CANCER INSTITUTE (WIA) Canal Bank Road, Adyar Chennai 600 020 Phone:+91 44 2220 9150 Extn (179) Email:[email protected] www.caninstitutewia.in Addendum to Tender I PROCUREMENT OF MEDICAL EQUIPMENTS Procurement of : Linear Accelerator BID REFERENCE: CI: SCI:NP/ROG/P-I/2016-17/01DATED DECEMBER 15, 2016 Abstract Schedule SL. No. Description Amount in Rs: 1. HVAC WORKS 2. CIVIL AND INTERIOR WORKS 3 ELECTRICAL WORKS Grand Total Rs
Transcript
Page 1: CANCER INSTITUTE (WIA) Canal Bank Road, Adyar Chennai 600 020cancerinstitutewia.in/CIWIA/download/Adendom to Tender I Linear... · Dismantling of Plain Cement Concrete or Flooring

CANCER INSTITUTE (WIA)

Canal Bank Road, Adyar

Chennai 600 020 Phone:+91 44 2220 9150 Extn (179)

Email:[email protected]

www.caninstitutewia.in

Addendum to Tender – I

PROCUREMENT OF MEDICAL EQUIPMENTS

Procurement of : Linear Accelerator

BID REFERENCE: CI: SCI:NP/ROG/P-I/2016-17/01DATED DECEMBER 15, 2016

Abstract Schedule

SL.

No. Description Amount in Rs:

1. HVAC WORKS

2. CIVIL AND INTERIOR WORKS

3 ELECTRICAL WORKS

Grand Total Rs

Page 2: CANCER INSTITUTE (WIA) Canal Bank Road, Adyar Chennai 600 020cancerinstitutewia.in/CIWIA/download/Adendom to Tender I Linear... · Dismantling of Plain Cement Concrete or Flooring

Sr.

No. Item Description Qty. Unit Unit Rate

in Rs.

Total Amt

in Rs.

HVAC WORKS

1

Supply installation testing commissioning of 8.5 ton ductble split unit with supply

of grills,ducting, insulation with 4 fresh air arrangement, upto 5 mrt copper pipe

considered.(N+N) with 100% standy-by

Ls No

2 Supply of 2 ton Hi wall split unit for TPS room with 5 kva stabilizer, upto 5 mrt

copper pipe considered with 100% standy-by Ls No

3 Supply of 2 ton Hi wall split unit for UPS room with 5 kva stabilizer, upto 5 mrt

copper pipe considered with 100% standy-by Ls

4 Supply of Ceiling suspended unit for control consol area2 tr, upto 5 mtr copper

pipe considered. Ls no

5 Supply installation of Hooks for lifting ,shifting, and instalation of Linac

machine.

One No

TOTAL

Page 3: CANCER INSTITUTE (WIA) Canal Bank Road, Adyar Chennai 600 020cancerinstitutewia.in/CIWIA/download/Adendom to Tender I Linear... · Dismantling of Plain Cement Concrete or Flooring

Sr.

No. Item Description Qty. Unit

Unit Rate in

Rs.

Total Amt in

Rs.

CIVIL AND INTERIOR WORKS

1

Excavation in all types of soil including dense soil, disintegrated/ weathered/ soft rock

(Poclainable) for Footings of columns, Retaining walls, Core walls, catch pits, Pits,

Trenches, etc., by mechanical means including manual excavation for leveling, dressing

the edges, with all leads and lifts including back filling in layers of 150mm with watering

and compaction. dewatering of both ground and surface water, removal of slurry

generated while excavation and keeping the area free of water with necessary shoring,

struting, required for keeping earth in position etc, Rate to include disposing the excess

earth and spreading in layers to the required levels within the site wherever specified by

the local authorities. Note: Working space and Provision of slopes if required for

execution shall not be paid seperately. Rate to include all royalties, Seignorage, taking

statutory approvals as necessary to carry out the works etc., complete.

Upto 1.50 Metre depth below average ground level.

Cum

Supply and filling in foundations and the area whereever specified with approved good

quality filling materials in plinths, area development etc. wherever specified in layers of

not exceeding 150 mm thick including breaking clods,storing,transportation ,double

handling, watering, compacting each layer with vibratory compactor and at unaccessible

places with wooden/steel rammers to achieve 90 to 95% proctor density at optimum

moisture content, all leads and lifts, bailing/ pumping out of water to keep site dry while

backfilling; cost shall include conveyance of all materials, labour, machinery etc.

complete as directed.The rate to includes loading,unloading, hire and fuel charges for

tools and plants, all royalties,taking staxtutory approvals as necessary to carry out the

works and other incidental charges etc., complete. (Soil excavated from within site can

be used)

Cum

1

Providing and casting in situ cement concrete M-25 (Concrete Density 2.35 gms/cc) of

trap / granite /quartzite/ gneiss metal for R.C.C. Walls as per detailed designs and

drawings or as directed including centering, formwork, cover blocks compacting and

roughening if special finish is to be provided and curing complete. (Excluding

reinforcement).With fully automatic micro processor based PLC with SCADA enabled

reversible drum type concrete mixer. With natural sand.

i Between Maze and Console with Bed thickness 800mm Cum

ii Between Maze and Waiting hall with Bed thickness 600mm Cum

Page 4: CANCER INSTITUTE (WIA) Canal Bank Road, Adyar Chennai 600 020cancerinstitutewia.in/CIWIA/download/Adendom to Tender I Linear... · Dismantling of Plain Cement Concrete or Flooring

Sr.

No. Item Description Qty. Unit

Unit Rate in

Rs.

