Bulletin 1606 Power Supplies 8-2 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold ! 1 2 3 4 5 6 7 8 9 10 11 12 13 Product Overview Bulletin 1606-XLS 1606-XLE 1606-XLP 1606-XL Type Single/Three Phase Single Phase Single/Two Phase Single/Three Phase Features y Ultra-small size y Extra-low inrush current y Active power factor correction y Wide range AC/DC input; auto select input y Superior reserve power (can support 150% rated power for five seconds) y Superior efficiency and temperature rating y DC OK and overload LED y Low inrush current y Ultra-small size y Auto select input y Superior overload design y Superior efficiency and temperature rating y Regional voltage input y Low inrush current y Wide range input with auto select y Superior overload design (continuous current, no hiccup) y NEC Class 2 “Limited Power“ y Superior efficiency and temperature rating y Low inrush current y PFC Choke y Wide range input; auto select input y Superior overload design (continuous current, no hiccup) y NEC Class 2 “Limited Power“ y Selectable operating mode (single/parallel) y Superior efficiency and temperature rating y Output signals Output Power 80...480 W 80...240 W 15…100 W 60...960 W Input Voltage / Primary Voltage 85…276/323…552V AC 88…375/450…780V DC 90…132/180…264V AC 85…264V AC 85…375V DC 85…132/176…264/340…576V AC 160...375/450…820V DC Efficiency 91.6...95% 90...92% 80...90% 87...93% Output Voltage / Secondary Voltage 24V DC 24, 48V DC 5, 10...12, 12, 15, 24, 48V DC 24, 36, 48V DC Rated Output Current 3.4…20 A 3.4…10 A 0.63…4.2 A 2.5…40 A Operating Temperature Range (Tamb) -25…+70 °C >60 °C with derating -25…+70 °C >60 °C with derating -10…+70 °C >60 °C with derating -10…+70 °C >60 °C with derating Non-Operating Temperature Range -40…+85 °C Certifications cULus, CE UL, CE, CSA cULus, CE, CSA cULus, CE Standards EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, EN 61000-3-2 (A14), EN 50081-1 UL 508 UL 1950 EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, EN 61000-3-2 (A14), EN 50081-1 UL 508 UL 1950 CAN/CSA C22.2 No. 107-1 EN 50081-1, EN 61000-6-2, EN 61000-3-2 (A14) UL 508 UL 60950, CAN/CSA C22.2 No. 60950 EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, EN 61000-3-2 (A14), EN 50081-1 UL 508 UL 60950, CAN/CSA C22.2 No. 60950 Special Application Products Compact redundancy module for 10…60V DC Buffer module for extended ride-through Redundant power supplies Redundancy modules DC UPS DC converter Product Selection Page 8-5 Page 8-6 Page 8-6 Page 8-7
Transcript
Page 1: Bulletin 1606 Product Overview - Elit€¦ · The Bulletin 1606 line of Power Supplies is designed with "reserve power" thereby eliminating the need to oversize your power supply

Bulletin 1606

Power Supplies

8-2Visit our website: www.ab.com/catalogs

Preferred availability cat. nos. are printed in bboolldd

!

1

2

3

4

5

6

7

8

9

10

11

12

13

Product Overview

Bulletin 1606-XLS 1606-XLE 1606-XLP 1606-XL

Type Single/Three Phase Single Phase Single/Two Phase Single/Three Phase

Features

Ultra-small sizeExtra-low inrush currentActive power factor correctionWide range AC/DC input; autoselect inputSuperior reserve power (cansupport 150% rated power forfive seconds)Superior efficiency andtemperature ratingDC OK and overload LED

Low inrush currentUltra-small sizeAuto select inputSuperior overload designSuperior efficiency andtemperature ratingRegional voltage input

Low inrush currentWide range input with autoselectSuperior overload design(continuous current, no hiccup)NEC Class 2 “Limited Power“ Superior efficiency andtemperature rating

Low inrush currentPFC ChokeWide range input; auto selectinputSuperior overload design(continuous current, no hiccup)NEC Class 2 “Limited Power“ Selectable operating mode(single/parallel)Superior efficiency andtemperature ratingOutput signals

Output Power 80...480 W 80...240 W 15…100 W 60...960 W

Input Voltage /Primary Voltage

85…276/323…552V AC88…375/450…780V DC 90…132/180…264V AC 85…264V AC

85…375V DC85…132/176…264/340…576V AC

160...375/450…820V DC

Efficiency 91.6...95% 90...92% 80...90% 87...93%

Output Voltage /SecondaryVoltage

24V DC 24, 48V DC 5, 10...12, 12, 15, 24, 48V DC 24, 36, 48V DC

Rated OutputCurrent 3.4…20 A 3.4…10 A 0.63…4.2 A 2.5…40 A

OperatingTemperatureRange (Tamb)

-25…+70 °C>60 °C with derating

-25…+70 °C>60 °C with derating

-10…+70 °C>60 °C with derating

-10…+70 °C>60 °C with derating

Non-OperatingTemperatureRange

-40…+85 °C

Certifications cULus, CE UL, CE, CSA cULus, CE, CSA cULus, CE

Standards

EN 55011 (Class B), EN 55022 (Class B),

EN 61000-6-2, EN 61000-3-2 (A14),

EN 50081-1UL 508UL 1950

EN 55011 (Class B), EN 55022 (Class B),

EN 61000-6-2, EN 61000-3-2 (A14),

EN 50081-1UL 508

UL 1950CAN/CSA C22.2 No. 107-1

EN 50081-1, EN 61000-6-2,

EN 61000-3-2 (A14)UL 508

UL 60950, CAN/CSA C22.2 No. 60950

EN 55011 (Class B), EN 55022 (Class B),

EN 61000-6-2, EN 61000-3-2 (A14),

EN 50081-1UL 508

UL 60950,CAN/CSA C22.2 No. 60950

SpecialApplicationProducts

Compact redundancy module for 10…60V DCBuffer module for extended ride-throughRedundant power suppliesRedundancy modulesDC UPSDC converter

ProductSelection Page 8-5 Page 8-6 Page 8-6 Page 8-7

00_1606.qxd 4/17/2008 9:33 AM Page 8-2

Page 2: Bulletin 1606 Product Overview - Elit€¦ · The Bulletin 1606 line of Power Supplies is designed with "reserve power" thereby eliminating the need to oversize your power supply

Bulletin 1606

Power Supplies

8-3Visit our website: www.ab.com/catalogs

Preferred availability cat. nos. are printed in bboolldd

!

1

2

3

4

5

6

7

8

9

10

11

12

13

Selection Information

Bulletin 1606 — Power Supplies

UL Listed NEC Class 2; Class 1, Div. 2; Semi F47; ODVA ApprovedLow inrush current limitingPFC Active or PassiveWide range input; auto select inputSuperior overload design (continuous current, no hiccup)NEC Class 2 'Limited Power' optionsSelectable operating mode (single/parallel)Superior efficiency and temperature rating

Special ModulesBrownout buffer, DC to DC converter, N+1 redundancy, DC UPS

Not all features apply to all power supplies; see individual power supply descriptions for specificsA more detailed list of performance specifications can be found at the Allen-Bradley web site http://www.ab.com/industrialcontrols/products/power_supplies/index.html

Certifications

How to Select a Bulletin 1606 Power SupplyThe Bulletin 1606 line of Power Supplies is designed with "reserve power" thereby eliminating the need to oversize your power supply to starthigh inrush loads.

Quick mounting and connecting, innovative DIN-Rail mount, smallest in class

Standards ComplianceWorld-wide Certifications cULus, CE, C-TickNEC Class 2 SEMI F47 CompatibleClass 1 Div. 2 (T3A) ABS/GL/RINA (Marine)

IRATED: 5 A ISHORT CIRCUIT: >9 A IPOWER BOOST: 7.5 A

Steps to size a Power Supply

1. Determine the "Average" continuous current of the load and the typicalinrush current.

2. Select a power supply where the rated load is at/or below the current ofthe device and the Peak Current is less than the short-circuit rating of thepower supply.

Notes:

PowerBoost will deliver up to 25% additional current continuously at40 °C or less.

ReservePower will deliver 150% of rated current for up to 5 s.

Example:

Application: Single Phase 120V input, 24V output, 5 A continuous current @35 °C, with 7.5 A inrush current

Solution: 1606-XLS120E

Output Characteristic for XLS120E (5 A) Power Supply

Cat. No. IRATED [A]ISHORT CIRCUIT

(25 °C) [A]IPOWER BOOST or

IRESERVEPOWER [A]

1606-XLP90B 7.5 8 —

1606-XLP90E-2 3.75 7 —

1606-XLP95E 3.9 7 —

1606-XLP100E 4.2 7.1 —

1606-XLP100E-2 4.2 8 —

1606-XLP100F 2.1 3.6 —

1606-XL60D 2.5 4.5♣ —

1606-XL180B 15 21♣ —

1606-XL480EPT 20 22 25

1606-XL480GP 13.3 12 16.6

1606-XL480F 10 24 12.5

1606-XL120E-3 5 11♣ 6

1606-XL240E-3 10 22♣ 12

1606-XL480E-3W 20 25 25

1606-XL480F-3H 10 N/A 12.5

1606-XL720E-3 30 N/A 33

1606-XL960E-3 40 44 45

1606-XL960E-3S 40 44 45

1606-XL60DR 2.5 4.5♣ —

1606-XL120DR 5 10♣ 6

1606-XL240DR 10 18♣ 12

§ Products with ReservePower.♣ Short circuit current values are temperature dependent for the selected product; i.e., the higher the ambient temperature, the lower the short circuit current.

Hiccup Overload design.

Cat. No. IRATED [A]ISHORT CIRCUIT

(25 °C) [A]IPOWER BOOST or

IRESERVEPOWER [A]

1606-XLS80E 3.4 5.2 5.4§

1606-XLS120E 5 9 7.5§

1606-XLS240E 10 21 15§

1606-XLS480E 20 30 30§

1606-XLS480E-3 20 29 30§

1606-XLSDNET4 3.8 4 —

1606-XLSDNET8 8 7 —

1606-XLE80E 3 5.5 3.6

1606-XLE120E 5 11 6

1606-XLE240E 10 16 12

1606-XLE240EP 10 16 12

1606-XLE240F 5 8.5 6

1606-XLP15E 0.6 0.75 —

1606-XLP25A 5 5 —

1606-XLP30B 3 4 —

1606-XLP30E 1.3 1.9 —

1606-XLP36C 2.8 2 —

1606-XLP50B 4.2 4.3 —

1606-XLP50E 2.1 3.1 —

1606-XLP50EZ 2.1 3.1 —

1606-XLP50F 1 1.7 —

1606-XLP72E 3 4.5 —

Product Sizing............. this pageQuick Guide................. 8-4Special Applications. 8-4Cat. No. Explanation 8-5Product Selection ...... 8-5Accessories.................. 8-8Specifications.............. 8-9Approx. Dimensions . 8-171606-XLRedundancy................. 8-201606-XLBuffer............. 8-211606-XLS DC UPS.... 8-22

Table of Contents

01_1606_a.qxd 4/24/2008 12:21 PM Page 8-3

Page 3: Bulletin 1606 Product Overview - Elit€¦ · The Bulletin 1606 line of Power Supplies is designed with "reserve power" thereby eliminating the need to oversize your power supply

Bulletin 1606

Power Supplies

8-4Visit our website: www.ab.com/catalogs

Preferred availability cat. nos. are printed in bboolldd

!

