Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
SpecificationsGenerator Set Specifications
Minimum Rating 230 kVA
Maximum Rating 330 kVA
Voltage 220-480 Volts
Frequency 50 Hz
Speed 1500 RPM
Generator Set Configurations
Emissions/Fuel Strategy EU Stage IIIA, Low Fuel Consumption, U.S. EPA Certified for Stationary Emergency Use only ( Tier 3 Nonroad
Equivalent Emission Standards)
Engine Specifications
Engine Model C9 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
Bore 112 mm 4.41 in
Displacement 8.8 L 537.01 in³
Stroke 149 mm 5.87 in
Compression Ratio 16.1:1
Aspiration Air to Air Aftercooled
Governor Type Adem™A4
Fuel System Hydraulic electronic unit injection
Benefits and FeaturesCat Generator Set Packages
Cat® generator set packages have been fully prototype tested, and certified torsional vibration analysis reports are available. The packages are designed to meet the NFPA 110 requirement for loading, and conform to the ISO 8528-5 steady state and transient response requirements.
Cat Diesel Engines
Page: M-1 of M-4© 2017 Caterpillar All Rights ReservedMSS-EPG-18331028-031.pdf
C9 Generator SetElectric Power
SS-9641220-18331028-003 SS Page 1 of 7
The four cycle Cat diesel engine combines consistent performance with excellent fuel economy and transient response that meets or exceeds ISO 8528-5. The engines have been designed and built for a wide range of applications and can be optimized for low fuel consumption or low emissions. The engines feature a reliable, rugged, and durable design that has been field proven in thousands of applications worldwide from emergency standby installations to continuously operating power plants.
Cooling System
The cooling system has been designed to operate in standard ambient temperatures up to 50°C (122°F) with an air flow restriction of 0.5 in water. The factory installed cooling system has been designed and tested to ensure proper generator set cooling, and includes the radiator, fan, belts, and all guarding installed as standard. Contact your Cat Dealer for specific ambient and altitude capabilities.
Generators
The generators used on Cat packages have been designed and tested to work with the Cat engine. The generators are built with robust Class H insulation and provide industry leading motor starting capability. They provide high efficiency in a majority of applications and optional coastal protection for the windings is available for harsh environments.
Cat EMCP Control Panel
The EMCP controller features the reliability and durability you have come to expect from your Cat equipment. EMCP4 is a scalable control platform designed to ensure reliable generator set operation, providing extensive information about power output and engine operation. EMCP4 systems can be further customized to meet your needs through programming and expansion modules.
World Wide Product Support
Cat Dealers provide extensive post sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Caterpillar S•O•S℠ program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products.
Standard EquipmentAir Inlet System
• Air cleaner, light duty with disposable paper filter
Control Panels
• EMCP4.4 control panel
Cooling System
• Radiator and cooling fan with guard
• Coolant drain line with valve
• Fan drive, battery charging alternator drive
• Caterpillar extended life coolant
Exhaust System
• Stainless steel exhaust flex, gaskets, rain cap and SAE exhaust
• Flange for customer; shipped loose
Fuel System
• Standard open set fuel tank / base supplied
• Base, formed steel with single wall integral 8-hour fuel tank
Generators and Generator Attachments
Page: M-2 of M-4© 2017 Caterpillar All Rights ReservedMSS-EPG-18331028-031.pdf
C9 Generator SetElectric Power
SS-9641220-18331028-003 SS Page 2 of 7
• 12 leads
• IP23 protection
• Voltage regulator (single phase sensing)
• Power centre, IP22
• Segregated low voltage (AC/DC) wiring panel
• Mandatory option circuit breaker, IEC, 3 pole
