Case Studies on Chiller Plant System Energy-saving Control Strategies Analysis – Shanghai IFC W.K. Kwok
Transcript
Page 1: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Case Studies on Chiller Plant System Energy-saving Control Strategies

Analysis – Shanghai IFC

W.K. Kwok

Page 2: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

2

Page 3: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

3

Page 4: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Partners in the Research Works

4

Page 5: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Energy Pareto

Source : WBCSD, Report 2009. U.S. DOE, Energy Data Book, Oct. 2009

Global

Buildings 40%

Industry 32%

Transportation 28%

Buildings (USA)

HVAC 40%

Lightings 16% Water

heating 10%

Electronics 9%

Other 25%

Chiller Plant

Chillers 70%

Pumps 24%

CT & etc 6%

Source : Carrier’s one job reference

5

Page 6: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

First cost

Life Cycle Cost =

• Power consumption • Water consumption • Equipment maintenance (etc.)

• Initial investment • Residual Values • Utility Rebate •Taxes • Non-monetary costs & benefits

+

Operating Cost

Part Load operation is 95%~99% of whole system

operating hours

Operating Cost Saving

Gross Margin Increasing

Importance of Part Load Operation

6

Page 7: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

0 2 4 6 8

Operating Cost Increasing

5

0

5

10

Year

Down

Up

Standard Maintenance + System Solution Retrofit

0 2 4 6 8

Eff.

Dec

reas

e %

0

10

0

5

10

15

Without Maintenance

With the System Solution, the system efficiency could be maintained and even increased. The energy consumption could be saved for life cycle.

Eff.

Dec

reas

e %

Down

Standard Maintenance

0 2 4 6 8

Down Down Down Ef

f. D

ecre

ase

%

Year Year

Maintenance & Retrofit

7

Page 8: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Location Map - Shanghai ifc

8

Page 9: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Shanghai ifc - Section Plan Total Area 399,400 m2

Total C/P space : 1,900 nos

OFFICE 30 storeys 82,600 m2

RITZ CARLTON HOTEL

15 storeys 47,400 m2

23 storeys 47,900 m2

RETAIL 6 storeys 98,500 m2

HSBC Building

(One ifc) Two ifc Services apartments Podium & Basement

OFFICE 45 storeys 123,000 m2

9

Page 10: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

International Retail Mall

• Most prestigious shopping destination in Shanghai

10

Page 11: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Atrium

11

Page 12: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Apple

39 12

Page 13: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

MTR Tunnel

13

Page 14: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Grade A Office • over 2.2 million sq.ft office area

14

Page 15: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Luxury Hotels Ritz-Carlton Hotel

•totaling 300 luxury guestrooms

15

Page 16: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Equipment List of Chiller Plant

Equipment Type No.

Chillers

1000 Tons (centrifugal) 2850 Tons

(centrifugal)

3+6

Primary chilled water pumps 37 KW, 132 KW 3+7

Secondary chilled water pumps

132 KW, 220 KW (VFD) 7+4

Condensing water pumps 110 KW, 315 KW 3+7

Cooling tower fans 55 KW 14 * 3

16

Page 17: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Plant Configuration

Cooling towers

Secondary chilled water pumps

Primary chilled water pumps

Chillers Condensing water pumps

低座酒店

裙楼及地库

南塔楼低座

南塔楼中 座及高座

北塔楼低座

北塔楼中 座及高座

17

Page 18: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Health Analysis of Chiller Plant System before System Optimizing Retrofit

Warning Board of Fault Equipments

Note: fault equipments marked in yellow,

No Existing Problems (before retrofit)

1 The chillers load-unload control and the starting sequence are irrational, resulting in system operating with low efficiency

2 Fixed chilled water temperature set points, no considering changes of weather and load requirement

3 Irrational start and stop of cooling tower and fan control, cooling tower did not fully functioning, resulting in a waste of energy

4 Primary and secondary pump exist the reverse flow phenomena, resulting in inefficient system performance

5 Secondary chilled water pumps running at fixed speed, resulting in high power consumption even at low load conditions

6

No suitable energy consumption metrology device, resulting in the operators do not know the energy consumption of each equipments and which equipment has the high-energy consumption

Summary of System Operating Status Analysis

Breakdown of Plant Power Consumption

Note: power meter data of a typical summer day.