1

2

3

4

5

6

7

8

9

10

11

12

13

Selection Information, Continued/Quick Guide

Quick GuideBulletin 1606-(number from table) Power Supply Quick Guide

Special Applications

NEC Class 2

ABS/GL/RINA (Marine)

Hazardous Location Rating, Class 1 Div. 2

Semiconductor F47 Sag Immunity Requirements

ODVA Requirements1606-XLSDNET4 1606-XLSDNET8

Conformal Coating1606-XLE120EC 1606-XL240E-3C1606-XLS240EC 1606-XLS480E-3C

1606-XLP15A 1606-XLP50EZ1606-XLP15B 1606-XLP72E1606-XLP15E 1606-XLP90B1606-XLP25A 1606-XLP100E1606-XLP30E 1606-XLP100F1606-XLP36C 1606-XLPRED1606-XLP50E

1606-XLSDNET4 1606-XLP50E1606-XLE72E 1606-XLP50EZ1606-XLE80E 1606-XLP50F1606-XLP15A 1606-XLP72E1606-XLP15B 1606-XLP90B1606-XLP15E 1606-XLP95E1606-XLP25A 1606-XLP90E-21606-XLP30B 1606-XL60D1606-XLP30E 1606-XLDNET41606-XLP36C 1606-XL60DR1606-XLP50B

1606-XLP15A 1606-XLP30B1606-XLP15B 1606-XLP30E1606-XLP15E 1606-XLP50B1606-XLS80E 1606-XLP50E1606-XLS120E 1606-XLP50EZ1606-XLS240E 1606-XLP72E1606-XLS480E 1606-XLP90B1606-XLS480E-3 1606-XLP95E1606-XLSDNET4 1606-XLP100E1606-XLSDNET8 1606-XLPRED1606-XLSRED 1606-XL240E1606-XLP25A 1606-XL240EP

Product Input Mains Voltage Output Current Range1606-XLS80E Full Range Full Range1606-XLS120E Full Range Full Range1606-XLS240E Full Range Full Range1606-XLS480E Full Range Full Range1606-XLS480E-3 Full Range Full Range1606-XLSDNET4 Full Range Full Range1606-XLSDNET8 Full Range Full Range1606-XLP30E AC 200V or higher Full Range up to 1.3 A1606-XLP50E AC 200V or higher Full Range up to 2.1 A1606-XLP100E AC 200V or higher Full Range up to 4.2 A1606-XL60D AC 120V or higher Full Range up to 2.5 A1606-XL120D AC 120V or higher Full Range up to 5 A1606-XLDNET4 AC 120V or higher Up to 3 A1606-XL480E AC 200V or higher Full Range up to 20 A

15...40 W 50 W 60 W 72...80 W 90...100 W 120 W 180 W 240 W 480 W 720 W 960 W

5...5.5V XLP15AXLP25A — — — — — — — — — —

10...12V XLP30B — — — — — — — — — —

12...15V XLP15B XLP50B — — XLP90B — XL180B — — — —

(+/-)12 and 15V XLP36C — — — — — — — — — —

24...28V 1-Ph XLP15EXLP30E

XLP50EXLP50EZ XL60D

XLS80EXLE80EXLP72E

XLP95EXLP100E

XLS120EXLE120E

XLE120EC—

XLS240EXLS240ECXLE240E

XLE240EP

XLS480EXL480E

XL480EPXL480EPT

— —

24...28V 2-Ph/3-Ph — — — — XLP90E-2

XLP100E-2 XL120E-3 — XL240E-3XL240E-3C

XLS480E-3XLS480E-3CXL480E-3W

XL720E-3 XL960E-3XL960E-3S

36...43V — — — — — — — — XL480GP — —

48...56V 1-Ph — XLP50F — — XLP100F — —XLE240FXL240FP XL480F — —

48...56V 3-Ph — — — — — — — — XL480F-3H — —

24V Redundant — — XL60DR — — XL120DR — XLPREDXL240DR

XLSREDXLERED

XLRED20-30

XLRED20-30 XLRED40

DeviceNet — — — — XLSDNET4 — — XLSDNET8 — — —

Example: For a 24...28 Volt, 3-Phase, 120 Watt power supply, the Catalog Number would be 1606-XL120E-3.

01_1606_a.qxd 4/24/2008 12:21 PM Page 8-4

Page 4: Bulletin 1606 Product Overview - Elit€¦ · The Bulletin 1606 line of Power Supplies is designed with "reserve power" thereby eliminating the need to oversize your power supply

Bulletin 1606

Power Supplies

8-5Visit our website: www.ab.com/catalogs

Preferred availability cat. nos. are printed in bboolldd

!

1

2

3

4

5

6

7

8

9

10

11

12

13

Catalog Number Explanation/Product Selection

Cat. No. ExplanationImportant: The following cat. no. breakdown is for explanation purposes only. It is not a product configurator. Not all combinations of fieldsare valid product cat. nos. First, select the desired power supply using the Product Selection tables. Then, use this breakdown for verificationand explanation only.

Product Selection

1606-XLS Performance ⎯ Single- and Three-Phase

Single-Phase

Three-Phase

Input Voltage

InputVoltageSelector

OutputPower

[W]OutputVoltage

OutputCurrent

[A] Input Circuit ProtectionInrush

CurrentParallel

Operation

Meets EN61000-3-2

PFCHarmonics

DC OKRelay Cat. No.

380…480V AC,600V DC Auto 480 24…28V DC 20 6 A (X3) SLOW BLOW FUSE

OR 1492-SP3C060 <4.0 A Yes Yes 1606-XLS480E-3

♣ Unit has internal (not accessible/replaceable) input fuse. Additional protection is not required if used on branch circuits ≤ UL test levels. Consult local codes and regulations for installation.

1606 – XLS 480 E – 3a b c d e

aPower Supply Type

Code Description

XLP Compact family

XL Standard family

XLS Performance family

XLE Essential family

bRated Output Watts

Code Description

15 15 W

25 25 W

30 30 W

36 36 W

40 40 W

50 50 W

60 60 W

72 72 W

80 80 W

90 90 W

95 95 W

100 100 W

120 120 W

180 180 W

240 240 W

480 480 W

720 720 W

960 960 W

cOutput Voltage

Code Description

A 5V DC

B 10...12V DC or 12...15 V DC

C Dual +/- 12 and 15V DC

D 24V DC

E 24...28V DC

F 48...56V DC

G 36...43V DC

dSpecial Functions

Code Description

Can be left blank

C Conformal coating

R Redundancy module

P Power factor correction

L Load sharing

T Remote shutdown

Z Removeable Terminations

X Semi-Regulated

E Regional voltage; 230V AC input only

N Regional voltage; 120V AC input only

Special output signals are onlyavailable with the 960 W powersupply.

Input Voltage

InputVoltageSelector

OutputPower

[W]OutputVoltage

OutputCurrent

[A] Input Circuit Protection♣Inrush

CurrentParallel

Operation

Meets EN61000-3-2

PFCHarmonics

DC OKRelay Cat. No.

100…240V AC,110…300V DC Auto 80 24…28V DC 3.4 6 A SLOW BLOW FUSE OR

1492-SPU1C060/20 A <7.0 A Yes Yes — 1606-XLS80E

100…240V AC,110…300V DC Auto 120 24…28V DC 5 6 A SLOW BLOW FUSE OR

1492-SPU1C060/20 A <4.9 A Yes Yes 1606-XLS120E

100…240V AC,110…300V DC Auto 240 24…28V DC 10 6 A SLOW BLOW FUSE OR

1492-SPU1C060/20 A <5.0 A Yes Yes 1606-XLS240E

100…240V AC,110…300V DC Auto 480 24…28V DC 20 6 A SLOW BLOW FUSE OR

1489-A1C060/20 A <9.0 A Yes Yes 1606-XLS480E

100…240V AC,110…300V DC Auto 91 24V DC 3.8 6 A SLOW BLOW FUSE OR

1489-A1C060/20 A <4.9 A Yes Yes 1606-XLSDNET4

100…240V AC,110…300V DC Auto 192 24V DC 8 6 A SLOW BLOW FUSE OR

1489-A1C060/20 A <7.6 A Yes Yes 1606-XLSDNET8

eMulti-Phase Variations

Code Description

Can be left blank

-2 Two phase

-3 Three phase

-3C Three phase, conformalcoating

-3HThree phase, input voltage400V AC and 450...700V

DC

-3W Three phase, wide inputrange

-3S Three phase, special outputsignals

01_1606_a.qxd 4/24/2008 12:22 PM Page 8-5

Page 5: Bulletin 1606 Product Overview - Elit€¦ · The Bulletin 1606 line of Power Supplies is designed with "reserve power" thereby eliminating the need to oversize your power supply

Bulletin 1606

Power Supplies

8-6Visit our website: www.ab.com/catalogs

Preferred availability cat. nos. are printed in bboolldd

!

1

2

3

4

5

6

7

8

9

10

11

12

13

Product Selection, Continued

1606-XLE Essential ⎯ Single-Phase

1606-XLP Compact ⎯ Single- and Two-Phase

Single-Phase

♣ Unit has internal (not accessible/replaceable) input fuse. Additional protection is not required if used on branch circuits ≤ UL test levels. Parallel use for 1 + 1 redundancy only.

‡ Single/parallel operation (inclined characteristic) selectable (jumper).Consult local codes and regulations for installation.

Input Voltage

InputVoltageSelector

OutputPower

[W]OutputVoltage

OutputCurrent

[A] Input Circuit ProtectionInrush

CurrentParallel

Operation

Meets EN61000-3-2

PFCHarmonics

DC OKRelay Cat. No.