Governing System
• Cat electronic governor (ADEM A4)
Lube System
• Oil cooler
• Lubricating oil
• Oil drain valves
Mounting System
• Captive linear vibration isolators between base and engine-generator
• Includes lifting provisions and termination points for coolant and lube oil drain lines
Starting / Charging System
• 24V battery with rack and cables
General
• Engine and alternator re-paint, Caterpillar Yellow
Optional EquipmentCertifications
• European Certifications
• Global Certifications
Air inlet system
• Single element air cleaner
Control Panels
• Volt free contact
• Local alarm horn
• Oil temperature displays
• Earth fault relay
• Earth leakage ground fault relay
• Overload alarm switch
• Low fuel level alarm
• Low fuel level shutdown
• High fuel level alarm
• Fuel level sensor
Control System
Page: M-3 of M-4© 2017 Caterpillar All Rights ReservedMSS-EPG-18331028-031.pdf
C9 Generator SetElectric Power
SS-9641220-18331028-003 SS Page 3 of 7
• Stone guard / radiator trans flance
• Low coolant temperature alarm
Enclosures
• High ambient sound attenuated enclosure
• Sound attenuated enclosure
Exhaust System
• Muffler - 10 dBA attenuation
• Muffler - 25 dBA attenuation
Fuel
• Integral duel wall fuel tank base
Generators
• Permanent magnet generator
• LC frame generator
Mounting System
• Narrow skid base
Special Packing / Inspectons for Shipment
• Special tests / reports
• Special packing for shipping
• Special inspections
Starting / Charging
• Battery charger 5 amp single
• Battery removal
• Battery disconnet switch
• Jacket water heater
The International System of Units (SI) is used in this publication. CAT, CATERPILLAR, their respective logos, ADEM, EUI, S•O•S, "Caterpillar Yellow" and the "Power Edge" trade dress, as well
as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
Page: M-4 of M-4© 2017 Caterpillar All Rights ReservedMSS-EPG-18331028-031.pdf
C9 Generator SetElectric Power
SS-9641220-18331028-003 SS Page 4 of 7
C9240 ekW/ 300 kVA
50 Hz/ 1500 rpm/ 400 V
Image shown may not reflect actual configuration
Metric English
Package Performance
Genset Power Rating with Fan @ 0.8 Power Factor 240 ekW
Genset Power Rating 300 kVA
Aftercooler (Separate Circuit) N/A N/A
Fuel Consumption
100% Load with Fan 64.2 L/hr 17.0 gal/hr
75% Load with Fan 48.4 L/hr 12.8 gal/hr
50% Load with Fan 34.4 L/hr 9.1 gal/hr
25% Load with Fan 20.9 L/hr 5.5 gal/hr
Cooling System¹
Engine Coolant Capacity 13.9 L 3.7 gal
Inlet Air
Combustion Air Inlet Flow Rate 16.6 m³/min 584.5 cfm
Max. Allowable Combustion Air Inlet Temp 44 ° C 111 ° F
Exhaust System
Exhaust Stack Gas Temperature 551.1 ° C 1024.1 ° F
Exhaust Gas Flow Rate 48.3 m³/min 1704.3 cfm
Exhaust System Backpressure (Maximum Allowable) 10.0 kPa 40.0 in. water
TSS-EM0877-01-GS-EPG-9641220.pdf © 2017 Caterpillar All Rights Reserved Page 1 of 3
ELECTRIC POWER - Technical Spec Sheet
240 ekW/ 300 kVA/ 50 Hz/ 1500 rpm/ 400 V/ 0.8 Power Factor
Rating Type: STANDBY Fuel Strategy: LOW FUEL CONSUMPTION
STANDARD
C9
SS-9641220-18331028-003 SS Page 5 of 7
DEFINITIONS AND CONDITIONS
1. For ambient and altitude capabilities consult your Cat dealer. Air flow restriction (system) is added to existing restriction from factory.
2. UL 2200 Listed packages may have oversized generators with a different temperature rise and motor starting characteristics. Generator temperature rise is based on a 40° C ambient per NEMA MG1-32.
3. Emissions data measurement procedures are consistent with those described in EPA CFR 40 Part 89, Subpart D & E and ISO8178-1 for measuring HC, CO, PM, NOx. Data shown is based on steady state operating conditions of 77° F, 28.42 in HG and number 2 diesel fuel with 35° API and LHV of 18,390 btu/lb. The nominal emissions data shown is subject to instrumentation, measurement, facility and engine to engine variations. Emissions data is based on 100% load and thus cannot be used to compare to EPA regulations which use values based on a weighted cycle.
