+ All Categories
Home > Documents > BUILDING AUTOMATION AND CONTROL SYSTEMS SECTIONV

BUILDING AUTOMATION AND CONTROL SYSTEMS SECTIONV

Date post: 10-Jan-2022
Category:
Upload: others
View: 2 times
Download: 0 times
Share this document with a friend
27
4/19/2012 1 BUILDING AUTOMATION AND CONTROL SYSTEMS SECTION V WHAT HAT WILL ILL WE COVER OVER ? Controls Controls Basic Types Inputs & Outputs Technologies Technologies Pneumatic Electric DDC Terminology PID Controls Review Building Automation Systems for Energy Building Automation Systems for Energy Management Management Basic Functions Programs Review Section V - 2
Transcript
Page 1: BUILDING AUTOMATION AND CONTROL SYSTEMS SECTIONV

4/19/2012

1

BUILDING AUTOMATION AND CONTROLSYSTEMS

SECTION V

WWHATHAT WWILLILL WWEE CCOVEROVER ?? ControlsControls

Basic Types Inputs & Outputs TechnologiesTechnologies

Pneumatic Electric DDC

Terminology PID Controls Review

Building Automation Systems for Energy Building Automation Systems for Energy ManagementManagement Basic Functions Programs Review

Section V - 2

Page 2: BUILDING AUTOMATION AND CONTROL SYSTEMS SECTIONV

4/19/2012

2

BBASICASIC TTYPESYPES

Manual Manual SwitchesSwitchesDimmers

Open Loop AutomaticOpen Loop AutomaticTimer

Cl d L A t tiCl d L A t tiClosed Loop AutomaticClosed Loop AutomaticThermostatHumidistatDimmable Ballast w/Photosensor

Section V - 3

BASIC FEEDBACK CONTROL SYSTEM

SET POINT RC

CONTROLLER

RC

T

CONTROLLEDDEVICE

SENSOR

ACTUATOR

AIR FLOW

HEATING COIL

Section V - 4

Page 3: BUILDING AUTOMATION AND CONTROL SYSTEMS SECTIONV

4/19/2012

3

BBASICASIC TTYPESYPES

Two Position Two Position The system is either OFF or ON (gas furnace). Accomplished with a relay whose contacts are either Accomplished with a relay whose contacts are either

open or closed, or a valve whose stem position is either open or closed.

Proportional Proportional A variation from the set point produces a proportional

movement in the actuator. Pneumatic controls vary the air pressure. Electric controls use a potentiometer (a type of

variable resistor).

Section V - 5

BBASICASIC IINPUTSNPUTS & O& OUTPUTSUTPUTS

Binary or Digital (D)Binary or Digital (D) Signal with two states or positions which can be

incremental (on-off, day-night, open-closed, occupied-unoccupied, series of 1’s & 0’s)

Analog (A)Analog (A) Signal can be monitored or controlled through a

f i i l (range of positions or values (0 to 50o C, 20 to 35 kPa, 0 to 10 VDC,4 to 20 milliamps)

Section V - 6

Page 4: BUILDING AUTOMATION AND CONTROL SYSTEMS SECTIONV

4/19/2012

4

Input ExamplesInput ExamplesAnalogAnalog DigitalDigital

Outside Air Temp. SensorAnalog Input

Low Temp. DetectorDigital Input

End SwitchDigital Input

Duct Smoke DetectorDigital Input

LANDIS & GYR

Room Temperature SensorAnalog Input

High Pressure DetectorDigital Input

Smoke Detector

Section V - 7

Input Points

Inputs & OutputsInputs & Outputs

pTemperature Relative HumidityFlow PressureStatus or Proof Air Quality

AIAI

AI / DIAI / DIAI / DIAI / DI

AIAIAIAIAIAI

Output PointsMotors for Pumps / Fans ValvesLights Dampers

DODO AOAODODO AOAOLights Dampers

Variable Speed Drives Lighting Contactors(or digital)

DODODODO AOAO

AOAO

Section V - 8

Page 5: BUILDING AUTOMATION AND CONTROL SYSTEMS SECTIONV

4/19/2012

5

Inputs & OutputsInputs & Outputs

1.VFD Start/Stop

2.VFD Speed Signal

DOAO

Variable Air Volume Variable Air Volume SystemSystem

5.Static Press

4.High Static Cutout

3.Air Flow AIDI AI

Section V - 9

BBASICASIC TTECHNOLOGIESECHNOLOGIES

PneumaticPneumatic

ElectricElectric

Direct Digital Control (DDC)Direct Digital Control (DDC)

Section V - 10

Page 6: BUILDING AUTOMATION AND CONTROL SYSTEMS SECTIONV

4/19/2012

6

PPNEUMATICNEUMATIC CCONTROLSONTROLS Use clean, dry, oil-free compressed aircompressed air to operate the control system. Have been used in many HVAC applications.

