24
Air Handling Units BWY Series Chilled/Hot water BWY03 thru BWY25 3 TR thru 30 TR 10 KW thru 100 KW
Transcript
Page 1: BWY Series

7/27/2019 BWY Series

http://slidepdf.com/reader/full/bwy-series 1/24

Air Handling UnitsBWY Series

Chilled/Hot water 

BWY03 thru BWY25

3 TR thru 30 TR

10 KW thru 100 KW

Page 2: BWY Series

7/27/2019 BWY Series

http://slidepdf.com/reader/full/bwy-series 2/24

Company Business

Zamil Air Conditioners was founded in 1974 as one of the first air conditioning business to be established in Saudi Arabiaand today is a leading international manufacturer of air conditioning systems and is No. 1 in the Middle East.

Zamil Air conditioners manufactures both consumer and central air conditioners and has sales operations in over 55

countries in the Middle East, Europe, Africa and Asia.

The company’s operations are structured into four Strategic Business Units (SBUs) supporting five in-house product andservice brands as well as a number of international brands under the OEM sales.

The five in-house brands are Classic, Cooline, CoolCare, Clima Tech and Geoclima.

The four SBUs are:1. Consumer Business Unit supporting Classic, Cooline, GE and OEM brands for consumers.

2. Unitary & Applied Business Unit supporting Classic, Cooline, GE and OEM brands for commercial and industrialcustomers.

3. Zamil CoolCare providing engineering & project management services, HVAC maintenance, retrofit services and parts.

4. Geoclima srl is an independent business supporting other SBUs for their requirement of Chillers & Double skin AHU’s.

The first three SBUs - Consumer Products, Unitary & Applied Products and CoolCare Service direct their businessoperations from the corporate headquarters at Dammam, Saudi Arabia.

Geoclima has its engineering & production departments located at Monfalcone, Italy and has a design center in Austria.

All the four SBUs, while operating independently, supplement each other’s activities in a way that makes synergy work at

its best and achieve the corporate goals of maximizing customer satisfaction.

Factories and Productions

Zamil Air Conditioners has two manufacturing plants in Dammam, Saudi Arabia and has one speciality production facility

in Italy operated by Geoclima.

The company can produce up to 550,000 Room Air Conditioners, 300,000 Mini-Split systems and 50,000 Central AirConditioning systems per year.

Quality & Product Certificates

The Quality systems and policies at Zamil Air Conditioners comply with the required ISO 9001:2000 certification.

Zamil Air Conditioners is the first company in Saudi Arabia to receive the SASO (Saudi Arabia’s Standard Organization)Certificate for Room Air Conditioners. ZAC's products are also certified with:

1. CE (Council of European Community)

2. UL (Underwriters Laboratory)

3. Eurovent

4. DEMKO

5. ETL

Other awards include the prestigious Engineering Excellence Award of General Electric and the inaugural Prince Mohammedbin Fahd Al Saud Award for Factory Safety.

Our Products

In addition to the consumer products such as the Room Air Conditioners (RAC) and the Mini Splits, Zamil Air Conditionersmanufacturers a host of residential, commercial and industrial air conditioners. This broad range extends from the Con-

cealed Units up to 5 tons, the Ducted Splits up to 30 tons, the Packaged Units up to 90 tons, the Single and Double SkinAir Handling Units up to 70,630 CFM and the Water Chillers up to 660 tons cooling capacity.

Page 3: BWY Series

7/27/2019 BWY Series

http://slidepdf.com/reader/full/bwy-series 3/24

Contents Page

Outstanding features ................................................................................................................................ 2

Model decoding ........................................................................................................................................ 3

Blower drive options ................................................................................................................................. 4

Standard specifications ............................................................................................................................ 4

Options and accessories .......................................................................................................................... 5

Physical data ............................................................................................................................................ 6

Cooling capacities ................................................................................................................................. 7-8

Fan performance data ......................................................................................................................... 9-10

Electrical data .................................................................................................................................... 11-13

Dimensions........................................................................................................................................ 14-17

Dimensions, heater box .......................................................................................................................... 18

Typical schematic wiring diagram ........................................................................................................... 19

Controls and sequence of operation ....................................................................................................... 20

Installation instructions ........................................................................................................................... 21

Recommended spare parts .................................................................................................................21

INDEX

CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS.

THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

1

Page 4: BWY Series

7/27/2019 BWY Series

http://slidepdf.com/reader/full/bwy-series 4/24

*  INDEPENDENT HORIZONTAL OR VERTICAL AIR DISCHARGE UNITS 

*  LOW CEILING HEIGHT REQUIREMENTS 

*  CHILLED & HOT WATER COILS 

*  ONE SIDE TOTAL SERVICE ACCESSIBILITY 

*  SINGLE POINT POWER ENTRY 

*  UV FLOW™ LIGHT EMITTERS FOR ENHANCED IAQ (INDOOR AIR QUALITY) 

*  NUMBER CODED WIRES 

*  INSULATED DRAIN PAN 

*  FACTORY INSTAL LED OPTIONS UPON REQUEST 

*  SMAL L FOOTPRINT 

*  L IGHT WEIGHT 

*  PRE-PAINTED CAB INETS WITH FIBERGLASS INSULATION 

*  LARGE CHOICE OF HEATERS; FACTORY OR FIELD INSTAL LATION 

*  STANDARD OR OPTIONAL MOTORS; FACTORY OR FIELD INSTAL LATION 

*  ALUMINUM OR SYNTHETIC FILTERS 

*  UL L ISTED MAJOR COMPONENTS 

OUTSTANDING FEATURES

2

Page 5: BWY Series

7/27/2019 BWY Series

http://slidepdf.com/reader/full/bwy-series 5/24

1,2&3

BASIC

4&5

FACEAREA

(SQ.FT.)

7

ELECTRICAL

SUPPLY

(V-Ph-Hz)

9

BLOWER

MOTOR

12

COILFINS

13

FILTER

11

HEATER

OPTIONS

     (       k     W     /      S      T     A     G      E     )  

14

UNIT

ACCESSO

RIES

BWY

AIRHANDLING

UNIT

(CHILLEDWATER)

03

05

     C :208/230-1-60

H:208/230-3-60

M:380-3-60

(4WIRE)

F:460-3-60

U:0.5HPODP

W

:0.75HPODP

W

:0.75HPODP

Y

:1HPODP

A:ALUMINUM

FIN

B:COATED

ALUMINUM

FIN

C:COPPERFIN

N

:NO

HEATER

A

:5/1

B

:6/1

C

:7.5/1

            *            *

N

:STD.UNIT

.

NOACCESORIES

MO

DELDECODING

N:DIRECT

DRIVE

10

DRIVE

OPTIONS

15

OTHER

OPTIONS

N:STD.UNIT

V:VOLTFREE

CONTACTS

           *

6

ARRANG

EMENT

H:HORIZONTAL

V:VERTICAL

N:NOFILTER

E:1/2"ALUMINUM

F:1/2"SYNTHETIC

A:1"ALUMINUM

C:1"SYNTHETIC

8

COILAPPLICATION

A:STD.3ROW

CHILLED

WATERCOIL

B:2ROW

CHILLED

WATER

+1ROW

HEATINGSPLITCOIL

NOTES:  *

–BlowermotorON/OF

Fandtripindication.

           *           *

–Heatercapacitywillbe7kW

forsinglephasepowersupply.

07

10

14

18

25

MODELS:BWY03-BW

Y05

MODELS:BWY07-BW

Y25

1,2&3

BASIC

4&5

FACEAREA

(SQ.FT.)

BWY

AIRHANDLING

UNIT

(CHILLEDWATER)

H:208/230-3-60

M:380-3-60

(4WIRE)

F:460-3-60

A:ALUMINUM

FIN

B:COATED

ALUMINUM

FIN

C:COPPERFIN

N

:NOHEATER

A

:5/1

B

:6/1

C

:7.5/1

D

:10/2

E

:12/2

F

:15/2

G

:20/2

H

:25/2

J

:30/2

N

:NOHEATER

E

:12/2

F

:15/2

G

:20/2

H

:25/2

J

:30/2

K

:35/2

L

:40/2

N

:STD.UNIT

.

NOACCESORIES

J:ALT.I

K:ALT.II

N:STD.UNIT

V:VOLTFREE

CONTACTS

           *

H:HORIZONTAL

V:VERTICAL

A

:STD.3ROW

CHILLED

WATERCOIL

B

:2ROW

CHILLED

WATER+1ROW

HEATINGSPLITCOIL

C

:STD.4ROW

CHILLED

WATERCOIL

D

:3ROW

CHILLED

WATER+1ROW

HEATINGSPLITCOIL

NOTES:  *

–BlowermotorON/OF

Fandtripindication.

D:2HPODP

E

:3HPODP

D:2HPODP

E

:3HPODP

G

:5HPODP

J

:7.5HPODP

J

:7.5HPODP

L

:10HPODP

FORBWY07

FORBWY10

FORBWY14/18

FORBWY25

FORBWY07

N:NOFILTER

E:1/2"ALUMINUM

F:1/2"SYNTHETIC

A:1"ALUMINUM

C:1"SYNTHETIC

N:NOFILTER

A:1"ALUMINUM

B:2"ALUMINUM

C:1"SYNTHETIC

D:2"SYNTHETIC

N:NOFILTER

B:2"ALUMINUM

D:2"SYNTHETIC

FORBWY10,14&18

FORBWY25

7

ELECTRICAL

SUPPLY

(V-Ph-Hz)

9

BLOWER

MOTOR

12

COILFINS

13

FILTER

11

HEATER

OPTIONS

     (       k     W     /      S      T     A     G      E     )  

14

UNIT

ACCESSO

RIES

10

DRIVE

OPTIONS

15

OTHER

OPTIONS

6

ARRANG

EMENT

8

COILAPPLICATION

FORBWY18/25

3

Page 6: BWY Series

7/27/2019 BWY Series

http://slidepdf.com/reader/full/bwy-series 6/24

BLOWER DRIVE OPTIONS

MODELNUMBER OPTION

MOTOR BLOWER APPROX. SPEEDCHANGE PER

PULLEYTURN (RPM)

PULLEYPITCH DIA.

(INCH)

SPEED RANGE (RPM)

MINIMUM MAXIMUM

PULLEYPITCH DIA.

(INCH)HP RPM

BWY07

BWY10

BWY14

BWY18

BWY25

ALT. I

ALT. II

ALT. I

ALT. II

ALT. I

ALT. II

ALT. I

ALT. II

ALT. I

ALT. II

2

3

23

5

 7.5

5

7.5

7.5

10

1750

1750

1750

1750

1750

1750

1750

1750

1750

1750

2.7 - 3.7

2.7 - 3.7

3.1 - 4.1

3.1 - 4.1

3.7 - 4.7

4.3 - 5.5

3.7 - 4.7

4.3 - 5.5

4.3 - 5.5

4.3 - 5.5

893

964

733

875

809

940

809

875

800

800

1156

1321

970

1157

1028

1203

1028

1120

1023

1023

5.6

4.9

7.4

6.2

8.0

8.0

8.0

8.6

9.4

9.4

62

71

40

47

37

44

37

40

44

44

STANDARD SPECIFICATIONS

A. GeneralThese Air Handling Units are factory fabricated and assembled, consisting of forward-curved fan section with blower

motor, chilled/hot water coil, electric heaters (optional), filters & electrical control box and are suitable for indoor applica-

tions. The unit is ready to operate when connected to piping, power/controls and air ducts or plenums.

