Export
EN
Regulation
Diematic iSystemFor C 330 / C 630 ECO
C002695-A
Installation, Userand ServiceManual
7600676-001-01
Contents
1 Introduction ................................................................................................41.1 Symbols used .......................................................4
1.2 Abbreviations ........................................................4
1.3 General ..................................................................41.3.1 Manufacturer's liability .............................................41.3.2 Installer's liability .....................................................51.3.3 User's liability ..........................................................5
1.4 Certifications .........................................................6
2 Safety instructions and recommendations ..............................................72.1 Recommendations ................................................7
3 Technical specifications ............................................................................83.1 Sensor characteristics .........................................8
4 Installation ..................................................................................................94.1 Package list ...........................................................9
4.1.1 Standard delivery ....................................................94.1.2 Accessories .............................................................9
4.2 Installing the outside sensor .............................104.2.1 Choice of the location ............................................104.2.2 Connecting the outside sensor ..............................10
4.3 Fitting and connecting the control panel .........11
4.4 Electrical connections ........................................114.4.1 Connecting a direct heating circuit ........................114.4.2 Connecting a direct heating circuit and a domestic hot
water tank ..............................................................124.4.3 Connecting two circuits and a domestic hot water
tank .......................................................................144.4.4 Connecting two circuits and a domestic hot water tank
after the mixing tank ..............................................164.4.5 Hot water storage tank connection ........................174.4.6 Pool connection .....................................................214.4.7 Connecting the options .........................................234.4.8 Connection in cascade ..........................................24
5 Commissioning ........................................................................................265.1 Control panel .......................................................26
5.1.1 Description of the keys ..........................................26
1 29/05/2012 - 7600676-001-01
5.1.2 Description of the display ......................................275.1.3 Access to the various browsing levels ..................305.1.4 Browsing in the menus ..........................................31
5.2 Putting the appliance into operation ................32
5.3 Checks and adjustments aftercommissioning ...................................................335.3.1 Displaying the parameters in extended
mode .....................................................................335.3.2 Setting the parameters specific to the
installation .............................................................335.3.3 Naming the circuits and generators ......................375.3.4 Setting the heating curve ......................................38
5.4 Reading out measured values ...........................40
5.5 Modifying the user settings ...............................415.5.1 Setting the set point temperatures ........................415.5.2 Selecting the operating mode ...............................425.5.3 Forcing domestic hot water production .................435.5.4 Setting the contrast and lighting on the
display ...................................................................445.5.5 Setting the time and date ......................................445.5.6 Selecting a timer programme ................................455.5.7 Customising a timer programme ...........................455.5.8 Setting an annual clock .........................................47
5.6 Modifying the installer settings .........................505.6.1 Language selection ...............................................505.6.2 Calibrating the sensors .........................................515.6.3 Professional settings .............................................525.6.4 Configuring the network ........................................605.6.5 Return to the factory settings ................................63
6 Maintenance ..............................................................................................646.1 General instructions for the user ......................64
6.2 Chimney sweep instructions .............................64
6.3 Customising maintenance .................................656.3.1 Maintenance message ..........................................656.3.2 Contact details of the professional for After Sales
Support ..................................................................66
7 Troubleshooting .......................................................................................677.1 Anti-hunting ........................................................67
7.2 Messages (Code type Bxx or Mxx) ....................67
7.3 Message history ..................................................70
7.4 Faults (Code type Lxx or Dxx) ...........................707.4.1 Deletion of sensors from the memory in the
PCB .......................................................................79
Contents
2 29/05/2012 - 7600676-001-01
7.5 Failure history .....................................................79
7.6 Parameter and input/output check (modetests) ....................................................................807.6.1 Control system sequence ......................................82
3 29/05/2012 - 7600676-001-01
1 Introduction
1.1 Symbols used
In these instructions, various danger levels are employed to draw theuser's attention to particular information. In so doing, we wish tosafeguard the user's safety, obviate hazards and guarantee correctoperation of the appliance.
DANGER
Risk of a dangerous situation causing serious physicalinjury.
WARNING
Risk of a dangerous situation causing slight physicalinjury.
CAUTION
Risk of material damage.
Signals important information.
¼ Signals a referral to other instructions or other pages in theinstructions.
1.2 Abbreviations
4 DHW: Domestic hot water4 3WV: 3-way valve
1.3 General
1.3.1. Manufacturer's liability
Our products are manufactured in compliance with the requirementsof the various applicable European Directives. They are therefore
delivered with [ marking and all relevant documentation.
Diematic iSystem For C 330 / C 630 ECO 1. Introduction
29/05/2012 - 7600676-001-01 4
In the interest of customers, we are continuously endeavouring tomake improvements in product quality. All the specifications stated inthis document are therefore subject to change without notice.
Our liability as the manufacturer may not be invoked in the followingcases:
4 Failure to abide by the instructions on using the appliance.4 Faulty or insufficient maintenance of the appliance.4 Failure to abide by the instructions on installing the appliance.
1.3.2. Installer's liability
The installer is responsible for the installation and inital start up of theappliance. The installer must respect the following instructions:
4 Read and follow the instructions given in the manuals providedwith the appliance.
4 Carry out installation in compliance with the prevailing legislationand standards.
4 Perform the initial start up and carry out any checks necessary.4 Explain the installation to the user.4 If a maintenance is necessary, warn the user of the obligation to
check the appliance and maintain it in good working order.4 Give all the instruction manuals to the user.
1.3.3. User's liability
To guarantee optimum operation of the appliance, the user mustrespect the following instructions:
4 Read and follow the instructions given in the manuals providedwith the appliance.
4 Call on qualified professionals to carry out installation and initialstart up.
4 Get your installer to explain your installation to you.4 To carry out inspections and maintenance required by a qualified
professional.4 Keep the instruction manuals in good condition close to the
appliance.This appliance is not intended to be used by persons (includingchildren) whose physcial, sensory or mental capacity is impaired orpersons with no experience or knowledge, unless they have thebenefit, through the intermediary of a person responsible for theirsafety, of supervision or prior instructions regarding use of theappliance. Care should be taken to ensure that children do not playwith the appliance.
1. Introduction Diematic iSystem For C 330 / C 630 ECO
5 29/05/2012 - 7600676-001-01
1.4 Certifications
This product complies to the requirements to the european directivesand following standards:
4 2006/95/EC Low Voltage Directive. Reference Standard:EN60.335.1.
4 2004/108/EC Electromagnetic Compatibility Directive. Genericstandards: EN1000-6-3 , EN 61000-6-1.
Diematic iSystem For C 330 / C 630 ECO 1. Introduction
29/05/2012 - 7600676-001-01 6
2 Safety instructions andrecommendations
2.1 Recommendations
WARNING
Any intervention on the appliance and heating equipmentmust be carried out by a qualified engineer.For a proper operating of the boiler, follow carefully theinstructions.
Keep this document close to the place where the boiler isinstalled.
2. Safety instructions and recommendations Diematic iSystem For C 330 / C 630 ECO
7 29/05/2012 - 7600676-001-01
3 Technical specifications
3.1 Sensor characteristics
Outside sensorTemperature in °C -20 -16 -12 -8 -4 0 4 8 12 16 20 24Resistance in Ω 2392 2088 1811 1562 1342 1149 984 842 720 616 528 454
Specifications of the flow sensor circuit B + CSpecifications of the DHW sensorSpecifications of the system sensorTemperature in °C 0 10 20 25 30 40 50 60 70 80 90Resistance in Ω 32014 19691 12474 10000 8080 5372 3661 2535 1794 1290 941
Diematic iSystem For C 330 / C 630 ECO 3. Technical specifications
29/05/2012 - 7600676-001-01 8
4 Installation
4.1 Package list
4.1.1. Standard delivery
The delivery includes:
4 The control panel with the Diematic iSystem module4 Outside sensor4 Installation, User and Service Manual
4.1.2. Accessories
Various options are available depending on the configuration of theinstallation:
Control system optionsDescription packageRX12 cable AD134TELCOM 2 voice remote monitoring module AD152Flow sensor AD199DHW sensor AD212Optional PCB for 3-way valve AD249Hot water storage tank sensor AD250Outside radio-controlled temperature sensor AD251Boiler radio module AD252Radio remote control AD253Interactive remote control AD254Room sensor FM52Room sensor AD244RX11 cable AD124Connecting cable (40 m) DB119Dip sensor AD218
4. Installation Diematic iSystem For C 330 / C 630 ECO
9 29/05/2012 - 7600676-001-01
4.2 Installing the outside sensor
4.2.1. Choice of the location
It is important to select a place that allows the sensor to measure theoutside conditions correctly and effectively.
Advised positions:
4 on one face of the area to be heated, on the north if possible4 half way up the wall in the room to be heated4 under the influence of meteorological variations4 protected from direct sunlight4 easy to access
A Recommended positionB Possible positionH Inhabited height controlled by the sensorZ Inhabited area controlled by the sensor
Positions to be avoided:
4 masked by a building element (balcony, roof, etc.)4 close to a disruptive heat source (sun, chimney, ventilation grid,
etc.)
4.2.2. Connecting the outside sensor
Mount the sensor using the screws and dowels provided.
8800N001-C
8800N002-C
Diematic iSystem For C 330 / C 630 ECO 4. Installation
29/05/2012 - 7600676-001-01 10
A Inserts
Z Ø4 wood screw
¼ For the connection of the outside temperature sensor, refer tothe chapter "Electrical Connections".
4.3 Fitting and connecting the control panel
¼ Refer to the boiler's installation and service manual.
4.4 Electrical connections
4.4.1. Connecting a direct heating circuit
L000158-C
2
4
3
On/off
OTBLRLTout
1
TS + B AB
0-10V S AMB C
4 3 2 1 2 1+ -
S AMB B
2 1
S AMB A
2 1
S SYST + TA - S ECS S EXT S DEP C
2 12 12 12 1 2 1
S DEP B
2 1
SCU PCU
PUMP
5
A Do not connect anything to the terminal block.
Z Connect the outside temperature sensor.
E Heating connection pump.
8800N003-C
2
4. Installation Diematic iSystem For C 330 / C 630 ECO
11 29/05/2012 - 7600676-001-01
R Connect a safety thermostat if the heating circuit is forunderfloor heating.
4 Remove the bridge.4 Connect the wires from the safety thermostat to the
connector.
T Do not connect anything to the terminal block.
4.4.2. Connecting a direct heating circuit and adomestic hot water tank
L000159-C
6
4
5
7
8
2
3
1
TS + B AB
0-10V S AMB C
4 3 2 1 2 1+ -
S AMB B
2 1
S AMB A
2 1
S SYST + TA - S ECS S EXT S DEP C
2 12 12 12 1 2 1
S DEP B
2 1
SCU PCU
TS + C AUXC
On/off
OTBLRLTout
PUMP
9
A Do not connect anything to the terminal block.
Z Domestic load pump connection
E Connect the heating pump
R Connect a safety thermostat if the heating circuit is forunderfloor heating.
4 Remove the bridge.4 Connect the wires from the safety thermostat to the
connector.
Diematic iSystem For C 330 / C 630 ECO 4. Installation
29/05/2012 - 7600676-001-01 12
T Connect the DHW tank anode.
CAUTION
4 If the tank is fitted with a Titan ActiveSystem® impressed current anode,connect the anode to the inlet (+ TA on theanode, - on the tank).
4 If the tank is not fitted with an impressedcurrent anode, put the simulationconnector in place (delivered with the DHWsensor - package AD212).
Y Connect the outside temperature sensor.
U Connect the DHW sensor (Package AD212).
I Connect the domestic hot water looping pump(Optional).
O Do not connect anything to the terminal block.
If a low-loss header is used, connect the primary pumpbefore the header to the PUMP connector on the PCU.
Settings to be made for this type of installationParameters Access Settings to be made SeeINSTALLATION Installer level
Menu #SYSTEMEXTENDED ¼ "Displaying the
parameters in extended mode",page 33
If a domestic hot water looping pump isconnected to MAUX on the terminalblock:O.PUMP AUX(1)
Installer levelMenu #SYSTEM
DHW LOOP ¼ "Setting the parametersspecific to the installation", page33
If safety thermostat is connected toBL on the connection terminal block:IN.BL
Installer levelMenu #PRIMARYINSTAL.P
TOTAL STOP ¼ "Professional settings",page 52
(1) The parameter is only displayed if INSTALLATION is set to EXTENDED
4. Installation Diematic iSystem For C 330 / C 630 ECO
13 29/05/2012 - 7600676-001-01
4.4.3. Connecting two circuits and a domestic hotwater tank
L000160-C
7
8
11
10
6
5
1
2
4
9
3
TS + B AB
0-10V S AMB C
4 3 2 1 2 1+ -
S AMB B
2 1
S AMB A
2 1
S SYST + TA - S ECS S EXT S DEP C
2 12 12 12 1 2 1
S DEP B
2 1
TS + C AUXC
SCU
On/off
OTBLRLTout
PCU
PUMP
12
A Do not connect anything to the terminal block.
Z Connect a safety thermostat if the heating circuit is forunderfloor heating.
4 Remove the bridge.4 Connect the wires from the safety thermostat to the
connector.
E Connecting an additional circuit to the AD249 option.
R Connect the heating pump (circuit A).
If underfloor heating is being used, put a safetythermostat in place after the heating pump. Thesafety thermostat will shut down the heatingpump in the event of overheating.
Diematic iSystem For C 330 / C 630 ECO 4. Installation
29/05/2012 - 7600676-001-01 14
T Connect the DHW tank anode.
CAUTION
4 If the tank is fitted with a Titan ActiveSystem® impressed current anode,connect the anode to the inlet (+ TA on theanode, - on the tank).
4 If the tank is not fitted with an impressedcurrent anode, put the simulationconnector in place (delivered with the DHWsensor - package AD212).
Y Connect the outside temperature sensor.
U Connect the heating pump (circuit B).
I Connect the 3-way valve (circuit B).
O Domestic load pump connection.
P Connect the DHW sensor (Package AD212).
a Connect the domestic hot water looping pump to theMAUX outlet on the AD249 option.
z Do not connect anything to the terminal block.
4. Installation Diematic iSystem For C 330 / C 630 ECO
15 29/05/2012 - 7600676-001-01
4.4.4. Connecting two circuits and a domestic hotwater tank after the mixing tank
M002734-A
7
8
11
10
6
5
1
2
4
9
3
TS + B AB
0-10V S AMB C
4 3 2 1 2 1+ -
S AMB B
2 1
S AMB A
2 1
S SYST + TA - S ECS S EXT S DEP C
2 12 12 12 1 2 1
S DEP B
2 1
TS + C AUXC
SCU
On/off
OTBLRLTout
PCU
PUMP
12
13
14
A Do not connect anything to the terminal block.
Z Connect a safety thermostat if the heating circuit is forunderfloor heating.
4 Remove the bridge.4 Connect the wires from the safety thermostat to the
connector.
E Connecting an additional circuit to the AD249 option.
R Connect the heating pump (circuit A).
If underfloor heating is being used, put a safetythermostat in place after the heating pump. Thesafety thermostat will shut down the heatingpump in the event of overheating.
Diematic iSystem For C 330 / C 630 ECO 4. Installation
29/05/2012 - 7600676-001-01 16
T Connect the DHW tank anode.
CAUTION
4 If the tank is fitted with a Titan ActiveSystem® impressed current anode,connect the anode to the inlet (+ TA on theanode, - on the tank).
4 If the tank is not fitted with an impressedcurrent anode, put the simulationconnector in place (delivered with the DHWsensor - package AD212).
Y Connect the outside temperature sensor.
U Connect the heating pump (circuit B).
I Connect the 3-way valve (circuit B).
O Domestic load pump connection.