100…240V AC,85…375V DC Auto 15

5…5.5V DC 310 A SLOW BLOW FUSE OR

1489-A1C100/15 A♣ <11 A Yes N/A

— 1606-XLP15A

12…15V DC 1.3 — 1606-XLP15B

24…28V DC 0.6 — 1606-XLP15E

100…240V AC,85…375V DC Auto 25 5…5.5V DC 5

10 A SLOW BLOW FUSE OR1489-A1C100/15 A♣ <18 A Yes N/A — 1606-XLP25A

100…240V AC,85…375V DC Auto 30

10…12V DC 3 10 A SLOW BLOW FUSE OR1489-A1C100/15 A♣ <18 A Yes N/A —

1606-XLP30B

24…28V DC 1.3 1606-XLP30E

100…240V AC,85…375V DC Auto 36 +/- 12/15V DC 2.8

10 A SLOW BLOW FUSE OR1489-A1C100/15 A♣ <18 A Yes N/A — 1606-XLP36C

100…240V AC,85…375V DC Auto 50

12…15V DC 4.2

10 A SLOW BLOW FUSE OR1489-A1C100/15 A♣ <18 A Yes N/A

— 1606-XLP50B

24…28V DC 2.1 1606-XLP50E

24…28V DC 2.1 1606-XLP50EZ

48…56V DC 1 — 1606-XLP50F

100…120/220…240V AC,

220…375V DCMan. 72 24…28V DC 3

10 A SLOW BLOW FUSE OR1489-A1C100/15 A♣ <30 A Yes N/A — 1606-XLP72E

100…120/220…240V AC,

220…375V DCAuto 90 12…15V DC 7.5

10 A SLOW BLOW FUSE OR1489-A1C100/15 A♣ <30 A Yes‡ Yes — 1606-XLP90B

100…200/200…240V AC,

220…375V DCAuto 95 24…28V DC 3.9

10 A SLOW BLOW FUSE OR1489-A1C100/15 A♣ <30 A Yes Yes — 1606-XLP95E

100…200/200…240V AC,

220…375V DCAuto

100

24…28V DC 4.210 A SLOW BLOW FUSE OR

1489-A1C100/15 A♣ <30 A Yes‡ Yes — 1606-XLP100E

100…200/200…240V AC,

220…375V DCAuto 48…56V DC 2.1

10 A SLOW BLOW FUSE OR1489-A1C100/15 A♣ <30 A Yes‡ Yes — 1606-XLP100F

Input Voltage

InputVoltageSelector

OutputPower

[W]OutputVoltage

OutputCurrent

[A] Input Circuit ProtectionInrush

CurrentParallel

Operation

Meets EN61000-3-2

PFCHarmonics

DC OKRelay Cat. No.

100…120/200…240V AC

Auto

80 24…28V DC 3.310 A SLOW BLOW FUSEOR 1489-A1C100/20 A♣ <3 A Yes No — 1606-XLE80E

100…120/200…240V AC

120

24…28V DC 510 A SLOW BLOW FUSEOR 1489-A1C100/20 A♣ <3 A Yes No — 1606-XLE120E

90…132V AC 24…28V DC 510 A SLOW BLOW FUSEOR 1489-A1C100/20 A♣ <3 A Yes No — 1606-XLE120EN

180…264V AC 24…28V DC 510 A SLOW BLOW FUSEOR 1489-A1C100/20 A♣ <3 A Yes No — 1606-XLE120EE

100…120/200…240V AC

240

24…28V DC 1010 A SLOW BLOW FUSEOR 1489-A1C100/20 A♣ <3 A Yes No — 1606-XLE240E

90…132V AC 24…28V DC 1010 A SLOW BLOW FUSEOR 1489-A1C100/20 A♣ <3 A Yes No — 1606-XLE240EN

180…264V AC 24…28V DC 1010 A SLOW BLOW FUSEOR 1489-A1C100/20 A♣ <3 A Yes No — 1606-XLE240EE

100…120/200…240V AC 24…28V DC 10

10 A SLOW BLOW FUSEOR 1489-A1C100/20 A♣ <3 A Yes Yes — 1606-XLE240EP

100…120/200…240V AC 48…52V DC 5

10 A SLOW BLOW FUSEOR 1489-A1C100/20 A♣ <3 A Yes No — 1606-XLE240F

01_1606_a.qxd 4/24/2008 12:22 PM Page 8-6

Page 6: Bulletin 1606 Product Overview - Elit€¦ · The Bulletin 1606 line of Power Supplies is designed with "reserve power" thereby eliminating the need to oversize your power supply

Bulletin 1606

Power Supplies

8-7Visit our website: www.ab.com/catalogs

Preferred availability cat. nos. are printed in bboolldd

!

1

2

3

4

5

6

7

8

9

10

11

12

13

Product Selection, Continued

1606-XL Standard ⎯ Single- and Three-Phase

Single-Phase

Three-Phase

‡ Single/parallel operation (inclined characteristic) selectable (jumper).♣ Unit has internal (not accessible/replaceable) input fuse. Additional protection is not required if used on branch circuits ≤ UL test levels.

DC OK output is provided through a 24V DC signal.Consult local codes and regulations for installation.

Two-Phase

Input VoltageOutput

Power [W]OutputVoltage

OutputCurrent [A] Input Circuit Protection

InrushCurrent

ParallelOperation

Meets EN61000-3-2

PFCHarmonics

DC OKRelay Cat. No.

400…500V AC,450…820V DC 120 24…28V DC 5 10 A (X3) SLOW BLOW FUSE

OR 1492-SP3C100 <25 A Yes Yes — 1606-XL120E-3

400…500V AC,450…820V DC 240 24…28V DC 10

6 A (X3) SLOW BLOW FUSEOR 1492-SP3C060/15 A♣ <17 A Yes‡ Yes — 1606-XL240E-3

400…500V AC,450…820V DC

48024…28V DC 20

6 A (X3) SLOW BLOW FUSEOR 1492-SP3C060/16 A♣ <7 A

Yes‡ Yes —1606-XL480E-3W

400V AC,450…700V DC 48…56V DC 10 10 A (X3) SLOW BLOW FUSE

OR 1492-SP3C100 <15 A 1606-XL480F-3H

400…500V AC,450…820V DC 720 24…28V DC 30 10 A (X3) SLOW BLOW FUSE

OR 1492-SP3C100 <17 A Yes‡ Yes — 1606-XL720E-3

400…500V AC 960 24…28V DC 40 10 A (X3) SLOW BLOW FUSEOR 1492-SP3C100 <30 A

Yes‡

Yes

— 1606-XL960E-3

Activecurrentsharing

1606-XL960E-3S

Input Voltage

InputVoltageSelector

OutputPower

[W]OutputVoltage

OutputCurrent

[A] Input Circuit ProtectionInrush

CurrentParallel

Operation

Meets EN61000-3-2

PFCHarmonics

DC OKRelay Cat. No.

380…480V AC — 90 24…28V DC 3.7510 A (X2) SLOW BLOW FUSE

OR 1489-A2C100/20 A♣ <35 A Yes‡ Yes — 1606-XLP90E-2

380…480V AC — 100 24…28V DC 4.210 A (X2) SLOW BLOW FUSE

OR 1489-A2C100/20 A♣ <35 A Yes‡ Yes — 1606-XLP100E-2

Input Voltage

InputVoltageSelector

OutputPower

[W]OutputVoltage

OutputCurrent

[A] Input Circuit ProtectionInrush

CurrentParallel

Operation

Meets EN61000-3-2

PFCHarmonics

DC OKRelay Cat. No.

100…120/200…240V AC,

160…375V DCMan. 60 24V DC 2.5

10 A SLOW BLOW FUSEOR 1489-A1C100/16 A♣ <18 A Yes Yes — 1606-XL60D

100…200/200…240V AC,

240…375V DCMan. 180 12…15V DC 15

10 A SLOW BLOW FUSEOR 1489-A1C100/10 A♣ <21 A Yes No — 1606-XL180B

200…240V AC,270…370V DC —

480

24…28V DC 20 10 A SLOW BLOW FUSEOR 1489-A1C100/16 A <23 A Yes‡ No — 1606-XL480E

100…120/200…240V AC Auto 24…28V DC 20 10 A SLOW BLOW FUSE

OR 1489-A1C100<18 A @

25°C Yes‡ Yes — 1606-XL480EP

100…120/200…240V AC Auto 24…28V DC 20 10 A SLOW BLOW FUSE

OR 1489-A1C100<18 A @

25°C Yes‡ Yes — 1606-XL480EPT

100…120/200…240V AC Auto 36…43V DC 13.3 10 A SLOW BLOW FUSE

OR 1489-A1C100<18 A @

25°C Yes‡ Yes — 1606-XL480GP

100…120/200…240V AC Auto 48…56V DC 10 10 A SLOW BLOW FUSE

OR 1489-A1C100<18 A @

25°C Yes‡ No — 1606-XL480F

01_1606_a.qxd 4/24/2008 12:22 PM Page 8-7

Page 7: Bulletin 1606 Product Overview - Elit€¦ · The Bulletin 1606 line of Power Supplies is designed with "reserve power" thereby eliminating the need to oversize your power supply

Bulletin 1606

Power Supplies

8-8Visit our website: www.ab.com/catalogs

Preferred availability cat. nos. are printed in bboolldd

!

1

2

3

4

5

6

7

8

9

10

11

12

13

1606 Accessories

Product Selection, Continued/Accessories

1606 Special Modules

1606 Special Modules with UPS

To be used alongside 20, 30, and 40 A power supplies.‡ Single/parallel operation (inclined characteristic) selectable (jumper).§ To be used alongside 40 A power supplies (or smaller).♣ Unit has internal (not accessible/replaceable) input fuse. Additional protection is not required if used on branch circuits ≤ UL test levels.

See product specifications for proper use.The 1606-XLS240-UPS is a charging module, used along side a power supply and a battery assembly, which must be ordered separately. (See Accessories

below.)Consult local codes and regulations for installation.

Input Voltage

InputVoltageSelector

OutputPower

[W]OutputVoltage

OutputCurrent

[A] Input Circuit ProtectionInrush

CurrentParallel

Operation

Meets EN61000-3-2

PFCHarmonics

DC OKRelay Cat. No.

22.5…30V DC — 240 22.5…30V DC 10 N/A — — N/A — 1606-XLS240-UPS

24…28.8V DC — 480 23…27.8V DC 20 N/A — — N/A — 1606-XLBUFFER

Input Voltage

InputVoltageSelector

OutputPower

[W]OutputVoltage

OutputCurrent

[A] Input Circuit ProtectionInrush

CurrentParallel

Operation

Meets EN61000-3-2

PFCHarmonics

DC OKRelay Cat. No.

18…36V DC — 40 5.1V DC 8 N/A <5 A — No — 1606-XLDC40A

100…240V AC,110…300V DC Auto 91 24V DC 3.8

6 A SLOW BLOW FUSE OR1489-A1C060/20 A♣ <4.9 A Yes Yes 1606-XLSDNET4

100…240V AC,110…300V DC Auto 192 24V DC 8

6 A SLOW BLOW FUSE OR1489-A1C060/20 A♣ <7.6 A Yes Yes 1606-XLSDNET8

100…120/200…240V AC,

160…375V DCMan. 60

24V DC

2.510 A SLOW BLOW FUSE OR

1489-A1C100/16 A♣ <18 A Yes‡ N/A 1606-XL60DR

100…120/200…240V AC,

210…375V DCMan. 120 5

10 A SLOW BLOW FUSE OR1489-A1C100/16 A♣ <11 A Yes‡ Yes 1606-XL120DR

100…120/200…240V AC,

240…375V DCMan. 240 10

10 A SLOW BLOW FUSE OR1489-A1C100/10 A♣ <21 A Yes‡ No 1606-XL240DR

24V DC — 720 Vin -.5V typ 30 N/A N/A — N/A — 1606-XLRED20-30

24V DC — 960 Vin -.6V typ 40 N/A N/A§ — N/A — 1606-XLRED40

10…60V DC — 384 Vin 1 -.9V typ 16 N/A N/A — N/A — 1606-XLPRED

10…60V DC — 480 Vin 1 -.9V typ 20 N/A N/A — N/A — 1606-XLSRED

24…60V DC — 480 Vin 1 -.9V typ 20 N/A N/A — — — 1606-XLERED

— Auto 120 24…28V DC 510 A SLOW BLOW FUSE OR

1489-A1C100/20 A♣ <3 A Yes No — 1606-XLE120EC

100…240V AC,110…300V DC Auto 240 24…28V DC 10

6 A SLOW BLOW FUSE OR1489-A1C060/20 A♣ <4 A Yes Yes 1606-XLS240EC

400…500V AC,450…820V DC — 240 24…28V DC 10

6 A (X3) SLOW BLOW FUSEOR 1492-SP3C060/15 A♣ <3 A Yes Yes — 1606-XL240E-3C

— Auto 480 24…28V DC 20 6 A (X3) SLOW BLOW FUSEOR 1492-SP3C060 <15 A Yes Yes 1606-XLS480E-3C

Description Cat. No.

