Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science and Technology (IBST) Hanoi and Ho Chi Minh City December 12-16, 2011
Transcript
Page 1: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Building Code Requirements for Structural Concrete (ACI 318M-11)

Design of Wall Structures by ACI 318

David Darwin

Vietnam Institute for Building Science and Technology (IBST)

Hanoi and Ho Chi Minh City

December 12-16, 2011

Page 2: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

This morning

Slender columns

Walls

High-strength concrete

Page 3: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Walls (Chapters 14, 10, and 11)

Page 4: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Outline

OverviewNotationGeneral design requirementsMinimum reinforcementReinforcement around openingsDesign of bearing walls (3 methods)Design of shear walls

Page 5: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Walls can be categorized based on

Construction Design

method loadingCast-in-place Axial load, flexure,

Precast and out-of-plane shear

Tilt-up In-plane shear

Page 6: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Types of Walls

Cast-in-place

Precast

Tilt-up

Page 7: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.
Page 8: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.
Page 9: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.
Page 10: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Walls can be categorized based on

Construction Design

method loadingCast-in-place Axial load, flexure,

Precast and out-of-plane shear

Tilt-up In-plane shear

Bearing walls*

Shear walls*

Page 11: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Notation and Abbreviation

l = Vertical reinforcement ratio

t = Horizontal reinforcement ratio

c = Height of wall measured center-to-center of supports

h = Wall thickness

hw = Total height of wall

w = Length of wall

Mcr = Cracking moment

WWR = welded wire reinforcement

Page 12: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

General design requirements in ACI 318

Design for axial, eccentric, lateral, shear and other loads to which the wall is subjected

Walls must be anchored to intersecting structural elements (floors, roofs, columns…)

Horizontal length of a wall considered effective for each concentrated load

≤ center-to center spacing of loads

≤ bearing width + 4 wall thickness h

Page 13: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.
Page 14: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Outer limits of compression member built integrally with a wall ≤ 40 mm from outside of spiral or ties

Minimum reinforcement and reinforcement based on the Empirical Method may be waived if analysis shows adequate strength and stability

Transfer force to footing at base of wall in accordance with Chapter 15 (Footings)

Page 15: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Minimum reinforcement

Vertical reinforcement ratio l 0.0015

Reduce to 0.0012 for bar sizes No. 16 and

fy 420 MPa

or for WWR reinforcement sizes 16 mm

Horizontal reinforcement ratio t 0.0025

Reduce to 0.0020 for bar sizes No. 16 and

fy 420 MPa

or for WWR reinforcement sizes 16 mm

Page 16: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Walls more than 250 mm thick (except basement walls):

Must have two layers of reinforcement parallel with the faces

(a)1/2 to 2/3 of reinforcement in each direction located between 50 mm and 1/3 of wall thickness from exterior surface

(b) balance of reinforcement in each direction located between 20 mm and 1/3 of wall thickness from interior surface

Page 17: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Vertical and horizontal reinforcement spaced

≤ 3h

≤ 450 mm

Ties not required around vertical reinforcement when l ≤ 0.01

Page 18: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Reinforcement around openings

At least 2 No. 16 bars in walls with 2 layers of reinforcement in both directions

At least 1 No. 16 bar in walls with 1 layer of reinforcement in both directions

Anchored to develop fy

Page 19: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Reinforcement around openings

Page 20: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Design of bearing walls

Axial load and flexure

Shear perpendicular to the wall

Page 21: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Design of walls for axial load and flexure

Design options:

Wall Designed as Compression Members (subjected to P & M design as columns)

Empirical Design Method (some limitations)

Alternative Design of Slender Walls (some limitations)

Page 22: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Walls designed as compression members

Design as column, including slenderness requirements

Also meet general and minimum reinforcement requirements for walls

Page 23: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Empirical Design Method

Limitations

Thickness of solid rectangular cross section

h (cor w between supports)/25

100 mm for bearing walls

190 mm for exterior basement and foundation walls

Page 24: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Resultant of all factored loads

must be located within the

middle third of the overall

wall thickness

h

Pu

e h/6

h/6

Wall cross section

Page 25: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Design axial strength

= 0.65

2

0 55 132

cn c g u

kP . f A P

h

Page 26: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Effective length factor, k

Walls braced at top and bottom against lateral translation

Restrained against rotation at one or both ends…k = 0.8

Unrestrained against rotation at both ends …k = 1.0

Walls not braced against lateral translation…k = 2.0

Page 27: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Alternative Design of Slender Walls