P Connect the DHW sensor (Package AD212).
a Connect the domestic hot water looping pump to theMAUX outlet on the AD249 option.
z Do not connect anything to the terminal block.
e Low loss header
r Boiler pump
4.4.5. Hot water storage tank connection
n QUADRO DU storage tank
In this installation example, the storage tank (type QUADRO DU)incorporates a domestic hot water zone. The boiler starts upsystematically to maintain the domestic hot water zone in the storagetank or to maintain the independent tank at temperature.
If the storage tank does not have a DHW zone, use anindependent domestic hot water tank.
4. Installation Diematic iSystem For C 330 / C 630 ECO
17 29/05/2012 - 7600676-001-01
L000161-CTS + B AB
0-10V S AMB C
4 3 2 1 2 1+ -
S AMB B
2 1
S AMB A
2 1
S SYST + TA - S ECS S EXT S DEP C
2 12 12 12 1 2 1
S DEP B
2 1
SCU
On/off
OTBLRLTout
PCU
PUMP
10
6
3
2
4
9
8
5
7
1
M
A Do not connect anything to the terminal block.
Z Connect the load pump from the buffer tank.
E Connect the sensor from the storage tank (PackageAD250).
R Buffer tank.
T Connect the DHW tank anode.
If the tank is not fitted with an impressed currentanode, put the simulation connector in place(delivered with the DHW sensor - packageAD212).
Y Connect the DHW sensor (Package AD212).
U Connect the heating pump (Circuit A).
I Solar sensor probe.
O Connect the solar station to the solar collectors.
P Do not connect anything to the terminal block.
Diematic iSystem For C 330 / C 630 ECO 4. Installation
29/05/2012 - 7600676-001-01 18
Settings to be made for this type of installationParameters Access Settings to be made SeeINSTALLATION Installer level
Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in extended mode", page
33I.SYST(1) Installer level
Menu #SYSTEMSTORAGE TANK ¼ "Setting the parameters specific to the installation",
page 33(1) The parameter is only displayed if INSTALLATION is set to EXTENDED
The DHW part is maintained at the DHW set point by theboiler.The heating zone is maintained at the set temperaturecalculated according to the outside temperature. The zoneis reheated when the heating buffer temperature sensorE falls -6°C below the calculated set temperature.Reheating in the heating zone stops when the heatingbuffer temperature rises above the calculated settemperature.
4. Installation Diematic iSystem For C 330 / C 630 ECO
19 29/05/2012 - 7600676-001-01
n PS storage tank and DHW tank connected to the boiler
5
3
2
1
L000162-DTS + B AB
0-10V S AMB C
4 3 2 1 2 1+ -
S AMB B
2 1
S AMB A
2 1
S SYST + TA - S ECS S EXT S DEP C
2 12 12 12 1 2 1
S DEP B
2 1
SCU
On/off
OTBLRLTout
PCU
PUMP
10
4
7
8
11
126
9
A Do not connect anything to the terminal block.
Z Reversal valve
E Buffer tank load pump.
R Connect a domestic hot water tank if the storage tank Ois only used for heating
T Connect the DHW sensor (Package AD212).
Y Connect the DHW tank anode.
If the tank is not fitted with an impressed currentanode, put the simulation connector in place(delivered with the DHW sensor - packageAD212).
U Connect the heating pump (Circuit A).
Diematic iSystem For C 330 / C 630 ECO 4. Installation
29/05/2012 - 7600676-001-01 20
I Solar sensor probe.
O Buffer tank.
P Do not connect anything to the terminal block.
a Connect the solar station to the solar collectors.
z Solar sensor probe
Settings to be made for this type of installationParameters Access Settings to be made SeeINSTALLATION Installer level
Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in extended mode", page
33I.SYST(1) Installer level
Menu #SYSTEMSTORAGE TANK ¼ "Setting the parameters specific to the installation",
page 33(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED
The DHW part is maintained at the DHW set point by theboiler.The heating zone is maintained at the set temperaturecalculated according to the outside temperature. The zoneis reheated when the heating buffer temperature sensor falls -6°C below the calculated set temperature. Reheatingin the heating zone stops when the heating buffertemperature rises above the calculated set temperature.
4.4.6. Pool connection
L000163-C
1
35
2
TS + B AB
0-10V S AMB C
4 3 2 1 2 1+ -
S AMB B
2 1
S AMB A
2 1
S SYST + TA - S ECS S EXT S DEP C
2 12 12 12 1 2 1
S DEP B
2 1
SCU
4
On/off
OTBLRLTout
PCU
PUMP
6
A Connect the secondary swimming pool pump.
Z Connect the swimming pool sensor.
E Plate heat exchanger.
4. Installation Diematic iSystem For C 330 / C 630 ECO
21 29/05/2012 - 7600676-001-01
R Pool heating cut-off control
When the parameter I.TEL: is on 0/1 B, theswimming pool is no longer heated when thecontact is open (factory setting), only theantifreeze continues to be active.The contact direction can still be adjusted by theparameter CT.TEL.
T Connect the primary swimming pool pump.
Y Do not connect anything to the terminal block.
Settings to be made for this type of installationParameters Access Settings to be made SeeINSTALLATION Installer level
Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in
extended mode", page 33CIRC. B: Installer level
Menu #SYSTEMSWIM.P. ¼ "Setting the parameters
specific to the installation", page33If I.TEL: is used
I.TEL:Installer levelMenu #SYSTEM
0/1 B
MAX. CIRC. B Installer levelMenu #SECONDARY LIMITS
Set the value of MAX.CIRC.B tothe temperature corresponding tothe needs of the exchanger
¼ "Professional settings", page52
n Controlling the pool circuit
The control system can be used to manage a swimming pool circuitin both cases:
Case 1: The control system regulates the primary circuit (boiler/exchanger) and the secondary circuit (exchanger/pool).
4 Connect the primary circuit pump (boiler/exchanger) to the MBoutlet on the connection terminal block. The temperature MAX.CIRC. B is then guaranteed during comfort periods on programmeB in summer and winter alike.
4 Connect the swimming pool sensor (package AD212) to the SDEP B inlet on the connection terminal block.
4 Set the set point of the pool sensor using key C in the range 5 -39°C.
Case 2: The pool has already a regulation system that is to bekept. The control system only regulates the primary circuit(boiler/exchanger).
4 Connect the primary circuit pump (boiler/exchanger) to the MBoutlet on the connection terminal block.The temperature MAX. CIRC. B is then guaranteed during comfortperiods on programme B in summer and winter alike.
The swimming pool can also be connected to circuit C byadding the AD249 option:
4 Make the connection to the terminal blocks markedC.
4 Set the parameters for circuit C.
Diematic iSystem For C 330 / C 630 ECO 4. Installation
29/05/2012 - 7600676-001-01 22
n Hourly programming of the secondary circuit pump
The secondary pump operates during programme B comfort periodsin summer and winter alike.
n Stopping
To prepare your pool for winter, consult your pool specialist.
4.4.7. Connecting the options
For example: TELCOM remote vocal monitoring module, remotecontrols for circuits A and B, second DHW tank
L000164-C
V
PRG
TELCOM 2
ALPAL2AL1
321
SET#09
V8765
4321
61
TS + B AB
0-10V S AMB C
4 3 2 1 2 1+ -
S AMB B
2 1
S AMB A
2 1
S SYST + TA - S ECS S EXT S DEP C
2 12 12 12 1 2 1S DEP B
2 1
TS + C AUXC
SCU PCU
On/off
OTBLRLTout
PUMP
8
3
4
2
7
5
MODE r
x 0 2 4 6 8 10 12 14 16 18 22 2420
c
MODE r
x 0 2 4 6 8 10 12 14 16 18 22 2420
c
A Do not connect anything to the terminal block.
Z Connect the load pump of the second tank
E Second domestic hot water tank
R Connect the DHW sensor of the second tank
T Connect the TELCOM remote vocal monitoring module(depending on its availability in your country).
Y Connecting the BUS cascade, VM
U Connect the remote control (Package AD254/FM52).
I Do not connect anything to the terminal block.
4. Installation Diematic iSystem For C 330 / C 630 ECO
23 29/05/2012 - 7600676-001-01
Settings to be made to connect a second tankParameters Access Settings to be made SeeINSTALLATION Installer level
Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in extended
mode", page 33If second tank connected:S.AUX:(1)
Installer levelMenu #SYSTEM
DHW ¼ "Setting the parameters specific to theinstallation", page 33
(1) The parameter is only displayed if INSTALLATION is set to EXTENDED
4.4.8. Connection in cascade
n DHW tank after the mixing tank
A Master boiler (DIEMATIC iSystem)
Z Secondary boiler (DIEMATIC iSystem or IniControl)
E Secondary boiler (DIEMATIC iSystem or IniControl)
R Cable BUS
T Boiler pump
Y Low loss header
U Cascade outlet sensorConnect the sensor to the terminal block S SYST on themaster boiler.
I D.H.W. load pump
O Connect the DHW sensor (Package AD212)
L000165-C
5
1 2
6
7
89
4 4
3
PUMP
Diematic iSystem For C 330 / C 630 ECO 4. Installation
29/05/2012 - 7600676-001-01 24
DIEMATIC iSystem - Settings to be made for this type of installation: Master boilerParameters Access Settings to be made SeeINSTALLATION Installer level
Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in extended
mode", page 33P.DHW(1) Installer level
Menu #SYSTEMPUMP ¼ "Setting the parameters specific to the
installation", page 33CASCADE:(1) Installer level
Menu #NETWORKON ¼ "Configuring the network", page 60
MASTER CONTROLLER(1) Installer levelMenu #SYSTEM
ON
SYSTEM NETWORK(1) Installer levelMenu #SYSTEM
ADD SLAVE
(1) The parameter is only displayed if INSTALLATION is set to EXTENDED
DIEMATIC iSystem - Settings to be made for this type of installation: Follower boilersParameters Access Settings to be made SeeINSTALLATION Installer level
Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in extended
mode", page 33CASCADE:(1) Installer level
Menu #NETWORKON ¼ "Configuring the network", page 60
MASTER CONTROLLER(1) Installer levelMenu #SYSTEM
OFF
SLAVE NUMBER(1) Installer levelMenu #SYSTEM
2, 3, ...
(1) The parameter is only displayed if INSTALLATION is set to EXTENDED
4. Installation Diematic iSystem For C 330 / C 630 ECO
25 29/05/2012 - 7600676-001-01
5 Commissioning
5.1 Control panel
5.1.1. Description of the keys
A Temperature setting key (heating, DHW, swimming pool)B Operating mode selection keyC DHW override keyD Key to access the parameters reserved for the installerE Keys on which the function varies as and when selections
are madeF Rotary setting button:
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the menu selectedor confirm a value modification
A0
00
86
6-A
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
A
B
C
D E F
( '
Diematic iSystem For C 330 / C 630 ECO 5. Commissioning
29/05/2012 - 7600676-001-01 26
5.1.2. Description of the display
n Key functions
> Access to the various menus
( Used to scroll through the menus
' Used to scroll through the parameters? The symbol is displayed when help is available
f Used to display the curve of the parameter selectedSTD Reset of the time programmes
b Selection of comfort mode or selection of the days to beprogrammed
v Selection of reduced mode or deselection of the days tobe programmed
j Back to the previous levelESC Back to the previous level without saving the
modifications made
t Manual reset
n Flame output level
C002705-A
The whole symbol flashes: The burner starts up but theflame is not yet present
C002704-A
Part of the symbol flashes: Output is increasing
C002703-A
Steady symbol: The required output has been reached
C002702-A
Part of the symbol flashes: Output is dropping
bar
r
STD( ' t
0 2 4 6 8 10 12 14 16 18 22 2420
C002696-A
pb AUTOx c rjLg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002701-B
pb AUTOx c rjMg m
5. Commissioning Diematic iSystem For C 330 / C 630 ECO
27 29/05/2012 - 7600676-001-01
n Solar (If connected)
u The solar load pump is running
L000200-A The top part of the tank is reheated to the tank set point
L000201-A The entire tank is reheated to the tank set point
L000198-A The entire tank is reheated to the solar tank set point
L000199-A The tank is not loaded - Presence of the solar control
system
n Operating modes
p Summer mode: The heating is off. Domestic hot watercontinues to be produced
b WINTER mode: Heating and domestic hot water working
AUTO Operation in automatic mode according to the timerprogramme
x Comfort mode: The symbol is displayed when a DAYoverride (comfort) is activated
4 Flashing symbol: Temporary override4 Steady symbol: Permanent override
m Reduced mode: The symbol is displayed when a NIGHToverride (reduced) is activated
4 Flashing symbol: Temporary override4 Steady symbol: Permanent override
g Holiday mode: The symbol is displayed when a HOLIDAYoverride (antifreeze) is activated
4 Flashing symbol: Holiday mode programmed4 Steady symbol: Holiday mode active
m Manual mode
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
L000197-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002697-B
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002698-B
pb AUTOx c rjMg m
Diematic iSystem For C 330 / C 630 ECO 5. Commissioning
29/05/2012 - 7600676-001-01 28
n System pressure
bar Pressure indicator: The symbol is displayed when a waterpressure sensor is connected.
4 Flashing symbol: The water pressure is insufficient.4 Steady symbol: The water pressure is sufficient.
l Water pressure level
4 R : 0,9 to 1,1 bar4 E : 1,2 to 1,5 bar4 Z : 1,6 to 1,9 bar4 A : 2,0 to 2,3 bar4 l : > 2,4 bar
n Domestic Hot Water override
A bar is displayed when a DHW override is activated:
4 Flashing bar: Temporary override4 Steady bar: Permanent override
n Other information
r The symbol is displayed when domestic hot waterproduction is running.
w Valve indicator: The symbol is displayed when a 3-wayvalve is connected.
4 x : 3-way valve opens4 c : 3-way valve closes
M The symbol is displayed when the pump is operating.
Name of the circuit for which the parameters aredisplayed.
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002708-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002707-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002699-B
pb AUTOx c rjMg m
5. Commissioning Diematic iSystem For C 330 / C 630 ECO
29 29/05/2012 - 7600676-001-01
5.1.3. Access to the various browsing levels
n User level
The information and settings in the User level can be accessed byeveryone.
1. Press the > key.
n Installer level
The information and settings in the Installer level can be accessed byexperienced people.
1. Press the > key.
2. Press the - key.
It is also possible to access the installer level by pressingonly the - key for around 5 seconds.
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
C002219-D-04
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
C002219-D-04
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
TEMP.: 68°
C002271-F-04
Diematic iSystem For C 330 / C 630 ECO 5. Commissioning
29/05/2012 - 7600676-001-01 30
n After Sales level
The After Sales Service information and settings can be accessed bythe professional providing the After Sales Service.
1. Press the > key.
2. Press key - for around 5 seconds.
It is also possible to access the After Sales level bypressing only the - key for around 10 seconds.
5.1.4. Browsing in the menus
1. To select the desired menu, turn the rotary button.2. To access the menu, press the rotary button.
To go back to the previous display, press the key j.
3. To select the desired parameter, turn the rotary button.4. To modify the parameter, press the rotary button.
To go back to the previous display, press the key j.
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
C002219-D-04
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
5"
TEMP.: 68°
C002235-F-04
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
#MEASURES
#CHOICE TIME PROG.
#TIME PROGRAM
#SETTING
#TIME .DAYa
C002220-B-04
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROG.B
CURRENT PROG.C
P2
P3
a
C002221-C-04
5. Commissioning Diematic iSystem For C 330 / C 630 ECO
31 29/05/2012 - 7600676-001-01
5. To modify the parameter, turn the rotary button.6. To confirm, press the rotary button.
To cancel, press key h.
7. To go back to the main display, press key j2 times.
It is possible to use the ( and ' keys instead of the rotarybutton.
5.2 Putting the appliance into operation
1. Open the main gas supply.2. Open the gas valve on the boiler.3. Turn on the boiler using the on/off switch.
4. The first time the boiler is powered up, the LANGUAGE menu isdisplayed. Select the desired language by turning the rotarybutton.
