10
© E T HP BU Bushing Group Resin Impregnated Paper condenser core bushings with fiberglass tube and Silicone rubber sheds
Transcript
Page 1: Bushing Group - cigre.cl Group Resin Impregnated ... BCTC British Columbia Transmission Company PacifiCorp, Portland OR ... West coast, USA; RIP 550 kV Transformer Bushings

© E T HP BU

Bushing Group

Resin Impregnated Paper condenser core bushings

with fiberglass tube and Silicone rubber sheds

Page 2: Bushing Group - cigre.cl Group Resin Impregnated ... BCTC British Columbia Transmission Company PacifiCorp, Portland OR ... West coast, USA; RIP 550 kV Transformer Bushings

Page 2 E T HP BUOct. 2010; Cigre meeting Santiago / Chile

Locations

TSF – St. Louis/Basel

TCB – Toronto

TUK – Hebburn

HSP - Cologne

TCN – Shenyang

Customised solutions

High reputation in

service business

Technology leader

UHV AC

Market leader in China

Proven technology

OIP/RIP

High degree of

standardisation

CoC - OIP

High flexibility for

customer demand

Strong in ANSI market

Short lead time

Top of innovation

Technology leader

Market leader RIP AC/DC

Customised solutions

Page 3: Bushing Group - cigre.cl Group Resin Impregnated ... BCTC British Columbia Transmission Company PacifiCorp, Portland OR ... West coast, USA; RIP 550 kV Transformer Bushings

Page 3 E T HP BUOct. 2010; Cigre meeting Santiago / Chile

Technologies for transformer bushings

Bushing core, made of resin impregnated paper

RIP core insulator (activ part)

crêpe insulating paper with condenser layered,

dried under temperature and vacuum,

impregnated under vacuum with epoxy resin.

+ no oil losses possible

+ no risk of fire (non-inflammable)

+ no risk of explosions

+ excellent seismic behaviour

+ lower weight - easier handling

+ lower long term costs

+ oil and gas tight system

+ no housing for oil end necessary

+ operates with damaged housing temporarily

+ core can be fixed to flange

+ partial discharge free

+ excellent ageing experience

+ no loss of insulation media

o max. temperature < 120 or higher

- higher production costs

RIP

condenser layers

Page 4: Bushing Group - cigre.cl Group Resin Impregnated ... BCTC British Columbia Transmission Company PacifiCorp, Portland OR ... West coast, USA; RIP 550 kV Transformer Bushings

Page 4 E T HP BUOct. 2010; Cigre meeting Santiago / Chile

Characteristics of composite insulators

+ hydrophobic surfaces

+ good characteristics under pollution

+ high life expectancy

+ low leakage current

+ low manufacturing tolerances

+ low weight - easier handling

+ high mechanical stability

+ elasticity in case of bending

+ optimal solution for seismic stress

+ no damage of splintering, no bursting

+ no danger of scattering

+ pressure resistant

+ significantly shorter delivery times

- high price

Different technologies for outdoor end housing…

Characteristics of porcelain

+ smooth glazed surfaces

+ surface leakage current resistant

+ high life expectancy

+ mechanical stability

+ easy forming

+ economically reasonable material

+ low price

- restricted bending strength

- high manufacturing tolerances

- sensitive with respect to temperature changes

- high danger of scattering in case of bursting

- restricted pressure resistance

- low impact strength

- long delivery times

- high weight

Page 5: Bushing Group - cigre.cl Group Resin Impregnated ... BCTC British Columbia Transmission Company PacifiCorp, Portland OR ... West coast, USA; RIP 550 kV Transformer Bushings

Page 5 E T HP BUOct. 2010; Cigre meeting Santiago / Chile

silicon sheds

Fiber glass reinforced

laminate epoxy resin tube

aluminium

cast flange

RIP active part

dry material foam

The Gap is filled with a dry material foam

+ used for more than 20 years

+ no compensation volume needed

+ no ageing problems

+ no leakage possible

+ additional sealing effect

+ no fire-danger in case of damage

+ flexible in a wide temperature range

Composite insulator structure and secondary insulation

Page 6: Bushing Group - cigre.cl Group Resin Impregnated ... BCTC British Columbia Transmission Company PacifiCorp, Portland OR ... West coast, USA; RIP 550 kV Transformer Bushings

Page 6 E T HP BUOct. 2010; Cigre meeting Santiago / Chile

One of the major advantages of silicone

polymer insulators over porcelain:

High hydrophobicity over the whole lifetime !

