Section J Selection Guide ................................... J-2 MicroSmart PLCs • CPU Modules . . . . . . . . . . . . . . . . . J-3 • Expansion Modules . . . . . . . . . . . J-10 • Dimensions and Specifications . .J-16 OpenNet Controller • ONC . . . . . . . . . . . . . . . . . . . . . . . J-23 • Interbus . . . . . . . . . . . . . . . . . . . . . J-51 • DeviceNet . . . . . . . . . . . . . . . . . . . J-61 • LONWorks . . . . . . . . . . . . . . . . . . J-71 Original Micro PLCs • Micro 3 and Micro 3 C. . . . . . . . . . . J-81 Other PLCs • Micro-1. . . . . . . . . . . . . . . . . . . . . J-99 • FA2J . . . . . . . . . . . . . . . . . . . . . . J-101 • FA3S. . . . . . . . . . . . . . . . . . . . . . J-103 Programming Software • WindLDR™ . . . . . . . . . . . . . . . . J-105 Programmable Logic Controllers
Transcript
Page 1: CATALOGO DE PLCS IDEC

Section

J

Selection Guide...................................J-2

MicroSmart PLCs

• CPU Modules . . . . . . . . . . . . . . . . .J-3• Expansion Modules . . . . . . . . . . .J-10• Dimensions and Specifications . .J-16

OpenNet Controller

• ONC . . . . . . . . . . . . . . . . . . . . . . .J-23• Interbus. . . . . . . . . . . . . . . . . . . . .J-51• DeviceNet. . . . . . . . . . . . . . . . . . .J-61• LONWorks . . . . . . . . . . . . . . . . . .J-71

Original Micro PLCs

• Micro

3

and Micro

3

C. . . . . . . . . . .J-81

Other PLCs

• Micro-1. . . . . . . . . . . . . . . . . . . . .J-99• FA2J . . . . . . . . . . . . . . . . . . . . . .J-101• FA3S. . . . . . . . . . . . . . . . . . . . . .J-103

Programming Software

• WindLDR™ . . . . . . . . . . . . . . . .J-105

Program

mable Logic Controllers

Page 2: CATALOGO DE PLCS IDEC

Programmable Logic Controllers

Selection Guide

J-2

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

IDEC, a pioneer in the micro-PLC market, is proud to offer so many quality micro programmable logic controllers, from the original Micro-1 to the brand new MicroSmart series. Not all information about our older PLCs has been included in this catalog. Please refer to previous catalogs or call IDEC Technical Support with any questions.

Series Appearance Specifications Page

MicroSmart

2 types of CPU modules4 types of Expansion modules J-3

ONC

Available with SX5 Smart I/O modules to communicate with Interbus, DeviceNet, and LONWorks

J-23

Micro

3

and Micro

3

C

J-81

Micro-1

The original micro-PLC J-99

FA2J

Flat-Pak Modular J-101

FA3S

J-103

WindLDR

Software for programming all of IDEC’s PLCs J-105

Selection Guide

NEW!

NEW!

Page 3: CATALOGO DE PLCS IDEC

Programmable Logic Controllers

MicroSmart Series

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-3

J

CE Certified

The Next Generation of PLC

Key features of the MicroSmart series include:

• 10, 16, or 24 I/O All-in-one type CPU modules with Sink/Source DC input and Relay Output

• 20 I/O Slim type CPU modules with Sink/Source DC input and Transistor Sink or Source Output

• 20 I/O Slim type CPU modules with Sink/Source DC input and Relay Output with high-speed Transistor Sink or Source Output

• 40 I/OSlim type CPU module with Sink/Source DC input and Transistor Sink or Source Output

• DC Input, Relay Output, Transistor Output, Combination I/O and Analog I/O expansion modules available

• 24 I/O All-in-one CPU expandable to 88 I/O points; 20 I/O slim types expandable up to 148 or 244 I/O; 40 I/O slim type expandable up to 264 I/O points

• Standard RS232 port, optional plug-in RS485/RS232 port• Optional memory cartridge or real-time clock and calendar

cartridge• Data link to other MicroSmart modules, PLCs, PCs or HG

series operator interfaces• UL1604 approved for Class 1–Div. 2 hazardous locations• Compact size

UL ListedFile No. E211795

MicroSmart

CPU MODULES

INPUTMODULES

COMBINATION I/O MODULES

OUTPUT MODULES

Page 4: CATALOGO DE PLCS IDEC

Programmable Logic Controllers

MicroSmart Series

J-4

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Part Numbers: MicroSmart

Item Description Part Number

CPU modules

10 I/O All-in-one Type

FC4A-C10R2

16 I/O All-in-one Type

FC4A-C16R2

24 I/O All-in-one Type

FC4A-C24R2

20 I/O Slim Type, Transistor Sink Output

FC4A-D20KS

20 I/O Slim Type, Transistor Source Output

FC4A-D20S3

20 I/O Slim Type, Relay Sink Output

FC4A-D20RK1

20 I/O Slim Type, Relay Source Output

FC4A-D20RS1

40 I/O Slim Type, Transistor Sink Output

FC4A-D40K3

40 I/O Slim Type, Transistor Source Output

FC4A-D40S3

Input Modules

8-point 24V DC Input, Removable Terminal Block

FC4A-N08B1

16-point 24V DC Input, Removable Terminal Block

FC4A-N16B1

16-point 24V DC Input, MIL Connector

FC4A-N16B3

32-point 24V DC Input, MIL Connector

FC4A-N32B3

Output Modules

8-point Relay Output, Removable Terminal Block

FC4A-R081

16-point Relay Output, Removable Terminal Block

FC4A-R161

8-point Transistor Sink Output, Removable Terminal Block

FC4A-T08K1

8-point Transistor Source Output, Removable Terminal Block

FC4A-T08S1

16-point Transistor Sink Output, MIL Connector

FC4A-T16K3

16-point Transistor Source Output, MIL Connector

FC4A-T16S3

32-point Transistor Sink Output, MIL Connector

FC4A-T32K3

32-point Transistor Source Output, MIL Connector

FC4A-T32S3

Combination I/O Modules4-point 24V DC Input, 4-point Relay Output

FC4A-M08BR1

16-point 24V DC Input, 8-point Relay Output

FC4A-M24BR2

Analog I/O Modules

2-point DC Input, 1-point DC Output

FC4A-L03A1

2-point Thermocouple Resistance Input, 1-point DC Output

FC4A-L03AP1

2-point DC Input

FC4A-J2A1

1-point DC Output

FC4A-K1A1

Programming Software WindLDR 4.10

FC9Y-LP2CDW

HMI Module For displaying and changing required operands

FC4A-PH1

HMI Base Module For mounting HMI module with Slim type CPU module

FC4A-HPH1

ANALOG MODULES HMI MODULE MEMORY CARTRIDGE

CLOCK CARTRIDGE

COMMUNICATION ADAPTERS

Page 5: CATALOGO DE PLCS IDEC

Programmable Logic Controllers

MicroSmart Series

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-5

J

Part Numbers: MicroSmart Options

Description Part Number

RS232C Communication Adapter (mini DIN type)

FC4A-PC1

RS485 Communication Adapter (mini DIN type)

FC4A-PC2

RS485 Communication Adapter (screw terminal type)

FC4A-PC3

RS232C Communicator Adapter for Slim Type CPU (mini DIN type)

FC4A-HPC1

RS485 Communication Adapter for Slim Type CPU (mini DIN type)

FC4A-HPC2

RS485 Communication Adapter for Slim Type CPU (terminal block type)

FC4A-HPC3

Clock Cartridge

FC4A-PT1

Memory Cartridge (32KB)

FC4A-PM32

RS232C/RS485 Converter (modem connectable)

FC2A-MD1

26-position Connector Socket, MIL Connector for Slim Type CPU (package quantity: 2)

FC4A-PMC26P

26-position Connector Socket, MIL Connector for I/O Modules (package quantity: 2)

FC4A-PMC20P

10-position Terminal Blocks for I/O Modules (package quantity: 2)

FC4A-PMT10P

11-position Terminal Blocks for I/O Modules (package quantity: 2)

FC4A-PMT11P

13-position Terminal Blocks for Slim Type CPU Modules FC4A-D20RK1 and FC4A-D20RS1 (package quantity: 2)

FC4A-PMT13P

16-position Terminal Blocks for Slim Type CPU Module FC4A-D20RK1 (package quantity: 2)

FC4A-PMTK16P

16-position Terminal Blocks for Slim Type CPU Module FC4A-D20RS1 (package quantity: 2)

FC4A-PMTS16P

Analog Voltage Input Cable - 1m (3.28 ft)

FC4A-PMAC2P

Computer LInk Cable 4C - 3m (9.84 ft.)

FC4A-KC4C

Modem Cable 1C - 3m (9.84 ft.)

FC2A-KM1C

RS232C Cable (4-wire) - 1.5m (4.92 ft.)

HD9Z-C52

PLC to IDEC’s HG series Connection Cable - 3m (9.84 ft.) (for 2nd RS232 port only)

HG9Z-XC183

User Communication Cable 1C - 2.4m (7.87 ft.)

FC2A-KP1C

O/I Communication Cable IC - 5m (16.4 ft)

FC4A-KC1C

O/I Communication Cable 2C - 5m (16.4 ft)

FC4A-KC2C

Direct Mounting Strips (package quantity: 2)

FC4A-PSP1P

35mm DIN Rails (aluminum, 1m)

BNDN1000BAA1000

Mounting Clips

BNL6

Screwdriver (3.5)

FC9Z-SD1

Screwdriver (2.5)

FC9Z-SD2

14-point input switch simulator

FC4A-DS824-SW14

9-point input switch simulator

FC4A-DS824-SW9

6-point input switch simulator

FC4A-DS824-SW6

I/O Cables

20-wireShielded 2 m FC9Z-H200A20

Non-shielded 2 m FC9Z-H200B20

26-wireShielded 2 m FC9Z-H200A26

Non-shielded 2 m FC9Z-H200B26

MicroSmart Starter Kit with FC4A-C10R2, WindLDR 4.10, cables, simulator switch, screwdrivers, manual

MM-SMART-10

MicroSmart Starter Kit with FC4A-C16R2, WindLDR 4.10, cables, simulator switch, screwdrivers, manual

MM-SMART-16

MicroSmart Starter Kit with FC4A-C24R2, WindLDR 4.10, cables, simulator switch, screwdrivers, manual

MM-SMART-24

Page 6: CATALOGO DE PLCS IDEC

Programmable Logic Controllers

MicroSmart Series

J-6

www.idec.com

USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

* CPU module power consumption includes 250 mA sensor power.** CPU module (including 250 mA sensor power) + 4 I/O modules# CPU module + 7 I/O modules

Communication Port 1 Specifications

FC4A-C10R2 FC4A-C16R2 FC4A-C24R2 FC4A-D20K3FC4A-D20S3

FC4A-D20RK1FC4A-D20RS1

FC4A-D40KSFC4A-D40S3

CPU

Gen

eral

Spe

cific

atio

ns

Rated Voltage

100-240V AC 24V DC

Allowable Range

85-264V AC 20.4 to 26.4V DC (including ripple)

Rated Frequency

50/60 Hz (47-63 Hz) —

Maximum Input Current

0.25A (85V AC) 0.30A (85V AC) 0.45A (85V AC) ** 0.56A (26.4V DC) # 0.70A (26.4V DC) #

Max. Power Consumption

30VA/264V AC *20VA/100V AC

31VA/264V AC *22VA/100V AC

40VA/264V AC **33VA/100V AC 15W/26.4V DC # 19W/26.4V DC #

Allowable Momentary Power Interruption

20 msec maximum, Level PS-2 (IEC61131) 10 msec (at 24V DC)

Dielectric Strength

Between power and terminal: 1500V AC, 1 minBetween I/O and terminal: 1500V AC, 1 min

Between power and terminal: 500V AC, 1 minBetween I/O and terminal: 1500V AC, 1 min

Insulation Resistance

Between power and terminal: 10 m

Ω

(min), 500V DCBetween I/O and terminal: 10 m

Ω

(min), 500V DCBetween power and terminal: 10 m

Ω

(min)Between I/O and terminal: 10 m

Ω

(min)

Noise Resistance

AC power terminal: 1.5 kV, 50ns to 1µsI/O terminal (coupling clamp): 1.5 kV, 50ns to 1µs

DC power terminals: 1.0 kV, 50 nsec to 1µsecI/O terminals (coupling clamp): 1.5 kV, 50 nsec to 1µsec

Inrush Current

35A max. 35A max. 40A max. 50A maximum (24V DC)

Power Supply Wire UL1015, AWG22, UL1007, AWG18

Operating Temperature 0 to 55°C

Storage Temperature –25 to +70°C

Operating Humidity 30-95% Level RH1 (no condensation)

Altitude Operation: 0 to 2,000m (0 to 6,595 ft)Transport: 0 to 3,000m (0 to 9.840 ft)

Pollution Degree 2 (IEC60664)

Corrosion Immunity Free from corrosive gases

Degree of Protection IP20

Ground Grounding resistance 100Ω maximum

Vibration Resistance DIN rail mounted: 10 to 57Hz / amplitutde 0.075mm, 57 to 150Hz / acceleration 9.8m/s2 (1G)Direct mounted: 2 to 25Hz / amplitude 1.6mm, 25 to 100Hz / acceleration 39.2m/s2 (4B) in each of 3 axes

Shock Resistance 15G, 11ms, 3 shocks in each of 3 axes

Standards EIA RS232C

Maximum Baud Rate 19200 bps

Maintenance Communication Possible

User Communication Possible

Modem Communication Not possible

Data Link Communication Not possible

Cable Special Cables: FC2A-KC4C, FC2A-KP1C, FC4A-KC1C, FC4A-KC2C

Isolation between Internal Circuit and Communication Port Not isolated

Page 7: CATALOGO DE PLCS IDEC

Programmable Logic Controllers MicroSmart Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-7

J

FC4A-C10R2 FC4A-C16R2 FC4A-C24R2 FC4A-D20K3FC4A-D20S3

FC4A-D20RK1FC4A-D20RS1

FC4A-D40KSFC4A-D40S3

CPU

Fun

ctio

n Sp

ecifi

catio

ns

Control System Stored program system

Instruction words35 basic instructions

38 advanced 40 advanced 46 advanced 53 advanced 70 advanced

Program Capacity 4,800 bytes(800 steps)

15,000 bytes(2,500 steps)

27,000 bytes(4,500 steps)

27,000 bytes(4,500 steps)

31,200 bytes(5,200 steps)

Calculated 6 bytes per step

User ProgramStorage Internal EEPROM, Memory cartridge (option: EEPROM)

Processing Time Basic instruction: 1.65 msec (1000 steps); END processing: 0.64 msec (does not include expansion I/O service, clock function processing, data link processing and interrupt processing)

Expandable I/O Modules – – 4 modules 7 modules

RAM Backup

Backup Data: Internal relay, shift register, counter, data registerBackup Duration: Approx. 30 days (typical) at 25° C after backup battery fully chargedBattery: Lithium secondary batteryCharging Time: Approx. 15 hours for charging from 0% to 90% of full chargeBattery Life: 5 yearsReplaceability: Impossible to replace battery

I/O Points 6 input, 4 output 9 input, 7 output 14 input, 10 outputExpansion: 64 I/O

12 input, 8 outputExpansion: 128 I/O

12 intput, 8 outputExpansion: 224 I/O

24 input, 16 outputExpansion: 224 I/)

Internal Relay 256 1024

Shift Register 64 128

Data Register 400 1300

Expansion Data Register — 6000

Counter 32 100

Timer (1-sec, 100-msec, 10-msec, 1-msec)

32 100

Self-Diagnostic Function

Power failure check, watchdog timer, data link connection, user program EEPROM sum check, timer/counter preset value sum check, user program RAM sum check, keep data, user program syntax, user program writing, CPU module, clock IC, I/O bus initialize, user program execution

Input Filter 3 to 15 msec (1-msec increments)

Catch Input/Interrupt Input 4 input (I2 through I5) Minimum turn on pulse width: 40 µsec maximum Minimum turn off pulse width: 150 µsec maximum

High-Speed Counter

Total 4 points: Single/two-phase selectable: 20kHz (1 point)Single-phase: 5kHz (3 points)

Total 4 points: Single/two-phase selectable: 20kHz (2 points)Single-phase: 5kHz (2 points)

Counting Range 0 to 65535 (16 bits), Operation Mode: Rotary encoder mode and adding counter mode

AnalogPotentiometer

1 point 2 points 1 point

Data Range: 0 to 255

Analog Voltage Input — 1 point, 0 to 10V DC Input Voltage Range, approx. 100kΩ Input

Impedance, data range 0-255 (8 bit)

Pulse Output — 2 points, max. frequency 20kHz

Sensor PowerSupply

24V DC (+10% to -15%), 250 mA, no overload detectionIsolated from the internal circuit —

Port 1 RS232C Maintenance Communication, User Communication, Modem Communication

Port 2 (optional) — Possible: RS232C or RS485 (Maintenance communication, data link)

Clock Function (optional) Possible

Select either clock or memory cartridge

PossibleYear, month, day, day of week, hour, minute, second

Memory Cartridge (optional) Possible

HMI Module (optional) Possible Possible using HMI Base Module

Page 8: CATALOGO DE PLCS IDEC

Programmable Logic Controllers MicroSmart Series

J-8 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

DC Input Specifications for CPU modules

FC4A-C10R2 FC4A-C16R2 FC4A-C24R2 FC4A-D20K3FC4A-D20S3

FC4A-D20RK1FC4A-D20RS1

FC4A-D40KSFC4A-D40S3

Rated Input Voltage 24V DC (both sink and source)

Allowable Range 20.4 to 28.8V DC 20.4 to 26.4V DC

Rated Input Current I0, I1: 11mA, I2 to I7, I10 to I15: 7mA I0, I1, I6, I7: 5mA/point, I2 to I5, I10 to I27: 7mA/point

Input Impedance I0, I1: 2.1kΩ, I2 to I7, I10 to I15: 3.4kΩ I0, I1, I6, I7: 5.7kΩ, I2 to I5, I10 to I27: 3.4kΩ

OFF/ON TimeOFF/ON I0 to I5: 35µsec + Filter Value

I6, I7, I10 to I15: 40µsec + Filter ValueI0 to I7: 35µsec + Filter ValueI10 to I27: 40µsec + Filter Value

ON/OFF I0, I1: 45µsec + Filter ValueI2 to I7, I10 to I15: 150µsec + Filter Value

I0, I1, I6, I7: 45µsec + Filter ValueI2 to I5, I10 to I27: 150µsec + Filter Value

Input Points 6 inputs6/1 common

9 inputs9/1 common

14 inputs 14/1 common

12 inputs12/1 common

12 inputs12/1 common

24 inputs,12/1 common

ConnectorOn Mother Board —

FL26A2MA (Oki Electric Cable)

MC1.5/13-G-3.81BK(Phoenix Contact)

FL26A2MA(Oki Electric Cable)

Insertion/Removal Durability — 100 times minimum

Isolation Between input terminals: Not isolatedInternal circuit: Photocoupler isolated

Input Type Type 1 (IEC61131)

External Load for I/O Interconnection Not needed

Signal Determination Method Static

Effect of Improper Input Connection Both sinking and sourcing input signals can be connected. If any input exceeding the rated value is applied, permanent damage may be caused.

Cable Length 3m (9.84 ft)

Relay Output Specifications for CPU modules

FC4A-C10R2 FC4A-C16R2 FC4A-C24R2 FC4A-D20RK1FC4A-D20RS1

Output Points 4 points 7 points 10 points 8 points

Output Points per Common

COM0 3 points 4 points 4 points 2 points(transistor output)

COM1 1 point 2 points 4 points 3 points

COM2 – 1 point 1 point 2 points

COM3 – – 1 point 1 point

Type of Output 1NO

Maximum Load Current 1 point 2A

Common 8A

Minimum Switching Load 0.1mA, 0.1V DC (reference value)

Initial Contact Resistance 30mΩ maximum

Electrical Life 100,000 operations (rated load) @ 1,800 operations/hr

Mechanical Life 200,000 operations (no load) @ 18,000 operations/hr

Rated Load Current (resistive/inductive) 240V AC/2A, 24V DC/2A (30V DC / 2A)

Dielectric StrengthBetween output and terminals: 1500V AC, 1 minute

Between output terminals and internal circuit: 1500V AC, 1 minuteBetween output terminals (COMs): 1500 V AC, 1 minute

Connector

On Mother Board — MC1.5/16-G-3.81BK

(Phoenix Contact)

Insertion/Removal Durability

— 100 times minimum

Page 9: CATALOGO DE PLCS IDEC

Programmable Logic Controllers MicroSmart Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-9

J

Transistor Sink and Source Output Specifications for CPU modules

FC4A-D20K3FC4A-D20S3

FC4A-D20RK1FC4A-D20RS1

FC4A-D40K3FC4A-D40S3

Output Points and Common Line 8 points, 8/1 common 2 points, 2/1 common 16 points, 8/1 common

Type of Output FC4A-D20K3/D20RK1/D40K3 = Sink OutputFC4A-D20S3/D20RS1/D40S3 = Source Output

Rated Load Voltage 24V DC

Operating Load Voltage Range 20.4 to 28.8V DC

Rated Load Current 0.3A per output point

Maximum Load Current 1A per common line

Voltage Drop (ON Voltage) 1V maximum (voltage between COM and output terminals when output is on)

Inrush Current 1A maximum

Leakage Current 0.1 mA maximum

Clamping Voltage 39V±1V

Maximum Lamp Load 8W

Inductive Load L/R = 10ms (28.8V DC, 1Hz)

External Current Draw 100mA maximum, 24V DC (power voltage at the +V or -V terminal)

Isolation Between output terminal and internal circuit: Photocoupler isolatedBetween output terminals: Not isolated

ConnectorOn Mother Board FL26A2MA

(Oki Electric Cable)MC1.5/16-G-3.81BK(Phoenix Contact)

FL26A2MA(Oki Electric Cable)

Insertion/Removal Durability 100 times minimum

Output DelayTurn ON time 5 µs (Q0, Q1), 300 µs max (Q2 to Q7, Q10 to Q17)

Turn OFF time 5 µs (Q0, Q1), 300 µs max (Q2 to Q7, Q10 to Q17)

Page 10: CATALOGO DE PLCS IDEC

Programmable Logic Controllers MicroSmart Series

J-10 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

DC Input Module Specifications

Relay Output Module Specifications

FC4A-N08B1 FC4A-N16B1 FC4A-N16B3 FC4A-N32B3

Input Points 8 points (8/1 common) 16 points (16/1 common) 32 points (16/1 common)

Rated Input Voltage 24V DC sink/source input signal

Input Voltage Range 20.4 to 28.8V DC

Rated Input Current 7mA/point (24V DC) 5mA/point (24V DC)

Input Impedance 3.4 kΩ 4.4 kΩ

Input Delay Time (24V DC) ON time: 4 msecOFF time: 4 msec

Isolation Between input terminals: Not isolatedInternal circuit: Photocoupler isolated

External Load for I/O Interconnection Not needed

Signal Determination Method Static

Effect of Improper Input Connection Both sinking and courcing input signals can be connected. If any input exceeding the rated value is applied, permanent damage may be caused.

