Brisk Air Penguin High Performance High Efficiency
Transcript

•Brisk Air

•Penguin

•High Performance

•High Efficiency

PENGUIN low profile COOL ONLY

HEATPUMP

15,000 BTU

13,500 BTU

11,000 BTU

Pre-installed

Heat Strip Option

Pre-installed Controls Option

9” Height

Analog CCC

Non-Ducted Manual

BRISK AIR/PENGUIN Heat Pumps 59146- Manual or

Analog Only.

- Operates down

to 40 degrees.

59136 –Comfort

Control Only

- Operates down

to 32 degrees.

630 series Penguins

Air Conditioning Cycle

Note: Heat is

removed from the

inside air and is

released to the

outside air.

Pressure Temperature Chart Temperature,

Degrees F R22 Pressure

(PSIG) R410A

Pressure (PSIG)

Temperature, Degrees F

R22 Pressure (PSIG)

R410A Pressure

(PSIG)

15 38 70 80 144 235

20 43 78 85 156 254

25 49 87 90 168 274

30 55 97 95 182 295

35 62 107 100 196 317

40 69 118 105 211 340

45 76 130 110 226 364

50 84 142 115 243 390

55 93 155 120 260 417

60 102 170 125 278 446

65 111 185 130 297 476

70 121 200 135 317 507

75 132 217 140 337 540

UPPER UNIT

CAPACITORS

CONDENSOR

EVAPORATOR

BLOWER MOTOR

COMPRESSOR

Refer to DATA TAG 1. Model # 2. Product # 3. Serial #

PG. 33

Amp Draw Per Temperature

Compressor Amps Temperature at AC Outdoor Coil

10.1 Amps 75 Degrees

11.1 Amps 85 Degrees

12.1 Amps 95 Degrees

13.1 Amps 105 Degrees

14.1 Amps 115 Degrees

15.1 Amps 125 Degrees

Design specifications of all Air Conditioners, 95 degrees at AC (outdoor coil),

80 degrees inside, 50% humidity and exactly 115 Volt AC

PG. 33

Degree Split (Differential) A simple test to see if the Unit is operating to Industry Standards

RETURN AIR

DISCHARGE

* Look for an 18-20 degree split * * Must be 70°F or warmer * * Take Humidity into consideration *

PG. 33

Heat Pump Operation

Note: A Heat Pump

is designed to

remove heat from

the outside air and

release it to the

inside air.

Troubleshoot Freeze-Ups

Blocked Duct Loose Cold Control

Reduced

Air Flow

PG. 26

Air leaks can cause Freeze-Ups

PG. 26

Freeze-Ups cont. Items to check when a freeze up occurs:

• RECURCULATION OF COLD AIR

• AIR FLOW (damaged coil, blocked ducts, dirty, filters, etc.)

• Low Charge on Compressor

Note: It is rare that a freeze up is occurring because of a low charge on the compressor.

• Also make sure that the Cold Control is located in the right position and is within specifications.

• Make sure to ask the customer if the freeze-ups are happening at night (i.e., when temperatures are around 60°F.) ☺ Discuss

PG. 26

COLD CONTROL (Freeze sensor) Old Style New Style

PG. 25

CHECK CONTINUITY Used on roof top air

conditioners ONLY.

(If used with a Heat Pump, it will cause premature shut off of the compressor)

Normally OPEN

CLOSED when temperatures are below 45° F +/- 4.

Switch will OPEN at 65° F +/- 5.

PG. 25

COMPRESSOR

CHECK FOR SHORT TO CASE

CHECK FOR OPEN WINDINGS

PG. 23

COMPRESSOR To check for OPEN WINDINGS

1. Disconnect all power and turn

all switches to the “OFF”

position.

2. Disconnect 3 leads going to

compressor (C, R, S).

3. Check for continuity between

all terminals.

4. There SHOULD be continuity.

To check for SHORT to CASE

1. Same as above, but to the

case of compressor.

2. You should NOT have

continuity.