Total Amt in

Rs.

iii At Machine opposite inside Side Wall with Bed thickness 500mm Cum

iv Between Blood sample Room and Machine with Bed thickness 450mm Cum

v At Console with Bed thickness 300mm Cum

vi Near PET CT with Bed thickness 230mm Cum

vii Between Console and Maze with Bed thickness 200mm

Cum

viii At roof top with Bed thickness 900mm Cum

2

Providing and injecting chemical emulsion for PRE-CONSTRUCTIONAL anti-termite

treatment and creating a chemical barrier under and around the column pits, wall

trenches, basement excavation, top surface of plinth filling, junction of wall and floor,

along the external perimeter of building expansion joints, surroundings of pipes &

conduits etc. complete (plinth area of the building at ground floor only shall be

measured). (Chloropyrophos 20%)

Sqm

9 Supply of MS plate 70mm thick , 7.89g/CC (5602MM X 2794MM) AND (2705mm X

3500mm) KG

10 Supply of MS plate 265 mm thick , 7.89g/CC (3020X 4668MM) and (368mmx 113mm)

KG

11 Supply of MS plate 113mm thick , 7.89g/CC , (368mm x 4668mm)

KG

12 150mm thick Brick work in work with bricks of class designation 75 in super structure

above plinth for all heights in cement mortar 1:4 ( 1 cement : 4 coarse sand ) Sqm

13 230mm thick Brick work in work with bricks of class designation 75 in super structure

above plinth for all heights in cement mortar 1:4 ( 1 cement : 4 coarse sand ) Sqm

14

Dismantling of Plain Cement Concrete or Flooring or Brick work to any depth and

width, at all levels below & above Ground Level of any shape, removal of debris,

disposing the same away from the site, loading and unloading, making the surface good

etc. complete. Rate shall include for dismantling of Plain Cement Concrete / Brick work

by manually / mechanical means with necessary tools and plants, scaffolding, water and

power charges, cleaning the surface, preparation of surface etc. Rate shall include for

stacking the serviceable materials and disposing the unserviceable materials/debris away

from the site premises by mechanical means including loading, unloading, clearing the

site etc. complete, as directed.

Cum

Page 5: CANCER INSTITUTE (WIA) Canal Bank Road, Adyar Chennai 600 020cancerinstitutewia.in/CIWIA/download/Adendom to Tender I Linear... · Dismantling of Plain Cement Concrete or Flooring

Sr.

No. Item Description Qty. Unit

Unit Rate in

Rs.

Total Amt in

Rs.

Providing and applying 12mm thick plaster in cement mortar mix ratio CM 1:6 (1

cement : 6 sand) mixed with polypropylene fibers as per instruction of the approved

manufacturer, to internal surfaces of concrete and masonry work; including raking out

joints, hacking concrete surfaces and applying approved chemical bonding agent and

applying a scratch coat over concrete surfaces by bonding / adhesive chemical coat as

directed by approved manufacturer to create a key, cleaning / grooving deep junctions of

concrete & masonry, grouting then back by mortar mixed with non shrinking compound

along with packing of clean, fresh square cut aggregate; also providing and fixing 20

gauge GI chicken mesh @ 150 mm wide to junctions of concrete and masonry, preparing

jambs, sills, grooves, pattas, wattas, rounding of corners, etc. all complete as per

architectural drawings, specifications and finished smooth with wooden rundha etc. or

as specified by the PM at all leads,depth and lifts, doing independent double-legged

scaffolding, cleaning of surfaces, curing, etc. complete as per specification and to the

approval of the PM.

(Location : Internal Wall surfaces)

Sqm

16

Providing and applying plastic emulsion paint of approved make and colour conforming

to IS in two coats (surface and finish acceptable to the PM must be achieved by the

contractor and any additional coats if required shall be at the cost of the contractor);

including preparing surfaces, filling up with gypsum or approved crack filler, binder;

cleaning and making the surface dust-free, applying a sealer or primer coat of paint as

recommended by approved paint manufacturer, applying two coats of paint (of approved

make and shade), required scaffolding, cleaning and protecting till the handing over of

site to the employer all complete to entire satisfaction of the PM. (Location:Internal

walls)

Sqm

17 Providing concrete of grade M25 platform base for Linac Machine and Chiller Cum

18 Fabrication, Supply and Fixing inposition all works complete of Light duty MS Grating

with one coat of Primer and two coats of Finished Paint RMT

Page 6: CANCER INSTITUTE (WIA) Canal Bank Road, Adyar Chennai 600 020cancerinstitutewia.in/CIWIA/download/Adendom to Tender I Linear... · Dismantling of Plain Cement Concrete or Flooring

Sr.

No. Item Description Qty. Unit

Unit Rate in

Rs.

Total Amt in

Rs.

19

Providing and fixing 600mm x 600mm x 15mm thick Mineral fibre grid false ceiling

system as manufactured by M/s. Armstrong or equivalent approved; fixed using hot

dipped galvanized steel section, exposed surface with pre-coated cappings, tees,

rotary stitched cross tees, sub cross tee and wall angle fixed to the periphery of the wall.

The grid shall be suspended at every 1200mm c/c. in both directions using 2.0 mm.

thick pre-straightened GI wire, including cutting and making arrangement with

required reinforcement, to fix light fillings, AC grills, access services doors/panel

required double legged scaffolding / staging, finishing joints smooth to correct line and

level complete having 3 coats of white paint back of the tile duly sanded and finished

with a coat of protective paint over the formed grid complete all as per approved

reflected false ceiling layout to approval and satisfaction of the PM.