Cable Length 3m (9.84 ft) in compliance with electromagnetic immunity

ConnectorOn Mother Board MC1.5/10-G-3.81BK (Phoenix contact) FL20A2MA (Oki Electric Cable)

Insertion/Removal Durability 100 times minimum

Internal Current Draw

All Inputs ON 25 mA (5V DC)0 mA (24V DC)

40 mA (5V DC)0 mA (24V DC)

35 mA (5V DC)0 mA (24V DC)

65 mA (5V DC)0 mA (24V DC)

All Inputs OFF 5 mA (5V DC)0 mA (24V DC)

5 mA (5V DC)0 mA (24V DC)

5 mA (5V DC)0 mA (24V DC)

10 mA (5V DC)0 mA (24V DC)

Weight 85g 100g 65g 100g

FC4A-R08B1 FC4A-R16B1

Output Points and Common Lines 8 points (4/1 common) 16 points (8/1 common)

Output Type 1NO

Maximum Load Currentper point 2A

per common 7A 8A

Minimum Switching Load 0.1 mA/0.1V DC (reference value)

Initial Contact Resistance 30 mΩ maximum

Electrical Life 100,000 operations minimum(rated load 1,800 operations/hour)

Mechanical Life 20,000,000 operations minimum(no load 18,000 operations/hour)

Rated Load (resistive/inductive) 240V AC/2A, 30V DC/2A

Dielectric StrengthBetween output and terminals: 1500V AC, 1 minute

Between output terminals and internal circuit: 1500V AC, 1 minuteBetween output terminals (COMs): 1500 V AC, 1 minute

ConnectorOn Mother Board MC1.5/11-G-3.81BK

(Phoenix contact)MC1.5/10-G-3.81BK(Phoenix contact)

Insertion/Removal Durability 100 times minimum

Internal Current DrawAll Inputs ON 30 mA (5V DC)

40 mA (24V DC)45 mA (5V DC)

75 mA (24V DC)

All Inputs OFF 5 mA (5V DC)0 mA (24V DC)

5 mA (5V DC)0 mA (24V DC)

Weight 110g 145g

Specifications — Expansion Modules

Page 11: CATALOGO DE PLCS IDEC

Programmable Logic Controllers MicroSmart Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-11

J

Transistor Output Module Specifications

FC4A-T08K1FC4A-T08S1

FC4A-T16K3FC4A-T16S3

FC4A-T32K3FC4A-T32S3

Output Points 8 points (8/1 common) 16 points (16/1 common) 32 points (16/1 common)

Output Type FC4A-TK: Transistor sink outputFC4A-TS: Transistor source output

Rated Load Voltage 24V DC

Operating Load Voltage Range 20.4 to 28.8V DC

Rated Load Current 0.3A per output point (at 28.8V DC) 0.1A per output point (at 28.8V DC)

Maximum Load Currentper point 0.36A (at28.8V DC) 0.12A (at 28.8V DC)

per common 3A (at 28.8V DC) 1A (at 28.8V DC)

Voltage Drop (ON Voltage) 1V maximum (between COM and output terminals when output is on)

Inrush Current 1A maximum

Leakage Current 0.1A maximum

Clamping Voltage 39V ± 1V

Maximum Clamping Load 8W

Inductive Load L/R = 10 msec (DC 28.8V, 1Hz)

External Current Draw FC4A-TK: 100mA maximum, 24V DC (power voltage at the +V)FC4A-TS: 100mA maximum, 24V DC (power voltage at the -V)

Isolation Between output terminal and internal circuit: Photocoupler isolatedBetween output terminals: Not isolated

Connector

Type (on Mother Board)

MC1.5/10-G-3.81BK (Phoenix contact) FL20A2MA (Oki Electric Cable)

Insertion/Removal Durability 100 times minimum

Internal Current DrawAll Inputs ON 10mA (5V DC)

20mA (24V DC)10mA (5V DC)

40mA (24V DC)20mA (5V DC)

70mA (24V DC)

All Inputs OFF 5mA (5V DC)0mA (24V DC)

5mA (5V DC)0mA (24V DC)

10mA (5V DC)0mA (24V DC)

Output DelayTurn ON time 300µsec maximum

Turn OFF time 300µsec maximum

Weight 85g 70g 105g

Page 12: CATALOGO DE PLCS IDEC

Programmable Logic Controllers MicroSmart Series

J-12 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Combination I/O Module Specifications

FC4A-M08BR1 FC4A-M24BR2

DC

Inpu

t Spe

cific

atio

ns

Input Points 4 points (4/1 common) 16 points (16/1 common)

Rated Input Voltage 24V DC sink/source input signal

Input Voltage Range 20.4 to 28.8V DC

Range Input Current 7 mA/point (24V DC)

Input Impedance 3.4 kΩ

Turn ON Time 4 msec (24V DC)

Turn OFF Time 4 msec (24V DC)

Isolation Between input terminals: Not isolatedInternal circuit: Photocoupler isolated

External Load for I/O Interconnection Not needed

Signal Determination Method Static

Effect of Improper Input Connection Both sinking and sourcing input signals can be connected. If any input exceeding the rated value is applied, permanent damage may be caused.

Cable Length 3m (9.84 ft) in compliance with electromagnetic immunity

Rela

y O

utpu

t Spe

cific

atio

ns

Output Points 4 points (4/1 common) 8 points (8/1 common)

Output Type 1NO

Maximum Load Currentper point 2A

per common 7A

Minimum Switching Load 0.1 mA/0.1V DC (reference value)

Initial Contact Resistance 30 mΩ maximum

Electrical Life 100,000 operations minimum (rated load 1,800 operations/hour)

Mechanical Life 20,000,000 operations minimum (no load 18,000 operations/hour)

Rated Load (resistive/inductive) 240V AC/2A, 30V DC/2A

Dielectric StrengthBetween output and or terminals: 1,500V AC, 1 minute

Between output terminal and internal circuit: 1,500V AC, 1 minuteBetween output terminal (COMs): 1,500V AC, 1 minute

Connectoron Mother Board MC1.5/11-G-3.81BK

(Phoenix contact)Input: F6018-17P (Fujicon)

Output: F6018-11P (Fujicon)

Insertion/Removal Durability 100 times minimum —

Internal Current DrawAll Inputs ON 25 mA (5V DC)

20 mA (24V DC)65 mA (5V DC)

45 mA (24V DC)

All Inputs OFF 5 mA (5V DC)0 mA (24V DC)

10 mA (5V DC)0 mA (24V DC)

Weight 95g 140g

Page 13: CATALOGO DE PLCS IDEC

Programmable Logic Controllers MicroSmart Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-13

J

Analog I/O Module Specifications

Analog Output Specifications

FC4A-L03A1 FC4A-L03AP1 FC4A-J2A1 FC4A-K1A1

Input Points 2 2 2 —

Input Signal TypeVoltage Input (0 to 10V DC)Current Input

(4 to 20 mA DC)

Thermocouple Resistance

Thermometer

Voltage Input (0 to 10V DC)Current Input

(4 to 20 mA DC)—

Output Points 1 1 — 1

Output Signal TypeVoltage Output(0 to 10V DC)

Current Output (4 to 20 mA DC)

Voltage Output (0 to 10V DC)

Current Output (4 to 20 mA DC)

—Voltage Output (0 to 10V DC)

Current Output (4 to 20 mA DC)

Rated Power Voltage 24V DC

Allowable Voltage Range 20.4 to 28.8V DC

ConnectorOn Mother Board MC1.5/11-G-3.81BK (Phoenix contact)

Insertion/Removal Durability 100 times minimum

Internal Current Draw

Internal Power 50 mA (5V DC)0 mA (24V DC)

50 mA (5V DC)0 mA (24V DC)

50 mA (5V DC)0 mA (24V DC)

50 mA (5V DC)0 mA (24V DC)

External Power 40 mA (24V DC) 40 mA (24V DC) 40 mA (24V DC) 40 mA (24V DC)

Weight 85g

FC4A-L03A1, FC4A-L03AP1, FC4A-K1A1

Output Signal Type Voltage Output Current Output

Output Range 0 to 10V DC 4 to 20 mA DC

Load Impedance 2 kΩ minimum 300Ω maximum

Applicable Load Type Resistive load

Setting Time 20 msec

Total Output System Transfer Time 20 msec + 1 scan time

Output Error

Maximum Error at 25°C ±0.2% of full scale

Temperature Coefficient ±0.015% of full scale/°C

Repeatabliity after Stabilization Time ±0.5% of full scale

Output Voltage Drop ±1% of full scale —

Non-lineality ±0.2% of full scale

Output Ripple 1 LSB maximum

Overshoot 0%

Total Error ±1% of full scale

Data

Digital Resolution 4096 increments (12 bits)

Output Value of LSB 2.5 mV 4 µA

Data Type in Application Program 0 to 4095 (12-bit data); -32768 to 32767 (optional range designation)See note on page J-14

Monotonicity Yes

Current Loop Open — Detectable (See note on page J-14)

Noise

Maximum Termporary Deviation during Electrical Noise Tests ±3% max. when a 500V clamp is applied to the power and I/O wiring

Cable Twisted pair shielded cable recommended for inproved noise immunity

Crosstalk No crosstalk because of 1 channel output

Dielectric Strength 500V between output and power circuit

Type of Protection Photocoupler between output and internal circuit

Effect of Improper Output Connection No damage

Selection of Analog Output Signal Type Using software programming

Calibration or Verification to Maintain Rated Accuracy Impossible (approx. 10 years)

Page 14: CATALOGO DE PLCS IDEC

Programmable Logic Controllers MicroSmart Series

J-14 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Analog Input Specifications

FC4A-L03A1, FC4A-J2A1, FC4A-L03AP1 FC4A-L03AP1 only

Input Signal Type Voltage Input Current Input Thermocouple Resistance Thermometer

Input Range 0 to 10V DC 4 to 20 mA DCType K (0 to 1300°C)Type J (0 to 1200°C)Type T (0 to 400°C)

Pt 100 3-wire type(-100 to 500°C)

Input Impedance 1 MΩ minimum 10Ω 1 MΩ minimum 1 MΩ minimum

Allowable Conductor Resistance — — — 200Ω maximum

Input Detection Current — — — 1.0 mA maximum

Sample Duration Time 16 msec maximum 50 msec maximum

Sample Repetition Time 16 msec maximum 50 msec maximum

Total Input System Transfer Time 32 msec + 1 scan time * 100 msec + 1 scan time *

Type of Input Single-ended input Differential input

Operating Mode Self scan

Conversion Method ∑∆ type ADC

Input Error

Maximum Error at 25°C ±0.2% of full scale±0.2% of full scale plus

reference junction compensa-tion accuracy (±4°C maximum)

±0.2% of full scale

Temperature Coefficient ±0.006% of full scale / °C

Repeatabliity after Stabilization Time ±0.5% of full sclae

Non-lineality ±0.2% of full scale

Maximum Error ±1% of full scale

Data

Digital Resoltuion 4096 increments (12 bits)

Input Value of LSB 2.5 mV 4 µA K: 0.325°C; J: 0.300°C; T: 0.100°C 0.15°C

Data Type in Application Program 0 to 4095 (12-bit data); -32768 to 32767 (optional range designation) **

Monotonicity Yes

Input Data Out of Range Detectable #

NoiseResistance

Maximum Termporary Deviation duringElectrical Noise Tests

±3% maximum when a 500V clamp voltage is applied to the power and I/O wiring Accuracy is not assured when noise is applied

Common Mode Characteristics Common mode reject ratio (CMRR): -50 dB

Common Mode Voltage 16V DC

Input Filter No

Cable Twisted pair shielded cable recommended for improved noise immunity —

Crosstalk 2 LSB maximum

Dielectric Strength 500V between input and power circuit

Type of Protection Photocoupler between input and internal circuit

Effect of Improper Input Connection No damage

Maximum Permanent Allowed Overload (No damage) 13V DC 40 mA DC —

Selection of Analog Input Signal Type Using software programming

Calibration or Verification to Maintain Rated Accuracy Impossible (approx. 10 years)

NOTES FOR ANALOG EXPANSION UNITS:* Total input system transfer time = Sample repetition time x 2 + 1 scan time** The 12-bit data (0 to 4095) processed in the analog I/O module can be linear-converted to a value between -32768 and 32767. Select the optional

range designations and analog I/O data minumum and maximum values by using data registers allocated to analog I/O modules.# When an error is detected, a corresponding error code is sorted to a data register allocated to analog I/O operating status.

Page 15: CATALOGO DE PLCS IDEC

Programmable Logic Controllers MicroSmart Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-15

J

Communication Adapter and Communication Module Specifications

Optional HMI Module Specifications

Optional Memory Cartridge Specificaions

Optional Clock Cartridge Specificaions

FC4A-PC1FC4A-HPC1

FC4A-PC2FC4A-HPC2

FC4A-PC3FC4A-HPC3

Standards EIA RS232C EIA RS485 EIA RS485

Maximum Baud Rate 19200 bps 19200 bps Computer link: 19200 bpsData link: 38400 bps

Maintenance Communication Possible Possible Possible

User Communication Possible Impossible Impossible

Modem Communication Possible Impossible Impossible

Data Link Communication Impossible Impossible Possible

Maximum Cable Length Use FC2A-KC4C, FC2A-KM1C, FC4A-KC1C, FC4A-KC2C Use FC2A-KP1C 200m

Quantity of Slave Stations — — 31

Isolation between Internal Circuit and Communication Port Not isolated

Recommended Cable for RS485 — Twisted-piar shielded cable with a minimum core wire of 0.3 mm2

Conductor Resistance — 85 Ω/km maximum

Shield Resistance — 20Ω/km maximum

FC4A-PH1

Power Voltage 5V DC (supplied from the CPU module)

Internal Current Draw 200mA DC

Weight 20g

FC4A-PM32

Memory Type EEPROM

Accessible Memory Capacity 32 KB

Hardware for Storing Data CPU module

Software for Storing Data WindLDR

Quantity of Store Programs One user program can be stored on one memory cartridge

FC4A-PT1

Accuracy ±30 sec/month (typical) at 25°C

Backup Duration Approx. 30 days (typical) at 25°C after backup battery fully charged

Battery Lithium secondary battery

Charging Time Approx. 10 hours for charging from 0% to 90% of full charge

Replaceability Impossible to replace battery

Page 16: CATALOGO DE PLCS IDEC

Programmable Logic Controllers MicroSmart Series

J-16 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

CPU Modules:

Expansion Modules:

Dimensions

90.0

4.5*

80.0 70.0

FC4A-C10R2, FC4A-C16R2

95.0

90.0

70.0

FC4A-C24R2

35.4

90.0

70.011.3

FC4A-D20K3, FC4A-D20S3

47.5

90.0

70.014.6

FC4A-D20RK1, FC4A-D20RS1

47.5

90.0

70.011.3

FC4A-D40K3, FC4A-D40S3

70.014.623.53.8

90.0

4.5*

FC4A-N08B1, FC4A-T08K1, FC4A-M08BR1,FC4A-L03AP1, FC4A-K1A1, FC4A-R081FC4A-T08S1, FC4A-L03A1, FC4A-J2A1

70.014.623.53.8

90.0

FC4A-N16B1, FC4A-R161

70.01.039.13.8

90.0

FC4A-M24BR2

70.011.317.63.8

90.0

FC4A-N16B3, FC4A-T16K3, FC4A-T16S3

70.011.329.73.8

90.0

FC4A-N32B3, FC4A-T32K3, FC4A-T32S3

70.0

4.5*

90.0

22.5 13.9

FC4A-HPC1, FC4A-HPC2, FC4A-HPC3

71.0

90.0

38.0 13.9

FC4A-HPH1

95.0

DIN RailBNL6P Mounting Clip

23.5 23.5 9.09.0

90.0

45.0

35.0

4.5*

EXAMPLE: This figure illustrates a system setup with the FC4A-C24R2 All-in-one type CPU, an 8-point relay output module, and a 16-point DC input module, mounted on a 35mm DIN rail using BNL6P mounting clips.

Page 17: CATALOGO DE PLCS IDEC

Programmable Logic Controllers MicroSmart Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-17

J

CPU Modules:

Expansion Modules:

Mounting Hole Layout

90.0

83.0

68.0

80.0

FC4A-C10R2FC4A-C16R2

90.0

83.0

83.0

95.0

2-ø4.3

FC4A-C24R2

103.

090

.0

35.424.1

3.0

2-ø4.3

FC4A-C20K3FC4A-D20S3

90.0

103.

0

47.524.1

2-ø4.3

3.0

FC4A-C20RK1, FC4A-D40K3FC4A-C20RS1, FC4A-D40S3

23.56.3

3.0

90.0

103.

0

2-ø4.3

FC4A-N08B1, FC4A-N16B1, FC4A-R081, FC4A-R161, FC4A-T08K1, FC4A-T08S1, FC4A-M08BR1, FC4A-L03A1 FC4A-L03AP1, FC4A-J2A1, FC4A-K1A1

90.0

103.

0

17.66.3 2-ø4.3

3.0

FC4A-N16B3FC4A-T16K3FC4A-T16S3

29.76.3

3.0

90.0

103.

0

2-ø4.3

FC4A-N32B3FC4A-T32K3FC4A-T32S3

22.54.8

3.0

90.0

103.

0

2-ø4.339.16.3

3.0

90.0

103.

0

2-ø4.3

FC4A-M24BR2FC4A-HP1CFC4A-HPC2FC4A-HPC3

38.020.3

3.0

90.0

103.

0

2-ø4.3

FC4A-HPH1

23.5 23.5 23.512.3

15.3 23.5 23.5 23.583.03.0 3.0 3.0 3.0

103.

0

83.0

10-ø4.3

41.8

3.0 3.0 3.0 3.03.0

41.8 17.6 17.6 29.7

103.

0

17.6 17.6 29.7

EXAMPLE:Mounting hole layout for FC4A-C24R2 and 23.5mm-wide I/O modules.

EXAMPLE:Mounting hole layout for, from left, FC4A-HPH1, FC4A-D20K3, FC4A-N16B3, FC4A-N32B3, and FC4A-M24R2 modules.

Page 18: CATALOGO DE PLCS IDEC

Programmable Logic Controllers MicroSmart Series

J-18 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

I/O Usage Limits

All-in-one Type CPU Modules:

Input Internal Circuits

Usage Limits

Input Voltage (V DC)

28.8V26.4V24.0V

0 50% 100%

Ambient temperature 55°C

Input Voltage (V DC)

28.8V

26.4V

0 50% 100%

Ambient temperature 55°C

I/O Simultaneous ON Ratio (%)

Ambient temperature 45°C

Input Voltage (V DC)

28.8V26.4V24.0V

0 50% 100%

Ambient temperature 30°C

Input Voltage (V DC)

28.8V26.4V24.0V

0 50% 100%

Input Voltage (V DC)

28.8V26.4V24.0V

0 50% 100%

Ambient temperature 55°C

Ambient temperature 45°C

Input Voltage (V DC)

28.8V26.4V24.0V

0 50% 100%

Input Voltage (V DC)

28.8V

26.4V

0 50% 100%

Ambient temperature 45°C

Ambient temperature

55°C

Ambient temperature

55°C

Ambient temperature

55°C

Ambient temperature

55°C

Ambient temperature

55°C

Ambient temperature

55°C

Ambient temperature

55°C

I/O Simultaneous ON Ratio (%)

Input Voltage (V DC)

26.4V

24.0V

0 50% 100%

Ambient temperature 40°C

I/O Simultaneous ON Ratio (%)

I/O Simultaneous ON Ratio (%) I/O Simultaneous ON Ratio (%) I/O Simultaneous ON Ratio (%) I/O Simultaneous ON Ratio (%) I/O Simultaneous ON Ratio (%)

I/O Simultaneous ON Ratio (%) I/O Simultaneous ON Ratio (%)

Input Voltage (V DC)

26.4V

24.0V

0 50% 100%

Ambient temperature 40°C

Input Voltage (V DC)

28.8V

26.4V

0 50% 100%

Ambient temperature 45°C

I/O Simultaneous ON Ratio (%)

Input Voltage (V DC)

26.4V

24.0V

0 50% 100%

Ambient temperature 55°C

Slim Type CPU Modules:

Input Usage Limits

When using at an operating ambient temperature above 40°C, reduce the input voltage or the quantity of I/O points that turn on simultaneously.

