Quickly and easily ribbonized Applications • Building Interconnections • Data Centers and Central Offices • Anywhere MTP®/MPO connections can be used • High Density Interconnects • 40gbit and 100gbit Ethernet Architecture Innovative bonding pattern SPIDERWEB RIBBON ® 1 2 F i b e r S i m p l e x 2 4 F i b e r S i m p l e x Patent Pending
Transcript

12 Fiber Simplex

Quickly and easily ribbonized

Applications• Building Interconnections• Data Centers and

Central Offices• Anywhere MTP®/MPO

connections can be used• High Density Interconnects• 40gbit and 100gbit

Ethernet Architecture

Innovative bonding pattern

SPIDERWEB RIBBON®

12 Fiber Simplex

24 Fiber Simplex

Patent Pending

BRO-04009 7.20.17

Specifications

CORE SIZE/FIBER TYPE ISO

MAXIMUM ATTENUATION(DB/KM)

OVERFILL LAUNCHMIN. BANDWIDTH

(MHZ•KM)EMBc

(MHZ•KM)

GIGABIT ETHERNET MIN. LINK DISTANCE

(METERS)

10 GIGABIT ETHERNET MIN. LINK DISTANCE

(METERS)850 NM 1300 NM 1550 NM 850 NM 1300 NM 850 NM 1300 NM 850 NM 1300 NM

(L) 50μm OM3 - Bend Insensitive Laser-Link 300

OM3 3.0 1.2 N/A 1500 500 2000 1000 550 300 —

(C) 50μm OM4 - Bend Insensitive Laser-Link 550

OM4 3.0 1.2 N/A 3500 550 4700 1040 550 550 —

(K) AFL Bend Insensitive SMF (ITU G.657.A) OS2 N/A 0.5 0.5 N/A N/A N/A N/A 5000 N/A 10000

Tested to meet or exceed EIA/TIA 568-B3 / Telcordia GR-409-CORE

Mechanical Data

CABLETYPE

PLENUM LSZHFIBER

COUNT

NOMINAL DIAMETER WEIGHT TENSION

LBS (N)BENDING RADIUS

INCHES (CM)AFL NO.

SP/ZP SE/ZE INCHES (MM)

LBS/1000FT (KG/KM) INSTALLATION LONG

TERM INSTALLATION LONG TERM

SimplexSP012301#0B SE012301#0B 12 0.12 (3.0) 6.0 (9.0) 22 (100) 7 (30) 1.8 (4.5) 1.2 (3.0)SP024301#0B SE024301#0B 24 0.12 (3.0) 5.3 (8.0) 22 (100) 7 (30) 1.8 (4.5) 1.2 (3.0)

Temperature Specifications

TEMPERATURE RANGE

OPERATING/INSTALLATION STORAGE

0°C to +70°C -40°C to +75°C

Interconnect Premise Microcore Cables are designed for MTP®/MPO terminations and meet the interconnect standards of Telcordia GR-409. To minimize the cable’s diameter, multiple colored 250 µm fibers and aramid strands are packaged in a high performance PVC jacket. Fiber counts of 12 and 24 fibers are available (contact AFL for higher fiber counts).

SWR® is a bonded fiber design allowing for either a highly efficient ribbonizing application or for individual fiber break-outs. This flexibility allows for the application of a single cable type to cover a diverse set of applications. High-density round designs allow for the most efficient use of space and materials to combine for a cost-effective solution.

Features

• Plenum NFPA 262 Rated • lSZH cables compliant to IEC60332, IEC60754, and IEC61034 • Tested to meet or exceed GR-409-CORE • Compliant to Directive 2002/95/EC (RoHS) • 3.0 mm Outer Diameter for Round Boot 12-count MTP®/MPO connectors • 3.0 mm Outer Diameter for Round Boot 24-count MTP®/MPO connectors • Exceptional skew performance

Applications

• Building Interconnections• Data Centers and Central Offices• Anywhere MTP®/MPO connections

can be used• High Density Interconnects• 40gbit and 100gbit Ethernet Architecture

www.AFLglobal.com | 1.800.235.3423

SPIDERWEB RIBBON®

# Please specify outer jacket/sub-unit color when ordering (see below)

Please specify fiber type when ordering (see specifications)

1=Blue2=Orange3=Green4=Brown5=Slate6=White

7=Red8=Black9=YellowA=VioletB=RoseC=Aqua

Interconnect Premise MicroCore® Cable with SWR® Technology