They should be ordered separately as horizontal air discharge or vertical air discharge units as per application require-

ments.

B. Unit EnclosureCasing Panels are of heavy gauge (G-90) galvanized steel. Removable access panels are provided for inspection and

access to all internal parts. These panels are insulated with 1/2" thick fiberglass insulation to prevent condensation from

forming on the unit casing. Insulation meets the requirements of NFPA 90A and is protected against deterioration and

errosion from air currents. Steel sheet is zinc-coated, galvanized by the hot dip process of lock forming quality conform-

ing to ASTM A 653 commercial weight G-90, followed by baked-on electrostatic polyester dry powder coat.

C. CoilsCoils are of the enhanced louvered fin-and-tube type, constructed of seamless copper tubes, mechanically bonded to

aluminum fins. As an option, corrugated copper or enhanced coated aluminum fins may be provided.

The standard chilled water coil is 3 row for BWY03, BWY05 & BWY07 and 4 row for BWY10 & above. For heating

application, the coils are split as 2 row chilled water + 1 row hot water for BWY03, BWY05 & BWY07 and 3 row chilled

water + 1 row hot water for BWY10 & above. End plates and tube support sheets are 18 gauge galvanized steel, formed

to provide structural strength.

Each coil is pressure tested in the factory at not less than 300 psi (2070 kPa) air pressure. Coils conform to ARI 410.

D. Drain PansDrain pans provided under cooling coil section are made of G-90 galvanized steel with mastic coated liner for additional

corrosion protection and the outer surface is thermally insulated. Drain outlets of 3/4" NPT is provided for field connec-

tion.

E. Evaporator FanEvaporator fan is of a centrifugal forward-curved blade design and sized to meet system airflow/pressure. Fan motor

(except for BWY03 & BWY05, which have direct drive motors) is mounted on an adjustable base and secured by a

locking device. Fan drive is through adjustable motor pitch pulley and belt-driven. Fan shafts are designed to operate at

less than 2/3rds of the first critical speed when the unit comes up to rated revolutions per minute (RPM). Units have

sealed, permanently lubricated ball or sleeve fan bearing and are statically / dynamically balanced in the fan housing

during final assembly. Fan motors are of the open drip-proof type (totally enclosed types are optional, for belt driven

only) and conform to NEMA MG-1 & MG-2. Motor starters are magnetic contactor, across-the-line type.

4

Page 7: BWY Series

7/27/2019 BWY Series

http://slidepdf.com/reader/full/bwy-series 7/24

TYPICAL THERMOSTAT

OPTIONS AND ACCESSORIESA. Zone ControlTotal comfort zone control systems are available up to 19 zones and can provide a comfortable temperature to eachzone/room (field supplied).

B. Electric Heaters

Electric heaters are of the resistance open coil type and conform to the requirements of UL 573 or equivalent. Electricalcharacteristics, kW capacities and number of stages are as indicated. Thermal cut-outs, fusible links and airflow switchesare provided to shut-off power to heaters in case of airflow failure.

C. FiltersFilters are easily accessible through the filter access panel. Filters may be synthetic or permanent washable aluminum type, one or two inchthick (refer to model decoding for details). As an accessory, bag filter section can be provided for belt driven units (BWY07 - BWY25).

D. Discharge Air Plenum & Return Air GrilleAs an accessory, discharge air plenum with return air grilles can be provided on vertical units.

E. UV Flow™ Light EmittersThe damp & dark environment inside the AHU is ideal for the growth and development of hazardous bacteria & fungi. The UV

flow concept uses emitters of Ultra Violet light to simulate the effect of healthy sun radiation. This will inhibit the growth of these

microorganisms reducing in this manner mold related allergies and diseases. Breath safely with UV flow™.

To order the UV flow™ use the kit numbers in the table below.

F. Electronic ThermostatsGeneral Informations: Single stage or two stage thermostats provide low voltage control of one or two stage heating and/or

cooling applications. The thermostat normally displays room temperature, mode of operation and which system is currently on.

You may select different heating and cooling setpoints for the systems to maintain (example 700F in heating and 750F in

cooling). Raising or lowering the setpoints in heating or cooling is as simple as pushing a button.

The thermostat also allows you to select continuous fan operation, (useful when using an electronic air cleaner), or have

the fan on intermittent operation with the equipment.

The thermostat is best located about 1500 mm (5 Ft.) above floor level, on a partition wall (not an outside wall), and should not

be exposed to direct light from lamps, sun etc. It should be in return air stream, away from supply air registers /diffusers.

MODEL NUMBER BWY03 BWY05 BWY07 BWY10 BWY14 BWY18 BWY25

KIT PART NUMBER 700-391-16 700-391-17 700-391-18 700-391-19 700-391-20 700-391-21 700-391-22

  800-645-31 1 1 OFF-AUTO - HEAT/COOL ON - AUTO

  800-645-21* 2 2 OFF-AUTO - HEAT/COOL ON - AUTO

  800-646-23 2 2 OFF-AUTO - HEAT/COOL ON - AUTO

TYPICAL THERMOSTAT

Heating

Stages

Cooling

Stages

Selector Switch Positions

Mode SwitchPart No.

Fan Switch

* with built-in compressor fault & clogged filter indication led lights.

5

Page 8: BWY Series

7/27/2019 BWY Series

http://slidepdf.com/reader/full/bwy-series 8/24

PHYSICAL DATA

Corrugated Fin & Tube, 3/8" dia tube, 14 FPI

HOT WATER CAPACITIES

MODEL

NUMBER

EWT - 1500F (650C)

BWY03 2.5 (0.16) 24.7 (7.23) 4 (0.25) 38.5 (11.3)

BWY05 3.8 (0.24) 36.5 (10.7) 6 (0.38) 57.7 (16.9)

BWY07 5.7 (0.36) 56.2 (16.5) 9 (0.57) 89.2 (26.1)

BWY10 8.1 (0.51) 80.4 (23.5) 13 (0.81) 128.3 (37.6)

BWY14 11.6 (0.73) 113.4 (33.2) 18 (1.13) 177 (51.8)

BWY18 14 (0.90) 138 (40.4) 22 (1.40) 218 (63.8)

BWY25 20 (1.26) 194.3 (56.9) 31 (1.95) 304 (89)

NOTE: Capacities @ 700F (210C) Entering Air Temperature & 200F (110C) Water Temperature Drop.

LEGEND: EWT - Entering Water Temperature; MBH - 1000 BTUH; GPM - Gallons Per Minute; LPS - Liters Per Second

GPM (LPS)CAPACITIES

MBH (kW)

EWT - 1800F (820C)

GPM (LPS)CAPACITIES

MBH (kW)

6

MODEL NUMBER BWY03 BWY05 BWY07 BWY10 BWY14 BWY18 BWY25

EVAPORATOR BLOWER Type Centrifugal

Nominal airflow, CFM (L/S) 1200 (566) 2000 (944) 3000 (1416) 4600 (2171) 5500 (2596)7000 (3303) 9000 (4247)

Motor HP, Std./Alt. 0.5/0.75 0.75/1 2/3 3/2 5/7.5 5/7.5 7.5/10

Drive type Direct Direct Belt Belt Belt Belt Belt

Blower size 10x10 10x10 12x12 15x15 15x15 15x12 18x18

Quantity 1 1 1 1 1 2 2

EVAPORATOR COIL Type

Rows, std. chilled water 3 3 3 4 4 4 4

Rows, split (chilled + hot water) 2+1 2+1 2+1 3+1 3+1 3+1 3+1

Face area, Sq. ft. (Sq. m.) 3.2 (0.3) 4.5 (0.42) 7 (0.65) 10 (0.93) 14 (1.3) 17.5 (1.62) 25 (2.32)

Water in/out size, MPT (inch) Chilled water 3/4 1 1-1/4 1-1/2 1-1/2 1-1/2 1-1/2

Water in/out size, MPT (inch) Hot water 3/4 1 1 1-1/4 1-1/4 1-1/4 1-1/2

Condensate drain connection (inch) 3/4 3/4 3/4 3/4 3/4 3/4 3/4

RETURN AIR FILTER Size (inch) 24 x 20 x 1/2 16 x 20 x 1/2 20 x 20 x 1/2 18 x 24 x 1 20 x 24 x 1 20 x 24 x 1 20 x 24 x 2

Quantity 1 2 2 3 3 4 4

SHIPPING WEIGHT kg. (approx.) 80 120 165 225 300 340 420

Page 9: BWY Series

7/27/2019 BWY Series

http://slidepdf.com/reader/full/bwy-series 9/24

CHILLED WATER COOLING CAPACITIESSTANDARD COIL

BWY03 37.87 23.64 9.46 30.59 20.55 7.65 24.37 18.54 6.09BWY05 61.29 38.37 15.32 49.28 33.26 12.32 38.95 29.87 9.74BWY07 97.68 60.84 24.42 77.28 51.86 19.32 60.71 46.22 15.18

8 BWY10 165.61 102.19 41.40 131.67 87.23 32.92 103.05 77.16 25.76BWY14 212.95 130.60 53.24 169.61 111.30 42.40 131.18 97.03 32.79BWY18 282.70 172.69 70.67 223.23 145.85 55.81 170.46 125.64 42.61BWY25 390.34 236.86 97.58 307.49 199.09 76.87 231.68 169.10 57.92

BWY03 35.99 22.58 7.20 29.80 20.09 5.96 23.71 18.14 4.74BWY05 57.86 35.78 11.57 47.59 32.26 9.52 37.61 28.98 7.52BWY07 90.57 56.78 18.11 74.15 50.03 14.83 58.33 44.74 11.66

10 BWY10 152.98 95.08 30.60 125.95 83.93 25.19 99.70 75.06 19.94BWY14 196.88 121.53 39.37 160.32 106.04 32.06 126.92 94.46 25.38BWY18 258.49 159.22 51.70 208.21 137.29 41.64 163.94 121.66 32.79BWY25 355.94 217.76 71.19 282.91 185.25 56.58 222.31 163.45 44.46

BWY03 35.23 22.14 5.87 29.14 19.70 4.86 23.12 17.76 3.85BWY05 56.24 35.47 9.37 46.25 31.44 7.71 36.47 28.24 6.08BWY07 87.60 54.92 14.60 71.77 48.62 11.96 56.39 43.46 9.40