Internal Circuits

Inte

rnal

Circ

uit

Input1.8 kΩ

I0, I1

COM

ALL-IN-ONE TYPE

Inte

rnal

Circ

uit

COM

Input3.3 kΩ

I2 to I15

Inte

rnal

Circ

uit

Input4.7 kΩ

I0, I1, I6, I7

COM

SLIM TYPE

Inte

rnal

Circ

uit

COM

Input3.3 kΩ

I2 to I5 and I10 to I27

SINK OUTPUT

InternalCircuit

+V

Output

COM(-)

InternalCircuit

-V

Output

COM(+)SOURCE OUTPUT

Output Internal Circuit (Slim Type)

Page 19: CATALOGO DE PLCS IDEC

Programmable Logic Controllers MicroSmart Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-19

J

Input Internal Circuits (Expansion Modules) Output Internal Circuits

Analog I/O Module

Inte

rnal

Circ

uit

COM

Input3.3 kΩ

FC4A-N081, FC4A-N16B1

Inte

rnal

Circ

uit

COM

Input4.3 kΩ

FC4A-N16B3, FC4A-N32B3

Inte

rnal

Circ

uit

COM

Input3.3 kΩ

FC4A-M08BR1, FC4A-M24BR2

InternalCircuit

+V

Output

COM(-)

FC4A-T08K1, FC4A-T16K3, FC4A-T32K3

InternalCircuit

-V

Output

COM(+)

FC4A-T08S1, FC4A-T16S3, FC4A-T32S3

+

-

Out

put C

ircui

t

NC(A)1 kΩ

15 MΩ

+ (B')

- (B)

1 kΩ

1 kΩ10 Ω

+V2 +V1

- V1

Mul

tiple

xer

Input Data

InputSelectionSignal

Input Circuit

Output Circuit

Page 20: CATALOGO DE PLCS IDEC

Programmable Logic Controllers MicroSmart Series

J-20 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Basic Instruction List

Symbol Function Qty. of Bytes

LOD Stores intermediate results and reads contact status 6

LODN Stores intermediate results and reads inverted contact status 6

OUT Outputs the result of bit logical operation 6

OUTN Outputs the inverted result of bit logical operation 6

SET Sets output, internal relay, or shift register bit 6

RST Resets output, internal relay, or shift register bit 6

AND Series connection of NO contact 4

ANDN Series connection of NC contact 4

OR Parallel connection of NO contact 4

ORN Parallel connection of NC contact 4

AND • LOD Series connection of circuit blocks 5

OR • LOD Parallel connection of circuit blocks 5

BPS Saves the result of bit logical operation temporarily 5

BRD Reads the result of bit logical operation which was saved temporarily 3

BPP Restores the result of bit logical operation which was saved temporarily 2

TML Subracting 1-sec timer (0 to 65535 sec) 4

TIM Subtracting 100-msec timer (0 to 6553.5 sec) 4

TMH Subtracting 10-msec timer (0 to 655.35 sec) 4

TMS Subtracting 1-msec timer (0 to 65.535 sec) 4

CNT Adding counter (0 to 65535) 4

CDP Dual pulse reversible counter (0 to 65535) 4

CUD Up/down selection reversible counter (0 to 65535) 4

CC= Equal to comparison of counter current value 7

CC≥ Greater than or equal to comparison of counter current value 7

DC= Equal to comparison of data register value 8

DC≥ Greater than or equal to comparison of data register value 8

SFR Forward shift register 6

SFRN Reverse shift register 6

SOTU Rising-edge differentiation output 5

SOTD Falling-edge differentiation output 5

JMP Jumps a designated program area 4

JEND Ends a jump instruciton 4

MCS Starts a master control 4

MCR Ends a master control 4

END Ends a program 2

Programming Instructions

Page 21: CATALOGO DE PLCS IDEC

Programmable Logic Controllers MicroSmart Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-21

J

Advanced Instruction List

Function Qty. of Bytes

All-in-one Type Slim Type

Symbol FC4A-C10R2

FC4A-C16R2

FC4A-C24R2

FC4A-D20K3FC4A-D20S3

FC4A-D20RK1FC4A-D20RS1FC4A-D40K3FC4A-D40S3

NOP No Operation 2

MOV Move 16

MOVN Move Not 16

IMOV Indirect Move 24-28

IMOVN Indirect Move Not 24-28

IBMV Indirect Bit Move 24 — — — —

IBMVN Indirect Bit Move Not 24 — — — —

BMOV Block Move 18 — — — —

CMP= Compare Equal To 20

CMO<> Compare Unequal To 20

CMP< Compare Less Than 20

CMP> Compare Greater Than 20

CMP<= Compare Less Than or Equal To 20

CMP>= Compare Greater Than or Equal To 20

ICMP>= Interval Compare Greater Than or Equal To 22 — — — —

ADD Addition 20

SUB Subtraction 20

MUL Multiplication 20

DIV Division 20

ANDW AND Word 20

ORW OR Word 20

XORW Exclusive OR Word 20

SFTL Shift Left 12

SFTR Shift Right 12

BCDLS BCD Left Shift 14 — — — —

WSFT Word Shift 18 — — — —

ROTL Rotate Left 12

ROTR Rotate Right 12

HTOB Hex to BCD 14

HTOA Hex to ASCII 18

BTOH BCD to Hex 14

BTOA BCD to ASCII 18

ATOH ASCII to Hex 18

ATOB ASCII to BCD 18

ENCO Encode 16 — — — —

DECO Decode 16 — — — —

TXD1 Transmit 1 21-819

TXD2 Transmit 2 21-819 —

Not applicable to previously released CPU modules FC4A-C10R2B, FC4A-C16R2B, or FC4A-C24R2B. Applicable only to newer MicroSmart All-in-one-type CPU modules.

Page 22: CATALOGO DE PLCS IDEC

Programmable Logic Controllers MicroSmart Series

J-22 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Advanced Instruction List, continued

Function Qty. of Bytes

All-in-one Type Slim Type

Symbol FC4A-C10R2

FC4A-C16R2

FC4A-C24R2

FC4A-D20K3FC4A-D20S3

FC4A-D20RK1FC4A-D20RS1FC4A-D40K3FC4A-D40S3

RXD1 Receive 1 21-819

RXD2 Receive 2 21-819 —

LABEL Label 8

LJMP Label Jump 10

LCAL Label Call 10

LRET Label Return 6

ROOT Root 14

DISP Display 16 — —

DGRD Digital Read 20 — —

WKTBL Week Table 13-89

WKTIM Week Timer 24

PULS1 Pulse Output 1 12 — — —

PULS2 Pulse Output 2 12 — — —

PWM1 Pulse Width Modulation 1 24 — — —

PWM2 Pulse Width Modulation 2 24 — — —

RAMP Ramp Pulse Output 14 — — —

ZRN1 Zero Return 1 18 — — — —

ZRN2 Zero Return 2 18 — — — —

XYFS XY Format Set 24-124 — —

CVXTY Convert X to Y 18 — —

CVYTX Convery Y to X 18 — —

PID PID Control 26 — —

IOREF I/O Refresh 16

BCNT Bit Count 18 — — — —

ALT Alternate Output 10 — — — —

DTML 1-sec Dual Timer 22 — — — —

DTIM 100-msec Dual Timer 22 — — — —

DTMH 10-msec Dual Timer 22 — — — —

DTMS 1-msec Dual Timer 22 — — — —

TTIM Teaching Timer 10 — — — —

DI Disable Interrupt 8 — — — —

EI Enable Interrupt 8 — — — —

Not applicable to previously released CPU modules FC4A-C10R2B, FC4A-C16R2B, or FC4A-C24R2B. Applicable only to newer MicroSmart All-in-one-type CPU modules.

Page 23: CATALOGO DE PLCS IDEC

Programmable Logic Controllers ONC Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-23

J Hardware Features

•Digital I/O- 8, 16, and 32 point cards- 224 inputs and outputs, 480 with expansion power supply

•Analog I/O- up to 42 analog inputs or 14 analog outputs- 0-5V, 0-10V, ±5V, ±10V, 4-20mA

•Built-In Communications Ports- 2 RS232 (programming port, ASCII, printer and modem ready)- 1 RS485 (programming port and data link)

•Build-in High-Speed Counter- 1 channel, 10kHz, 16-bit resolution

•Memory- 16K words (8K steps) user program capacity- Flash miniature memory card slot (FC3A-CP2KM/SM only)

•Realtime Calendar/Clock, Y2K compliant•Password Protection•PID Algorithm

•Networking ONC capable of communicating with various standard networks:

• DeviceNet • INTERBUS • LONWORKS

•Programming Software; WindLDR® 4.10 • Programs all IDEC PLCs• Windows-based (compatible with Windows 3.10, 3.11,

Win 95, Win-98, Win-2000, or Win-NT 4.0)

•Programming Instructions• Transmit/Receive• Built-in X/Y Conversion • Sub-Routine Call/Return for Modular Programming• Square Root• 16- and 32-bit Math, Add, Sub, Mult, Div• Data Conversion to/from Dec, Hex, BCD, ASCII• Block Move• Summation• Averaging• Day of Week Program Scheduling

•Built-in Hayes "AT" command set for modem dialup/pager applications

OpenNet Controller(without memory card connector)

OpenNet Controller

FC3A-CP2KFC3A-CP2S

FC3A-CP2KMFC3A-CP2SM

Flash memory card ready

CPU

s

FC3A-CP2K High-speed counter sink output, no memory card connector

FC3A-CP2KM High-speed counter sink output with memory card connector

FC3A-CP2S High-speed counter source output, no memory card connector

FC3A-CP2SM High-speed counter source output with memory card connector

Elec

tric

al S

peci

ficat

ions

Rated Voltage 24V DC (19-30V DC, including ripple)

Maximum Input Current 1.5A at 24V DC

Reverse Polarity Protection Prevents damage if incorrectly wired.

Operating Temperature 0 to +55°C

Storage Temperature -25 to +70°C

Relative Humidity 30 to 95% (non-condensing)

Vibration Resistance10 to 57 Hz, amplitude 0.075mm 57 to 150 Hz 9.8 m/sec2 10 sweep cycles/axis (IEC 1131)

Shock Resistance 147 m/sec2, 11 ms3 shocks each in 3 axes (IEC 1131)

Dielectric Strength Between power terminal and FG: 500V AC, 1 minBetween I/O terminal and FG: 1500V AC, 1 min

Ground Grounding resistance 100Ω (maximum)

Mounting Style 35mm DIN rail

OpenNet Controller(with memory card connector)

CE Certified

UL ListedFile No. E102342

Page 24: CATALOGO DE PLCS IDEC

Programmable Logic Controllers ONC Series

J-24 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

PS5R Power Supply

PS5R

-D24 Wattage & Current Ratings 50W, 2.1A

Rating UL 508 listed

Mounting DIN rail mountable

Standard ONC CPU

Gen

eral

ON

C Sp

ecifi

catio

ns

Available Instructions 37 basic, 65 advanced (PID, square root, subroutine calls, etc.)

User Program Capacity 16K words flash memory

Memory (Miniature Card) 2, 4 and 8MB; 5V type

Average Scan Time 1 ms or greater

Input 224 points (I0-I277)

Output 224 points (Q0-Q277)

Total I/O Points Using expansion power supply: 480 I/O points

Internal Relay 2048 (M0-M2557)

Special Internal Relay 192 (M8000-M8237)

Shift Register 256 (R0-R255)

Timer 256 (T0-T255; 1-sec, 100-msec, 10-msec, 1-msec)

Counter 256 (C0-C255; adding, dual pulse reversible, up/down selection reversible)

Data Register 8000 (D0-D7999)

Link Register 256 master (L1000 - L1317), 168 slave (L100 - L127, L200 - L227, ......, L700 - L727)

Remote I/O 512 points

Real-Time Calendar/Clock Runtime Yes (Y2K complaint)

Program Protection Yes (password protected)

External Run/Stop Control Yes

Power Failure Protection Yes

Self-Diagnostics Yes

Auto Start Function Yes

Powered by IDEC’s PS5R Series 50W Power Supply

The eighth slot must be expansion power supply module. (Above photo is only an example of the range of available modules.)

Page 25: CATALOGO DE PLCS IDEC

Programmable Logic Controllers ONC Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-25

J

Part Numbers: OpenNet Controller

Item Description Part Number

CPU Modules

High-speed counter, source output type,No memory card available FC3A-CP2K

High-speed counter, source output type,With memory card connector FC3A-CP2KM

High-speed counter, sink output type,No memory card available FC3A-CP2S

High-speed counter, sink output type,With memory card connector FC3A-CP2SM

Input Modules

DC Input

16 points 24V DC input, sink/source compatible, terminal block FC3A-N16B1

16 points 24V DC input, sink/source compatible,nylon connector (10P*2) FC3A-N16B3

32 points 24V DC input, sink/source compatible,nylon connector (10P*2) FC3A-N32B4

32 points 24V DC input, sink/source compatible,FUJITSU connector FC3A-N32B5

AC Input 8 points 100V AC input, terminal block FC3A-N08A11

Analog Input 6 channels, 4-20mA,selectable by DIP sw, terminal block FC3A-AD1261

Output Modules

Analog Output 2 channels, 4-20mA, selectable by DIP sw, terminal block FC3A-DA1221

Relay Output16 points relay output, terminal block FC3A-R161

16 points relay output, nylon connector (5P*4) FC3A-R162

Transistor Output

16 points transistor output sink, terminal block FC3A-T16K1

16 points transistor output sink, nylon connector FC3A-T16K3

16 points transistor output protect source, terminal block FC3A-T16P1

32 points transistor output sink, nylon connector FC3A-T32K4

32 points transistor output sink, FUJITSU connector FC3A-T32K5

Expansion Module Expansion power supply FC3A-EA1

Page 26: CATALOGO DE PLCS IDEC

Programmable Logic Controllers ONC Series

J-26 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Part Numbers: SX/IO

For Use With Description Part Number

INTERBUS

DC-16 Inputs, Source SX5S-SBN16S

DC-16 Inputs, Sink SX5S-SBN16K

Relay Output, 8 points SX5S-SBR08

Transistor Output, 16 points SX5S-SBT16K

Transistor Output, 16 points, Protect Source SX5S-SBT16P

DC-8 points Source Input / Transistor 8 points SInk Output SX5S-SBM16K

DC-8 points Sink Input / Transistor 8 points Protect Source Output SX5S-SBM16P

DEVICENET

DC-16 Inputs, Source SX5D-SBN16S

DC-16 Inputs, Sink SX5D-SBN16K

Relay Output, 8 points SX5D-SBR08

Transistor Output, 16 points SX5D-SBT16K

Transistor Output, 16 points, Protect Source SX5D-SBT16P

DC-8 points Source Input / Transistor 8 points SInk Output SX5D-SBM16K

DC-8 points Sink Input / Transistor 8 points Protect Source Output SX5D-SBM16P

LONWORKS

DC-16 Inputs, Source SX5L-SBN16S

DC-16 Inputs, Sink SX5L-SBN16K

Relay Output, 8 points SX5L-SBR08

Transistor Output, 16 points SX5L-SBT16K

Transistor Output, 16 points, Protect Source SX5L-SBT16P

DC-8 points Source Input / Transistor 8 points SInk Output SX5L-SBM16K

DC-8 points Sink Input / Transistor 8 points Protect Source Output SX5L-SBM16P

Common Unit

Upper terminal block for SX5*-SBN16*, -SBT16*, -SBM16* SX9Z-SS1

Lower terminal block for SX5*-SBN16*, -SBT16* SX9Z-SS2

Lower terminal block for SX5*-SBN16* SX9Z-SS3

Lower terminal block for SX5*-SBN16* SX9Z-SS4

Lower terminal block for SX5*-SBN16* SX9Z-SS5

SX5D (DeviceNet connector), comes with mounting screws SX9Z-CN5G2

SX5L (LON connector), comes with mounting screws SX9Z-CN22

LonWorks slave interface module FC3A-SX5LS1

ONC Remote I/O Master module FC3A-SX5SM1

Page 27: CATALOGO DE PLCS IDEC

Programmable Logic Controllers ONC Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-27

J

01234567891011121314151617

Computer Link Cable 4CFC2A-KC4C3m (9.84 ft.) long

D-sub 9-pin Female Connector

RS232C Port 1 or Port 2

01234567891011121314151617RS232C/RS485 Converter

FC2A-MD1

1st Unit

2nd Unit

32nd Unit

RS232C CableHD9Z-C521.5m (4.92 ft.) long

01234567891011121314151617

01234567891011121314151617

Twist-pair Shielded Cable

D-sub 9-pin Female Connector

RS485

OpenNet Controller, Networking & Applications

Printer

Barcode Reader

Modem

PC CommunicationThe ONC is programmed by our intuitive WindLDR™3.0 software -use RS232 or RS485 ports -upload, download and monitor programs

Data Link - Superiority in NetworkingConnect up to 32 ONC, Micro3, FA Series PLCs orthe HG Series operator interface on the data link network.

Communication FlexibilityEasy connections to any R232C equipmentthrough the user defined RS232C port 1 or 2.Built-in Hayes “AT” command set for directmodem dialup and pager applications.

Computer Link - Power & VersatilityConnect 32 ONCs on a 1:N computer link system.Upload, download, monitor, and update data.

For RS485 programming, use FC2A-KC6C cable.

Communication Selector DIP Switch

Master Station Slave Station 1 Slave Station 2

HG SeriesOperatorInterface

01234567891011121314151617

01234567891011121314151617

Slave Station 31

01234567891011121314151617

AB

GR

S485

CO

MA

BZ

HS

CO

UT

+24V

0V

POWER

RUN

ERROR

HSC OUT

12

3

O N

DIPSwitch

Page 28: CATALOGO DE PLCS IDEC

Programmable Logic Controllers ONC Series

J-28 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

INTERBUS DeviceNet LONWORKS

Expansion Connector

(1) Module ID(5) Status LED

(3) Connector 1

(4) Connector 2

Expansion Connector

(1) Module ID(4) Status LED

(2) FG Terminal

(2) DIP Switch

(3) Connector

Expansion Connector

(1) Module ID(5) Status LED

(3) Service Request

(4) Connector

SERVIOSE

REQUESI

NETWORK

(2) FG Terminal

V.24

Inte

rfac

eR

EMO

TE O

UT

idec

REM

OTE

IN

REM

OTE

OU

T

idec idec

NOH/LDR1DR0

NA5NA4NA3

NA2NA1NA0

idec

SERVICEREQUPST

NET WORK

INTERBUS

DeviceNet

LONWORKS

INTERBUS

Remote I/OMaster Module

CPUModule

SX5S Communication Terminals

OpenNet Interface Modules I/O Modules

AB

GR

S485

CO

MA

BZ

HS

CO

UT

+24V0V

Remote I/O

REM

OTE

OU

TR

EMO

TE I

NR

EMO

TE O

UT

REM

OTE

IN

Remote I/O

REM

OTE

OU

TR

EMO

TE I

NR

EMO

TE O

UT

REM

OTE

IN

POWER

RUN

ERROR

HSC OUT

Network Communication SystemThe ONC offers versatility and power with the unique capabilityto inferface with standard networks such as INTERBUS,DeviceNet and LONWORKS.

OpenNet Interface Modules

Add 8 or 16 I/O points to theremote I/O network with a simpleconnection: SX5S communicationterminals offer a simple and lowcost method of system expan-sion.

