Fire Pumps
Bristol: A History & Future.In 1971, seven emirates joined forces to create the United Arab Emirates, with the goal of becoming a growing leader on an international scale. The UAE’s focus has always been the safety of its land and people, BRISTOL was established in support of that same vision.
BRISTOL FIRE ENGINEERING, part of the Concorde – Corodex Group, is the leading fire-fighting and fire protection manufacturer in the Middle East and has been unsurpassed in innovative fire-fighting solutions for more than 44 years.
We have been steadfast in our developments and have grown to become pioneers in the industry for unmatched quality and dependability, longstanding commitment and unwavering dedication. Our headquarters and manufacturing facility started in the UAE’s Emirate of Dubai, producing world-class fire-fighting systems and equipment in cooperation with international know-how and technology with a grand vision to expand globally.
We strive to continue to adopt the highest international and national standards in line with the UAE’s goal to become the safest country in the world.
BRISTOL was one of the first fire-fighting companies in the Middle East to receive an ISO 9001 certification, placing great emphasis on achieving local and international approvals on product certifications such as Kite Mark, LPBC, UL listing, and FM approval. Moreover, Bristol is certified to ISO 14001 and OHSAS 18001.
We focus on innovation by means of continual research and development of advanced fire-fighting solutions, ensuring we not only meet, but exceed the demands of our rapidly changing market.
For decades, we have been proudly supplying various government entities and sectors such as the oil and gas, commercial, and industrial sectors across the globe with world-class equipment and services.
BRISTOL has been serving Middle Eastern, African, Asian, and European markets for more than four decades with a vision to expand further.
Paving the road towards safety for more than four decades, and counting: BRISTOL.
3
Table of Contents:
Firer Pumps - End Suction 4
Fire Pump - Horizontal Split Case 8
Fire Pumps - Vertical Turbine 12
4
Fire Pumps - End SuctionBristol End Suction Pumps are designed according to NFPA 20 for Fire Fighting applications. This pump is designed with latest technology and has premium components for fast maintenance and absoluteefficiency.
5
Performance Range
- Capacity : From 50 GPM up to 1000 GPM
- Head : From 40 MTR up to 160 MTR
Features
- Available in electric motor driven or engine driven configuration- Dynamic balanced impellers- Available in clockwise or counter-clockwise rotation to simplify pump- room layout- UL Certificate No. : Ex16459
Material Construction
- Shaft : Stainless Steel- Casing : Ductile Iron- Impeller : Bronze- Shaft Seal : Packing Gland-Immersion Graphite
General Information for Centrifugal Fire Pumps, End Suction
Model Rated Capacity(GPM) Size (In) Rated Net Pressure
Range (psi)Approx Speed
(RPM)
IS32 – 200 50 2 x 1 ¼ 62-95 2950
IS32 – 200 50 2 x 1 ¼ 55-85 2800
IS32 – 260 50 2 x 1 ¼ 113 - 130 2950
IS32 – 260 100 2 x 1 ¼ 103 - 125 2950
IS50 – 320H 50 2½ x 2 103-167 2600
IS50 – 320H 50 2½ x 2 88-142 2400
IS50 – 320H 100 2½ x 2 178-298 3500
IS50 – 320H 100 2½ x 2 132-210 2950
IS50 – 320H 100 2½ x 2 119-189 2800
IS50 – 320H 100 2½ x 2 102-166 2600
IS50 – 320H 100 2½ x 2 87-141 2400
IS50 – 320H 150 2½ x 2 177-296 3500
IS50 – 320H 150 2½ x 2 132-209 2950
IS50 – 320H 150 2½ x 2 118-188 2800
IS50 – 320H 150 2½ x 2 99-165 2600
IS50 – 320H 150 2½ x 2 84-140 2400
IS50 – 320H 200 2½ x 2 173-296 3500
IS50 – 320H 200 2½ x 2 127-209 2950
IS50 – 320H 200 2½ x 2 113-188 2800
IS65 – 320H 200 3 x 2½ 159-290 3500
IS65 – 320H 200 3 x 2½ 108-201 2950
IS65 – 320H 200 3 x 2½ 97-181 2800
IS65 – 320H 200 3 x 2½ 104-158 2600
IS65 – 320H 200 3 x 2½ 88-133 2400
IS65 – 320H 250 3 x 2½ 157-290 3500
IS65 – 320H 250 3 x 2½ 107-201 2950
IS65 – 320H 250 3 x 2½ 97-181 2800
IS65 – 320H 250 3 x 2½ 102-155 2600
IS65 – 320H 250 3 x 2½ 85-131 2400
IS65 – 320H 300 3 x 2½ 155-289 3500
