Date post: | 02-Apr-2015 |
Category: |
Documents |
Upload: | m-kumar-marimuthu |
View: | 12 times |
Download: | 1 times |
Trip Unit Technologies & Arc Flash Solutions from GE
End The Reliability & Protection Compromise
March, 2009By Darrin K Bock
Flexible Options to upgrade your existing gear to the latest
EntelliGuard TU
2GEM. Valdes – Train the Expert – Arc Flash Lesson 3September 16, 2008
EntelliGuard® TU• Arc Flash and Selectivity at the same time
• ZSI - short time, ground fault and instantaneous
• Reduced Energy Let Thru (RELT)• Create the curve shape that best
suits your system’s need (fuse-like Long Time and Ground curves)
• A large backlit LCD screen makes set-up easier in difficult environments
• Metering, Relaying, WaveForm Functions
• Universal Rating Plug (and trip unit Ent G)
• Modbus or Profibus (Comnet is gone)
• Flexible programmable inputs/2 outputs for needs such as Load shedding, ground fault alarm, trip indication and many others
• Plug and play compatibility with 4 previous generation power circuit breakers – PowerBreak I, PowerBreak II, AKR and WavePro
• Available in kit format to modernize Westinghouse, I-T-E, and Allis Chalmers circuit breakers
ANSI, UL, IEC
Modern Circuit Breaker Technology
March, 2009By Darrin K Bock
• Reduced Energy Let – ThruReduced Energy Let – Thru
• Flexible Time Current Curves to “fit” all your needsFlexible Time Current Curves to “fit” all your needs
• Advanced Instantaneous AlgorithmAdvanced Instantaneous Algorithm
• ZSI (Zone Selective Interlock) – now has ZSI (Zone Selective Interlock) – now has InstantaneousInstantaneous
Enables…. Arc Flash and Selectivity at the Same Time
4GEM. Valdes – Train the Expert – Arc Flash Lesson 3September 16, 2008
Arc Flash Hazard Overview
Arc Flash energy is a function of:
• Voltage
• Available short circuit current
• Working distance
• Arc gap
• Arcing fault clearing time (not short circuit clearing time)
• Sensitivity Clearing time is the only parameter than can be modified after
the power system design is set. Therefore….
• Fixed
• Based on system design and source
• Arms are only so long
• Determined by equipment type
• A function of the protective device acting upon the arcing current
Arcing fault clearing time becomes the critical factor
SourceHeat
Measurement
Arcing current RMS & peak magnitude, &
time
• Working Distance
• Voltage• Av ailable Short
Circuit Current
• Time to clear
• Electrode Gap
• Enclosure
SourceHeat
Measurement
Arcing current RMS & peak magnitude, &
time
• Working Distance
• Voltage• Av ailable Short
Circuit Current
• Time to clear
• Electrode Gap
• Enclosure
Figure 1
5GEM. Valdes – Train the Expert – Arc Flash Lesson 3September 16, 2008
RELT (Reduced Energy Let-Through) Instantaneous Trip Setting
Separate independent adjustable instantaneous pickup:
• 1.5X-15X or max Instantaneous Pick Up of CB if less
• ½ cycle faster than normal Instantaneous Pick Up
• Overrides all other higher pickups
• Operated via a Remote Switch or Modbus Communications
RELT – Reduced Energy Let ThruRELT – Reduced Energy Let Thru
Aka; Maintenance Switch, ARMS, Safety Setting, Arc Flash Switch, Alternate Setting… Used when performing maintenance or other live work to improve protection
6GEM. Valdes – Train the Expert – Arc Flash Lesson 3September 16, 2008
GTU Curve, CB1 & CB2
0.01
0.10
1.00
10.00
100.00
1000.00
100 1,000 10,000 100,000 1,000,000Amperes
Se
co
nd
sRELT TCC
RELT OFF
RELT ON
7GEM. Valdes – Train the Expert – Arc Flash Lesson 3September 16, 2008
RELT Wiring with Positive Indication
RELT Control Power Available indication
RELT Control switch must be 2 position lockable in “ON” position. Lock suitable for LOTO procedures, 3/8” hasp.
Actual Trip, CB and harness connections not shown, will vary by CB type and mounting style
Position of switch and indicating lights may be in equipment or remote.
RELT indicating lights are long life LED.
GE will provide a 3 position switch with built in blue light.