M ain A ir L ine

H ot W aterSupply

Air Com pressorC ontroller

A nalog Signal

B ranch A ir L ine

HC

O utside A ir

Supply A ir Sensor

H eatingC oil

Supply Fan

A nalog Signal

H ot W ater V alve

Section V - 11

PPNEUMATICNEUMATIC CCONTROLSONTROLS

AdvantagesAdvantages Are well understood by many designers and most

maintenance people maintenance people. Are inherently proportional and very reliable. Were relatively inexpensive in the past.

DisadvantagesDisadvantages Not very precise. Typically required frequent calibration. Pneumatic control algorithms are hard to change.

(typically pre-set by manufacturer)

Section V - 12

Page 7: BUILDING AUTOMATION AND CONTROL SYSTEMS SECTIONV

4/19/2012

7

EELECTRICLECTRIC CCONTROLSONTROLS

Can be analog electric or electronic controls. Use a variable, but continuous, electrical voltage or electrical voltage or

currentcurrent to operate the control system. Transmit signals

quickly and accurately.

Section V - 13

EELECTRICLECTRIC CCONTROLSONTROLS

AdvantagesAdvantages Can be very accurate and very stable. Do not require field calibration and are drift free if Do not require field calibration, and are drift-free, if

good quality sensors are used. Relatively easy to implement proportional plus

integral (PI) control electronically.

DisadvantagesDisadvantages Difficult to interchange parts easily because of the g p y

many different systems. Do not interface directly with our digital computers

Section V - 14

Page 8: BUILDING AUTOMATION AND CONTROL SYSTEMS SECTIONV

4/19/2012

8

DDIRECTIRECT DDIGITALIGITAL CCONTROLSONTROLS Use electrical pulseselectrical pulses to send signals. Interface directly with microprocessors, directly &/or via the

internet using TCP/IP.

Section V - 15

DDIRECTIRECT DDIGITALIGITAL CCONTROLSONTROLS

AdvantagesAdvantages Algorithms can be adjusted relatively easily after

installation Precise Precise No controller drift, recalibration is normally not

necessary Cost effective (similar to electronics market)

DisadvantagesDisadvantages Possibly not well understood by O&M staff Possibly not well understood by O&M staff Different communication protocols, interface

standards, and internal logic are typically complex (BACNET-ASHRAE 135-2008; and Lonworks – LonmarkCorporation; are both addressing these interface problems)

Section V - 16

Page 9: BUILDING AUTOMATION AND CONTROL SYSTEMS SECTIONV

4/19/2012

9

WWEBEB BBASEDASED EENERGYNERGY IINFORMATIONNFORMATION

ANDAND CCONTROLONTROL SSYSTEMSYSTEMS

TCP/IP is Transmission Control Protocol/Internet Protocol Internet Explorer, Netscape Navigator, Mozilla Firefox all take

TCP/IP iTCP/IP input Many submeters now have data accumulators that have URL

addresses, and send data by TCP/IP over Local Area Networks This data will come into your PC in standard spread sheet format

for you to use as you like You can make charts, graphs, tables, etc in Excel or other

common SS programs You now have your own web based energy information system And it doesn’t cost you a fortune. Save your money for the really

fancy analysis and diagnostic systems that many companies can provide to you

Section V - 17

CCONTROLONTROL AALGORITHMSLGORITHMS

PID Controls P is proportional I is integral I is integral D is derivative

Controls are usually P, PI or PID PID is considered the best of this group Newer control algorithms are:

Fuzzy logic Learning systems Self-optimizing systems

Section V - 18

Page 10: BUILDING AUTOMATION AND CONTROL SYSTEMS SECTIONV

4/19/2012

10

PID Controls Loop ResponsePID Controls Loop Response

Section V - 19

Stability Stable if process doesn't show continuing trend away from setpoint or continuous oscillation following an upset in either load or setpoint

Loop DefinitionsLoop Definitions

PID ControlsPID Controls

Response Time

Time required for PV to reach SP following a step change in mode or setpoint

Overshoot The amount the PV goes beyond the SP following a change in load or setpoint

