+ All Categories
Home > Documents > Bus Bar Protection

Bus Bar Protection

Date post: 25-Nov-2015
Category:
Upload: darrell-edwards
View: 22 times
Download: 0 times
Share this document with a friend
Description:
Protection
Popular Tags:
28
Bus Bar Protection Bus Bar Protection
Transcript
  • Bus Bar ProtectionBus Bar Protection

  • Outline

    Bus arrangements Bus components Bus protection techniques

  • 1 2 3 n-1 n

    ZONE 1

    - - - -

    Distribution and lower transmission voltage levels No operating flexibility Fault on the bus trips all circuit breakers

    Single bus - single breaker

  • ZONE 1 ZONE 2

    Distribution and lower transmission voltage levels Limited operating flexibility

    Multiple bus sections - single breaker with bus tie

  • ZONE 1

    ZONE 2

    Transmission and distribution voltage levels Fault on a bus disconnects only the circuits

    connected to that bus

    Double bus - single breaker with bus tie

  • ZONE 1

    MAIN BUS

    TRANFER BUS

    Increased operating flexibility A bus fault requires tripping all breakers Transfer bus for breaker maintenance

    Main and transfer buses

  • ZONE 1

    ZONE 2

    Very high operating flexibility Fault on a bus disconnects only the circuits

    connected to that bus Transfer bus for breaker maintenance

    Double bus single breaker w/ transfer bus

  • ZONE 1

    ZONE 2

    High operating flexibility Line protection covers bus section between two CTs

    Double bus - double breaker

  • ZONE 1

    ZONE 2

    Used on higher voltage levels More operating flexibility Requires more breakers Middle bus sections covered by line or other equipment

    protection

    Breaker-and-a-half bus

  • Higher voltage levels High operating flexibility with minimum breakers

    B1 B2

    TB1

    L1 L2

    L3 L4

    TB1

    Ring bus

  • Bus components breakers

    SF6, EHV & HV - Synchropuff

    Low Voltage circuit breakers

    BUS 2

    CB 1

    BUS 1

    ISO 1 ISO 2

    ISO 3BYPASS

  • -+

    F1aF1c

    Contact Input F1a OnContact Input F1c On

    F1b

    ISO

    LATO

    R 1

    ISOLATOR 1 OPEN

    7B 7A

    BUS 1

    -

    +

    F1aF1c

    Contact Input F1a OnContact Input F1c On

    F1b

    ISO

    LATO

    R 1

    ISOLATOR 1 CLOSED

    7B 7A

    BUS 1

    Disconnect switches & auxiliary contacts

    BUS 2

    CB 1

    BUS 1

    ISO 1 ISO 2

    ISO 3BYPASS

  • BUS 2

    CB 1

    BUS 1

    ISO 1 ISO 2

    ISO 3BYPASS

    Current Transformers

    Oil insulated current transformer (35kV up to 800kV)

    Gas (SF6) insulated current transformer

    Bushing type (medium voltage switchgear)

  • Bus Bar Protection Requirements

    High bus fault currents due to large number of circuits connected: CT saturation often becomes a problem as CTs may not be sufficiently

    rated for worst fault condition case large dynamic forces associated with bus faults require fast clearing

    times in order to reduce equipment damage

    False trip by bus protection may create serious problems: service interruption to a large number of circuits (distribution and sub-

    transmission voltage levels) system-wide stability problems (transmission voltage levels)

    With both dependability and security important, preference is always given to security

  • Bus Protection Techniques

    Overcurrent (unrestrained or unbiased) differential

    Overcurrent percent (restrained or biased) differential

    High-impedance bus differential schemes Low-impedance bus differential schemes

  • Overcurrent (unrestrained) Differential

    Differential signal formed by summation of all currents feeding the bus

    CT ratio matching may be required

    On external faults, saturated CTs yield spurious differential current

    Time delay used to cope with CT saturation

    51

  • Relay

  • AdvantagesSimpleLow costDifferent ratios of CTs can be used with the help of Aux CT

    High operating timeAll CTs must have equal ratioLow sensitivityDegree of CT saturation level to be very low

    Disadvantages

  • High Impedance relay

    R

    Relay

  • High Impedance Differential Operating signal created by

    connecting all CT secondaries in parallel

    o CTs must all have the same ratioo Must have dedicated CTs

    Overvoltage element operates on voltage developed across resistor connected in secondary circuit

    Accuracy dependent on secondary circuit resistance

    o Usually requires larger CT cables to reduce errors higher cost

    Cannot easily be applied to reconfigurable buses and offers no advanced functionality

    59

  • AdvantagesIt avoids the problem of unequal CT performances.It uses high impedance voltage relay.Highly sensitive and fast.

    DisadvantagesAll CTs must have equal Turns ratioAll CTs must have high Knee point voltage preferably twice the nominal valueThe CT must be exclusively used for differential protection.

  • Percent Differential

    Percent characteristic used to cope with CT saturation and other errors

    Restraining signal can be formed in a number of ways

    No dedicated CTs needed Used for protection of re-

    configurable buses possible

    5187

  • Low Impedance Percent Differential( Digital relay) Individual currents sampled by protection and summated digitally

    o CT ratio matching done internally (no auxiliary CTs)o Dedicated CTs not necessary

    Additional algorithms improve security of percent differential characteristic during CT saturation

    Dynamic bus replica allows application to reconfigurable buseso Done digitally with logic to add/remove current inputs from differential

    computationo Switching of CT secondary circuits not required

    Low secondary burdens Additional functionality available

    o Time-stamped event recordingo Breaker failure protection

  • Relay

  • Low Impedance Differential (Distributed)

    Data Acquisition Units (DAUs) installed in bays

    Central Processing Unit (CPU) processes all data from DAUs

    Communications between DAUsand CPU over fiber using proprietary protocol

    Sampling synchronisation between DAUs is required

    Perceived less reliable (more hardware needed)

    Difficult to apply in retrofit applications

    52

    DAU

    52

    DAU

    52

    DAU

    CU

    copper

    fiber

  • Low Impedance Differential (Centralized)

    All currents applied to a single central processor

    No communications, external sampling synchronisation necessary

    Perceived more reliable (less hardware needed)

    Well suited to both new and retrofit applications.

    52 52 52

    CU

    copper

  • Bus bar protections

    Standard practice400 kV Duplicated main protection per zone (bus) Two prot connected to different CT cores Preferably, both main protections on different principle Two out of two principle(main 1 & 2) for tripping

    220 kV / 132 kV One main protection per zone (bus) Single CT core is switched to respective main zone through switching relays Common check zone for all the buses connected to an independent CT core other

    than main protection Tripping based on operation of both main and check zone

    27


Recommended