Page 29: CATALOGO DE PLCS IDEC

Programmable Logic Controllers ONC Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-29

J

Spec

ifica

tions

Analog Type Input Output

Point Per Card 6 Points 2 PointsPart Number FC3A-AD1261 FC3A-DA1221Connector Type Phoenix Contact Phoenix Contact

Input Signal 0-10V DC, ±10V DC, 0-5V DC, ±5V DC, 4-20mA

0-10V DC, ±10V DC, 0-5V DC, ±5V DC, 4-20mA

Resolution 12 bits 12 bitsRange 0-4000 counts 0-4000 countsInput Error ±0.6% of full scale @ 25°C NAOutput Error NA ±0.6% of full scale @ 25°C Conversion Time 3ms per point NASettling Time NA 3ms

Input Impedance Voltage: 1 MΩ minimumCurrent: 250Ω NA

Output Load Impedance NA Voltage=2 kΩ minimum

(Current=250Ω, 300Ω max.)Internal Current Draw 120mA@24V DC 120mA@24V DC

Analog Input and Output Modules

Analog Input ModuleFC3A-AD1261

Key features include:• One card handles 5 different signal types,

[±5V, ±10V, 0-5V, 0-10V, or 4-20mA], switch selectable

• Input module has 6 inputs per card, 7 cards per CPU, 42 analog input points maximum

• Output module has 2 outputs per card, 7 cards per CPU, 14 analog output points maximum

• 12-bit resolution, 0-4000 counts, count range divides evenly• Fast input scan, 3ms + 1 scan time• I/O error ±0.6% full scale @25°C• Convenient input termination, Phoenix Contact type connector

Analog Input Module Analog Output Module

Voltage Input

COM

+V

250Ω

+

–V

Differential

Current Input

Amplifier

Voltage Output

COM

+V

–V

Current Output

Analog Output ModuleFC3A-DA1221

Type of Protection

Page 30: CATALOGO DE PLCS IDEC

Programmable Logic Controllers ONC Series

J-30 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Terminal No. Channel Name

1

Channel 0

+V (voltage)

2 +I (current)

3 COM (-V, -I)

4

Channel 1

+V (voltage)

5 +I (current)

6 COM (-V, -I)

7

Channel 2

+V (voltage)

8 +I (current)

9 COM (-V, -I)

10

Channel 3

+V (voltage)

11 +I (current)

12 COM (-V, -I)

13

Channel 4

+V (voltage)

14 +I (current)

15 COM (-V, -I)

16

Channel 5

+V (voltage)

17 +I (current)

18 COM (-V, -I)

19 — NC

20 — NC

FC3A-AD1261 Analog Input Module Terminal Arrangement

6-Channel - Screw Terminal TypeApplicable Connector: SMSTB2.5/20-ST-5.08 (Phoenix Contact)

FC3A-DA1221 Analog Output Module Terminal Arrangement

2-Channel - Screw Terminal TypeApplicable Connector: SMSTB2.5/20-ST-5.08 (Phoenix Contact) Terminal

No. Channel Rotary Switch Position Name

1

Channel 0

0Voltage Output (0 to 10V)

2 COM (GND)

31

Voltage Output (±10V)

4 COM (GND)

52

Voltage Output (0 to 5V)

6 COM (GND)

73

Voltage Output (±5V)

8 COM (GND)

94

Current Output (4 to 20mA)

10 COM (GND)

11

Channel 1

0Voltage Output (0 to 10V)

12 COM (GND)

131

Voltage Output (±10V)

14 COM (GND)

152

Voltage Output (0 to 5V)

16 COM (GND)

173

Voltage Output (±5V)

18 COM (GND)

194

Current Output (4 to 20mA)

20 COM (GND)

PCW

A/D

D/A

PCW

Page 31: CATALOGO DE PLCS IDEC

Programmable Logic Controllers ONC Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-31

J

16-Point DC Input Modules

Input Type DC Sink/Source

16-P

oint

DC

Part Number FC3A-N16B1 FC3A-N16B3Connector Type Phoenix Contact NylonInput Voltage Range 19-30V DC 19-30V DCRated Input Voltage 24V DC 24V DCCurrent Per Point 7mA 7mAInternal Current - all inputs ON 40mA 40mAInput Impedance 3.4kΩ 3.4kΩOn/Off Voltage 15/5V DC 15/5V DCOn/Off Time 20/120µs 20/120µs

Key features include:• One card handles sink (NPN) or source (PNP)

type input signals• 16 points per card, 7 cards local, 8 cards expansion,

15 cards max. per CPU• 19-30V DC input voltage range• Software selectable input filtering, 0-32 msec• High-speed catch inputs, first 8 points user definable,

pulse detection within 20-120µsec range• Termination connector

-FC3A-N16B1 - removable Phoenix Contact type-FC3A-N16B3 - removable Nylon type

Input Operating RangeThe input operating range of the Type 1 (EN61131) input module is shown below:

Input Internal Circuit

Transition

OFF AreaInpu

t Vo

ltage

(V

DC

)

30

15

5

01.5 8.8

Input Current (mA)

ON Area

Area

74.4

24

COM

Inte

rnal

Circ

uit

Input

DC Input ModuleFC3A-N16B1

DC Input ModuleFC3A-N16B3

Page 32: CATALOGO DE PLCS IDEC

Programmable Logic Controllers ONC Series

J-32 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Terminal No. Name

1 COM

2 COM

3 I0

4 I1

5 I2

6 I3

7 I4

8 I5

9 I6

10 I7

11 COM

12 COM

13 I10

14 I11

15 I12

16 I13

17 I14

18 I15

19 I16

20 I17

Terminal No. CN1

1 COM

2 COM

3 I0

4 I1

5 I2

6 I3

7 I4

8 I5

9 I6

10 I7

Terminal No. CN2

1 COM

2 COM

3 I10

4 I11

5 I12

6 I13

7 I14

8 I15

9 I16

10 I17

FC3A-N16B1 Input Module Terminal Arrangement

16-Point DC - Screw Terminal TypeApplicable Connector: SMSTB2.5/20-ST-5.08 (Phoenix Contact)

FC3A-N16B3 Input Module Terminal Arrangement

16-Point DC - Nylon Connector TypeApplicable Connectors: VHR-10N (J.S.T. Mfg.)

SVH-21T-P1.1 (J.S.T. Mfg.)

012345671011121314151617

DCIN

012345671011121314151617

CN2

CN1 DCIN

Page 33: CATALOGO DE PLCS IDEC

Programmable Logic Controllers ONC Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-33

J

Key features include:• One card handles sink (NPN) or source (PNP) type input signals• 32 points per card, 7 cards local, 8 cards expansion,

15 cards max. per CPU• 20-28V DC input voltage range• Software selectable input filtering, 0-32 msec• High-speed catch inputs, first 8 points user definable,

pulse detection within 20-120µsec range• Termination connector

-FC3A-N32B4 - removable Nylon type-FC3A-N32B5 - removable Fujitsu type

32-Point DC Input Modules

Input Type DC Sink/Source

32-P

oint

DC

Part Number FC3A-N32B4 FC3A-N32B5Connector Type Nylon FujitsuInput Voltage Range 20-28V DC 20-28V DCRated Input Voltage 24V DC 24V DCCurrent Per Point 5mA 5mAInternal Current-all inputs ON 50mA 50mA

Input Impedance 4.7kΩ 4.7kΩOn/Off Voltage 15/5V DC 15/5V DCOn/Off Time 20/120µs 20/120µs

Input Operating RangeThe input operating range of the Type 1 (EN61131) input module is shown below:

Input Internal Circuit

Transition

OFF AreaInpu

t Vo

ltage

(V

DC

)

27.6

15

5

01 5.4

Input Current (mA)

ON Area

Area

4.94.4

24

COM

Inte

rnal

Circ

uit

Input

DC Input ModuleFC3A-N32B4

DC Input ModuleFC3A-N32B5

Page 34: CATALOGO DE PLCS IDEC

Programmable Logic Controllers ONC Series

J-34 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Terminal No. CN1 CN2

18 I0 I20

17 I1 I21

16 I2 I22

15 I3 I23

14 I4 I24

13 I5 I25

12 I6 I26

11 I7 I27

10 I10 I30

9 I11 I31

8 I12 I32

7 I13 I33

6 I14 I34

5 I15 I35

4 I16 I36

3 I17 I37

2 COM COM

1 COM COM

Terminal No. Name

B20 I0

B19 I1

B18 I2

B17 I3

B16 I4

B15 I5

B14 I6

B13 I7

B12 I10

B11 I11

B10 I12

B9 I13

B8 I14

B7 I15

B6 I16

B5 I17

B4 NC

B3 NC

B2 COM

B1 COM

Terminal No. Name

A20 I20

A19 I21

A18 I22

A17 I23

A16 I24

A15 I25

A14 I26

A13 I27

A12 I30

A11 I31

A10 I32

A9 I33

A8 I34

A7 I35

A6 I36

A5 I37

A4 NC

A3 NC

A2 NC

A1 NC

FC3A-N32B5 Input Module Terminal Arrangement

32-Point DC - Fujitsu Connector TypeApplicable Connector: FCN-367J040-AU (Fujitsu)

FC3A-N32B4 Input Module Terminal Arrangement

32-Point DC - Nylon Connector TypeApplicable Connectors: H18-SHF-AA (J.S.T. Mfg.)

SHF-001T-0.8BS (J.S.T. Mfg.)

01234567

CN1

CN2

101112131415161720212223242526273031323334353637

DCIN

01234567101112131415161720212223242526273031323334353637

DCIN

FOR MODULE FC3A-N32B5 ONLY:

Accessory Part No.

RIbbon Cable FC3A-KUSA1

Breakout ModulesBX1D-T40A

BX1D-S40A

Page 35: CATALOGO DE PLCS IDEC

Programmable Logic Controllers ONC Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-35

J

Key features include:• 8 points per card, 7 cards local, 8 cards expansion,

15 cards max. per CPU• 100-120V AC rated input voltage• 85-132V AC input voltage range• On/off detection set at 20ms• Convenient termination connector, removable Phoenix Contact type

8-Point AC Input Module

Input Type AC

8-Po

int A

C

Part Number FC3A-N08A11Connector Type Phoenix ContactInput Voltage Range 85-132V ACRated Input Voltage 100-120V ACCurrent Per Point 8mAInternal Current - all inputs ON 30mAInput Impedance 12kΩ (60Hz)On/Off Voltage 79/20V ACOn/Off Time 20ms

Input Operating RangeThe input operating range of the Type 1 (EN61131) input module is shown below:

Input Internal Circuit

Transition

OFF AreaInpu

t Vo

ltage

(V

AC)

132

79

20

01.6 11

Input Current (mA)

ON Area

Area

8.36.5

100

COMIn

tern

al C

ircui

t

Input

AC Input ModuleFC3A-N08A11

Page 36: CATALOGO DE PLCS IDEC

Programmable Logic Controllers ONC Series

J-36 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Terminal No. Name

1 COM0

2 I0

3 COM1

4 I1

5 COM2

6 I2

7 COM3

8 I3

9 COM4

10 I4

11 COM5

12 I5

13 COM6

14 I6

15 COM7

16 I7

17 NC

18 NC

19 NC

20 NC

FC3A-N08A11 Input Module Terminal Arrangement

8-Point AC - Screw Terminal TypeApplicable Connector: SMSTB2.5/20-ST-5.08 (Phoenix Contact)

0

ACIN

1234567

Page 37: CATALOGO DE PLCS IDEC

Programmable Logic Controllers ONC Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-37

J

Key features include:• 16 points per card, 4 points per common,

15 cards max. per CPU• Outputs rated 240V AC/2A or 24V DC/2A• Turn On/Off delay 6-10ms• 20,000,000 operations per relay minimum• Termination connector

-FC3A-R161 - removable Phoenix Contact type-FC3A-R162 - removable Nylon type

16-Point Relay Output Modules

Output Type Relay Output

16-P

oint

Rel

ay

Part Number FC3A-R161 FC3A-R162Connector Type Phoenix Contact NylonRated Output Voltage 240V AC/24V DC 240V AC/24V DCRated Current Per Point 2A 2AInternal Current - all inputs ON 170mA 170mA

On/Off Time 6/10ms 6/10ms

Output Delay

Command

Output Status

OFF delay: 10 msec maximumChatter: 6 msec maximumON delay: 6 msec maximum

Relay Output ModuleFC3A-R162

Relay Output ModuleFC3A-R161

Page 38: CATALOGO DE PLCS IDEC

Programmable Logic Controllers ONC Series

J-38 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Terminal No. Name

1 COM0

2 Q0

3 Q1

4 Q2

5 Q3

6 COM1

7 Q4

8 Q5

9 Q6

10 Q7

11 COM2

12 Q10

13 Q11

14 Q12

15 Q13

16 COM3

17 Q14

18 Q15

19 Q16

20 Q17

Terminal No. CN1

1 COM0

2 Q0

3 Q1

4 Q2

5 Q3

Terminal No. CN2

1 COM1

2 Q4

3 Q5

4 Q6

5 Q7

Terminal No. CN3

1 COM2

2 Q10

3 Q11

4 Q12

5 Q13

Terminal No. CN1

1 COM3

2 Q14

3 Q15

4 Q16

5 Q17

FC3A-R162 Output Module Terminal Arrangement

16-Point Relay - Nylon Connector TypeApplicable Connectors: VHR-5N (J.S.T. Mfg.)

SVH-21T-P1.1 (J.S.T. Mfg.)

FC3A-R161 Output Module Terminal Arrangement

16-Point Relay - Screw Terminal TypeApplicable Connector: SMSTB2.5/20-ST-5.08 (Phoenix Contact)

0

RyOUT

12345671011121314151617

01234567

CN1

CN2

CN3

CN4

RyOUT

1011121314151617

Page 39: CATALOGO DE PLCS IDEC

Programmable Logic Controllers ONC Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-39

J

Key features include:• 16 transistor sink outputs per card, 15 cards max. per CPU• Outputs rated 19-30V DC/0.5A• Turn On/Off delay 500µsec max.• Opto-isolated outputs• Termination connector

-FC3A-T16K1 - removable Phoenix Contact type-FC3A-T16K3 - removable Nylon type

16-Point DC Sink Output Modules

Output Type DC Sink

16-P

oint

DC

Part Number FC3A-T16K1 FC3A-T16K3Connector Type Phoenix Contact NylonRated Output Voltage 19-30V DC 19-30V DCRated Current Per Point 500mA@ 24V DC 500mA@ 24V DCInternal Current - all inputs ON 60mA 60mA

On/Off Time 500/500µs 500/500µs

DC Sink Output ModuleFC3A-T16K1

DC Sink Output ModuleFC3A-T16K3

Output Delay Output Internal Circuit

Command

Output Status

ON delay 500 µsec maximum

+V

Output

Inte

rnal

Circ

uit

COM (–)

OFF delay 500 µsec maximum

Page 40: CATALOGO DE PLCS IDEC

Programmable Logic Controllers ONC Series

J-40 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

FC3A-T16K3 Sink Output Module Terminal Arrangement

16-Point DC - Nylon Connector TypeApplicable Connectors: VHR-10N (J.S.T. Mfg.)

SVH-21T-P1.1 (J.S.T. Mfg.)

FC3A-T16K1 Sink Output Module Terminal Arrangement

16-Point DC - Screw Terminal TypeApplicable Connector: SMSTB2.5/20-ST-5.08 (Phoenix Contact) Terminal No. Name

1 Q0

2 Q1

3 Q2

4 Q3

5 Q4

6 Q5

7 Q6

8 Q7

9 COM(-)

10 +V

11 Q10

12 Q11

13 Q12

14 Q13

15 Q14

16 Q15

17 Q16

18 Q17

19 COM(-)

20 +V

Terminal No. CN1

1 Q0

2 Q1

3 Q2

4 Q3

5 Q4

6 Q5

7 Q6

8 Q7

9 COM(-)

10 +V

Terminal No. CN2

1 Q10

2 Q11

3 Q12

4 Q13

5 Q14

6 Q15

7 Q16

8 Q17

9 COM(-)

10 +V

0

TrOUT

12345671011121314151617

01234567

CN2

CN1 TrOUT

1011121314151617

Page 41: CATALOGO DE PLCS IDEC

Programmable Logic Controllers ONC Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-41

J

16-Point DC Protect Source Output Module

Protect Source Output ModuleFC3A-T16P1

Key features include:• 16 transistor protect source outputs per card, 15 cards max. per CPU• Outputs rated 19-30V DC/0.5A• Turn On/Off delay 500µsec max.• Opto-isolated outputs• Termination connector, removable Phoenix Contact type

Output Type DC Source

16-P

oint

DC

Part Number FC3A-T16P1Connector Type Phoenix ContactRated Output Voltage 19-30V DCRated Current Per Point 500mA @ 24V DCInternal Current - all inputs ON 70mAOn/Off Time 500µs/500µs

Output Delay Output Internal Circuit

Command

Output Status

ON delay 500 µsec maximum

COM (+)

Output

–V

Overload

Out

put

Prot

ect

Dev

ice

Signal

Inte

rnal

Circ

uit

OFF delay 500 µsec maximum

Page 42: CATALOGO DE PLCS IDEC

Programmable Logic Controllers ONC Series

J-42 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

FC3A-T16P1 Protect Source Output Module Terminal Arrange-

ment

16-Point DC - Screw Terminal TypeApplicable Connector: SMSTB2.5/20-ST-5.08 (Phoenix Contact)

Terminal No. Name

1 Q0

2 Q1

3 Q2

4 Q3

5 Q4

6 Q5

7 Q6

8 Q7

9 COM(+)

10 -V

11 Q10

12 Q11

13 Q12

14 Q13

15 Q14

16 Q15

17 Q16

18 Q17

19 COM(+)

20 -V

0

TrOUT

12345671011121314151617

Page 43: CATALOGO DE PLCS IDEC

Programmable Logic Controllers ONC Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-43

J

Key features include:• 32 transistor sink outputs per card, 15 cards max. per CPU• Outputs rated 20.4-27.6V DC/0.1A• Turn On/Off delay 500µsec max. • Opto-isolated outputs• Termination connector

-FC3A-T32K4 - removable Nylon type-FC3A-T32K5 - removable Fujitsu type

32-Point DC Sink Output Modules

Output Type DC Sink

32-P

oint

DC

Part Number FC3A-T32K4 FC3A-T32K5Connector Type Nylon FujitsuRated Output Voltage 20.4-27.6V DC 20.4-27.6V DCRated Current Per Point 100mA@24V DC 100mA@24V DCInternal Current - all inputs ON 90mA 90mA

On/Off Time 500/500µs 500/500µs

Output Delay Output Internal Circuit

Command

Output Status

ON delay 500 µsec maximum

+V

Output

Inte

rnal

Circ

uit

COM (–)

DC Sink Output ModuleFC3A-T32K4

DC Sink Output ModuleFC3A-T32K5

OFF delay 500 µsec maximum

Page 44: CATALOGO DE PLCS IDEC

Programmable Logic Controllers ONC Series

J-44 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Terminal No. CN1 CN2

18 Q0 Q20

17 Q1 Q21

16 Q2 Q22

15 Q3 Q23

14 Q4 Q24

13 Q5 Q25

12 Q6 Q26

11 Q7 Q27

10 Q10 Q30

9 Q11 Q31

8 Q12 Q32

7 Q13 Q33

6 Q14 Q34

5 Q15 Q35

4 Q16 Q36

3 Q17 Q37

2 COM(-) COM(-)

1 +V +V

Terminal No. Name

B20 Q0

B19 Q1

B18 Q2

B17 Q3

B16 Q4

B15 Q5

B14 Q6

B13 Q7

B12 Q10

B11 Q11

B10 Q12

B9 Q13

B8 Q14

B7 Q15

B6 Q16

B5 Q17

B4 NC

B3 NC

B2 +V

B1 +V

Terminal No. Name

A20 Q20

A19 Q21

A18 Q22

A17 Q23

A16 Q24

A15 Q25

A14 Q26

A13 Q27

A12 Q30

A11 Q31

A10 Q32

A9 Q33

A8 Q34

A7 Q35

A6 Q36

A5 Q37

A4 NC

A3 NC

A2 COM(-)

A1 COM(-)

FC3A-T32K5 Sink Output Module Terminal Arrangement

32-Point DC - Fujitsu Connector TypeApplicable Connector: FCN-367J040-AU (Fujitsu)

FC3A-T32K4 Sink Output Module Terminal Arrangement

32-Point DC - Nylon Connector TypeApplicable Connectors: H18-SHF-AA (J.S.T. Mfg.)

SHF-001T-0.8BS (J.S.T. Mfg.)

01234567

CN1

CN2

TrOUT

101112131415161720212223242526273031323334353637

01234567101112131415161720212223242526273031323334353637

TrOUT

Page 45: CATALOGO DE PLCS IDEC

Programmable Logic Controllers ONC Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-45

J

Key features include:• Expands the ONC from 224 up to 480 I/O points• Increases I/O and functional modules by 8• Comes with a cable connector and contacts• Simple, easy and convenient mounting• Install in the 8 slot only

Expansion Power Supply Module

Specifications

Expa

nsio

n Po

wer

Sup

ply

Part Number FC3A-EA1Connector Type Nylon - 5 pinInput Voltage Range 19 - 30V DC (including ripple)Rated Input Voltage 24V DCInternal Current 30mA

Momentary Power Interruption 10 msec (24V DC), Level PS-2 (EN61131)

Power Supply Wiring

1: NC

2: NC

3: 24V DC (red)

4: 0V (blue)

5: FG (green)

Ground

Fuse– +Power Voltage: 24V DCInrush Current: 50A

(same power source for CPU)

Connector

Expansion Power Supply ModuleFC3A-EA1

Page 46: CATALOGO DE PLCS IDEC

Programmable Logic Controllers ONC Series

J-46 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

FC3A-EA1 Expansion Power Supply Module Mounting Position

Mount the expansion power supply module in the eighth slot.

7 modules (I/O and functional)Expansion Power Supply Module

8 modules (I/O and functional)

A maximum of 7 functional modules can be mounted in any of 15 slots

CPU Module

Mount the expansion power supply module only in the eighth slot, otherwise correct allocation of I/O and link register numbers may not occur.

Page 47: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-47

J

UL/c-UL ListedFile No. E102542

SX5 Series Smart I/O (General Information)

SX5 Communication Terminals

Bus I/O Type Specifications Part No.

INTERBUS

DC Input16-point source input (24V DC) SX5S-SBN16S16-point sink input (24V DC) SX5S-SBN16K

Relay Output 8-point relay output (240V AC/24V DC, 5A) SX5S-SBR08

Transistor Output16-point transistor sink output (24V DC, 0.5A/point, 6.0A/common) SX5S-SBT16K16-point transistor protect source output (24V DC, 0.5A/point, 6.0A/common) SX5S-SBT16P

DC inputTransistor Output

8-point source input (24V DC)8-point transistor sink output (24V DC, 0.5A/point, 4.0A/common) SX5S-SBM16K

8-point sink input (24V DC)8-point transistor protect source output (24V DC, 0.5A/point, 4.0A/common) SX5S-SBM16P

DeviceNet

DC Input16-point source input (24V DC) SX5D-SBN16S16-point sink input (24V DC) SX5D-SBN16K

Relay Output 8-point relay output (240V AC/24V DC, 5A) SX5D-SBR08

Transistor Output16-point transistor sink output (24V DC, 0.5A/point, 6.0A/common) SX5D-SBT16K16-point transistor protect source output (24V DC, 0.5A/point, 6.0A/common) SX5D-SBT16P

DC InputTransistor Output

8-point source input (24V DC)8-point transistor sink output (24V DC, 0.5A/point, 4.0A/common) SX5D-SBM16K

8-point sink input (24V DC)8-point transistor protect source output (24V DC, 0.5A/point, 4.0A/common) SX5D-SBM16P

LonWorks

DC Input16-point source input (24V DC) SX5L-SBN16S16-point sink input (24V DC) SX5L-SBN16K

Relay Output 8-point relay output (240V AC/24V DC, 5A) SX5L-SBR08

Transistor Output16-point transistor sink output (24V DC, 0.5A/point, 6.0A/common) SX5L-SBT16K16-point transistor protect source output (24V DC, 0.5A/point, 6.0A/common) SX5L-SBT16P

DC InputTransistor Output

8-point source input (24V DC)8-point transistor sink output (24V DC, 0.5A/point, 4.0A/common) SX5L-SBM16K

8-point sink input (24V DC)8-point transistor protect source output (24V DC, 0.5A/point, 4.0A/common) SX5L-SBM16P

DeviceNet™ and LONWORKS® are trademarks of ODVA and Echelon, USA, respectively.