5. To confirm, press the rotary button.
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROG.C"Choice of the timeprogram applied C"
P4
a
C002222-C-04
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
LUNDI 11:45
C002224-D-04
2x
C002366-B
Français - Deutsch - English - Italiano - Espanol - Nederlands- Pycck - Polski - Türk -
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb x c rg m
ÿLANGUE FRANCAIS
C002286-C
Diematic iSystem For C 330 / C 630 ECO 5. Commissioning
29/05/2012 - 7600676-001-01 32
5.3 Checks and adjustments after commissioning
5.3.1. Displaying the parameters in extendedmode
The display mode on the control panel is set as standard in such away as only to show the conventional parameters. It is possible toswitch to extended mode by proceeding as follows:
1. Access the installer level: Press key - for around 5 seconds.2. Select the menu #SYSTEM.
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 31
3. Set parameter INSTALLATION to EXTENDED.
Installer level - Menu #SYSTEMParameter Adjustment range Description Factory setting Customer settingINSTALLATION CLASSIC Displays the parameters of a conventional
installationCLASSIC
EXTENDED Displays all parameters
Regardless of what is done to the keys, the regulatorswitches back to CLASSIC mode after 30 minutes.
5.3.2. Setting the parameters specific to theinstallation
1. Access the installer level: Press key - for around 5 seconds.2. Select the menu #SYSTEM.
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 31
3. Set the following parameters according to the connections madeto the PCBs:
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
5"
TEMP.: 68°
C002235-F-04
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
5"
TEMP.: 68°
C002235-F-04
5. Commissioning Diematic iSystem For C 330 / C 630 ECO
33 29/05/2012 - 7600676-001-01
Installer level - #SYSTEM menu
Parameter Adjustment range Description Factory setting Customersetting
CIRC. A: (1)(2) DIRECT Use as a direct heating circuit DIRECT PROGRAM. Use as an independent programmable outletH.TEMP Enables operation of circuit A in summer despite
manual or automatic summer shutdownDHW Connection of a second domestic hot water tankDHW ELEC Used to control the electrical resistor according to the
timer programme on circuit A in summer modeDISAB. No data for circuit A is displayed
O.PUMP A (1)
(2)CH.PUMP A Heating pump circuit A: The MA outlet is used to
control the pump on circuit ACH.PUMP A
CIRC.AUX Used to resume the functions of the S.AUX: parameterwithout adding the PCB + sensor option (PackageAD249)
DHW LOOP Used to control the domestic hot water looping pumpaccording to the DHW timer programme and force itsoperation during an override
PRIMARY PUMP The outlet MA is active if a heating demand is presenton the secondary pump
ORDER BURNER The outlet MA is active when a burner demand ispresent
FAILURE The outlet MA is active if an fault is detectedCIRC. B: (1) 3WV Connecting a circuit with 3-way valve (For example:
Underfloor heating)3WV
SWIM.P. Using the circuit for pool managementDIRECT Use of circuit in direct heating circuit
CIRC. C: (1) 3WV Connecting a circuit with 3-way valve (For example:Underfloor heating)
3WV
SWIM.P. Using the circuit for pool managementDIRECT Use of circuit in direct heating circuit
P.DHW: (1) PUMP Use of a tank load pump on the Mr outlet PUMP* (3) RV DO NOT USE
S.AUX (1)(4) DHW LOOP Use as a domestic loop pump DHW LOOP PROGRAM. Use as an independent programmable outletPRIMARY PUMP The outlet MAUX is active if a heating demand is
present on the secondary pumpORDER BURNER The outlet MAUX is active when a burner demand is
presentDHW Use of primary circuit of second DHW tankFAILURE The outlet MAUX is active if an fault is detectedDHW ELEC Used to control the electrical resistor according to the
timer programme on circuit AUX in summer modeI.SYST (1) SYSTEM The inlet sensor is used to connect the common flow
sensor of a cascade systemSYSTEM
STORAGE TANK Hot water storage tank affected to heating onlyDHW STRAT Using the DHW tank with 2 sensors (top and bottom)ST.TANK+DHW Hot water storage tank affected to heating and
domestic hot water(1) The parameter is only displayed if INSTALLATION is set to EXTENDED(2) If the pump incorporated in the boiler is used for circuit A (parameter CIRC. A: set to DIRECT), the MA outlet is free(3) This setting cannot be modified(4) The parameter is only displayed if the parameter O.PUMP A is set to CIRC.AUX or the 3-way valve PCB option is connected
Diematic iSystem For C 330 / C 630 ECO 5. Commissioning
29/05/2012 - 7600676-001-01 34
Installer level - #SYSTEM menu
Parameter Adjustment range Description Factory setting Customersetting
O. TEL: (1) FAILURE The telephone outlet is closed in the event of failure FAILURE REVISION The telephone outlet is closed in the event of revision
displayDEF+REV The telephone outlet is closed in the event of failure or
revision displayCT.TEL (1) CLOSE See table below. CLOSE
OPENI.TEL: (1) ANTIFR Start anti-freeze in boiler command ANTIFR
0/1 A ON or OFF contact: I.TEL: can be used as anantifreeze activation inlet on circuit A
0/1 B ON or OFF contact: I.TEL: can be used as anantifreeze activation inlet on circuit B
0/1 A+B ON or OFF contact: I.TEL: can be used as anantifreeze activation inlet on circuits A+B
0/1 C ON or OFF contact: I.TEL: can be used as anantifreeze activation inlet on circuit C
0/1 A+C ON or OFF contact: I.TEL: can be used as anantifreeze activation inlet on circuits A+C
0/1 B+C ON or OFF contact: I.TEL: can be used as anantifreeze activation inlet on circuits B+C
0/1 A+B+C ON or OFF contact: I.TEL: can be used as anantifreeze activation inlet on circuits A+B+C
I.TEL: (1) 0/1 DHW ON or OFF contact: I.TEL: can be used as anantifreeze activation inlet on circuit ECS
ANTIFR
0/1 A+DHW ON or OFF contact: I.TEL: can be used as anantifreeze activation inlet on circuits A+ECS
0/1 B+DHW ON or OFF contact: I.TEL: can be used as anantifreeze activation inlet on circuits B+ECS
0/1 A+B+DHW ON or OFF contact: I.TEL: can be used as anantifreeze activation inlet on circuits A+B+ECS
0/1 C+DHW ON or OFF contact: I.TEL: can be used as anantifreeze activation inlet on circuits C+ECS
0/1 A+C+DHW ON or OFF contact: I.TEL: can be used as anantifreeze activation inlet on circuits A+C+ECS
0/1 B+C+DHW ON or OFF contact: I.TEL: can be used as anantifreeze activation inlet on circuits B+C+ECS
0/1 AUX ON or OFF contact: I.TEL: can be used as anantifreeze activation inlet on circuit AUX (S.AUX: if theAD249 option is connected or the parameter O.PUMPA is set to CIRC.AUX)When I.TEL: is not active, the auxiliary circuit (AUX)follows the maximum boiler temperature (parameterBOILER MAX).
(1) The parameter is only displayed if INSTALLATION is set to EXTENDED(2) If the pump incorporated in the boiler is used for circuit A (parameter CIRC. A: set to DIRECT), the MA outlet is free(3) This setting cannot be modified(4) The parameter is only displayed if the parameter O.PUMP A is set to CIRC.AUX or the 3-way valve PCB option is connected
5. Commissioning Diematic iSystem For C 330 / C 630 ECO
35 29/05/2012 - 7600676-001-01
Influence of the parameter setting CT.TEL on the I.TEL: contactCT.TEL I.TEL: C contact closed C contact openCLOSE ANTIFR The antifreeze mode is active on all boiler circuits. The mode selected on the boiler is active.
0/1 A The mode selected on the circuit is active. The antifreeze mode is active on the circuitconcerned.
0/1 B The mode selected on the circuit is active. The antifreeze mode is active on the circuitconcerned.
0/1 A+B The mode selected on the circuits is active. The antifreeze mode is active on the circuitsconcerned.
0/1 C The mode selected on the circuit is active. The antifreeze mode is active on the circuitconcerned.
0/1 A+C The mode selected on the circuits is active. The antifreeze mode is active on the circuitsconcerned.
0/1 B+C The mode selected on the circuits is active. The antifreeze mode is active on the circuitsconcerned.
0/1 A+B+C The mode selected on the circuits is active. The antifreeze mode is active on the circuitsconcerned.
0/1 DHW The mode selected on the DHW circuit is active. The antifreeze mode is active for the DHW circuit.0/1 A+DHW The mode selected on the circuits is active. The antifreeze mode is active on the circuits
concerned.0/1 B+DHW The mode selected on the circuits is active. The antifreeze mode is active on the circuits
concerned.0/1 A+B+DHW The mode selected on the circuits is active. The antifreeze mode is active on the circuits
concerned.0/1 C+DHW The mode selected on the circuits is active. The antifreeze mode is active on the circuits
concerned.0/1 A+C+DHW The mode selected on the circuits is active. The antifreeze mode is active on the circuits
concerned.0/1 B+C+DHW The mode selected on the circuits is active. The antifreeze mode is active on the circuits
concerned.0/1 AUX 4 The MAUX outlet on the connection terminal
block is active.4 The boiler operates at a set point temperature
equal to BOILER MAX.
4 The MAUX outlet on the connection terminalblock is not active.
4 The boiler operates with a set pointtemperature as a function of the outsidetemperature.
Diematic iSystem For C 330 / C 630 ECO 5. Commissioning
29/05/2012 - 7600676-001-01 36
Influence of the parameter setting CT.TEL on the I.TEL: contactCT.TEL I.TEL: C contact closed C contact openOPEN ANTIFR The mode selected on the boiler is active. The antifreeze mode is active on all boiler circuits.
0/1 A The antifreeze mode is active on the circuitconcerned.
The mode selected on the circuit is active.
0/1 B The antifreeze mode is active on the circuitconcerned.
The mode selected on the circuit is active.
0/1 A+B The antifreeze mode is active on the circuitsconcerned
The mode selected on the circuits is active
0/1 C The antifreeze mode is active on the circuitconcerned.
The mode selected on the circuit is active.
0/1 A+C The antifreeze mode is active on the circuitsconcerned
The mode selected on the circuits is active
0/1 B+C The antifreeze mode is active on the circuitsconcerned
The mode selected on the circuits is active
0/1 A+B+C The antifreeze mode is active on the circuitsconcerned
The mode selected on the circuits is active
0/1 DHW The antifreeze mode is active for the DHW circuit. The mode selected on the DHW circuit is active.0/1 A+DHW The antifreeze mode is active on the circuits
concernedThe mode selected on the circuits is active
0/1 B+DHW The antifreeze mode is active on the circuitsconcerned
The mode selected on the circuits is active
0/1 A+B+DHW The antifreeze mode is active on the circuitsconcerned
The mode selected on the circuits is active
0/1 C+DHW The antifreeze mode is active on the circuitsconcerned
The mode selected on the circuits is active
0/1 A+C+DHW The antifreeze mode is active on the circuitsconcerned
The mode selected on the circuits is active
0/1 B+C+DHW The antifreeze mode is active on the circuitsconcerned
The mode selected on the circuits is active
0/1 AUX 4 The MAUX outlet on the connection terminalblock is not active.
4 The boiler operates with a set pointtemperature as a function of the outsidetemperature.
4 The MAUX outlet on the connection terminalblock is active.
4 The boiler operates at a set point temperatureequal to BOILER MAX.
5.3.3. Naming the circuits and generators
1. Access the installer level: Press key - for around 5 seconds.2. Select the menu #NAMES OF THE CIRCUITS.
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 31
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
5"
TEMP.: 68°
C002235-F-04
5. Commissioning Diematic iSystem For C 330 / C 630 ECO
37 29/05/2012 - 7600676-001-01
3. Select the circuit or generator you wish to rename.
Installer level - Menu #NAMES OF THE CIRCUITSParameter Description Name given by the customerCIRC. A: Circuit A CIRC. B: Circuit B CIRC. C: Circuit C CIRC.AUX Auxiliary circuit CIRC.DHW Domestic hot water circuit GENE Generator
4. Turn the rotary button to choose the first character from the list.To confirm, press the rotary button.
5. Then press again to enter a second character or turn the rotarybutton to leave an empty space.
6. Choose the other characters in the same way. The input zone maycontain up to 6 characters.
To move from one character to another, turn the rotarybutton. To exit without modifications, press key h.
7. To confirm the name, press the rotary button and then turn thebutton slightly anti-clockwise. When the symbol U appears, pressthe rotary button. The name is confirmed.
If the name reaches 6 characters, it is automaticallyconfirmed when the last character is confirmed.
5.3.4. Setting the heating curve
1. Access the installer level: Press key - for around 5 seconds.2. Select the menu #SECONDARY INSTAL.P.
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 31.
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CIRC.B I
"Personalize the nameof this circuit B"
a
E
F
G
H
..
.
C002344-E-04
I
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CIRC.B FLOOR1
"Personalize the nameof this circuit B"
a
X
Y
Z
.
.
.
C002345-D-04
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
5"
TEMP.: 68°
C002235-F-04
Diematic iSystem For C 330 / C 630 ECO 5. Commissioning
29/05/2012 - 7600676-001-01 38
3. Select the parameter CIRC. CURVE ....
4. To modify the value directly, turn the rotary button.To modify the value by displaying the curve, press key f.
5. To modify the curve, turn the rotary button.6. To confirm, press the rotary button.
To cancel, press key h.
0.7 = Heating curve set.
n Heating curve without BCT
A Maximum temperature of the circuit
Z Water temperature in the circuit for an outsidetemperature of 0°C
E DAY set point on the circuit
R Outside temperature for which the maximum watertemperature in the circuit is reached
T Value of the heating curveSelect the parameter CIRC. CURVE ...
When you modify the heating curve, Z and R arerecalculated and repositioned automatically.
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
BUILD.INERTIA
CIRC.CURVE B
CIRC.CURVE C
SCREED DRYING
3
2.0
0.7
No a
C002316-E-04
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
CIRC.CURVE B"Slope of the heatcurve of the circuit B"
2.0
C002317-D-04
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
7564
50
020 -15
C002318-B-04
0,7
0.7
20 0 -16
50
75
C°
C°
1.5
C002319-B
1
2
3
4
5
5. Commissioning Diematic iSystem For C 330 / C 630 ECO
39 29/05/2012 - 7600676-001-01
n Heating curve with BCT
The BCT (Base heat Curve Temperature) parameter allows aminimum operating temperature to be imposed on the heating circuit(this temperature may be constant if the circuit gradient is nil).
A Maximum temperature of the circuit
Z Water temperature in the circuit for an outsidetemperature of 0°C
E DAY set point on the circuit
R Outside temperature for which the maximum watertemperature in the circuit is reached
T Value of the heating curveSelect the parameter CIRC. CURVE ...
x Value set to the parameter HCZP D
When you modify the heating curve, Z and R arerecalculated and repositioned automatically.
5.4 Reading out measured values
The various values measured by the appliance are displayed in the#MEASURES menu.
1. To access user level: Press the > key.2. Select the menu #MEASURES.
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 31.
User level - Menu #MEASURES
Parameter Description UnitOUTSIDE TEMP. Outside temperature °CROOMTEMP. A (1) Room temperature of circuit A °C
ROOMTEMP. B (1) Room temperature of circuit B °C
ROOMTEMP. C (1) Room temperature of circuit C °CBOILER TEMP. Water temperature in the boiler °CPRESSURE Water pressure in the installation barWATER TEMP. (1) Water temperature in the DHW tank °CSTOR.TANK.TEMP(1)
Water temperature in the storage tank °C
SWIMMING P.T.B(1)
Water temperature of the swimming pool on circuit B °C
(1) The parameter is only displayed for the options, circuits or sensors actually connected.