PG. 23

OVERLOAD PROTECTOR

PG. 23

Use an ohmmeter to

check for continuity

through the overload

device. If no continuity is

found and the compressor

is hot, allow 15 to 20

minutes for the

compressor to cool. If a

repeat of this test still

shows the overload to be

open, it is defective and

requires replacement.

NOTE: On some units the overload is an internal

component of the compressor and is non-replaceable.

Condenser Coil

What is the problem with this air conditioner?

Penguin Foam Kit • Installed on Older

Models

• Some New Units have the foam installed on the shroud. • Symptom – High Amps, Tripping Breakers • The foam makes an air tight seal which forces the air through the condenser – Air will travel the path of least resistance if foam is missing, compressed or installed improperly. Plastic Housing

See Bulletin A30-7A Note: If the foam is installed on the shroud and you are getting high amps/breakers tripping, remove foam and call Warranty Department to order foam kit part# 3312081.000. Install Foam Kit on Unit – NOT the shroud.

It is okay to have foam on shroud – only if experiencing problems does it need to be replaced.

BLOWER MOTOR

1. Check for open

windings in the

motor through

the 6-pin wire

harness.

2. Check for a

short to the motor

case through the

6-pin wire

harness.

PG. 23

CAPACITORS

1. Discharge Capacitors

2. Check continuity with

analog meter or

Microfarad’s with a

digital meter.

WARNING:

Capacitors

are rated at

370 Volts AC.

Identification

located on

capacitor.

PG. 22

START CAPACITOR AND PTCR’S PTCR

PTCR

Start Capacitor

PG. 22

REVERSING VALVE / SOLENOID COIL

The reversing valve is the heart of a heat pump. It changes the

direction of the refrigerant flow through the coils, and changes the

system from cooling to heating and vice versa.

PG. 26

265 OHMS +/- 10%

465 OHMS +/- 10%

Out Door Temperature Sensor

The Change-over thermostat is

a capillary tube/bellows-type

switch. Its function is to shut

the compressor and fan off by

opening the neutral side when

outside temperatures are 40

degrees +/- 10%.

•Used on Heat Pumps Only •Analog and Mechanical

To Test a Change-Over Thermostat

1. Verify temperature at capillary tube.

2. If temperatures are above 45○ F,

continuity SHOULD be between 2 and

3 and NOT between 2 and 1.

3. If temperatures are below 40○ F,

continuity SHOULD be between

terminals 2 and 1 and should NOT be

between 2 and 3.

PG. 17

ANALOG THERMOSTAT Ground Activated

= GROUND

= FAN (LOW)

= FAN (HIGH)

= FURNACE

= COOL (COMPRESSOR)

/ = +7.5

= OPTIONAL HEAT

STRIP/HEAT PUMP

PG. 17/18

ANALOG WIRING at Control Box

= GROUND

= FAN (LOW)

= FAN (HIGH)

= FURNACE

= COOL

(COMPRESSOR)

/ = +7.5

= OPTIONAL HEAT

STRIP/HEAT PUMP

/ = FURNACE (2)

= +12 VDC

• BLACK = -12 VDC

Note: If any of the Low Voltage wires from control box goes to

ground ( ), it SHOULD activate that function.

Verify circuits are being completed through the control box

Never use a volt

meter when

checking a

completed circuit.

Using a 115 Volt AC

incandescent bulb, check from

terminal 5 --( Common)

to other terminals to determine

if a particular circuit is being

completed.

5

PG. 19/20

TIME DELAY

Delays the compressor start up for

2 ½ minutes.

Used when 115 VAC is interrupted

or if the thermostat is inadvertently

turned off and back on again

causing the compressor to quick

cycle under load.

Used to help prevent breaker

tripping and to extend compressor

and compressor relay life.

COMFORT CONTROL CENTER Fully digital system creates up to four

different climate zones from one centralized location.

Operate heat pump, AC, fan and other functions for each zone, up to 4 zones.

Intel-set technology lets you easily change settings; internal memory retains all settings--you never need to reprogram after a power failure.