IS65 – 320H 300 3 x 2½ 107-201 2950
Model Rated Capacity(GPM) Size (In) Rated Net Pressure
Range (psi)Approx Speed
(RPM)
IS65 – 320H 300 3 x 2½ 97-181 2800
IS65 – 320H 300 3 x 2½ 98-152 2600
IS65 – 320H 300 3 x 2½ 82-128 2400
IS80 - 260 400 4 x 3 105-139 2950
IS80 - 260 500 4 x 3 101-137 2950
IS80 – 320H 300 4 x 3 159-203 2950
IS80 – 320H 300 4 x 3 143-183 2800
IS80 – 320H 400 4 x 3 158-203 2950
IS80 – 320H 400 4 x 3 142-183 2800
IS100 – 320H 400 5 x 4 123-158 2950
IS100 – 320H 400 5 x 4 110-142 2800
IS100 – 320H 400 5 x 4 98-172 2600
IS100 – 320H 400 5 x 4 83-147 2400
IS80 – 320H 450 4 x 3 157-203 2950
IS80 – 320H 450 4 x 3 140-182 2800
IS100 – 320H 450 5 x 4 122-158 2950
IS100 – 320H 450 5 x 4 110-142 2800
IS100 – 320H 450 5 x 4 98-172 2600
IS100 – 320H 450 5 x 4 83-147 2400
IS80 – 320H 500 4 x 3 155-202 2950
IS80 – 320H 500 4 x 3 136-182 2800
IS100 – 320H 500 5 x 4 122-158 2950
IS100 – 320H 500 5 x 4 110-142 2800
IS100 – 320H 500 5 x 4 97-172 2600
IS100 – 320H 500 5 x 4 82-147 2400
IS100 – 320H 750 5 x 4 119-147 2950
IS100 – 320H 750 5 x 4 104-131 2800
IS100 – 320H 750 5 x 4 89-166 2600
IS100 - 260 750 5 x 4 113-139 2950
IS100 - 260 1000 5 x 4 104-131 2950
6
Characteristics
Discharge
Wear Ring
Impeller
Casing
Suction
Wear Ring
Lantern Ring
Gland Cover
Shaft Sleeve
Shaft
Bearing (Outboard)
Bearing (Inboard)
Description
- Discharge- Wear Ring- Bearing (Ind. & Out.)- Packing Gland- Shaft- Gland Cover- Lantern Ring- Impeller- Suction- Casing
: Vertical Discharge on the center line: Bronze - Is standard for the certified ANSI pumps Radially split casing with flanged connections: Deep Grooved Ball Bearing: Immersion Graphite Rope: Stainless Steel - Sleeve shaft as standard for extended seal life: Bronze - to house a gland seal: Bronze - to keep packing lubricated: Bronze - Enclosed impeller design ensures maximum efficiency: Horizontal End Suction ANSI 150# or 300# flange drilling is available based on material selection: Ductile Iron 65-45-12 - Heavy-duty power frame
7
Dimensions
Pump - Table of Dimension in (mm)
Flange - Table of Dimension in (mm)
MODEL A B C D E F Ff G H L M N P Ø j K
IS32 - 200 80 360 160 183.5 70 100 50 267 49 110 140 190 240 22.225 4.7x4.7x32
IS32 - 260 100 360 180 228 95 125 65 267 49 110 140 250 320 22.225 4.7x4.7x32
IS50 - 320H 125 470 225 285.6 95 125 65 342 79.4 110 140 280 345 28.575 6.35x6.35x44.5
IS65 - 320H 125 470 225 284 120 160 80 342 79.4 110 140 315 400 28.575 6.35x6.35x44.5
IS80 - 260 125 470 200 280 120 140 80 342 79.4 110 140 315 400 28.575 6.35x6.35x44.5
IS80 - 320H 125 470 250 317 120 160 80 342 79.4 110 140 315 400 28.575 6.35x6.35x44.5
IS100 - 260 140 470 225 280 120 160 80 342 79.4 110 140 315 400 28.575 6.35x6.35x44.5
IS100 - 320H 142 470 250 316 120 160 80 342 79.4 110 140 315 400 28.575 6.35x6.35x44.5
Model
Suction Discharge
Ø ID Ø OD Ø dp Ø ID Ø OD Ø dp
4 holes Ø19
On PCD 120
4 holes Ø16
On PCD 90
4 holes Ø19
On PCD 120
4 holes Ø16
On PCD 90
4 holes Ø19
On PCD 133
4 holes Ø19
On PCD 120
4 holes Ø19
On PCD 152
4 holes Ø19
On PCD 140
8 holes Ø19
On PCD 190
4 holes Ø19
On PCD 152
8 holes Ø19
On PCD 190
4 holes Ø19
On PCD 152
8 holes Ø19
On PCD 190
8 holes Ø19
On PCD 190
8 holes Ø19
On PCD 216
8 holes Ø19
On PCD 190IS100 – 320H 127 228.6 101.6 228.6
IS80 - 320H 101.6 228.6 76.2 190.5
IS100 – 260 127 254 101.6 228.6
IS65 – 320H 76 190 63.5 178
IS80 – 260 101.6 228.6 76.2 190.5
IS32 – 260 50.8 152 32 117
IS50 – 320H 63.5 178 50.8 152
50.8 152 32 117IS32 – 200
8
Fire Pumps - Horizontal Split CaseBristol Split Case Pump is a single stage, non-self-priming, centrifugal volute pump with radial suction and discharge port. This pump has a horizontal pump shaft with the impeller placed in the middle of the shaft and with self contained combination bearing housing and seal chamber on both sides of the impeller. Without disturbing the motor or pipe-work, the split case construction enables the pump casing to be dis-mantled in the horizontal plane along the drive shaft. Removal and dismantling of the internal pump parts e.g. bearings, wear rings, impeller and shaft seal can then take place.