20 0 -15
64
50
75
C°
C°
0.7
C002320-B
1
2
X
3
4
5
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
C002219-D-04
Diematic iSystem For C 330 / C 630 ECO 5. Commissioning
29/05/2012 - 7600676-001-01 40
User level - Menu #MEASURES
Parameter Description UnitSWIMMING P.T.C(1)
Water temperature of the swimming pool on circuit C °C
OUTLET TEMP. B(1)
Temperature of the flow water in circuit B °C
OUTLET TEMP. C(1)
Temperature of the flow water in circuit C °C
SYST.TEMP (1) Temperature of the system flow water if multi-generator °CT.DHW BOTTOM(1)
Water temperature in the bottom of the DHW tank °C
TEMP.TANK AUX(1)
Water temperature in the second DHW tank connected to the AUX circuit °C
DHW A TEMP. (1) Water temperature in the second DHW tank connected to circuit A °CTEMP.EXCHANGE Exchanger sensor measurement °CBACK TEMP Temperature of the boiler return water °CWIND SPEED Fan rotation speed rpmPOWER Instantaneous boiler output (0%: Burner off or running at minimum output) %CURRENT (µA) Ionization current µANB IMPULS. Number of burner starts (not restartable)
The meter is incremented by 8 every 8 start-ups
RUNTIME Number of burner operation hours (not restartable)The meter is incremented by 2 every 2 hours
h
IN 0-10V (1) Voltage at input 0-10 V VSEQUENCE Control system sequence CTRL Software control number (1) The parameter is only displayed for the options, circuits or sensors actually connected.
5.5 Modifying the user settings
5.5.1. Setting the set point temperatures
To set the various heating, DHW and swimming pool temperatures,proceed as follows:
1. Press the C key.2. To select the desired parameter, turn the rotary button.3. To modify the parameter, press the rotary button.
To go back to the previous display, press the key j.4. To modify the parameter, turn the rotary button.5. To confirm, press the rotary button.
To cancel, press key h.
MODE
C002266-A
5. Commissioning Diematic iSystem For C 330 / C 630 ECO
41 29/05/2012 - 7600676-001-01
Menu C
Parameter Adjustment range Description Factory settingDAY TEMP. A 5 to 30 °C Desired room temperature in comfort periods on circuit A 20 °CNIGHT TEMP. A 5 to 30 °C Desired room temperature in reduced periods on circuit A 16 °CDAY TEMP. B (1) 5 to 30 °C Desired room temperature in comfort periods on circuit B 20 °CNIGHT TEMP. B (1) 5 to 30 °C Desired room temperature in reduced periods on circuit B 16 °CDAY TEMP. C (1) 5 to 30 °C Desired room temperature in comfort periods on circuit C 20 °CNIGHT TEMP. C (1) 5 to 30 °C Desired room temperature in reduced periods on circuit C 16 °CWATER TEMP. (1) 10 to 80 °C Desired domestic hot water temperature in the DHW circuit 55 °CWATER T.NIGHT(1)
(2)10 to 80 °C Set tank temperature, night programme 10 °C
TEMP.TANK AUX (1) 10 to 80 °C Desired domestic hot water temperature in the auxiliary circuit 55 °CAUX.TANKT.NIGHT(1)(2)
10 to 80 °C Set tank temperature, night programme 10 °C
DHW A TEMP. (1) 10 to 80 °C Desired domestic hot water temperature in circuit A 55 °CA.TANK T.NIGHT(1)
(2)10 to 80 °C Set tank temperature, night programme 10 °C
SWIMMING P.T.B (1) 5 to 39 °C Desired temperature for swimming pool B 20 °CSWIMMING P.T.C (1) 5 to 39 °C Desired temperature for swimming pool C 20 °C(1) The parameter is only displayed for the options, circuits or sensors actually connected.(2) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED
5.5.2. Selecting the operating mode
To select an operating mode, proceed as follows:
1. Press the MODE key.2. To select the desired parameter, turn the rotary button.3. To modify the parameter, press the rotary button.
To go back to the previous display, press the key j.4. To modify the parameter, turn the rotary button.5. To confirm, press the rotary button.
To cancel, press key h.
Menu MODEParameter Adjustment range Description Factory settingAUTOMATIQUE The comfort ranges are determined by the timer programme.DAY 7/7, xx:xx Comfort mode is forced until the time indicated or all the time (7/7). Present time + 1
hourNIGHT 7/7, xx:xx Reduced mode is forced until the time indicated or all the time
(7/7).Present time + 1hour
(1) The start and end days and the number of days are calculated in relation to each other.(2) The parameter is only displayed if a room sensor is connected.
MODE
C002267-A
Diematic iSystem For C 330 / C 630 ECO 5. Commissioning
29/05/2012 - 7600676-001-01 42
Menu MODEParameter Adjustment range Description Factory settingHOLIDAYS 7/7, 1 to 365 The antifreeze mode is active on all boiler circuits.
Number of days' holiday: xx (1)
heating OFF: xx:xx (1)
Restarting: xx:xx (1)
Present date + 1day
SUMMER The heating is off.Domestic hot water continues to be produced.
MANUEL The generator operates according to the set point setting. All ofthe pumps operate. Option of setting the set point by simplyturning the rotary button.
FORCE AUTO (2) YES / NO An operating mode override is activated on the remote control(option).To force all circuits to run on AUTOMATIQUE mode, selectYES.
(1) The start and end days and the number of days are calculated in relation to each other.(2) The parameter is only displayed if a room sensor is connected.
5.5.3. Forcing domestic hot water production
To force domestic hot water production, proceed as follows:
1. Press the r key.2. To select the desired parameter, turn the rotary button.3. To modify the parameter, press the rotary button.
To go back to the previous display, press the key j.4. To modify the parameter, turn the rotary button.5. To confirm, press the rotary button.
To cancel, press key h.
Menu rParameter Description Factory settingAUTOMATIQUE The domestic hot water comfort ranges are determined by the timer programme. COMFORT Domestic hot water comfort mode is forced until the time indicated or all the time (7/7). Present time + 1 hour
MODE
C002268-A
5. Commissioning Diematic iSystem For C 330 / C 630 ECO
43 29/05/2012 - 7600676-001-01
5.5.4. Setting the contrast and lighting on thedisplay
1. To access user level: Press the > key.2. Select the menu #SETTING.
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 31.
3. To set the following parameters:
User level - Menu #SETTING
Parameter Adjustment range Description Factory setting Customer settingCONTRAST DISP. Adjusting the display contrast. BACK LIGHT COMFORT The screen is illuminated continuously in
daytime periods.ECO
ECO The screen is illuminated for 2 minuteswhenever pressed.
5.5.5. Setting the time and date
1. To access user level: Press the > key.2. Select the menu #TIME .DAY.
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 31.
3. To set the following parameters:
User level - Menu #TIME .DAY (1)
Parameter Adjustment range Description Factory setting Customer settingHOURS 0 to 23 Hours setting MINUTE 0 to 59 Minutes setting DAY Monday to Sunday Setting the day of the week DATE 1 to 31 Day setting MONTH January to December Month setting YEAR 2008 to 2099 Year setting SUM. TIME: AUTO automatic switch to summer time on the last Sunday
in March and back to winter time on the last Sundayin October.
AUTO
MANU for countries where the time change is done onother dates or is not in use.
(1) According to the configuration
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
C002219-D-04
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
C002219-D-04
Diematic iSystem For C 330 / C 630 ECO 5. Commissioning
29/05/2012 - 7600676-001-01 44
5.5.6. Selecting a timer programme
1. To access user level: Press the > key.2. Select the menu #CHOICE TIME PROG..
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 31.
3. To select the desired parameter.4. Assign the desired timer programme (P1 to P4) to the circuit with
the rotary button.
User level - Menu #CHOICE TIME PROG.
Parameter Adjustment range DescriptionCURRENT PROG.A P1 / P2 / P3 / P4 Comfort programme activated
(Circuit A)CURRENT PROG.B P1 / P2 / P3 / P4 Comfort programme activated
(Circuit B)CURRENT PROG.C P1 / P2 / P3 / P4 Comfort programme activated
(Circuit C)
5.5.7. Customising a timer programme
1. To access user level: Press the > key.2. Select the menu #TIME PROGRAM.
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 31.
3. To select the desired parameter.
User level - Menu #TIME PROGRAM
Parameter Time schedule DescriptionTIME PROG.A PROG P2 A
PROG P3 APROG P4 A
Timer programme for circuit A
TIME PROG.B PROG P2 BPROG P3 BPROG P4 B
Timer programme for circuit B
TIME PROG.C PROG P2 CPROG P3 CPROG P4 C
Timer programme for circuit C
TIME PROG.DHW DHW circuit timer programmeTIME PROG.AUX Auxiliary circuit timer programme
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
C002219-D-04
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
C002219-D-04
5. Commissioning Diematic iSystem For C 330 / C 630 ECO
45 29/05/2012 - 7600676-001-01
4. To select a timer programme to be modified.5. To select to days for which the timer programme is to be
modified:Turn the rotary button to the left until you reach the day desired.To confirm, press the rotary button.
6. b : Day selectionPress key b / v until the symbol b is displayed.Turn the rotary button to the right to select the day(s) desired.v : Cancelling the day selectionPress key b / v until the symbol v is displayed.Turn the rotary button to the right to cancel selection of the relevantday(s).
7. When the days desired for the programme have been selected,press the rotary button to confirm.
8. To define the timer ranges for the comfort mode and reducedmode:Turn the rotary button to the left until 0:00 is displayed. The firstsegment of the graphic bar for the timer programme flashes.
9. b : Comfort mode selectionPress key b / v until the symbol b is displayed.To select a comfort time range, turn the rotary button to the right.v : Reduced mode selectionPress key b / v until the symbol v is displayed.To select a reduced time range, turn the rotary button to the right.
10.When the times for the comfort mode have been selected, pressthe rotary button to confirm.
User level - Menu #TIME PROGRAM
Day Comfort periods / Filling enabled:P1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROG.A Monday 6:00 to 22:00 Tuesday 6:00 to 22:00 Wednesday 6:00 to 22:00 Thursday 6:00 to 22:00 Friday 6:00 to 22:00 Saturday 6:00 to 22:00 Sunday 6:00 to 22:00
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa Su"Display of the timeprogram. To continuepush on the button" a
C002228-B-04
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa Su"Select the days toprogram" a
C002229-C-04
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSet the time program. a
C002230-E-04
06:00
06:00
Diematic iSystem For C 330 / C 630 ECO 5. Commissioning
29/05/2012 - 7600676-001-01 46
User level - Menu #TIME PROGRAM
Day Comfort periods / Filling enabled:P1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROG.B Monday 6:00 to 22:00 Tuesday 6:00 to 22:00 Wednesday 6:00 to 22:00 Thursday 6:00 to 22:00 Friday 6:00 to 22:00 Saturday 6:00 to 22:00 Sunday 6:00 to 22:00
TIME PROG.C Monday 6:00 to 22:00 Tuesday 6:00 to 22:00 Wednesday 6:00 to 22:00 Thursday 6:00 to 22:00 Friday 6:00 to 22:00 Saturday 6:00 to 22:00 Sunday 6:00 to 22:00
TIME PROG.DHW Monday Tuesday Wednesday Thursday Friday Saturday Sunday
TIME PROG.AUX Monday Tuesday Wednesday Thursday Friday Saturday Sunday
5.5.8. Setting an annual clock
The annual clock is used to programme up to 10 heating stop periodsover one year. The circuits selected for this stop are in Antifreezemode during the period chosen.
1. To access user level: Press the > key.2. Select the menu #ANNUAL PROG.
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 31.
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
C002219-D-04
5. Commissioning Diematic iSystem For C 330 / C 630 ECO
47 29/05/2012 - 7600676-001-01
3. To select the desired parameter.
OFF No stopA circuit AB circuit BA+B circuit A, BC circuit CA+C circuit A, CB+C circuit B, CA+B+C circuit A, B, CSU DHW circuitA+E circuit A and DHWB+E circuit B and DHWA+B+W circuit A, B and DHWC+E circuit C and DHWA+C+W circuit A, C and DHWB+C+W circuit B, C and DHWALL circuit A, B, C and DHW
4. Set the start date and the end date of the shutdown selected.5. To deactivate a shutdown, select the shutdown and set to OFF.6. To select another shutdown, press the ' button.
Annual programme (Factory setting)Stop no. Circuit concerned Start date End date1 OFF 01-01 01-012 OFF 01-01 01-013 OFF 01-01 01-014 OFF 01-01 01-015 OFF 01-01 01-016 OFF 01-01 01-017 OFF 01-01 01-018 OFF 01-01 01-019 OFF 01-01 01-0110 OFF 01-01 01-01
For example: Customised programmingStop no. Circuit concerned Start date End date1 A+C 01-11 10-112 A+C 20-12 02-01
If setting STOP: OFF, the stop is deactivated and the start and enddates are not displayed.
Diematic iSystem For C 330 / C 630 ECO 5. Commissioning
29/05/2012 - 7600676-001-01 48
User level - Menu #ANNUAL PROG Description Factory
settingAdjustment range
STOP N 1: Selection of the circuit stopped OFF OFF, A, B, A+B, C, A+C, B+C, A+B+C,SU, A+E, B+E, A+B+W, C+E, A+C+W, B+C+W, ALL
BEG.DATE N 01 Setting start date of the stop 01 1-31BEG.MONTH N 01 Setting start month of the stop 01 1-12END DATE N 01 Setting end date of the stop 01 1-31END MONTH N 01 Setting end month of the stop 01 1-12
STOP N 2: Selection of the circuit stopped OFF OFF, A, B, A+B, C, A+C, B+C, A+B+C,SU, A+E, B+E, A+B+W, C+E, A+C+W, B+C+W, ALL
BEG.DATE N 02 Setting start date of the stop 01 1-31BEG.MONTH N 02 Setting start month of the stop 01 1-12END DATE N 02 Setting end date of the stop 01 1-31END MONTH N 02 Setting end month of the stop 01 1-12
STOP N 3: Selection of the circuit stopped OFF OFF, A, B, A+B, C, A+C, B+C, A+B+C,SU, A+E, B+E, A+B+W, C+E, A+C+W, B+C+W, ALL
BEG.DATE N 03 Setting start date of the stop 01 1-31BEG.MONTH N 03 Setting start month of the stop 01 1-12END DATE N 03 Setting end date of the stop 01 1-31END MONTH N 03 Setting end month of the stop 01 1-12
STOP N 4: Selection of the circuit stopped OFF OFF, A, B, A+B, C, A+C, B+C, A+B+C,SU, A+E, B+E, A+B+W, C+E, A+C+W, B+C+W, ALL
BEG.DATE N 04 Setting start date of the stop 01 1-31BEG.MONTH N 04 Setting start month of the stop 01 1-12END DATE N 04 Setting end date of the stop 01 1-31END MONTH N 04 Setting end month of the stop 01 1-12
STOP N 5: Selection of the circuit stopped OFF OFF, A, B, A+B, C, A+C, B+C, A+B+C,SU, A+E, B+E, A+B+W, C+E, A+C+W, B+C+W, ALL
BEG.DATE N 05 Setting start date of the stop 01 1-31BEG.MONTH N 05 Setting start month of the stop 01 1-12END DATE N 05 Setting end date of the stop 01 1-31END MONTH N 05 Setting end month of the stop 01 1-12
STOP N 6: Selection of the circuit stopped OFF OFF, A, B, A+B, C, A+C, B+C, A+B+C,SU, A+E, B+E, A+B+W, C+E, A+C+W, B+C+W, ALL
BEG.DATE N 06 Setting start date of the stop 01 1-31BEG.MONTH N 06 Setting start month of the stop 01 1-12END DATE N 06 Setting end date of the stop 01 1-31END MONTH N 06 Setting end month of the stop 01 1-12
STOP N 7: Selection of the circuit stopped OFF OFF, A, B, A+B, C, A+C, B+C, A+B+C,SU, A+E, B+E, A+B+W, C+E, A+C+W, B+C+W, ALL
BEG.DATE N 07 Setting start date of the stop 01 1-31BEG.MONTH N 07 Setting start month of the stop 01 1-12END DATE N 07 Setting end date of the stop 01 1-31END MONTH N 07 Setting end month of the stop 01 1-12
5. Commissioning Diematic iSystem For C 330 / C 630 ECO
49 29/05/2012 - 7600676-001-01
User level - Menu #ANNUAL PROG Description Factory
settingAdjustment range
STOP N 8: Selection of the circuit stopped OFF OFF, A, B, A+B, C, A+C, B+C, A+B+C,SU, A+E, B+E, A+B+W, C+E, A+C+W, B+C+W, ALL
BEG.DATE N 08 Setting start date of the stop 01 1-31BEG.MONTH N 08 Setting start month of the stop 01 1-12END DATE N 08 Setting end date of the stop 01 1-31END MONTH N 08 Setting end month of the stop 01 1-12
STOP N 9: Selection of the circuit stopped OFF OFF, A, B, A+B, C, A+C, B+C, A+B+C,SU, A+E, B+E, A+B+W, C+E, A+C+W, B+C+W, ALL
BEG.DATE N 09 Setting start date of the stop 01 1-31BEG.MONTH N 09 Setting start month of the stop 01 1-12END DATE N 09 Setting end date of the stop 01 1-31END MONTH N 09 Setting end month of the stop 01 1-12
STOP N 10: Selection of the circuit stopped OFF OFF, A, B, A+B, C, A+C, B+C, A+B+C,SU, A+E, B+E, A+B+W, C+E, A+C+W, B+C+W, ALL
BEG.DATE N 10 Setting start date of the stop 01 1-31BEG.MONTH N 10 Setting start month of the stop 01 1-12END DATE N 10 Setting end date of the stop 01 1-31END MONTH N 10 Setting end month of the stop 01 1-12