18

Page 19: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

No Optimization Control Strategies (Phase I)

1 Cooling Tower Optimization Control

2 Chilled Water Supply Temperature Reset

3 Chiller Start/Stop Sequence control

4 Secondary Pump Start/Stop Control

5 Anti-reverse flow control for primary-secondary system

6 Standard Chiller Monitoring Interface

7 Energy Consumption Monitoring System

8 Sensors Failure Diagnose and Calibration Reminder

9 Data Report, operating logging

Optimization Strategies Recommendations

19

Page 20: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Chiller + Cooling Tower Optimization

20

Page 21: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Chiller + Cooling Tower Optimization

21

Page 22: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Chiller + Cooling Tower Optimization

22

Page 23: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Set point at 7C

Set point according to 1.Outdoor air dew point temp. 2.Building load 3.Dehumidification requirement

Conventional Mode

100% 107%

10C 7C

Less chiller power consumption

Chilled water temp.

If we increase Chilled Water Supply Temperature at partial Load, Chiller performance can be improved.

Chilled Water Supply Temperature Reset

23

Energy-saving Mode

Page 24: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Chiller Control Challenges

Dynamic Changes of Building Loads

Chiller Performance at Different Conditions Performance of Different Chillers

Variable Utility Rates

Characteristics of Building Heat Response

Conventional Control Methods

Constant settings Schedules Sensor feedbacks Depends on people (manual control) No cost function No degradation Non-optimized Non-predictive …… 24

Page 25: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Chiller Plant Controls

Time

Weather, utility rates, historical trends, incentives, …

Save money?

3D optimization

Other Targets: Operation efficiency

Energy efficiency

Comfort

Safety

……

25

Page 26: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Control System Structure

Terminals

Building Automation System (BAS)

Data Checking

Pumps Chillers

Real-time data (up), commands (down)

Cooling Towers Boilers, etc

Advanced Chiller Plant Control System

Real-time data (up), commands (down)

User Interface (UI)

Interfaces

Database

Model Libraries

Optimization Engine

Fault / Energy Diagnostics

26

Page 27: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Enhancement of Secondary Pump Control

Reset the differential pressure setting of the most critical location with reference to the differential chilled water temperature

27

Page 28: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Anti-reverse Flow Control

Primary-Secondary Water System

500 tons

0 tons

0 tons

1200gpm

0 gpm

0 gpm

44 F 44.9 F

54 F

1200gpm

120gpm

1320gpm

1320gpm

0%

100%

0%

54 F

Chillers

Primary Pumps

Secondary Pumps

De-

coup

ler

i

sp

dtTTTT

211 '

Phenomena: reverse flow in de-coupler when secondary side demand is greater than chiller load.

Cooling load

Chiller capacity

Reverse flow

3° C 2° C

Results: mixed chiller water supply temperature is raised higher than chiller supply temperature, resulting in energy waste.

Coordination control of flow and temperature is a key problem to be resolved.

28

Page 29: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Performance Visualization & Energy Management

Chiller standard monitoring interface

Energy consumption monitoring system

Power meter monitoring interface

Optimization suggestion interface

29

Page 30: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Optimization suggestion interface

30

Page 31: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Sensors Failure Diagnose and Calibration Reminder

Functions: Diagnose all main sensors running status; Remind operators to calibration sensors according to each sensors calibration time.

31

Page 32: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Data Report and Operation Logging

Functions: Record history data which can be used for system energy analysis and chart plotting (Offline Data Analysis Tool); Record operators’ actions which can be used for cause checking and performance feedback.