24V
RELT ManualInput Switch
RELT Feedback from Trip
RELT On Light
RELT Ctrl Pwr Available
Light 24V ACor DC
ON
OFF
Trip Unit
TB for user wiring
8GEM. Valdes – Train the Expert – Arc Flash Lesson 3September 16, 2008
Flexible Time Curves GTU Curve, CB1 & CB2
0.01
0.10
1.00
10.00
100.00
1000.00
100 1,000 10,000 100,000 1,000,000Amperes
Sec
on
ds
1
2
7
6
3
5
4
1) Plugs: 37.5-100% sensor. LTPU 50-100% Plug – Universal Rating Plugs
2) CB & Fuse Shaped LT Bands
3) 22 LT delays in both CB & Fuse shapes, 44 total
4) STPU:1.5-12X LTPU, (0.05 increments)
5) STI2T slope: 3 different slopes
6) ST TB: As fast as 1.5 Cycles, 11 different bands, in 55ms increments
7) Instantaneous pickup 2X-15X standard, 1.5-30X optional in ANSI GACB.
more precision in settings and tolerances
9GEM. Valdes – Train the Expert – Arc Flash Lesson 3September 16, 2008
Minimum and maximum LT delaysGTU Curve, CB1 & CB2
0.01
0.10
1.00
10.00
100.00
1000.00
100 1,000 10,000 100,000 1,000,000Amperes
Se
co
nd
s
GTU Curve, CB1 & CB2
0.01
0.10
1.00
10.00
100.00
1000.00
100 1,000 10,000 100,000 1,000,000Amperes
Se
co
nd
s
10GEM. Valdes – Train the Expert – Arc Flash Lesson 3September 16, 2008
ST PU and Delays
Note fast 25 millisecond ST delay, clearing time well under 100mS!
Note that upper ST band intersects LT band with “no” vertical transition!• Lots of flexibility• Faster protection• Lots of range• But some unusual
combinations are possible
GTU Curve, CB1 & CB2
0.01
0.10
1.00
10.00
100.00
1000.00
100 1,000 10,000 100,000 1,000,000Amperes
Se
co
nd
s
Envelope/Standard = Envelope 1/ANSI ST PU = 1.5 X LTPU I PU = 30 X Trip Rating PlugExt RangeOverride = 65000A ST TD = Min STDB Net I PU I = 30000A
Sensor = 1600A ST Slope = OFF RELT I PU = OFFPlug = 1000A ST PU = 1500A In zone Fault Net RELT I = 0A
LT PU = 1 X Plug LT PU = 1000A NO GF Tol =15%
LT TD = Min CB GF = OFF 0A PU Slope = I2T 3rdTD BandEnvelope/Standard = 1/ANSI ST PU = 12 X LTPU ZSI I PU = 30 X Trip Rating Plug Ext Range
Override = 65000A ST TD = Max STDB 5th STDB Net I PU I = 30000ASensor = 2000A ST Slope = OFF OFF RELT I PU = OFF
Plug = 1000A ST PU = 12000A Net RELT I = 0A
LT PU = 1 X Plug LT PU = 1000A IPU ZSI = ON GF Tol =15%
LT TD = C-2 GF = OFF 0A PU Slope = OFF MinimumTD BandGF ZSI =--------------------------------------------> Slope = SGF 3rdTD Band
CB1-Fault CB2 Restrained Response
CB1 - 60Hz
CB2 - 60Hz
11GEM. Valdes – Train the Expert – Arc Flash Lesson 3September 16, 2008
ST Slopes
3 different slopes available
K=I2t = slope definition
K = 2, 8, & 18
Shown are 2 and 18, 8 falls in between
GTU Curve, CB1 & CB2
0.01
0.10
1.00
10.00
100.00
1000.00
100 1,000 10,000 100,000 1,000,000Amperes
Se
co
nd
s
Envelope/Standard = Envelope 1/ANSI ST PU = 1.5 X LTPU I PU = 30 X Trip Rating PlugExt RangeOverride = 65000A ST TD = Min STDB Net I PU I = 30000A
