SCHOOL OF ARCHITECTURE, BUILDING & DESIGN
Modern Architecture Studies in Southeast Asia (MASSA) Research Unit
Bachelor of Science (Honours) (Architecture)
BUILDING SCIENCE 2
Project 2: Integration with Design Studio 5
NAME: YAP KAR JUEN
STUDENT ID: 0313737
TUTOR: MR.EDWIN
TABLE OF CONTENT
1.0 INTRODUCTION
2.0 LIGHTING
2.1 NATURAL DAYLIGHTING
2.1.1 DISCUSSION ROOM (2NDFLOOR)
2.1.2 BOARD GAME AREA
2.2 ARTIFICIAL LIGHTING
2.2.1 COMPUTER ROOM
2.2.2 CULTURAL FOOD MARKET
2.3 PSALI
2.3.1 DISCUSSION ROOM 2 (3RD FLOOR)
2.3.2 LIBRARIAN OFFICE
3.0 ACOUSTIC
3.1 SOUND PRESSURE LEVEL (External Noise)
3.2 REVEBERBERATION TIME, RT
3.2.1 DISCUSSION ROOM (2ND FLOOR
3.2.2 COMPUTER ROOM
3.3 SOUND REDUCTION LEVEL, SRL
3.3.1 DISCUSSION ROOM 1 (3RD FLOOR)
3.3.2 DISCUSSION ROOM 2 (3RD FLOOR)
4.0 REFERENCES
1.0 INTRODUCTION
This is an integration project with the Design Studio V project, the infill project
with community library. Located at Jalan Ipoh, Sentul, right next to the most busy
road
The aim of this project is to create an understanding of the principles of
lighting and acoustics in the context physical environment. It encompasses
daylighting and artificial lighting systems, also the strategies for internal and external
noise management and room acoustics.
Identification of 2 spaces which need both artificial lighting and 2 spaces
with day-lighting significance will be conducted. For acoustic, 2 spaces will be
identified to integrate external noises and 2 spaces to integrate internal noises. This
report consists of various calculations for lighting and acoustic system for the design
integration.
2.0 PLAN DRAWINGS
G FLOOR PLAN 1ST FLOOR PLAN
2ND FLOOR PLAN 3RD FLOOR PLAN
2.0 LIGHTING
2.1 NATURAL DAYLIGHTING
According to MS 1525, Daylight Factor distribution is as shown in Table 1 below:
Zone DF (%) Distribution
Very
Bright
>6 Very large with thermal and glare
problems
Bright 3 – 6 Good
Average 1 – 3 Fair
Dark 0 – 1 Poor
NOTE: The figures are average daylight factor for windows
without glazing. Tab: Daylight Factors and Distribution (Source: MS 1525, 2007)
2.1.1 DISCUSSION ROOM (2ND FLOOR)
The selected area is located at second floor, it is a room with full ceiling height
curtain glass panel, therefore no artificial lighting is needed.
DAYLIGHT FACTOR CALCULATION
Floor Area, m2 18.4
Area of fenestrations, m2 48.2
Area of skylight, m2 0
Daylight Factor (%) [EXPOSED AREA + AREA OF
SKYLIGHT] / FLOOR AREA
= [48.2+0] / 18.4
= 2.62
= 262% x 0.1
= 26.2%
NATURAL ILLUMINATION CALCULATION
ILLUMINANCE EXAMPLE
120, 000 lux BRIGHTEST SUNLIGHT
110, 000 lux BRIGHT SUNLIGHT
20, 000 lux SHADE ILLUMINATED BY ENTIRE CLEAR BLUE SKY, MIDDAY
1, 000 – 2, 000 lux TYPICAL OVERCAST DAY, MIDDAY
<200 lux EXTREME OF DARKEST STORM CLOUDS, MIDDAY
400 lux SUNRISE OR SUNSET ON A CLEAR DAY (AMBIENT
ILLUMINATION)
40 lux FULLY OVERCAST, SUNSET/SUNRISE
<1 lux EXTREME OF DARKEST STORM CLOUDS, SUNSET/RISE
E external = 20, 000 lux
DF =
26.2 =
E internal = 26.2 x 20 000 / 100
= 5240 lux
CONCLUSION
The second floor discussion room has a daylight factor of 26.2% and 5240 lux of
natural illumination. It fulfills the requirement the standard for a discussion room
according to MS1525. There will be no problems like glare and over heat in the
space. However, shading devices or double glazed low e glass can be used to
achieve better lighting and thermal comfort.