12 BWY10 148.85 92.77 24.81 122.60 81.96 20.43 96.94 73.32 16.16BWY14 189.47 117.38 31.58 156.06 103.49 26.01 123.47 92.41 20.58BWY18 245.97 152.16 40.99 201.69 133.55 33.61 158.86 118.69 26.48BWY25 334.17 205.75 55.69 273.54 179.83 45.59 215.17 159.08 35.86

WTR UNIT40

0F EWT 45

0F EWT 50

0F EWT

0F SIZE TC SC GPM TC SC GPM TC SC GPM

ENTERING AIR TEMP. = 760F DB/650F WB

BWY03 47.30 29.43 11.82 39.53 26.17 9.88 31.96 23.53 7.99BWY05 77.63 48.35 19.41 64.16 42.63 16.04 51.58 38.15 12.89BWY07 124.79 77.23 31.20 102.39 67.52 25.60 81.08 59.52 20.27

8 BWY10 208.72 128.14 52.18 173.15 112.65 43.29 138.95 99.94 34.74BWY14 268.25 163.51 67.06 222.61 143.44 55.65 178.89 126.99 44.72BWY18 360.07 218.37 90.02 296.09 189.60 74.02 235.88 166.38 58.97BWY25 491.2 298.1 121.0 409.10 259.51 102.27 325.04 226.37 81.26

BWY03 44.35 27.76 8.87 37.35 24.92 7.47 31.14 23.01 6.23BWY05 71.52 43.85 14.30 60.13 40.27 12.03 49.80 37.06 9.96BWY07 113.74 71.02 22.75 94.23 62.78 18.84 77.67 57.42 15.53

10 BWY10 193.61 119.71 38.72 159.91 105.18 31.98 131.76 95.73 26.35BWY14 249.05 152.92 49.81 206.06 134.16 41.21 167.72 120.43 33.54BWY18 329.72 201.68 65.94 270.95 175.67 54.19 218.07 155.99 43.61BWY25 454.86 276.33 90.97 373.16 239.74 74.63 296.47 209.98 59.29

BWY03 42.76 26.28 7.13 36.57 24.46 6.09 30.46 22.59 5.07BWY05 68.72 43.30 11.45 58.45 39.28 9.74 48.41 36.20 8.07BWY07 107.54 66.16 17.92 91.10 60.97 15.18 75.17 55.86 12.53

12 BWY10 181.69 113.03 30.28 154.64 102.14 25.77 128.25 93.60 21.37BWY14 233.36 144.14 38.89 196.85 128.98 32.81 163.25 117.90 27.21BWY18 306.28 188.70 51.05 255.80 167.16 42.63 211.18 151.94 35.20BWY25 421.72 258.06 70.29 347.67 225.48 57.94 286.51 204.19 47.75

WTR UNIT40

0F EWT 45

0F EWT 50

0F EWT

0F SIZE TC SC GPM TC SC GPM TC SC GPM

ENTERING AIR TEMP. = 800F DB/670F WB

BWY03 56.99 35.17 14.25 49.01 31.89 12.25 41.21 29.24 10.30BWY05 94.75 58.49 23.69 80.62 52.54 20.15 67.04 47.76 16.76BWY07 153.80 94.25 38.45 129.82 83.87 32.45 107.16 75.48 26.79

8 BWY10 254.16 154.60 63.54 216.65 138.36 54.16 180.76 125.13 45.19BWY14 326.78 197.38 81.69 278.45 176.04 69.61 232.35 158.78 58.09BWY18 437.20 263.60 109.10 374.52 235.07 93.63 309.66 209.78 77.41BWY25 605.20 360.60 149.00 510.00 321.50 126.00 428.14 286.00 107.03

BWY03 53.71 33.34 10.74 46.01 30.20 9.20 38.72 27.76 7.74BWY05 87.60 54.49 17.52 74.35 48.97 14.87 62.41 45.01 12.48BWY07 140.25 86.72 28.05 118.38 77.39 23.68 97.91 70.05 19.58

10 BWY10 235.97 144.60 47.19 201.06 129.71 40.21 167.16 117.40 33.43BWY14 303.30 184.55 60.66 258.57 165.16 51.71 215.30 149.14 43.06BWY18 405.03 245.25 81.01 342.85 217.76 68.57 283.51 195.21 56.70BWY25 560.45 336.96 112.09 473.19 297.69 94.64 390.57 265.58 78.11

BWY03 50.85 31.73 8.47 44.12 29.10 7.35 37.91 27.28 6.32BWY05 81.77 51.21 13.63 70.98 47.04 11.83 60.66 43.97 10.11BWY07 129.88 79.83 21.64 111.18 73.25 18.53 94.63 68.12 15.77

12 BWY10 221.71 136.62 36.95 188.16 122.43 31.36 160.46 113.46 26.74BWY14 285.29 174.59 47.55 242.53 156.25 40.42 204.27 142.92 34.04BWY18 377.02 229.86 62.84 318.70 204.48 53.11 265.70 185.04 44.28BWY25 519.84 314.87 86.64 438.88 278.96 73.15 361.03 249.00 60.17

WTR UNIT40

0F EWT 45

0F EWT 50

0F EWT

0F SIZE TC SC GPM TC SC GPM TC SC GPM

ENTERING AIR TEMP. = 840F DB/690F WB

BWY03 35.0 22.5 8.8 29.7 20.6 7.5 23.5 18.4 6.0BWY05 53.8 34.6 13.5 44.7 31.0 11.2 34.8 27.4 8.7BWY07 85.4 54.7 21.4 71.7 49.3 18.0 56.1 43.7 14.2

8 BWY10 172.5 107.8 43.0 143.2 95.5 36.0 115.3 85.6 29.0BWY14 230.1 142.5 57.5 191.0 126.0 48.0 153.0 112.0 38.5

BWY18 296.3 183.0 74.0 245.0 161.0 62.0 194.4 142.0 49.0BWY25 386.1 238.8 81.5 335.0 219.0 81.0 268.8 194.7 67.0

BWY03 32.9 21.2 6.6 26.4 18.5 5.3 20.0 16.0 4.1BWY05 49.2 31.9 9.8 39.4 27.7 7.9 28.8 23.1 5.8BWY07 79.3 51.0 16.0 62.3 43.5 12.5 45.4 36.4 9.1

10 BWY10 159.6 100.4 32.0 132.4 89.1 26.7 103.8 78.5 21.0BWY14 213.0 133.0 42.8 178.1 118.5 35.8 139.6 103.8 28.0BWY18 272.4 169.6 55.0 223.0 148.3 45.0 174.2 129.6 35.0BWY25 377.4 233.8 75.5 308.1 203.6 61.5 245.2 180.5 49.0

BWY03 29.7 19.4 5.0 23.2 16.5 4.0 19.5 15.6 3.9BWY05 43.8 28.6 7.3 32.4 23.1 5.4 21.8 18.1 4.0BWY07 69.4 45.1 11.6 52.1 37.0 8.7 25.6 21.7 4.8

12 BWY10 149.2 94.5 25.0 120.0 81.8 20.0 89.9 69.5 15.0BWY14 200.1 122.7 33.5 162.2 109.1 27.0 124.4 94.3 20.8BWY18 251.0 154.4 42.0 203.0 136.5 34.0 154.6 117.3 26.0BWY25 353.4 220.3 59.0 286.1 190.9 47.8 217.8 163.5 36.5

WTR UNIT40

0F EWT 45

0F EWT 50

0F EWT

0F SIZE TC SC GPM TC SC GPM TC SC GPM

ENTERING AIR TEMP. = 800F DB/670F WB

SPLIT COIL*

* 2 Row coil for BWY03, BWY05 & BWY07. 3 Row coil for BWY10 & above.

NOTE:

1. Capacities are based on nominal airflow.

2. For any other conditions, please use selection software for fan coil units.Apart from capacities, this software provides;

a) Sensible heat ratio

b) Leaving air temperature (DB/WB) - 0F

c) Leaving water temperature - 0F

d) Water pressure drop (feet of water)

LEGEND:

TC - Total Capacity (MBH)

SC - Sensible Heat Capacity (MBH)

WTR - Water Temperature Rise (0F)

EWT - Entering Water Temperature (0F)

GPM - Water flow (Gallons Per Minute)

7

Page 10: BWY Series

7/27/2019 BWY Series

http://slidepdf.com/reader/full/bwy-series 10/24

CHILLED WATER COOLING CAPACITIESSTANDARD COIL

BWY03 10.96 7.09 0.52 8.92 6.25 0.43 6.97 5.63 0.33BWY05 17.61 11.42 0.84 14.31 10.06 0.68 11.10 9.02 0.53BWY07 27.95 18.03 1.34 22.36 15.65 1.07 17.25 13.94 0.82

5 BWY10 47.78 30.51 2.28 37.83 26.15 1.81 29.39 23.31 1.40BWY14 61.49 39.01 2.94 48.16 33.02 2.30 37.41 29.30 1.79BWY18 81.20 51.31 3.88 62.95 42.98 3.01 48.44 37.82 2.31BWY25 111.94 70.27 5.35 86.67 58.63 4.14 65.75 50.82 3.14

BWY03 10.68 6.92 0.43 8.73 6.12 0.35 6.81 5.52 0.27BWY05 17.12 11.13 0.68 13.91 9.81 0.55 10.78 8.80 0.43BWY07 26.76 17.33 1.07 21.63 15.19 0.86 16.69 13.57 0.66

6 BWY10 45.28 29.06 1.80 36.82 25.53 1.47 28.60 22.79 1.14BWY14 57.65 36.79 2.30 46.87 32.23 1.87 36.42 28.70 1.45BWY18 75.30 47.93 3.00 60.75 41.68 2.42 46.95 36.87 1.87BWY25 103.67 65.55 4.13 82.48 56.18 3.28 63.62 49.48 2.53

BWY03 10.48 6.80 0.36 8.56 6.02 0.29 6.66 5.42 0.23BWY05 16.72 10.89 0.57 13.57 9.61 0.46 10.49 8.61 0.36BWY07 26.02 16.89 0.89 21.04 14.83 0.72 16.21 13.23 0.55

7 BWY10 44.26 28.47 1.51 35.99 25.03 1.23 27.91 22.33 0.95BWY14 56.33 36.03 1.92 45.81 31.61 1.56 35.56 28.14 1.21BWY18 73.07 46.64 2.49 59.15 40.73 2.02 45.70 36.11 1.56BWY25 99.23 63.02 3.39 80.20 54.84 2.74 61.88 48.37 2.11

WTR UNIT4

0C EWT 7

0C EWT 10

0C EWT

0C SIZE TC SC LPS TC SC LPS TC SC LPS

ENTERING AIR TEMP. = 250C DB/18.30C WB

BWY03 13.91 8.72 0.66 11.48 7.69 0.55 9.35 7.00 0.45BWY05 22.67 14.24 1.08 18.50 12.44 0.88 15.02 11.31 0.72BWY07 36.27 22.64 1.73 29.41 19.64 1.40 23.50 17.58 1.12

