Page 1: Broag Pressurisation  · PDF fileCompact wall mounted and free standing pressurisation units, ... common fault, volt free contact (Boiler interlock ... protection of the cylinder
Page 2: Broag Pressurisation  · PDF fileCompact wall mounted and free standing pressurisation units, ... common fault, volt free contact (Boiler interlock ... protection of the cylinder

1

Compact wall mounted and free standing pressurisation units, utilising the latest microprocessor control. For use on sealed heating and cooling systems, offering accurate control and reliability.

♦ Digital equipment comes with a 4 digit bright LED display with scrolling messages including pump operation and alarm modes.

♦ Single or twin pump configurations.♦ Complete with integral water break tank utilising an AB airgap and a WRAS approved float valve.♦ Twin pump equipment operates as cyclic duty – standby with automatic changeover.♦ Internal alarm with mute function.♦ Security password protected.♦ Auto resetting low water detection, for pump protection.♦ Auto resetting high and low pressure alarm.♦ Digital pressure setpoint with adjustable differential.♦ Flood protection through a pump run limit timer.♦ Normally closed, common fault, volt free contact (Boiler interlock).♦ Normally open, individual volt free contacts for pump trip, high pressure, low pressure and sensor health.♦ All volt free contacts are rated for use with electrical supplies up to 230v with a maximum current draw of 5 amps.

♦ RS 485 Connectivity

♦ Hours run counter(per pump)

♦ 12 month service reminder

♦ Excessive start alarm (>3 times in 8 hours)

♦ Pump pulse option

(2 second pulse per pump

if inactive for 60 days)

♦ Fill system option(Not available on 13OD/23OD)

Broag P ressur i sa t i on equ ipment

Page 3: Broag Pressurisation  · PDF fileCompact wall mounted and free standing pressurisation units, ... common fault, volt free contact (Boiler interlock ... protection of the cylinder

2

Broag P ressur i sa t i on equ ipment

Page 4: Broag Pressurisation  · PDF fileCompact wall mounted and free standing pressurisation units, ... common fault, volt free contact (Boiler interlock ... protection of the cylinder

3

Page 5: Broag Pressurisation  · PDF fileCompact wall mounted and free standing pressurisation units, ... common fault, volt free contact (Boiler interlock ... protection of the cylinder

4

Remtank Unvented Cyl inders Expansion Vessel suppl ied with k i ts

Maximum e

Using

Water at 10 C expands approx. 0.5%Water at 60 C expands approx. 1.7%

Using a safety factor of 25% water expands between 10 C and 60 C @ 1.5%Using the vessel efficiency calculated as above = 42.8%1000 Ltr x 1.5% = 15 Ltr expansion; 15 / 42.8% = 35 (35 Ltr vessel)800 Ltr x 1.5% = 12 Ltr expansion; 12 / 42.8% = 28 (35 Ltr vessel)500 Ltr x 1.5% = 7.5 Ltr expansion; 7.5 / 42.8% = 17.5 (24 Ltr vessel)

(NOTE: The above sizing relates to Cylinder water content ONLY. Any additional system expansion should be calculated independently.)

o

o

o o

Page 6: Broag Pressurisation  · PDF fileCompact wall mounted and free standing pressurisation units, ... common fault, volt free contact (Boiler interlock ... protection of the cylinder

5

Page 7: Broag Pressurisation  · PDF fileCompact wall mounted and free standing pressurisation units, ... common fault, volt free contact (Boiler interlock ... protection of the cylinder

6

1. Flexcon floor standing digital flexfiller.2. Flexcon Uni-fil filling set. (Must be disconnected after filling system).3. Flexcon expansion vessel sited on heating system return.4. Flexvent Super automatic air vent-mounted vertically where air naturally collects.5. PS Vessel (Intermediate for heating) or (Buffer for chilled systems).6. Safety valve and tundish sited on top or above the Boiler or plant.7. Flamcovent clean de-aerator - in flow from the boiler before the pump.8. Supastor indirect calorifier.9. PSD pressure step degasser.

Page 8: Broag Pressurisation  · PDF fileCompact wall mounted and free standing pressurisation units, ... common fault, volt free contact (Boiler interlock ... protection of the cylinder

7

R e m t a n k S S D i re c t u n v e n t e d c y l i n d e r s

Select ion Guide

*In areas with a high concentration of

Chlorine (200 ppm or above) additional

protection of the cylinder is required

with an electronic anode.