5.6 Modifying the installer settings
5.6.1. Language selection
1. Access the installer level: Press key - for around 5 seconds.2. Select the menu #LANGUAGE.
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 31
Installer level - Menu #LANGUAGEAdjustment range DescriptionFRANCAIS Display in FrenchDEUTSCH Display in GermanENGLISH Display in EnglishITALIANO Display in ItalianESPANOL Display in SpanishNEDERLANDS Display in DutchPOLSKI Display in PolishPУCCKИЙ Display in RussianTÜRK Display in Turkish
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
5"
TEMP.: 68°
C002235-F-04
Diematic iSystem For C 330 / C 630 ECO 5. Commissioning
29/05/2012 - 7600676-001-01 50
5.6.2. Calibrating the sensors
1. To access user level: Press the > key.2. Select the menu #SETTING.
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 31
3. To set the following parameters:
User level - Menu #SETTING
Parameter Adjustment range Description Factory setting Customersetting
SUM/WIN 15 to 30 °C Used to set the outside temperature abovewhich heating will be shut down.
4 The heating pumps are shut down.4 The burner will only start for domestic
hot water needs.4 The symbol p appears.
22 °C
NO Heating is never shut down automaticallyCALIBR. OUT Outside sensor calibration: Used to
correct the outside temperatureOutside temperature
CALIBR. ROOM A(1)(2)
Calibration of the room sensor oncircuit AMake this setting 2 hours after switchingon, when the room temperature hasstabilised
Room temperatureof circuit A
OFFSET ROOM A (1)
(3)-5.0 to +5.0 °C Room offset on circuit A: Is used to set a
room offsetMake this setting 2 hours after switchingon, when the room temperature hasstabilised
0.0
ANTIFR. ROOM A 0.5 to 20 °C Room temperature antifreeze activationon circuit A
6 °C
CALIBR. ROOM B(2)(1)(4)
Calibration of the room sensor oncircuit BMake this setting 2 hours after switchingon, when the room temperature hasstabilised
Room temperatureof circuit B
OFFSET ROOM B (3)
(4)(1)-5.0 to +5.0 °C Room offset on circuit B: Is used to set a
room offsetMake this setting 2 hours after switchingon, when the room temperature hasstabilised
0.0
ANTIFR. ROOM B (4) 0.5 to 20 °C Room temperature at which the antifreezemode is activated on circuit B
6 °C
(1) The parameter is only displayed if INSTALLATION is set to EXTENDED(2) The parameter is only displayed if a room sensor is connected to the circuit concerned(3) The parameter is only displayed if no room sensor is connected to the circuit concerned or the sensor has no influence(4) The parameter is only displayed if the circuit concerned is actually connected
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
C002219-D-04
5. Commissioning Diematic iSystem For C 330 / C 630 ECO
51 29/05/2012 - 7600676-001-01
User level - Menu #SETTING
Parameter Adjustment range Description Factory setting Customersetting
CALIBR. ROOM C(4)(1)(2)
Calibration of the room sensor oncircuit CMake this setting 2 hours after switchingon, when the room temperature hasstabilised
Room temperatureof circuit C
OFFSET ROOM C (4)
(1)(3)-5.0 to +5.0 °C Room offset on circuit C: Is used to set a
room offsetMake this setting 2 hours after switchingon, when the room temperature hasstabilised
0.0
ANTIFR. ROOM C (4) 0.5 to 20 °C Room temperature antifreeze activationon circuit C
6 °C
(1) The parameter is only displayed if INSTALLATION is set to EXTENDED(2) The parameter is only displayed if a room sensor is connected to the circuit concerned(3) The parameter is only displayed if no room sensor is connected to the circuit concerned or the sensor has no influence(4) The parameter is only displayed if the circuit concerned is actually connected
5.6.3. Professional settings
1. Access the installer level: Press key - for around 5 seconds.2. To set the following parameters:
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 31.
Installer level - #PRIMARY LIMITS menu
Parameter Adjustment range Description Factory setting Customer settingBOILER MAX 20 to 90 °C Maximum boiler temperature 75 °C MAX.R.HEAT(%) (1) 0-100% Maximum boiler output during heating 100% MAX.DHW(%) (1)(2) 0-100% Maximum boiler output in DHW 100% MIN.VENT. (1) 1000-5000 rpm Minimum fan speed See table below MAX.VENT. (1) 1000-7000 rpm Maximum fan speed setting in heating See table below START RPM (1) 1000-5000 rpm Optimum start-up speed setting See table below MIN.PUMP SPEED (1) 20-100% Minimum pump speed 20 % MAX.PUMP SPEED (1) 20-100% Maximum pump speed 60 % (1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED(2) The parameter is only displayed if P.DHW is set to PUMP
Type of gas used Parameter Unit C 330-5 C 330-6 C 330-7 C 330-8 C 330-9 C 330-10Gas H (G20) MIN.VENT. rpm 1300 1400 1000 1000 1100 1100
MAX.VENT. rpm 5400 5500 3500 3900 4200 3900START SP. rpm 2500 2500 1300 1400 1400 1700
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
5"
TEMP.: 68°
C002235-F-04
Diematic iSystem For C 330 / C 630 ECO 5. Commissioning
29/05/2012 - 7600676-001-01 52
Type of gas used Parameter Unit C 330-5 C 330-6 C 330-7 C 330-8 C 330-9 C 330-10Gas L (G25) MIN.VENT. rpm 1300 1400 1000 1000 1100 1100
MAX.VENT. rpm 5500 5600 3600 4000 4200 4000START SP. rpm 2500 2500 1300 1400 1400 1700
Type of gas used Parameter Unit C 630-5 C 630-6 C 630-7 C 630-8 C 630-9 C 630-10Gas H (G20) MIN.VENT. rpm 1700 1800 1300 1300 1500 1300
MAX.VENT. rpm 5500 5500 3800 4200 4500 4400START SP. rpm 2500 2500 1400 1400 1500 1700
Gas L (G25) MIN.VENT. rpm 1700 1800 1300 1300 1500 1300MAX.VENT. rpm 5500 5500 3800 4200 4500 4500START SP. rpm 2500 2500 1400 1400 1500 1700
Installer level - Menu #SECONDARY LIMITSParameter Adjustment range Description Factory settingMAX.CIRC.A 20 to 95 °C Maximum temperature (Circuit A)
¼ "MAX.CIRC...", page 5775 °C
MAX.CIRC.B 20 to 95 °C Maximum temperature (Circuit B)¼ "MAX.CIRC...", page 57
50 °C
MAX.CIRC.C 20 to 95 °C Maximum temperature (Circuit C)¼ "MAX.CIRC...", page 57
50 °C
OUT.ANTIFREEZE OFF, -8 to +10 °C Outside temperature at which the installation's antifreezeprotection is activated.Below this temperature the pumps are permanently on and theminimum temperatures for each circuit are respected.When NIGHT :STOP is set, the reduced temperature ismaintained in each circuit (Menu #SECONDARY INSTAL.P).OFF: Antifreeze protection is not activated
+3 °C
HCZP D A (1) (2) OFF, 20 to 90 °C Curve base temperature in Daytime mode (Circuit A) OFF
HCZP N A (1) (2) OFF, 20 to 90 °C Curve base temperature in Nighttime mode (Circuit A) OFF
HCZP D B (1) (2) OFF, 20 to 90 °C Curve base temperature in Daytime mode (Circuit B) OFF
HCZP N B (1) (2) OFF, 20 to 90 °C Curve base temperature in Nighttime mode (Circuit B) OFF
HCZP D C (1) (2) OFF, 20 to 90 °C Curve base temperature in Daytime mode (Circuit C) OFF
HCZP N C (1) (2) OFF, 20 to 90 °C Curve base temperature in Nighttime mode (Circuit C) OFF
PRIM.TEMP.DHW (1) 50 to 79 °C Boiler temperature setting if producing domestic hot water 65 °C(1) The parameter is only displayed if INSTALLATION is set to EXTENDED(2) The parameter can be set to the heating curve by pressing key f.
5. Commissioning Diematic iSystem For C 330 / C 630 ECO
53 29/05/2012 - 7600676-001-01
Installer level - Menu #PRIMARY INSTAL.P(1)
Parameter Adjustment range Description Factorysetting
Customersetting
BURN.MIN.RUN 0 to 180 seconds Setting the burner minimum operation time(In heating mode)
30 seconds
TIMER GENE P.(1) 1 to 30 minutes Maximum post-operation duration of thegenerator pump
4 minutes
IN.BL(1) STOP HEAT Configuration of the PCU BL inletIf the contact is open, heating and DHWproduction are off. . Automatic restart whenthe contact closes.Opening the contact does not generate amessage
TOTAL STOP
TOTAL STOP Configuration of the PCU BL inletIf the contact is open, heating and DHWproduction are off. Automatic restart whenthe contact closes.Opening the contact generates a message
SAFETY MODE Configuration of the PCU BL inletIf the contact is open, the boiler goes intosafety lockout. The boiler needs to be resetto restart.
ANALOG OUTL Analogue outlet command WILO_010V 0-10V Wilo control PCBGRUND_010V 0-10V Grundfoss control PCBPUMP PWM Modulating pumpOUTP.FEEDB Heat output feedbackTHOT FEEDB. Temperature feedback
CCE : ON/OFF Leak proofing system NO PSG : ON/OFF Check gas pressure switch before start-up NO TIME DEL.HYDRAU.V. 0 to 255 seconds Time delay after the command to open the
hydraulic valve0 seconds
TIME DEL.FLUEG.VALV.
0 to 255 seconds Time delay after the command to open theflue gas valve
0 seconds
MIN PRESSURE 0 to 3 bar Minimum pressure to generate a lock-out 0 bar BOIL.INERTIA 1 to 255 seconds Characterisation of boiler inertia 10 seconds (1) The menu is displayed only if the INSTALLATION parameter is set to EXTENDED
Diematic iSystem For C 330 / C 630 ECO 5. Commissioning
29/05/2012 - 7600676-001-01 54
Installer level - Menu #SECONDARY INSTAL.P
Parameter Adjustment range Description Factorysetting
Customersetting
BUILD. INERTIA (1) 0 (10 hours) to 10(50 hours)
Characterisation of building's inertia:0 for a building with low thermal inertia.3 for a building with normal thermalinertia.10 for a building with high thermal inertia.Modification of the factory setting isonly useful in exceptional cases.
3 (22 hours)
CIRC.CURVE A(2) 0 to 4 Heating curve of the circuit A¼ "CIRC. CURVE ...", page58
1.5
ANTICIP.A(1) 0.0 to 10.0 Activation and adjustment of theanticipation time¼ "ANTICIP.A, ANTICIP.B,ANTICIP.C ", page 58
NO
ROOM INFL. A (1) 0 to 10 Influence of room sensor A¼ "ROOM S.INFL", page 59
3
CIRC.CURVE B(2) 0 to 4 Heating curve of the circuit B¼ "CIRC. CURVE ...", page58
0.7
ANTICIP.B(1) 0.0 to 10.0 Activation and adjustment of theanticipation time¼ "ANTICIP.A, ANTICIP.B,ANTICIP.C ", page 58
NO
ROOM INFL. B (1) 0 to 10 Influence of room sensor B¼ "ROOM S.INFL", page 59
3
CIRC.CURVE C(2) 0 to 4 Heating curve of the circuit C¼ "CIRC. CURVE ...", page58
0.7
ANTICIP.C(1) 0.0 to 10.0 Activation and adjustment of theanticipation time¼ "ANTICIP.A, ANTICIP.B,ANTICIP.C ", page 58
NO
ROOM INFL. C (1) 0 to 10 Influence of room sensor C¼ "ROOM S.INFL", page 59
3
SCREED DRYING NO, B, C, B+C Drying the floor¼ "SCREED DRYING", page58
NO
START DRYING TEMP(3) 20 to 50 °C Screed drying start temperature 20 °C STOP DRYING TEMP(3) 20 to 50 °C Screed drying stop temperature 20 °C NB DAYS DRYING(3) 0 to 99 0 (1) The parameter is only displayed if INSTALLATION is set to EXTENDED(2) The parameter can be set to the heating curve by pressing key f(3) The parameter is only displayed if SCREED DRYING is other than OFF(4) The parameter is only displayed if IN 0-10V is set to ON.(5) The parameter is only displayed if P.DHW is set to PUMP(6) If a reversal valve is connected, DHW priority will always be total regardless of the setting.(7) The parameter is only displayed if LEG PROTEC is other than OFF
5. Commissioning Diematic iSystem For C 330 / C 630 ECO
55 29/05/2012 - 7600676-001-01
Installer level - Menu #SECONDARY INSTAL.P
Parameter Adjustment range Description Factorysetting
Customersetting
NIGHT (1) DEC. The lower temperature is maintained(Night mode)¼ "NIGHT", page 59
DEC.
STOP The boiler is stopped (Night mode)¼ "NIGHT", page 59
IN 0-10V OFF /TEMPERATURE /POWER %
Activating the control at 0-10 V¼ "Function 0-10 V", page 60
OFF
VMIN/OFF 0-10V (1)(4) 0 to 10 V Voltage corresponding to the instructionset minimum
0.5 V
VMAX 0-10V (1)(4) 0 to 10 V Voltage corresponding to the instructionset maximum
10 V
CONS.MIN 0-10V (1)(4) 0 to 100 Minimum set point temperature or output 5 CONS.MAX 0-10V (1)(4) 5 to 100 Maximum set point temperature or output 100 BAND WIDTH (1) 4 to 16 K Control unit bandwidth for the 3-way
valves.Option of increasing the bandwidth if thevalves are rapid or of reducing it if theyare slow.
12 K
BOIL/3WV SHIFT (1) 0 to 16 K Minimum temperature differencebetween the boiler and the valves
4 K
H. PUMP DELAY (1) 0 to 15 minutes Timing of the shutdown of the heatingpumps.The timing of heating pump shutdownprevents the boiler overheating.