Sensor = 1600A ST Slope = Min RELT I PU = OFFPlug = 1000A ST PU = 1500A In zone Fault Net RELT I = 0A
LT PU = 1 X Plug LT PU = 1000A NO GF Tol =15%
LT TD = Min CB GF = OFF 0A PU Slope = I2T 3rdTD BandEnvelope/Standard = 1/ANSI ST PU = 2.5 X LTPU ZSI I PU = 30 X Trip Rating Plug Ext Range
Override = 65000A ST TD = 5th STDB 5th STDB Net I PU I = 30000ASensor = 2000A ST Slope = Max OFF RELT I PU = OFF
Plug = 1000A ST PU = 2500A Net RELT I = 0A
LT PU = 1 X Plug LT PU = 1000A IPU ZSI = ON GF Tol =15%
LT TD = C-2 GF = OFF 0A PU Slope = OFF MinimumTD BandGF ZSI =--------------------------------------------> Slope = SGF 3rdTD Band
CB1-Fault CB2 Restrained Response
CB1 - 60Hz
CB2 - 60Hz
12GEM. Valdes – Train the Expert – Arc Flash Lesson 3September 16, 2008
Adjustable Selective Instantaneous
GTU Curve, CB1 & CB2
0.01
0.10
1.00
10.00
100.00
1000.00
100 1,000 10,000 100,000 1,000,000Amperes
Se
co
nd
s
Envelope/Standard = Envelope 1/ANSI ST PU = 1.5 X LTPU I PU = 2 X Trip Rating PlugOverride = 65000A ST TD = Min STDB Net I PU I = 2000A
Sensor = 1600A ST Slope = OFF RELT I PU = OFFPlug = 1000A ST PU = 1500A In zone Fault Net RELT I = 0A
LT PU = 1 X Plug LT PU = 1000A NO GF Tol =15%LT TD = Min CB GF = OFF 0A PU Slope = I2T 3rdTD Band
Envelope/Standard = 1/ANSI ST PU = 3 X LTPU ZSI I PU = 30 X Trip Rating Plug Ext RangeOverride = 65000A ST TD = 4th STDB 5th STDB Net I PU I = 30000A
Sensor = 2000A ST Slope = OFF OFF RELT I PU = OFFPlug = 1000A ST PU = 3000A Net RELT I = 0A
LT PU = 1 X Plug LT PU = 1000A IPU ZSI = ON GF Tol =15%
LT TD = C-2 GF = OFF 0A PU Slope = OFF MinimumTD BandGF ZSI =--------------------------------------------> Slope = SGF 3rdTD Band
CB1-Fault CB2 Restrained Response
CB1 - 60Hz
CB2 - 60Hz
2X to 15 or 30X plug available but may be limited by Icw.
Note 3 cycle clearing and 12mS commit drawn above the 0.01 axis.
The 0.012S differentiates the HSIOC (override), drawn down to 0.01S.
The 12mS should not be used like a traditional commit time.
13GEM. Valdes – Train the Expert – Arc Flash Lesson 3September 16, 2008
GF4 different shapes.
Right up against what the standards allow.
The double knee shape is specially good for selectivity purposes.
Maximum 1200A or 60% of sensor, whichever is less.
Minimum is 20%, 10% IEC.
GTU Curve, CB1 & CB2
3000A, 1 Second
150%, 2 Seconds
0.01
0.10
1.00
10.00
100.00
1000.00
100 1,000 10,000 100,000 1,000,000Amperes
Se
co
nd
s
GTU Curve, CB1 & CB2
3000A, 1 Second
150%, 2 Seconds
0.01
0.10
1.00
10.00
100.00
1000.00
100 1,000 10,000 100,000 1,000,000Amperes
Se
co
nd
s
I2t
SGF
Definite time (no slope)
I4t
14GEM. Valdes – Train the Expert – Arc Flash Lesson 3September 16, 2008
GF Selectivity
800A CB fits under 1200A GF.
