Flexi BTS Mounting Shield Quick Guide This guide can be used as quick reference for Flexi Mounting Shield (FMSA/FMSB) installations. Flexi Mounting Shield (FMSA/FMSB) is an outdoor shield for a stacked Flexi BTS. Used instead of the plastic front and rear covers, it provides protection against solar load, large insects and slight vandalism. In addition, you need Flexi Mounting Kit Floor/Wall/Pole (FMFA) in all installation cases. Flexi Mounting Shield 6U (FMSA) provides installation space for up to any two Flexi 3U modules and the plinth (6U in total). It is installed on a pole or wall. Flexi Mounting Shield 18U (FMSB) provides installation space for up to any six Flexi 3U modules and the plinth (18U in total). It is installed on the floor. Check the delivery Contents of deliveries 1 Clearances 2 Check the site Minimum clearances Fixing points Preparing modules for installation 3 Preparing modules for installation Mounting shields grounding principle 4 Mounting shields grounding principle Installing air guide plate 5 Install air guide plate Installing the mounting shields 6 Principle of lifting the mounting shields Installing FMSA 7 Installing FMSA/FMSB Installation check list 9 Installation check list Installing FMSB 8 FMSA FMSB
Transcript
Page 1: bts_flexi_mountshield_qg.pdf

DN70324723

DN70321153

Flexi BTS Mounting ShieldQuick Guide

This guide can be used as quick reference for Flexi Mounting Shield (FMSA/FMSB) installations.

Flexi Mounting Shield (FMSA/FMSB) is an outdoor shield for a stacked Flexi BTS. Used instead of the plastic front and rear covers, it provides protection against solar load, large insects and slight vandalism. In addition, you need Flexi Mounting Kit Floor/Wall/Pole (FMFA) in all installation cases.

Flexi Mounting Shield 6U (FMSA) provides installation space for up to any two Flexi 3U modules and the plinth (6U in total). It is installed on a pole or wall.

Flexi Mounting Shield 18U (FMSB) provides installation space for up to any six Flexi 3U modules and the plinth (18U in total). It is installed on the floor.

Check the delivery

Contents of deliveries1 Clearances2

Check the site

Minimum clearances

Fixing points

Preparing modules for installation

3

Preparing modules for installation

Mounting shields grounding principle

4

Mounting shields grounding principle

Installing air guide plate

5

Install air guide plate

Installing the mounting shields

6

Principle of lifting the mounting

shields

Installing FMSA

7

Installing FMSA/FMSB

Installation check list

9

Installation check list

Installing FMSB

8

FMSA FMSB

Page 2: bts_flexi_mountshield_qg.pdf

The information in this document is subject to change without notice and describes only the product defined in the introduction of this documentation. This document is not an official customer document and Nokia Siemens Networks does not take responsibility for any errors or omissions in this document. This document is intended for the use of Nokia Siemens Networks customers only for the purposes of the agreement under which the document is submitted. No part of this documentation may be used, reproduced, modified or transmitted in any form or means without the prior written permission of Nokia Siemens Networks. The documentation has been prepared to be used by professional and properly trained personnel, and the customer assumes full responsibility when using it. Nokia Siemens Networks welcomes customer comments as part of the process of continuous development and improvement of the documentation. The information or statements given in this documentation concerning the suitability, capacity or performance of the mentioned hardware or software products are given “as is” and all liability arising in connection with such hardware or software products shall be defined conclusively and finally in a separate agreement between Nokia Siemens Networks and the customer. IN NO EVENT WILL Nokia Siemens Networks BE LIABLE FOR ERRORS IN THIS DOCUMENTATION OR FOR ANY DAMAGES, INCLUDING BUT NOT LIMITED TO SPECIAL, DIRECT, INDIRECT, INCIDENTAL OR CONSEQUENTIAL OR ANY LOSSES SUCH AS BUT NOT LIMITED TO LOSS OF PROFIT, REVENUE, BUSINESS INTERRUPTION, BUSINESS OPPORTUNITY OR DATA, that might arise from the use of this document or the information in it. THE CONTENTS OF THIS DOCUMENT ARE PROVIDED “AS IS”. EXCEPT AS REQUIRED BY APPLICABLE MANDATORY LAW, NO WARRANTIES OF ANY KIND, EITHER EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE AND NON-INFRINGEMENT, ARE MADE IN RELATION TO THE ACCURACY, RELIABILITY OR CONTENTS OF THIS DOCUMENT. NOKIA SIEMENS NETWORKS RESERVES THE RIGHT TO REVISE THIS DOCUMENT OR WITHDRAW IT AT ANY TIME WITHOUT PRIOR NOTICE. This document and the product it describes are considered protected by copyrights and other intellectual property rights according to the applicable laws. The wave logo is a trademark of Nokia Siemens Networks Oy. Nokia is a registered trademark of Nokia Corporation. Siemens is a registered trademark of Siemens AG. Other product names mentioned in this document may be trademarks of their respective owners, and they are mentioned for identification purposes only. Copyright © Nokia Siemens Networks 2011. All rights reserved.