Sqm

20 Supply of Modular flush door with frame approx size 900 X 2100mm with 35 mm thick

solid wood, including lock, handle, keel and other accessories for inner main door. No

21

Providing and fixing 35mm thick flush door shutters single leaf / Double leaf of solid

core of block board type bonded with phenol formaldehyde synthetic resin thermo

pressed with 8 mm thick teak wood tongue & groove external lipping. The construction

procedure of the shutter should be as per IS 2202. The shutter shall be shop prepared

for taking mortice lock or latches suitable lock block of wood may be provided for fixing

the hardware. The size of block, shall perfectly correspond to the maximum size of lock,

covered in IS 2209. All the four edges of the door shutter shall be square. The shutter

shall be free from twist or warp in its plane and of required size etc. complete as

directed.Rate shall include for supplying and fixing the door with necessary approved

hardwares such as S.S.ball bearing Hinges of satin finish of suitable size and thickness

with S.S.Screws, Mortice Lock with handle, lever handle with lock, SS forend and SS

strike plate, europrofile cylinder, all of Satin finish Grade SS 304 confirming to BS

7352 , door closer with Paralel arm bracket in Active Leaf , stainless steel tower bolt,

S.S latches, door stoppers, door buffers etc. complete and as directed and all as per the

approved make and model as mentioned in the drawing

No

Page 7: CANCER INSTITUTE (WIA) Canal Bank Road, Adyar Chennai 600 020cancerinstitutewia.in/CIWIA/download/Adendom to Tender I Linear... · Dismantling of Plain Cement Concrete or Flooring

Sr.

No. Item Description Qty. Unit

Unit Rate in

Rs.

Total Amt in

Rs.

22

Providing and laying approved quality, colour, design and shade fully homogeneous

Vitrified tile 600mmx600mm (confirming to IS 15622 / EN 176 Group B1a and water

absorption less than 0.08%) flooring in pattern as detailed in drawing or as directed by

the PM. Tile to be bedded over cement concrete screed using approved quality

compatible adhesive of approved make, joints to be cleaned and grouted with matching

colour approved quality polymer based readymade grout, curing, cleaning etc. to

required line, level, etc. all complete at all heights, lifts and leads to the entire

satisfaction of the PM. The tile should be grouted having 5mm epoxy filler of approved

shade as per tile color .

Sqm

23

Providing and laying approved quality, colour, design and shade fully homogeneous

Vitrified tile 300mmx300mm (confirming to IS 15622 / EN 176 Group B1a and water

absorption less than 0.08%) flooring in pattern as detailed in drawing or as directed by

the PM. Tile to be bedded over cement mortar 1:3, joints to be cleaned and grouted with

matching colour approved quality polymer based readymade grout, curing, cleaning etc.

to required line, level, etc. all complete at all heights, lifts and leads to the entire

satisfaction of the PM. The tile should be grouted having 5mm epoxy filler of approved

shade as per tile color .

i For Machine Room Sqm

ii For TPS Room

Sqm

24

Providing and applying plastic emulsion paint of approved make and colour conforming

to IS in two coats (surface and finish acceptable to the PM must be achieved by the

contractor and any additional coats if required shall be at the cost of the contractor);

including preparing surfaces, filling up with gypsum or approved crack filler, binder;

cleaning and making the surface dust-free, applying a sealer or primer coat of paint as

recommended by approved paint manufacturer, applying two coats of paint (of approved

make and shade), required scaffolding, cleaning and protecting till the handing over of

site to the employer all complete to entire satisfaction of the PM. (Location:Internal

walls)

Sqm

25 Supply of working table in control console area 12' X3' X 3'.6" Nos

26 Wooden almirah inside linear accelerator room of size 6’ X 7’ X 2’ Nos

27 Supply of over head cabinet 12' X 2'.6" X2' Nos

Page 8: CANCER INSTITUTE (WIA) Canal Bank Road, Adyar Chennai 600 020cancerinstitutewia.in/CIWIA/download/Adendom to Tender I Linear... · Dismantling of Plain Cement Concrete or Flooring

Sr.

No. Item Description Qty. Unit

Unit Rate in

Rs.

Total Amt in

Rs.

28 Wooden table 20 RFT for TPS room

Nos

29 Storage cabinet for TPS room 20RFT.

Nos

30 Supply of Chairs

Nos

32

Designing, providing and laying proprietary chemical water proofing system consisting

of polymer modified acrylic base composite coating (of one part or two part component)

as approved by the Client and as recommended by the approved manufacturer of

waterproofing coating, sandwiched nylon mesh / fibre mesh and protective screed. The

work shall include removing of existing waterproofing course, cleaning of surface,

grouting porous surfaces including making ‘V’ grooves at junctions, cracks etc. Further

including horizontal surface protected with 20mm screeding in 1:4 mortar (1 cement : 4

sand) and vertical surface (wall) plastered with cement, sand mortar in ratio 1:4 (1

cement : 4 sand), finished in ready to receive Architectural finish, in correct line, level

and plumb, curing, grouting, testing, etc. all complete to entire satisfaction of the PM,

contractor to provide guarantee for 10 years Rs.100/- stamp paper in approved proforma.

Sqm

34

Making Core Cutting of size 150mm dia in slabs / beams / retaining walls and any other

R.C members to any dia & depth by using 'HILTI' make diamond drilling machine with

tolerance for any type of inserts, anchor fasteners etc. Rate shall include for sealing the

gaps between RC surface and inserts with fire retardent grouting material as per

manufactures specification ,all charge, preparation of surface, cutting of reinforcement,

cleaning the surface, staging, scaffolding with necessary tools and equipments water and

power, removal of debris from the site, staging scaffolding etc complete, as directed.