9
General Information for Centrifugal Fire Pumps, Split
Features
- In line Pump- Double Suction- Low NPSH- Low axial load on the shaft- Double Volute- Improved efficiency (Overall higher efficiency)- Low radial load on the shaft- Low axial and radial loads extends wear ring, seal and- bearing life, minimize vibration and provides quit operation- Easy service bearing and packing gland can be changed- without removing the top casing half- UL Certificate No. EX16089
Performance Range
Capacity
Head
Material Construction
Shaft
Casing
Impeller
Shaft Seal
: From 300 GPM up to 1500 GPM
: From 50 MTR up to 150 MTR
: Stainless Steel
: Ductile Iron
: Bronze
: Packing Gland D - Immersion Graphite Rope
Model Rated Capacity(GPM) Size (In) Rated Net Pressure
Range (psi) Approx Speed (RPM)
BSP-125-270 300 5 x 3 117 – 159 2950
BSP-125-270 400 5 x 3 115 – 157 2950
BSP-125-270 450 5 x 3 114 - 155 2950
BSP-125-270 500 5 x 3 112 - 154 2950
BSP-150-310 500 6 x 4 129 - 222 2950
BSP-150-310 750 6 x 4 125 - 223 2950
BSP-150-310 1000 6 x 4 117 - 218 2950
BSP-200-290 1000 8 x 5 155 – 194 2950
BSP-200-290 1250 8 x 5 147 – 191 2950
BSP-200-290 1500 8 x 5 138 - 184 2950
10
Characteristics
Description
Casing - (Ductile Iron) - Upper and Lower half bolted and dowelled to provide perfect alignment. Upper half casing can be removed forinspection, without disturbing bearings or alignment.
Shaft Sleeve - (Stainless Steel) - Protect the shaft against corrosion and wear, extends through gland for maximum shaft protection.
Impeller - (Bronze) - Enclosed, double suction, Cast in one-piece and balance to minimize the thrust and to ensure longer bearing life. Locked in position by shaft sleeve.
Stuffing Box - (Ductile Iron) - Designed to accept packing with lantern ring. Internally drilled liquid passage in upper-half casing provideslubrication to the packing area.
Shaft - (Stainless Steel) - Large - diameter, precision-machined, high strength steel shaft for maximum strength with minimum shaft deflection.
Bearking - (SKF) - High speed capability and low friction bearing.
Wear Ring - (Bronze) - A sacrificial component installed to inhibit fluid from re-circulating back to suction from the discharge.
Lantern Ring - (Stainless Steel) - A perforated hollow ring that receives relatively cool, clean liquid. Distribute uniformly around the shaftto provide lubrication and cooling.
Packing Gland - (Immersion Graphite) - flexibility allows the shaft to run freely as well as leak proof.
Stuffing Box (Gland) - (Bronze) - to press the packing gland into the seal area through bolts.
Plug - (Stainless Steel).
Bearing Housing - (Cast Iron).
Flushing Pipe - (Stainless Steel) - Line from discharge of the pump and recirculated through an pressure regulating valve into the gland.
Water Singer - (Oil Resistant Rubber).
Pump Coupling (ASTM No.35).