2.1.2 BOARD GAME AREA
The board game area is located at the ground floor. It is covered up with walls with
one curtain wall exterior exposing to the back lane. The curtain wall is at full height
and is wide enough to allow enough sunlight into the building.
DAYLIGHT FACTOR CALCULATION
Floor Area, m2 14.9
Area of fenestrations, m2 13.58
Area of skylight, m2 0
Daylight Factor (%) [EXPOSED AREA + AREA OF
SKYLIGHT] / FLOOR AREA
= [13.58+0] / 14.9
= 0.9114
= 91.14% x 0.1
= 9.11%
NATURAL ILLUMINATION CALCULATION
ILLUMINANCE EXAMPLE
120, 000 lux BRIGHTEST SUNLIGHT
110, 000 lux BRIGHT SUNLIGHT
20, 000 lux SHADE ILLUMINATED BY ENTIRE CLEAR BLUE SKY, MIDDAY
1, 000 – 2, 000 lux TYPICAL OVERCAST DAY, MIDDAY
<200 lux EXTREME OF DARKEST STORM CLOUDS, MIDDAY
400 lux SUNRISE OR SUNSET ON A CLEAR DAY (AMBIENT
ILLUMINATION)
40 lux FULLY OVERCAST, SUNSET/SUNRISE
<1 lux EXTREME OF DARKEST STORM CLOUDS, SUNSET/RISE
E external = 20, 000 lux
DF =
8.6 =
E internal = 9.11 x 20 000 / 100
= 1822 lux
CONCLUSION
The board game area has a daylight factor of 9.11% and 1822 lux of natural
illumination. The illumination level is much higher than the recommended
illumination of MS1525. Therefore sun shading device must be applied to disable
glaring and also thermal discomfort and board game area requires a lot of focus.
2.2 ARTIFICIAL LIGHTING
2.2.1 COMPUTER ROOM
The computer room is located at the second floor, it is a very tight space and is
surrounded by concrete, therefore there is no light permeability and usage and
placement of artificial light is crucial.
ACCORDING TO MS 1525, THE MINIMUM LIGHTING LEVEL REQUIRED FOR A LIBRARY IS
300 to 500.
TYPE OF FIXTURE FLUORESCENT TUBE
WITH REFLECTOR
TYPE OF LIGHT BULB
MATERIAL OF
FIXTURE
ALUMINIUM
PRODUCT BRAND &
CODE
F39W/TS/830/ECO
NOMINAL LIFE
(HOURS)
36000
WATTAGE RANGE
(W)
39
CRI 85
COLOUR
TEMPERATURE, K
3000
COLOUR
DESIGNATION
WARM WHITE
LUMENS 3500
COMPONE
NT
MATERIAL COLOUR SURFACE
FINISH
REFLECTA
NCE
VALUE
WALL PLASTER
WALL
WHITE MATTE 0.47
FLOOR CONCRETE
TILES
GREY MATTE 0.30
CEILING PLASTER GREY MATTE 0.47
UF TABLE BY LIGHTSBYLINEA
Source: http://lightsbylinea.com/index.php?route=information/information&information_id=10]
SAMPLE LLMF GRAPHIC FOR FLUORESCENT LIGHTING BY ETAP
Source:
http://www.etaplighting.com/uploadedFiles/Downloadable_documentation/documentatie/Maintenance%20f
actor%20whitepaper%20_EN.pdf
LUMEN METHOD CALCULATIONS
LOCATION LIBRARY
DIMENSION LENGTH (L) = 6.2 m
WIDTH (W) = 3.4 m
HEIGHT OF THE CEILING = 4.2 m
AREA (A) L X W = 6.2 X 3.4 = 12.24 m²
LUMINAIRES HEIGHT 4.2 m
MOUNTING HEIGHT (Hm) 4.2 – 0.8 = 3.4 m
RECOMMENDED
AVERAGE ILLUMINATION
LEVELS BY MS 1525 (E)
300 lux
REFLECTANCE VALUE CEILING: 0.47, FLOOR: 0.3, WALL: 0.47
ROOM INDEX
( )
( )
UTILISATION FACTOR FROM TABLE, UF = 0.26
MAINTENANCE FACTOR LUMINAIRE CATEGORY = D (IP2X)
TIME BETWEEN CLEANING (YEARS) = 0.5
TYPE OF LIGHT FLUORESCENT LAMPS WITH 1 BULBS,
3500 x 2 = 7000 lumen (F)
NUMBER OF LIGHT
REQUIRED
3 LUMINAIRES ARE NEEDED TO REACH THE
MINIMUM REQUIREMENT FOR MS 1525 = 300 lux.