Nos

35 Co-ordination for Fixing of base frame and Pouring Concrete of grade M25 as directed

by Engineer in Charge Cum

37

Structural Consultancy Fees, including providing Stability Certificate and Test

Certificates from government recognized institutes for Concrete and Steel LS

TOTAL

Page 9: CANCER INSTITUTE (WIA) Canal Bank Road, Adyar Chennai 600 020cancerinstitutewia.in/CIWIA/download/Adendom to Tender I Linear... · Dismantling of Plain Cement Concrete or Flooring

Sl. No. Description of Item Qty Unit Unit Rate in Rs. Amount in Rs. Total Amount

in Rs.

ELECTRICAL WORKS

Supply Erection Supply Erection

I

SECTION-A: SUPPLY, FIXING, TESTING &

COMMISSIONING MAIN PANEL & DISTRIBUTION

BOARDS

1.1

Supply, Installation, Testing and Commissioning of following LT

Panel shall be designed for 415V, 3 Phase, 50Hz, 4wire A.C

system made up of sheet steel, dust and vermin proof of Cubicle

type, Indoor type, floor mounting, free standing, L.T panel

compartmentalized design and fabricated with 2mm CRCA sheet

steel for main frames, folded sections and load bearing members

and 1.6mm CRCA sheet steel for doors & covers and base

channel 75mm X 40mmX 3mm and removable Gland plates at

bottom and top entry complete with adequate rating of bus-bars,

single bus-bar system, interconnections, cable chamber, powder

coated painting, earthing etc., as mentioned in the Schedule of

quantity / schematic diagram. Providing and fixing of below Panel

with all accessories. The LT panel shall be accommodated in a

modular multi type arrangements, adequate size of cable rack in

cable chamber, painting, Two separate earth bus-bar throughout

the length of the panel, numbering, danger plate etc. as per the

drawings etc as required.

a MAIN LT PANEL

Incomer :

400A TP&N 25KA MCCB1 No with RYB Phase indication

lamps, control MCB and all other required accessories. - 1 No.

Instruments Panel

Digital type Ammeter, Voltmeter, kWH meter, necessary CTs,

and On-Off-Trip trip indicating lamps with control MCB etc.

as per schematic layout.

400A 25 KA TPN Aluminium busbars

Page 10: CANCER INSTITUTE (WIA) Canal Bank Road, Adyar Chennai 600 020cancerinstitutewia.in/CIWIA/download/Adendom to Tender I Linear... · Dismantling of Plain Cement Concrete or Flooring

Sl. No. Description of Item Qty Unit Unit Rate in Rs. Amount in Rs. Total Amount

in Rs.

Outgoings :

40A TPN MCCB 25KA with all other required accessories - 1

Nos for LDB

63A TPN MCCB 25KA with all other required accessories - 5

Nos for HVAC - 2 nos, PDB - 2 nos & Spare - 1 no

100A TPN MCCB 25KA with all other required accessories - 1

No for Chiller

250A TPN MCCB 25KA with all other required accessories - 1

No for 120KVA UPS

With necessary Aluminium busbar interconnection providing

control MCB, ON, OFF indication lamps etc. for each outgoing

feeders as per schematic layout.

With necessary Aluminium busbar interconnection etc. for each

outgoing feeders as per and schematic layout.

1 Each 0 0 0

b Clinac with OBI Costmer Control Board

Incomer :

250A TPN 25KA MCCB with RYB Phase indication lamps,

control MCB and all other required accessories. - 1 No.

Instruments Panel

Digital type Ammeter, Voltmeter, Earth Falt Relay, necessary

CTs, and On-Off-Trip trip indicating lamps with control MCB

etc. as per schematic layout.

250A 25 KA TPN Aluminium busbars

Outgoings :

100A 25KA 4pole MCCB - 2nos, 100A 4pole power contactor -

2nos

24VDC aux Contactor - 5 Nos, 110VAC aux contactor - 4 nos,

230VAC aux contactor - 1 no

16A Double pole MCB - 7 Nos, 40A 4P MCB - 2 nos, 230/24v

5A Power supply - 1 No

Page 11: CANCER INSTITUTE (WIA) Canal Bank Road, Adyar Chennai 600 020cancerinstitutewia.in/CIWIA/download/Adendom to Tender I Linear... · Dismantling of Plain Cement Concrete or Flooring

Sl. No. Description of Item Qty Unit Unit Rate in Rs. Amount in Rs. Total Amount

in Rs.

With necessary Aluminium busbar interconnection providing

control MCB, ON, OFF indication lamps etc. for each outgoing

feeders as per schematic layout.

With necessary Aluminium busbar interconnection etc. for each

outgoing feeders as per and schematic layout.

1 Each 0 0 0

1.2 DISTRIBUTION BOARDS:

Supply, Installation, Testing and Commissioning of the following

TPN MCB distribution boards shall be designed for metal

door type IP 42 protection, with MCB / Isolator / RCCB / RCBO

as incomer. The distribution boards shall be designed for

415V,3Ph,50Hz, 4 wire AC system sheet steel, dust and vermin

proof suitable for wall mounting type (recessed) designed and

fabricated made up of Standard reputed make manufacture. The

DB shall have suitable neutral and earth terminal block to

facilitate easy termination of wires. All wires inside the DB shall

be terminated using copper crimping socket. The DB shall be

suitable body earthing terminals with powder coated painting,

danger board, sign writing including minor civil works (recessed

system) etc as required.

a LDB 1

The double door type 4 Way TPN Compartmental

Horizontal ( 7 Segment Phase Segregation ) MCB DB

comprising of the following :

Incoming

32 A TPN MCB 'C' Curve – 1 No.

Outgoings

32 A DP 30 mA RCCB – 3 Nos. as outgoing with 12 Nos 6A SP

MCB 'C' Curve

(Each 32A DP 30 mA RCCB consist of 4 Nos of 6A 10 KA SP

MCB 'C' Curve )

Page 12: CANCER INSTITUTE (WIA) Canal Bank Road, Adyar Chennai 600 020cancerinstitutewia.in/CIWIA/download/Adendom to Tender I Linear... · Dismantling of Plain Cement Concrete or Flooring

Sl. No. Description of Item Qty Unit Unit Rate in Rs. Amount in Rs. Total Amount

in Rs.