This is an optional extra and is not

reflected in the pricing.

Property Type Direct SizeBedsit

1/2 beds with 1 bath / shower

3 beds with 1 bath / shower

4 beds with 1 bath / shower

2/3 beds with 2 baths / showers

4/5 beds with 2 baths / showers

Sports club, Restaurant etc.

Hotels, Schools etc

120

150 or 180

180 or 210

210

210 or 250

300 or 500

800 or 1000

Technical Speci f icat ion Direct ( including Ki t )

Volume (Nominal)

1750

606

42

342

3/4”

7 bar

95ºC

6 bar

2

3 kW

101 mins

144 mins

35 Ltr

977

555

20.8

141

3/4”

7 bar

95ºC

6 bar

2

3 kW

34 mins

40 mins

35 Ltr

1167

555

23.5

174

3/4”

7 bar

95ºC

6 bar

2

3 kW

46 mins

65 mins

35 Ltr

1347

555

26.5

207

3/4”

7 bar

95ºC

6 bar

2

3 kW

56 mins

80 mins

35 Ltr

1569

555

33

243

3/4”

7 bar

95ºC

6 bar

2

3 kW

69 mins

98 mins

35 Ltr

1759

555

35.5

286

3/4”

7 bar

95ºC

6 bar

2

3 kW

80 mins

114 mins

35 Ltr

1823

734

59

559

3/4”

7 bar

95ºC

6 bar

2

3 kW

159 mins

256 mins

50 Ltr

Direct Height (mm)

Diameter (mm)

Weight (Dry kg)

Weight (Normal Full kg)

T&P Tapping

T&P Pressure Setting

T&P Temperature Setting

Expansion Relief Setting

Electrical Heater Quantity

Electrical Heater Rating (Each)

Re-heat Times (2x3 kW)

Heat Up Times (From Cold)

Expansion Vessel

120 litres 150 litres 180 litres 210 litres 250 litres 300 litres 500 litres

Direct unvented cylinders for potable water installations

Fluid Flow SequenceMains Water Isolation Valve (Not Supplied)

3 bar Pressure Reducing Valve

Safety Group (6 bar Expansion Relief Valve c/w Non Return Valve)

Expansion Vessel

Drain Valve (Not Supplied)

Stainless Supastor Hot Water Calorifier

Pressure Reducing

Valve Pre-SetSafety Group c/w

Non Return Valve

6 bar Relief

Tundish Combined Temperature

& Pressure Relief Valve

Factory Fitted

7 bar / 95oC

Expansion Vessel

120 - 500 3/4” Connection

800 - 1000 1” (Floor Standing Model)

2 off 3kW 230v/50Hz

Immersion Heater

VesselsDirect vessels

can be supplied

without kits as

a storage vessel

800 litres 1000 litres

1960

950

100

900

3/4”

7 bar

95ºC

6 bar

2

3 kW

260 mins

400 mins

80 Ltr

2360

950

115

1115

3/4”

7 bar

95ºC

6 bar

2

3 kW

318 mins

512 mins

80 Ltr

Insulation is interlocked polystyrene to allow for inspection of cylinder if required.

N.B. The expansion vessel provided is sized to accommodate a total hot water system volume of 1.25 times the calorifier size. It is theresponsibility of the installer to verify that this vessel size is appropriate for the installation and add additional vessels if required.

Page 9: Broag Pressurisation  · PDF fileCompact wall mounted and free standing pressurisation units, ... common fault, volt free contact (Boiler interlock ... protection of the cylinder

8

R e m t a n k S S D i re c t u n v e n t e d c y l i n d e r s

120 to 300 litre 500 to 1000 litre

1750

606

47

1” BSP (M)

282

1532

1444

Top Centre

1” BSP (M)

977

555

51

1” BSP (M)

289

749

644

Top Centre

1” BSP (M)

1167

555

51

1” BSP (M)

289

939

834

Top Centre

1” BSP (M)

1347

555

51

1” BSP (M)

289

1119

1014

Top Centre

1” BSP (M)

1569

555

51

1” BSP (M)

289

1341

1236

Top Centre

1” BSP (M)

1759

555

51

1” BSP (M)

289

1531

1426

Top Centre

1” BSP (M)

1823

734

52

1” BSP (M)

317

1517

932

1517

1” BSP (M)

Height A (mm)

Diameter B (mm)

Cold Water C (mm)