Offset The amount of constant error existing between PV and SP once the process reaches steady state

S li Ti Ti i d f t h t d t t f ll i h i l d t i tSettling Time Time required for process to reach steady state following a change in load or setpoint

Steady StateCondition that exists in closed loop system when the control variable (CV) equals a constant value and no oscillation occurs

Section V - 20

Page 11: BUILDING AUTOMATION AND CONTROL SYSTEMS SECTIONV

4/19/2012

11

CONTROL MODE PURPOSE ERROR DETECTIONS

Summary Of GainsSummary Of Gains

PID ControlsPID Controls

DETECTIONS

PG Reacts to Change Detects SIZE of Error

IG Reduces/Eliminates Offset Averages Error over TIME

S Hi h R t L dDG Senses High Rate Load Detects RATE of change of error

biasactiondt

errordDGactiondterror

IGactionerror

PGadjustableCV

*

)(

1000*

1000*

1000)(

Section V - 21

RREVIEWEVIEW::

CCONTROLSONTROLSCCONTROLSONTROLS

Section V - 22

Page 12: BUILDING AUTOMATION AND CONTROL SYSTEMS SECTIONV

4/19/2012

12

1. List advantages and disadvantages of pneumatic controls.

2. Why is DDC so popular?

3 What does the term “direct acting” mean?3. What does the term direct acting mean?

Section V - 23

4. The difference between the setting at which a controller operates to one position and the setting at which it changes to the other is known as the:

A) Throttling range B) OffsetC) Differential D) Control point

5. What is the flow rate of 16°C water through a control valve with a flow coefficient of 0.01 and a pressure difference of 100 kPa?

A) 0.1 LPS B) 0.2 LPSC) 0.6 LPS D) 0.4 LPS

Section V - 24

Page 13: BUILDING AUTOMATION AND CONTROL SYSTEMS SECTIONV

4/19/2012

13

BBUILDINGUILDINGAAUTOMATIONUTOMATIONSSYSTEMSYSTEMSSSYSTEMSYSTEMS

(BAS)(BAS)

Section V - 25

Floor Level Network

Building Level Network

Management Level Network

BAS AnatomyBAS Anatomy

Management Level Network

Remote System Access

Remote Alarm NotificationRemote Alarm Notification

Interoperability with other Buildings/Systems/Networks

Section V - 26

Page 14: BUILDING AUTOMATION AND CONTROL SYSTEMS SECTIONV

4/19/2012

14

RECOMMENDED GOAL FOROPERATION OF NEW BAS’S

Single seat operation for the BAS using a common database for all operational and maintenance data database for all operational and maintenance data accessible in the facility.

This means that the Maintenance Management System and the Energy Management System(s), at the minimum, must share a common database.

Section V - 27

BBASICASIC FFUNCTIONSUNCTIONS

1.1. Monitoring/SurveillanceMonitoring/Surveillance• Building Conditions• Equipment Status• Equipment Status• Utility Submetering• Climatic Data• Fire & Security

BUILDING

2FacilityHVAC

3EnergyPower

4FactoryPower

5FactoryPower

and

6OfficePower

71st

FloorOffice

82nd

FloorOffice

9Computer

RoomPower

10Computer

RoomHVAC

11OfficeHVAC

1A. General Service Meter(Utility Meter for Billing)

1B. Electric Heat Meter(Utility Meter for Billing)

Lights Lights Lights and LightsHVAC

12OfficeRTU-1

13Office

RTU-13

14OfficeRTU-3

15OfficeRTU-4

19CAFE

20FactoryLights

24Air

Compressor

21Energy

MezzanineTest Room

22Elevator

23English

Labs

16Factory

RTU

17Factory

RTU

18Factory

RTU

Section V - 28

Page 15: BUILDING AUTOMATION AND CONTROL SYSTEMS SECTIONV

4/19/2012

15

BBASICASIC FFUNCTIONSUNCTIONS

2.2. Demand LimitingDemand Limiting• Load shedding• Duty cycling

3.3. MaintenanceMaintenance• Remote operation and control of equipment• Generation of maintenance schedules• Diagnosing breakdowns

4.4. Record GenerationRecord Generation• Trends and operation logsp g• Utility demand profile (“baseline”)• Modification/replacement analysis• Energy conservation documentation

Section V - 29

SSTARTTART--SSTOPTOP OOPTIMIZATIONPTIMIZATIONHow It WorksHow It Works

Start the equipment at the latest possible time Stop at the earliest possible time

G ( )ENERGY (KWH)SAVINGS

FROM SSTO

EM

AN

D (

KW

)

ENERGY (KWH)SAVINGS

FROM SSTO

DE

0 2018161412108642 22 24

OFF-PEAK$0.0453/KWH

OFF-PEAK$0.0453/KWH

PEAK$0.0759/KWH

OCCUPANCY PARTIALOCC

Section V - 30

Page 16: BUILDING AUTOMATION AND CONTROL SYSTEMS SECTIONV

4/19/2012

16

CCHILLEDHILLED WWATERATER RRESETESET IntroductionIntroduction

Many buildings’ chilled water setting is designed for the heaviest anticipated cooling load.