Back-of-panel bracket for XL 1606-XLA

Back-of-panel bracket for XLS or XLE 1606-XLB

7 Ah/12V battery assembly with bracket, for use with DC UPS 1606-XLSBATASSY1

7 Ah/12V battery 1606-XLSBAT1

Battery bracket for 7 Ah/12V battery 1606-XLSBATBR1

26 Ah/12V battery assembly with bracket, for use with DC UPS 1606-XLSBATASSY2

26 Ah/12V battery 1606-XLSBAT2

Battery bracket for 26 Ah/12V battery 1606-XLSBATBR2

01_1606_a.qxd 4/24/2008 12:22 PM Page 8-8

Page 8: Bulletin 1606 Product Overview - Elit€¦ · The Bulletin 1606 line of Power Supplies is designed with "reserve power" thereby eliminating the need to oversize your power supply

Bulletin 1606

Power Supplies

8-9Visit our website: www.ab.com/catalogs

Preferred availability cat. nos. are printed in bboolldd

!

1

2

3

4

5

6

7

8

9

10

11

12

13

SpecificationsΣπεχιφιχατιονσ

1606-XLS Performance Specifications

1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards = EN 55011 (Class B), EN55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1

♣ MTBF determined by Siemens norm SN 29500 at full load current and 40 °CBecause these catalog numbers end with "C", it indicates these devices have conformal coating.

1606-XLS80E 1606-XLS120E1606-XLS240E and1606-XLS240EC 1606-XLS480E

1606-XLS480E-3 and1606-XLS480E-3C

Output Volts/Watts 24…28V/80 W 24…28V/120 W 24…28V/120 W 24…28V/480 W 24…28V/480W

Input Voltage (47...63 Hz) 100…240V AC,110...300V DC

100…240V AC,110...300V DC

100…240V AC,110...300V DC

100…240V AC,110...300V DC 380…480V AC, 600V DC

Operational Range 85…276V AC,88…375V DC

85…264V AC,88…360V DC

85…276V AC,88…375V DC

85…276V AC,88…375V DC

323…552V AC,450…780V DC

Hold-up Time 27…174 ms 33…59 ms 27 ms 32…51 ms 19 ms

Rated Input Current 1.4 A (100V AC), 0.82 A (240V AC)

1.4 A (100V AC), 0.65 A (240V AC)

2.8 A (100V AC), 1.2 A (240V AC)

4.6 A (100V AC), 2.5 A (240V AC)

0.9 A (380V AC), 0.65 A (480V AC)

Efficiency typ. 90.0% typ. 92.7% typ. 91.8% typ. 92.4% typ. 94.8%

Output Voltage 24…28V 24…28V 24…28V 24…28V 24…28V

Rated Output Current 3.4 A (@ 24V)3.0 A (@ 28V)

5 A (@ 24V)4.5 A (@ 28V)

10 A (@ 24V)9 A (@ 28V)

20 A (@ 24V)17 A (@ 28V)

20 A (@ 24V)17.5 A (@ 28V)

ReservePower (typ. 4 s) 5.4 A (@ 24V)5.0 A (@ 28V)

7.5 A (@ 24V)6.7 A (@ 28V)

15 A (@ 24V)13.5 A (@ 28V)

30 A (@ 24V)26 A (@ 28V)

30 A (@ 24V)26 A (@ 28V)

Ripple/Noise <100 mVPP <50 mVPP <50 mVPP <100 mVPP <100 mVPP

Operating TemperatureRange (Tamb)

-25...+70 °C>60 °C with derating

Non-OperatingTemperature Range -40...+85 °C

MTBF♣ >650 000 hours >831 000 hours >581 000 hours >469 000 hours >690 000 hours

Dimensions (W x H x D) 32 x 124 x 102 mm 40 x 124 x 117 mm 60 x 124 x 117 mm 84 x 124 x 127 mm 65 x 124 x 127 mm

Weight 420 g 620 g 900 g 1200 g 870 g

Certifications/Standards 1, 2, 3, 5, 6, 7

Special Features Active PFC; Class 1 Div. 2; Semi F47

1606-XLSDNET4 1606-XLSDNET8

Output Volts/Watts 24V/91 W 24V/192 W

Input Voltage (47...63 Hz) 100…240V AC; 110...300V DC

Operational Range 85…264V AC 88…360V DC 85…276 V AC 88…375 V DC

Hold-up Time 43 ms (120V AC)77 ms (240V AC)

38 ms (120V AC)41 ms (240V AC)

Rated Input Current 1.1 A (100V AC)0.5 A (240V AC)

2.3 A (100V AC)1.0 A (240V AC)

Efficiency typ. 92.4% typ. 92.7%

Output Voltage 24V

Rated Output Current 3.8 A 8 A

Ripple/Noise < 50 mVpp

Operating TemperatureRange (Tamb)

-25...+70 °C>60 °C with derating

Non-OperatingTemperature Range -40...+85 °C

MTBF♣ >581 000 hours >831 000 hours

Dimensions (W x H x D) 40 x 124 x 117 mm 60 x 124 x 117 mm

Weight 620 g 900 g

Certifications/Standards 1, 2, 3, 5, 6, 7

Special Features NEC Class 2 power supply; Active PFC; ODVA Approved;Class 1 Div. 2; Semi F47 Active PFC; ODVA Approved; Class 1 Div. 2; Semi F47

01_1606_a.qxd 4/24/2008 12:23 PM Page 8-9

Page 9: Bulletin 1606 Product Overview - Elit€¦ · The Bulletin 1606 line of Power Supplies is designed with "reserve power" thereby eliminating the need to oversize your power supply

Bulletin 1606

Power Supplies

8-10Visit our website: www.ab.com/catalogs

Preferred availability cat. nos. are printed in bboolldd

!

1

2

3

4

5

6

7

8

9

10

11

12

13

1606-XLE

Specifications, Continued

Output Volts/Watts 24V...28V/80 W 24V...28V/120 W 24V...28V/240 W 24V...28V/240 W 48V...52V/240 W

Input Voltage (47...63Hz) AC 100...120V/200...240V

Operational Range 90...132V/180...264V AC

Hold-up Time >60 ms (120V)>244 ms (240V)

>80 ms (120V)>78 ms (240V)

>46 ms (120V)>42 ms (240V)

Rated Input Current 20 A (100V AC)45 A (240V AC)

2.6 A (100V AC)1.3 A (240V AC)

5 A (100V AC)2.5 A (240V AC)

Efficiency typ. 90% typ. 90% typ. 91% typ. 91% typ. 92%

Output Voltage 24...28V 48...52V

Rated Output Current 3.3 A @ 24V2.9 A @ 28V

5 A @ 24V4.3 A @ 28V

10 A @ 24V8.6 A @ 28V

5 A @ 48V4.6 A @ 52V

Ripple/Noise <50 mVPP

Operating TemperatureRange (Tamb) -25...+70 °C, >60 °C with derating

Non-OperatingTemperature Range -40...+85 °C

MTBF§ >700 000 hours

Dimensions (W x H x D) 32 x 124 x 102 mm 32 x 124 x 117 mm 60 x 124 x 117 mm

Weight 430 g 500 g 700 g 800 g 700 g

Certifications/Standards 1, 2, 3, 4, 5, 6, 7

Special Features NEC Class 2 ⎯

1606-XLE80E1606-XLE120E and

1606-XLE120EC 1606-XLE240E 1606-XLE240EP 1606-XLE240F

1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 107-1, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards =EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1

§ MTBF determined by Siemens norm SN 29500 at full load current and 40 °CBecause this catalog number ends with C, it indicates the device has conformal coating.Available in regional voltages: add N to the end of the cat. no. for 90...132V, or add E to the end of the cat. no. for 180...264V.

01_1606_a.qxd 4/24/2008 12:23 PM Page 8-10

Page 10: Bulletin 1606 Product Overview - Elit€¦ · The Bulletin 1606 line of Power Supplies is designed with "reserve power" thereby eliminating the need to oversize your power supply

Bulletin 1606

Power Supplies

8-11Visit our website: www.ab.com/catalogs

Preferred availability cat. nos. are printed in bboolldd

!

1

2

3

4

5

6

7

8

9

10

11

12

13

Specifications, Continued

1606-XLP Compact Specifications

1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards =EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1

♣ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C

1606-XLP15A 1606-XLP15B 1606-XLP15E 1606-XLP25A

Output Volts/Watts 5...5.5V/15 W 12...15V/15 W 24...28V/15 W 5...5.5V/25 W

Input Voltage (47...63 Hz) 100...240V AC wide range; 85...370V DC

Operational Range 85...264V AC

Hold-up Time >168 ms (230V AC)>45 ms (100V AC)

>191 ms (230V AC)>46 ms (100V AC)

>196 ms (230V AC)>47 ms (100V AC)

>170 ms (230V AC)>19 ms (100V AC)

Rated Input Current <0.28 A (100V AC)<0.17 A (196V AC)

<0.5 A (100V AC)<0.35 A (196V AC)

Efficiency typ. >77% typ. >83% typ. >88% typ. >80%

Output Voltage 5...5.5V5.1V preset 12...15V 24...28V 5...5.5V

5.1V preset

Rated Output Current 0.54...0.63 A 3 A 1.0...1.3 A 5 A (at 5.1V),4.5 A (at 5.5V)

Ripple/Noise <50 mVpp <75 mVpp <50 mVpp <50 mVpp

Operating TemperatureRange (Tamb) -10...+70 °C, >60 °C: 0.4 W/K derating -10...+70 °C

>60 °C: 0.5 W/K derating

Non-OperatingTemperature Range -40...+85 °C

MTBF♣ 2 686 000 hours 3 811 000 hours 4 369 000 hours 600 000 hours

Dimensions (W x H x D) 22.5 x 75 x 91 mm 45 x 75 x 91 mm

Weight 130 g 240 g

Certifications/Standards 1, 2, 4, 5, 7

Special Features NEC Class 2 power supply; ABS/GL/RINA (Marine); Class 1 Div. 2

1606-XLP30B 1606-XLP30E 1606-XLP36C 1606-XLP50B

Output Volts/Watts 10...12V/30 W 24...28V/30 W ±12V/±15V/36 W 12...15V/50 W

Input Voltage (47...63 Hz) 100...240V AC wide range; 85...375V DC 100...240V AC wide range;85...375V DC