Cold Water Connection

Immersion D (mm)

T&P Valve J (mm)

Immersion K (mm)

DHW Flow J

DHW Connection

120 litres 150 litres 180 litres 210 litres 250 litres 300 litres 500 litresDirect Direct Direct Direct Direct Direct Direct

Volume (Nominal)

Technical Speci f icat ion Connect ions800 litres 1000 litres

Direct Direct

1960

950

338

1 1/2”BSP (M)

343

1603

1103

1603

1 1/2”BSP (M)

2360

950

338

1 1/2”BSP (M)

343

2003

1103

2003

1 1/2”BSP (M)

Secondary Flow

(120 - 300)

(500 - 1000)

Page 10: Broag Pressurisation  · PDF fileCompact wall mounted and free standing pressurisation units, ... common fault, volt free contact (Boiler interlock ... protection of the cylinder

9

R e m t a n k S S I n d i re c t u n v e n t e d c y l i n d e r s

Select ion Guide

*In areas with a high concentration of

Chlorine (200 ppm or above) additional

protection of the cylinder is required

with an electronic anode.

This is an optional extra and is not

reflected in the pricing.

Property Type Indirect SizeBedsit

1/2 beds with 1 bath / shower

3 beds with 1 bath / shower

4 beds with 1 bath / shower

2/3 beds with 2 baths / showers

4/5 beds with 2 baths / showers

Sports club, Restaurant etc.

Hotels, Schools etc

120

150 or 180

180 or 210

210

210 or 250

300 or 500

800 or 1000

Indirect unvented cylinders for potable water installations

Fluid Flow SequenceMains Water Isolation Valve (Not Supplied)

3 bar Pressure Reducing Valve

Safety Group (6 bar Expansion Relief Valve c/w Non Return Valve)

Expansion Vessel

Drain Valve (Not Supplied)

Stainless Supastor Hot Water Calorifier

Pressure Reducing

Valve Pre-SetSafety Group c/w

Non Return Valve

6 bar Relief

Tundish

2 Port Valve For Use

With The IMIT

Thermostat

Controlling The

Primary Flow (Boiler)

Water To The Coil

Combined Temperature &

Pressure Relief Valve

7 bar / 95oC

3kW 230v/50Hz

Immersion Heater

IMIT Combined

Thermostat &

Safety Relay

Technical Speci f icat ion Indirect ( including Ki t )

Volume (Nominal) 120 litres 150 litres 180 litres 210 litres 250 litres 300 litres 500 litres 800 litres 1000 litres

Indirect Height (mm)

Diameter (mm)

Weight (Dry kg)

Weight (Normal Full kg)

T&P Tapping

T&P Pressure Setting

T&P Temperature Setting

Expansion Relief Setting

Electrical Heater Quantity

Electrical Heater Rating (Each)

Re-heat Times (82º Supply)

Heat Up Times (From Cold)

Max. Primary Pressure (Coil)

Primary Flow Rate (Boiler L/min)

Primary Resistance (mbar)

976

555

23

143

3/4”

7 bar

95ºC

6 bar

1

3 kW

17 mins

29 mins

16 bar

25

64.9

464

24.7

35 Ltr

1167

555

27

177

3/4”

7 bar

95ºC

6 bar

1

3 kW

20 mins

31 mins

16 bar

34

141.9

493

26.2

35 Ltr

1347

555

30

210

3/4”

7 bar

95ºC

6 bar

1

3 kW

25 mins

37 mins

16 bar

34

141.930

493

26.2

35 Ltr

1569

555

38

248

3/4”

7 bar

95ºC

6 bar

1

3 kW

22 mins

27 mins

16 bar

42

324.8

627

33.4

35 Ltr

1759

555

41

291

3/4”

7 bar

95ºC

6 bar

1

3 kW

24 mins

30 mins

16 bar

42

354.6

684

36.4

35 Ltr

1960

950

110.5

911

3/4”

7 bar

95ºC

6 bar

2

3 kW

31 mins

40 mins

16 bar

92

1287.0

1695

90.2

80 Ltr

2360

950

124.5

1245

3/4”

7 bar

95ºC

6 bar

2

3 kW

40 mins

49 mins

16 bar

92

1287.0

1695

90.2

80 Ltr

Continuous Output (mbar)

Coil Rating kW

Expansion Vessel

1750

606

50

350

3/4”

7 bar

95ºC

6 bar

1

3 kW

28 mins

35 mins

16 bar

42

520

985

52.4

35 Ltr

1823

734

68.5

569

3/4”

7 bar

95ºC

6 bar

1

3 kW

31 mins

38 mins

16 bar

67

509.8

1059

56.4

50 Ltr

Insulation is interlocked polystyrene to allow for inspection of cylinder if required.