Heat Rejection
Heat Rejection to Jacket Water 115 kW 6565 Btu/min
Heat Rejection to Exhaust (Total) 217 kW 12320 Btu/min
Heat Rejection to Aftercooler 46 kW 2592 Btu/min
Heat Rejection to Atmosphere from Engine 27 kW 1559 Btu/min
Heat Rejection to Atmosphere from Generator 19 kW 1058 Btu/min
Alternator²
Motor Starting Capability @ 30% Voltage Dip 586 skVA
Current 433 amps
Frame Size LC5014J
Excitation SE
Temperature Rise 163 ° C
Emissions (Nominal)³
NOx 3322.7 mg/Nm³ 6.9 g/hp-hr
CO 891.8 mg/Nm³ 1.8 g/hp-hr
HC 11.9 mg/Nm³ 0.0 g/hp-hr
PM 28.4 mg/Nm³ 0.1 g/hp-hr
TSS-EM0877-01-GS-EPG-9641220.pdf © 2017 Caterpillar All Rights Reserved Page 2 of 3
ELECTRIC POWER - Technical Spec Sheet
240 ekW/ 300 kVA/ 50 Hz/ 1500 rpm/ 400 V/ 0.8 Power Factor
Rating Type: STANDBY Fuel Strategy: LOW FUEL CONSUMPTION
STANDARD
C9
SS-9641220-18331028-003 SS Page 6 of 7
Applicable Codes and Standards:AS1359, CSA C22.2 No100-04, UL142,UL489, UL869, UL2200, NFPA37, NFPA70, NFPA99, NFPA110, IBC, IEC60034-1, ISO3046, ISO8528, NEMA MG1-22,NEMA MG1-33, 2006/95/EC, 2006/42/EC, 2004/108/EC.
Note: Codes may not be available in all model configurations. Please consult your local Cat Dealer representative for availability.
Ratings are based on SAE J1349 standard conditions. These ratings also apply at ISO3046 standard conditions
Fuel Rates are based on fuel oil of 35º API [16º C (60º F)] gravity having an LHV of 42 780 kJ/kg (18,390 Btu/lb) when used at 29º C (85º F) and weighing 838.9 g/liter (7.001 lbs/U.S. gal.). Additional ratings may be available for specific customer requirements, contact your Cat representative for details. For information regarding Low Sulfur fuel and Biodiesel capability, please consult your Cat dealer.
www.Cat-ElectricPower.com
STANDBY:Output available with varying load for the duration of the interruption of the normal source power. Average power output is 70% of the standby power rating. Typical operation is 200 hours per year, with maximum expected usage of 500 hours per year.
The International System of Units (SI) is used in this publication. CAT, CATERPILLAR, their respective logos, ADEM, EUI, S•O•S, "Caterpillar Yellow" and the "Power Edge" trade dress, as well as corporate
and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
Performance No.: EM0877-01Feature Code: C09DE1MGenerator Arrangement: 4692278
Source Country: U.K.
Date: 08/01/2017
TSS-EM0877-01-GS-EPG-9641220.pdf © 2017 Caterpillar All Rights Reserved Page 3 of 3
ELECTRIC POWER - Technical Spec Sheet
240 ekW/ 300 kVA/ 50 Hz/ 1500 rpm/ 400 V/ 0.8 Power Factor
Rating Type: STANDBY Fuel Strategy: LOW FUEL CONSUMPTION
STANDARD
C9
SS-9641220-18331028-003 SS Page 7 of 7
LEHE0948-03 Page 1 of 3
Features
C9 ACERT™ Sound Attenuated Level 1 and Level 2 Enclosures50 Hz: 275 – 330 kVA
60 Hz: 250 – 300 ekW
Image shown may not reflect actual configuration.