5 BWY10 61.08 37.81 2.92 50.11 33.01 2.39 39.71 29.19 1.90BWY14 78.52 48.28 3.75 64.47 42.04 3.08 50.94 36.94 2.43BWY18 104.76 64.14 5.01 85.29 55.32 4.08 66.85 48.21 3.19BWY25 144.91 88.11 6.92 117.63 75.61 5.62 92.04 65.55 4.40

BWY03 13.16 8.29 0.52 11.10 7.47 0.44 9.15 6.87 0.36BWY05 21.15 13.37 0.84 17.83 12.05 0.71 14.60 11.05 0.58BWY07 33.57 21.11 1.34 27.90 18.75 1.11 22.73 17.09 0.91

6 BWY10 57.37 35.73 2.28 47.16 31.31 1.88 38.64 28.53 1.54BWY14 73.84 45.67 2.94 60.37 39.74 2.40 49.18 35.90 1.96BWY18 97.51 60.09 3.88 79.19 51.89 3.15 63.82 46.41 2.54BWY25 134.42 82.31 5.35 109.04 70.79 4.34 86.69 62.42 3.45

BWY03 12.86 8.12 0.44 10.90 7.35 0.37 8.98 6.76 0.31BWY05 20.65 13.08 0.70 17.41 11.81 0.59 14.25 10.83 0.49BWY07 32.30 20.37 1.10 27.12 18.30 0.93 22.11 16.71 0.75

7 BWY10 54.60 34.15 1.86 46.08 30.68 1.57 37.77 28.00 1.29BWY14 69.80 43.39 2.38 58.65 38.74 2.00 48.08 35.26 1.64BWY18 91.54 56.73 3.12 76.16 50.17 2.60 62.13 45.43 2.12BWY25 126.03 77.64 4.30 103.47 67.69 3.53 84.27 60.99 2.88

WTR UNIT4

0C EWT 7

0C EWT 10

0C EWT

0C SIZE TC SC LPS TC SC LPS TC SC LPS

ENTERING AIR TEMP. = 270C DB/19.50C WB

BWY03 16.42 10.22 0.78 13.95 9.19 0.67 11.52 8.35 0.55BWY05 27.05 16.84 1.29 22.73 15.01 1.09 18.56 13.54 0.89BWY07 43.59 26.96 2.08 36.37 23.82 1.74 29.50 21.31 1.41

5 BWY10 72.66 44.59 3.47 61.24 39.62 2.93 50.27 35.59 2.40BWY14 93.39 56.94 4.46 78.72 50.43 3.76 64.67 45.19 3.09BWY18 125.73 76.24 6.01 105.05 66.87 5.02 85.56 59.37 4.09BWY25 172.00 103.80 9.00 145.31 89.97 6.94 118.01 80.79 5.64

BWY03 15.62 9.76 0.62 13.20 8.76 0.53 11.13 8.12 0.44BWY05 25.34 15.87 1.01 21.20 14.14 0.84 17.88 13.13 0.71BWY07 40.44 25.18 1.61 33.67 22.27 1.34 27.97 20.38 1.11

6 BWY10 68.39 42.21 2.72 57.53 37.53 2.29 47.28 33.86 1.88BWY14 87.92 53.90 3.50 74.03 47.83 2.95 60.57 42.82 2.41BWY18 116.94 71.39 4.66 97.78 62.85 3.89 79.45 55.87 3.16BWY25 161.56 97.97 6.43 134.80 85.84 5.37 109.39 75.98 4.36

BWY03 14.88 9.34 0.51 12.89 8.58 0.44 10.93 8.00 0.37BWY05 24.02 15.12 0.82 20.70 13.83 0.71 17.46 12.87 0.60BWY07 37.84 23.71 1.29 32.37 21.53 1.10 27.20 19.92 0.93

7 BWY10 64.80 40.20 2.21 54.73 35.94 1.87 46.20 33.22 1.58BWY14 83.42 51.39 2.85 70.00 45.55 2.39 58.81 41.83 2.01BWY18 110.04 67.55 3.76 91.80 59.51 3.13 76.36 54.08 2.61BWY25 151.65 92.51 5.18 126.39 81.16 4.31 103.75 72.75 3.54

WTR UNIT4

0C EWT 7

0C EWT 10

0C EWT

0C SIZE TC SC LPS TC SC LPS TC SC LPS

ENTERING AIR TEMP. = 290C DB/20.50C WB

BWY03 10.25 6.59 0.55 8.70 6.03 0.47 6.88 5.39 0.38BWY05 15.75 10.13 0.85 13.09 9.08 0.71 10.19 8.02 0.55BWY07 25.01 16.02 1.35 21.0 14.44 1.13 16.43 12.80 0.89

5 BWY10 50.51 31.57 2.71 41.93 27.96 2.27 33.76 25.07 1.83BWY14 67.38 41.73 3.62 55.93 36.90 3.02 44.80 32.80 2.43

BWY18 86.76 53.59 4.66 71.74 47.14 3.91 56.93 41.58 3.09BWY25 113.06 69.93 5.13 98.10 64.13 5.10 78.71 57.01 4.22

BWY03 9.63 6.21 0.42 7.73 5.42 0.33 5.86 4.69 0.26BWY05 14.41 9.34 0.62 11.54 8.11 0.50 8.43 6.76 0.37BWY07 23.22 14.93 1.01 18.24 12.74 0.79 13.29 10.66 0.57

6 BWY10 46.73 29.40 2.02 38.77 26.09 1.68 30.40 22.99 1.32BWY14 62.37 38.95 2.70 52.15 34.70 2.26 40.88 30.40 1.76BWY18 79.77 49.66 3.47 65.30 43.43 2.84 51.01 37.95 2.21BWY25 110.51 68.46 4.76 90.22 59.62 3.87 71.80 52.86 3.09

BWY03 8.70 5.67 0.32 6.79 4.83 0.25 5.71 4.57 0.25BWY05 12.83 8.37 0.46 9.49 6.76 0.34 6.38 5.30 0.25BWY07 20.32 13.21 0.73 15.26 10.83 0.55 7.50 6.35 0.30

7 BWY10 43.69 27.67 1.58 35.14 23.95 1.26 26.33 20.35 0.95BWY14 58.59 35.93 2.11 47.50 31.95 1.70 36.43 27.61 1.31BWY18 73.50 45.21 2.65 59.44 39.97 2.14 45.27 34.35 1.64BWY25 103.48 64.51 3.72 83.78 55.90 3.01 63.78 47.88 2.30

WTR UNIT4

0C EWT 7

0C EWT 10

0C EWT

0C SIZE TC SC LPS TC SC LPS TC SC LPS

ENTERING AIR TEMP. = 270C DB/19.50C WB

SPLIT COIL*

* 2 Row coil for BWY03, BWY05 & BWY07. 3 Row coil for BWY10 & above.

NOTE:

1. Capacities are based on nominal airflow.

2. For any other conditions, please use selection software for fan coil units.Apart from capacities, this software provides;

a) Sensible heat ratio

b) Leaving air temperature (DB/WB) - 0C

c) Leaving water temperature - 0C

d) Water pressure drop (feet of water)

LEGEND:

TC - Total Capacity (kW)

SC - Sensible Heat Capacity (kW)

WTR - Water Temperature Rise (0C)

EWT - Entering Water Temperature (0C)

LPS - Water flow (Liters Per Second)

8

Page 11: BWY Series

7/27/2019 BWY Series

http://slidepdf.com/reader/full/bwy-series 11/24

BLOWER MOTOR HP BLOWER MOTOR

SPEED 0.1 0.2 0.3 0.4 0.5 0.6

HIGH 1350 1290 1220 1160 1070 990

0.5 MEDIUM 1260 1200 1125 1060 1000 900

LOW 1070 1020 960 900 830 740

HIGH 1660 1480 1300 1230 1140 1060

0.75 MEDIUM 1570 1375 1180 1120 1060 960

LOW 1500 1320 1130 940 870 780

MODEL No.: BWY03

  FAN PERFORMANCE DATADIRECT DRIVE MOTORS

CFM @ External Static Pressure (inch wg.)

BLOWER MOTOR HP BLOWER MOTOR

SPEED 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8

HIGH 2010 1920 1820 1730 1620 1490 1350 1230

0.75 MEDIUM 1830 1740 1660 1570 1470 1360 1240 1100

LOW 1710 1650 1570 1490 1390 1300 1170 975

HIGH 2252 2215 2180 2140 2105 2065 2020 1950

1.0 MEDIUM 2021 1990 1950 1920 1880 1840 1795 1700

LOW 1820 1805 1790 1735 1700 1665 1630 1530

MODEL No.: BWY05

CFM @ External Static Pressure (inch wg.)

BELT DRIVEN MOTORSMODEL No.: BWY07

NOTE: Values include losses for dry coil, filter & unit casing.

MODEL No.: BWY10

9

NOTES (For BWY07/BWY10): 1. Values include losses for filters, unit casing and wet coils.2. 2 HP motor and alternative drive I to be used for the unshaded portion.3. 3 HP motor and alternative drive II to be used for the shaded portion.

2800 (1321)

3000 (1416)3200 (1510)

3400 (1605)

3600 (1699)

3800 (1793)

4000 (1888)

4200 (1982)

4400 (2076)

4600 (2170)

4800 (2265)

5000 (2360)

Airflow,CFM (L/S)

0.2

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

610 0.62 710 0.75 745 0.87 760 0.95 850 1.2

625 0.69 720 0.80 760 0.95 810 1.12 865 1.25636 0.77 734 0.92 780 1.06 820 1.26 870 1.38

660 0.88 746 1.01 805 1.18 833 1.34 881 1.5

675 1.0 760 1.16 820 1.32 848 1.48 900 1.66

700 1.13 778 1.3 840 1.43 868 1.63 913 1.8

727 1.28 790 1.45 865 1.62 882 1.8 926 1.96

772 1.41 843 1.62 880 1.78 921 1.96 968 2.16

791 1.58 864 1.79 887 1.94 934 2.14 979 2.34

840 1.79 890 1.96 931 2.2 975 2.38 1017 2.59

857 1.95 906 2.17 947 2.4 988 2.57 1035 2.76

876 2.15 920 2.38 961 2.6 1005 2.76

External Static Pressure (inch wg.)0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

905 1.32 965 1.5 1000 1.6 1054 1.8 1100 2.0

915 1.4 970 1.6 1013 1.75 1065 2.0 1115 2.15925 1.51 978 1.73 1023 1.86 1073 2.1 1122 2.28

