7/29/2019 CASE STUDY OF A MCC SWITCHGEAR PANEL (MOTOR CONTROL CENTRE) TRIPPING DUE TO SHORTED MOTOR.
http://slidepdf.com/reader/full/case-study-of-a-mcc-switchgear-panel-motor-control-centre-tripping-due-to 1/10
REPORT 4: CASE STUDY OF A MCC SWITCHGEAR PANEL (MOTOR
CONTROL CENTRE) TRIPPING DUE TO SHORTED MOTOR.
TABLE OF CONTENT
CHAPTER PAGE
4.1 CASE STUDY OF THE MOTOR 1
4.2 CASE STUDY ON THE SWITCHGEAR PANEL 1
4.3 RECOMMENDATION 9
7/29/2019 CASE STUDY OF A MCC SWITCHGEAR PANEL (MOTOR CONTROL CENTRE) TRIPPING DUE TO SHORTED MOTOR.
http://slidepdf.com/reader/full/case-study-of-a-mcc-switchgear-panel-motor-control-centre-tripping-due-to 2/10
1
4.1 Case study of the motor.
On 9/01/2011, at around 0309hrs the paper stock preparation plant tripped.
Checked at the switchgear room and found the MCC (Motor Control Centre) panel
tripped at the main incoming air circuit breaker (ACB). The breaker tripped with
alarm no.6 indicated on the protection relay (SPAJ 140C), which is the earth fault.
The alarm was acknowledged and the breaker was switched on back. Then all
the motors were started from the control room but at around 0418hrs the MCC panel
tripped again when the faulted motor was started.
Further inspected and found the motor was shorted to earth. The motor
winding measurement was checked and found that the motor stator winding has
shorted to earth. The motor stator winding insulation resistance and the resistanceresult is as below:
The insulation resistance test showed one phase of the stator winding has
shorted to earth.
Insulation Phase to Earth (Mega Ohm) – U: 800 V: 0 W: 500
Insulation Phase to Phase (Mega Ohm) - U-V: 800 V-W: 500 W-U: 500
The winding resistance test showed the winding resistance was also unbalance.
Stator Coil resistance (Low Ohm) - U: 0.124 V: 0.063 W: 0.063
The faulty motor was dismantled and replaced with the spare motor. At
around 0650hrs motor replacement job was completed and tested the motor on the
rotation. The motor running amps was 120A (red phase), 119A (yellow phase), 123A
(blue phase) whereas the full load current of the motor is 143A.
After dismantling the motor, found one of the stator bar at the bottom part of
the motor (in between 2 foot mountings) was broken due to burnt and the paper
insulation was also found damaged. From this evident the suspected root cause is due
to hotspot problem. It was confirmed after performing an IR thermographic analysis
on the motor’s stator core lamination. Please refer to figure 4.1 and 4.2 for the
thermographic results. Further inspected in the motor terminal box, the winding cable
7/29/2019 CASE STUDY OF A MCC SWITCHGEAR PANEL (MOTOR CONTROL CENTRE) TRIPPING DUE TO SHORTED MOTOR.
http://slidepdf.com/reader/full/case-study-of-a-mcc-switchgear-panel-motor-control-centre-tripping-due-to 3/10
2
condition, the cable lug condition and the terminals, all were found in good condition
and no burnt marks.
The upper and side part of the motor was found clean except for the bottom
part of the motor (near to the mounting) was found dirty. From the data collected, it is
suspected the stock which covered the motor fins at the bottom part of the motor,
where the stator bar was found broken which had caused high temperature at that
particular area. The motor insulation was Class F, which the permissible temperature
was 155 degree Celsius.
When the motor continuously operates in this condition, it had caused the
insulation at the area deteriorate rapidly and resulted in insulation failure and lead to
motor burnt. Increasing the temperature by 10°C will reduce the life expectancy of the
insulation into half.
Figure 4.1: Thermal Analysis – Before Rewinding
7/29/2019 CASE STUDY OF A MCC SWITCHGEAR PANEL (MOTOR CONTROL CENTRE) TRIPPING DUE TO SHORTED MOTOR.
http://slidepdf.com/reader/full/case-study-of-a-mcc-switchgear-panel-motor-control-centre-tripping-due-to 4/10
3
Figure 4.2: Thermal Analysis – After Rewinding
4.2 Case Study on Switchgear Panel.
Referring to the insulation resistance measurement the motor’s stator ‘V’
windings has the lowest resistance value when measured with respect to earth. The
‘V’ phase winding which failed on the insulation has caused the ‘V’ phase winding to
be shorted to the stator core. The stator core is physically connected to the motor
frame which has been terminated to the earth.
The MCC panel cabling arrangement and protection co-ordination are well
explained in Figure 3. From the incident on 9/1/2010 the earth fault current from the
motor has triggered the protection relay to trip the main incoming Air Circuit Breaker
which consequently shuts off the entire panel. An earth fault current of 29% was
recorded on the relay. The 29% of earth fault current would yield around 1160A from
the existing earth fault protection setting. The calculation is as shown below.