DN0951827 issue 02A

Approval Date 2012-10-24

- 2 -

Page 3: bts_flexi_mountshield_qg.pdf

Contents of deliveries1Delivery Contents Versions Codes

FMSA delivery Flexi Mounting Shield 6U (FMSA) 471614A2 x module grounding cable1 x grounding cable between the shield and plinth1 x upper bracket/lifting handle1 x pole/wall adapter3 x rubber cable entry7 x M8 screw3 x washer2 x cable tie point plate1 x air guide plate2 x Baffle knock out1 x Pawl1 x Nut for customer specific lock1 x FMSA/FMSB Quick Guide

FMSB delivery Flexi Mounting Shield 18U (FMSB) 471650A6 x module grounding cables1 x grounding cable between the shield and plinth3 x rubber cable entry6 x cable tie point plates1 x air guide plate1 x M5 nut for ground cable2 x Baffle knock out1 x Pawl1 x Nut for customer specific lock1 x FMSA/FMSB Quick Guide

Optional items Contents Versions CodesVMPB Pole Mounting Kit 469978AFPKA Flexi Pole Kit 471649AWLHA Lifting Handle Kit 469554A

- 3 -

Page 4: bts_flexi_mountshield_qg.pdf

Clearances2

Preparing modules for installation3

Minimum clearances

Mounting shields grounding principle4

FMSA fixing points

fixing pointso 10 mm

1

2

1. Remove the plinth rear stopper. 2. Prepare the casings for installation without modules and rear covers. Remove modules and rear covers as required.

Upper bracket

623 mm (24.5 in.)185 mm

(7.3 in.)

185 mm

(7.3 in.)

118.5 mm (4.7 in.)

558.

5 m

m (2

2.0

in.)

688

mm

(26.

3 in

.)

Lower bracket

40 mm (1.6 in.) for air intake

200 mm (7.9 in.) for maintenance from the back

fixing pointso 10 mm(0.4 in.)

600 mm (23.6 in.) for maintenance from the front

FMSB fixing points

149.5 mm (5.9 in.)

300 mm (11.8 in.)

40 mm (1.6 in.)for air intake

200 mm (7.9 in.) for maintenance from the back

fixing pointso 18 mm(0.7 in.)

359

mm

(14.

1 in

.)

Front side

106.5 mm (4.2 in.)

150 mm (5.9 in.) for cabling

600 mm (23.6 in.) for maintenance from the front

- 4 -

Page 5: bts_flexi_mountshield_qg.pdf

plinth

FMSA door

grounding cable

FMSA

bottom plate

FMSA

door

FMSA plinth

grounding cable

FMSB

bottom plate

FMSB plinth

grounding cable

plinth

Mounting shields grounding principle (cont.)4FMSA grounding to plinth

Installing air guide plate5FMSA installations: If there is less than 6U in the configuration, install the air guide plate on the casing of the top or outermost unit in the configuration.1. Remove the rearmost fixing studs.2. Install the air guide plate.3. Fix the fixing studs back in their place.

1

23 3

FMSB installations: If there is less than 18 U in the configuration, install the air guide plate on top of the topmost module casing.

1. Remove the rearmost fixing studs.

2. Install the air guide plate.

3. Fix the fixing studs back in their place.

NOTE: If using a full FMSA/FMSB configuration (6U/18U), the air guide plate is not needed.

NOTE: The appearance of the modules may vary depending on the product or module type.

TIP: Install the air guide plate to the topmost module before inserting the module into the mounting shield.