4 minutes
HW. PUMP DELAY (1)(5) 2 to 15 minutes Timing of the shutdown of the domestichot water pump.The timing of the domestic hot water loadpump shutdown prevents the boiler andthe heating circuits overheating (Only if aload pump is used).
2 minutes
ADAPT ON Automatic adaptation of the heatingcurves for each circuit with a room sensorwith an influence of >0.
ON
OFF The heating curves can only be modifiedmanually.
PRIORITY DHW(6) TOTAL Interruption of pool heating and reheatingduring domestic hot water production.
TOTAL
SLIDING Domestic hot water production andheating on the valve circuits if theavailable output is sufficient and thehydraulic connection allows.
NO Heating and domestic hot waterproduction in parallel if the hydraulicconnection allows.a Risk of overheating in the directcircuit.
(1) The parameter is only displayed if INSTALLATION is set to EXTENDED(2) The parameter can be set to the heating curve by pressing key f(3) The parameter is only displayed if SCREED DRYING is other than OFF(4) The parameter is only displayed if IN 0-10V is set to ON.(5) The parameter is only displayed if P.DHW is set to PUMP(6) If a reversal valve is connected, DHW priority will always be total regardless of the setting.(7) The parameter is only displayed if LEG PROTEC is other than OFF
Diematic iSystem For C 330 / C 630 ECO 5. Commissioning
29/05/2012 - 7600676-001-01 56
Installer level - Menu #SECONDARY INSTAL.P
Parameter Adjustment range Description Factorysetting
Customersetting
LEG PROTEC The anti legionella function acts toprevent the development of legionella inthe dhw tank, these bacteria areresponsible for legionellosis.
OFF
OFF Anti-legionella function not activatedDAILY The tank is overheated every day from
4:00 o'clock to 5:00 o'clockWEEKLY The tank is overheated every Saturday
from 4:00 o'clock to 5:00 o'clockSTART.TIM.LEG.P(7) 00:00 to 23:30 Antilegionella start-up time 4:00 h
(Increment: 30minutes)
DURAT.LEG.PROTECT(
7)60 to 360 min Antilegionella running time 60 minutes
(Increment: 30minutes)
OPTIM. DHW(5) OFF The function is deactivated OFF BOILER. T. When, in heating mode, the boiler
temperature exceedsPRIM.TEMP.DHW by +3°C and DHWtank needs are not met, the domestic hotwater pump starts up
SYST.TEMP When, in heating mode, the systemtemperature exceedsPRIM.TEMP.DHW by +3°C and DHWtank needs are not met, the domestic hotwater pump starts up
ON.DHW(5) OFF The function is deactivated OFF BOILER. T. In DHW mode, the DHW load pump
starts up only if the boiler temperature ishigher than the WATER TEMP. set point+ 5°C
SYST.TEMP In DHW mode, the DHW load pumpstarts up only if the system temperatureis higher than the WATER TEMP. setpoint + 5°C
(1) The parameter is only displayed if INSTALLATION is set to EXTENDED(2) The parameter can be set to the heating curve by pressing key f(3) The parameter is only displayed if SCREED DRYING is other than OFF(4) The parameter is only displayed if IN 0-10V is set to ON.(5) The parameter is only displayed if P.DHW is set to PUMP(6) If a reversal valve is connected, DHW priority will always be total regardless of the setting.(7) The parameter is only displayed if LEG PROTEC is other than OFF
n MAX.CIRC...
WARNING
If using underfloor heating, do not modify the factorysetting (50 °C). To install this, please consult existinglegislation.
4 In the case of a direct circuit, connect a safety thermostat to theBL contact.
4 In the case of a 3-way valve circuit (B or C), connect a safetythermostat to the TS contact.
5. Commissioning Diematic iSystem For C 330 / C 630 ECO
57 29/05/2012 - 7600676-001-01
n CIRC. CURVE ...
Heating curve circuit A, B or C
x Outside temperature (°C)y Water flow temperature (°C)
A Maximum temperature of the circuit B - C
n ANTICIP.A, ANTICIP.B, ANTICIP.C
A Room temperature instruction - Comfort
Z Room temperature instruction - Low
E Time schedule
R Anticipation time = Accelerated reheating phase
The anticipation function calculates the heating restart time to reachthe desired room temperature less 0.5 K at the time programmed forswitching to comfort mode.The start time of the timed programmed corresponds to the end of theaccelerated reheating phase.The function is activated by setting a different OFF value.The value set corresponds to the time considered necessary to returnthe installation to the required temperature (outside temperature0°C), starting from a residual room temperature corresponding to thelow nocturnal instruction.Anticipation is optimised if a room sensor is connected.The regulator will automatically fine set the anticipation time.
This function is dependent on the surplus output availablein the installation.
n SCREED DRYING
Used to force a constant flow temperature or a train to acceleratescreed drying on underfloor heating.The setting for these temperatures must follow the screed-layer'srecommendations.The activation of this parameter (setting other than OFF) forces thepermanent display of SCREED DRYING and deactivates all otherfunctions on the control unit.When floor drying is active on a circuit, all other circuits (e.g. DHW)are shut down. The use of this function is only possible on circuits Band C.
M001678-B
1
0,5K
8801N033
1
4
2
3
Diematic iSystem For C 330 / C 630 ECO 5. Commissioning
29/05/2012 - 7600676-001-01 58
A STOP DRYING TEMP
Z START DRYING TEMP
E Today
R NB DAYS DRYING
T Normal regulation (End of drying)
Y Heating temperature setting (°C)
For example
A STOP DRYING TEMP: 47 °C
Z START DRYING TEMP: 20 °C
R NB DAYS DRYING
T Normal regulation (End of drying)
Y Heating temperature setting (°C)
Every day at midnight (00:00): the set point (STARTDRYING TEMP) is recalculated and the remaining numberof days (NB DAYS DRYING) is decremented.
n ROOM S.INFL
Used to adjust the influence of the room sensor on the watertemperature for the circuit concerned.
0 No influence (remote control fitted in a location with no influence)1 Slight influence3 Average influence (recommended)10 Room thermostat type operation
n NIGHT
This parameter is displayed if at least one circuit does notinclude a room sensor.
For circuits without a room sensor:
4 NIGHT :DEC. (Reduced): The reduced temperature is maintainedduring reduced periods. The circuit pump operates constantly.
4 NIGHT :STOP (Stop): Heating is shut down during reducedperiods. When installation antifreeze is active, the reducedtemperature is maintained during reduced periods.
For circuits with a room sensor:
4 When the room temperature is lower than the room sensor setpoint: The reduced temperature is maintained during reducedperiods. The circuit pump operates constantly.
2
34
1
6
5
C002768-A
00:00 00:00 00:00
2
10 9 8 7 6 5 4 3 2 1
23
20
26
29
32
35
38
41
44
47
4
4
5
1
6C002769-A
00:00 00:00 00:00
5. Commissioning Diematic iSystem For C 330 / C 630 ECO
59 29/05/2012 - 7600676-001-01
4 When the room temperature is higher than the room sensor setpoint: Heating is shut down during reduced periods. Wheninstallation antifreeze is active, the reduced temperature ismaintained during reduced periods.
n Function 0-10 V
This function controls the boiler using an external system thatincludes a 0-10 V output connected to the 0-10 V input. This commandimposes a temperature or output instruction on the boiler. It isnecessary to ensure that the BOILER MAX parameter is higher thanCONS.MAX 0-10V if the command is on temperature.
1 Flow set point temperature (°C) or output (%)2 Voltage at input (V) - DC3 0 V4 CONS.MIN 0-10V
5 CONS.MAX 0-10V
6 VMIN/OFF 0-10V
7 VMAX 0-10V
8 10 Vx Voltage at inputy Boiler temperature or sliding output
If the input voltage is less than VMIN/OFF 0-10V, the boiler is off.The boiler temperature setting corresponds strictly to the 0-10 Vinput. The secondary boiler circuits continue to operate but have noimpact on the water temperature in the boiler. If using the 0-10 V inputand a secondary boiler circuit, the external regulator providing this0-10 V power supply must always request a temperature at leastequal to the needs of the secondary circuit.
5.6.4. Configuring the network
1. Access the installer level: Press key - for around 5 seconds.2. Select the menu #NETWORK.
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 31
3. To set the following parameters:
M001679-A
5
1
4
3 6 2 7 8
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
5"
TEMP.: 68°
C002235-F-04
Diematic iSystem For C 330 / C 630 ECO 5. Commissioning
29/05/2012 - 7600676-001-01 60
Installer level - Menu #NETWORK(1)
Parameter Adjustment range Description Factory setting Customer settingCASCADE: ON / NO ON: System in cascade NO VM NETWORK Specific menu: Enlist VMs in cascade
mode (See following chapter:"Connect VMs only in cascade")
MASTER CONTROLLER(2)
ON / NO Configure this control system asmaster on the bus
ON
SYSTEM NETWORK (3) Specific menu: Enlist generators orVMs in cascade mode (See followingchapter: "Connecting appliances incascade")
FUNCT (3) CLASSIC Operation in cascade: Successivetriggering of the various boilers in thecascade according to requirements
CLASSIC
PARALLEL Functioning in parallel cascade: If theoutside temperature is lower than thevalue PARALLEL CASC., all of theboilers are started up at the same time
PARALLEL CASC. (4) -10 to 20 °C Outside temperature triggering allstages in parallel mode
10 °C
TIMER GENE P. CASC(2) 0 to 30 min Minimum duration of post-operation ofthe generator pump
0 mn
INTER STAGE TIMER (2) 1 to 30 min Time delay for starting up or shuttingdown generators.
4 mn
SLAVE NUMBER (5) 2 to 10 Set the network address of thesecondary generator
2
(1) The menu is displayed only if the INSTALLATION parameter is set to EXTENDED(2) The parameter is only displayed if CASCADE: is set to ON(3) The parameter is only displayed if MASTER CONTROLLER is set to ON(4) The parameter is only displayed if FUNCT is set to PARALLEL(5) The parameter is only displayed if MASTER CONTROLLER is set to OFF
User level - Menu #SETTING
Parameter Adjustment range Description Factory setting Customer settingPERMUT(1) AUTO / 1 ... 10 This parameter is used to set the master boiler.
4 AUTO: The master boiler switches automaticallyevery 7 days
4 1 ... 10: The master boiler is always the onedefined by this value
AUTO
(1) The parameter is only displayed if CASCADE: is on ON and MASTER CONTROLLER on ON
n Connecting appliances in cascade
It is possible, in a cascade configuration, to enlist generators and/orVM iSystem as slaves. Proceed as follows:
1. Set parameter CASCADE: to ON.
5. Commissioning Diematic iSystem For C 330 / C 630 ECO
61 29/05/2012 - 7600676-001-01
2. Select SYSTEM NETWORK and press the rotary button to go tothe specific menu.
3. To add a slave appliance to the network, select ADD SLAVE.
4. The screen displayed allows you to choose numbers for the slaveboilers to be added to the network. Numbers 2 to 10 are dedicatedto the generators and numbers 20 to 39 to the VM iSystem. Turnthe rotary button to scroll through the numbers and press toconfirm the number chosen. Press j to go back to the previouslist.
5. To remove a slave appliance from the network, select ERASENETWORK.
6. The screen displayed allows you to choose the numbers of theslave boilers to be removed from the network. Turn the rotarybutton to scroll through the numbers and press to remove thenumber chosen. Press j to go back to the previous list.
7. Select NB. ELEMENTS.NETWORK. This screen summarises theelements in the network recognised by the system. Press j to goback to the previous list.
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CASCADE
MASTER CONTROLER
SYSTEM NETWORK
FUNCT
INTER STAGE TIMER
ON
ON
TRADITIONAL
4'a
C002409-C-04
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
NB.NETWORK ELEMENTS
ADD SLAVE
ERASE NETWORK
4
a
C002410-C-04
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
ADD SLAVE
GENE: 2, 5,
VM: 29,
4
a
C002412-B-04
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
ERASE NETWORK
GENE: 2, 5,
VM: 29,
4
a
C002413-B-04
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
NB.NETWORK ELEMENTS
GENE: 2, 5,
VM: 29,
4
a
C002411-C-04
Diematic iSystem For C 330 / C 630 ECO 5. Commissioning
29/05/2012 - 7600676-001-01 62
5.6.5. Return to the factory settings
To reset the appliance, proceed as follows:
1. Press key C, > and j simultaneously for 4 seconds. The menu#RESET is displayed.
2. To set the following parameters:
Menu #RESETChoice of generator Parameter DescriptionGENERATOR RESET TOTAL Performs a TOTAL RESET of all parameters
EXCEPT PROG. Performs a parameter RESET but retains the timer programmesPROG. Performs a RESET on the timer programmes but retains the parametersSENSOR SCU Performs a RESET of the generator sensors connectedROOM SENSOR Performs a RESET of the room sensors connected
After reset (TOTAL RESET and RESET EXCEPT PROG.), thecontrol system goes back to the display of the language choice aftera few seconds.
1. Select the desired language by turning the rotary button.2. To confirm, press the rotary button.
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
MODE
SUNDAY 11:45
C002296-B-04
4"
+ +
Français - Deutsch - English - Italiano - Espanol - Nederlands- Pycck - Polski - Türk -
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb x c rg m
ÿLANGUE FRANCAIS
C002286-C
5. Commissioning Diematic iSystem For C 330 / C 630 ECO
63 29/05/2012 - 7600676-001-01
6 Maintenance
6.1 General instructions for the user
The boiler displays a message whenever maintenance is necessary.
1. When the message, REVISION, is displayed, press ? to displaythe installer's telephone number.
2. Contact the fitter.3. To carry out inspections and maintenance required by a qualified
professional.
6.2 Chimney sweep instructions
1. Press the - key.2. Check the combustion each time the flues are swept.¼ Refer to the manual delivered with the boiler.
3. To go back to the main display, press key j2 times.
Menu #EMISSION MEASUREMENTS
Generator Function available Description Values displayedGenerator name AUTO normal operation BOILER TEMP.
CURRENTWIND SPEEDBACK TEMP
°CµArpm°C
PMIN Operating at minimum output BOILER TEMP.CURRENTWIND SPEEDBACK TEMP
°CµArpm°C
PMAX Operating at maximum output BOILER TEMP.CURRENTWIND SPEEDBACK TEMP
°CµArpm°C
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
TEMP. : 68°
PCU COM.FAIL D27
C002302-D-04
Diematic iSystem For C 330 / C 630 ECO 6. Maintenance
29/05/2012 - 7600676-001-01 64
6.3 Customising maintenance
6.3.1. Maintenance message
The boiler incorporates a function that can be used to display amaintenance message. To set the parameters for this function,proceed as follows:
1. Access the "After Sales" level: Hold down the - key until#PARAMETERS is displayed.
2. Select the menu #REVISION.
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 31
3. To set the following parameters:
After Sales level - Menu #REVISION
Parameter Adjustment range DescriptionTYPE NO Factory setting
No message indicating that maintenance is necessaryMANU Recommended setting
Signals that maintenance is necessary on the date selected. Set the date using theparameters below.
AUTO a Not applicable. Do not select this setting.REVISION HOUR(1) 0 to 23 Time at which the REVISION display appears
REV. YEAR(1) 2008 to 2099 Year in which the REVISION display appears
REVIS. MONTH(1) 1 to 12 Month in which the REVISION display appears
REVISION DATE(1) 1 to 31 Day on which the REVISION display appears(1) The parameter is only displayed if MANU is configured.
Clearing the maintenance message:
After carrying out the maintenance operations, modify the date in the#REVISION menu to clear the message.
In the event of maintenance before the maintenance message isdisplayed:
After carrying out early maintenance operations, it is necessary to seta new date in the #REVISION menu.