Temp/Flow

Building Cooling Load -

Tons

kW / RT - Chiller 1, 2, 3 & 4

0.00

0.50

1.00

1.50

2.00

2.50

11:43

18:25 1:0

7

7:49

14:31

21:13 3:5

5

10:37

17:19 0:0

1

6:43

13:25

20:07 2:4

9

9:32

16:14

22:56 5:3

8

12:20

19:02 1:4

4

8:26

15:08

21:50 4:3

2

11:14

17:56 0:3

8

7:20

14:02

20:44 3:2

6

10:08

16:50

23:32 6:1

4

12:56

Time

kW / R

TkW/RT - C1 kW/RT - C2 kW/RT - C3 kW/RT - C4

Chiller Efficiency –ikW/ton

Electrical Consumption -

kW

32

Page 33: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Chiller Plant Efficiency Definition

Input Electricity

supply (kW)

Output Cooling in

refrigeration ton (ton)

Chiller Plant Efficiency = Input electricity (ikW)

Output Cooling (ton) = ikW/ton

Example : = 1.20 ikW/ton 120 (ikW) 100 (ton)

Building Cooling Demands

Our objective is to reduce

this Chiller Plant System

Chillers Pumps Cooling towers

33

Page 34: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Chiller Plant Efficiency Benchmarks (Source: ASHRAE Journal)

0.5 (7.0)

0.6 (5.9)

0.7 (5.0)

0.8 (4.4)

0.9 (3.9)

1.0 (3.5)

1.1 (3.2)

1.2 (2.9)

NEEDS IMPROVEMENTFAIRGOODEXCELLENT

AVERAGE ANNUAL CHILLER PLANT EFFICIENCY IN KW/TON (C.O.P.)(Input energy includes chillers, condenser pumps, tower fans and chilled water pumping)

New Technology All-Variable Speed

Chiller Plants

High-efficiency Optimized

Chiller Plants

Conventional Code Based Chiller Plants

Older Chiller Plants

Chiller Plants with Correctable Design or Operational Problems

Based on electrically driven centrifugal chiller plants in comfort conditioning applications with

42F (5.6C) nominal chilled water supply temperature and open cooling towers sized for 85F

(29.4C) maximum entering condenser water temperature and 20% excess capacity.

Local Climate adjustment for North American climates is +/- 0.05 kW/ton

kW/ton C.O.P.

Thomas Hartman, All-variable speed centrifugal chiller plants [J], ASHRAE Journal, 2001, 43(9):43-53.

34

Page 35: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Building Cooling Load Prediction

• Traditional modeling approach using predefined profiles of weather, occupancy, operating schedules, etc. to predict the building cooling load

• They are unable to respond directly to the current weather and building conditions

• Real time building cooling load is impossible by these approaches.

35

Page 36: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Real time Cooling Load Prediction

• Artificial neural network (ANN) model learns the nonlinear correlation between the weather and building conditions and the building cooling load through the historical data of the building systems.

• The prediction can be improved along with time when more and more data of the building systems is fed into the artificial neural network model.

Kwok SSK, Yuen RKK, Lee EWM (2011) An intelligent approach to assessing the effect of building occupancy on building cooling load prediction, Building and Environment 46(8), 1681-1690.

36

Page 37: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Ahead Prediction of Cooling Load

• Ahead prediction can be used for building energy saving (e.g. chiller sequencing, chiller on/off, etc.)

• The application of real-time cooling load

prediction can be applied to system fault diagnosis.

• When the actual cooling load is largely

deviated from the predicted cooling load, it may indicates the abnormality of the building systems.

37

Page 38: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

General ANN Model

Real time cooling load

Temperature

Relative Humidity

Solar irradiance

Occupancy Rate of Office Towers

Landlord power consumption rate

Occupancy Rate of Shopping Mall

Tenants power consumption rate

38

Page 39: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Weather Stations

Pyranometer for measurement of solar irradiance

39

Page 40: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Measurement of Occupancy Rate

Turnstiles at Office Lift Lobbies

People Counting System at Shopping Mall

40

Page 41: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Network Configuration for Cooling Load Prediction

41

Page 42: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Ahead Prediction of Cooling Load

42

Page 43: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Key Factors for Energy Saving of HVAC

Production

Distribution

Demand Prediction

Maintenance

Page 44: Case Studies on Chiller Plant System Energy-saving … · 2015-05-24 · phenomena, resulting in inefficient system performance 5 Secondary chilled water pumps running at fixed speed,

Conclusion

• Adaptive control in comparison with traditional fixed logic chiller plant control

• Advanced intelligent technique in predicting cooling load

• No modification on mechanical parts • Easily applied for existing projects

44