When flexural tension controls the out-of-plane design, the requirements of this procedure are considered to satisfy the slenderness requirements for compression members

Pu/Ag 0.06f’c at midheight

Wall must be tension-controlled

Mn ≥ Mcr

P

Lat

eral

Lo

ad

Page 28: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Distribution of load within wall

Page 29: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Provisions cover

Factored moment Mu

Out-of-plane service load deflection s

Page 30: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Factored moment Mu

By iteration

By direct solution

c u

P

e

wu

Page 31: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Solve by iteration

Factored moment Mu by iteration

2

8u c

u u u

wM Pe P

25

0 75 48u c

uc cr

M

. E I

u ua u uM M P

u = +

Pu

Mua Puu

e

Page 32: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Icr = moment of inertia of cracked section

32

2 3s u w

cr sc y

E P h cI A d c

E f d

not taken < 6s

c

E

E

Page 33: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Factored moment Mu by direct solution

251

0 75 48

uau

u c

c cr

MM

P. E I

u = +

Pu

Mua Puu

e

Page 34: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Out-of-plane service load deflection

Loading

D + 0.5L + Wa or

D + 0.5L + 0.7E

(per ACI Commentary and

ASCE 7-10)

s c / 150

c s

P

e

Service Deflection Limit

Page 35: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Service Load Deflections

35(2/3)cr

(2/3)Mcr

n

Mn

Ma

ss

Mcr

Ma

cr

Page 36: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Ma = Service load moment at midheight including P-

Service deflection

Find Ma by iteration

Service load deflections for Ma (2/3)Mcr

c s

P

e

25

48

as cr

cr

cr ccr

c cr

M

M

M

E I

Page 37: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Service load deflections for Ma > (2/3)Mcr

Service deflection

Find Ma and Icr by iteration

c s

P

e

2

2 32 3 2 3

2 3

5

48

a crs cr n cr

n cr

n cn

c cr

M / M/ /

M / M

M

E I

Page 38: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Design of shear walls

Shear parallel to the wall in-plane shear

Page 39: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Shear wall

Page 40: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Design loading

Design for bending, axial load, and in-plane shear

Bending and axial load: design as beam or column

If hw 2w, design is permitted using a strut-and-tie model (Appendix A)

Page 41: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Shear design

0 83

u n

n c s

n c

V V

V V V

V . f hd

Page 42: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Effective depth d

0 8

Larger value equal to the distance from

extreme compression fiber to center of

force of all reinforcement in tension permitted

when determined by strain compatibility

wd . h

Page 43: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

For walls subject to vertical compression,

0 17

For walls subject to vertical tension ,

0 29 0 17 1

is negative for tension

lightweight concrete factor

c c

u

uc c

g

u

V . f hd

N

. NV . f hd

A

N

Page 44: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Alternatively, use the lesser of

0 274

or

0 1 0 20 05

2

When 2 is negative, second

equation is not applicable

uc c

w

w c u w

c cu u w

u u w

N dV . f hd

. f . N hV . f hd

M V

M V

Page 45: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

First equation corresponds to a principal tensile

stress of about 0 33 at centroid of shear-wall

cross section.

Second equation corresponds to a flexural tensile

stress of about 0 50 at a section

c

c

. f

. f 2 above

the section being investigated

w

Page 46: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Horizontal sections closer to the wall base than w /2 or hw/2, whichever is less, may be designed for the same Vc as computed

at w /2 or hw/2

Where Vu Vc/2, minimum wall reinforcement may be used

Where Vu Vc/2, wall reinforcement must meet the requirements described next

Page 47: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Horizontal shear reinforcement

v y u c

s vy

A f d V V sV A

s f d

0 0025

5, 3 , 450 mm

vt

w

A.

hs

s h

Page 48: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Vertical shear reinforcement

1

1

0 0025 0 5 2 5 0 0025

0 0025

3, 3 , 450 mm

h wt

w

w

A h. . . .

hs

.

s h

Page 49: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Summary

Design of wallsNotationGeneral design requirementsMinimum reinforcementReinforcement around openingsDesign of bearing walls (3 methods)Design of shear walls

Page 50: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

50

Page 51: Building Code Requirements for Structural Concrete (ACI 318M-11) Design of Wall Structures by ACI 318 David Darwin Vietnam Institute for Building Science.

Figures copyright 2010 by

McGraw-Hill Companies, Inc.

1221 Avenue of the America

New York, NY 10020 USA

Duplication authorized for use with this presentation only.

Photographs and figures on bearing wall design provided courtesy of the Portland Cement Association, Skokie, Illinois, USA