Expansion Vessel

120 - 500 3/4” Connection

800 - 1000 1” (Floor Standing Model)

N.B. The expansion vessel provided is sized to accommodate a total hot water system volume of 1.25 times the calorifier size. It is theresponsibility of the installer to verify that this vessel size is appropriate for the installation and add additional vessels if required.

Page 11: Broag Pressurisation  · PDF fileCompact wall mounted and free standing pressurisation units, ... common fault, volt free contact (Boiler interlock ... protection of the cylinder

10

R e m t a n k S S I n d i re c t u n v e n t e d c y l i n d e r s

1750

606

47

1” BSP (M)

412

47

722

1”BSP (M)

802

1” BSP (F)

1225

1532

N/A

Top Centre

1”BSP (M)

976

555

51

1” BSP (M)

419

51

379

1” BSP (M)

518

1” BSP (F)

627

749

N/A

Top Centre

1”BSP (M)

1167

555

51

1” BSP (M)

419

51

379

1”BSP (M)

518

1” BSP (F)

721

939

N/A

Top Centre

1”BSP (M)

1347

555

51

1” BSP (M)

419

51

379

1”BSP (M)

518

1” BSP (F)

845

1119

N/A

Top Centre

1”BSP (M)

1569

555

51

1” BSP (M)

419

51

554

1”BSP (M)

634

1” BSP (F)

984

1341

N/A

Top Centre

1”BSP (M)

1759

555

51

1” BSP (M)

419

51

579

1”BSP (M)

659

1” BSP (F)

1108

1531

N/A

Top Centre

1”BSP (M)

1823

734

52

1” BSP (M)

932

312

832

1”BSP (M)

1142

1” BSP (F)

952

1517

N/A

1517

1”BSP (M)

Height A (mm)

Diameter B (mm)

Cold Water C (mm)

Cold Water Connection

Immersion D (mm)

Primary Flow F (mm)

Primary Return E (mm)

Primary Connection

DHW Return G (mm)

Secondary Return Connection (mm)

Thermostat H (mm)

T&P Valve J (mm)

Immersion K (mm)

DHW Flow J

DHW Connection

120 litres Indirect

150 litres Indirect

180 litres Indirect

210 litresIndirect

250 litres Indirect

300 litres Indirect

500 litres Indirect

800 litres Indirect

1000 litres Indirect

1960

950

50

1.1/2”BSP (M)

343

338

1038

1”BSP (M)

1238

1.1/2” BSP (F)

1103

1603

1103

1603

1.1/2”BSP (M)

2360

950

338

1.1/2”BSP (M)

343

338

1038

1”BSP (M)

1238

1.1/2” BSP (F)

1103

2023

1103

2003

1.1/2”BSP (M)

Volume (Nominal)

Technical Speci f icat ion Connect ions

120 to 300 litre 800 to 1000 litre500 litre

Secondary Flow

(120 - 300)

(500 - 1000)

Indirect unvented cylinders for potable water installations

Page 12: Broag Pressurisation  · PDF fileCompact wall mounted and free standing pressurisation units, ... common fault, volt free contact (Boiler interlock ... protection of the cylinder

11

Pressure Reducing

Valve Pre-SetTundish

2 Port Valve For Use With

The IMIT Thermostat

Controlling The Primary Flow

(Boiler) Water To The Coil

Combined Temperature &

Pressure Relief Valve

Factory Fitted 7 bar / 95oC

3kW 230v/50Hz

Immersion Heater

IMIT Combined

Thermostat &

Safety Relay

R e m t a n k S S S o l a r u n v e n t e d c y l i n d e r s

Technical Speci f icat ion SS Solar ( including Ki t )

Volume (Nominal) 250 litres 300 litres 500 litres 800 litres 1000 litres

Supastor Solar Height (mm)

Diameter (mm)

Weight (Dry kg)

Weight (Normal Full kg)

T&P Tapping

T&P Pressure Setting

T&P Temperature Setting

Expansion Relief Setting

Electrical Heater Quantity

Electrical Heater Rating (Each)

Primary Re-heat Times (82º Supply)