Sure-Touch control panel features user-friendly, intuitive controls; LCD panel provides readouts in degrees F or C.

AGS system monitors power supply/demand and automatically starts on-board generator as needed.

PG.

18

COMMUNICATION CABLE

A standard telephone cable will NOT work You must have straight through polarity

The communication cable

supplies the thermostat

with 12 VDC. It will also

supply 12 VDC to all other

Zones.

PG. 19

Symptom- No display lights Check Solder joints above the

communication cable

connection on the back side of

the thermostat.

NEGATIVE

POSITIVE

Top Right and

Bottom Left

You should see +12 VDC. If you see – 12 VDC, you

have reversed polarity on communication cable.

PG. 19

SYSTEM RESET

PG. 19

Turn the ON/OFF switch to the “OFF” position.

Simultaneously depress and hold the “MODE” & “ZONE” buttons while

turning the ON/OFF switch to the “ON” position.

“FF” should appear on the display until the “MODE” & “ZONE” buttons are

released.

If “EE” appears when the buttons are released, perform the reset again. If

“EE” keeps displaying, there is a communication problem.

When a dip switch is turned on or off after initial configuration, a reset must

be performed to allow the Comfort Control Center to recognize the updated

change.

Any time a component is added or removed, it is best to perform a reset .

There are no repairs to be done on the Comfort Control Center.

DIP SWITCHES For proper operation,

the dip switches

MUST be set.

1. Heat Strip

2. Zone 2

3. Zone 3

4. Zone 4

5. Furnace

6. Differential

7. Stage

8. Gen Start

PG. 30

Dip Switches have to be set on each control board for the options to be

available to the customer. Heat Strip- If the zone selected has a heat strip, dip switch #1 needs to be

turned on.

Dip switches 2, 3, and 4 are for each additional air conditioner (Zone).

Note: All “ZONE” dip switches OFF, defaults to zone 1.

Furnace- If the air conditioner has a furnace connected, dip switch # 5 needs to be turned on.

Differential- If there is an excessive temperature swing in the furnace mode, dip switch # 6 needs to be turned on. This will cut the temperature swing in HALF.

Stage- Allows Dual-Basement air conditioners to operate off of 1 control board. Dip switch # 7 needs to be turned on.

Gen Start- On vehicles equipped with AGS kit the vehicle generator will automatically start when any zone calls for cooling and will shut down when all zones have reached set point. Dip Switch #8 needs to be turned on.

PG. 30

Temperature Sensors

Ambient

Temperature

Sensor

Remote Temperature

Sensor

Cold Control

PG. 24/25

To test the Ambient Temp Sensor 1. Disconnect 115 VAC.

2. Remove the RED 2-pin

connector from the control

board.

3. Set your meter to OHMs.

4. Probe across both wires to

get an OHMs value.

5. Once you have the value,

compare the reading to the

chart.

6. Check each wire to Chassis

ground. Note: You will still

get a resistance reading if

one wire has gone to ground.

The ambient sensor is the outside air temperature sensor and

used on CCC Heat Pumps Only. Allows the Heat Pump to

operate down to 32°F.

PG. 25

To test the Cold Control 1. Disconnect 115 VAC.

2. Remove the BLUE 2-pin

connector from the control

board.

3. Set your meter to OHMs.

4. Probe across both wires to

get an OHMs value.

5. Once you have the value,

compare the reading to the

chart.

6. Check each wire to Chassis

ground. Note: You will still

get a resistance reading if

one wire has gone to ground.

•Used on both air conditioners and heat pumps. When the

temperature of the coil reaches the freezing point the

compressor will stop operation and the fan will automatically go

to high speed.

PG. 25

To test the Sensor 1. Disconnect 115 VAC.

2. Remove the 2-pin

connector from the control

board.

3. Set your meter to OHMs.

4. Probe across both wires to get

an OHMs value.

5. Once you have the value,

compare the reading to the

chart.

6. Check each wire to Chassis

ground. Note: You will still get

a resistance reading if one wire

has gone to ground.

PG. 24