Key features:• INTERBUS I/O compatible with IDEC ONC remote I/O• Removable terminal blocks for easy maintenance• Finger-safe spring-up screw terminals• Compact body 75 × 132 × 48 mm• Mounting on a 35-mm-wide DIN rail or on a panel surface• Both inputs and outputs are available in sink or source types.

Relay outputs are also available.• The source output is protected against overload.

Designed to communicate with major industrial networks: INTERBUS, DeviceNet™ and LONWORKS®.

Page 48: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O

J-48 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Options (For INTERBUS, DeviceNet, and LONWORKS)

• One upper and one lower terminal blocks are supplied with every SX5 communication terminal.

Option (For DeviceNet)

• One network connector and connector mounting screws are supplied with every SX5D communication terminal.

Option (For LONWORKS)

• One network connector and connector mounting screws are supplied with every SX5L communication terminal.

Name Part No. RemarksTerminal Block 1 SX9Z-SS1 Upper terminal block for SX5*-SBN16*, -SBT16*, -SBM16*Terminal Block 2 SX9Z-SS2 Lower terminal block for SX5*-SBN16*, SBT16*Terminal Block 3 SX9Z-SS3 Lower terminal block for SX5*-SBM16*Terminal Block 4 SX9Z-SS4 Upper terminal block for SX5*-SBR08Terminal Block 5 SX9Z-SS5 Lower terminal block for SX5*-SBR08

DIN RailAluminum (1m) BNDN1000 35-mm-wide DIN rail available in US and Canada marketsSteel (1m) BAP1000 35-mm-wide DIN rail available in other than US and Canada marketsAluminum (1m) BAA1000 35-mm-wide DIN rail available in other than US and Canada markets

Mounting Clip BNL5 Used on DIN rail to fasten SX5 communication terminals

Name Part No. RemarksSX5D Network Connector SX9Z-CN5G2 Mounting screws are attached

Name Part No. RemarksSX5L Network Connector SX9Z-CN22 Mounting screws are attached

General Specifications

I/O Terminals

Rated Pow er Voltage 2 4 V D C

Allow a b le Vo l tage Range 19 to 30V DC ( including 5% r ipple)

IsolationI/O – Control Circuit Not isolated

Control Circuit – C o m m . Interface

I N T E R B U S , DeviceNet,PhotocouplerL O N W O R K S :Transformer coupl ing

Insulat ion Resistance Between pow er terminals and ground:1 0 0 MΩ min imum (500V DC megger )

Dielectr ic Strength

B e t ween pow er terminals and ground:1 0 0 0 V AC , 1 minuteB e t ween relay outputs and other l ive par ts: 2000V AC , 1 minute

Vibration Res is tance

Damage L im i ts Ampl i tude: 0.35 mm, 10 to 55 Hz

O p e rat ing Extremes(relay output)

Ampl i tude: 0.35 mm, 10 to 55 Hz(contact opening ≤ 1 msec when energ ized)

S h o ck Res is tance

Damage L im i ts 294 m/sec 2, 11 m/sec, sine half-wave pulse

O p e rat ing Extremes(relay output)

59 m/sec2 (in the direction of relay contact move-ment )98 m/sec2 (in other 5 directions)

O p e rating Te m p e r ature 0 to +55°C

O p e rat ing Humidi ty 30 to 90% RH (non-condens ing)

Storage Te m p e r ature –20 to +75°C

Storage Humid i ty 30 to 90% RH (non-condens ing)

Moun t ing Snap-on mount on 35-mm DIN railP anel-mount wi th M4 screw s

W eight (approx.) 2 8 0 g

Terminal Style R e m o va b le

Rated Insulat ion Voltage 2 5 0 V

Terminal Screw M3 (center to center : 7 .62 mm)

Number o f Poles 1 0

Rated Operat ing Current 7 A

Damage L im i ts 100 inser t ion/removal cycles

Finger Protect ion Yes

Network Status Indicators• INTERBUS

• DeviceNet

• LonWorks

Indicator Status DescriptionU L G r e e n O N P ow er ON

R C G r e e n O N Remote- in cable connected correct ly

B A G r e e nFlash Ready for transmit t ing data

O N Transmit t ing data

E R R e d O N Module error (available on protect output module only; pro-tect ion is reset when over load is removed)

R D R e d O N Remote-ou t cable disabled or network error

Indicator Status Description

P O W— O F F P ow er OFF

G r e e n O N P ow er ON

M N S

— O F F P ow er OFF o r Dup_MAC_ID test not completed

G r e e nFlash Nor mal opera t ion (communication not established)

O N Nor mal opera t ion (communicat ion established)

R e dFlash Minor fault ( temporary network error)

O N Cr itical fault

IO

— O F F I/O inactive ( c o m m unication not established)

G r e e nFlash I/O idle ( c o m m unicat ion established)

O N I/O active

R e d O N I/O error or communication interrup ted

Indicator Status DescriptionP O W G r e e n O N P ow er ON

R U N G r e e n O N Nor mal operation

E R R R e d O N C o m m unication error

I /O R e d O N I / O c o m munication error

S E R YellowO N Appl icat ion program not configured

F lash N e t w ork management no t configured

Page 49: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-49

J

Wiring SX5D and SX5L Cable Connector

• For wiring the communication cable connector on the SX5D and SX5L, use a cable of 24 AWG to 14 AWG (0.2 to 2.5 mm2). Strip the cable 7 mm from the end as shown below. Each communication terminal can accommodate up to two cables.

• When connecting two cables to one terminal, use cables of 24 AWG to 16 AWG (0.2 to 1.5 mm2).

• Do not solder the cable end for connection.• Tighten terminal screws on the communication cable connec-

tor to a torque of 0.5 to 0.6 N-m.• Tighten mounting screws on the communication cable con-

nector to a torque of 0.3 to 0.5 N-m.

7 mm

Terminal SymbolsSX5*-SBR08SX5*-SBM16*SX5*-SBN16*/SBT16* 7

7C3

+++

–––

000

11

C0

C5 C6 C7C4

221

33

C1

442

55

C2

663

157

804

91

1025

113

1246

135

1467

+ –POWER

+ –POWER

+ –POWERSX5*-SBR08

SX5*-SBM16*SX5*-SBN16*/SBT16*

Insertion Pin PositionsWhen purchasing terminal blocks separately, set the insertion pins asshown below.

SX5 Type No. Terminal Block Type No. Pin Positions

SX5*-SBN16*Upper SX9Z-SS1 B D F H

Lower SX9Z-SS2 A C E G

SX5*-SBR08 Upper SX9Z-SS4 B D E G

Lower SX9Z-SS5 A C F H

SX5*-SBT16*Upper SX9Z-SS1 B C E G

Lower SX9Z-SS2 A D F H

SX5*-SBM16*Upper SX9Z-SS1 B C F H

Lower SX9Z-SS3 A D E G

HE F GA B C D

A B C D E F G H

Dimensions

19m

m (

0.75

in)

3.6m

m (0

.14i

n)75

mm

(2.

95in

)132mm (5.24in) 19.3mm

48mm (1.89in)

(0.76in)

Safety Precautions• Turn power off to the SX5 communication terminals before start-

ing installation, removal, wiring, maintenance, and inspection of the SX5. Failure to turn power off may cause electrical shocks or fire hazard.

• Wire the SX5 correctly. Improper wiring may cause malfunction, abnormal heat, and fire hazard.

• Use wires of a proper size to meet voltage and current require-ments of the SX5. Tighten the terminal screws to a proper tighten-ing torque. A loose screw may cause abnormal heat and fire hazard. Check periodically to see if the screws are tightened securely.

• All SX5 communication terminals are manufactured under IDEC’s rigorous quality control system, but users must add a backup or fail safe provision to the control system using a SX5 communica-tion terminal in applications where heavy damage or personal injury might result should the SX5 fail.

Mounting Hole Layout (Top view)

4.5mm (0.18 in)

33mm

50m

m m

in.

0.5+–100mm 0.5+–

60m

m0.

5+ –

(3.94in ± 0.05) (1.3in ± 0.05)

(2.3

6in

± 0.

05)

(1.9

7 in

min

)

SX5 Series Smart I/O (General Information)

Page 50: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O

J-50 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Input/Output Requirements

• When connecting DC two-wire sensors to the SX5, the sensors must meet the following specifications. Operating voltage: 12 to 24V DCLeakage current: 1 mA maximumResidual voltage: 6V maximumON output current: 5.5 mA minimum (at 24V DC)

The sensor must have an ON output current of 4 mA at the minimum. If the sensor does not meet this lower limit, connect a bleeder resis-tor as shown below. But if the residual voltage is 6V or less, the sen-sor can still be used although the ON output may be less than 3.5 mA.

• Use the following formula for calculating the bleeder resistance if needed.

Vcc: Power voltage

I: Lower limit of DC two-wire sensor ON output (mA)• Do not apply a DC power voltage to the output circuit without con-

necting a load, otherwise internal elements will be damaged (except for the protect source output type).

• When an overload or short circuit occurs, the protect source output shuts down the output immediately to protect the internal elements from permanent damage. When the cause of the overload or short cir-cuit is removed, the SX5 will restore normal operation automatically.

• When the capacity of main power supply is small, the overcurrent protection of the main supply may reduce power supply to the SX5, then the SX5 will stop operation, causing a network error.

• When using the relay output in environments where extraneous noises exist or inductive loads are switched frequently, generating high reverse emf, connect contact protection elements to the output terminals and across the load as shown below.

Response Time• The response time of the SX5 system varies greatly depending on

such factors as the quantity of modules and cable length. The accu-rate response time can be confirmed on the actual network system.

Terminators• DeviceNet and LONWORKS networks require terminators. For details

about the terminators, see publications on DeviceNet or LONWORKS, or consult IDEC.

+ – Input

DC two-wire

Source Input Type

R

I

sensor

+ – Input

Sink Input Type

R

I

DC two-wire sensor

R (kΩ)Vcc 6–

I 4–-------------------=

Varistor System

SX5*-SBR08 SX5*-SBR08

LoadC0

OUT0

Load

OUT0

C0

• For both AC and DC power voltages • For DC power voltage only

+

Diode and Zener Diode System

LoadPower

LoadPower

Operating InstructionsInstallation and Wiring (All SX5 Modules)

• Turn power off to the SX5 before installing or removing the con-nector or the detachable terminal block.

• Tighten the terminal screws to a torque of 0.6 to 1.0 N-m.• When mounting the SX5 on a panel, tighten the mounting screws

to a torque of 1.0 to 1.3 N-m. Recommended mounting screw: M4• When mounting the SX5 on a 35-mm-wide DIN rail, put the SX5

on the DIN rail and press the SX5 towards the rail to lock. To remove, pull out the latch from the bottom of the module using a screwdriver and release the SX5. To re-attach, push back the latch into place and snap on the SX5 again.

• The upper-right mounting hole has a FG terminal. Connect the FG terminal and control box. Use a wire of 4 mm2 at the minimum to connect the relay terminal block with the safety ground. When mounting on a 35-mm-wide DIN rail, a steel DIN rail is recom-mended for easy grounding.

Mounting on Steel DIN Rail (Recommended)• A metal grounding clip is provided on the back of the SX5S and

SX5L to contact with a DIN rail. When mounting the SX5 on a steel DIN rail, the metal grounding clip comes in electrical contact with the DIN rail. Connect the DIN rail to a proper ground.

Mounting on Aluminum DIN Rail• The upper-right mounting hole has a FG terminal. When mounting

the SX5 on an aluminum DIN rail, connect the FG terminal to the panel using the attached M4 screw and nut, and connect the panel to a proper ground.

Panel Mounting• When mounting the SX5 on a panel surface, attach a crimping

terminal of a grounding wire to the FG terminal on the upper-right mounting hole of the SX5, and insert a screw through the mount-ing hole. Connect the grounding wire to the panel and connect the panel to a proper ground.

• Note: For secure electrical connection, remove coating from the grounding area on the panel.

Terminal Block• The SX5 uses detachable terminal blocks. To remove and attach

the terminal block, follow the procedures below.• To remove the terminal block, squeeze both latches on top of the

block inward to unlock the block from the socket.• To reattach the terminal block, place the block in the socket with

the latches opened and press the block until it bottoms in the socket, then the latches snap outward to lock the terminal block.

• Insertion pins are positioned on the base of the terminal block and inside the socket to prevent insertion of invalid blocks into the socket. The pins are keyed to ensure correct matching of block and socket, and prevent swapping of upper and lower blocks.

• When the block does not fit into the socket properly, check to see if the pin positions on the block agree with the pin-slot arrange-ment in the socket. If the pins and the pin slots are in matching positions, check for any chips and obstacles in the socket.

• When cutting cables or wires, keep the SX5 out of the way to pre-vent ingress of wire chips and fragments.

• When wiring the screw terminals using crimping terminals, use crimping terminals of the dimensions shown below. Each screw terminal can accommodate up to two crimping terminals.

• Note: Spade crimping terminals can also be used.

ø3.2 min.

3.0 max. 5.2 min.

6 max.

(Dimensions are in mm)

Page 51: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (INTERBUS)

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-51

J

16-PointTransistor Input Modules (INTERBUS)

Input Type Part Number

Source SX5S-SBN16SSink SX5S-SBN16K

DC Input Type

Part No. SX5S–SBN16S SX5S–SBN16KInput Type DC source input DC sink inputInput Logic Active Low Active HighInput Points 16 points

Input TypeNo-voltage input (2-wire DC sensor, 3-wire NPN sensor, no-voltage contact)

No-voltage input (2-wire DC sensor, 3-wire PNP sensor, no-voltage contact)

Rated Input Voltage 24V DCInput Voltage Range 0 to the power voltageTurn ON Voltage 6V maximum 10V minimumTurn OFF Voltage 10V minimum 6V maximumInput Current 6 mA/24V DC 6 mA/24V DCCommon 1 commonCurrent Draw 200 mA 200 mA

Communication Speed and Distance

Bus Baud Rate Transmission Distance

INTERBUS 500 kbps 400m (between slaves)12.8 km (total length)

Communication Cable

Bus Network I/F Connector (on the module) Cable

INTERBUS9-pin D-sub connectorRemote-in: MaleRemote-out: Female

INTERBUS cable

Terminal Arrangement

Upper Terminal Block (SX9Z-SS1)

Lower Terminal Block (SX9Z-SS2)

Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 IN0 8 IN81 IN1 9 IN92 IN2 10 IN103 IN3 11 IN114 IN4 12 IN125 IN5 13 IN136 IN6 14 IN147 IN7 15 IN15

Communication Configuration

Type No. ID Code Station Type Data Length Data Address

SX5S-SBN16SSX5S-SBN16K 02hex Remote Bus Station with

Digital Inputs1 word(16 inputs)

Byte 1

7 0

Byte 0

15 8

Key features include:• Communicate with INTERBUS network• 16-point input modules (sink/source)• Removable terminal blocks• Use as remote I/O on ONC

Page 52: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (INTERBUS)

J-52 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

DC Power

ContactSwitch

ContactSwitch

3.8 kΩ

3.8 kΩ

3.8 kΩ

3.8 kΩ

++

–Blue (White)

IN0Black (White)

Brown (Red)

Network

Brown (Black)IN1

Blue (Black)

IN14

IN15

ControlCircuit

DC3-wireSensorNPN

Output

DC2-wireSensor

CommunicationInterface

3.8 kΩ

3.8 kΩ

3.8 kΩ

3.8 kΩ

ContactSwitch

ContactSwitch

++

––

Brown (Red)

Blue (Black)

IN0Black (White)

IN1

Brown (White)

Blue (Black)

IN15

IN14CommunicationInterface

ControlCircuit

DCPower

Network

DC3-wireSensor

PNPOutput

DC2-wireSensor

16-Point Source Input

16-Point Sink Input

Wiring INTERBUS Cable

• Do not install the INTERBUS cable in parallel with or close to motor lines. Keep the INTERBUS cable away from noise sources.

• Turn power off before wiring the INTERBUS cable. Make sure of correct wiring before turning power on.

• Use a special INTERBUS cable and connect the cable as shown below. Use D-sub connectors made of metal or made of plastic with metallic plating. Connect the cable shield with the connector housing electrically.

• INTERBUS Cable Connector Pinouts

• Stripping and Clamping Cable Ends

• Leave open the remote out connector at the last station in the network.• Supply power to each slave station or to each group of stations sepa-

rately.• Master and slave stations may be powered up in any order. But, if a

slave station is not powered up while the master is in preparation for transmission, a network error will result.

• Causes of network errors include disconnection or short-circuit of the network cable, strong external noise, invalid command sent to the mas-ter station, momentary power voltage drop below the minimum power voltage, faulty transmission line, incorrect cable, and transmission longer than the rated distance.

• When a network error occurs, all outputs are turned off.• For further information on INTERBUS, read documents published by the

INTERBUS CLUB.

16

9 5

/DO 6DO 1/DI 7DI 2COM 3

95

Housing

GreenYellowPinkGray

Brown

6 /DO1 DO7 /DI2 DI3 COM

HousingSolderedSide

SolderedSide

Bridge pins 5 and 9 inside the housing of the male connector.

1 6

95

D-sub 9-pin Male Connector

D-sub 9-pin Female Connector

3 8

20

First, strip the cable sheath 20 mm from both ends of the cable and shorten the braided screen by 12 mm.Bare the core ends 3 mm.

Next, place the braided screen evenly around the cable sheath.Clamp the shield under the cable grip in the connector housing for conduc-tive connection with the housing.

SX5S-SBN16K

SX5S-SBN16S

Page 53: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (INTERBUS)

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-53

J

8-Point Relay Output Module (INTERBUS)

Output Type Part Number

Relay Output SX5S-SBR08

Key features include:• Communicate with INTERBUS network• 8-point relay output module• Handles current up to 5A per point• Removable terminal blocks• Use as remote I/O on ONC

Communication Speed and Distance

Bus Baud Rate Transmission Distance

INTERBUS 500 kbps 400m (between slaves)12.8 km (total length)

Communication Cable

Bus Network I/F Connector (on the module) Cable

INTERBUS9-pin D-sub connectorRemote-in: MaleRemote-out: Female

INTERBUS cable

Terminal Arrangement

Upper Terminal Block (SX9Z-SS4)

Lower Terminal Block (SX9Z-SS5)

Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 OUT0 4 OUT4

C0 COM0 C4 COM41 OUT1 5 OUT5

C1 COM1 C5 COM52 OUT2 6 OUT6

C2 COM2 C6 COM63 OUT3 7 OUT7

C3 COM3 C7 COM7

Communication Configuration

Type No. ID Code Station Type Data Length Data Address

SX5S-SBR08 01hex Remote Bus Station with Digital Outputs

1 word(8 outputs)

Byte 1

7 0 Unused

Relay Output Type

Rated Relay Contact

Part No. SX5S–SBR08Output Type Relay outputOutput Points 8 pointsOutput Type 1NO relay contactRated Load Voltage 250V AC, 24V DCMaximum Load Current 5A/point Commons/Current 8 commons/5ACurrent Draw 140 mABuilt-in Relay PCB mount, not replaceable

Maximum Applicable Voltage 250V AC, 125V DCMaximum Current 5ARated Load (resistive load) 250V AC/5A, 24V DC/5AMinimum Applicable Load 1V DC / 1mA

LifeMechanical 20,000,000 operations minimum

(18,000 operations/hour)

Electrical See Electrical Life Curve on next page (1,800 operations/hour)

Page 54: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (INTERBUS)

J-54 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Load PowerPilotLight

Load Power

Solenoid

PilotLight

Load Power

Load Power

Solenoid

++

Network

OUT1COM1

COM7OUT7

OUT0COM0

COM6OUT6

ControlCircuit

CommunicationInterface

DCPower

––

8-Point Relay Output Wiring INTERBUS Cable

• Do not install the INTERBUS cable in parallel with or close to motor lines. Keep the INTERBUS cable away from noise sources.

• Turn power off before wiring the INTERBUS cable. Make sure of correct wiring before turning power on.

• Use a special INTERBUS cable and connect the cable as shown below. Use D-sub connectors made of metal or made of plastic with metallic plat-ing. Connect the cable shield with the connector housing electrically.

• INTERBUS Cable Connector Pinouts

• Stripping and Clamping Cable Ends

• Leave open the remote out connector at the last station in the network.• Supply power to each slave station or to each group of stations sepa-

rately.• Master and slave stations may be powered up in any order. But, if a slave

station is not powered up while the master is in preparation for transmis-sion, a network error will result.

• Causes of network errors include disconnection or short-circuit of the net-work cable, strong external noise, invalid command sent to the master station, momentary power voltage drop below the minimum power volt-age, faulty transmission line, incorrect cable, and transmission longer than the rated distance.

• When a network error occurs, all outputs are turned off.• For further information on INTERBUS, read documents published by the

INTERBUS CLUB.

16

9 5

/DO 6DO 1/DI 7DI 2COM 3

95

Housing

GreenYellowPinkGray

Brown

6 /DO1 DO7 /DI2 DI3 COM

HousingSolderedSide

SolderedSide

Bridge pins 5 and 9 inside the housing of the male connector.