With necessary tinned copper busbars, interconnections, separate

earth bus, separate neutral bus for each phases. The

board shall be powder coated type fixed with concealed system in

wall. The rate shall include necessary connected civil works like

chipping, rough plastering to match with good orginal surface etc.

1

Each

0

0

0

b PDB (Bunker & TPS Room)

The double door type 6 Way TPN Compartmental

Horizontal ( 7 Segment Phase Segregation ) MCB DB

comprising of the following :

Incoming

63A TPN 10kA MCB'C'Curve with all other required accessories – 1

No.

Outgoings

63 A DP 30 mA RCCB – 3 Nos. as outgoing with 9 Nos 16A & 3 Nos

SP MCB 'C' Curve

(Each 63A DP 30 mA RCCB consist of 6 Nos of 10/16/20A 10 KA SP

MCB 'C' Curve )

With necessary tinned copper busbars, interconnections, separate earth

bus, separate neutral bus for each phases. The

board shall be powder coated type fixed with concealed system in

wall. The rate shall include necessary connected civil works like

chipping, rough plastering to match with good orginal surface etc.

2

Each

c UPS DB - Bunkar & TPS Room

The double door type 4 Way TPN Compartmental Horizontal (

7 Segment Phase Segregation ) MCB DB comprising of the

following :

Incoming

32 A TPN MCB 'C' Curve – 1 No.

Page 13: CANCER INSTITUTE (WIA) Canal Bank Road, Adyar Chennai 600 020cancerinstitutewia.in/CIWIA/download/Adendom to Tender I Linear... · Dismantling of Plain Cement Concrete or Flooring

Sl. No. Description of Item Qty Unit Unit Rate in Rs. Amount in Rs. Total Amount

in Rs.

Outgoings

32 A DP 30 mA RCCB – 3 Nos. as outgoing with 12 Nos 6A SP

MCB 'C' Curve

(Each 32A DP 30 mA RCCB consist of 4 Nos of 6A 10 KA SP MCB

'C' Curve )

With necessary tinned copper busbars, interconnections, separate earth

bus, separate neutral bus for each phases. The

board shall be powder coated type fixed with concealed system in

wall. The rate shall include necessary connected civil works like

chipping, rough plastering to match with good orginal surface etc.

2

Each

1.3 63A 4P MCB & IP 65 Encloser

Supply, Installation, Testing and Commissioning 40/63A TPN MCB

with water proof enclosure including earthing and all other

required accessories as per site conditions. For A/C & Chiller

3

Each

1.4 120 KVA UPS Input & Output Switch

Supply, Erection, Testing and Commisioining of 250A 25KA TPN

MCCB with cubicle type free standing IP 42 Protection encloser with

support clamps and angles frames as required as per the site condition.

Incoming and outgoing cables shall be of Top and bottam entry

(Optional)

2

Each

SECTION - A:-Total C/o to summary : Rs.

II SECTION-B: WIRING AND CONNECTED ACCESSORIES

2.1 SUBMAINS UPS & RAW POWER CIRCUTS

Page 14: CANCER INSTITUTE (WIA) Canal Bank Road, Adyar Chennai 600 020cancerinstitutewia.in/CIWIA/download/Adendom to Tender I Linear... · Dismantling of Plain Cement Concrete or Flooring

Sl. No. Description of Item Qty Unit Unit Rate in Rs. Amount in Rs. Total Amount

in Rs.

a Supply & Laying of 2R 2.5sqmm 1R 1.5 PVC insulated multistrand

copper wire with 25mm dia PVC conduit with all accessories as

required as per site conditions.(lighting circuit mains)

100 Mtr.

b Supply & Laying of 2R 2.5sqmm 1R 1.5 PVC insulated multistrand

copper wire with 25mm dia PVC conduit with all accessories as

required as per site conditions.(Raw Power Circuit)

95 Mtr.

c Supply & Laying of 2R 2.5sqmm 1R 1.5 PVC insulated multistrand

copper wire with 25mm dia PVC conduit with all accessories as

required as per site conditions.(Ups Circuit)

450 Mtr.

d Supply & Laying of 2R 4sqmm 1R4sq.mm PVC insulated FRLS

multistrand copper wire with 25mm dia FRPVC conduit with all

accessories as required as per site conditions.(Split A/C & 16A

Power Socket Circuit)

150 Mtr.

e Supply & Laying of 12R 1.5sq.mm PVC insulated multistrand copper

wire with 25mm dia PVC conduit with all accessories as required as

per site conditions. (for CCP to Door InterLock and Warning

Lamp control wiring)

55 Mtr.

f Supply & Laying of 12C 1.5sq.mm PVC insulated multistrand copper

wire with 25mm dia PVC conduit with all accessories as required as

per site conditions. (for CCP to Modulator Interphase wiring)

12 Mtr.

g Supply & Laying of 2 Run 1.5sqmm PVC insulated multistrand

copper wire with 20mm dia PVC conduit with all accessories

for Emergency push button wiring.

90 Mtr.

2.2 LIGHT POINT

Page 15: CANCER INSTITUTE (WIA) Canal Bank Road, Adyar Chennai 600 020cancerinstitutewia.in/CIWIA/download/Adendom to Tender I Linear... · Dismantling of Plain Cement Concrete or Flooring

Sl. No. Description of Item Qty Unit Unit Rate in Rs. Amount in Rs. Total Amount

in Rs.