Significant cost savings can result from resetting chilled water Significant cost savings can result from resetting chilled water temperatures in anticipation of cooling load

How It WorksHow It Works When the load, chilled water T, or return chilled water

temperature increases, the chilled water setpoint is lowered, and vice versa

A one degree C increase in CWT makes the chiller about 2% more efficient

You must be able to meet both sensible and latent cooling loads. Also, there may be minimum flow condition on the chiller that limits this change.

Section V - 31

CCONDENSERONDENSER WWATERATER RRESETESET

The same idea can be used on the other side of the chiller by reducing the t t f th li t f th temperature of the cooling water from the cooling tower.

For every one degree C reduction in the temperature of the cooling water, the chiller efficiency goes up about 1.5 %.

Be careful with older chillers since they Be careful with older chillers, since they can not take too cold cooling water without developing head pressure problems.

Section V - 32

Page 17: BUILDING AUTOMATION AND CONTROL SYSTEMS SECTIONV

4/19/2012

17

SSUPPLYUPPLY AAIRIR RRESETESET

Supply Air Reset Based on LoadSupply Air Reset Based on Load A good rule of thumb provides for a supply air

t t t f f th th diff b t temperature reset for one-fourth the difference between the supply design temperature and the design space temperature

Savings CalculationDesignAirSupply

DesignAirSupplyTempDesiredLowestSAR

4

Where: Lowest Desired Temp is the temperature of the coolest room Supply Air Design is the current temperature of Supply Air

Section V - 33

SSTATICTATIC PPRESSURERESSURE RRESETESET How It WorksHow It Works

The DDC system monitors the VAV static pressure and lowers the pressure until only one damper is completely open

The Static Pressure and VFD control sensors must be located on the same DDC control panel

40% 50% 60%

7 5 % 1 0 0 % 7 0 %

Section V - 34

Page 18: BUILDING AUTOMATION AND CONTROL SYSTEMS SECTIONV

4/19/2012

18

SSTATICTATIC PPRESSURERESSURE RRESETSESETS•• Proof of PerformanceProof of Performance

– Operating the fan with zero airflow wastes energy– Modulating fan speed based on damper position reduces

fan usage and saves energy

2.5

2.0

1.5

ssu

re (

in. w

.g.)

No Reset

1.0

0.5

0.00 50% 100%

Sta

tic

Pre

s

Demand

Reset

Energy Savings

Section V - 35

EECONOMIZERCONOMIZER

•• How It WorksHow It Works– Reduce cooling & heating energy by optimizing mixed air temp– As the outside air allows, the outdoor air damper opens more

F h i / li h f i i i d – Free heating/cooling occurs when occupant comfort is maintained without using mechanical heating or cooling

E c o n o m iz e rS w itc h P o in t

o r A ir D am

p e r

He a tin g -C

o il V a ling -C

o il V a lv

e

1 0 0

pen

Ou td

o o r

V a lv e Co o li

O u ts id e A ir T e m p e ra tu re ( ºF )

M e c h a n ic a l H e a t in g F re e C o o lin g M e c h a n ic a l C o o lin g

5 0 7 0

0

6 5

M A M

% O

p

Section V - 36

Page 19: BUILDING AUTOMATION AND CONTROL SYSTEMS SECTIONV

4/19/2012

19

DDEMANDEMAND CCONTROLONTROL VVENTILATIONENTILATION

How It WorksHow It Works DCV provides just the right amount of outside needed by

occupantsM d l t til ti t i t t f / Modulates ventilation to main target cfm/person ventilation based on actual occupancy Less than 700 ppm above outside CO2 concentration