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
10"
TEMP.: _ _ _ _
C002272-C-04
6. Maintenance Diematic iSystem For C 330 / C 630 ECO
65 29/05/2012 - 7600676-001-01
6.3.2. Contact details of the professional for AfterSales Support
In order to assist the user if an error or service message is displayed,it is possible to provide the contact details of the professional to becontacted. To input the professional's contact details, proceed asfollows:
1. Access the "After Sales" level: Hold down the - key until#PARAMETERS is displayed.
2. Select the menu #SUPPORT.
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 31
3. To set the following parameters:
After Sales level - Menu #SUPPORT
Parameter DescriptionNAME Input the installer's nameTELEPHONE NUM. Input the installer's telephone number
When the message REVISION is displayed, press ? to display theprofessional's telephone number.
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
10"
TEMP.: _ _ _ _
C002272-C-04
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
TEMP. : 68°
PCU COM.FAIL D27
C002302-D-04
Diematic iSystem For C 330 / C 630 ECO 6. Maintenance
29/05/2012 - 7600676-001-01 66
7 Troubleshooting
7.1 Anti-hunting
When the boiler is in Anti-short-cycle operating mode, the symbol ?flashes.
1. Press the "?" key.The message Operation assured when the restart temperaturewill be reached is displayed.
This message is not an error message but an item ofinformation.
7.2 Messages (Code type Bxx or Mxx)
In the case of failure, the control panel displays a message and acorresponding code.
1. Make a note of the code displayed.The code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded.
2. Switch the boiler off and switch back on.The boiler starts up again automatically when the reason for theblocking has been removed.
3. If the code is displayed again, correct the problem by following theinstructions in the table below:
Code Messages Description Checking / solutionB00 BL.CRC.PSU The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Set the type of generator again in the menu#CONFIGURATION (Refer to the original rating plate)
B01 BL.MAX BOILER Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction, pump, valves)B02 BL.HEATING
SPEEDMaximum increase of the flowtemperature has been exceeded
The water flow in the installation is insufficient
4 Check the circulation (direction, pump, valves)4 Check the water pressure4 Check the cleanliness of the heat exchangerSensor error
4 Check that the sensors are operating correctly4 Check whether the boiler sensor has been correctly fitted
B03 BL.MAX EXCHAN Maximum heat exchangertemperature exceeded
The water flow in the installation is insufficient
4 Check the circulation (direction, pump, valves)
7. Troubleshooting Diematic iSystem For C 330 / C 630 ECO
67 29/05/2012 - 7600676-001-01
Code Messages Description Checking / solutionB04 BL.DERIVE EXCH Maximum heat exchanger
temperature increase has beenexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction, pump, valves)4 Check the water pressure4 Check the cleanliness of the heat exchangerSensor error
4 Check that the sensors are operating correctly4 Check whether the boiler sensor has been correctly fitted
B05 BL.DTEXC.BACK
The maximum differencebetween the exchangertemperature and the returntemperature has been exceeded
The water flow in the installation is insufficient
4 Check the circulation (direction, pump, valves)4 Check the water pressure4 Check the cleanliness of the heat exchangerSensor error
4 Check that the sensors are operating correctly4 Check whether the boiler sensor has been correctly fitted
B06 BL.DT BOI.EXC. The maximum differencebetween the boiler temperatureand the exchanger temperaturehas been exceeded
The water flow in the installation is insufficient
4 Check the circulation (direction, pump, valves)4 Check the water pressure4 Check the cleanliness of the heat exchangerSensor error
4 Check that the sensors are operating correctly4 Check whether the boiler sensor has been correctly fitted
B07 BL.DT OUTLRET.
Maximum difference between theflow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction, pump, valves)4 Check the water pressure4 Check the cleanliness of the heat exchangerSensor error
4 Check that the sensors are operating correctly4 Check whether the boiler sensor has been correctly fitted
B08 BL.RL OPEN The RL inlet on the PCU PCBterminal block is open
Parameter error
4 Set the type of generator again in the menu#CONFIGURATION (Refer to the original rating plate)
Bad connection
4 Check the wiringB09 BL.INV. L/N Set the type of generator again in the menu #CONFIGURATION (Refer to the original rating plate )B10B11
BL.BL INPUTOPEN
The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Check the contact on the BL inletParameter error
4 Check the parameter IN.BLBad connection
4 Check the wiringB13 BL.COM PCU-D4 Communication error with the
SCU PCBBad connection
4 Check the wiringSCU PCB not installed in the boiler
4 Install an SCU PCBB14 BL.WATER MIS. The water pressure is lower than
0,8 barNot enough water in the circuit
4 Top up the installation with water
Diematic iSystem For C 330 / C 630 ECO 7. Troubleshooting
29/05/2012 - 7600676-001-01 68
Code Messages Description Checking / solutionB15 BL.GAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU PCB
4 Check that the gas valve is fully opened4 Checking the gas supply pressure4 Check whether the gas pressure control system has been
correctly fitted4 Replace the gas pressure control system if need be
B16 BL.BAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Replace the SU PCBB17 BL.PCU ERROR The parameters saved on the
PCU PCB are impairedParameter error on the PCU PCB
4 Replace the PCU PCBB18 BL.BAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Replace the PSU PCBB19 BL.NO CONFIG The boiler has not been
configuredThe PSU PCB has been changed
4 Set the type of generator again in the menu#CONFIGURATION (Refer to the original rating plate)
B21 BL. COM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Check that the SU PCB has been correctly put in place onthe PCU PCB
4 Replace the SU PCBB22 BL.FLAME LOS No flame during operation No ionization current
4 Purge the gas supply to remove air4 Check that the gas valve is fully opened4 Check the supply pressure4 Check the operation and setting of the gas valve unit4 Check that the air inlet and flue gas discharge flues are not
blocked4 Check that there is no recirculation of flue gases
B25 BL.SU ERROR Internal error on the SU PCB 4 Replace the SU PCBM04 REVISION A service is required The date programmed for the service has been reached
4 Carry out maintenance on the boiler4 To clear the inspection, programme another date in the menu
#REVISION or set the parameter REVISION TYPE to OFFM05 REVISION A An A, B or C service is required The date programmed for the service has been reached
4 Carry out maintenance on the boiler4 To clear the inspection, press key t
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FL.DRY.B XX
DAYSFloor drying is activeXX DAYS = Number of days' floordrying remaining.
Floor drying is underway. Heating on the circuits not concerned isshut down.
4 Wait for the number of days shown to change to 04 Set the parameter SCREED DRYING to OFF
FL.DRY.C XXDAYSFL.DRY.B+C XXDAYS
M23 CHANGEOUTSI.S
The outside temperature sensoris defective.
Change the outside radio temperature sensor.
STOP N XX The shutdown is activeXX = Number of the activeshutdown
A shutdown is underway. The circuits selected for this stop are inAntifreeze mode during the period chosen.
4 Wait until the end date has been passed4 Set the parameter STOP NXX to OFF
7. Troubleshooting Diematic iSystem For C 330 / C 630 ECO
69 29/05/2012 - 7600676-001-01
7.3 Message history
The menu (#MESSAGE HISTORIC) is used to consult the last 10messages displayed by the control panel.
1. Access the "After Sales" level: Hold down the - key until#PARAMETERS is displayed.
2. Select the menu (#MESSAGE HISTORIC).
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 31
3. The list of the last 10 messages is displayed.
4. Select a message to consult the information pertaining to it.
7.4 Faults (Code type Lxx or Dxx)
In the event of operational failure, the control panel flashes anddisplays an error message and a corresponding code.
1. Make a note of the code displayed.The code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded.
2. Press the t key. If the code is displayed again, switch off the boilerand then switch it back on.
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
10"
TEMP.: _ _ _ _
C002272-C-04
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
BL.HEATING SPEED
BL.WATER MIS.
BL.RL OPEN
BL.FLAME LOS
21/10
02/09
26/08
26/08 a
C002381-B-04
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
BL INPUT OPEN M21
28/08/2008 - 13h32
NUMBER OF CASE
OUTSIDE TEMP.
OUTLET TEMP.B
8
1.0 °C
12.0°Ca
C002382-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
TEMP. : 68°
PCU. COM. FAIL. D27
C002604-B-04
Diematic iSystem For C 330 / C 630 ECO 7. Troubleshooting
29/05/2012 - 7600676-001-01 70
3. Press the ? key. Follow the instructions displayed to solve theproblem.
4. Consult the meaning of the codes in the table below:
Code Faults Causeof thefault
Description Checking / solution
L00 PSU FAIL PCU PSU PCB not connected Bad connection
4 Check the wiring between the PCU and PSU PCBsPSU PCB faulty
4 Replace the PSU PCBL01 PSU PARAM FAIL PCU The safety parameters are
incorrectBad connection
4 Check the wiring between the PCU and PSU PCBsPSU PCB faulty
4 Replace the PSU PCBL02 EXCHAN.S.FAIL. PCU The exchanger sensor is short
circuitedBad connection
4 Check the wiring between the PCU PCB and thesensor
4 Check that the SU PCB is correctly in place4 Check that the sensor has been correctly fittedSensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessary
L03 EXCHAN.S.FAIL. PCU The exchanger sensor is on anopen circuit
Bad connection
4 Check the wiring between the PCU PCB and thesensor
4 Check that the SU PCB is correctly in place4 Check that the sensor has been correctly fittedSensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessary
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
TEMP. : 68°
PCU COM.FAIL D27
C002302-D-04
7. Troubleshooting Diematic iSystem For C 330 / C 630 ECO
71 29/05/2012 - 7600676-001-01
Code Faults Causeof thefault
Description Checking / solution
L04 DEF.OUTLET S. PCU Temperature of heat exchangertoo low
Bad connection
4 Check the wiring between the PCU PCB and thesensor
4 Check that the SU PCB is correctly in place4 Check that the sensor has been correctly fittedSensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessaryNo water circulation
4 Vent the air in the heating system4 Check the circulation (direction, pump, valves)4 Check the water pressure4 Check the cleanliness of the heat exchanger
L05 STB EXCHANGE PCU Exchanger temperature toohigh
Bad connection
4 Check the wiring between the PCU PCB and thesensor
4 Check that the SU PCB is correctly in place4 Check that the sensor has been correctly fittedSensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessaryNo water circulation
4 Vent the air in the heating system4 Check the circulation (direction, pump, valves)4 Check the water pressure4 Check the cleanliness of the heat exchanger
L06 BACK S.FAILURE PCU The return temperature sensorhas short-circuited
Bad connection
4 Check the wiring between the PCU PCB and thesensor
4 Check that the SU PCB is correctly in place4 Check that the sensor has been correctly fittedSensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessary
L07 BACK S.FAILURE PCU The return temperature sensoris on an open circuit
Bad connection
4 Check the wiring between the PCU PCB and thesensor
4 Check that the SU PCB is correctly in place4 Check that the sensor has been correctly fittedSensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessary
Diematic iSystem For C 330 / C 630 ECO 7. Troubleshooting
29/05/2012 - 7600676-001-01 72
Code Faults Causeof thefault
Description Checking / solution
L08 BACK S.FAILURE PCU Return temperature too low Bad connection
4 Check the wiring between the PCU PCB and thesensor
4 Check that the SU PCB is correctly in place4 Check that the sensor has been correctly fittedSensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessaryNo water circulation
4 Vent the air in the heating system4 Check the circulation (direction, pump, valves)4 Check the water pressure4 Check the cleanliness of the heat exchanger
L09 STB BACK PCU Return temperature too high Bad connection
4 Check the wiring between the PCU PCB and thesensor
4 Check that the SU PCB is correctly in place4 Check that the sensor has been correctly fittedSensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessaryNo water circulation
4 Vent the air in the heating system4 Check the circulation (direction, pump, valves)4 Check the water pressure4 Check the cleanliness of the heat exchanger
L10 DEF.DT.ECH.RET PCU Difference insufficient betweenthe exchanger temperature andthe return temperature
Sensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessaryBad connection
4 Check that the sensor has been correctly fittedNo water circulation
4 Vent the air in the heating system4 Check the circulation (direction, pump, valves)4 Check the water pressure4 Check the cleanliness of the heat exchanger4 Check that the heating pump is operating correctly
7. Troubleshooting Diematic iSystem For C 330 / C 630 ECO
73 29/05/2012 - 7600676-001-01
Code Faults Causeof thefault
Description Checking / solution
L11 DEF.DT.RET.ECH PCU Difference between the returntemperature and the exchangertemperature too big
Sensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessaryBad connection
4 Check that the sensor has been correctly fittedNo water circulation
4 Vent the air in the heating system4 Check the circulation (direction, pump, valves)4 Check the water pressure4 Check the cleanliness of the heat exchanger4 Check that the heating pump is operating correctly
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connection
4 Check the wiring between the PCU PCB and theSTB
4 Check that the SU PCB is correctly in place4 Check the electrical continuity of the STB4 Check whether the STB has been correctly fittedSensor fault
4 Replace the STB if necessaryNo water circulation
4 Vent the air in the heating system4 Check the circulation (direction, pump, valves)4 Check the water pressure4 Check the cleanliness of the heat exchanger
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Check the wiring between the PCU PCB and theignition transformer
4 Check that the SU PCB is correctly in place4 Check the ionization/ignition electrode4 Check the earthing4 SU PCB faulty: Change the PCBIgnition arc, but no flame formation
4 Vent the gas flues4 Check that the gas valve is fully opened4 Checking the gas supply pressure4 Check the operation and setting of the gas valve
unit4 Check that the air inlet and flue gas discharge flues
are not blocked4 Check the wiring on the gas valve unit4 SU PCB faulty: Change the PCBPresence of the flame but insufficient ionization (<3 µA)
4 Check that the gas valve is fully opened4 Checking the gas supply pressure4 Check the ionization/ignition electrode4 Check the earthing4 Check the wiring on the ionization/ignition
electrode
Diematic iSystem For C 330 / C 630 ECO 7. Troubleshooting
29/05/2012 - 7600676-001-01 74
Code Faults Causeof thefault
Description Checking / solution
L15 CCE TEST FAIL PCU The cyclical leak proofing kit(CCE) has detected a leak
Reset the box
4 Check that the gas valve is fully opened4 Checking the gas supply pressure4 Check the gas valve and replace if necessary
L16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present when there should not be aflameIgnition transformer defective
4 Check the ionization/ignition electrodeGas valve defective
4 Check the gas valve and replace if necessaryThe burner remains very hot: CO2 too high
4 Set the CO2L17 VALVE FAIL PCU Problem on the gas valve Bad connection
4 Check the wiring between the PCU PCB and thegas valve
4 Check that the SU PCB is correctly in placeSU PCB faulty
4 Inspect the SU PCB and replace it if need beL32 DEF.OUTLET S. PCU The boiler flow sensor has
short-circuitedBad connection
4 Check the wiring between the PCU PCB and thesensor
4 Check that the SU PCB is correctly in place4 Check that the sensor has been correctly fittedSensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessary
L33 DEF.OUTLET S. PCU The boiler flow sensor is on anopen circuit
Bad connection
4 Check the wiring between the PCU PCB and thesensor
4 Check that the SU PCB is correctly in place4 Check that the sensor has been correctly fittedSensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessary
L34 FAN FAILURE PCU The fan is not running at theright speed
Bad connection
4 Check the wiring between the PCU PCB and thefan
Fan defective
4 Check for adequate draw on the chimneyconnection
4 Replace the fan if need beL35 BACK>BOIL FAIL PCU Flow and return reversed Bad connection
4 Check that the sensor has been correctly fittedSensor fault
4 Check the Ohmic value of the sensors4 Replace the sensor if necessaryWater circulation direction reversed
4 Check the circulation (direction, pump, valves)
7. Troubleshooting Diematic iSystem For C 330 / C 630 ECO
75 29/05/2012 - 7600676-001-01
Code Faults Causeof thefault
Description Checking / solution
L36 I-CURRENT FAIL PCU The flame went out more than5 times in 24 hours while theburner was operating
No ionization current
4 Purge the gas supply to remove air4 Check that the gas valve is fully opened4 Checking the gas supply pressure4 Check the operation and setting of the gas valve
unit4 Check that the air inlet and flue gas discharge flues
are not blocked4 Check that there is no recirculation of flue gases
L37 SU COM.FAIL PCU Communication failure with theSU PCB
Bad connection
4 Check whether the SU PCB has been correctlyfitted into the connector on the PCU PCB
4 Change the SU PCBL38 PCU COM.FAIL PCU Communication failure
between the PCU and SCUPCBs
Bad connection
4 Check the wiring between the PCU and SCU PCBs4 Run an AUTODETECTION in the menu
#CONFIGURATIONSCU PCB not connected or faulty
4 Replace the SCU PCBL39 BL OPEN FAIL PCU The BL inlet opened for a short
timeBad connection
4 Check the wiringExternal cause
4 Check the device connected to the BL contactParameter incorrectly set
4 Check the parameter IN.BLD03D04
OUTL S.B FAIL.OUTL S.C FAIL.