Enclosures
Robust/Highly Corrosion Resistant Construction• Factory-installed on integral fuel tank base• Environmentally-friendly, polyester powder baked paint• All-round overhanging base to protect enclosure• High grade engineering thermoplastic corner posts for protection• Compression door latches giving solid door seal• Zinc-plated or black coated stainless steel fasteners• Internally mounted critical exhaust silencing system
Excellent Access• Large cable entry area for installation ease• Accommodates rear-mounted breaker and control panel• Vertically-hinged double doors on both sides• Removable ducts providing maintenance access with enclosure in place• Lube oil and coolant drains piped to baseframe side rail, on exterior• Coperchio di riempimento del radiatore
Security and Safety• Lockable access doors which give full access to control panel and breaker• Cooling fan and battery charging alternator fully guarded• Fuel fill, oil fill, and battery can only be reached via lockable access• Externally-mounted emergency stop button• Designed for spreader-bar lifting to ensure safety• Control panel viewing window• Stub-up area is rodent proof
Options• Caterpillar yellow or white paint• Integral dual wall fuel tank base for total fluid containment (fuel, oil, and coolant) DEFRA compliant• Integral lifting frame
Enclosures
Enclosure Package Operating Characteristics
Model kVA ekWSP/PP LWA
Sound Pressure Levels BA
Air Flow Rate
Ambient Capability at 100% Load*1m (3.3 ft) 7m (23 ft)
75% Load
100% Load
75% Load
100% Load m3/s cfm °C °F
50 Hz Level 2
DE300E3300 240 SB 97 74 76 67 69 4.6 9747 47 117
275 220 PP 97 74 76 67 68 4.6 9747 50 122
DE300E0300 240 SB 97 74 76 67 69 4.6 9747 51 124
275 220 PP 97 74 75 67 68 4.6 9747 54 129
DE330E3330 264 SB 97 75 76 66 70 4.6 9747 48 118
300 240 PP 97 74 76 67 69 4.6 9747 51 124
60 Hz Level 2
DE275SE0344 275 SB – 78 80 69 71 5.4 11477 53 127
313 250 PP – 78 79 69 70 5.4 11477 56 133
DE300SE3375 300 SB – 78 80 69 72 5.4 11477 43 109
300 279 PP – 78 80 69 71 5.4 11477 48 118
DE300SE0375 300 SB – 79 80 70 72 5.4 11477 50 122
338 270 PP – 78 79 69 71 5.4 11477 54 129
50 Hz Level 1
DE300E3300 240 SB – 79 80 70 70 4.5 9464 47 117
275 220 PP – 78 79 69 70 4.5 9464 50 122
DE300E0300 240 SB – 79 80 70 71 4.5 9464 53 127
275 220 PP – 79 80 70 71 4.5 9464 56 133
DE330E3330 264 SB – 80 76 70 70 4.5 9464 50 122
300 240 PP – 79 76 70 69 4.5 9464 53 127
60 Hz Level 1
DE275SE0344 275 SB – 82 83 72 73 5.4 11477 48 118
313 250 PP – 82 83 72 72 5.4 11477 52 126
DE300SE3375 300 SB – 82 83 72 73 5.4 11477 44 111
300 279 PP – 82 83 72 73 5.4 11477 49 120
DE300SE0375 300 SB – 82 83 72 73 5.4 11477 44 111
338 270 PP – 82 83 72 73 5.4 11477 49 120
*Ambient capability measured with Cat Extended Life Coolant at sea level.
LEHE0948-03 Page 2 of 3
Enclosures
Weights and Dimensions
LEHE0948-03 (01/17)
www.cat.com/electricpower©2017 Caterpillar
All rights reserved.Materials and specifications are subject to change without notice.
CAT, CATERPILLAR, their respective logos ACERT, “Caterpillar Yellow”, the “Power Edge” trade dress as well as corporate and product identity used
herein, are trademarks of Caterpillar and may not be used without permission.
Model
Weight* Fuel Capacity Estimated Run Time
at 100% PrimeLevel 1
PackageLevel 2
Package Fillable Usablekg lb kg lb L U.S. gal L U.S. gal hours
DE300E33276 7222 3404 7505 665 176 610 161
10.1
DE300E0 10.5
DE330E0 3396 7487 3524 7769 665 176 610 161 9.8
DE275SE0
3276 7222 3404 7505 665 176 610 161
9.2
DE300SE3 8.2
DE300SE0 9.2
*Weight with lube oil, coolant, no fuel. Exact weight is dependent on options.
3985 mm (156.9") Level 14300 mm (169.3") Level 2
1410 mm (55.5")
2165
mm
(85.
2")
1015 mm (40.0") 995 mm (39.2")