1 0 0 %

8 0 %

6 0 %

4 0 %nt B

uild

ing

Occ

up

ancy

or

t T

ota

l Ve

ntila

tion

Ca

pac

ity

2 0 %Pe

rce

Pe

rcen

t

B u ild in g O ccu p a n cy /D e m a n dV e n tila t io n C o n tro l

E n e rg y S a v in g s w ithD e m a n d C o n tro lle d V e n tila t io n

O cc u p a n cy P e r io dE n e rg y C o s t w ithD e m a n d C o n tro lle d V e n tila t io n

4 :0 0 6 :0 0 8 :0 0 1 0 :0 0 1 2 :0 0 1 4 :0 0 1 6 :0 0 1 8 :0 0 2 0 :0 0 2 2 :0 0 2 4 :0 0

Section V - 37

HHOTOT WWATERATER RRESETESET -- HHOWOW IITT WWORKSORKS

Hot water boilers are very efficient at partial load Distribution losses are less when temperature is reduced Hot water reset conserves energy by reducing the boiler’s

i operating temperature Hot water reset reduces thermal shock because it does not

involve drastic temperature fluctuations To minimize flue gas corrosion, do not reset lower than 60 ºC

Section V - 38

Page 20: BUILDING AUTOMATION AND CONTROL SYSTEMS SECTIONV

4/19/2012

20

HHOTOT WWATERATER RRESETESETProof of PerformanceProof of Performance

Maintaining 180ºF (82 ºC)water temperature forces the heating valves to cycle open and closed

180

130

80

70

60

160

150

140

170

180Hot Water Supply (ºF)

Valve Position (% open)

50

40

30

20

10

0

7:0

0

8:0

0

9:0

0

10:

00

11:

00

12:

00

13

:00

14:

00

15:

00

16:

00

17:

00

18

:00

19

:00

Outside Air Temp (ºF)

Section V - 39

HHOTOT WWATERATER RRESETESET

Proof of PerformanceProof of Performance Resetting the hot water temperature allows heating

valves to operate in more efficient mid-actuation positions180

130

80

70

60

160

150

140

170

Valve Position (% open)

Hot Water Supply (ºF)

Theoretical Potential Savings

50

40

30

20

10

0

7:00

8:00

9:00

10:

00

11:

00

12:

00

13:0

0

14:

00

15:

00

16:

00

17:

00

18:0

0

19:0

0

Outside Air Temp (ºF)

Section V - 40

Page 21: BUILDING AUTOMATION AND CONTROL SYSTEMS SECTIONV

4/19/2012

21

RREVIEWEVIEW::

BASBASBASBAS

Section V - 41

RREVIEWEVIEW: BAS/EMS: BAS/EMS

1. Distinguish between analog and digital controlcontrol.

2. Devices using 4-20 mA current loops are using digital data transmission.(A) True (B) False

Section V - 42

Page 22: BUILDING AUTOMATION AND CONTROL SYSTEMS SECTIONV

4/19/2012

22

3. A facility is heated by fan coil units using hot water pumped from a central boiler system List some EMS controls that could system. List some EMS controls that could reduce the facility energy costs.

4. List some maintenance aids that could be provided by an EMS.

Section V - 43

5. An optimum start device is a control function that:(A) Shuts off the outside ventilation air during start up of the building.

(B) Shuts off equipment for duty cycling purpose.

(C) Senses outdoor and indoor temperatures to determine the minimum time needed to heat up or cool down a building.

(D) Compares the enthalpy of outdoor and return air and determines the optimum mix of the two streams.

Section V - 44

Page 23: BUILDING AUTOMATION AND CONTROL SYSTEMS SECTIONV

4/19/2012

23

Control BasicsControl BasicsControl Functions & TerminologyControl Functions & Terminology

Overall RecapOverall Recap

BAS/EMS BasicsBAS/EMS BasicsBAS/EMS Functions & ProgramsBAS/EMS Functions & Programs

Section V - 45

APPENDIX

Section V - 46

Page 24: BUILDING AUTOMATION AND CONTROL SYSTEMS SECTIONV

4/19/2012

24

CCONTROLONTROL TTERMINOLOGYERMINOLOGY Set PointSet Point – The value of the controlled variable

that is to be maintained. Control PointControl Point - The actual value of the controlled

variable (temperature, pressure, flow, etc,).( p , p , f , ,) OffsetOffset - The difference between the set point and

the control point or the actual value of the controlled variable. (This is sometimes called drift, deviation, or control point shift.)

Direct Acting ControllerDirect Acting Controller – A controller for which an increase in the level of the sensor signal (temperature, pressure, etc,) results in an increase in the level of the controller output.p

Modulating ControllerModulating Controller – A type of controller for which the output can vary infinitely over the range of the controller.