SPACING TO HEIGHT
RATIO (SHR)
√
√
APPROXIMATE FITTINGS
LAYOUT/m
FITTINGS REQUIRED ALONG 21.2 m WALL;
= 3 ROWS
THEREFORE, APPROXIMATELY 3 x 2 = 6 LUMINAIRES
REQUIRED;
SPACING ALONG 3.4 m WALL;
3.4 / 2
= 1.7 m
FINAL FIXTURE LAYOUT
CONCLUSION
6 FLUORESCENT LAMPS ARE USED TO ACHIEVE MINIMUM OF 300 lux FOR THIS AREA,
ACCORDING TO MS 1525. THE WHOLE SPACE AREA IS WELL ILLUMINATED SO THAT
PERFORMANCE IS NOT WEAKENED DUE TO POOR LIGHTING AND COMFORT.
2.2.2 CULTURAL FOOD MARKET
Cultural food market is a space at the ground floor with concrete surrounding it
therefore artificial light is very crucial as well.
ACCORDING TO MS 1525, THE MINIMUM LIGHTING LEVEL REQUIRED FOR A LIBRARY IS
300 to 500.
TYPE OF FIXTURE LED DOWNLIGHT
TYPE OF LIGHT BULB
MATERIAL OF
FIXTURE
ALUMINIUM
PRODUCT BRAND &
CODE
RIO LDL801
NOMINAL LIFE
(HOURS)
50000
WATTAGE RANGE
(W)
44
CRI 80
COLOUR
TEMPERATURE, K
3000
COLOUR
DESIGNATION
WARM WHITE
LUMENS 3753
COMPONE
NT
MATERIAL COLOUR SURFACE
FINISH
REFLECTANCE
VALUE
WALL PLASTER
WALL
WHITE MATTE 0.47
FLOOR CONCRETE
TILES
GREY MATTE 0.30
CEILING PLASTER GREY MATTE 0.47
LUMEN METHOD CALCULATIONS
LOCATION LIBRARY
DIMENSION LENGTH (L) = 3.9 m
WIDTH (W) = 2.2 m
HEIGHT OF THE CEILING = 4.2 m
AREA (A) L X W = 3.9 X 2.2 = 8.58 m²
LUMINAIRES HEIGHT 4.2 m
MOUNTING HEIGHT (Hm) 4.2 – 0.8 = 3.4 m
RECOMMENDED
AVERAGE ILLUMINATION
LEVELS BY MS 1525 (E)
300 lux
REFLECTANCE VALUE CEILING: 0.47, FLOOR: 0.3, WALL: 0.47
ROOM INDEX
( )
( )
UTILISATION FACTOR FROM TABLE, UF = 0.26
MAINTENANCE FACTOR LUMINAIRE CATEGORY = D (IP2X)
TIME BETWEEN CLEANING (YEARS) = 0.5
TYPE OF LIGHT LED DOWNLIGHT
3573 Lumen
NUMBER OF LIGHT
REQUIRED
4 LUMINAIRES ARE NEEDED TO REACH THE
MINIMUM REQUIREMENT FOR MS 1525 = 300 lux.
