR SIZE

    D5

    D4

    D1

    D2

    D3

    D3

    D3

    D3

    D3

    F1

    F3

    F5

    F1

    F2

    F2

    F2

    F2

    F2

    LEADED LEADED

    45 MIN

    COORD DOOR HEIGHT W/ RCP

    -

    -

    SECURITY ACCESS SWIPE PANEL

    SECURITY ACCESS SWIPE PANEL, AUTOMATICDOOR OPERATOR & PUSH BUTTON

    SECURITY ACCESS SWIPE PANEL

    HARDWAREGROUP

    1

    2

    3

    4

    5

    6

    REF SPECS

    D12 EXISTING - ------

    965 2050 HM F1 HMPT-1NEW

    PT-1

    PT-1

    PT-1

    PT-1

    PT-1

    PT-1

    PT-1

    PT-1

    PT-1

    PT-1

    PT-1 45 MIN

    PT-1

    PT-1

    PT-1

    PT-1

    PT-1

    PT-1

    PT-1

    PT-1

    PT-1

    PT-1

    PT-1

    PT-1

    LEADED

    LEADED

    LEADED

    COORD DOOR HEIGHT W/ RCP

    COORD DOOR HEIGHT W/ RCP

    COORD DOOR HEIGHT W/ RCP

    COORD DOOR HEIGHT W/ RCP

    EXISTING DOUBLE DOOR

    REF SPECS

    REF SPECS

    REF SPECS

    REF SPECS

    D13 EXISTING - ------ PT-1 45 MINPT-1

    50 50

    50

    FRAME TYPE 'F1'FIRE RATED METAL

    FRAME TYPE 'F2'"FRAMELESS FULL HEIGHT

    OPENING"

    FRAME TYPE 'F3'HOLLOW METAL

    2700

    CO

    OR

    D W

    RC

    P

    FRAME TYPE 'F4'LEADED

    100 VARIES 100

    DOOR W

    DO

    OR

    H

    50 50

    50

    DOOR W

    DO

    OR

    H

    50 50

    50

    DOOR W

    DO

    OR

    H

    50 50

    50

    F50.8MM LEADED FRAMEGL-2 = LEADED GLASS

    50

    915

    50

    GL2

    50

    610 DOOR W

    DO

    OR

    HE

    IGH

    T

    OP

    EN

    ING

    HE

    IGH

    T

    VARIES

    DOOR TYPE 'D3'SLIDING LEADED

    DOOR

    HE

    IGH

    T

    WIDTH

    DOOR TYPE 'D1'FIRE RATED

    METAL DOOR

    HE

    IGH

    T

    WIDTH

    DOOR TYPE 'D2'FIRE RATED METAL DOOR W/

    FIRE RATED GLAZED LITE

    150

    GL-3

    HE

    IGH

    T

    WIDTH

    DOOR TYPE 'D4'LEADED DOOR

    150

    HE

    IGH

    T

    WIDTH

    DOOR TYPE 'D5'SOLID CORE WD DOOR

    100 100OPENING W

    250

    150

    915

    915

    1220

    50 50

    5050

    GL1

    S01GL1 = 13MM

    TEMPERED GLASS

    915

    610

    610

    50 50

    5050

    GL1

    PASSTHROUGHWINDOW TYPE S04REFER TO SECTION

    08 56 13GL1 = 13MM

    TEMPERED GLASS

    50 16

    PA

    RTI

    TIO

    N T

    YP

    E

    VA

    RIE

    S T

    O S

    UIT

    CONT. SEALANT

    50 16

    PA

    RTI

    TIO

    N T

    YP

    E

    VA

    RIE

    S T

    O S

    UIT

    FIRE STOP INSULATION

    CONT. SEALANT

    5016

    PARTITION TYPE

    VARIES TO SUIT

    CONT. SEALANT

    5016

    PARTITION TYPE

    VARIES TO SUIT

    FIRE STOP INSULATION

    CONT. SEALANT

    5016

    PARTITION TYPE

    VARIES TO SUIT

    LEAD SHIELDING IN FRAME

    CONT. SEALANT

    50 16

    PA

    RTI

    TIO

    N T

    YP

    E

    VA

    RIE

    S T

    O S

    UIT

    LEAD SHIELDING INFRAME

    CONT. SEALANT

    100

    SLIDING DOOR SYSTEM

    PAINTED BLOCKING

    SLIDING DOORFINISHED CEILING

    915

    COUNTERTOP - 19mm SOLIDSURFACE ON 19MM

    PLYWOOD

    HOLES W/ MTL GROMMETS FORADJUSTABLE SHELF SUPPORTS

    13mm SOLID WDBASE

    T.O. FINISHED FLOOR

    BACK: 13mm G1S VENEER CORE

    PLYWOOD

    ADJUSTABLE 19mm G1S VENNERCORE PLYWOOD SHELF W/

    10mm SOLID WD EDGING

    INTERIOR GABLES: 19mm G1S VENEER CORE PLYWOOD

    PROVIDE ADDITIONAL G1S PLY PANEL ATALL EXPOSED EXTERIOR GABLE ENDS

    BOTTOM: 19mm G1S VENER CORE

    PLYWOOD

    100

    50

    PROVIDE 50mm HOLES INCOUNTER TOP WITH MTL.

    GROMMETS AT LOCATIONSPROVIDED BY OWNER

    55

    SOLID SURFACE WITH BUILT-UP,RADIUSED EDGES

    ON 19mm PLYWOOD

    38

    TYP. DIM

    50

    All drawing andspecifications are theproperty of the architect.The contractor shall verifyall dimensions andinformation on site andreport any discrepancy toarchitect before proceeding.

    24 Ryerson Avenue, Suite 206. Toronto, ON M5T 2P3www.garchitects.ca | 647.727.8860 | [email protected]

    scale:

    drawn by:

    reviewed by:

    job number:

    plot date:

    drawing number:

    architects

    As indicated

    DOOR SCHEDULE, SCREEN TYPES, MILLWORK

    16084

    Baycrest Geriatric Care Dentistry Alterations

    CL

    MG

    20170503

    A9.00

    3560 Bathurst St. Toronto, ON M6A 2E1

    1 : 502

    FRAME TYPES

    1 : 501

    DOOR TYPES

    1 : 503

    SCREEN TYPES

    1 : 56

    JAMB - HM FRAME F3 IN GWB PARTITION

    1 : 54

    JAMB - RATED HM FRAME F1 IN GWB PARTITION

    1 : 57

    HEAD - HM FRAME F3 IN GWB PARTITION

    1 : 55

    HEAD - RATED HM FRAME F1 IN GWB PARTITION

    1 : 59

    HEAD - HM LEADED FRAME F4 IN GWB PARTITION

    1 : 58

    JAMB - HM LEADED FRAME F4 IN GWB PARTITION

    1 : 510

    SLIDING DOOR CONCEALED HARDWARE DETAIL - DOOR TYPE D3

    1 : 1011

    MW-01 SECTION

    1 : 512

    MW-01 COUNTER DETAIL

    # date: revision: by:

    1 20161130 ISSUED FOR PERMIT G

    2 20170503 ISSUED FOR TENDER G