Surface is Water repellant & self cleaning

...even through thick layers of contamination

Different technologies for outdoor housings…

Composite insulators properties

Page 7: Bushing Group - cigre.cl Group Resin Impregnated ... BCTC British Columbia Transmission Company PacifiCorp, Portland OR ... West coast, USA; RIP 550 kV Transformer Bushings

Page 7 E T HP BUOct. 2010; Cigre meeting Santiago / Chile

Seismic references

For well over 20 years, Electric Utilities on the West Coast of the USA and Canada have used almost exclusively HSP RIP condenser core + composite insulator bushings.NO seismic event failure to any of those bushings.BCTC & BC Hydro - 145,230,245,420,550 kV class

BPA Bonneville Power Administration- 196,230,550 kV class

PacifiCorp, Portland OR- 550 kV class

Nevada Power Company - 138,196 kV class

PG&E Pacific Gas and Electric Company- 69,123,138,196,230,550 kV class

SCE Southern California Edison- 230,550 kV class

LADWP Los Angeles Department of Water & Power- 196,230,550 kV class

SDG&E San Diego Gas & Electric- 230,550 kV class

Page 8: Bushing Group - cigre.cl Group Resin Impregnated ... BCTC British Columbia Transmission Company PacifiCorp, Portland OR ... West coast, USA; RIP 550 kV Transformer Bushings

Page 8 E T HP BUOct. 2010; Cigre meeting Santiago / Chile

HSP`s Customer References

BC Hydro British Columbia Hydro

BCTC British Columbia Transmission Company

PacifiCorp, Portland OR

PG&E Pacific Gas and Electric Company

SCE Southern California Edison

LADWP LosAngeles Depart.of Water & Power

SDG&E San Diego Gas & Electric

Mr.Hanxin Zhu

Phone: +001-604-5282314

Mail: [email protected]

Matt Weisensee

Phone: +001-503-813-6901

Mail: [email protected]

Ms Jennifer Yu

Phone: +001-510-874-2628

Mail: [email protected]

Mr. Dong S. Kim

Phone: +001.909.274.61677

Mail: [email protected]

Mr. Bina Vatanpour

Phone: +001.213.367.2212

Mail: [email protected]

Mr. Robert J. Mayer

Phone: +001.858.654.1119

Mail: [email protected]

ContactCustomer

Page 9: Bushing Group - cigre.cl Group Resin Impregnated ... BCTC British Columbia Transmission Company PacifiCorp, Portland OR ... West coast, USA; RIP 550 kV Transformer Bushings

Page 9 E T HP BUOct. 2010; Cigre meeting Santiago / Chile

Seismic test of a RIP-

550kV-transformer-

bushing on the shake

table in worst-case

service position

Seismic test reports\Seismic Test-

Qualification Report SETFta 1800-550-

2000 spez.pdf

Specifications\SETFta 1800-550-2000

spez (600258).pdf

Time history test acc.

to IEEE 693

Materials combination

for high mechanic

demands

West coast, USA; RIP 550 kV Transformer Bushings

Materials combination for high mechanic demands

Seismic test according IEEE 693

Page 10: Bushing Group - cigre.cl Group Resin Impregnated ... BCTC British Columbia Transmission Company PacifiCorp, Portland OR ... West coast, USA; RIP 550 kV Transformer Bushings

Page 10 E T HP BUOct. 2010; Cigre meeting Santiago / Chile

Weight: 4 to

Length: 13500 mm

Yun-Guang, China; RIP 800 kV UHVDC Transformer Bushings

This is the first bushing worldwide for 800 kV

UHVDC transmission in RIP dry technology.


Recommended