Provide all materials, accessories, labour etc. for wiring with conduit

and accessories in recessed system wiring for lights,

ceiling fan & exhaust fan point wiring. using 3 Runs of 1.5sqmm PVC

insulated multistrand Flexible copper conductor wires (FRLS) of

650/1100V grade drawn through rigid PVC conduit with 2mm wall

thickness including supply and laying of conduits and its accessories

concealed in the slab / wall, surface mounted / using PVC pull /

junction boxes, light outlet boxes, G.I.switch outlet boxes, Modular

switch plates, 6A switches in recessed system of G.I / Nickel

Cadmium outlet box etc., including testing and commissioning

complete wiring system. The rate for point wiring should inclusive of

supply and fixing of 6A modular type switch in a suitable size

modular box in concealed system, wiring from first switch point and

then looping between the points and switches. Connect the all lights,

switches sockets with suitable PVC sleeves etc as required in the

following manner.

a 1 Light controlled by 1 switch 20 Pts

b 2 light points controlled by 1 switch (1set = 2 lights) 12 Pts

c 4 light points controlled by 1 switch with 400W Dimmer 1(1set = 4

lights) - for Dimmer 1 Pts

2.3 SOCKETS

a

Supply, fixing, testing & commissioning of 6A, multipin shuttered

socket outlet controlled by one way 6A switch. The rate shall be

inclusive of G.I / Nickel Cadmium metal box, modular front plate,

switches & socket and necessary fixing accessories. In recessed

mounting system with civil works (cutting, chipping, plastering to

match the original finish as required. (Consol & Bunker Raw

Power)

6

Nos

Page 16: CANCER INSTITUTE (WIA) Canal Bank Road, Adyar Chennai 600 020cancerinstitutewia.in/CIWIA/download/Adendom to Tender I Linear... · Dismantling of Plain Cement Concrete or Flooring

b

Supply, fixing, testing & commissioning of 6/13A, multistandard

shuttered socket outlet controlled by one way 6A switch. The

rate shall be inclusive of G.I / Nickel Cadmium metal box, modular

front plate, switches & socket and necessary fixing accessories. In

recessed mounting system with civil works (cutting, chipping,

plastering to match the original finish as required. (Consol & Bunker

UPS Power)

30

Nos

c

Supply, fixing, testing & commissioning of 6/16A, multipin shuttered

socket outlet controlled by one way 16A switch. The rate

shall be inclusive of G.I / Nickel Cadmium metal box, modular front

plate, switches & socket and necessary fixing accessories. In recessed

mounting system with civil works (cutting, chipping, plastering to

match the original finish) as required. (Consol, Bunker & TPS

Room UPS & Raw Power)

15

Nos

d

Supply, fixing, testing & commissioning of 1No 25A 3 Pin socket with

plug top and controlled by 25A DP 'C' Curve MCB in a suitable size

MS enclosure with necessary making interconnection, wiring, earthing,

painting etc., and required fixing accessories. (Splite AC Control)

7

Nos

SECTION - B:-Total C/o to summary : Rs.

III SECTION - C : SUPPLY, FIXING, TESTING & COMMISSIONING

OF LIGHT FITTINGS

3.1 Light Fittings

a

Supply,Erection, Testing and Commissioning of 2' X 2' LED 40 watts

recessed mounting fitting with all accessories and

interconnecting with 3 R 1.5 sqmm PVC insulated FRLS copper wire

Make: Philips, other branded first class companies preferred.

15

Nos

b

Supply,Erection, Testing and Commissioning of LED 18 watts recessed

mounting down light fitting with all accessories and

interconnecting with 3 R 1.5 sqmm PVC insulated FRLS copper wire

Make: Philips, other branded first class companies preferred.

10

Nos

Page 17: CANCER INSTITUTE (WIA) Canal Bank Road, Adyar Chennai 600 020cancerinstitutewia.in/CIWIA/download/Adendom to Tender I Linear... · Dismantling of Plain Cement Concrete or Flooring

c

Supply,Erection, Testing and Commissioning of single 15W Recessed

fixed type LED Dimmer fitting with Electronics ballast

and all accessories and interconnecting with 3 core 1.5 sqmm PVC

insulated FRLS copper wire and fixing the same in the

Ceiling

4

Nos

d

Supply, Erection, Testing and Commisioining of Box type 28W T5

fitting along with 1 nos 28w Compact Fluorescent Lamps

and with high frequency electronic ballasts with all accessories.

6 Nos

SECTION - C :- Total C/o to summary : Rs.

IV SECTION - D : SUPPLY, LAYING, FIXING, TESTING &

COMMISSIONING LT CABLES AND CABLE TERMINATION

4.1 L.T.CABLES

Supply, Laying, Testing and Commissioning of the following size PVC

insulated and PVC sheathed/XLPE Power cable of

1.1KV grade Aluminium/Copper armoured/unarmoured LT UG cables.