939 1.67 983 1.84 1033 2.02 1083 2.25 1128 2.44

950 1.82 995 1.98 1043 2.21 1090 2.41 1131 2.6

966 2.0 1006 2.18 1056 2.39 1100 2.58 1143 2.78

980 2.18 1023 2.4 1066 2.6 1108 2.77

1011 2.36 1054 2.56 1096 2.76

1024 2.54 1067 2.77

1058 2.77

* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

I

II

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

820* 0.62* 900 0.71 965 0.82 1020 0.88 1102 1.03

824* 0.7* 905 0.79 970 0.91 1026 1.0 1107 1.12

853 0.81 927 0.91 986 1.02 1041 1.13 1111 1.25

950 0.94 1004 1.05 1059 1.21 1132 1.27 1155 1.38

968 1.1 1032 1.22 1086 1.33 1150 1.45 1194 1.57

1054 1.4 1106 1.5 1160 1.61 1216 1.76 1261 1.88

1066 1.55 1133 1.7 1180 1.82 1234 1.94 1276 2.09

1091 1.75 1157 1.91 1202 2.02 1255 2.2 1307 2.33

1116 1.96 1171 2.1 1228 2.3 1276 2.45 1329 2.6

1800 (849)

2000 (944)

2200 (1038)

2400 (1133)

2600 (1227)

2800 (1321)

3000 (1416)

3200 (1510)

3400 (1605)

Airflow,CFM (L/S)

External Static Pressure (inch wg.)1.0 1.2 1.4

RPM BHP RPM BHP

1145 1.14 1220 1.26

1152 1.25 1225 1.35

1160 1.36 1237 1.48

1244 1.5 1297 1.65

1250 1.69 1305 1.82

1323 2.02 1380* 2.2*

1334* 2.23* 1400* 2.3*

1359* 2.47*

1368* 2.73*

0.80.60.40.2

I

II

Page 12: BWY Series

7/27/2019 BWY Series

http://slidepdf.com/reader/full/bwy-series 12/24

FAN PERFORMANCE DATA (BELT DRIVEN MOTORS)

MODEL No.: BWY14

MODEL No.: BWY18

NOTES (For BWY14/BWY18): 1. Values include losses for filters, unit casing and wet coils.2. Standard 5 HP motor and Alt. I drive to be used for the unshaded portion.3. Alt. 7.5 HP motor and Alt. II drive to be used for the shaded portion.* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

MODEL No.: BWY25

Notes: 1. Values include losses for filters, unit casing and wet coils.2. Standard 7.5 HP motor to be used for the unshaded portion.3. Alt. 10 HP motor to be used for the shaded portion.

* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

10

4000 (1888)

4200 (1982)

4400 (2076)

4600 (2170)

4800 (2265)

5000 (2360)

5200 (2454)

5400 (2548)

5600 (2643)

5800 (2737)

6000 (2832)

6200 (2926)

6400 (3020)

6600 (3115)

Airflow,CFM (L/S)

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

694* 1.21* 743* 1.3* 797 1.52 845 1.66 890 1.83

705* 1.33* 761* 1.45* 811 1.67 857 1.81 903 2.0

719* 1.43* 774 1.6 823 1.8 869 1.97 918 2.17735* 1.57* 787 1.75 835 1.95 885 2.17 929 2.34

748* 1.72* 800 1.92 846 2.09 897 2.35 935 2.52

761* 1.87* 812 2.09 862 2.30 904 2.52 948 2.70

778 2.06 823 2.27 873 2.48 917 2.70 959 2.91

800 2.31 846 2.5 894 2.72 934 2.94 979 3.15

808 2.46 858 2.7 903 2.90 945 3.12 987 3.38

826 2.68 869 2.9 917 3.12 955 3.4 1000 3.65

837 2.90 885 3.12 927 3.37 965 3.64 1009 3.9

850 3.12 900 3.41 940 3.65 980 3.92 1021 4.17

879 3.41 920 3.70 962 3.96 1000 4.2 1040 4.45

894 3.76 933 4.0 973 4.24 1013 4.44 1050 4.68

0.2

External Static Pressure (inch wg.)

0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

937 2.03 975 2.25 992 2.4 1075 2.64 1102 2.85

951 2.19 992 2.43 1002 2.6 1080 2.82 1110 3.05

963 2.33 1006 2.58 1010 2.78 1093 2.97 1133 3.2971 2.55 1013 2.75 1053 2.93 1100 3.17 1138 3.41

979 2.72 1023 2.91 1065 3.14 1107 3.4 1144 3.62

989 2.91 1032 3.11 1068 3.37 1113 3.6 1150 3.86

1001 3.11 1038 3.34 1070 3.59 1119 3.85 1159 4.08

1019 3.38 1056 3.64 1098 3.88 1133 4.10 1171 4.36

1028 3.65 1063 3.83 1106 4.14 1139 4.35 1176 4.57

1041 3.9 1078 4.13 1114 4.37 1150 4.6 1186 4.78

1047 4.13 1088 4.35 1123 4.59 1157 4.85 1194 5.05

1061 4.38 1100 4.66 1133 4.85 1167 5.1 1205 5.4

1078 4.69 1114 4.92 1150 5.2 1183 5.45 1218 5.76

1091 4.92 1125 5.2 1161 5.51 1194 5.8 1229 6.08

I   II

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

955 2.66 1005 2.96 1057 3.3 1104 3.6 1153* 3.88

961 2.83 1010 3.15 1060 3.46 1107 3.76 1155* 4.04

966 2.96 1012 3.23 1062 3.57 1109 3.88 1157* 4.27

968 3.07 1015 3.38 1065 3.73 1110 4.07 1158* 4.4*

970 3.23 1020 3.53 1066 3.84 1113 4.18 1159* 4.59

980 3.4 1025 3.69 1070 4.0 1118 4.4 1162* 4.72

985 3.56 1030 3.84 1080 4.27 1120 4.63 1163* 4.95

990 3.72 1036 4.04 1082 4.45 1126 4.82 1165* 5.09

1000 3.88 1045 4.23 1083 4.6 1127 5 1170* 5.3*

1004 4.14 1050 4.47 1090 4.83 1134 5.16 1175* 5.51

1012 4.28 1054 4.66 1095 5.04 1135 5.39 1179* 5.72

1017 4.47 1059 4.85 1100 5.19 1141* 5.58* 1183* 5.95

1021 4.68 1065 5.09 1108 5.47 1150* 5.8* 1185* 6.12

1026 4.85 1069 5.23 1112 5.66 1154* 6* 1193* 6.42

1041 5.14 1083 5.47 1125 5.9 1158* 6.36* 1200* 6.78

1046 5.33 1087 5.75 1128 6.12 1164* 6.6*

1054 5.56 1100 6 1132 6.36 1172* 6.84*

1066 5.85 1107 6.24 1140 6.72

5000 (2360)

5200 (2454)

5400 (2548)

5600 (2643)

5800 (2737)

6000 (2832)

6200 (2926)

6400 (3020)

6600 (3115)

6800 (3209)

7000 (3303)

7200 (3398)

7400 (3492)

7600 (3587)

7800 (3681)

8000 (3775)

8200 (3870)

8400 (3964)

Airflow,CFM (L/S)

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

715* 1.33* 731* 1.56* 787* 1.82* 850 2.07 902 2.4

718* 1.42* 737* 1.68* 793* 1.96* 856 2.26 905 2.53

721* 1.53* 750* 1.81* 802* 2.07* 860 2.35 911 2.66

725* 1.68* 756* 1.92* 807 2.21 866 2.5 916 2.79

729* 1.81* 762* 2.03* 816 2.35 872 2.64 921 2.9

733* 1.9* 775* 2.14* 833 2.42 877 2.78 930 3.02

738* 2.03* 788* 2.35* 839 2.57 888 2.92 935 3.24

745* 2.15* 795* 2.5* 850 2.71 900 3.08 940 3.41

753* 2.38* 800* 2.64* 855 2.92 905 3.25 950 3.58

761* 2.5* 810 2.78 863 3.08 910 3.41 960 3.75

772* 2.69* 820 2.92 875 3.33 918 3.58 967 3.95

777* 2.84* 830 3.08 880 3.41 927 3.75 976 4.14

794* 2.96* 845 3.3 890 3.62 936 3.95 985 4.4

805 3.18 850 3.5 900 3.83 941 4.2 990 4.57

820 3.36 870 3.69 909 4.1 954 4.5 1002 4.9

830 3.59 880 3.86 922 4.25 963 4.65 1008 5.05

867 3.77 890 4.1 936 4.5 972 4.9 1016 5.25

890 4.05 904 4.42 945 4.75 986 5.1 1025 5.45

0.2External Static Pressure (inch wg.)

0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0

I   II

BHP RPM BHP RPM BHP RPM BHP RPM BHP

4.5 944 5.0 980 5.46 1015 6.0 1059* 6.6*

4.73 945 5.23 981 5.71 1017 6.3 1059* 6.92

4.96 946 5.45 982 5.97 1017 6.6 1059* 7.22

5.2 946 5.68 983 6.23 1018 6.95 1060* 7.51

5.45 947 5.9 985 6.5 1018 7.25 1060* 7.785.65 947 6.12 986 6.8 1019 7.5 1061* 8.05

5.97 949 6.48 988 7.2 1020 7.8 1062* 8.35

6.3 951 6.8 990 7.6 1020 8.1 1062* 8.65

6.75 953 7.15 992 8.0 1022 8.45 1064* 9.0*

7.1 955 7.6 994 8.35 1023 8.75 1065* 9.45

7.4 957 8.06 996 8.71 1023 9.25 1067* 9.8*

7.85 965 8.4 1003 9.1 1034* 9.7* - -

8.3 973 8.8 1009 9.5 - - - -

8.7 981 9.25 1014 9.9 - - - -

9.15 989 9.6 - - - - - -

9.6 996 10.1 - - - - - -

6000 (2832)

6400 (3020)

6800 (3209)

7200 (3398)

7600 (3587)8000 (3775)

8400 (3964)

8800 (4152)

9200 (4341)

9600 (4530)

10000 (4719)

10400 (4907)

10800 (5096)

11200 (5286)

11600 (5474)

12000 (5663)

Airflow,CFM (L/S)

RPM BHP RPM BHP RPM BHP RPM BHP RPM

700* 2.6* 762* 3.12* 812 3.6 857 4.0 900

706* 2.8* 764* 3.3* 813 3.78 858 4.22 901

716* 3.05* 766* 3.5* 814 4.0 859 4.42 902

722* 3.24* 768* 3.7* 815 4.19 860 4.64 903

732* 3.4* 770* 3.82* 816 4.35 861 4.88 904740* 3.6* 772* 4.0* 818 4.56 861 5.18 904

751* 3.9* 778* 4.35* 819 4.85 865 5.5 906

790* 4.2* 800 4.65 821 5.16 869 5.81 908

800 4.5 810 5.0 823 5.5 873 6.14 911

805 4.9 820 5.35 825 5.84 877 6.45 915

815 5.2 825 5.67 826 6.15 882 6.7 920

825 5.55 830 6.1 838 6.6 890 7.1 928

835 5.9 840 6.5 870 7.0 898 7.5 936

840 6.4 856 6.9 876 7.4 906 7.95 944

852 6.8 872 7.3 885 7.9 914 8.45 952

870 7.2 885 7.8 892 8.5 925 9.0 961

0.4External Static Pressure (inch wg.)