ST pick up is at 1.5X & I2t slope is minimum . . . But it is possible even without ZSI
GTU Curve, CB1 & CB2
0.01
0.10
1.00
10.00
100.00
1000.00
100 1,000 10,000 100,000 1,000,000Amperes
Se
co
nd
s
Envelope/Standard = Envelope 1/ANSI ST PU = 1.5 X LTPU I PU = 9 X Trip Rating PlugOverride = 65000A ST TD = Min STDB Net I PU I = 0A
Sensor = 2000A ST Slope = OFF RELT I PU = OFFPlug = 2000A ST PU = 999999A In zone Fault Net RELT I = 0A
LT PU = 1 X Plug LT PU = 0A NO GF Tol =15%LT TD = C-5 GF = 0.6 X Sensor 1200A PU Slope = SGF 2ndTD Band
Envelope/Standard = 1/ANSI ST PU = 1.5 X LTPU ZSI I PU = 5.5 X Trip Rating PlugOverride = 65000A ST TD = 4th STDB 5th STDB Net I PU I = 4400A
Sensor = 800A ST Slope = Min OFF RELT I PU = OFFPlug = 800A ST PU = 1200A Net RELT I = 0A
LT PU = 1 X Plug LT PU = 800A IPU ZSI = ON GF Tol =15%
LT TD = C-3 GF = OFF 0A PU Slope = OFF MinimumTD BandGF ZSI =--------------------------------------------> Slope = SGF 3rdTD Band
CB1-Fault CB2 Restrained Response
CB1 - 60Hz
CB2 - 60Hz
15GEM. Valdes – Train the Expert – Arc Flash Lesson 3September 16, 2008
16GEM. Valdes – Train the Expert – Arc Flash Lesson 3September 16, 2008
Adjustable Instantaneous “starts” at 12 mS clears at 50 in new CB,
Fastest short time band starts at 25mS and clear at 80mS or 88mS.
Faster Clearing Times
17GEM. Valdes – Train the Expert – Arc Flash Lesson 3September 16, 2008
(80,000)
(60,000)
(40,000)
(20,000)
-
20,000
40,000
60,000
80,000
100,000
- 0.005 0.010 0.015 0.020
Seconds
Am
per
es
Prospective
Let-through
Prospective fault current (Ibf)
Let-through I peak
Let-through I2t
0.01
0.10
1.00
10.00
100.00
1000.00
100 1,000 10,000 100,000 1,000,000
Advanced Instantaneous AlgorithmInstantaneous algorithm able to discern a fault current from a “peak” let-through. Filters out the wave shape that corresponds to the let-through of a current limiting OCPD (CB or fuse)
18GEM. Valdes – Train the Expert – Arc Flash Lesson 3September 16, 2008
GTU Curve, CB1 & CB2
0.01
0.10
1.00
10.00
100.00
1000.00
100 1,000 10,000 100,000 1,000,000Amperes
Se
co
nd
s
Minimum selective IPU setting
Instantaneous Selectivity
0.01
0.10
1.00
10.00
100.00
1000.00
100 1,000 10,000 100,000 1,000,000
Transition
GTU selective settings based on the curve of the downstream current limiting molded case CB.
Depends on the MCCB curve being defined correctly.
Only instantaneous selectivity you can see on the curve
20GEM. Valdes – Train the Expert – Arc Flash Lesson 3September 16, 2008
Safety features that reduce the risk of the arc flash hazard
• Two instantaneous settings, one for maximum selectivity and one for maximum safety (RELT)
• Zone Selective Interlocking simultaneously provides short time, ground fault and instantaneous selectivity with separate settings of the band to switch from & to
• Instantaneous Zone Selective Interlocking with overlapping instantaneous characteristics – a unique GE capability
• Selectivity up to 65, 85 or 100kA is available with instantaneous set at much lower values, while still clearing in less than 3 cycles
21GEM. Valdes – Train the Expert – Arc Flash Lesson 3September 16, 2008
GTU Curve, CB1 & CB2
0.01
0.10
1.00
10.00
100.00
1000.00
100 1,000 10,000 100,000 1,000,000Amperes
Se
co
nd
s
1) ZSI I2t curves - 2) Can set restrained & unrestrained positions independently - 3) ZSI Instantaneous & ST independently
GTU Curve, CB1 & CB2
0.01
0.10
1.00
10.00
100.00
1000.00
100 1,000 10,000 100,000 1,000,000Amperes
Se
co
nd
s
I2t shifted
ST TDB shifted
Instantaneousshifted
ZSI (Zone Selective Interlock) –ZSI (Zone Selective Interlock) –InstantaneousInstantaneous Instantaneous zone selective interlocking so CBs can be kept protecting at instantaneous speeds while still maintaining selectivity up to 100kA
22GEM. Valdes – Train the Expert – Arc Flash Lesson 3September 16, 2008
ZSI
Requires that each CB have the ST and GF bands set for the “restrained” and “unrestrained” positions. Same with slopes if used. One pick up setting.