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarks:The circuit pump is running.The 3-way valve motor on thecircuit is no longer powered andcan be adjusted manually.
Bad connection
4 Check whether the sensor is connected: ¼See chapter: "Deletion of sensors from thememory in the PCB", page 79
4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessary
D05 OUTSI.S.FAIL. SCU Outside temperature sensorfaultRemarks:The boiler operates on BOILERMAX temperature.The valve setting is no longerensured but monitoring themaximum temperature of thecircuit after the valve isensured.Valves may be manuallyoperated.Reheating the domestic hotwater remains ensured.
Bad connection
4 Check whether the sensor is connected: ¼See chapter: "Deletion of sensors from thememory in the PCB", page 79
4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessary
Diematic iSystem For C 330 / C 630 ECO 7. Troubleshooting
29/05/2012 - 7600676-001-01 76
Code Faults Causeof thefault
Description Checking / solution
D07 AUX.SENS.FAIL. SCU Auxiliary sensor fault Bad connection
4 Check whether the sensor is connected: ¼See chapter: "Deletion of sensors from thememory in the PCB", page 79
4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessary
D09 DHW S.FAILURE SCU Domestic hot water sensor faultRemarks:Heating of domestic hot water isno longer ensured.The load pump operates.The load temperature of thedhw tank is the same as theboiler.
Bad connection
4 Check whether the sensor is connected: ¼See chapter: "Deletion of sensors from thememory in the PCB", page 79
4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessary
D11D12D13
ROOM S.A FAIL.ROOM S.B FAIL.ROOM S.C FAIL.
SCU A room temperature sensorfaultB room temperature sensorfaultC room temperature sensorfaultNote:The circuit concerned operateswithout any influence from theroom sensor.
Bad connection
4 Check whether the sensor is connected: ¼See chapter: "Deletion of sensors from thememory in the PCB", page 79
4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessary
D14 MC COM.FAIL SCU Communication failurebetween the SCU PCB and theboiler radio module
Bad connection
4 Check the link and the connectorsBoiler module failure
4 Change the boiler moduleD15 ST.TANK S.FAIL SCU Storage tank sensor fault
Note:The hot water storage tankreheating operation is no longerassured.
Bad connection
4 Check whether the sensor is connected: ¼See chapter: "Deletion of sensors from thememory in the PCB", page 79
4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessary
7. Troubleshooting Diematic iSystem For C 330 / C 630 ECO
77 29/05/2012 - 7600676-001-01
Code Faults Causeof thefault
Description Checking / solution
D16D16
SWIM.P.B. S.FAILSWIM.P.C. S.FAIL
SCU Swimming pool sensor faultcircuit BSwimming pool sensor faultcircuit CNote:Swimming pool reheating isalways done during the circuit'scomfort period.
Bad connection
4 Check whether the sensor is connected: ¼See chapter: "Deletion of sensors from thememory in the PCB", page 79
4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessary
D17 DHW 2 S.FAIL SCU Sensor fault tank 2 Bad connection
4 Check whether the sensor is connected: ¼See chapter: "Deletion of sensors from thememory in the PCB", page 79
4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessary
D27 PCU COM. FAIL SCU Communication failure between the SCU and PCU PCBs
4 Check the wiring between the SCU and PCU PCBs4 Check that the PCU PCB is powered up (green LED on or flashing)4 Change the PCU PCB
D32 5 RESET:ON/OFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back onD37 TA-S SHORT-CIR SCU The Titan Active System® is short-circuited
4 Check that the connection cable between the SCU PCB and the anode is not short-circuited
4 Check that the anode is not short-circuitedRemarks:Domestic hot water production has stopped but can nonetheless be restarted using keyr.The tank is no longer protected.If a tank without Titan Active System® is connected to the boiler,check that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card.
D38 TA-S DISCONNEC SCU The Titan Active System® is on an open circuit
4 Check that the connection cable between the SCU PCB and the anode is not severed4 Check that the anode is not brokenRemarks:Domestic hot water production has stopped but can nonetheless be restarted using keyr.The tank is no longer protected.If a tank without Titan Active System® is connected to the boiler,check that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card.
Diematic iSystem For C 330 / C 630 ECO 7. Troubleshooting
29/05/2012 - 7600676-001-01 78
7.4.1. Deletion of sensors from the memory in thePCB
The configuration of the sensors is memorised by the SCU PCB. If asensor fault appears whilst the corresponding sensor is notconnected or has been voluntarily removed, please delete the sensorfrom the SCU PCB memory.
4 Press key ? repeatedly until Do you want to delete thissensor? is displayed.
4 Select YES by turning the rotary button and press to confirm.
The outside temperature sensor cannot be deleted.
7.5 Failure history
The menu #DEFAULT HISTORIC is used to consult the last 10 faultsdisplayed by the control panel.
1. Access the "After Sales" level: Hold down the - key until#PARAMETERS is displayed.
2. Select the menu #DEFAULT HISTORIC.
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 31
3. The list of the last 10 faults is displayed.
4. Select a fault to consult the information pertaining to it.
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
10"
TEMP.: _ _ _ _
C002272-C-04
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
aAUX1.SENS.FAIL 21/10
C002274-F-04
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
AUX1.SENS.FAIL D07
28/08/2008 - 13h32
NUMBER OF CASE
OUTSIDE TEMP.
OUTLET TEMP.B
8
1.0 °C
35.0°Ca
C002275-C-04
7. Troubleshooting Diematic iSystem For C 330 / C 630 ECO
79 29/05/2012 - 7600676-001-01
7.6 Parameter and input/output check (mode tests)
Use the following menus to target the cause of a malfunction.
1. Access the "After Sales" level: Hold down the - key until#PARAMETERS is displayed.
2. Check the following parameters:
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 31
After Sales level - Menu #PARAMETERS
Parameter DescriptionPERMUT Master boiler activeSTAGE Number of boilers requesting heatingNB.CASC.: Number of boilers recognised in the cascadeNB. VM: Number of DIEMATIC VM control systems recognised in the cascadePOWER % Current output of the boilerPERCENT PUMP Modulating pump commandSPEED FAN (1) Fan rotation speedSETPOINT FAN Fan rotation speed desiredMEAN OUTSIDE T Average outside temperatureCALC.T. BOILER Temperature calculated by the boilerBURNER SETPOINT Set point parameter of the burnerAVERAGE BOIL.T Average temperature of the boiler flow sensorBOILER. T. (1) Measurement of the boiler flow sensor
BACK TEMP (1) Temperature of the boiler return water
SYST.TEMP (1) Temperature of the system flow water if multi-generator
SYST. CALC. T. (2) System flow temperature calculated by the control systemCALCULATED T. A Calculated temperature for circuit ACALCULATED T. B (3) Calculated temperature for circuit B
CALCULATED T. C (3) Calculated temperature for circuit C
OUTLET TEMP. B (1)
(3)Temperature of the flow water in circuit B
SWIMMING P.T.B Temperature of the swimming pool water sensor on circuit BOUTLET TEMP. C (1)
(3)Temperature of the flow water in circuit C
SWIMMING P.T.C Temperature of the swimming pool water sensor on circuit COUTSIDE TEMP. (1) Outside temperature
ROOMTEMP. A (1) Room temperature of circuit A
ROOMTEMP. B (1) (3) Room temperature of circuit B
ROOMTEMP. C (1) (3) Room temperature of circuit C(1) The parameter can be displayed by pressing key f.(2) The parameter is only displayed if CASCADE: is set to ON(3) The parameter is only displayed for the options, circuits or sensors actually connected
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
10"
TEMP.: _ _ _ _
C002272-C-04
Diematic iSystem For C 330 / C 630 ECO 7. Troubleshooting
29/05/2012 - 7600676-001-01 80
After Sales level - Menu #PARAMETERS
Parameter DescriptionWATER TEMP. (1)(3) Water temperature in the DHW tank
IN 0-10V (1)(3) Voltage at input 0-10 V
CURRENT (1) Ionization current
PRESSURE (1) Water pressure in the installation
STOR.TANK.TEMP (1)
(3)Water temperature in the storage tank
T.DHW BOTTOM (1)(3) Water temperature in the bottom of the DHW tank
DHW A TEMP. (1)(3) Water temperature in the second DHW tank connected to circuit A
TEMP.TANK AUX (1)(3) Water temperature in the second DHW tank connected to the AUX circuitKNOB A Position of temperature setting button on room sensor AKNOB B(3) Position of temperature setting button on room sensor B
KNOB C(3) Position of temperature setting button on room sensor COFFSET ADAP A Parallel trigger calculated for circuit AOFFSET ADAP B (3) Parallel trigger calculated for circuit B
OFFSET ADAP C (3) Parallel trigger calculated for circuit C(1) The parameter can be displayed by pressing key f.(2) The parameter is only displayed if CASCADE: is set to ON(3) The parameter is only displayed for the options, circuits or sensors actually connected
After Sales level - Menu #TEST OUTPUTS
Parameter Adjustment range DescriptionP. CIRC. A ON / NO Stop/start pump circuit AP. CIRC. B (1) ON / NO Stop/start pump circuit B
P. CIRC. C (1) ON / NO Stop/start pump circuit C
HW. PUMP (1) ON / NO Stop/start domestic hot water pumpAUX.CIRC. ON / NO On/Off auxiliary outlet3WV B (1) REST No command
OPEN Opening 3-way valve circuit BCLOSE Closure 3-way valve circuit B
3WV C (1) REST No commandOPEN Opening 3-way valve circuit CCLOSE Closure 3-way valve circuit C
TEL.OUTPUT ON / NO On/Off telephone relay outlet(1) The parameter is only displayed for the options, circuits or sensors actually connected
After Sales level - Menu #TEST INPUTS
Parameter Status DescriptionPHONE REM. Bridge on telephone input (1 = presence, 0 = absence)FLAME Flame presence test (1 = presence, 0 = absence)GAS VALVE OPEN/CLOSE Opening the valve
Closing the valveFAILURE ON Fault display
OFF No faultSEQUENCE Control system sequence. ¼ See chapter: "Control system sequence", page
82(1) The parameter is only displayed if INSTALLATION is set to EXTENDED
7. Troubleshooting Diematic iSystem For C 330 / C 630 ECO
81 29/05/2012 - 7600676-001-01
After Sales level - Menu #TEST INPUTS
Parameter Status DescriptionBOILER Index of the generator in the systemTYPE Generator typeR.CTRL A (1) ON Presence of a remote control A
OFF No remote control AR.CTRL B (1) ON Presence of a remote control B
OFF No remote control BR.CTRL C (1) ON Presence of a remote control C
OFF No remote control CCALIBRA.CLOCK(1) Clock calibration(1) The parameter is only displayed if INSTALLATION is set to EXTENDED
After Sales level - #INFORMATION menu
Parameter DescriptionS/N SCU Serial number of the SCU boardCTRL Software version of the SCU boardS/N PCU Serial number of the PCU boardVER.ROM Version of the PCU PCB programmeVERS.PARAM PCU Version of the PCU PCB parametersS/N SU Serial number of the SU boardVERS.PARAM SU Version of the SU PCB programmeVERS.PARAM PCU Version of the SU PCB parametersMC.VERSION (1) Version of the boiler radio module programme
SOLAR VERS. (1) Solar control system software version
CALIBRA.CLOCK(2) Clock calibration(1) The parameter is only displayed for the options, circuits or sensors actually connected(2) The parameter is only displayed if INSTALLATION is set to EXTENDED
After Sales level - Menu #CONFIGURATION
Parameter Adjustment range DescriptionMODE: MONO/ ALL.CIRC. To chose if the exemption made for one remote control applies to a single circuit
(MONO) or if it must be transmitted to a group of circuits (ALL.CIRC.)TYPE Boiler type (Refer to the original rating plate)AUTODETECTION OFF/ON System reset if error L38 is displayedTAS OFF/ON Activation of the Titan Active System® function
7.6.1. Control system sequence
Control system sequenceStatus Sub-status Operation0 Rest 0 Rest1 Boiler start (Heat demand) 1 Anti-short cycle activated
2 Open isolating valve3 Start-up of the boiler pump4 Wait for the correct temperatures for burner start
Diematic iSystem For C 330 / C 630 ECO 7. Troubleshooting
29/05/2012 - 7600676-001-01 82
Control system sequenceStatus Sub-status Operation2 Burner start 10 Open gas valve (External)
11 Fan start-up12 Opening of the flue gas flue damper13 Preventilation14 Awaiting closure of the RL contact (if the function is activated)15 Burner on switch request16 Leak proofing system test17 Pre-ignition18 Ignition19 Check flame presence20 Inter-ignition time delay
3 Boiler on heating service 30 Nominal internal set point31 Limited internal set point32 Output control33 Temperature protection gradient level 1 (Modulate down)34 Temperature protection gradient level 2 (Part load)35 Temperature protection gradient level 3 (Blockage)36 Modulate up for flame control37 Temperature stabilisation time38 Cold start
5 Burner stop 40 Burner shutdown request41 Post-ventilation42 Fan speed reduction43 Closure of the flue gas flue damper44 Stop fan
6 Switching off the boiler 60 Post-operation time delay on the boiler pump61 Stop boiler pump62 Close isolating valve63 Start anti short cycle
8 Stop 0 Awaiting burner start-up1 Anti-short cycle activated
9 Blockage XX Shutdown code XX10 Blocking 0 Rest16 Burner running to guarantee AF 30 Antifreeze protection
31 Nominal internal set point32 Limited internal set point33 Temperature protection gradient level 1 (Modulate down)34 Temperature protection gradient level 2 (Part load)35 Temperature protection gradient level 3 (Blockage)36 Modulate up for flame control37 Temperature stabilisation time38 Cold start
7. Troubleshooting Diematic iSystem For C 330 / C 630 ECO
83 29/05/2012 - 7600676-001-01
Diematic iSystem For C 330 / C 630 ECO 7. Troubleshooting
29/05/2012 - 7600676-001-01 84
DUEDI S.r.l.www.duediclima.it
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
Via Passatore, 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 [email protected]
IT
DE DIETRICH THERMIQUE Iberia S.L.U.
DE DIETRICH THERMIQUE S.A.S
www.dedietrich-calefaccion.es
Av. Princep d’Astúries 43-4508012 BARCELONA
+34 932 920 520+34 932 184 709
ES
AD
001N
U-A
H
129164, Россия, г. МоскваЗубарев переулок, д. 15/1
Бизнес-центр «Чайка Плаза», офис 309
+7 (495) 221-31-51
© CopyrightAll technical and technological information contained in these technical instructions,as well as any drawings and technical descriptions supplied, remain our propertyand shall not be multiplied without our prior consent in writing.
29/05/2012
7600676-001-01
DE DIETRICH THERMIQUE
57, rue de la Gare F- 67580 MERTZWILLER - BP 30