100...240V AC wide range;85...375V DC

Operational Range 85...264V AC

Hold-up Time >170 ms (230V AC)>18 ms (100V AC)

>190 ms (230V AC)>19 ms (100V AC)

>180 ms (230V AC)>18 ms (100V AC)

>170 ms (230V AC)>17 ms (100V AC)

Rated Input Current <0.6 A (100V AC)<0.25 A (240V AC)

<0.6 A (100V AC)<0.35 A (196V AC)

<0.65 A (AC 100V AC)<0.4 A (AC 196V AC)

<1.0 A (100V AC)<0.6 A (196V AC)

Efficiency typ. 84% typ. 87.5% typ. 86% typ. 90%

Output Voltage

10...12V12V preset (with jumper),

10...12V adjustable (withoutjumper)

24...28V24.5V preset

±12V (without jumper),±15V (with jumper)

±15V preset

12...15V15V preset (with jumper)

12...15V adjustable (withoutjumper)

Rated Output Current 3 A (@ 10V),2.5 A (@ 12V)

1.3 A (@ 24.5V),1 A (@ 28V)

0...2.8 A (@ +12V),0...1.4 A (@ -12V)0...2.4 A (@ +15V),0...1.4 A @ (-15V)

4.2 A (@ 12V),3.4 A (@ 15V)

Ripple/Noise <10 mVpp <50 mVpp <50 mVpp <100mVpp

Operating TemperatureRange (Tamb)

-10...+70 °C>60 °C: 0.6 W/K derating

-10...+70 °C>60 °C: 0.5 W/K derating

-10...+70 °C> 60 °C: 1 W/K derating

-10...+70 °C>60 °C: 1 W/K derating

Non-OperatingTemperature Range

-10...+70 °C>60 °C: 0.6 W/K derating

-10...+70 °C>60 °C: 0.5 W/K derating

-10...+70 °C> 60 °C: 1 W/K derating

-10...+70 °C>60 °C: 1 W/K derating

MTBF♣ appr. 650 000 hours 600 000 hours appr. 600 000 hours

Dimensions (W x H x D) 45 x 75 x 91 mm

Weight 250 g 230 g 240 g 260 g

Certifications/Standards 1, 2, 4, 5, 7

Special Features NEC Class 2 power supply;Class 1 Div. 2

NEC Class 2 power supply;Class 1 Div. 2; Semi F47

Output voltage adjustable:DC ±12V without jumperor DC ±15V with jumper;

NEC Class 2 power supply;ABS/GL/RINA (Marine);

Class 1 Div. 2

Output voltage adjustable:DC 12...15V without jumper or

DC 15V with jumper; NEC Class 2 power supply;

Class 1 Div. 2

01_1606_a.qxd 4/24/2008 12:23 PM Page 8-11

Page 11: Bulletin 1606 Product Overview - Elit€¦ · The Bulletin 1606 line of Power Supplies is designed with "reserve power" thereby eliminating the need to oversize your power supply

Bulletin 1606

Power Supplies

8-12Visit our website: www.ab.com/catalogs

Preferred availability cat. nos. are printed in bboolldd

!

1

2

3

4

5

6

7

8

9

10

11

12

13

Specifications, Continued

1606-XLP Compact Specifications, Continued

1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards =EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1

♣ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C

1606-XLP50E 1606-XLP50EZ 1606-XLP50F 1606-XLP72E 1606-XLP90B 1606-XLP90E-2

Output Volts/Watts 24...28V/50 W 48...56V/50 W 24...28V/72 W 12...15V/90 W 24...28V/90 W

Input Voltage (47...63 Hz) 100...240V AC wide range; 85...375V DC100...120/220...240V AC

manual select;220...375V DC

100...120/220...240V AC;220...375V DC 2Ø, 380...480V AC

Operational Range 85...264V AC 85...132/184...264V AC 323..552V AC

Hold-up Time >171 ms (230V AC)>17 ms (100V AC)

>170 ms (230V AC)>17 ms (100V AC)

>40 ms (230V AC)>25 ms (100V AC)

>40 ms (230V AC)>20 ms (196V AC,

100V AC)

>52 ms (400V)>93 ms (480V)

Rated Input Current <1.0 A (100V AC)<0.6 A (196V AC)

<1.6 A (100V AC)<0.8 A (220V AC) <1.9 A <0.42 A (400V)

<0.36 A (480V)

Efficiency typ. 88.5% typ. 90% typ. 89% typ. 88.5% typ. 89%

Output Voltage 24...28V24.5V preset

48...56V48V preset

24...28V24.5V preset (at 2.9 A)

12...15V Preset at 12V

24...28V Preset at 24.5V

Rated Output Current 2.1 A (@ 24.5V),1.8 A (@ 28V)

1.05 A (@ 48V),0.9 A (@ 56V)

3 A (@ 24V),2.6 A (@ 28V)

7.5 A (@ 12V),6 A (@ 15V)

3.75 A (@ 24V),3.2 A (@ 28V)

Ripple/Noise <50 mVpp <200 mVpp <50 mVpp <50 mVpp <50 mVpp

Operating TemperatureRange (Tamb)

-10...+70 °C>60 °C: 1 W/K derating

-10...+70 °C>60 °C: 1.5 W/K derating

-10...+70 °C>60 °C: 1 W/K derating

-10...+70 °C>60 °C: 2 W/K

derating

Non-OperatingTemperature Range -40...+85 °C

Dimensions (W x H x D) 45 x 75 x 91 mm 45 x 75 x 91 mm 73 x 75 x 103 mm 73 x 75 x 103 mm

Weight 240 g 260 g 360 g 360 g

Certifications/Standards 1, 2, 3, 4, 5, 6 1, 2, 3, 4, 5, 6 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 4, 5, 6, 7

Special Features

NEC Class 2 powersupply;

ABS/GL/RINA(Marine);

Class 1 Div. 2; Semi F47

RemoveableTerminations;

NEC Class 2 powersupply;

ABS/GL/RINA(Marine);

Class 1 Div. 2

NEC Class 2 powersupply

NEC Class 2 power supply;ABS/GL/RINA (Marine);

Class 1 Div. 2

NEC Class 2 power supply;ABS/GL/RINA (Marine);

Class 1 Div. 2

NEC Class 2 powersupply

MTBF♣ appr. 600 000 hours appr. 600 000 hours appr. 500 000 hours appr. 500 000 hours

1606-XLP95E 1606-XLP100E 1606-XLP100F 1606-XLP100E-2

Output Volts/Watts 24...28V/95 W 24...28V/100 W 48...56V/100 W 24...28V/100 W

Input Voltage (47...63 Hz) 100...120/220...240V AC auto select; 220...375V DC 2Ø, 380...480V AC

Operational Range 85...132/184...264V AC 323..552V AC

Hold-up Time >40 ms (230V AC)>20 ms (100V AC)

>48 ms (400V)>85 ms (480V)

Rated Input Current <2.0 A (100V AC)<0.95 A (220V AC)

<2.1 A (100V AC)<1.0 A (220V AC)

<0.46 A (400V)<0.40 A (480V)

Efficiency typ. 90% typ. 91% typ. 89%

Output Voltage 24...28V24.5V preset

48...56V48V preset

24...28V Preset at 24.5V

Rated Output Current 3.9 A (@ 24.5V),3.2 A (@ 28V)

4.2 A (@ 24.5V),3.6 A (@ 28V)

2.1 A (@ 48V),1.8 A (@ 56V)

4.2 A (@ 24V),3.6 A (@ 28V)

Power Boost ⎯ ⎯ ⎯ ⎯

Ripple/Noise <50 mVpp <50 mVpp <50 mVpp <50 mVpp

Operating TemperatureRange (Tamb)

-10...+70 °C>60 °C: 2 W/K derating

Non-Operating TemperatureRange -40...+85 °C

MTBF♣ appr. 500 000 hours

Dimensions (W x H x D) 73 x 75 x 103 mm

Weight 360 g

Certifications/Standards 1, 2, 3, 4, 5, 6, 7

Special Features NEC Class 2 power supply;Class 1 Div. 2

Single/parallel operation (inclinedcharacteristic) select on front

panel;ABS/GL/RINA (Marine);

Class 1 Div. 2;Semi F47

Single/parallel operation (inclined characteristic) select on frontpanel;

ABS/GL/RINA (Marine)

01_1606_a.qxd 4/24/2008 12:24 PM Page 8-12

Page 12: Bulletin 1606 Product Overview - Elit€¦ · The Bulletin 1606 line of Power Supplies is designed with "reserve power" thereby eliminating the need to oversize your power supply

Bulletin 1606

Power Supplies

8-13Visit our website: www.ab.com/catalogs

Preferred availability cat. nos. are printed in bboolldd

!

1

2

3

4

5

6

7

8

9

10

11

12

13

Specifications, Continued

1606-XL Single Phase Specifications

1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards =EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1

‡ Low inrush current♣ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C

1606-XL60D 1606-XL180B 1606-XL480EP1606-

XL480EPT 1606-XL480GP 1606-XL480F

Output Volts/Watts 24V/60 W 12...15V/180 W 24...28V/480 W 36...43V/480 W 48...56V/480 W

Input Voltage (47...63 Hz)100...120/200...240V AC

manual select;160...375V DC

100...120/220...240V AC240...375V DC 100...120/200...240V AC

Operational Range 85...132/176...264V AC 85...132/176...264V AC 85...132/184...264V AC

Hold-up Time >20 ms (196V AC)>81 ms (230V AC)>84 ms (120V AC)>45 ms (100V AC)

30 ms (120/230V AC) >27 ms (230V AC) 30 ms (230V AC)

Rated Input Current <1.3 A (115V)/<0.7A(230V) <5A (115V)/<2.3 A (230V) 10 A (115V)/5 A (230V)

Efficiency typ. 87.5% typ. >87% typ. 90.5% typ. 92% typ. 93%

Output Voltage 24V 12...15VPreset at 12V

24...28VFront panel potentiometer

36...43VFront panel

potentiometer

48...56VFront panel

potentiometer

Rated Output Current 2.5 A 15 A (@ 12V),12 A (@ 15V)

20 A (@ 24V),18 A (@ 28V)

13.3 A (@ 36V),11.2 A (@ 43V)

10 A (@ 48V),8.6 A (@ 56V)

Power Boost ⎯ 18 A 25 A (22 A) 16.6 A (14 A) 12.5 A (10.7 A)

Ripple/Noise <25 mVpp <50 mVpp< 20 mVpp (single operation)<40 mVpp (parallel operation)

<30 mVpp (singleoperation)

<80 mVpp (paralleloperation)

<40 mVpp (singleoperation)

<80 mVpp (paralleloperation)

Operating TemperatureRange (Tamb)

-10...+70 °C>60 °C with derating

0...70 °C>60 °C with derating

0...+70 °C>60 °C with derating

Non-OperatingTemperature Range -40...+85 °C 0...70 °C

>60 °C with derating -40...+85 °C

MTBF♣ 740 000 hours <425 000 hours 519 000 hours

Dimensions (W x H x D) 49 x 124 x 102 mm 120 x 124 x 102 mm 220 x 124 x 102 mm

Weight 460 g 980 g 2500 g 1800 g

Certifications/Standards 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 4, 5, 6 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 4, 5, 6

Special FeaturesNEC Class 2 power

supply;Semi F47

PFC choke;Overload behavior

selectable;(hiccup/continuous

current); ‡

PFC choke; ‡

Selectablesingle/parallel

operation (inclinedcharacteristic);PFC choke; ‡

01_1606_a.qxd 4/24/2008 12:24 PM Page 8-13

Page 13: Bulletin 1606 Product Overview - Elit€¦ · The Bulletin 1606 line of Power Supplies is designed with "reserve power" thereby eliminating the need to oversize your power supply

Bulletin 1606

Power Supplies

8-14Visit our website: www.ab.com/catalogs

Preferred availability cat. nos. are printed in bboolldd

!