0.6 0.8 1.0 1.2 1.4 2.01.81.6

I   II

Page 13: BWY Series

7/27/2019 BWY Series

http://slidepdf.com/reader/full/bwy-series 13/24

MIN. MAX. HP FLA kW FLA

– – 2.3 15

5 21.7 29.4 300.50 1.8 6/7 26.1/30.4 34.9/40.3 40/4510* /12* 43.5/52.2 56.6/67.5 60/70

208/230-1-60 187 25314* 60.9 78.4 80– – 5.9 155 21.7 33 35

0.75 4.7 6/7 26.1/30.4 38.5/43.9 40/4510* /12* 43.5/52.2 60.3/71.1 70/80

14* 60.9 82 90– – 2.3 155 12.6 18 20

0.50 1.8 6/7.5 15.1/18.8 21.1/25.8 25/3010* /12* 25.1/30.1 33.6/39.9 35/40

208/230-3-60 187 25315* 37.7 49.4 50– – 5.9 155 12.6 21.6 25

0.75 4.7 6/7.5 15.1/18.8 24.8/29.4 30/3510* /12* 25.1/30.1 37.3/43.5 40/45

15* 37.7 53 60– – 2.3 155 7.6 11.8 15

0.50 1.8 6/7.5 9.1/11.4 13.6/16.5 15/2010* /12* 15.2/18.2 21.3/25 25/30

380-3-60 342 418 15* 22.8 30.8 35– – 5.9 155 7.6 15.4 20

0.75 4.7 6/7.5 9.1/11.4 17.3/20.1 20/2510* /12* 15.2/18.2 24.9/28.6 30/30

15* 22.8 34.4 35– – 1.3 155 6.3 9.1 15

0.50 1.0 6/7.5 7.5/9.4 10.6/13 15/2010* /12* 12.6/15.1 17/20.1 20/25

460-3-60 414 50615* 18.8 24.8 30– – 3.3 155 6.3 11.1 15

0.75 2.6 6/7.5 7.5/9.4 12.6/15 15/2010* /12* 12.6/15.1 19/22.1 20/25

15* 18.8 26.8 30

POWER

SUPPLY

(V-Ph-Hz)

VOLTAGE

RANGE

BLOWER

MOTOR**ELECTRIC HEATER

MCA MOCP

ELECTRICAL DATAMODEL No.: BWY03

MODEL No.: BWY05

MIN. MAX. HP FLA kW FLA

– – 5.9 155 21.7 33 40

0.75 4.7 6/7 26.1/30.4 38.5/43.9 45/5010* /12* 43.5/52.2 60.3/71.1 70/80

208/230-1-60 187 25314* 60.9 82 90– – 10.3 155 21.7 37.4 40

1.0 8.2 6/7 26.1/30.4 42.9/48.3 45/50

10* /12* 43.5/52.2 64.6/75.5 70/8014* 60.9 86.4 90– – 5.9 155 12.6 21.6 25

0.75 4.7 6/7.5 15.1/18.8 24.8/29.4 25/3010* /12* 25.1/30.1 37.3/43.5 40/45

208/230-3-60 187 25315* 37.7 53 60– – 10.3 155 12.6 26 30

1.0 8.2 6/7.5 15.1/18.8 29.1/33.8 30/3510* /12* 25.1/30.1 41.6/47.9 45/50

15* 37.7 57.4 60– – 5.9 155 7.6 15.4 20

0.75 4.7 6/7.5 9.1/11.4 17.3/20.1 20/2510* /12* 15.2/18.2 24.9/28.6 25/30

380-3-60 342 41815* 22.8 34.3 35– – 10.3 155 7.6 19.8 25

1.0 8.2 6/7.5 9.1/11.4 21.6/24.5 25/3010* /12* 15.2/18.2 29.3/33 30/35

15* 22.8 38.8 40– – 3.8 155 6.3 11.6 15

0.75 3.0 6/7.5 7.5/9.4 13.1/15.5 15/2010* /12* 12.6/15.1 19.5/22.6 20/25

460-3-60 414 50615* 18.8 27.3 30– – 5.5 155 6.3 13.4 15

1.0 4.4 6/7.5 7.5/9.4 14.9/17.3 20/2010* /12* 12.6/15.1 21.3/24.4 25/25

15* 18.8 29 30

POWER

SUPPLY

(V-Ph-Hz)

VOLTAGE

RANGE

BLOWER

MOTOR

**

ELECTRIC HEATER

MCA MOCP

MIN. MAX. HP FLA kW FLA

– – 8.3 15

5 12.6 24 25

208/230-3-60 187 253

2 6.6 6/7.5 15.1/18.8 27.1/31.8 30/35

10* /12* 25.1/30.1 39.6/45.9 40/50

15* /20* 37.7/50.2 55.4/71 60/80

25* /30* 62.8/75.3 86.8/102.4 90/110

– – 11 20

5 12.6 26.8 30

3 8.8 6/7.5 15.1/18.8 29.9/34.5 35/35

10* /12* 25.1/30.1 42.4/48.6 45/50

15* /20* 37.7/50.2 58.1/73.8 60/80

25* /30* 62.8/75.3 89.5/105.1 90/110

– – 5 15

5 7.6 14.5 15

380-3-60 342 418

2 4 6/7.5 9.1/11.4 16.4/19.3 20/20

10* /12* 15.2/18.2 24/27.8 25/30

15* /20* 22.8/30.4 33.5/43 35/45

25* /30* 38/45.6 52.5/62 60/70– – 6.4 15

5 7.6 15.9 20

3 5.14 6/7.5 9.1/11.4 17.8/20.7 20/25

10* /12* 15.2/18.2 25.4/29.2 30/30

15* /20* 22.8/30.4 34.9/44.4 40/45

25* /30* 38/45.6 53.9/63.4 60/70

– – 4.4 15

5 6.3 12.3 15

460-3-60 414 506

2 3.5 6/7.5 7.5/9.4 13.8/16.1 15/20

10* /12* 12.6/15.1 20.1/23.3 25/25

15* /20* 18.8/25.1 27.9/35.8 30/40

25* /30* 31.4/37.7 43.6/51.5 45/60

– – 5.1 15

5 6.3 13 15

3 4.1 6/7.5 7.5/9.4 14.5/16.9 15/20

10* /12* 12.6/15.1 20.9/24 25/25

15* /20* 18.8/25.1 28.6/36.5 30/40

25* /30* 31.4/37.7 44.4/52.3 45/60

POWER

SUPPLY

(V-Ph-Hz)

VOLTAGE

RANGE

BLOWER

MOTOR ELECTRIC HEATERMCA MOCP

MODEL No.: BWY07

(4 WIRE)

(STD.)

(STD.)

(ALT.)

(ALT.)

LEGEND:

FLA   – Full Load Amps

HP   – Horse Power

MCA   – Minimum Circuit Amps

MOCP – Maximum Over Current Protection

* Combination of 2 heater modules

** Single phase motors

(4 WIRE)

(STD.)

(4 WIRE)

(ALT.)

(STD.)

(ALT.)

(STD.)

(ALT.)

(STD.)

(ALT.)

(STD.)

(STD.)

(ALT.)

(ALT.)

(STD.)

(ALT.)

(STD.)

(ALT.)

(STD.)

(ALT.)

11

Page 14: BWY Series

7/27/2019 BWY Series

http://slidepdf.com/reader/full/bwy-series 14/24

ELECTRICAL DATA

MIN. MAX. HP FLA kW FLA

– – 8.3 15

5 12.6 24 25

208/230-3-60 187 253

2 6.6 6/7.5 15.1/18.8 27.1/31.8 30/35

10* /12* 25.1/30.1 39.6/45.9 40/50

15* /20* 37.7/50.2 55.4/71 60/80

25* /30* 62.8/75.3 86.8/102.4 90/110

– – 11 20

5 12.6 26.8 30

3 8.8 6/7.5 15.1/18.8 29.9/34.5 35/35

10* /12* 25.1/30.1 42.4/48.6 45/50

15* /20* 37.7/50.2 58.1/73.8 60/80

25* /30* 62.8/75.3 89.5/105.1 90/110

– – 5 15

5 7.6 14.5 15

380-3-60 342 418

2 4 6/7.5 9.1/11.4 16.4/19.3 20/20

10* /12* 15.2/18.2 24/27.8 25/30

15* /20* 22.8/30.4 33.5/43 35/45

25* /30* 38/45.6 52.5/62 60/70

– – 6.4 15

5 7.6 15.9 20

3 5.14 6/7.5 9.1/11.4 17.8/20.7 20/25

10* /12* 15.2/18.2 25.4/29.2 30/30

15* /20* 22.8/30.4 34.9/44.4 40/45

25* /30* 38/45.6 53.9/63.4 60/70

– – 4.4 15

5 6.3 12.3 15

460-3-60 414 506

2 3.5 6/7.5 7.5/9.4 13.8/16.1 15/20

10* /12* 12.6/15.1 20.1/23.3 25/25

15* /20* 18.8/25.1 27.9/35.8 30/40

25* /30* 31.4/37.7 43.6/51.5 45/60

– – 5.1 15

5 6.3 13 15

3 4.1 6/7.5 7.5/9.4 14.5/16.9 15/20

10* /12* 12.6/15.1 20.9/24 25/25

15* /20* 18.8/25.1 28.6/36.5 30/40

25* /30* 31.4/37.7 44.4/52.3 45/60

POWER

SUPPLY

(V-Ph-Hz)

VOLTAGE

RANGE

BLOWER

MOTOR ELECTRIC HEATERMCA MOCP

MODEL No.: BWY10

(ALT.)

(STD.)

(ALT.)

(STD.)

(ALT.)

(STD.)

(4 WIRE)

LEGEND:

FLA   – Full Load Amps

HP   – Horse Power

MCA   – Minimum Circuit Amps

MOCP – Maximum Over Current Protection

* Combination of 2 heater modules

MIN. MAX. HP FLA kW FLA

– – 17.3 30

5 12.6 33 40

208/230-3-60 187 253

5 13.8 6/7.5 15.1/18.8 36.1/40.8 45/45

10* /12* 25.1/30.1 48.6/54.9 50/60

15* /20* 37.7/50.2 64.4/80 70/90

25* /30* 62.8/75.3 95.8/111.4 100/125

– – 24.4 40

5 12.6 40.1 50

7.5 19.5 6/7.5 15.1/18.8 43.3/47.9 50/60

10* /12* 25.1/30.1 55.8/62 60/70

15* /20* 37.7/50.2 71.5/87.1 80/90

25* /30* 62.8/75.3 102.9/118.5 110/125

– – 11.3 20

5 7.6 20.8 25

380-3-60 342 418

5 9 6/7.5 9.1/11.4 22.6/25.5 25/30

10* /12* 15.2/18.2 30.3/34 35/35

15* /20* 22.8/30.4 39.8/49.3 45/50

25* /30* 38/45.6 58.8/68.3 60/70

– – 15.6 25

5 7.6 25.1 35

7.5 12.5 6/7.5 9.1/11.4 27/29.9 35/35

10* /12* 15.2/18.2 34.6/38.4 40/45

15* /20* 22.8/30.4 44.1/53.6 50/60

25* /30* 38/45.6 63.1/72.6 70/80

– – 8.6 15

5 6.3 16.5 20

460-3-60 414 506

5 6.9 6/7.5 7.5/9.4 18/20.4 20/25

10* /12* 12.6/15.1 24.4/27.5 30/30

15* /20* 18.8/25.1 32.1/40 35/45

25* /30* 31.4/37.7 47.9/55.8 50/60

– – 12.2 20

5 6.3 20.1 25

7.5 9.75 6/7.5 7.5/9.4 21.6/23.9 25/30

10* /12* 12.6/15.1 27.9/31.1 30/35

15* /20* 18.8/25.1 35.7/43.6 40/45

25* /30* 31.4/37.7 51.4/59.3 60/70

POWER

SUPPLY

(V-Ph-Hz)

VOLTAGE

RANGE

BLOWER

MOTOR ELECTRIC HEATERMCA MOCP

MODEL No.: BWY14

(STD.)