1

23

FMSB grounding to plinth

- 5 -

Page 6: bts_flexi_mountshield_qg.pdf

5

3

Installing FMSA7

5

3

1. Insert the plinth inside the mounting shield against the right-hand side wall.

2. Install the plinth to the mount-ing shield with the bottommost screws (3 x M8) first, secur-ing them with thread locking compound.

1

2

3a

8-10 Nm

Principle of lifting the mounting shields6

DN70321153

The FMSB can be carried by hand using the optional lifting handles (WLHA lifting han-dle kit 469554A).

The FMSA can be lifted by the lifting handle.

Lifting handle

Handle

NOTE: Do not lift the FMSB mounting shield with the modules inside.

- 6 -

Page 7: bts_flexi_mountshield_qg.pdf

3b

5. Remove the cover plates on the mounting shield wall, top, or bottom from the lead-throughs that you are going to use.

4

Installing FMSA (continued)7

6

3. Fix the mounting brackets.

a) Fix the upper mounting bracket to the mounting shield with four M8 screws, secur-ing them with thread locking compound.

b) Install the lower mounting bracket to the mounting shield with 3 x M8 screws and washers, securing them with thread lock-ing compound. Do not tighten the screws yet so that the bracket can be adjusted when installing the mounting shield on the wall or pole.

4. If there are two modules in the configuration, fix the empty casings to each other to make a stack of two casings.

6. Install the casing(s) on the plinth in the mounting shield.

- 7 -

5

Page 8: bts_flexi_mountshield_qg.pdf

8

11. Install the mounting shield on the wall or pole.

In pole installations, use the VMPB or FPKA Pole Mounting Kit.

11

11

9. Fix the cable tie points to the modules.

10. Fix the cables to the cable tie points with ties.

7

7. Insert the module core(s) into the casing(s).

8. Connect the module grounding cables first and after that any other internal cables.

- 8 -

NOTE: The examples show Flexi Multiradio WCDMA/LTE modules

10

9

Page 9: bts_flexi_mountshield_qg.pdf

Installing FMSA (continued)7

16. If there are unused cable entry holes, cover them with the rubber plugs.

17. Close the mounting shield door and install your padlock to the door handle (option 1) or install the customer-specific lock and close the mounting shield door (option 2).

12. Make sure that the site grounding cable is connected to the BTS site.

13. Connect the external cables. For instructions on how to connect the DC cable, see section Connecting external power feed in the Flexi

Multiradio GSM/EDGE or WCDMA/LTE installation manuals.

14. Insert the rubber cable entries to the lead-throughs you are going to use.

15. Complete the internal cabling, if necessary.

14

- 9 -

DN70324774

17

Page 10: bts_flexi_mountshield_qg.pdf

Installing FMSB81. Drill mounting holes on the floor.

2. Install the plinth on the FMSB floor and fix the FMSB to the floor with 4 bolts (M12).

2

3. Connect the site grounding cable.

4. Install the modules in a stack according to your con-figuration. See operating documentation or Flexi Mul-tiradio BTS Quick Guide for instructions.

5. Connect the module grounding cables first and after that any other internal cables.

NOTE: The appearance of the modules vary depending on the product or module type.

6

6. Fix the cable tie points to the modules.

- 10 -

NOTE: The examples show Flexi Multiradio WCDMA/LTE modules.

3

4

1

Page 11: bts_flexi_mountshield_qg.pdf

Installing FMSB (continued)87. Remove the cover plates from the lead-throughs that you are going to use.

8. Route the external cables through the lead-throughs.

9. Fix the cables to the cable tie points with ties.

10

89

11

DN70316525

10. Insert the rubber cable entries to the lead-throughs you are using.

11. If there are unused cable entry holes, cover them with the rubber plugs.

12. Close the mounting shield door and install your padlock to the door handle (option 1) or install the customer-specific lock and close the mounting shield door (option 2).

7

- 11 -

12

Page 12: bts_flexi_mountshield_qg.pdf

Installation check list9Perform these checks to make sure that the installation is complete:

Delivery is complete and undamaged.

Minimum clearances are met.

Grounding cables are connected.

Modules are installed as instructed.

Cable entries are installed.

Air guide plate is installed if not using a full configuration.

Internal cables are connected properly.

External cables are routed through the cable entries and connected properly.

Cables are tied to the cable tie points with cable ties.

If there are unused cable entry holes, they are covered with rubber plugs.

Mounting shield door is closed and padlock installed (option 1).

Customer-specific lock is installed and mounting shield door is closed (option 2).

- 12 -