1

2

3

4

5

6

7

8

9

10

11

12

13

Specifications, Continued

1606-XL Three Phase Specifications

1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMCstandards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1

‡ Low inrush current♣ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C

Because this catalog number ends with "C", it indicates the device has conformal coating.

"Shut Down" InputFunction: Turning the unit on or off usinglogic signal (remote monitoring).Unit switches off when Input is connectedto "Signal GND" terminal (DU ≤ 1V) or theinput has a voltage of +20...28V withrespect to the "Signal GND" terminal,(max. 20 mA).

"DC Ok" OutputFunction: Indicating whether the unit isoperating properly. Output can directlyenergize a relay or a control light.Signaling: Output signal is at a "high"level (24V, current source) in normaloperation (no overload, overheating, shortcircuit). When the output signal switchesto "low" level (no power at output), Voutremains for 5 ms (nominal) at nominalload.Connection (signal common):Connection is made with respect to the"Signal GND" terminal (signal output).Important: Do not connect to the poweroutput (terminals + and -).

Permissible load: resistance - min.300 Ω, e.g. 24V relay, control lights (LEDsneed no series resistance), Evaluationlogic.For 5V signal: In order to receive a 5Vsignal: switch a 5V Zener diode (0.5 W)and 1 kΩ, resistance in parallel betweenthis output and the "Signal GND" terminal.

"Thermal Alarm" OutputFunction: Output gives warning shortlybefore and while overtemperature stateoccurs. Output can directly control a relayor a control light.Signaling: Output signal is at a "high"level (24V, current source) in normaloperation (no overtemperature). Atovertemperature, the output switches to"low". Only when the temperature in theunit increases further will the unit reduceits output current (power output).Connection and permissible load: sameas for "DC ok" output.

"Current Monitor" OutputFunction: Measuring the output current(power output). Output signal isproportional to the output current of theunit.Connection: Made with respect to the"Signal GND" terminal (signal output).Important: Do not connect to the poweroutput (terminals + and -).Signaling:Voltage measuring: Voltage at signaloutput is 1V per 10 A output current(Ri(voltmeter) > 100 k ohm )Current measurement: Current at signaloutput is 1 mA per 10 A output current(Ri(ammeter) < 100 W)

"Current Balance" In-/OutputFunction: Using these terminals, paralleloperating units ensure an equal loadsharing (active balancing). Balancing alsoworks reliably with decoupling diodes atthe power output (redundancy).

Connection: Connect together "CurrentBalance" outputs of all units involved.Important: Signal common here is the -terminal of the power output, not the"Signal GND". Do not connect the "SignalGND" terminals to each other!

"Signal GND" TerminalFunction: Grounding terminal for all signalterminals (not for "Current Balance").Connection instructions: Do not connectthis terminal with terminals + or - of theunit (not even over a load: risk ofoverload). Do not connect this terminalwith terminals of other units (not even withthe "Signal GND" terminal of another unit).Permissible load: Maximum current load:0.3 A. Terminal is fused internally with aself-healing fuse (polyswitch).

Shu

t Dow

nD

C o

kT

herm

al A

larm

Cur

rent

Mon

itor

Cur

rent

Bal

ance

Sig

nal-G

ND

1 k Ω

1 kΩ

5V/0.5 W

DC OkThermal A larm

Signal -GND

5V signal

1606-XL120E-31606-XL240E-3 and1606-XL240E-3C 1606-XL480F-3H 1606-XL720E-3 1606-XL960E-3 1606-XL960E-3S♣

Output Volts/Watts 24...28V/120 W 24...28V/240 W 48...56V/480 W 24...28V/720 W 24...28V/960 W

Input Voltage (47...63 Hz)3Ø, 400...500V AC

wide range; 450...820V DC

3Ø, 400...500V ACwide range;

450...820V DC

3Ø, 400V AC; 450...700V DC

3Ø, 400...500V AC widerange;

450...820V DC3Ø, 400...500V AC wide range

Operational Range 340...576V AC 340...479V AC 340...576V AC

Hold-up Time >16 ms (3Ø 400V AC)>10 ms (2Ø 400V AC)

>24 ms (3Ø 400V AC)>20 ms (2Ø 400V AC) >11 ms >10 ms (3Ø 400V AC) >15 ms (3Ø 400V AC)

Rated Input Current 3 x 0.5 A 3 x 0.8/0.7 A @400/500V 3 x 1.5 A 3 x 2.0 A 3 x 3.0 A

Efficiency typ. 89% typ. 92% typ. 92% typ. 92.5% typ. 92.5%

Output Voltage 24...28V24.5V preset

24...28V24.5V preset

48...56V48.1V preset

24...28V front panelpotentiometer

24...28Vfront panel potentiometer

Rated Output Current 5 A (@ 24V),4.3 A (@ 28V)

10 A (@ 24V)8.6 A (@ 28V)

10 A (@ 48V),9 A (@ 56V)

30 A (@ 24V),26 A (@ 28V)

40 A (@ 24V),35 A (@ 28V)

Power Boost 6 A 12 A (up to 288 W) 12.5 A 33 A 45 A

Ripple/Noise <25 mVPP <30 mVPP <50 mVPP

<20 mVPP (singleoperation)

<40 mVPP (paralleloperation)

<50 mVPP

Operating TemperatureRange (Tamb)

-10...+70 °C>60 °C with derating

0...+70 °C>60 °C with derating

0...+70 °C>60 °C with derating

Non-OperatingTemperature Range -40...+85 °C -40...+85 °C

MTBF♣ 410 000 hours 543 000 hours (3Ø),525 000 hours (2Ø) 310 000 hours 425 000 h @ 400V AC,

360 000 h @ 480V AC 305 000 hours 268 000 hours

Dimensions (W x H x D) 73 x 124 x 117 mm 89 x 124 x 117 mm 220 x 124 x 102mm 240 x 124 x 112 mm 275 x 124 x 117 mm

Weight 730 g 980 g 1800 g 2000 g 3300 g

Certifications/Standards 1, 2, 3, 4, 5, 6, 7

Special Features PFC choke

Overload behaviorselectable (FUSEMode/continuouscurrent); 2-phase

operation admissible,Single/parallel

operation (inclinedcharacteristic); PFC

choke; ‡

Single/paralleloperation(inclined

characteristic)selectable

(jumper); PFCchoke; ‡

PFC choke; ‡

Single/paralleloperation(inclined

characteristic)selectable

(jumper); passiveload sharing;PFC choke; ‡

Parallel operationthrough active current

sharing; Outputsignals (Power-Fail,Shut-Down, internal

current measurement,overtemperature

warning); PFC choke; ‡♣

01_1606_a.qxd 4/24/2008 12:24 PM Page 8-14

Page 14: Bulletin 1606 Product Overview - Elit€¦ · The Bulletin 1606 line of Power Supplies is designed with "reserve power" thereby eliminating the need to oversize your power supply

Bulletin 1606

Power Supplies

8-15Visit our website: www.ab.com/catalogs

Preferred availability cat. nos. are printed in bboolldd

!

1

2

3

4

5

6

7

8

9

10

11

12

13

1606-XL Special Modules

Specifications, Continued

1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 5) Safety standards = IEC/EN 60950, EN 50178, 6 EMC standards = EN 55011 (Class B), EN55022 (Class B), EN 61000-6-2, 7) = EMC standards = EN 61000-3-2 (A14), EN 50081-1

‡ Low inrush current§ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C

Buffer Module UPS DC/DC Converter N+1 Redundancy N+1 Redundancy

1606-XLBUFFER 1606-XLS240-UPS 1606-XLDC40A 1606-XL60DR 1606-XL120DR

Output Volts/Watts 22.5V...27.8V/480 W 22.5V...30V/240 W DC 5.1V ±1% 24V/60 W 24V/120 W

Input Voltage (47...63 Hz) 24V DC (24...28.8V DC) 24V DC (22.5...30V DC) 18...36V DC100...120V/200...240V AC

manual select; 160...375V DC

100...120/200...240VAC manual select;

210...375V DC

Operational Range 23...35V DC 22.5...30V DC 18...36V DC — 85...132/176...264VAC

Hold-up Time >0.2 s (20 A) battery dependent >10 ms (DC 24 Vin) >20 ms (AC 196V) >37 ms (AC 196V)

Rated Input Current charging current<600 mA

<0.12 A (standby)<1.3 A (charging) <2.9 A/<1.5 A <1.3 A (115V)/<0.7 A

(230V)<2.6 A (115V)/<1.4 A

(230V)

Efficiency N/A N/A typ. 82% typ. 86.5% typ. 89%

Output Voltage Vin -1V: 23...27.8V 22.5V fixed 22.4V 5.1V DC ±1%

selectable 4.5...5.5V 24V 24V

Rated Output Current 0...20 A 10 A 8 A 2.5 A 5 A

Power Boost — 15 A — — 6 A

Ripple/Noise <200 mVPP — <50 mVPP <30 mVPP <30 mVPP

Operating TemperatureRange (Tamb)

-10...+70 °C>60 °C with derating -25...+60 °C 0...+70 °C

>60 °C with derating-10...+70 °C

>60 °C with derating-10...+70 °C

>60 °C with derating

Non-OperatingTemperature Range -40...+85 °C -40...+85 °C

MTBF§ 480 000 hours — 510 000 hours 700 000 hours 480.000 hours

Dimensions (W x H x D) 64 x 124 x 102 mm 49 x 124 x 117 49 x 124 x 102 mm 49 x 124 x 102 mm 64 x 124 x 102 mm

Weight 740 g 530 g 470 g 470 g 620 g

Certifications/Standards 1, 2, 3, 5, 6 1, 2, 3, 5, 6 1, 5, 6 1, 2, 3, 5, 6 1, 2, 3, 5, 6, 7

Special Features Selectable bufferedvoltage; ‡

Inhibit replacementbattery buffering

MOSFET inverse batteryprotection; ‡

RDY relay contact; N+1 redundancy; plug connectors;

NEC Class 2 powersupply

RDY relay contact; N+1 redundancy; plug connectors

01_1606_a.qxd 4/24/2008 12:25 PM Page 8-15

Page 15: Bulletin 1606 Product Overview - Elit€¦ · The Bulletin 1606 line of Power Supplies is designed with "reserve power" thereby eliminating the need to oversize your power supply

Bulletin 1606

Power Supplies

8-16Visit our website: www.ab.com/catalogs

Preferred availability cat. nos. are printed in bboolldd

!

