Description:
Intelligent power factor controller
Popular Tags:

of 41

Transcript
  • 5/22/2018 Beluk Technical Manual

    1/41

  • 5/22/2018 Beluk Technical Manual

    2/41

    - 1 -

    All rights reserved.No part of this book may be reproduced or utilized inany form or by any means, electronic or mechanical, including photocopyingor recording, or by any information storage and retrieval system, withoutpermission in writing from publisher.

    BELUK GmbH

  • 5/22/2018 Beluk Technical Manual

    3/41

    - 2 -

    Taubenstr. 1 Phone +49 8861 2332-0 Fax +49 8861 2332-51

  • 5/22/2018 Beluk Technical Manual

    4/41

    - 3 -

    1. How Electrical Reactive Power Originates

  • 5/22/2018 Beluk Technical Manual

    5/41

    - 4 -

    [ ]

  • 5/22/2018 Beluk Technical Manual

    6/41

    - 5 -

    2. Recording the Resultant Electric Reactive Power

  • 5/22/2018 Beluk Technical Manual

    7/41

    - 6 -

    3. Calculation of Capacitor Bank Size

    72.08200

    var5900tan

    ==kWh

    hk

  • 5/22/2018 Beluk Technical Manual

    8/41

    - 7 -

  • 5/22/2018 Beluk Technical Manual

    9/41

    - 8 -

  • 5/22/2018 Beluk Technical Manual

    10/41

    - 9 -

    4. Selection of Switching Programme and Relay Types

    4.1 Response Value (C/k-Value)

    =

  • 5/22/2018 Beluk Technical Manual

    11/41

    - 10 -

  • 5/22/2018 Beluk Technical Manual

    12/41

    - 11 -

    4.2 Economy or Step-back Switching Programmes

  • 5/22/2018 Beluk Technical Manual

    13/41

    - 12 -

  • 5/22/2018 Beluk Technical Manual

    14/41

    - 13 -

    4.3 Rotational Switching Programme

  • 5/22/2018 Beluk Technical Manual

    15/41

    - 14 -

  • 5/22/2018 Beluk Technical Manual

    16/41

    - 15 -

    5. Function of the Electronic Power Factor Control Relays of C-Series

    5.1 Structure and Mode of Operation

    5.2 Operating and Signalling Elements on BLR-CA

  • 5/22/2018 Beluk Technical Manual

    17/41

    - 16 -

    5.3 No-Volt Release Feature

    5.4 Target Power Factor Setting and Starting Current

    5.5 Hand / Automatic Switching

  • 5/22/2018 Beluk Technical Manual

    18/41

    - 17 -

    5.6 Technical Data on BLR-CA (C-series)

    5.7 Connection Diagram of BELUK Power Factor Control Relays

  • 5/22/2018 Beluk Technical Manual

    19/41

    - 18 -

    5.8 Determining the Required Current Transformer

    =

  • 5/22/2018 Beluk Technical Manual

    20/41

    - 19 -

    2 8m 0.0178 mm

    2,5mm m0.114

    2

    2

    =

    V

    A

  • 5/22/2018 Beluk Technical Manual

    21/41

    - 20 -

    6. Explanatory Notes on the Compensation Procedure in General

  • 5/22/2018 Beluk Technical Manual

    22/41

    - 21 -

    6.1 Relationship between Response Value (C/k-Value) and cos-setting

  • 5/22/2018 Beluk Technical Manual

    23/41

    - 22 -

  • 5/22/2018 Beluk Technical Manual

    24/41

    - 23 -

  • 5/22/2018 Beluk Technical Manual

    25/41

    - 24 -

    6.2 Power Factor Control Relays with Automatic C/k-Adjustment (C-series)

  • 5/22/2018 Beluk Technical Manual

    26/41

    - 25 -

    1 Transformer switch-over 5A / 1A(except BLR-CC)

    2 Alarm ON/OFF

    3 Function Switch

    4/5 +/- Button

    6 Stage indicator

    7 TTL-Interface

    (except BLR-CC and CD)

    8 Display/ Cos Indication

  • 5/22/2018 Beluk Technical Manual

    27/41

    - 26 -

    7. Reactive Power Compensation in the Four Load Quadrants

    7.1.1 Technical Consideration

  • 5/22/2018 Beluk Technical Manual

    28/41

    - 27 -

  • 5/22/2018 Beluk Technical Manual

    29/41

    - 28 -

    Variation of Power Factor on Import and Export of Power

    Case a): All power imported

    Case b) Power partly supplied

    by Generator(s)

    Case c) All Power supplied

    by Generator(s) and

    Power Export

    Measuring point: Current Transformer at Main Incomer or at Metering Point

    PN S

    Q

    PN

    PV

    cos= 0,23S

    Q

    PG

    cos= 0,2

    4

    S

    Q

    PG

    cos = 0,73

  • 5/22/2018 Beluk Technical Manual

    30/41

    - 29 -

    7.1.2 Commercial Consideration

  • 5/22/2018 Beluk Technical Manual

    31/41

    - 30 -

    7.2 Reactive Power Compensation with Mixed Measurement

    BLR

    CA-12

    20 kV / 50 Hz

    50 A / 5 A; k = 10 (Phase L2)

    Transformator1250 kVA20 kV / 0,66 kVDd 6

    660 V / 50 Hz

    Kompensation12 x 60 kvar

    660 V / 400 V(Phasen L3/L1)

  • 5/22/2018 Beluk Technical Manual

    32/41

    - 31 -

    Current transformer in L1 Measuring voltage

    (H.V.-side) (L.V.-side)

  • 5/22/2018 Beluk Technical Manual

    33/41

    - 32 -

    7.2.1 Calculation of C/k-Value in case if Mixed Measurement

    Ar

    kV

    kkC 10.0

    10320

    var606.0/

    =

    -

  • 5/22/2018 Beluk Technical Manual

    34/41

    - 33 -

    8. Reactive Power Compensation with more than one Incoming Supply

    8.1 Central Compensation by means of Summation Measurement

  • 5/22/2018 Beluk Technical Manual

    35/41

    - 34 -

    1200A 1200A 1200A

    5A 5A 5A

    5A 5A 5A

    5A

    3600A

    15A

    15A

    5A240 3 720

    + +

    + +

    + += = =

    0.6 P

    U 3 k

    0.6 33.3 kvar

    0.4 kV 3 7200,04Arc

    =

    =

  • 5/22/2018 Beluk Technical Manual

    36/41

    - 35 -

    0.60

    0.04Ar

    x

    0.05Ar0,06

    0.05Ar

    0.04Ar= =

  • 5/22/2018 Beluk Technical Manual

    37/41

    - 36 -

    8.2 Individual Compensation of Each Incoming Supply

    k1200A

    5A240= =

    Ar0.182403kV0.4

    kvar500,6=

  • 5/22/2018 Beluk Technical Manual

    38/41

    - 37 -

  • 5/22/2018 Beluk Technical Manual

    39/41

    - 38 -

    9. How to Trace Possible Mistakes when connecting Power Factor

    Control Relays of the Series C

    =

  • 5/22/2018 Beluk Technical Manual

    40/41

    - 39 -

    =

    =

  • 5/22/2018 Beluk Technical Manual

    41/41

    - 40 -

    10. Indirect Capacitor Control (z) on BELUK Power Factor Control

    Relays, Type CA

    The true Purpose of Harmonic Analysis