Primary Heat Up Times (From Cold)

Max. Primary Pressure (Coil)

Primary Flow Rate (Boiler L/M)

Primary Resistance (mbar)

1568

555

43

253

3/4”

7 bar

95ºC

6 bar

1

3 kW

22 mins

27 mins

16 bar

42

324.8

627

33.4

1750

606

55

355

3/4”

7 bar

95ºC

6 bar

1

3 kW

28 mins

35 mins

16 bar

42

520

985

52.4

1823

734

75.5

576

3/4”

7 bar

95ºC

6 bar

1

3 kW

31 mins

38 mins

16 bar

67

509.8

1059

56.4

1960

950

122.9

923.4

3/4”

7 bar

95ºC

6 bar

2

3 kW

31 mins

40 mins

16 bar

92

1287.0

1695

90.2

2360

950

136.9

1257.4

3/4”

7 bar

95ºC

6 bar

2

3 kW

40 mins

49 mins

16 bar

92

1287.0

1641

87.4Primary Coil Rating KW

Expansion Vessel

Primary Continuous Output (mbar)

210 litres

1754

555

46

296

3/4”

7 bar

95ºC

6 bar

1

3 kW

24 mins

30 mins

16 bar

42

354.6

684

36.4

Select ion Guide

*In areas with a high concentration of

Chlorine (200 ppm or above) additional

protection of the cylinder is required

with an electronic anode.

This is an optional extra and is not

reflected in the pricing.

Property Type Solar SizeBedsit

1/2 beds with 1 bath / shower

3 beds with 1 bath / shower

4 beds with 1 bath / shower

2/3 beds with 2 baths / showers

4/5 beds with 2 baths / showers

Sports club, Restaurant etc.

Hotels, Schools etc

120

150 or 180

180 or 210

210

210 or 250

300 or 500

800 or 1000

35 Ltr 35 Ltr 35 Ltr 50 Ltr 80 Ltr 80 Ltr

Insulation is interlocked polystyrene to allow for inspection of cylinder if required.

Fluid Flow SequenceMains Water Isolation Valve (Not Supplied)

3 bar Pressure Reducing Valve

Safety Group (6 bar Expansion Relief Valve c/w Non Return Valve)

Expansion Vessel

Drain Valve (Not Supplied)

Stainless Supastor Hot Water Calorifier

Expansion Vessel

120 - 500 3/4” Connection

800 - 1000 1” (Floor Standing Model)

Solar unvented cylinders for potable water installations

Safety Group c/w

Non Return Valve

6 bar Relief

N.B. The expansion vessel provided is sized to accommodate a total hot water system volume of 1.25 times the calorifier size. It is theresponsibility of the installer to verify that this vessel size is appropriate for the installation and add additional vessels if required.

Page 13: Broag Pressurisation  · PDF fileCompact wall mounted and free standing pressurisation units, ... common fault, volt free contact (Boiler interlock ... protection of the cylinder

12

R e m t a n k S S S o l a r u n v e n t e d c y l i n d e r s

Technical Speci f icat ion Connect ions

2360

950

338

1.1/2”BSP (M)

343

338

1038

1” BSP (M)

1238

1” BSP (F)

1103

2023

1103

2003

1.1/2”BSP (M)

1443

1853

1”BSP (M)

1103

1568

555

51

1” BSP (M)

881

51

379

1” BSP (M)

634

1” BSP (F)

1216

1341

N/A

Top Centre

1” BSP (M)

1098

1341

1”BSP (M)

289

1754

555

51

1” BSP (M)

834

51

379

1” BSP (M)

659

1” BSP (F)

1108

1531

N/A

Top Centre

1” BSP (M)

1288

1531

1”BSP (M)

289

1750

606

47

1” BSP (M)

1117

47

372

1” BSP (M)

774

1” BSP (F)

1225

1532

N/A

Top Centre

1” BSP (M)

1017

774

1”BSP (M)

282

1823

734

52

1” BSP (M)

932

312

832

1” BSP (M)

952

1” BSP (F)

952

1517

N/A

1517

1” BSP (M)

1077

1437

1”BSP (M)

558

1960

950

338

1.1/2”BSP (M)

343

338

1038

1” BSP (M)

1238

1” BSP (F)

1103

1603

1103

1603

1.1/2”BSP (M)

1193

1603

1”BSP (M)

1103

210 litresSolar

Height A (mm)