Lantern Ring
Flushing Pipe
Packing Gland
Casing (Lower)
Plug
Impeller
Bearing
Upper Casing
Shaft Sleeve
Bearing Housing
Shaft
Pump Coupling
Water Singer
Bearing
Wearing Ring
11
Dimensions
Split Case - Table of Dimension in (mm)
Flange - Table of Dimension in (mm)
Model A B C Cs E F G H L M N P KØ j
BSP-125-270 300 300 315 140 270 70 140 82 410 320 336 443 35 10x10x78
BSP-150-310 330 330 355 170 345 80 200 91.5 470 320 345 345 35 10x10x85
BSP-200-290 370 370 400 200 310 80 225 110 530 390 366 517.5 45 14x14x108
Model
Suction Discharge
Ø ID Ø OD Ø dp Ø ID Ø OD Ø dp
8 holes Ø22
on PCD 235
8 holes Ø22
on PCD 168
12 holes Ø26
on PCD 270
8 holes Ø22
on PCD 200
12 holes Ø26
on PCD 330
8 holes Ø22
on PCD 235
BSP-150-310 170.7 318 116.1 254
BSP-200-290 221.5 381 143.8 279
BSP-125-270 143.8 279 90.7 210
12
Fire Pumps - Vertical TurbineBristol Vertical Turbine centrifugal pump is developed and fabricated by our company, according to NFPA20. This pump is used for any underground water source where the water level is below the pump suction, it’s Impeller remains submerged with the water tank at all times.
13
Features
- Performance and hydrostatic tests
- In compliance with NFPA 20, FM approved
- Materials of construction: cast iron, bronze fitted
- Sealing arrangement: packing with flushing
- Modular construction: assures complete flexibility in selecting a pump
- Pre-engineered standard components
- Space-saver design: requires minimum floor space
- Static suction lift: permissible by NFPA 20 where water source is- located below ground
- Open line shaft: water-lubricated bowl and line-shaft bearings
- Stuffing Box (Gland) - (Bronze) - to press the packing gland into the seal area through bolts
- Bolted bowl: bowls and suction bell are bolted together, allowing easier disassembly
- Dynamic balanced impellers: secured to the shaft with steel locking collets
- Discharge gauge connection
Performance Range
Capacity
Head
Material Construction
Shaft
Casing
Impeller
: From 500 GPM up to 5000 GPM
: From 50 MTR up to 200 MTR
: Stainless Steel
: Ductile Iron
: Bronze
Where the fire protection water source is located below ground or deck level, the best technical pumping solution is the vertical suspended multi stage turbine pump. With this type of unit the impellers are fully immersed in the water maintaining prime at all times. The pumps are driven by vertical electric motors or by diesel engines through a right angle gearbox.
14
Cross Sectional
Typical Services
- Cooling Water- Seawater and River Water Intake- Industrial Process Pump- Utility Circulating Water- Condenser Circulating Water Pumps- Fire Service- Reclaimed Water
No. Type Capacity (m3 /h)(GPM) Speed Pressure (Kpa (psi))
1 BVP 350 115 (500) 1490 310 - 1605 (45 - 233)
2 BVP 350 170 (750) 1490 285 - 1480 (41 - 215)
3 BVP 350 170 (750) 1790 450 - 1560 (65 - 226)
4 BVP 350 227 (1000) 1790 405 - 1427 (59 - 208)
5 BVP 450 285 (1250) 1490 295 - 1545 (43 - 224)
6 BVP 400 285 (1250) 1490 365 - 1510 (53 - 219)
7 BVP 450 340 (1500) 1490 285 - 1505 (41 - 215)
8 BVP 400 340 (1500) 1490 330 - 1570 (48 - 228)
9 BVP 450 340 (1500) 1790 425 - 1700 (62 - 248)
10 BVP 400 340 (1500) 1790 530 - 1590 (77 - 231)
11 BVP 450 454 (2000) 1490 275 - 1415 (40 - 205)
12 BVP 450 454 (2000) 1790 405 - 1620 (59 - 236)
13 BVP 500 568 (2500) 1490 750 - 1500 (109 - 218)
14 BVP 650 680 (3000) 1490 635 - 1270 (92 - 184)
15 BVP 650 795 (3500) 1490 605 - 1210 (88 - 176)
16 BVP 650 908 (4000) 1490 600 - 1200 (87 - 174)
17 BVP 650 1022 (4500) 1490 580 - 1740 (84 - 252)
18 BVP 650 1135 (5000) 1490 560 - 1680 (81 - 243)
Performance Parameters of Table
Gear Head
Discharge Head “Ductile Iron”
Head Shaft Coupling - Stainless Steel
Upper Casing w/ Bushing - ASTM A48
Bushing - Vesconite Plastic
Shaft Sleeve - Stainless Steel
Casing Bowl - Cast Iron
Wearing Ring - Stainless Steel
Impeller - Bronze
Suction Assembly - Carbon Steel
Strainer - Stainless Steel
Discharge Pipe Assembly - AISI 1020
Bearing Spider w/ Bushing - ASTM A48
Column Pipe Assembly - AISI 1020
Shaft - Stainless Steel
Line Shaft Coupling - Stainless Steel
Bearing Spider w/ Bushing - ASTM A48
Column Pipe Assembly - AISI 1020