1 6

95

D-sub 9-pin Male Connector

D-sub 9-pin Female Connector

3 8

20

First, strip the cable sheath 20 mm from both ends of the cable and shorten the braided screen by 12 mm.Bare the core ends 3 mm.

Next, place the braided screen evenly around the cable sheath.Clamp the shield under the cable grip in the connector housing for conduc-tive connection with the housing.

Reference Data Electrical Life Curve: Relay in SX5S-SBR08

Note 1: AC/DC Resistive LoadOperating frequency: 1800 operations/hourDuty ratio: 40%

Note 2: AC Inductive Load

Note 3: DC Inductive LoadOperating frequency: 1800 operations/hourDuty ratio: 40%Time constant: L/R =15 msec

Line MakingCurrent

BreakingCurrent Frequency Duty

Ratio

Solid 10 I, cos θ = 0.7 I, cos θ = 0.3 to 0.4 1800 operations/h40%

Dashed 5 I, cos θ = 0.7 I, cos θ = 0.3 to 0.4 300 operations/h

100

500

50

10

0.05 0.1 1 2 3 50.2 0.3 0.5

110V ACInductive

220V ACInductive

220V AC Resistive110V AC Resistive

AC Load

Life

(x

1000

0 op

erat

ions

)

Load Current (A)

100

500

50

10

0.05 0.1 1 2 3 50.2 0.3 0.5

110V DCInductive

24V DC Resistive

48V DC Resistive

24V DC Inductive

Load Current (A)

110 DC Resistive

Life

(x

1000

0 op

erat

ions

)

48V DC Inductive

DC Load

SX5S-SBR08

Page 55: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (INTERBUS)

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-55

J

16-Point Transistor Output Modules (INTERBUS)

Key features include:• Communicate with INTERBUS network• 16-point transistor output modules (sink/source)• The source output is protected against overload• Removable terminal blocks• Use as remote I/O on ONC

Transistor Output Type

Part No. SX5S–SBT16K SX5S–SBT16P

Output Type Sink output Protect source output

Output Points 16 points

Output Type N-channel MOS open drain

P-channel MOS open drain

Rated Load Voltage 24V DC

Load Voltage Range 3 to 30V DC 19 to 30V DC

Maximum Load Current 0.5A/point

Commons/Current 1 common/6A

Short-circuit Protection No Yes

Current Draw 155 mA 180 mA

Communication Speed and Distance

Bus Baud Rate Transmission Distance

INTERBUS 500 kbps 400m (between slaves)12.8 km (total length)

Communication Cable

Bus Network I/F Connector (on the module) Cable

INTERBUS9-pin D-sub connectorRemote-in: MaleRemote-out: Female

INTERBUS cable

Terminal Arrangement

Upper Terminal Block (SX9Z-SS1)

Lower Terminal Block (SX9Z-SS2)

Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 OUT0 8 OUT81 OUT1 9 OUT92 OUT2 10 OUT103 OUT3 11 OUT114 OUT4 12 OUT125 OUT5 13 OUT136 OUT6 14 OUT147 OUT7 15 OUT15

Communication Configuration

Part No. ID Code Station Type Data Length Data Address

SX5S-SBT16KSX5S-SBT16P 01hex Remote Bus Station with

Digital Outputs1 word(16 outputs)

Byte 1

7 0

Byte 0

15 8

Output Type Part Number

Sink SX5S-SBT16KSource SX5S-SBT16P

Page 56: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (INTERBUS)

J-56 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Wiring INTERBUS Cable

• Do not install the INTERBUS cable in parallel with or close to motor lines. Keep the INTERBUS cable away from noise sources.

• Turn power off before wiring the INTERBUS cable. Make sure of correct wiring before turning power on.

• Use a special INTERBUS cable and connect the cable as shown below. Use D-sub connectors made of metal or made of plastic with metallic plating. Connect the cable shield with the connector housing electri-cally.

• INTERBUS Cable Connector Pinouts

• Stripping and Clamping Cable Ends

• Leave open the remote out connector at the last station in the network.• Supply power to each slave station or to each group of stations sepa-

rately.• Master and slave stations may be powered up in any order. But, if a

slave station is not powered up while the master is in preparation for transmission, a network error will result.

• Causes of network errors include disconnection or short-circuit of the network cable, strong external noise, invalid command sent to the mas-ter station, momentary power voltage drop below the minimum power voltage, faulty transmission line, incorrect cable, and transmission longer than the rated distance.

• When a network error occurs, all outputs are turned off.• For further information on INTERBUS, read documents published by the

INTERBUS CLUB.

16

9 5

/DO 6DO 1/DI 7DI 2COM 3

95

Housing

GreenYellowPinkGray

Brown

6 /DO1 DO7 /DI2 DI3 COM

HousingSolderedSide

SolderedSide

Bridge pins 5 and 9 inside the housing of the male connector.

1 6

95

D-sub 9-pin Male Connector

D-sub 9-pin Female Connector

3 8

20

First, strip the cable sheath 20 mm from both ends of the cable and shorten the braided screen by 12 mm.Bare the core ends 3 mm.

Next, place the braided screen evenly around the cable sheath.Clamp the shield under the cable grip in the connector housing for conduc-tive connection with the housing.

16-Point Transistor Sink Output

16-Point Transistor Protect Source Output

Relay

PilotLight

++

––

OUT15

ControlCircuit

Pro

tect

ion

Circ

uit

Pro

tect

ion

Circ

uit

DCPower

CommunicationInterface

Network

OUT0

SX5S-SBT16P

• SX5*-SBT16K

Relay

PilotLight

Relay

++

––

OUT0

OUT1

DCPower

ControlCircuit

CommunicationInterface

Network

OUT15

SX5S-SBT16K

Page 57: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (INTERBUS)

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-57

J

8-Point Source Input & 8-Point Transistor Sink Output Module (INTERBUS)

Key features include:• Communicate with INTERBUS network• 8-point source input and 8-point sink output module• Removable terminal blocks• Use as remote I/O on ONC

Communication Speed and Distance

Bus Baud Rate Transmission Distance

INTERBUS 500 kbps 400m (between slaves)12.8 km (total length)

Communication Cable

Bus Network I/F Connector (on the module) Cable

INTERBUS9-pin D-sub connectorRemote-in: MaleRemote-out: Female

INTERBUS cable

Terminal Arrangement

Upper Terminal Block (SX9Z-SS1)

Lower Terminal Block (SX9Z-SS3)

Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 IN0 0 OUT01 IN1 1 OUT12 IN2 2 OUT23 IN3 3 OUT34 IN4 4 OUT45 IN5 5 OUT56 IN6 6 OUT67 IN7 7 OUT7

Communication Configuration

Type No. ID Code Station Type Data Length Data Address

SX5S-SBM16K 03hex Remote Bus Station with Digital I/Os

1 byte(8 in / 8 out) Byte 0 (Output)

7 0

Byte 0 (Input)

7 0

Input/Output Type Part Number

Source Input/Sink Output SX5S-SBM16K

DC Input / Transistor Sink Output Type

Part No. SX5S–SBM16KI/O Type Source input / sink output

InputInput Logic Active Low

Input Points 8 points

Input TypeNo-voltage input

(2-wire DC sensor, 3-wire NPN sensor, no-voltage contact)

Rated Input Voltage 24V DC

Input Voltage Range 0 to the power voltage

ON Voltage 6V maximum

OFF Voltage 10V minimum

Input Current 6 mA/24V DC

Common 1 common

OutputOutput Points 8 points

Output Type N-channel MOS open drain

Rated Load Voltage 24V DC

Load Voltage Range 3 to 30V DC

Maximum Load Current 0.5A/point

Commons/Current 1 common/4A

Short-circuit Protection No

Current Draw 180 mA

Page 58: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (INTERBUS)

J-58 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

DC Power

ContactSwitch

ContactSwitch

3.8 kΩ

3.8 kΩ

3.8 kΩ

3.8 kΩ

++

–Blue (White)

IN0Black (White)

Brown (Red)

Network

Brown (Black)IN1

Blue (Black)

IN6

IN7

ControlCircuit

DC3-wireSensorNPN

Output

DC2-wireSensor

CommunicationInterface

Wiring INTERBUS Cable

• Do not install the INTERBUS cable in parallel with or close to motor lines. Keep the INTERBUS cable away from noise sources.

• Turn power off before wiring the INTERBUS cable. Make sure of correct wiring before turning power on.

• Use a special INTERBUS cable and connect the cable as shown below. Use D-sub connectors made of metal or made of plastic with metallic plating. Connect the cable shield with the connector housing electri-cally.

• INTERBUS Cable Connector Pinouts

• Stripping and Clamping Cable Ends

• Leave open the remote out connector at the last station in the network.• Supply power to each slave station or to each group of stations sepa-

rately.• Master and slave stations may be powered up in any order. But, if a

slave station is not powered up while the master is in preparation for transmission, a network error will result.

• Causes of network errors include disconnection or short-circuit of the network cable, strong external noise, invalid command sent to the mas-ter station, momentary power voltage drop below the minimum power voltage, faulty transmission line, incorrect cable, and transmission longer than the rated distance.

• When a network error occurs, all outputs are turned off.• For further information on INTERBUS, read documents published by the

16

9 5

/DO 6DO 1/DI 7DI 2COM 3

95

Housing

GreenYellowPinkGray

Brown

6 /DO1 DO7 /DI2 DI3 COM

HousingSolderedSide

SolderedSide

Bridge pins 5 and 9 inside the housing of the male connector.

1 6

95

D-sub 9-pin Male Connector

D-sub 9-pin Female Connector

3 8

20

First, strip the cable sheath 20 mm from both ends of the cable and shorten the braided screen by 12 mm.Bare the core ends 3 mm.

Next, place the braided screen evenly around the cable sheath.Clamp the shield under the cable grip in the connector housing for conduc-tive connection with the housing.

8-Point Source Input

8-Point Transistor Sink Output

Relay

PilotLight

Relay

++

––

OUT0

OUT1

DCPower

ControlCircuit

CommunicationInterface

Network

OUT7

Page 59: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (INTERBUS)

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-59

J

8-Point Sink Input & 8-Point Transistor Source Output Module (INTERBUS)

Key features include:• Communicate with INTERBUS network• 8-point sink input and 8-point source output module• Removable terminal blocks• Use as remote I/O on ONC• Source output short circuit and overload protected

Communication Speed and Distance

Bus Baud Rate Transmission Distance

INTERBUS 500 kbps 400m (between slaves)12.8 km (total length)

Communication Cable

Bus Network I/F Connector (on the module) Cable

INTERBUS9-pin D-sub connectorRemote-in: MaleRemote-out: Female

INTERBUS cable

Terminal Arrangement

Upper Terminal Block (SX9Z-SS1)

Lower Terminal Block (SX9Z-SS3)

Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 IN0 0 OUT01 IN1 1 OUT12 IN2 2 OUT23 IN3 3 OUT34 IN4 4 OUT45 IN5 5 OUT56 IN6 6 OUT67 IN7 7 OUT7

Communication Configuration

Type No. ID Code Station Type Data Length Data Address

SX5S-SBM16P 03hex Remote Bus Station with Digital I/Os

1 byte(8 in / 8 out) Byte 0 (Output)

7 0

Byte 0 (Input)

7 0

Input/Output Type Part Number

Sink Input/Source Output SX5S-SBM16P

DC Input / Transistor Source Output Type

Part No. SX5S–SBM16PI/O Type Sink input / protect source output

InputInput Logic Active High

Input Points 8 points

Input TypeNo-voltage input

(2-wire DC sensor, 3-wire PNP sensor, no-voltage contact)

Rated Input Voltage 24V DC

Input Voltage Range 0 to the power voltage

ON Voltage 10V minimum

OFF Voltage 6V maximum

Input Current 6 mA/24V DC

Common 1 common

OutputOutput Points 8 points

Output Type P-channel MOS open drain

Rated Load Voltage 24V DC

Load Voltage Range 19 to 30V DC

Maximum Load Current 0.5A/point

Commons/Current 1 common/4A

Short-circuit Protection Yes

Current Draw 180 mA

Page 60: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (INTERBUS)

J-60 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Wiring INTERBUS Cable

• Do not install the INTERBUS cable in parallel with or close to motor lines. Keep the INTERBUS cable away from noise sources.

• Turn power off before wiring the INTERBUS cable. Make sure of cor-rect wiring before turning power on.

• Use a special INTERBUS cable and connect the cable as shown below. Use D-sub connectors made of metal or made of plastic with metallic plating. Connect the cable shield with the connector housing electrically.

• INTERBUS Cable Connector Pinouts

• Stripping and Clamping Cable Ends

• Leave open the remote out connector at the last station in the net-work.

• Supply power to each slave station or to each group of stations sepa-rately.

• Master and slave stations may be powered up in any order. But, if a slave station is not powered up while the master is in preparation for transmission, a network error will result.

• Causes of network errors include disconnection or short-circuit of the network cable, strong external noise, invalid command sent to the master station, momentary power voltage drop below the minimum power voltage, faulty transmission line, incorrect cable, and transmis-sion longer than the rated distance.

• When a network error occurs, all outputs are turned off.• For further information on INTERBUS, read documents published by

the INTERBUS CLUB.

16

9 5

/DO 6DO 1/DI 7DI 2COM 3

95

Housing

GreenYellowPinkGray

Brown

6 /DO1 DO7 /DI2 DI3 COM

HousingSolderedSide

SolderedSide

Bridge pins 5 and 9 inside the housing of the male connector.

1 6

95

D-sub 9-pin Male Connector

D-sub 9-pin Female Connector

3 8

20

First, strip the cable sheath 20 mm from both ends of the cable and shorten the braided screen by 12 mm.Bare the core ends 3 mm.

Next, place the braided screen evenly around the cable sheath.Clamp the shield under the cable grip in the connector housing for conduc-tive connection with the housing.

8-Point Sink Input

8-Point Transistor Protect Source Output

3.8 kΩ

3.8 kΩ

3.8 kΩ

3.8 kΩ

ContactSwitch

ContactSwitch

++

––

Brown (Red)

Blue (Black)

IN0Black (White)

IN1

Brown (White)

Blue (Black)

IN7

IN6CommunicationInterface

ControlCircuit

DCPower

Network

DC3-wireSensor

PNPOutput

DC2-wireSensor

Relay

PilotLight

++

––

OUT7

ControlCircuit

Pro

tect

ion

Circ

uit

Pro

tect

ion

Circ

uit

DCPower

CommunicationInterface

Network

OUT0

Page 61: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (DeviceNet)

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-61

J

16-Point Transistor Input Modules (DeviceNet)

Input Type Part Number

Source SX5D-SBN16SSink SX5D-SBN16K

Key features include:• Communicate with DeviceNet network• 16-point input module (sink/source)• Removable terminal blocks

DC Input Type

Part No. SX5D–SBN16S SX5D–SBN16KInput Type DC source input DC sink input

Input Logic Active Low Active High

Input Points 16 points

Input TypeNo-voltage input

(2-wire DC sensor, 3-wire NPN sensor, no-voltage contact)

No-voltage input (2-wire DC sensor, 3-wire PNP sensor, no-voltage contact)

Rated Input Voltage 24V DC

Input Voltage Range 0 to the power voltage

Turn ON Voltage 6V maximum 10V minimum

Turn OFF Voltage 10V minimum 6V maximum

Input Current 6 mA/24V DC 6 mA/24V DC

Common 1 common

Current Draw 190 mA 170 mA

Communication Speed and Distance

Bus Transmission RateTransmission Distance

Thick Cable Thin Cable

DeviceNet125k baud 500m 100m250k baud 250m 100m500k baud 100m 100m

Communication Cable

Bus Network I/F Connector (on the module) Cable

DeviceNetPhoenix Contact5-pin connector MSTBV2.5/5-GF-5.08AU

DeviceNet cable

Terminal Arrangement

Upper Terminal Block (SX9Z-SS1)

Lower Terminal Block (SX9Z-SS2)

Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 IN0 8 IN81 IN1 9 IN92 IN2 10 IN103 IN3 11 IN114 IN4 12 IN125 IN5 13 IN136 IN6 14 IN147 IN7 15 IN15

Communication Configuration

[Baud Rate Selection][Output Hold or Load Off] [System Reserve]Baud Rate DR0 DR1

125 kbps OFF OFF250 kbps ON OFF500 kbps OFF ON(Selection Prohibited) ON ON

Output/Load H/LLOAD OFF OFFHOLD ON

System Reserve NOFixed to OFF(Selection Prohibited) ON

Page 62: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (DeviceNet)

J-62 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

DC Power

ContactSwitch

ContactSwitch

3.8 kΩ

3.8 kΩ

3.8 kΩ

3.8 kΩ

++

–Blue (White)

IN0Black (White)

Brown (Red)

Network

Brown (Black)IN1

Blue (Black)

IN14

IN15

ControlCircuit

DC3-wireSensorNPN

Output

DC2-wireSensor

CommunicationInterface

–3.8 kΩ

3.8 kΩ

3.8 kΩ

3.8 kΩ

ContactSwitch

ContactSwitch

++

––

Brown (Red)

Blue (Black)

IN0Black (White)

IN1

Brown (White)

Blue (Black)

IN15

IN14CommunicationInterface

ControlCircuit

DCPower

Network

DC3-wireSensor

PNPOutput

DC2-wireSensor

16-Point Source Input 16-Point Sink Input

Wiring DeviceNet Cable

• DeviceNet requires two power voltages; one for communication and the other for internal circuit and load.

• Use a special DeviceNet cable for connecting to the DeviceNet network.• Connect the core wires of the cable to terminals identified by labels of

matching colors.• DeviceNet Cable

Cable Part No. MakerThick Cable 1485C-P1A50

Rockwell AutomationThin Cable 1485C-P1-C150

Node Address SelectionNode Address NA0 NA1 NA2 NA3 NA4 NA5 Node Address NA0 NA1 NA2 NA3 NA4 NA5

0 OFF OFF OFF OFF OFF OFF 32 OFF OFF OFF OFF OFF ON

1 ON OFF OFF OFF OFF OFF 33 ON OFF OFF OFF OFF ON

2 OFF ON OFF OFF OFF OFF 34 OFF ON OFF OFF OFF ON

3 ON ON OFF OFF OFF OFF 35 ON ON OFF OFF OFF ON

4 OFF OFF ON OFF OFF OFF 36 OFF OFF ON OFF OFF ON

5 ON OFF ON OFF OFF OFF 37 ON OFF ON OFF OFF ON

6 OFF ON ON OFF OFF OFF 38 OFF ON ON OFF OFF ON

7 ON ON ON OFF OFF OFF 39 ON ON ON OFF OFF ON

8 OFF OFF OFF ON OFF OFF 40 OFF OFF OFF ON OFF ON

9 ON OFF OFF ON OFF OFF 41 ON OFF OFF ON OFF ON

10 OFF ON OFF ON OFF OFF 42 OFF ON OFF ON OFF ON

11 ON ON OFF ON OFF OFF 43 ON ON OFF ON OFF ON

12 OFF OFF ON ON OFF OFF 44 OFF OFF ON ON OFF ON

13 ON OFF ON ON OFF OFF 45 ON OFF ON ON OFF ON

14 OFF ON ON ON OFF OFF 46 OFF ON ON ON OFF ON

15 ON ON ON ON OFF OFF 47 ON ON ON ON OFF ON

16 OFF OFF OFF OFF ON OFF 48 OFF OFF OFF OFF ON ON

17 ON OFF OFF OFF ON OFF 49 ON OFF OFF OFF ON ON

18 OFF ON OFF OFF ON OFF 50 OFF ON OFF OFF ON ON

19 ON ON OFF OFF ON OFF 51 ON ON OFF OFF ON ON

20 OFF OFF ON OFF ON OFF 52 OFF OFF ON OFF ON ON

21 ON OFF ON OFF ON OFF 53 ON OFF ON OFF ON ON

22 OFF ON ON OFF ON OFF 54 OFF ON ON OFF ON ON

23 ON ON ON OFF ON OFF 55 ON ON ON OFF ON ON

24 OFF OFF OFF ON ON OFF 56 OFF OFF OFF ON ON ON

25 ON OFF OFF ON ON OFF 57 ON OFF OFF ON ON ON

26 OFF ON OFF ON ON OFF 58 OFF ON OFF ON ON ON

27 ON ON OFF ON ON OFF 59 ON ON OFF ON ON ON

28 OFF OFF ON ON ON OFF 60 OFF OFF ON ON ON ON

29 ON OFF ON ON ON OFF 61 ON OFF ON ON ON ON

30 OFF ON ON ON ON OFF 62 OFF ON ON ON ON ON

31 ON ON ON ON ON OFF 63 ON ON ON ON ON ON

SX5D-SBN16S SX5D-SBN16K

Page 63: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (DeviceNet)

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-63

J

8-Point Relay Output Module (DeviceNet)

Output Type Part Number

Relay Output SX5D-SBR08

Key features include:• Communicate with DeviceNet network• 8-point relay output module• Handles current up to 5A per point• Removable terminal blocks

Terminal Arrangement

Upper Terminal Block (SX9Z-SS4)

Lower Terminal Block (SX9Z-SS5)

Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 OUT0 4 OUT4

C0 COM0 C4 COM41 OUT1 5 OUT5

C1 COM1 C5 COM52 OUT2 6 OUT6

C2 COM2 C6 COM63 OUT3 7 OUT7

C3 COM3 C7 COM7

Communication Speed and Distance

Bus Transmission RateTransmission Distance

Thick Cable Thin Cable

DeviceNet125k baud 500m 100m250k baud 250m 100m500k baud 100m 100m

Communication Cable

Bus Network I/F Connector (on the module) Cable

DeviceNetPhoenix Contact5-pin connector MSTBV2.5/5-GF-5.08AU

DeviceNet cable

Communication Configuration

[Baud Rate Selection]

[Output Hold or Load Off][System Reserve]

Baud Rate DR0 DR1125 kbps OFF OFF250 kbps ON OFF500 kbps OFF ON(Selection Prohibited) ON ON

Output/Load H/LLOAD OFF OFFHOLD ON

System Reserve NOFixed to OFF(Selection Prohibited) ON

Relay Output Type

Rated Relay Contact

Part No. SX5D–SBR08Output Type Relay outputOutput Points 8 pointsOutput Type 1NO relay contactRated Load Voltage 250V AC, 24V DCMaximum Load Current 5A/point Commons/Current 8 commons/5ACurrent Draw 120 mABuilt-in Relay PCB mount, not replaceable

Maximum Applicable Voltage 250V AC, 125V DCMaximum Current 5ARated Load (resistive load) 250V AC/5A, 24V DC/5AMinimum Applicable Load 1V DC / 1mA

LifeMechanical 20,000,000 operations minimum

(18,000 operations/hour)

Electrical See Electrical Life Curve on next page (1,800 operations/hour)

Page 64: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (DeviceNet)

J-64 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Wiring DeviceNet Cable

• DeviceNet requires two power voltages; one for communication and the other for internal circuit and load.