The Cables shall be laying in the cable trenches/cable tray/ground/hume

pipes/cable duct and partially laid on wall/ceiling indoor/outdoor with

suitable clamps & necessary fixing accessories etc. as required.

a 4C 300 sq.mm Aluminium Ar. Cable for EB Incomming power

(Optional) Mtr.

b 4R 95 sq.mm Copper flexible cable UPS Incoming & Outgoing

16 Mtr.

c 4R 95 sq.mm Copper flexible cable for UPS to Clinac with OBI

Costmer Control Board 50 Mtr.

d 4R 35 sq.mm Copper flexible cable for CCP to Modulator

35 Mtr.

e 1C 95 sq.mm Copper flexible cable for additional Netural Earth and

Bodi Earth for 60KVA UPS & Machine 100 Mtr.

f 1C 35 sq.mm Copper flexible cable for Bodi Earth for Machine

35 Mtr.

g 4C 16 sq.mm Copper Ar. Cable for Chiller incoming

75 Mtr.

Page 18: CANCER INSTITUTE (WIA) Canal Bank Road, Adyar Chennai 600 020cancerinstitutewia.in/CIWIA/download/Adendom to Tender I Linear... · Dismantling of Plain Cement Concrete or Flooring

h 4C 10 sq.mm Copper Ar. Cable for PDB & Duct A/C incoming 150 Mtr.

i 4C 6 sq.mm Copper Ar. Cable for LDB & UPS DB incoming 125 Mtr.

4.2 CABLE TERMINATION

Supply, Installation and making of LT UG cable end termination of the

following size PVC insulated & PVC sheathed /XLPE insulated

Copper/Aluminium cable of 1.1KV grade with single compression

cable gland and suitable Aluminium/Copper crimpping

sockets/lugs,including Gland earth clip ,crimpping paste, sleeves,

ferrules etc., necessary accessories as required.

a 4 Core 300 Sqmm XLPE Ins.Ar.Alu. Cable 2 Each

b 4R 95 Sqmm Copper flexible cable

4 Each

c 4R 35 Sqmm Copper flexible cable

2 Each

d 1R 95 Sqmm Copper flexible cable 6 Each

e 1R 35 Sqmm Copper flexible cable 4 Each

f 4 Core 16 Sqmm Copper Ar. cable 2 Each

g 4 Core 10 Sqmm Copper Ar. cable 12 Each

h 4 Core 6 Sqmm Copper Ar. cable

12 Each

SECTION - D :- Total C/o to summary : Rs.

V SECTION-E: EARTHING SYSTEM, CABLE TRAY WORKS

5.1 Earth stations

a

Supply, Installation, Testing & Commisioning of 3 mtrs long 100mm

dia cast Iron pipe with 600 X 600 X 3mm copper plate

Earth electrode for Machine body earth & UPS Netural earth 3 Each

c Supply and laying of following flats for Earthing 25 x 3 mm GI flat for

main panel and other bodi earthing as required. 75 Mtr.

Page 19: CANCER INSTITUTE (WIA) Canal Bank Road, Adyar Chennai 600 020cancerinstitutewia.in/CIWIA/download/Adendom to Tender I Linear... · Dismantling of Plain Cement Concrete or Flooring

e

Supply and laying of following Earthing No '8' gauge Copper wire for

equipment and DB, AC & Chiller earthing. 150 Mtr.

5.2 Earth Links

Supply, Fixing of the following size Copper flat earth Station with 2

Nos DMC supporting Insulator clamp with predrilled machine made

holes of 12mm & 6 mm dia at 25mm intervals for fixing earth flat

including Nuts,Bolts & spring and plate washers complete as required.

(2Nos DMC supporting insulators shall be used for 400mm distance)

a 300 x 25 x 3mm thick copper earth flat

2 Each

5.3 CABLE TRAY

a

Supplying, fabricating, erecting and connecting the following 1.6mm

thickness GI perforated type cable trays with necessary

supports, tees, elbows, bends,bolts and nuts and any other associated

accessories to complete the job.-300mm (wide) X

50mm (collar height)

25

Mtr.

SECTION - E:-Total C/o to summary : Rs.

VI SECTION-F - SUPPLY, LAYING, FIXING, TESTING &

COMMISSIONING OF DATA, VOICE & Network

6.1 Supply, Laying & fixing of CAT6 unarmoured Data cable from Data

Rack Box to floor junction box & each individual Sockets

through existing rigid, PVC conduit with all accessories etc.

450 Mtr.

6.2 Supply, Laying & fixing of 2 pair unarmoured telephone cable from 20

Pair Krone connector Box to floor junction box & each

individual Sockets through existing rigid, 2mm thick PVC conduit with

all accessories etc.

100 Mtr.

6.3

Supply & fixing of type data socket outlet recessed mounted system on

a GI / Nickel Cadmium outlet box with UTP CAT6

Shuttered Flush mount with face plate in the exising metal box and all

necessary accessories complete as required including the termination of

wires.

24

Nos

6.4

Supply & fixing of type Voice socket outlet recessed mounted system

on a GI / Nickel Cadmium outlet box with UTP RJ11 IO

Shuttered Flush mount with face plate in the exising metal box and all

necessary accessories complete as required including the termination of

wires.

6

Nos

6.5 Supply,Fixing, Testing and Commissioning of 6U Communication

Rack 1 Nos

6.5 Supply & Fixing of 24port Patch panel and 10/100/1000 mbps Base T

Switch with 24 port patch panel 1 Nos

6.6 Supply of 1 mtr Patch card

24 Nos

6.7 Supply & Fixing of 105 X 50 mm CMS Tray for Electrical, Data &

Voice cable pulling 25 Mtr.

SECTION - F :- Total C/o to summary : Rs.