SPACING TO HEIGHT
RATIO (SHR)
√
√
APPROXIMATE FITTINGS
LAYOUT/m
FITTINGS REQUIRED ALONG 3.9 m WALL;
= 3 ROWS
THEREFORE, APPROXIMATELY 3 x 2 = 6 LUMINAIRES
REQUIRED;
SPACING ALONG 2.2 m WALL;
2.2 / 2
= 1.1 m
FINAL FIXTURE LAYOUT
CONCLUSION
6 FLUORESCENT LAMPS ARE USED TO ACHIEVE MINIMUM OF 300 lux FOR THIS AREA,
ACCORDING TO MS 1525. THE WHOLE SPACE AREA IS WELL ILLUMINATED SO THAT
PERFORMANCE IS NOT WEAKENED DUE TO POOR LIGHTING AND COMFORT.
2.3.1 PSALI – Permanent Supplementary Artificial Light of
Interior ( Discussion room 2, 3rd floor)
According to MS1525, the minimum lighting level requirement for a gallery is 300 lux.
Type of luminaire used as showed below:
Lightify Surface Downlight W23, by OSRAM
Type of fixture Light Panel LED
Lamp luminous flux (lm) 2800
Rated colour temp (k) 4800
Colour rendering index >80
Beam angle -
Voltage (v) 220-240
Bulb finish Warm Light
Placement Ceiling
Location 3rd floor
Dimension of room (m) L: 4.1 W: 3.1
Total Floor Area A / sqm 4.1 x 3.1 = 12.71
Type of Lighting Fixture Ledvance Led Downlight
Lumen of Lighting Fixture / F (lm) 2800
Height of luminaire (m) 4.2
Height of Work Level (m) 0.8
Mounting Height / H (m) 3.4
Assumption of Reflectance Value Ceiling: 0.7
Wall: 0.5
Floor: 0.3
Room Index / RI (K)
( 4.1 x 3.1 ))
(4.1 + 3.1 ) 3.4
=0.52
Utilisation Factor / UF 0.27
Maintenance Factor / MF 0.8
Standard Illuminance (lux) 300 (Library)
Numbers of Lights Required N = 300 x 12.71
2800 x 0.6 x 0.8
= 2.837
= 2.837
√
Spacing of Height Ratio (SHR)
SHR
√
= 0.37
SHR = S / 2.7 = 0.37
S = 1.8
Fitting layout by approximately
(m)
Fittings required along 4.1 m wall,
4.1 / 0.999 = 4 rows
Fittings required along 3.1 m wall,
3.1 / 0.999 = 3 rows
Therefore, approximately 12 lightings required
RI= L x W
(L+W) x H)
N= E x A
F x UF x MF
Lighting Fixture Proposal
2.3.2 PSALI – Perrmanent Supplementary Artificial Light of
Interior
(Librarian Office )
According to MS1525, the minimum lighting level requirement for a office space is
300-500 lux.
Type of luminaire used as showed below:
LIGHT PANEL LED XXL 0, OSRAM
Lumen Method Calculation
Type of fixture Downlight
Lamp luminous flux (lm) 2600
Rated colour temp (k) 3000
Colour rendering index > 80
Beam angle -
Voltage (v) 220 - 240 v
Bulb finish Warm Light
Placement Ceiling
Location Workshop
Dimension of room (m) L: 4.1 W: 2.8
Total Floor Area A / (m2) 2.8 x 4.1 = 11.48 m2
Type of Lighting Fixture LEDVANCE POWER SPOT XXL
Lumen of Lighting Fixture / F (lm) 2600
Height of luminaire (m) 4.2
Height of Work Level (m) 0.8
Mounting Height ,H (m) 3.4
Assumption of Reflectance Value Ceiling :0.7
Wall :0.5
Floor : 0.3
Room Index / RI (K)
(2.8 x 4.1)
(2.8 + 4.1 ) 3.4
=0.5
Utilisation Factor / UF 0.27
Maintenance Factor / MF 0.8
Standard Illuminance (lux) 300
RI= L x W
(L+W) x H)
Numbers of Lights Required N = 300 x 11.48
2600 x 0.27 x 0.8
=6.13
=6
√
Spacing of Height Ratio (SHR)
SHR
√
= 0.4
SHR = S / 3.4 = 0.4
S = 1.36
Fitting layout by approximately
(m)
Fittings required along 5.4 wall,
= 4.1 / 1.36
= 3 rows
Fittings required along 5.4 wall,
= 3.1 / 1.36
= 2.28, 2 rows
Approximately 6 luminaires required
N= E x A F x UF x MF
Lighting Fixture Proposal