(ALT.)

(STD.)

(ALT.)

(STD.)

(ALT.)

(4 WIRE)

12

Page 15: BWY Series

7/27/2019 BWY Series

http://slidepdf.com/reader/full/bwy-series 15/24

ELECTRICAL DATA

LEGEND:

FLA   – Full Load Amps

HP   – Horse Power

MCA   – Minimum Circuit Amps

MOCP – Maximum Over Current Protection

* Combination of 2 heater modules

MIN. MAX. HP FLA kW FLA

– – 25.5 45

5 12.6 41.2 50

208/230-3-60 187 253

7.5 20.4 6/7.5 15.1/18.8 44.3/49 60/60

10* /12* 25.1/30.1 56.9/63.2 70/70

15* /20* 37.7/50.2 72.6/88.3 80/90

25* /30* 62.8/75.3 103.9/119.6 110/125

35* /40* 87.9/100.4 135.3/151 150/175

– – 32.6 50

5 12.6 48.3 70

10 26.1 6/7.5 15.1/18.8 51.5/56.2 70/70

10* /12* 25.1/30.1 64/70.3 80/80

15* /20* 37.7/50.2 79.7/95.4 90/100

25* /30* 62.8/75.3 111.1/126.8 125/150

35* /40* 87.9/100.4 142.4/158.1 150/175

– – 15.6 25

5 7.6 25.1 35

380-3-60 342 418

7.5 12.5 6/7.5 9.1/11.4 27/29.9 35/35

10* /12* 15.2/18.2 34.6/38.4 40/45

15* /20* 22.8/30.4 44.1/53.6 50/60

25* /30* 38/45.6 63.1/72.6 70/80

35* /40* 53.2/60.8 82.1/91.6 90/100

– – 20 35

5 7.6 29.5 40

10 16 6/7.5 9.1/11.4 31.4/34.2 45/45

10* /12* 15.2/18.2 39/42.8 50/50

15* /20* 22.8/30.4 48.5/58 50/60

25* /30* 38/45.6 67.5/77 70/80

35* /40* 53.2/60.8 86.5/96 90/100

– – 12.8 20

5 6.3 20.6 25

460-3-60 414 506

7.5 10.2 6/7.5 7.5/9.4 22.2/24.5 30/30

10* /12* 12.6/15.1 28.4/31.6 35/35

15* /20* 18.8/25.1 36.3/44.1 40/45

25* /30* 31.4/37.7 52/59.8 60/60

35* /40* 43.9/50.2 67.7/75.5 70/80

– – 16.3 25

5 6.3 24.1 35

10 13 6/7.5 7.5/9.4 25.7/28 35/35

10* /12* 12.6/15.1 31.9/35.1 40/40

15* /20* 18.8/25.1 39.8/47.6 45/50

25* /30* 31.4/37.7 55.5/63.3 60/70

35* /40* 43.9/50.2 71.2/79 80/80

POWER

SUPPLY

(V-Ph-Hz)

VOLTAGE

RANGE

BLOWER

MOTOR ELECTRIC HEATERMCA MOCP

MODEL No.: BWY25

(STD.)

(ALT.)

(STD.)

(ALT.)

(STD.)

(ALT.)

(4 WIRE)

MIN. MAX. HP FLA kW FLA

– – 17.3 30

5 12.6 33 40

208/230-3-60 187 253

5 13.8 6/7.5 15.1/18.8 36.1/40.8 45/45

10* /12* 25.1/30.1 48.6/54.9 50/60

15* /20* 37.7/50.2 64.4/80 70/90

25* /30* 62.8/75.3 95.8/111.4 100/125

35* /40* 87.9/100.4 127.1/142.8 150/150

– – 24.4 40

5 12.6 40.1 50

7.5 19.5 6/7.5 15.1/18.8 43.3/47.9 50/60

10* /12* 25.1/30.1 55.8/62 60/70

15* /20* 37.7/50.2 71.5/87.1 80/90

25* /30* 62.8/75.3 102.9/118.5 110/125

35* /40* 87.9/100.4 134.3/149.9 150/175

– – 11.3 20

5 7.6 20.8 25

380-3-60 342 418

5 9 6/7.5 9.1/11.4 22.6/25.5 25/30

10* /12* 15.2/18.2 30.3/34 35/35

15* /20* 22.8/30.4 39.8/49.3 45/50

25* /30* 38/45.6 58.8/68.3 60/70

35* /40* 53.2/60.8 77.8/87.3 80/90

– – 15.6 25

5 7.6 25.1 35

7.5 12.5 6/7.5 9.1/11.4 27/29.9 35/35

10* /12* 15.2/18.2 34.6/38.4 40/45

15* /20* 22.8/30.4 44.1/53.6 50/60

25* /30* 38/45.6 63.1/72.6 70/80

35* /40* 53.2/60.8 82.1/91.6 90/100

– – 8.6 15

5 6.3 16.5 20

460-3-60 414 506

5 6.9 6/7.5 7.5/9.4 18/20.4 20/25

10* /12* 12.6/15.1 24.4/27.5 30/30

15* /20* 18.8/25.1 32.1/40 35/45

25* /30* 31.4/37.7 47.9/55.8 50/60

35* /40* 43.9/50.2 63.5/71.4 70/80

– – 12.2 20

5 6.3 20.1 25

7.5 9.75 6/7.5 7.5/9.4 21.6/23.9 25/30

10* /12* 12.6/15.1 27.9/31.1 30/35

15* /20* 18.8/25.1 35.7/43.6 40/45

25* /30* 31.4/37.7 51.4/59.3 60/70

35* /40* 43.9/50.2 67.1/74.9 70/80

POWER

SUPPLY

(V-Ph-Hz)

VOLTAGE

RANGE

BLOWER

MOTOR ELECTRIC HEATERMCA MOCP

MODEL No.: BWY18

(STD.)

(ALT.)

(STD.)

(ALT.)

(STD.)

(ALT.)

(4 WIRE)

13

Page 16: BWY Series

7/27/2019 BWY Series

http://slidepdf.com/reader/full/bwy-series 16/24

DIMENSIONS

BWY03 - BWY14 (HORIZONTAL DISCHARGE)

A B C D E F G H J K L M N P Q R

BWY03 1092(43) 648(25.5) 575(22.64) 483(19.02) 143(5.63) 406(15.98) 45(1.77) 542(21.34) 524(20.63) 297(11.69) 553(21.77) 171(6.73) 178(7.01) 140(5.51) 19(0.75) 19(0.75)

BWY05 1092(43) 813(32 ) 600 (23.62 ) 483(19 .02) 224(8.82) 406(15 .98) 45(1.77) 707(27.83 ) 550(21 .65) 297(11.69) 553(21 .77) 171(6.73 ) 178 (7 .01) 140 (5.51 ) 25(1) 25 (1 )

BWY07 1360(53.5) 1100(43.31) 600(23.62) 813(32) 182(7.16) 406(15.98) 66(2.6) 995(39.17) 550(21.65) 378(14.88) 721(28.38) 164(6.46) 165(6.5) 132(5.2) 32(1.25) 25(1)

BWY10 1490(58.7) 1400(55.12) 675(26.57) 813(32) 332(13.1) 406(15.98) 42(1.65) 1295(51) 625(24.61) 378(14.88) 721(28.38) 112(4.41) 206(8.11) 140(5.51) 38(1.5) 32(1.25)

BWY14 1625(64) 1600(63) 705(27.75) 1321(52) 187(7.36) 406(15 .98) 55 (2 .16) 1495(58.86 ) 655(25.8) 471(18 .54) 791 (31.14 ) 127(5) 152(5.98 ) 140(5.51) 38 (1.5) 32 (1.25 )

MODELDIMENSIONS

14

NOTE: 1. All dimensions are in mm (dimensions in brackets are in inches).2. Hot water coil connection is available only if hot water coils are ordered.

Page 17: BWY Series

7/27/2019 BWY Series

http://slidepdf.com/reader/full/bwy-series 17/24

DIMENSIONS

BWY03 - BWY14 (VERTICAL DISCHARGE)

A B C D E F G H J K L M N P Q R

BWY03 1092(43) 648(25.5) 575(22.64) 483(19.02) 134(5.28) 406(15.98) 35(1.38) 543(21.38) 502(19.76) 285(11.22) 553(21.77) 171(6.73) 178(7.01) 140(5.51) 19(0.75) 19(0.75)

BWY05 1092(43) 813(32 ) 600 (23.62 ) 483(19 .02) 229(9.02) 406(15 .98) 32(1.26) 712(28.03 ) 502(19 .76) 300(11.81) 553(21 .77) 171(6.73 ) 178 (7 .01) 140 (5.51 ) 25(1) 25 (1 )

BWY07 1360(53.5) 1100(43.31) 600(23 .62) 813(32 ) 213(8.4) 406(15 .98) 85(3.34) 991(39) 504(19 .83) 302(11.87) 697(27 .53) 164(6.46) 165(6.5 ) 132 (5 .2 ) 32 (1 .25 ) 25 (1)

BWY10 1490(58.7) 1400(55.12) 675(26.57) 813(32) 365(14.38) 406(15.98) 35(1.38) 1299(51.15) 607(23.91) 338(13.29) 732(28.81) 101(3.98) 194(7.64) 159(6.26) 38(1.5) 32(1.25)

BWY14 1625(64) 1600(63) 705(27.75) 1321(52) 224(8.82) 406(15 .98) 49 (1 .92) 1497(58.95 )607 (23.91 ) 370(14.59) 929 (36.56 ) 127(5) 152(5.98 ) 140(5.51) 38(1.5) 32 (1.25 )

MODEL

DIMENSIONS

15

NOTE: 1. All dimensions are in mm (dimensions in brackets are in inches).2. Hot water coil connection is available only if hot water coils are ordered.