• Use a special DeviceNet cable for connecting to the DeviceNet network.• Connect the core wires of the cable to terminals identified by labels of

matching colors.• DeviceNet Cable

Cable Type No. MakerThick Cable 1485C-P1A50

Rockwell AutomationThin Cable 1485C-P1-C150

8-Point Relay Output

Load PowerPilotLight

Load Power

Solenoid

PilotLight

Load Power

Load Power

Solenoid

++

Network

OUT1COM1

COM7OUT7

OUT0COM0

COM6OUT6

ControlCircuit

CommunicationInterface

DCPower

––

Reference Data

Electrical Life Curve: Relay in SX5D-SBR08

Note 1: AC/DC Resistive LoadOperating frequency: 1800 operations/hourDuty ratio: 40%

Note 2: AC Inductive Load

Note 3: DC Inductive LoadOperating frequency: 1800 operations/hourDuty ratio: 40%Time constant: L/R =15 msec

Line MakingCurrent

BreakingCurrent Frequency Duty

RatioSolid 10 I, cos θ = 0.7 I, cos θ = 0.3 to 0.4 1800 operations/h

40%Dashed 5 I, cos θ = 0.7 I, cos θ = 0.3 to 0.4 300 operations/h

100

500

50

10

0.05 0.1 1 2 3 50.2 0.3 0.5

110V ACInductive

220V ACInductive

220V AC Resistive110V AC Resistive

AC Load

Life

(x

1000

0 op

erat

ions

)

Load Current (A)

100

500

50

10

0.05 0.1 1 2 3 50.2 0.3 0.5

110V DCInductive

24V DC Resistive

48V DC Resistive

24V DC Inductive

Load Current (A)

110 DC Resistive

Life

(x

1000

0 op

erat

ions

)

48V DC Inductive

DC Load

Node Address SelectionNode Address NA0 NA1 NA2 NA3 NA4 NA5 Node Address NA0 NA1 NA2 NA3 NA4 NA5

0 OFF OFF OFF OFF OFF OFF 32 OFF OFF OFF OFF OFF ON

1 ON OFF OFF OFF OFF OFF 33 ON OFF OFF OFF OFF ON

2 OFF ON OFF OFF OFF OFF 34 OFF ON OFF OFF OFF ON

3 ON ON OFF OFF OFF OFF 35 ON ON OFF OFF OFF ON

4 OFF OFF ON OFF OFF OFF 36 OFF OFF ON OFF OFF ON

5 ON OFF ON OFF OFF OFF 37 ON OFF ON OFF OFF ON

6 OFF ON ON OFF OFF OFF 38 OFF ON ON OFF OFF ON

7 ON ON ON OFF OFF OFF 39 ON ON ON OFF OFF ON

8 OFF OFF OFF ON OFF OFF 40 OFF OFF OFF ON OFF ON

9 ON OFF OFF ON OFF OFF 41 ON OFF OFF ON OFF ON

10 OFF ON OFF ON OFF OFF 42 OFF ON OFF ON OFF ON

11 ON ON OFF ON OFF OFF 43 ON ON OFF ON OFF ON

12 OFF OFF ON ON OFF OFF 44 OFF OFF ON ON OFF ON

13 ON OFF ON ON OFF OFF 45 ON OFF ON ON OFF ON

14 OFF ON ON ON OFF OFF 46 OFF ON ON ON OFF ON

15 ON ON ON ON OFF OFF 47 ON ON ON ON OFF ON

16 OFF OFF OFF OFF ON OFF 48 OFF OFF OFF OFF ON ON

17 ON OFF OFF OFF ON OFF 49 ON OFF OFF OFF ON ON

18 OFF ON OFF OFF ON OFF 50 OFF ON OFF OFF ON ON

19 ON ON OFF OFF ON OFF 51 ON ON OFF OFF ON ON

20 OFF OFF ON OFF ON OFF 52 OFF OFF ON OFF ON ON

21 ON OFF ON OFF ON OFF 53 ON OFF ON OFF ON ON

22 OFF ON ON OFF ON OFF 54 OFF ON ON OFF ON ON

23 ON ON ON OFF ON OFF 55 ON ON ON OFF ON ON

24 OFF OFF OFF ON ON OFF 56 OFF OFF OFF ON ON ON

25 ON OFF OFF ON ON OFF 57 ON OFF OFF ON ON ON

26 OFF ON OFF ON ON OFF 58 OFF ON OFF ON ON ON

27 ON ON OFF ON ON OFF 59 ON ON OFF ON ON ON

28 OFF OFF ON ON ON OFF 60 OFF OFF ON ON ON ON

29 ON OFF ON ON ON OFF 61 ON OFF ON ON ON ON

30 OFF ON ON ON ON OFF 62 OFF ON ON ON ON ON

31 ON ON ON ON ON OFF 63 ON ON ON ON ON ON

SX5D-SBR08

Page 65: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (DeviceNet)

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-65

J

Communication Speed and Distance

Bus Transmission RateTransmission Distance

Thick Cable Thin Cable

DeviceNet125k baud 500m 100m250k baud 250m 100m500k baud 100m 100m

Communication Cable

Bus Network I/F Connector (on the module) Cable

DeviceNetPhoenix Contact5-pin connector MSTBV2.5/5-GF-5.08AU

DeviceNet cable

Communication Configuration

[Baud Rate Selection] [Output Hold or Load Off] [System Reserve]Baud Rate DR0 DR1125 kbps OFF OFF250 kbps ON OFF500 kbps OFF ON(Selection Prohibited) ON ON

Output/Load H/LLOAD OFF OFFHOLD ON

System Reserve NOFixed to OFF(Selection Prohibited) ON

16-Point Transistor Output Modules (DeviceNet)

Key features include:• Communicate with DeviceNet network• 16-point transistor output module (sink/source)• Removable terminal blocks• Source output short circuit and overload protected

Transistor Output Type

Part No. SX5D–SBT16K SX5D–SBT16P

Output Type Sink output Protect source output

Output Points 16 points

Output Type N-channel MOS open drain

P-channel MOS open drain

Rated Load Voltage 24V DC

Load Voltage Range 3 to 30V DC 19 to 30V DC

Maximum Load Current 0.5A/point

Commons/Current 1 common/6A

Short-circuit Protection No Yes

Current Draw 70 mA 100 mA

Terminal Arrangement

Upper Terminal Block (SX9Z-SS1)

Lower Terminal Block (SX9Z-SS2)

Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 OUT0 8 OUT81 OUT1 9 OUT92 OUT2 10 OUT103 OUT3 11 OUT114 OUT4 12 OUT125 OUT5 13 OUT136 OUT6 14 OUT147 OUT7 15 OUT15

Output Type Part Number

Sink SX5D-SBT16KSource SX5D-SBT16P

Page 66: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (DeviceNet)

J-66 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Wiring DeviceNet Cable

• DeviceNet requires two power voltages; one for communication and the other for internal circuit and load.

• Use a special DeviceNet cable for connecting to the DeviceNet network.• Connect the core wires of the cable to terminals identified by labels of

matching colors.• DeviceNet Cable

Cable Type No. MakerThick Cable 1485C-P1A50

Rockwell AutomationThin Cable 1485C-P1-C150

16-Point Transistor Sink Output

Node Address SelectionNode Address NA0 NA1 NA2 NA3 NA4 NA5 Node Address NA0 NA1 NA2 NA3 NA4 NA5

0 OFF OFF OFF OFF OFF OFF 32 OFF OFF OFF OFF OFF ON

1 ON OFF OFF OFF OFF OFF 33 ON OFF OFF OFF OFF ON

2 OFF ON OFF OFF OFF OFF 34 OFF ON OFF OFF OFF ON

3 ON ON OFF OFF OFF OFF 35 ON ON OFF OFF OFF ON

4 OFF OFF ON OFF OFF OFF 36 OFF OFF ON OFF OFF ON

5 ON OFF ON OFF OFF OFF 37 ON OFF ON OFF OFF ON

6 OFF ON ON OFF OFF OFF 38 OFF ON ON OFF OFF ON

7 ON ON ON OFF OFF OFF 39 ON ON ON OFF OFF ON

8 OFF OFF OFF ON OFF OFF 40 OFF OFF OFF ON OFF ON

9 ON OFF OFF ON OFF OFF 41 ON OFF OFF ON OFF ON

10 OFF ON OFF ON OFF OFF 42 OFF ON OFF ON OFF ON

11 ON ON OFF ON OFF OFF 43 ON ON OFF ON OFF ON

12 OFF OFF ON ON OFF OFF 44 OFF OFF ON ON OFF ON

13 ON OFF ON ON OFF OFF 45 ON OFF ON ON OFF ON

14 OFF ON ON ON OFF OFF 46 OFF ON ON ON OFF ON

15 ON ON ON ON OFF OFF 47 ON ON ON ON OFF ON

16 OFF OFF OFF OFF ON OFF 48 OFF OFF OFF OFF ON ON

17 ON OFF OFF OFF ON OFF 49 ON OFF OFF OFF ON ON

18 OFF ON OFF OFF ON OFF 50 OFF ON OFF OFF ON ON

19 ON ON OFF OFF ON OFF 51 ON ON OFF OFF ON ON

20 OFF OFF ON OFF ON OFF 52 OFF OFF ON OFF ON ON

21 ON OFF ON OFF ON OFF 53 ON OFF ON OFF ON ON

22 OFF ON ON OFF ON OFF 54 OFF ON ON OFF ON ON

23 ON ON ON OFF ON OFF 55 ON ON ON OFF ON ON

24 OFF OFF OFF ON ON OFF 56 OFF OFF OFF ON ON ON

25 ON OFF OFF ON ON OFF 57 ON OFF OFF ON ON ON

26 OFF ON OFF ON ON OFF 58 OFF ON OFF ON ON ON

27 ON ON OFF ON ON OFF 59 ON ON OFF ON ON ON

28 OFF OFF ON ON ON OFF 60 OFF OFF ON ON ON ON

29 ON OFF ON ON ON OFF 61 ON OFF ON ON ON ON

30 OFF ON ON ON ON OFF 62 OFF ON ON ON ON ON

31 ON ON ON ON ON OFF 63 ON ON ON ON ON ON

16-Point Transistor Protect Source Output

SX5D-SBT16K SX5D-SBT16P

Relay

PilotLight

++

––

OUT15

ControlCircuit

Pro

tect

ion

Circ

uit

Pro

tect

ion

Circ

uit

DCPower

CommunicationInterface

Network

OUT0

Relay

PilotLight

Relay

++

––

OUT0

OUT1

DCPower

ControlCircuit

CommunicationInterface

Network

OUT15

Page 67: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (DeviceNet)

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-67

J

Communication Speed and Distance

Bus Transmission RateTransmission Distance

Thick Cable Thin Cable

DeviceNet125k baud 500m 100m250k baud 250m 100m500k baud 100m 100m

Communication Cable

Bus Network I/F Connector (on the module) Cable

DeviceNetPhoenix Contact5-pin connector MSTBV2.5/5-GF-5.08AU

DeviceNet cable

Communication Configuration

[Baud Rate Selection]

[Output Hold or Load Off] [System Reserve]Baud Rate DR0 DR1125 kbps OFF OFF250 kbps ON OFF500 kbps OFF ON(Selection Prohibited) ON ON

Output/Load H/LLOAD OFF OFFHOLD ON

System Reserve NOFixed to OFF(Selection Prohibited) ON

8-Point Source Input & 8-Point Transistor Sink Output Module (DeviceNet)

Key features include:• Communicate with DeviceNet network• 8-point source input and 8-point sink output module• Removable terminal blocks

Terminal Arrangement

Upper Terminal Block (SX9Z-SS1)

Lower Terminal Block (SX9Z-SS3)

Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 IN0 0 OUT01 IN1 1 OUT12 IN2 2 OUT23 IN3 3 OUT34 IN4 4 OUT45 IN5 5 OUT56 IN6 6 OUT67 IN7 7 OUT7

DC Input / Transistor Sink Output Type

Part No. SX5D–SBM16KI/O Type Source input / sink output

InputInput Logic Active Low

Input Points 8 points

Input TypeNo-voltage input

(2-wire DC sensor, 3-wire NPN sensor, no-voltage contact)

Rated Input Voltage 24V DC

Input Voltage Range 0 to the power voltage

ON Voltage 6V maximum

OFF Voltage 10V minimum

Input Current 6 mA/24V DC

Common 1 common

OutputOutput Points 8 points

Output Type N-channel MOS open drain

Rated Load Voltage 24V DC

Load Voltage Range 3 to 30V DC

Maximum Load Current 0.5A/point

Commons/Current 1 common/4A

Short-circuit Protection No

Current Draw 130 mA

Input/Output Type Part Number

Source Input/Sink Output SX5D-SBM16K

Page 68: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (DeviceNet)

J-68 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Wiring DeviceNet Cable

• DeviceNet requires two power voltages; one for communication and the other for internal circuit and load.

• Use a special DeviceNet cable for connecting to the DeviceNet network.• Connect the core wires of the cable to terminals identified by labels of

matching colors.• DeviceNet Cable

Cable Type No. MakerThick Cable 1485C-P1A50

Rockwell AutomationThin Cable 1485C-P1-C150

8-Point Source Input 8-Point Transistor Sink Output

DC Power

ContactSwitch

ContactSwitch

3.8 kΩ

3.8 kΩ

3.8 kΩ

3.8 kΩ

++

–Blue (White)

IN0Black (White)

Brown (Red)

Network

Brown (Black)IN1

Blue (Black)

IN6

IN7

ControlCircuit

DC3-wireSensorNPN

Output

DC2-wireSensor

CommunicationInterface

Node Address SelectionNode Address NA0 NA1 NA2 NA3 NA4 NA5 Node Address NA0 NA1 NA2 NA3 NA4 NA5

0 OFF OFF OFF OFF OFF OFF 32 OFF OFF OFF OFF OFF ON

1 ON OFF OFF OFF OFF OFF 33 ON OFF OFF OFF OFF ON

2 OFF ON OFF OFF OFF OFF 34 OFF ON OFF OFF OFF ON

3 ON ON OFF OFF OFF OFF 35 ON ON OFF OFF OFF ON

4 OFF OFF ON OFF OFF OFF 36 OFF OFF ON OFF OFF ON

5 ON OFF ON OFF OFF OFF 37 ON OFF ON OFF OFF ON

6 OFF ON ON OFF OFF OFF 38 OFF ON ON OFF OFF ON

7 ON ON ON OFF OFF OFF 39 ON ON ON OFF OFF ON

8 OFF OFF OFF ON OFF OFF 40 OFF OFF OFF ON OFF ON

9 ON OFF OFF ON OFF OFF 41 ON OFF OFF ON OFF ON

10 OFF ON OFF ON OFF OFF 42 OFF ON OFF ON OFF ON

11 ON ON OFF ON OFF OFF 43 ON ON OFF ON OFF ON

12 OFF OFF ON ON OFF OFF 44 OFF OFF ON ON OFF ON

13 ON OFF ON ON OFF OFF 45 ON OFF ON ON OFF ON

14 OFF ON ON ON OFF OFF 46 OFF ON ON ON OFF ON

15 ON ON ON ON OFF OFF 47 ON ON ON ON OFF ON

16 OFF OFF OFF OFF ON OFF 48 OFF OFF OFF OFF ON ON

17 ON OFF OFF OFF ON OFF 49 ON OFF OFF OFF ON ON

18 OFF ON OFF OFF ON OFF 50 OFF ON OFF OFF ON ON

19 ON ON OFF OFF ON OFF 51 ON ON OFF OFF ON ON

20 OFF OFF ON OFF ON OFF 52 OFF OFF ON OFF ON ON

21 ON OFF ON OFF ON OFF 53 ON OFF ON OFF ON ON

22 OFF ON ON OFF ON OFF 54 OFF ON ON OFF ON ON

23 ON ON ON OFF ON OFF 55 ON ON ON OFF ON ON

24 OFF OFF OFF ON ON OFF 56 OFF OFF OFF ON ON ON

25 ON OFF OFF ON ON OFF 57 ON OFF OFF ON ON ON

26 OFF ON OFF ON ON OFF 58 OFF ON OFF ON ON ON

27 ON ON OFF ON ON OFF 59 ON ON OFF ON ON ON

28 OFF OFF ON ON ON OFF 60 OFF OFF ON ON ON ON

29 ON OFF ON ON ON OFF 61 ON OFF ON ON ON ON

30 OFF ON ON ON ON OFF 62 OFF ON ON ON ON ON

31 ON ON ON ON ON OFF 63 ON ON ON ON ON ON

Relay

PilotLight

Relay

++

––

OUT0

OUT1

DCPower

ControlCircuit

CommunicationInterface

Network

OUT7

Page 69: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (DeviceNet)

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-69

J

8-Point Sink Input & 8-Point Transistor Source Output Module (DeviceNet)

Key features include:• Communicate with DeviceNet network• 8-point sink input and 8-point source output module• Removable terminal blocks• Source output short circuit and overload protected

DC Input / Transistor Source Output Type

Part No. SX5D–SBM16PI/O Type Sink input / protect source output

InputInput Logic Active High

Input Points 8 points

Input TypeNo-voltage input

(2-wire DC sensor, 3-wire PNP sensor, no-voltage contact)

Rated Input Voltage 24V DC

Input Voltage Range 0 to the power voltage

ON Voltage 10V minimum

OFF Voltage 6V maximum

Input Current 6 mA/24V DC

Common 1 common

OutputOutput Points 8 points

Output Type P-channel MOS open drain

Rated Load Voltage 24V DC

Load Voltage Range 19 to 30V DC

Maximum Load Current 0.5A/point

Commons/Current 1 common/4A

Short-circuit Protection Yes

Current Draw 140 mA

Terminal Arrangement

Upper Terminal Block (SX9Z-SS1)

Lower Terminal Block (SX9Z-SS3)

Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 IN0 0 OUT01 IN1 1 OUT12 IN2 2 OUT23 IN3 3 OUT34 IN4 4 OUT45 IN5 5 OUT56 IN6 6 OUT67 IN7 7 OUT7

Input/Output Type Part Number

Sink Input/Source Output SX5D-SBM16P

Communication Speed and Distance

Bus Transmission RateTransmission Distance

Thick Cable Thin Cable

DeviceNet125k baud 500m 100m250k baud 250m 100m500k baud 100m 100m

Communication Cable

Bus Network I/F Connector (on the module) Cable

DeviceNetPhoenix Contact5-pin connector MSTBV2.5/5-GF-5.08AU

DeviceNet cable

Communication Configuration

[Baud Rate Selection]

[Output Hold or Load Off] [System Reserve]Baud Rate DR0 DR1125 kbps OFF OFF250 kbps ON OFF500 kbps OFF ON

(Selection Prohibited) ON ON

Output/Load H/LLOAD OFF OFF

HOLD ON

System Reserve NOFixed to OFF

(Selection Prohibited) ON

Page 70: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (DeviceNet)

J-70 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Wiring DeviceNet Cable

• DeviceNet requires two power voltages; one for communication and the other for internal circuit and load.