GTU Curve, CB1 & CB2
0.01
0.10
1.00
10.00
100.00
1000.00
100 1,000 10,000 100,000 1,000,000Amperes
Se
co
nd
s
0.01
0.10
1.00
10.00
100.00
1000.00
100 1,000 10,000 100,000 1,000,000
Envelope/Standard = Envelope 1/ANSI ST PU = 1.5 X LTPU I PU = 10 X Trip Rating PlugOverride = 65000A ST TD = Min STDB Net I PU I = 8000A
Sensor = 800A ST Slope = OFF RELT I PU = OFFPlug = 800A ST PU = 1200A In zone Fault Net RELT I = 0A
LT PU = 1 X Plug LT PU = 800A YES GF Tol =15%
LT TD = C-5 GF = OFF 0A PU Slope = SGF 2ndTD BandEnvelope/Standard = 1/ANSI ST PU = 1.5 X LTPU ZSI I PU = 6.5 X Trip Rating Plug
Override = 65000A ST TD = Min STDB 5th STDB Net I PU I = 10400ASensor = 1600A ST Slope = OFF OFF RELT I PU = OFF
Plug = 1600A ST PU = 2400A Net RELT I = 0A
LT PU = 1 X Plug LT PU = 1600A IPU ZSI = ON GF Tol =15%
LT TD = C-6 GF = OFF 0A PU Slope = OFF MinimumTD BandGF ZSI =--------------------------------------------> Slope = SGF 3rdTD Band
CB1-Fault CB2 Restrained Response
CB1 - 60Hz
CB2 - 60Hz
Two separate settingsRestrainedUnrestrainedLower CB restrained and unrestrained should be =, though in theory, unrestrained is not required
23GEM. Valdes – Train the Expert – Arc Flash Lesson 3September 16, 2008
GTU Curve, CB1 & CB2
0.01
0.10
1.00
10.00
100.00
1000.00
100 1,000 10,000 100,000 1,000,000Amperes
Se
co
nd
s
0.01
0.10
1.00
10.00
100.00
1000.00
100 1,000 10,000 100,000 1,000,000
IZSI Provides Flexibility: Protection & selectivity simultaneously
Add ZSI, slope ZSI, Instantaneous ZSI and you have best in class selectivity and best in class arc flash protection
24GEM. Valdes – Train the Expert – Arc Flash Lesson 3September 16, 2008
Arc Flash Performance depends on clearing time.
Trying to keep primary protection clearing fast without sacrificing selectivity
GTU Curve, CB1 & CB2
0.01
0.10
1.00
10.00
100.00
1000.00
100 1,000 10,000 100,000 1,000,000Amperes
Se
co
nd
s
CB1 - 1600ACB1 LTPU 1600ACB1 STPU 6400ACB1 IPU 21600ACB1 RELT IPU 999999ACB1 HSIOC 69892ACB1 0A GFNEC GF 3000A/1SGF1-0ACB2 - 3200AGF20A GF2Txfrmr inrushfuseR+ CB =GF 150% 2S480V Xfmr FLAHRC1HRC2HRC3HRC4IbfI arcing
Constant Energy line
Envelope/Standard = Envelope 1/ANSI ST PU = 4 X LTPU I PU = 13.5 X Trip Rating PlugOverride = 65000A ST TD = 3rd STDB Net I PU I = 21600A
Sensor = 1600A ST Slope = OFF RELT I PU = OFFPlug = 1600A ST PU = 6400A In zone Fault Net RELT I = 0A
LT PU = 1 X Plug LT PU = 1600A NO GF Tol =15%LT TD = C-8 GF = OFF 0A PU Slope = SGF 2ndTD Band
Envelope/Standard = 3/ANSI ST PU = 3 X LTPU ZSI I PU = 9 X Trip Rating PlugOverride = 100000A ST TD = Min STDB 6th STDB Net I PU I = 28800A
Sensor = 3200A ST Slope = OFF OFF RELT I PU = OFFPlug = 3200A ST PU = 9600A Net RELT I = 0A
LT PU = 1 X Plug LT PU = 3200A IPU ZSI = ON GF Tol =15%
LT TD = C-10 GF = OFF 0A PU Slope = OFF MinimumTD BandGF ZSI =--------------------------------------------> Slope = SGF 3rdTD Band
CB1-Fault CB2 Restrained Response
HRC 2 for 480V, Solidly Grounded, Gap = 32mm (Swgr), Working Distance = 24" (610mm), Arc type = In a Box, Arcing Current (Ia) plotted = 42.9kA-36.4kA for 100kA bolted fault current (Ibf)
CB1 - 60Hz
CB2 - 60Hz
Selectivity & Arc Flash
EntelliGuard® TU Trip Unit