Section V - 47

DifferentialDifferential – For a two-position controller it is the difference between the setting at which the controller operates at one position and the setting at which it changes to the other position. (All two-position controller need a differential to prevent “hunting,”

id li F h h diff i l i or rapid cycling. For a thermostat, the differential is expressed in degrees of temperature.)

DeadDead--BandBand – The range over which the output of the controller remains constant as the input varies, with the output changing only in response to an input outside the differential range.

Throttling RangeThrottling Range – The amount of change in the t ll d i bl i d t th t t f controlled variable required to run the actuator of

the controlled device from one end of its stroke to the other end. (If the actual value of the controlled variable lies within the throttling range of the controller, it is said to be in control. When it exceeds the throttling range it is said to be out of control.)

Section V - 48

Page 25: BUILDING AUTOMATION AND CONTROL SYSTEMS SECTIONV

4/19/2012

25

GainGain – The ratio of the output of the controller to the input. In a pneumatic temperature controller, for example, the gain would be expressed as:

gain = Controller Output (kPa)

Throttling Range (degrees)

Linear Percentage ValveLinear Percentage Valve – A valve with a plug shaped so that the flow varies directly with the lift.

Equal Percentage ValveEqual Percentage Valve – A valve with a plug h d th fl i th t f th shaped so the flow varies as the square root of the

lift. Flow (LPS) = Cv x √∆P

Section V - 49

WWATERATER FFLOWLOW TTHROUGHHROUGH VVALVESALVES

Section V - 50

Page 26: BUILDING AUTOMATION AND CONTROL SYSTEMS SECTIONV

4/19/2012

26

OOTHERTHER EMS PEMS PROGRAMSROGRAMS

1.1. Scheduled Start/StopScheduled Start/Stop – Starting and stopping equipment based upon the time of day, and the day of the weekand the day of the week.

2.2. Duty CyclingDuty Cycling – Shutting down equipment for predetermined short periods of time during normal operating hours.

3.3. Demand LimitingDemand Limiting – Temporarily shedding electrical loads to prevent exceeding a peak value.

4.4. Unoccupied SetbackUnoccupied Setback – Lowering the space pp g pheating setpoint or raising the space cooling setpoint during unoccupied hours.

Section V - 51

5.5. Warm Up/Cool Down Ventilation & Warm Up/Cool Down Ventilation & RecirculationRecirculation – Controls operation of the OA dampers when the introduction of OA would impose an additional thermal load during warm-up or cool-down cycles prior to occupancy of a building.

6.6. Hot Deck/Cold Deck Temperature ResetHot Deck/Cold Deck Temperature Reset -S l h / i h h h i d

ppSelects the zone/area with the greater heating and cooling requirements, and establishes the minimum hot and cold deck temperature differential which will meet the requirements.

7.7. Steam Boiler OptimizationSteam Boiler Optimization – Implemented in heating plants with multiple boilers. Boiler plant optimization is accomplishes through the selection of the most efficient boiler to satisfy the space temperature requirements during the building occupied period. R h C il/RR h C il/R8.8. Reheat Coil/ResetReheat Coil/Reset – Selects the zone/area with the greatest need for reheat, and establishes the minimum temperature of the heating hot water so that it is just hot enough to meet the reheat needs for that time period.

Section V - 52

Page 27: BUILDING AUTOMATION AND CONTROL SYSTEMS SECTIONV

4/19/2012

27

9.9. Chiller &/or Boiler OptimizationChiller &/or Boiler Optimization – For facilities with multiple chillers &/or boilers, the most efficient chiller(s) &/or boiler(s) are selected to meet the existing load with minimum demand and or energy.

10.10. Chiller Demand LimitingChiller Demand Limiting – The chiller electrical 10.10. Chiller Demand LimitingChiller Demand Limiting The chiller electrical load is reduced at certain times to meet a maximum pre-specified chiller kW load.

11.11. Lighting ControlLighting Control – Turns lighting off and on according to a pre-set time schedule.

12.12. Remote Boiler Monitoring and SupervisionRemote Boiler Monitoring and Supervision –Uses sensors at the boiler to provide inputs to the EMCS for automatic central reporting of alarms, critical p g ,operating parameters, and remote shutdown of boilers.

13.13. Maintenance ManagementMaintenance Management – Provides a maintenance schedule for utility plants, mechanical and electrical equipment based on run time, calendar time, or physical parameters.

Section V - 53

END OF SECTION V

Section V - 54


Recommended