29
1004000 ) =
7/29/2019 CASE STUDY OF A MCC SWITCHGEAR PANEL (MOTOR CONTROL CENTRE) TRIPPING DUE TO SHORTED MOTOR.
http://slidepdf.com/reader/full/case-study-of-a-mcc-switchgear-panel-motor-control-centre-tripping-due-to 5/10
4
The protection relay is an IDMT type of relay and configured to be a standard
inverse tripping curve characteristics. Figure 4 shows the typical time current curve
for a standard inverse IDMT curve. Based from the previous relay calibration settings,
the earth fault current was set for 15% which yields 600A and the time multiplier was
set for 0.1 whereas for the over-current, it was set for 87% which yields 3480A and
the time multiplier was set for 0.1. Both the calculation is as shown below.
15
1004000 ( ) =
87
100
4000 ( ) =
It can also be noted from the curve, for a current level of 1.93 which is the
ratio between the fault current level (1160A) and relay earth fault current setting
(600A), the tripping time would be approximately between 1.0 to 1.1 seconds from
the curve for TMS of 0.1. However for more accuracy, the tripping time could be
determined by using the standard inverse relay characteristics equation. The equation
is as stated below.
= 0.14
(
). 1
From the equation, for an earth fault current of 1160A, the time taken for the
air circuit breaker to trip is 1.054 seconds. Although the motor is protected by an
individual branch MCCB, yet from its time-current curve characteristics, the time that
will be taken for the MCCB to trip is from 30s to 300s. Referring to the time current
curve of the MCCB in figure 5, for a current rate of 1160A the MCCB is still in the
thermal characteristics region.
7/29/2019 CASE STUDY OF A MCC SWITCHGEAR PANEL (MOTOR CONTROL CENTRE) TRIPPING DUE TO SHORTED MOTOR.
http://slidepdf.com/reader/full/case-study-of-a-mcc-switchgear-panel-motor-control-centre-tripping-due-to 6/10
5
The thermal characteristics of a MCCB are also referred as a slow response
region. Most of the times, the upstream relay settings had been chosen by considering
the time grading co-ordination with the downstream breaker. However, in our case the
experience has shown that there has been a total lack of earth fault protection co-
ordination. The upstream breaker tends to trip in 1.054s for a fault level of 1160A
whereas the downstream breaker will take 20s to 300s to trip for the same fault
current level. Numerous incidents have been reported where breakers have tripped in
an uncoordinated manner leading extensive plant disruption causing longer down
times and extended restoration time.
7/29/2019 CASE STUDY OF A MCC SWITCHGEAR PANEL (MOTOR CONTROL CENTRE) TRIPPING DUE TO SHORTED MOTOR.
http://slidepdf.com/reader/full/case-study-of-a-mcc-switchgear-panel-motor-control-centre-tripping-due-to 7/10
6
Figure 4.3: Normal inverse-time characteristics of the Over-current and earth-fault
unit SPCJ 4D29.
If = 1.93
7/29/2019 CASE STUDY OF A MCC SWITCHGEAR PANEL (MOTOR CONTROL CENTRE) TRIPPING DUE TO SHORTED MOTOR.
http://slidepdf.com/reader/full/case-study-of-a-mcc-switchgear-panel-motor-control-centre-tripping-due-to 8/10
7
Figure 4.4: Time Current characteristics of SN250 ABB MCCB.
If = 1.93
7/29/2019 CASE STUDY OF A MCC SWITCHGEAR PANEL (MOTOR CONTROL CENTRE) TRIPPING DUE TO SHORTED MOTOR.
http://slidepdf.com/reader/full/case-study-of-a-mcc-switchgear-panel-motor-control-centre-tripping-due-to 9/10
8
`
Figure 4.5: MCC protection co-ordination.
Air Circuit Breaker
Make = OttermillRated voltage = 500VRated Current = 4000A
Breaking Capacity = 50kA
ProtectionRelay
Protection RelayMake = ABBModel = SPAJ 140CType = Standard InverseOver-Current setting =87%
Earth Fault setting = 15%
MCC1 transformer
Power = 2500kVAVoltage Ratio = 6.6/0.415 kV
Current Transformer
Ratio = 4000/5 A
MCCB
Make = ABBRated Voltage = 440V
Rated Current = 250ABreaking Capacity = 35kA
Motor
Fault Current =1160A
Earthing bond at MCC panel
M
7/29/2019 CASE STUDY OF A MCC SWITCHGEAR PANEL (MOTOR CONTROL CENTRE) TRIPPING DUE TO SHORTED MOTOR.
http://slidepdf.com/reader/full/case-study-of-a-mcc-switchgear-panel-motor-control-centre-tripping-due-to 10/10
9
4.3 Recommendation
Faults, which occur within the motor windings, are mainly earth faults and
phase to phase faults caused by breakdown in the winding insulation. The earth faults
can be very easily detected by means of an instantaneous earth fault relays, usually
with a setting of approximately 500mA which is connected to the zero current
transformer. The advantageous of earth fault relay are generally no need for time
delay as there isn’t any downstream protection. The sensitivity is also considered to
avoid nuisance tripping and the input to the relay is from a zero current transformer
(ZCT). The typical connection for an earth fault motor protection is shown below.
Figure 4.6: MCC protection co-ordination.