Diameter B (mm)

Cold Water C (mm)

Cold Water Connection

Immersion D (mm)

Primary Flow F (mm)

Primary Return E (mm)

Primary Connection

DHW Return G (mm)

DHW Return Connection (mm)

Thermostat H (mm)

T&P Valve J (mm)

Immersion K (mm)

DHW Flow J (mm)

DHW Connection

Solar Return L (mm)

Solar Flow J (mm)

Secondary Connection

Thermostat Primary Coil Pocket (mm)

250 litresSolar

300 litresSolar

500 litresSolar

800 litresSolar

1000 litresSolar

Volume (Nominal)

120 to 300 litre 500 litre 800 to 1000 litre

Secondary Flow

(120 - 300)

(500 - 1000)

Solar unvented cylinders for potable water installations

Page 14: Broag Pressurisation  · PDF fileCompact wall mounted and free standing pressurisation units, ... common fault, volt free contact (Boiler interlock ... protection of the cylinder

13

Wi r i n g d e t a i l s f o r a l l D i g i t a l P re s s u r i s a t i o n U n i t s

♦ Supply Voltage 230- v- Single Phase. ♦ Fuse Rating - 5 Amps ♦ Max Full Load Current - 4.5 Amps

• Under normal operation there is a permanent live feed back to the boiler, the water temperature is regulated by the operation of the motorised valve feeding the internal coil.

• To control the heating times, connect the electrical feed to the thermostat from the program or time clock (L).• When the Remtank Calorifier is at the desired temperature, the motorised valve will close and the boiler, itself, will register no demand

from the cylinder and shut down if appropriate.• Note: Control of hot water via Rematic 2945ck and Broag Priority Kits.• When using the Rematic 2945ck controller and Broag Priority Kits in conjunction with the supplied HWS immersion sensor, fit the

supplied brass pocket in the secondary return connection and connect immersion sensor into pocket, the secondary return connection should then be connected into the cold feed supply at the base of the calorifier between the safety group and the calorifier. Sensor wiring connections can be found in the boiler control wiring details.

• The 2 port valve must be wired as detailed in the diagrams above, with the electrical supply coming from the Priority Kit/Boiler controls.To ensure the correct operation of the Priority Kit set the control thermostat (connected to the 2 port valve) 10oC higher than the boiler or controller hot water temperature.

Page 15: Broag Pressurisation  · PDF fileCompact wall mounted and free standing pressurisation units, ... common fault, volt free contact (Boiler interlock ... protection of the cylinder

14

A s s e m b l y f o r D i re c t , I n d i re c t a n d S o l a r

1

1

2

2

3

3

4

4

5

5

6

6

A A

B B

C C

D D

Appendix 4

Stainless Supastor Direct Assembly

RJAC MC RJAC 25/05/2006 02/02/2006

Designed by Checked by Approved by Date

1 / 1 Edition Sheet

Date

400mm Maximum Length

400m

mM

inim

umLe

ngth

150mm Minimum Length

200mm Minimum Length

T&P TundishDrain Valve

(Not Supplied)

To Drain To Drain

Pressure Reducing ValveCold Water Inlet

Safety Group

Secondary Return(Anode Connection)

Hot Water Outlet

NOTE: The location of the Pressure Reducing Valve, Expansion Vessel, Safety Group and Drain Valve is flexible, as long as the distances shown and written instructions are followed.

This clause allows the Expasnion Vessel to be located above the Hot Water Calorifer / Cylinder.

1

1

2

2

3

3

4

4

5

5

6

6

A A

B B

C C

D D

Appendix 3

Stainless SupastorIndirect and Solar Assembly

RJAC MC RJAC 25/05/2006 02/02/2006

Designed by Checked by Approved by Date

1 / 1 Edition Sheet

Date

400mm Maximum Length

400m

mM

inim

umLe

ngth

150mmMinimum Length

Hot Water Outlet

Pressure Reducing ValveCold Water Inlet

T&P Tundish

200mm Minimum Length

Drain Valve(Not Supplied)

To Drain

To DrainSafety Group

Primary Return (Boiler)

Primary Flow (Boiler)

Secondary Return(Anode Connection)

NOTE: The location of the Pressure Reducing Valve, Expansion Vessel, Safety Group and Drain Valve is flexible, as long as the distances shown and written instructions are followed.

This clause allows the Expasnion Vessel to be located above the Hot Water Calorifer / Cylinder.