1

2

3

4

5

6

7

8

9

10

11

12

13

Specifications, Continued

1606-XL Special Modules, Continued

1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 5) Safety standards = IEC/EN 60950, EN 50178, 6 EMC standards = EN 55011 (Class B), EN55022 (Class B), EN 61000-6-2, 7) = EMC standards = EN 61000-3-2 (A14), EN 50081-1

§ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C

N+1 Redundancy N+1 Redundancy N+1 Redundancy N+1 Redundancy N+1 Redundancy

1606-XL240DR 1606-XLRED20-30 1606-XLRED40 1606-XLPRED 1606-XLSRED 1606-XLERED

Output Volts/Watts 24V/240 W 30 A Dualredundancy module

40 A Singleredundancy module

10 A Dualredundancy 20 A Dual redundancy

Input Voltage (47...63 Hz)

AC100...120/200...240V

manual select; DC 240...375V

DC 24V (max. 35V) DC 10...60V DC 10...60V

Operational Range 85...132/176...264 VAC 18...36 V DC 10...60V DC 10...60V DC

Hold-up Time >25 ms (AC 196V) — — — —

Rated Input Current <6 A (115V)/<2.8 A(230V) 20...30 A (max. 35 A) 0...40 A (max. 50 A)

Single input: 10 Amax.

Dual input: 16 Amax. total

Single input: 20 A max.Dual input: 20 A max. total

Efficiency typ. 89% typ. >97% typ. >97% — —

Output Voltage 24V Vin -0.5V typ. Vin -0.6V typ. Vin -0.9V typ. Vin -0.9V typ.

Rated Output Current 10 A 20...30 A (max. 35 A) 0...40 A (max. 50 A) 0...10 A 0...20 A

Power Boost 12 A — — — —

Ripple/Noise <30 mVPP — — — —

Operating TemperatureRange (Tamb)

0...+70 °C>60 °C with derating -10 °C...+70 °C -40 °C...+70 °C

>60 °C with derating-25 °C...+70 °C

>60 °C with derating

Non-OperatingTemperature Range -40...+85 °C

MTBF§ 390.000 hours — — — —

Dimensions (W x H x D) 120 x 124 x 102 mm 48 x 124 x 102 mm 48 x 124 x 117 mm 45 x 75 x 91 mm 32 x 124 x 102 mm 32 x 124 x 117 mm

Weight 980 g 625 g 646 g 136 g 290 g 350 g

Certifications/Standards 1, 2, 3, 5, 6 1, 2, 3, 6 1, 2, 3, 6 1, 2, 3, 6

Special FeaturesRDY relay contact; N+1 redundancy; plug connectors

Dual redundancymodule for 2x35 A;N+1 redundancy

Single redundancymodule for

2.5-50 A; N+1redundancy

Redundancy forDC 10...60Vapplications;

ABS/GL/RINA(Marine);

Class 1 Div. 2

Redundancy forDC 10...60Vapplications; Class 1 Div. 2

Redundancy forDC 10...60Vapplications;

Class 1 Div. 2;DC OK

01_1606_a.qxd 4/24/2008 12:25 PM Page 8-16

Page 16: Bulletin 1606 Product Overview - Elit€¦ · The Bulletin 1606 line of Power Supplies is designed with "reserve power" thereby eliminating the need to oversize your power supply

Bulletin 1606

Power Supplies

8-17Visit our website: www.ab.com/catalogs

Preferred availability cat. nos. are printed in bboolldd

!

1

2

3

4

5

6

7

8

9

10

11

12

13

Approximate DimensionsΑππροξιματε ΔιμενσιονσΑππροξιματε Διμενσιονσ ανδ Ωιρε Σιζε

Approximate dimensions are shown in inches (mm) unless otherwise indicated. Dimensions are not to be used for manufacturing purposes.Bulletin 1606 Dimensions Table

Depth measurement does not include DIN Rail.The wire sizes indicated refer only to the connection capability of the terminal.For proper operation, the correct wire size must be used (based on accurate determination of the electricalcharacteristics and loading of the system).

Catalog Number W [in. (mm)] H [in. (mm)] D [in. (mm)]

Wire Size(Input and Output unless

otherwise noted)

1606-XLS80E 1.26 (32) 4.88 (124) 4.02 (102) InputStranded

20...10 AWG (0.5...4 mm2)Solid

20...10 AWG (0.5...6 mm2)OutputStranded

28...12 AWG (0.3...2.5 mm2)Solid

28...12 AWG (0.3...4 mm2)

1606-XLS120E

1.57 (40) 4.88 (124) 4.61 (117)1606-XLSDNET4

1606-XLS240E2.36 (60) 4.88 (124) 4.61 (117)

Input/OutputStranded

20...10 AWG (0.5...4 mm2)Solid

20...10 AWG (0.5...6 mm2)

1606-XLS240EC

1606-XLS480E 3.31 (84) 4.88 (124) 4.61 (117)

1606-XLS480E-32.56 (65) 4.88 (124) 5.00 (127)

1606-XLS480E-3C

1606-XLSDNET8 2.36 (60) 4.88 (124) 4.61 (117)

1606-XLSRED 1.26 (32) 4.88 (124) 4.02 (102)

1606-XLE80E 1.26 (32) 4.88 (124) 4.02 (102)

1606-XLE120E

1.26 (32) 4.88 (124) 4.61 (117)

Input/OutputStranded

20...10 AWG (0.5...4 mm2)Solid

20...10 AWG (0.5...6 mm2)

1606-XLE120EC

1606-XLE120EE

1606-XLE120EN

1606-XLE240E

2.36 (60) 4.88 (124) 4.61 (117)

1606-XLE240EE

1606-XLE240EN

1606-XLE240EP

1606-XLE240F

1606-XLERED 1.26 (32) 4.88 (124) 4.61 (117)

1606-XLP15A

0.89 (22.5) 2.95 (75) 3.58 (91)

Input/OutputStranded

20...10 AWG (0.5...4 mm2)Solid

20...10 AWG (0.5...6 mm2)

1606-XLP15B

1606-XLP15E

1606-XLP25A

1.77 (45) 2.95 (75) 3.58 (91)

Input/OutputStranded

28...12 AWG (0.3...2.5 mm2)Solid

28...12 AWG (0.3...4 mm2)

1606-XLP30B

1606-XLP30E

1606-XLP36C

1606-XLP50B

1606-XLP50E

1606-XLP50EZ

1606-XLP50F

1606-XLP72E

1606-XLPRED

1606-XLP90B

2.87 (73) 2.95 (75) 4.06 (103)

1606-XLP90E-2

1606-XLP95E

1606-XLP100E

1606-XLP100E-2

1606-XLP100F

01_1606_a.qxd 4/24/2008 12:25 PM Page 8-17

Page 17: Bulletin 1606 Product Overview - Elit€¦ · The Bulletin 1606 line of Power Supplies is designed with "reserve power" thereby eliminating the need to oversize your power supply

Bulletin 1606

Power Supplies

8-18Visit our website: www.ab.com/catalogs

Preferred availability cat. nos. are printed in bboolldd

!

1

2

3

4

5

6

7

8

9

10

11

12

13

Approximate Dimensions, Continued

Bulletin 1606 Dimensions Table, ContinuedApproximate dimensions are shown in inches (mm) unless otherwise indicated. Dimensions are not to be used for manufacturing purposes.

Depth measurement does not include DIN Rail.The wire sizes indicated refer only to the connection capability of the terminal.For proper operation, the correct wire size must be used (based on accurate determination of the electricalcharacteristics and loading of the system).

Catalog Number W [in. (mm)] H [in. (mm)] D [in. (mm)]

Wire Size(Input and Output unless

otherwise noted)

1606-XL60D 1.93 (49) 4.88 (124) 4.02 (102)

Input/OutputStranded

20...10 AWG (0.5...4 mm2)Solid

20...10 AWG (0.5...6 mm2)

1606-XL180B 4.72 (120) 4.88 (124) 4.02 (102)

1606-XL480E

8.6 (220) 4.88 (124) 4.02 (102)

1606-XL480EP

1606-XL480EPT

1606-XL480GP

1606-XL480F

1606-XL120E-3 2.87 (73) 4.88 (124) 4.61 (117)

Input/OutputStranded

20...10 AWG (0.5...4 mm2)Solid

20...10 AWG (0.5...6 mm2)

1606-XL240E-3 3.50 (89) 4.88 (124) 4.61 (117)

1606-XL240E-3C 3.50 (89) 4.88 (124) 4.61 (117)

1606-XL480E-3 8.66 (220) 4.88 (124) 4.02 (102)

1606-XL480E-3W 5.91 (150) 4.88 (124) 4.76 (121)

1606-XL480F-3H 8.66 (220) 4.88 (124) 4.02 (102)

1606-XL720E-3 9.45 (240) 4.88 (124) 4.41 (112)

1606-XL960E-3

10.83 (275) 4.88 (124) 4.61 (117)

InputStranded

20...10 AWG (0.5...4 mm2)Solid

20...10 AWG (0.5...6 mm2)

1606-XL960E-3S

OutputStranded

22...8 AWG (0.5...10 mm2)Solid

22...8 AWG (0.5...16 mm2)

1606-XLS240-UPS 1.93 (49) 4.88 (124) 4.61 (117)

InputStranded

22...10 AWG (0.2...4 mm2)Solid

22...10 AWG (0.2...6 mm2)OutputStranded

22...14 AWG (0.2...2 mm2)Solid

22...14 AWG (0.2...2.5 mm2)

1606-XLBUFFER 2.56 (65) 4.88 (124) 4.02 (102) Input/OutputStranded

20...10 AWG (0.5...4 mm2)Solid

20...10 AWG (0.5...6 mm2)

1606-XLDC40A 1.93 (49) 4.88 (124) 4.02 (102)

1606-XLDNET4 2.56 (65) 4.88 (124) 4.02 (102)

1606-XLDNET8 4.72 (120) 4.88 (124) 4.02 (102)

Input/OutputStranded

22...10 AWG (0.2...2.5 mm2)Solid

22...10 AWG (0.2...2.5 mm2)

1606-XL60DR 1.93 (49) 4.88 (124) 4.02 (102) Input/OutputStranded

22...12 AWG (0.2...2.5 mm2)Solid

22...12 AWG (0.2...2.5 mm2)

1606-XL120DR 2.56 (64) 4.88 (124) 4.02 (102)

1606-XL240DR 4.72 (120) 4.88 (124) 4.02 (102)

1606-XLRED20-30 1.89 (48) 4.88 (124) 4.02 (102) Input/OutputStranded

20...10 AWG (0.5...4 mm2)Solid

20...10 AWG (0.5...6 mm2)

1606-XLRED40 1.89 (48) 4.88 (124) 4.61 (117)

01_1606_a.qxd 4/24/2008 12:26 PM Page 8-18

Page 18: Bulletin 1606 Product Overview - Elit€¦ · The Bulletin 1606 line of Power Supplies is designed with "reserve power" thereby eliminating the need to oversize your power supply

Bulletin 1606

Power Supplies

8-19Visit our website: www.ab.com/catalogs

Preferred availability cat. nos. are printed in bboolldd

!