Page 18: BWY Series

7/27/2019 BWY Series

http://slidepdf.com/reader/full/bwy-series 18/24

DIMENSIONS

BWY18 - BWY25 (HORIZONTAL DISCHARGE)

A B C D E F G H J K L M N P Q R

BWY18 1625(64) 2070(81.5) 705(27.75) 1575(62) 382(15.04) 483(19.02) 35(1.38) 1965(77.36) 655(25.79) 471(18.54) 791(31.14) 127(5) 152(5.98) 140(5.51) 38(1.5) 32(1.25)

BWY25 1825(71.85) 2362(93) 840(33.1) 1575(62) 590(23.23) 483(19.02) 50(1.97) 2257(88.86) 790(31.1) 503(19.8) 913(35.94) 127 (5 ) 152(5.98) 140 (5.51 ) 38(1.5) 32 (1.25 )

MODEL

DIMENSIONS

16

NOTE: 1. All dimensions are in mm (dimensions in brackets are in inches).2. Hot water coil connection is available only if hot water coils are ordered.

Page 19: BWY Series

7/27/2019 BWY Series

http://slidepdf.com/reader/full/bwy-series 19/24

DIMENSIONS

BWY18 - BWY25 (VERTICAL DISCHARGE)

A B C D E F G H J K L M N P Q R

BWY18 1625(64) 2070(81.5) 705(27.75) 1575(62) 422(16.61) 483(19.02) 46(1.81) 1969(77.52) 596(23.46) 354(13.94) 878(34.57) 127(5) 152(5.98) 140(5.51) 38(1.5) 32(1.25)

BWY25 1825(71.85) 2362(93) 840(33.1) 1575(62) 625(24.61) 483(19.02) 74(2.91) 2217(87.28) 596(23.46) 704(27.72) 878(34.57) 127(5) 152(5.98) 140(5.51) 38(1.5) 32(1.25)

MODEL

DIMENSIONS

17

NOTE: 1. All dimensions are in mm (dimensions in brackets are in inches).2. Hot water coil connection is available only if hot water coils are ordered.

Page 20: BWY Series

7/27/2019 BWY Series

http://slidepdf.com/reader/full/bwy-series 20/24

DIMENSIONS - HEATER BOX

 4 1 5 (  1 6.

 3  "  ) 

   2   0   5

   (   8 .   1

   "   )

4 9 0 ( 1 9 .3 "  )  

 2 5. 4 (  1

  "  ) 

HEATERCONTROLSMTG

COVER

HEATERCONTROLSMTGPLATE

  T  Y P

   2   0   5

   (   8 .   1

   "   )

 4 1 2 (  1 6

. 2  "  ) 

 2  5. 4  (  1

  "  )   T  Y  P

HEATER CONTROLS MTG

COVERHEATER CONTROLS MTG

HEATER ACCESS COVER

PLATE

15 8 1 ( 6 2 .3 " )  

   2   0   5

   (   8 .   1

   "   )

 4 9 2  (  1 9

. 4  "  ) 

 2  5. 4  (  1

  "  )   T  Y  P

HEATER CONTROLS MTGCOVER

HEATER CONTROLS MTG

HEATER ACCESS COVER

PLATE

(BOTH SIDES)

BWY03 - BWY05

BWY07 - BWY14

BWY18 - BWY25

NOTES: 1. All dimensions are in mm (dimensions in brackets are in inches).2. Heater box is an optional feature.

A

BWY07 818 (32.2)

BWY10 818 (32.2)

BWY14 1326(52.2)

MODEL

DIMENSIONS

18

Page 21: BWY Series

7/27/2019 BWY Series

http://slidepdf.com/reader/full/bwy-series 21/24

WITHFURNAS/SIEMENSCONTACTORAND OLR

VFCOPTION FORBMON,OFF&TRIP INDICATION

TYPICAL SCHEMATIC WIRING DIAGRAM

NOTES

1. POWER SUPPLY, REFER TO UNIT NAMEPLATE.

THERMOSTAT CONTROL VOLTAGE - 24VAC.

2. ANY WIRE REPLACEMENT SHOULD BE OF THE 900C

OR ITS EQUIVALENT.

USE COPPER CONDUCTOR WIRES ONLY.

3. A 3 TO 4 MINUTE (APPROX.) BUILT-IN SHORT CYCLEPROTECTION FOR COMPRESSOR IS AVAILABLE INZAMIL ELECTRONIC THERMOSTAT.

4. IF HEATERS ARE FACTORY INSTALLED, PLEASE

READ BROKEN LINES AS CONTINUOUS LINES.

5. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER

TO BE PROVIDED BY CONSUMER WITH RATING AS

RECOMMENDED BY MANUFACTURER.

6. HVTB IS REQUIRED ONLY FOR HEATER MODELS.

7. BMC-OLR CONNECTING WIRE NOT REQUIRED FOR

OLR. FIXED DIRECTLY BENEATH CONTACTOR.

8. NEUTRAL LINE REQUIRED ON 380V-3Ph-60Hz POWER

SUPPLY ONLY.

LEGEND

AFS AIRFLOW SWITCH

ATB AUXILIARY TERMINAL BLOCK

AR AUXILIARY RELAY

BM BLOWER MOTOR

BMC BLOWER MOTOR CONTACTORECB ELECTRONIC CONTROL BOARD

FL FUSE LINK

HC HEATER CONTACTOR

HVTB HIGH VOLTAGE TERMINAL BLOCK

HTR HEATER

L1 LINE 1

L2 LINE 2

L3 LINE 3

LVTB LOW VOLTAGE TERMINAL BLOCK

LUG LUG GROUND

MOHT MANUAL RESET OHT

N NEUTRAL

NTB NEUTRAL TERMINAL BLOCK

OHT OVERHEAT THERMOSTAT

OLR OVER LOAD RELAY

VFC VOLT FREE CONTACT

FIELD WIRINGDISCONNECT TAB - 1/4"

 _ _ _ +

19

REFER TO UNITNAMEPLATE FORPOWER SUPPLY

N (SEE NOTE -8)

Page 22: BWY Series

7/27/2019 BWY Series

http://slidepdf.com/reader/full/bwy-series 22/24

CONTROLS & SEQUENCE OF OPERATIONThe operation of the air conditioning unit is controlled by a 24VAC electronic control board. All the contactors are oper-

ated by the 24V circuit, including the thermostat.

Mode:

Select the desired mode of operation by continuous press-ing of the MODE button:

Controls cooling system only (the word COOL will

display for 5 seconds).

Controls heating system only (the word HEAT will

display for 5 seconds).

HEAT/COOL - Controls both systems automati-

cally (the word AUTO will display for 5 seconds).

OFF - Systems will not operate.

Cooling:

Select the temperature you want your cooling system tomaintain by pressing and holding the COOLING button

under the or symbols until the desired temperature

is displayed. The control setpoint temperature is displayed

for 5 seconds.

Heating:Select the temperature you want your heating system to maintain by pressing and holding the HEATING button under

the or symbols until the desired temperature is displayed. The control setpoint temperature is displayed for 5

seconds.

Fan:The fan will be energized automatically when the systems are operating but no indication of this on the display. To selectcontinuous fan operation, press the FAN button and the display will show . This is recommended for electronic air

cleaners and continuous ventilation requirements.

Off When the word OFF is displayed the heating and cooling systems will not operate. Avoid using the OFF mode during

extremely cold weather to prevent damage from freezing.

Auto:Selecting this mode of operation will control both heating and cooling systems. The thermostat will automatically switch

from one to the other as determined by the selected temperatures in heating and cooling.

NOTE: The thermostat always maintains a minimum 20F (10C) difference or dead band between the heating and cooling

setpoints.

Celsius/FahrenheitSimultaneously press and to switch between Celsius and Fahrenheit temperature display.

Clogged filter switch not provided

Field Wiring

Thermostat

LED 2

LED 1

*

W2

24 V

(C)24 V

L

HG

TS

I

RelaysEquipment

Y1

G

W1

Y2

R

2nd stage

Compressor Fault

Clogged Filter 

Heating

*

24VAC

Cooling

1st stageHeating

Fan Relay

1st stage

2nd stageCooling

Line VoltageTransformer 

20

Page 23: BWY Series

7/27/2019 BWY Series

http://slidepdf.com/reader/full/bwy-series 23/24

INSTALLATION INSTRUCTIONSA. GENERALBlower units are shipped completely wired. Only external power, control wiring & piping connections are needed tocomplete the installation.

B. UNIT LOCATION & ACCESS SPACEThe placement of the unit in relationship to the building is very important. A minimum of 36 inches clearance must be kepton the service access side and return air side.When making piping connections, be sure to provide clearance for electrical connections.

C. TUBING INSTALLATIONDo not remove plugs from the pipe stub out until tubing has been run and is ready for connection.

a. Make sure the tubing is round, without dent or burrs.

b. Cut tubing to the length required.

NOTE: When installing piping through walls or along side of any structural members, be sure the piping is isolated fromthese members or walls to avoid any transmission of vibration that may occur, while unit is running.

ELECTRICALSTEP 1: INSTALLATIONA) Please ensure power supply to the unit is as per unit nameplate (Volts/Ph/Hz) requirements.

Caution: Operation of the unit on improper power supply will result in damage to the unit.

NOTE: Use copper wires of proper rating for all field wiring.

Warning: Before servicing or installation of the unit, always TURN OFF all power to the unit. There may be more than

one disconnect switch. Ensure all of them are turned off. Electrical shock can cause personal injury or death.

B) Ground & power wires

Connect power wires to terminal block per wiring diagram.

Connect ground wire to the ground lug inside the control box.

C) Control wiring

Use 16 gauge color-coded wire for control wiring.

STEP 2: SEQUENCE OF OPERATIONWith power supplied to indoor unit, the unit starts responding to the thermostat mode requirement.

Cooling mode: When thermostat calls for cooling, the blower motor in the indoor unit is switched on.

As the conditioned space approaches the thermostat cooling set point, the unit cycles off.

Heating mode: When thermostat calls for heating, the blower motor in the indoor unit is switched on. The contactor for

electric heater is switched on to energize the heaters. If the room temperature is not satisfied and there are two heatersinstalled, the second heater also will be energized. Once, the conditioned space approaches the desired temperature setpoint, the heating stages cycles off.

Fan mode: In this mode the indoor unit blower motor is switched on alone.

21

PERCENTAGE OF SPARE PARTS

ONE YEAR SUPPLY TWO YEAR SUPPLY

100 UNITS 1000 UNITS 100 UNITS 1000 UNITS

ITEM

EVAPORATOR BLOWER MOTOR 2 1 4 2

HEATER CONTACTOR 2 1 3 2

ELECTRIC HEATER 2 1 4 2

BLOWER WHEEL 2 1 4 2

THERMOSTAT 2 1 4 2

FILTER 4 2 6 4

RECOMMENDED SPARE PARTS

NOTE :  When ordering spare parts, please quote the complete model number on the unit nameplate.

Page 24: BWY Series

7/27/2019 BWY Series

http://slidepdf.com/reader/full/bwy-series 24/24

PL-AP-BWY-08-2M-E


Recommended