VII SECTION - G - SUPPLY AND FIXING OF CCTV, FIRE ALARM,

LMO, WARNING LIGHT, EMERGENCY SWITCH & DOOR

INTER LOCK & MISCELLANEOUS

7.1 CC TV

Page 20: CANCER INSTITUTE (WIA) Canal Bank Road, Adyar Chennai 600 020cancerinstitutewia.in/CIWIA/download/Adendom to Tender I Linear... · Dismantling of Plain Cement Concrete or Flooring

a Supply, Fixing, Testing & Commissioning of Weather Proof IR

Camera, Sony CCD 1/3” colour camera

1 Nos

b Supply, Fixing, Testing & Commissioning of PTZ Doom Camera Sony

CCD 420TVL, X22 Zoom, 3.9 - 8.5 mm Auto iris lens,

RS485 Control

1 Nos

c Supply, Fixing, Testing & Commissioning of PTZ keyboard with

joystick

1 Nos

d Supply, Fixing, Testing & Commissioning of 24” LED Monitor / TV 2 Nos

e Supply, Fixing, Testing & Commissioning of 12VDC 2A power supply

for camera

2 Nos

f Supply and laying of 1 + 3 RG 59 CCTV cable 100 Mtr.

7.2 Tack / Tack Back System

a Supply, Fixing, Testing & Commissioning of Tack / Tack Back

Systems comprises of Console with Mike ( inbled amp.) Ceiling

Speaker - 1no.

1 Set

b Supply and laying of two core screened cable 50 Mtr.

7.3 Fire Alarm System

a Supply, Fixing, Testing & Commissioning of 2 Zone Conventional Fire

Alarm Panel with complete set. (RAVEL Make)

1 Nos

b Supply, Fixing, Testing & Commissioning of conventional Smoke

Detectors with base (SYSTEM SENSOR Make)

6 Nos

c Supply, Erection, Testing & Commissioning of Conventional Manual

Call Point.(RAVEL Make)

1 Nos

d Supply, Erection, Testing & Commissioning of Conventional Hooter/

Sounders (RAVEL Make)

1 Nos

e Supply and Laying of 2 core 1.5 sqmm Copper armoured cable (Policab

Make)

125 Mtr.

7.4 Emergency Switch, LMO & Warning Light

a Supply & Fixing of Emergency Stop switch and system On switch with

base box

4 Nos

b Supply and fixing of Magnetic Door switch 2 Nos

c Supply,Erection, Testing and Commissioning of Warning Lamp for

RED,Yellow,Green & Red, Green for OBI

1 Nos

Page 21: CANCER INSTITUTE (WIA) Canal Bank Road, Adyar Chennai 600 020cancerinstitutewia.in/CIWIA/download/Adendom to Tender I Linear... · Dismantling of Plain Cement Concrete or Flooring

d Supply of Last man out control unit, Last man out switch with

indicator, buzzer and External wiring kit (1.0 sq.mm cu. Wire &

pipes)

1 Nos

7.5

Installation testing and commissioning of Reynold or other equivalent

make 10TR Chiller with ancillary work such as piping ,

inbuilt 60 later water tank, valves, Grundfoss/wilo make pumps, LP,HP

pressure switch, flow switch, Antifreeze protection, Alarm with buzzer,

ext as per the standard. Including lifting and shifting of chiller with

crane

1

No

7.6 PROFESSIONAL CHARGES:

Towards professional charges for filing application, preparation of

drawings in necessary formats for approval, follow up and arranging

approval of drawings, scheme by Local electricity authority / Electrical

Inspectorate, arranging inspection, obtaining safety certificate clearance

from electrical Inspectorate for the installation and arranging power

connection. The Rate shall be including preparation and submission of

as built drawings of entire installation of the works executed need to be

submitted in the blue print of A1 size as required in 7 Sets of hard copy

and two set sets of soft copy in CD.

1

Job

SECTION - G :- Total C/o to summary : Rs.

Page 22: CANCER INSTITUTE (WIA) Canal Bank Road, Adyar Chennai 600 020cancerinstitutewia.in/CIWIA/download/Adendom to Tender I Linear... · Dismantling of Plain Cement Concrete or Flooring

Recommended Makes of EquipmentsFor Electrical Works:

1 MCB / MCCB / RCCB/RCBO - HAVELLS / HAGER / LEGRAND

2 Distribution boards - HAVELLS / HAGER / LEGRAND

3 Indicating instruments - DIGITAL - MECO/RISHABH/L&T /

HPL 4 Control Switch / Indication Lamp/ Push

Button

- L&T/SIEMENS/TEKNIC / KAYCEE

5 CTs (epoxy resin cast) - AE / KAPPA/PRECISION/KALPA

6 PVC conduit & accessories - PRECISION/AVONPLAST

7 LT Cables - POLY CAB /HAVELLS /KUNDAN

8 Modular Switch & Switch box [UL, CE

CERTIFIED]

- CRABTREE / LEGRAND/ MK

9 Industrial Type Sockets / Tops - CLIPSAL / HENSEL / LEGRAND

10 FRLS PVC ins. multi-strand copper wires/

Conductors

- POLY CAB /HAVELLS /KUNDAN

11 Light fittings - WIPRO/PHILIPS/HAVELLS/CGL

12 MDF - KRONE

13 Cat 6 utp cables - D-LINK / AMP/3 COM / NETGEAR

14 RJ 45 Computer Jack - D-LINK / AMP/3 COM / NETGEAR

15 Exhaust / Ceiling Fans - ALMONARD / CROMPTON / ORIENT

Note:

1. The Successful Tenderer shall submit test reports for all the materials/equipments.

2. If any make is not in accordance with the tender specification it will not be accepted even if

the make is indicated in the above List.

3. The Client / Consultants reserves the right to reject or accept any of the make given above

without assigning any reasons & bound to supply other brands in the list.

4. Successful Tenderer shall assess the required materials before procurement @ site. on this

account will be recovered in full in their bill.

5. Any excess material brought to site shall be taken back, if any payment made on this account

will be recovered in full in their bill.

All other terms and conditions in the original tender documents remain same as unchanged.

Dated 10/01/2017. The Director


Recommended