1

2

3

4

5

6

7

8

9

10

11

12

13

Approximate Dimensions, Continued

Accessories1606-XLA Back of Panel Mounting Bracket for XL Power SuppliesInstead of snapping the power supply onto a DIN-rail, you also can mount it to the back of the panel. This set consists of two aluminumprofiles which replace the existing profiles at the back of the unit.Notes:

You need one set per unit.In addition, two screws are required per set (e.g. M5 x 12 or corresponding sheet-metal screws; they are not included in the set.)

Approximate Dimensions (mm)

1606-XLB Back of Panel Mounting Bracket for XLS and XLE Power SuppliesInstead of snapping the power supply onto a DIN Rail, you can mount it to the back of the panel. This set consists of two steel bracketswhich replace the existing DIN Rail aluminum brackets at the back of the unit.

Note:You need one set per unit.

mm A B C 1606-XLS80E 32 4.8 22.5 1606-XLS120E 40 5.3 29.5 1606-XLS240E 60 5.8 48.5 1606-XLS480E-3 65 6.3 40

N L PE

+ + - -

CBA

133

143

5.1

INPUT

OUTPUT

1606-XLSRED 32 4.8 22.5

Approximate Dimensions (mm)

01_1606_a.qxd 4/24/2008 12:26 PM Page 8-19

Page 19: Bulletin 1606 Product Overview - Elit€¦ · The Bulletin 1606 line of Power Supplies is designed with "reserve power" thereby eliminating the need to oversize your power supply

Bulletin 1606

Power Supplies

8-20Visit our website: www.ab.com/catalogs

Preferred availability cat. nos. are printed in bboolldd

!

1

2

3

4

5

6

7

8

9

10

11

12

13

Functional Design

1606-XL Redundancy CapabilitiesThe 1606-XL family has two cost effective methods for providing redundancy to applications that are critical and can not risk failure.

1606-XL60DR, XL120DR and XL240DR Redundant Power Supplies

The 1606-XL60DR, XL120DR and XL240DR are enhanced versions of the standard power supplies.Each device has internal diodes which provide isolation against DC bus problems corrupting working supplies.Provides "DC OK" output relay to allow remote monitoring of DC power status.Utilizes pluggable terminals for easy installation.

1606-XLRED20-30 and 1606-XLRED40 Redundancy Modules

The 1606-XLRED20-30 and 1606-XLRED40 allow redundant wiring of 20…40 A power supplies.Devices provide isolation of power supplies via diodes.Provide remote monitoring of DC power status of each power supply.A single XLRED20-30 can be used per pair of identical 20 or 30 A power supplies.One XLRED40 is required for every 40 A power supply.

1606-XLPREDWhen used in 1 + 1 redundant systems (such as XLRED20-30) limited to 8 A (short circuit) per power supplyWhen used in 1 + 1 redundant system (such as XLRED40) limited to 13 A (short circuit)See product technical data sheets for more application information.

1606-XLSRED/1606-XLEREDWhen used in 1 + 1 redundant systems (such as XLRED20-30) limited to 10 A (short circuit) per power supplyWhen used in 1 + 1 redundant system (such as XLRED40) limited to 20 A (short circuit)See product instruction manual for more application information.

02_1606_b.qxd 4/21/2008 9:28 AM Page 8-20

Page 20: Bulletin 1606 Product Overview - Elit€¦ · The Bulletin 1606 line of Power Supplies is designed with "reserve power" thereby eliminating the need to oversize your power supply

Bulletin 1606

Power Supplies

8-21Visit our website: www.ab.com/catalogs

Preferred availability cat. nos. are printed in bboolldd

!

1

2

3

4

5

6

7

8

9

10

11

12

13

Product Overview Technical

1606-XLBufferFeatures

Buffering for 24V loadsGuaranteed hold-up time: 0.2 s/20 A…3.6 s/1 AFit for industrial use: Energy storage in electrolytic caps., noaccumulatorsClear status indication by Status LED and signalling terminalsNo batteries requiring replacement

Short DescriptionThe buffer unit is a supplementary device for regulated 24V DCpower supplies. It buffers load currents during typical mains faultsand switching events or load peaks.

Working principle

DC

BufferCharge

Discharge

In times when the power supplyprovides sufficient voltage, thebuffer unit stores energy inintegrated electrolytic capacitors.In case of a mains voltage fault,this energy is released again in aregulated process.

Bridges mains faults without interruption

DC

AC

Buffer Unit

Statistics show that 80% of allmains faults last less than 0.2 s.These mains faults are completelybridged by the buffer unit and willhave no influence on the DCpower. This increases thereliability of the system as awhole.

Extended hold-up time

DC

AC

Buffer Unit

Once the main power fails or isswitched off, the buffer unit willcontinue to provide the loadcurrent for a defined period oftime. Process data can be savedand processes can be terminatedbefore the DC power switches off.Controlled restarts aresubsequently possible.

Easy to handle, expandable, and maintenance-free

AC

DC

PowerSupply

Buffer Unit

Charge

The buffer unit does not requireany control wiring. It can beadded in parallel to the loadcircuit at any given point. Anygiven number of buffer units canbe installed in parallel to increasethe output capacity or the hold-uptime. The dual terminals allow foreasy wiring.

Operating Modes

Activation Threshold

“22.5V fixed” Buffering starts if terminal voltage <22.5V, voltageis kept at 22.5V.

“Vin -1V”

Buffering starts if terminal voltage decreases bymore than 1V, faster than typ. 0.54V/s. Voltage iskept at that level. Buffering ends when voltageincreases once more by 1V.

Noise (spikes) >200 mVPP (20 MHz bandw., 50 Ω measurement,buffer operation only)

Over voltage protection limited to max. ±35V

Hold-up Time

0,1 s

1,0 s

10,0 s

100,0 s

1000,0 s

10mA 100mA 1.000mA 10.000mA 100.000mA

BufferCurrent

BufferTime

10mA 100mA 1A 10A 100A

0.1s

1s

10s

100s

1000s

Operating Indicators and Elements

A

B

C

D

A - Signaling terminals:

B - Jumper back-upthreshold:

C - Status LEDIndicates charge status of buffercapacitor array

D - Power In/Out terminals:dual terminals

+ (positive)- (negative)

7 Active: unit is buffering

9 Inhibit: Initiates bufferdischarging, inhibitsrecharging of capacitorarray

8 Ready: unit is on stand-by

Housing connection ‘chassisground’

Position 2-3: DC 22.5Vfixed. Voltage bufferingstarts at Vin less than 22.5V

Position 1-2: variable:Vin -1V. Buffering if voltagedecreases faster thantypical 0.54V/s and greaterthan 1V

02_1606_b.qxd 4/21/2008 9:28 AM Page 8-21

Page 21: Bulletin 1606 Product Overview - Elit€¦ · The Bulletin 1606 line of Power Supplies is designed with "reserve power" thereby eliminating the need to oversize your power supply

Bulletin 1606

Power Supplies

8-22Visit our website: www.ab.com/catalogs

Preferred availability cat. nos. are printed in bboolldd

!

1

2

3

4

5

6

7

8

9

10

11

12

13

Product Overview Technical, Continued

1606-XLS DC UPSFeatures

Short DescriptionThe DC UPS is a supplementary device to a 24V power supply. It provides back-up power to bridge dips, sags, or brief losses of power usinga 12V battery. Based on the battery you select, you can achieve hold-up times anywhere from a few minutes to several hours.

Working principleIn times when the power supply provides sufficientvoltage, the DC UPS charges the 12V battery.When input power fails, the battery voltage will beboosted to a 24V level through a boost converterand the energy will be released in a regulatedprocess to the load.

Integrated in the DC UPS is a sophisticated batterymanagement system. This battery managementsystem incorporates a battery charger, deepdischarge protection, and overload protection whichtogether increase the service life of the battery.

In addition, there are extensive protective featuresthat self-protect the unit from damage along withdiagnostic and monitoring functions that aid introubleshooting.

Extended hold-up timeThe modular design of the DC UPS allows forflexible battery options. The design will acceptvalve regulated, lead-acid batteries between 3.9Ah– 27Ah. The modularity of the system enables youto match the battery with your applicationrequirements.

Extensive Diagnostic & Monitoring FunctionsProtective Features:

E - Signal contacts:

A - Status LED (green):

B - Diagnosis LED (yellow):

D - Adjustor:

ABC

D

E

Requires only one 12V battery Electronically protected against output overloadsFlexible battery options, modular system Extensive battery management including battery quality and installation testsRegulated output voltage in buffer mode Soft charger for optimum battery life50% power reserves Extensive diagnostic and monitoring functions

Wrong battery voltage (24V instead of 12V) Deep discharge (battery) protectionWrong battery polarity Wrong polarity on input terminalsToo high ambient temperature Over-voltage protection

(malfunctioning of the internal regulation loops)Output overload or output short-circuit

Ready: Battery is charged > 85%, no wiring failure isrecognized, input voltage is sufficient and inhibitsignal is not active.Charging: Battery is charging and battery capacity isbelow 85%.Buffering: Unit is in buffer mode.

Replace battery: Indicates a battery which failed thebattery quality test (SCH test). Battery should bereplaced soon.Buffer time expired: Output has switched off due tosettings of buffer time. The signal will be stored anddisplayed for 15 minutes.Inhibit active: Indicates that buffering is disabled dueto an active inhibit signal.

Overload: Output has switched off, due to longoverload in buffer mode or due to high temperatures.

C - Check wiring LED (red):

Check wiring between DC UPS and battery, as well asthe battery itself. Also indicates when input voltage isnot in range.

Inhibit input (contact 7&8):

Ready (contact 1-2):

Buffering (contact 3-4):

Contact is closed when unit is buffering.

Replace battery (contact 5-6):

Contact is closed when input voltage is sufficient andbattery quality test (SCH test) indicates a negative result,three times in a row.

Contact is closed when battery is charged more than85%, no wiring failure is recognized, input voltage issufficient, and inhibit signal is not active.

The inhibit input disables buffering. In normal mode, a staticsignal is required. In buffer mode, a pulse with a minimumlength of 250 ms is required to stop buffering. The inhibit isstored and can be reset by cycling the input voltage.

Buffer time limiter: User accessible switch which limits the maximum buffer timein a buffer event, to save battery capacity.End-of-charge voltage: User accessible potentiometer which sets the end-of-charge voltage. Adjust the potentiometer according to the expected batterytemperature.

02_1606_b.qxd 4/21/2008 9:28 AM Page 8-22


Recommended