• Use a special DeviceNet cable for connecting to the DeviceNet network.• Connect the core wires of the cable to terminals identified by labels of

matching colors.• DeviceNet Cable

Cable Type No. MakerThick Cable 1485C-P1A50

Rockwell AutomationThin Cable 1485C-P1-C150

Node Address SelectionNode Address NA0 NA1 NA2 NA3 NA4 NA5 Node Address NA0 NA1 NA2 NA3 NA4 NA5

0 OFF OFF OFF OFF OFF OFF 32 OFF OFF OFF OFF OFF ON

1 ON OFF OFF OFF OFF OFF 33 ON OFF OFF OFF OFF ON

2 OFF ON OFF OFF OFF OFF 34 OFF ON OFF OFF OFF ON

3 ON ON OFF OFF OFF OFF 35 ON ON OFF OFF OFF ON

4 OFF OFF ON OFF OFF OFF 36 OFF OFF ON OFF OFF ON

5 ON OFF ON OFF OFF OFF 37 ON OFF ON OFF OFF ON

6 OFF ON ON OFF OFF OFF 38 OFF ON ON OFF OFF ON

7 ON ON ON OFF OFF OFF 39 ON ON ON OFF OFF ON

8 OFF OFF OFF ON OFF OFF 40 OFF OFF OFF ON OFF ON

9 ON OFF OFF ON OFF OFF 41 ON OFF OFF ON OFF ON

10 OFF ON OFF ON OFF OFF 42 OFF ON OFF ON OFF ON

11 ON ON OFF ON OFF OFF 43 ON ON OFF ON OFF ON

12 OFF OFF ON ON OFF OFF 44 OFF OFF ON ON OFF ON

13 ON OFF ON ON OFF OFF 45 ON OFF ON ON OFF ON

14 OFF ON ON ON OFF OFF 46 OFF ON ON ON OFF ON

15 ON ON ON ON OFF OFF 47 ON ON ON ON OFF ON

16 OFF OFF OFF OFF ON OFF 48 OFF OFF OFF OFF ON ON

17 ON OFF OFF OFF ON OFF 49 ON OFF OFF OFF ON ON

18 OFF ON OFF OFF ON OFF 50 OFF ON OFF OFF ON ON

19 ON ON OFF OFF ON OFF 51 ON ON OFF OFF ON ON

20 OFF OFF ON OFF ON OFF 52 OFF OFF ON OFF ON ON

21 ON OFF ON OFF ON OFF 53 ON OFF ON OFF ON ON

22 OFF ON ON OFF ON OFF 54 OFF ON ON OFF ON ON

23 ON ON ON OFF ON OFF 55 ON ON ON OFF ON ON

24 OFF OFF OFF ON ON OFF 56 OFF OFF OFF ON ON ON

25 ON OFF OFF ON ON OFF 57 ON OFF OFF ON ON ON

26 OFF ON OFF ON ON OFF 58 OFF ON OFF ON ON ON

27 ON ON OFF ON ON OFF 59 ON ON OFF ON ON ON

28 OFF OFF ON ON ON OFF 60 OFF OFF ON ON ON ON

29 ON OFF ON ON ON OFF 61 ON OFF ON ON ON ON

30 OFF ON ON ON ON OFF 62 OFF ON ON ON ON ON

31 ON ON ON ON ON OFF 63 ON ON ON ON ON ON

8-Point Sink Input

3.8 kΩ

3.8 kΩ

3.8 kΩ

3.8 kΩ

ContactSwitch

ContactSwitch

++

––

Brown (Red)

Blue (Black)

IN0Black (White)

IN1

Brown (White)

Blue (Black)

IN7

IN6CommunicationInterface

ControlCircuit

DCPower

Network

DC3-wireSensorPNP

Output

DC2-wireSensor

8-Point Transistor Protect Source Output

Relay

PilotLight

++

––

OUT7

ControlCircuit

Pro

tect

ion

Circ

uit

Pro

tect

ion

Circ

uit

DCPower

CommunicationInterface

Network

OUT0

Page 71: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (LONWORKS)

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-71

J

Input Type Part Number

Source SX5L-SBN16SSink SX5L-SBN16K

Key features include:• Communicate with LONWORKS network• 16-point transistor input module (sink/source)• Removable terminal blocks

DC Input Type

Part No. SX5L–SBN16S SX5L–SBN16KInput Type DC source input DC sink input

Input Logic Active Low Active High

Input Points 16 points

Input TypeNo-voltage input

(2-wire DC sensor, 3-wire NPN sensor, no-voltage contact)

No-voltage input (2-wire DC sensor, 3-wire PNP sensor, no-voltage contact)

Rated Input Voltage 24V DC

Input Voltage Range 0 to the power voltage

Turn ON Voltage 6V maximum 10V minimum

Turn OFF Voltage 10V minimum 6V maximum

Input Current 6 mA/24V DC 6 mA/24V DC

Common 1 common

Current Draw 150 mA 130 mA

Communication Speed and Distance

Note: The transmission distances represent the values when using Level 4, 22 AWG cables (free topology).

Bus Baud Rate Transmission Distance

LonWorks 78 kbps 500m (total length) 400m (between nodes)

Communication Cable

Bus Network I/F Connector (on the module) Cable

LonWorksPhoenix Contact2-pin connectorMSTBV2.5/2-GF-5.08

Single twisted-pair cableAWG24 to 140.2 to 2.5 mm2

Terminal Arrangement

Upper Terminal Block (SX9Z-SS1)

Lower Terminal Block (SX9Z-SS2)

Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 IN0 8 IN81 IN1 9 IN92 IN2 10 IN103 IN3 11 IN114 IN4 12 IN125 IN5 13 IN136 IN6 14 IN147 IN7 15 IN15

Communication Configuration

All SX5L Modules:• The application program of the LonWorks is installed in the Neuron

chip of the SX5L module.• When wink is executed, the RUN LED flashes for 3 seconds in 500-

msec increments.• In the off-line mode, the RUN and ERR LEDs go off and all outputs

also go off.• The SX5L does not use SNVT.

SX5L-SBN16S/SX5L-SBT16K:• Output network variables are updated only at the transition of the

input status. (When all inputs are off at power-up, network variables are not updated.)

• When nv_update_fails is TRUE(1) while using the data acknowl-edged service (ACKD), the ERR LED goes on.

• The ERR LED goes off when nv_update_succeeds is TRUE(1).(When an attempt to send network variables fails, resending does not occur until the input changes status.

continued

16-Point Transistor Input Modules (LONWORKS)

Page 72: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (LONWORKS)

J-72 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Communication Configuration Continued

• When modifying the application program, please consult IDEC.

SX5L-SBN16SSX5L-SBN16K

8

15Input

InputOutput

0

7

nv_o8[1]

nv_o16

nv_o8[0]Input to SX5L

Network Variables

Input to SX5L

Wiring LONWORKS Cable

• Turn power off before wiring the SX5L to the LonWorks network. Make sure wiring is correct before turning power on. Supply power to each slave station or to each group of stations separately.

• The LONWORKS network uses a twisted-pair cable. The connector has no polarity and the core wires of the twisted-pair cable can be con-nected to either terminal of the connector.

• The LONWORKS network requires network management to enable communication between nodes, including the SX5L.

• The network management requires an XIF extension. For your XIF extension, find your XIF No., printed on the side of the SX5 module or on the shipping package. The network management is not completed successfully without the XIF extension.

DC Power

ContactSwitch

ContactSwitch

3.8 kΩ

3.8 kΩ

3.8 kΩ

3.8 kΩ

++

–Blue (White)

IN0Black (White)

Brown (Red)

Network

Brown (Black)IN1

Blue (Black)

IN14

IN15

ControlCircuit

DC3-wireSensorNPN

Output

DC2-wireSensor

CommunicationInterface

3.8 kΩ

3.8 kΩ

3.8 kΩ

3.8 kΩ

ContactSwitch

ContactSwitch

++

––

Brown (Red)

Blue (Black)

IN0Black (White)

IN1

Brown (White)

Blue (Black)

IN15

IN14CommunicationInterface

ControlCircuit

DCPower

Network

DC3-wireSensor

PNPOutput

DC2-wireSensor

16-Point Source Input

16-Point Sink Input

SX5L-SBN16S

SX5L-SBN16K

Page 73: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (LONWORKS)

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-73

J

8-Point Relay Output Module (LONWORKS)

Output Type Part Number

Relay Output SX5L-SBR08

Key features include:• Communicate with LONWORKS network• 8-point relay output module• Handles current up to 5A per point• Removable terminal blocks

Relay Output Type

Rated Relay Contact

Part No. SX5L–SBR08Output Type Relay output

Output Points 8 points

Output Type 1NO relay contact

Rated Load Voltage 250V AC, 24V DC

Maximum Load Current 5A/point

Commons/Current 8 commons/5A

Current Draw 80 mA

Built-in Relay PCB mount, not replaceable

Maximum Applicable Voltage 250V AC, 125V DC

Maximum Current 5A

Rated Load (resistive load) 250V AC/5A, 24V DC/5A

Minimum Applicable Load 1V DC / 1mA

LifeMechanical 20,000,000 operations minimum

(18,000 operations/ hour)

Electrical See Electrical Life Curve on next page (1,800 operations/ hour)

Terminal Arrangement

Upper Terminal Block (SX9Z-SS4)

Lower Terminal Block (SX9Z-SS5)

Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 OUT0 4 OUT4

C0 COM0 C4 COM41 OUT1 5 OUT5

C1 COM1 C5 COM52 OUT2 6 OUT6

C2 COM2 C6 COM63 OUT3 7 OUT7

C3 COM3 C7 COM7

Communication Speed and Distance

Note: The transmission distances represent the values when using Level 4, 22 AWG cables (free topology).

Bus Baud Rate Transmission Distance

LonWorks 78 kbps 500m (total length) 400m (between nodes)

Communication Cable

Bus Network I/F Connector (on the module) Cable

LonWorksPhoenix Contact2-pin connectorMSTBV2.5/2-GF-5.08

Single twisted-pair cableAWG24 to 140.2 to 2.5 mm2

Communication Configuration

All SX5L Modules:• The application program of the LonWorks is installed in the Neuron

chip of the SX5L module.• When wink is executed, the RUN LED flashes for 3 seconds in 500-

msec increments.• In the off-line mode, the RUN and ERR LEDs go off and all outputs

also go off.• The SX5L does not use SNVT.

SX5L-SBR08:• Output is updated only when input network variables are received.

(At power-up to the network, all outputs remain off until initial com-munication starts.)

• When modifying the application program, please consult IDEC.

SX5L-SBR08

Output0

7nv_i8[0]

Input Network Variable

Output from SX5L

Page 74: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (LONWORKS)

J-74 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Wiring LONWORKS Cable

• Turn power off before wiring the SX5L to the LonWorks network. Make sure wiring is correct before turning power on. Supply power to each slave station or to each group of stations separately.

• The LONWORKS network uses a twisted-pair cable. The connector has no polarity and the core wires of the twisted-pair cable can be con-nected to either terminal of the connector.

• The LONWORKS network requires network management to enable communication between nodes, including the SX5L.

• The network management requires an XIF extension. For your XIF extension, find your XIF No., printed on the side of the SX5 module or on the shipping package. The network management is not completed successfully without the XIF extension.

8-Point Relay Output

Load PowerPilotLight

Load Power

Solenoid

PilotLight

Load Power

Load Power

Solenoid

++

Network

OUT1COM1

COM7OUT7

OUT0COM0

COM6OUT6

ControlCircuit

CommunicationInterface

DCPower

––

Reference Data Electrical Life Curve: Relay in SX5L-SBR08

Note 1: AC/DC Resistive LoadOperating frequency: 1800 operations/hourDuty ratio: 40%

Note 2: AC Inductive Load

Note 3: DC Inductive LoadOperating frequency: 1800 operations/hourDuty ratio: 40%Time constant: L/R =15 msec

Line MakingCurrent

BreakingCurrent Frequency Duty

RatioSolid 10 I, cos θ = 0.7 I, cos θ = 0.3 to 0.4 1800 operations/h

40%Dashed 5 I, cos θ = 0.7 I, cos θ = 0.3 to 0.4 300 operations/h

100

500

50

10

0.05 0.1 1 2 3 50.2 0.3 0.5

110V ACInductive

220V ACInductive

220V AC Resistive110V AC Resistive

AC Load

Life

(x

1000

0 op

erat

ions

)

Load Current (A)

100

500

50

10

0.05 0.1 1 2 3 50.2 0.3 0.5

110V DCInductive

24V DC Resistive

48V DC Resistive

24V DC Inductive

Load Current (A)

110 DC Resistive

Life

(x

1000

0 op

erat

ions

)

48V DC Inductive

DC Load

SX5L-SBR08

Page 75: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (LONWORKS)

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-75

J

Key features include:• Communicate with LONWORKS network• 16-point transistor output module (sink/source)• Removable terminal blocks• Source output short circuit and overload protected

Transistor Output Type

Part No. SX5L–SBT16K SX5L–SBT16P

Output Type Sink output Protect source output

Output Points 16 points

Output Type N-channel MOS open drain

P-channel MOS open drain

Rated Load Voltage 24V DC

Load Voltage Range 3 to 30V DC 19 to 30V DC

Maximum Load Current 0.5A/point

Commons/Current 1 common/6A

Short-circuit Protection No Yes

Current Draw 30 mA 60 mA

Terminal Arrangement

Upper Terminal Block (SX9Z-SS1)

Lower Terminal Block (SX9Z-SS2)

Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 OUT0 8 OUT81 OUT1 9 OUT92 OUT2 10 OUT103 OUT3 11 OUT114 OUT4 12 OUT125 OUT5 13 OUT136 OUT6 14 OUT147 OUT7 15 OUT15

Output Type Part Number

Sink SX5L-SBT16KSource SX5L-SBT16P

16-Point Transistor Output Modules (LONWORKS)

Communication Speed and Distance

Note: The transmission distances represent the values when using Level 4, 22 AWG cables (free topology).

Bus Baud Rate Transmission Distance

LonWorks 78 kbps 500m (total length) 400m (between nodes)

Communication Cable

Bus Network I/F Connector (on the module) Cable

LonWorksPhoenix Contact2-pin connectorMSTBV2.5/2-GF-5.08

Single twisted-pair cableAWG24 to 140.2 to 2.5 mm2

Communication Configuration

All SX5L Modules:• The application program of the LonWorks is installed in the Neuron

chip of the SX5L module.• When wink is executed, the RUN LED flashes for 3 seconds in 500-

msec increments.• In the off-line mode, the RUN and ERR LEDs go off and all outputs

also go off.• The SX5L does not use SNVT.

SX5L-SBT16P/SX5L-SBT16K:• Output is updated only when input network variables are received.

(At power-up to the network, all outputs remain off until initial com-munication starts.)

continued

Page 76: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (LONWORKS)

J-76 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Communication Configuration continued

• When modifying the application program, please consult IDEC.

Output from SX5L

SX5L-SBT16KSX5L-SBT16P

Output

Output0

7

8

15

Input

nv_i8[1]

nv_i16

nv_i8[0]

Network Variables

Output from SX5L

Wiring LONWORKS Cable

• Turn power off before wiring the SX5L to the LonWorks network. Make sure wiring is correct before turning power on. Supply power to each slave station or to each group of stations separately.

• The LONWORKS network uses a twisted-pair cable. The connector has no polarity and the core wires of the twisted-pair cable can be con-nected to either terminal of the connector.

• The LONWORKS network requires network management to enable communication between nodes, including the SX5L.

• The network management requires an XIF extension. For your XIF extension, find your XIF No., printed on the side of the SX5 module or on the shipping package. The network management is not completed successfully without the XIF extension.

16-Point Transistor Sink Output

Relay

PilotLight

++

––

OUT15

ControlCircuit

Pro

tect

ion

Circ

uit

Pro

tect

ion

Circ

uit

DCPower

CommunicationInterface

Network

OUT0

16-Point Transistor Protect Source Output

SX5L-SBT16K

SX5L-SBT16P

Relay

PilotLight

Relay

++

––

OUT0

OUT1

DCPower

ControlCircuit

CommunicationInterface

Network

OUT15

Page 77: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (LONWORKS)

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-77

J

8-Point Source Input & 8-Point Transistor Sink Output Module (LONWORKS)

Key features include:• Communicate with LONWORKS network• 8-point source input and 8-point sink output module • Removable terminal blocks

DC Input / Transistor Sink Output Type

Part No. SX5L–SBM16KI/O Type Source input / sink output

InputInput Logic Active Low

Input Points 8 points

Input TypeNo-voltage input

(2-wire DC sensor, 3-wire NPN sensor, no-voltage contact)

Rated Input Voltage 24V DC

Input Voltage Range 0 to the power voltage

ON Voltage 6V maximum

OFF Voltage 10V minimum

Input Current 6 mA/24V DC

Common 1 common

OutputOutput Points 8 points

Output Type N-channel MOS open drain

Rated Load Voltage 24V DC

Load Voltage Range 3 to 30V DC

Maximum Load Current 0.5A/point

Commons/Current 1 common/4A

Short-circuit Protection No

Current Draw 95 mA

Terminal Arrangement

Upper Terminal Block (SX9Z-SS1)

Lower Terminal Block (SX9Z-SS3)

Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 IN0 0 OUT01 IN1 1 OUT12 IN2 2 OUT23 IN3 3 OUT34 IN4 4 OUT45 IN5 5 OUT56 IN6 6 OUT67 IN7 7 OUT7

Input/Output Type Part Number

Source Input/Sink Output SX5L-SBM16K

Communication Speed and Distance

Note: The transmission distances represent the values when using Level 4, 22 AWG cables (free topology).

Bus Baud Rate Transmission Distance

LonWorks 78 kbps 500m (total length) 400m (between nodes)

Communication Cable

Bus Network I/F Connector (on the module) Cable

LonWorksPhoenix Contact2-pin connectorMSTBV2.5/2-GF-5.08

Single twisted-pair cableAWG24 to 140.2 to 2.5 mm2

Communication Configuration

All SX5L Modules:• The application program of the LonWorks is installed in the Neuron

chip of the SX5L module.• When wink is executed, the RUN LED flashes for 3 seconds in 500-

msec increments.• In the off-line mode, the RUN and ERR LEDs go off and all outputs

also go off.• The SX5L does not use SNVT.

SX5L-SBM16K (inputs):• Output network variables are updated only at the transition of the

input status. (When all inputs are off at power-up, network variables are not updated.)

• When nv_update_fails is TRUE(1) while using the data acknowl-edged service (ACKD), the ERR LED goes on.

• The ERR LED goes off when nv_update_succeeds is TRUE(1).(When an attempt to send network variables fails, resending does not occur until the input changes status.

continued

Page 78: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (LONWORKS)

J-78 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

8-Point Source Input

DC Power

ContactSwitch

ContactSwitch

3.8 kΩ

3.8 kΩ

3.8 kΩ

3.8 kΩ

++

–Blue (White)

IN0Black (White)

Brown (Red)

Network

Brown (Black)IN1

Blue (Black)

IN6

IN7

ControlCircuit

DC3-wireSensorNPN

Output

DC2-wireSensor

CommunicationInterface

8-Point Transistor Sink Output

Relay

PilotLight

Relay

++

––

OUT0

OUT1

DCPower

ControlCircuit

CommunicationInterface

Network

OUT7

Communication Configuration ContinuedSX5L-SBM16K (outputs):

• Output is updated only when input network variables are received.(At power-up to the network, all outputs remain off until initial commu-nication starts.)

• When modifying the application program, please consult IDEC.

SX5L-SBM16K

Output

Input0

7

0

7

nv_o8[0]

nv_i8[0]

Output Network Variable

Input Network Variable

Input to SX5L

Output from SX5L

Wiring LONWORKS Cable

• Turn power off before wiring the SX5L to the LonWorks network. Make sure wiring is correct before turning power on. Supply power to each slave station or to each group of stations separately.

• The LONWORKS network uses a twisted-pair cable. The connector has no polarity and the core wires of the twisted-pair cable can be con-nected to either terminal of the connector.

• The LONWORKS network requires network management to enable communication between nodes, including the SX5L.

• The network management requires an XIF extension. For your XIF extension, find your XIF No., printed on the side of the SX5 module or on the shipping package. The network management is not completed successfully without the XIF extension.

Page 79: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (LONWORKS)

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-79

J

Communication Speed and Distance

Note: The transmission distances represent the values when using Level 4, 22 AWG cables (free topology).

Bus Baud Rate Transmission Distance

LonWorks 78 kbps 500m (total length) 400m (between nodes)

Communication Cable

Bus Network I/F Connector (on the module) Cable

LonWorksPhoenix Contact2-pin connectorMSTBV2.5/2-GF-5.08

Single twisted-pair cableAWG24 to 140.2 to 2.5 mm2

Communication Configuration

All SX5L Modules:• The application program of the LonWorks is installed in the Neuron

chip of the SX5L module.• When wink is executed, the RUN LED flashes for 3 seconds in 500-

msec increments.• In the off-line mode, the RUN and ERR LEDs go off and all outputs

also go off.• The SX5L does not use SNVT.

SX5L-SBM16P (inputs):• Output network variables are updated only at the transition of the

input status. (When all inputs are off at power-up, network variables are not updated.)

• When nv_update_fails is TRUE(1) while using the data acknowl-edged service (ACKD), the ERR LED goes on.

• The ERR LED goes off when nv_update_succeeds is TRUE(1).(When an attempt to send network variables fails, resending does not occur until the input changes status.

continued

Key features include:• Communicate with LONWORKS network• 8-point sink input and 8-point source output module • Removable terminal blocks• Source output short circuit and overload protected

DC Input / Transistor Source Output Type

Part No. SX5L–SBM16PI/O Type Sink input / protect source output

InputInput Logic Active High

Input Points 8 points

Input TypeNo-voltage input

(2-wire DC sensor, 3-wire PNP sensor, no-voltage contact)

Rated Input Voltage 24V DC

Input Voltage Range 0 to the power voltage

ON Voltage 10V minimum

OFF Voltage 6V maximum

Input Current 6 mA/24V DC

Common 1 common

OutputOutput Points 8 points

Output Type P-channel MOS open drain

Rated Load Voltage 24V DC

Load Voltage Range 19 to 30V DC

Maximum Load Current 0.5A/point

Commons/Current 1 common/4A

Short-circuit Protection Yes

Current Draw 100 mA

Terminal Arrangement

Upper Terminal Block (SX9Z-SS1)

Lower Terminal Block (SX9Z-SS3)

Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 IN0 0 OUT01 IN1 1 OUT12 IN2 2 OUT23 IN3 3 OUT34 IN4 4 OUT45 IN5 5 OUT56 IN6 6 OUT67 IN7 7 OUT7

Input/Output Type Sink Input/Source Output

Part Number SX5L-SBM16P

8-Point Sink Input & 8-Point Transistor Source Output Module (LONWORKS)

Page 80: CATALOGO DE PLCS IDEC

Programmable Logic Controllers SX5 Smart I/O (LONWORKS)

J-80 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

8-Point Sink Input

8-Point Transistor Protect Source Output

3.8 kΩ

3.8 kΩ

3.8 kΩ

3.8 kΩ

ContactSwitch

ContactSwitch

++

––

Brown (Red)

Blue (Black)

IN0Black (White)

IN1

Brown (White)

Blue (Black)

IN7

IN6CommunicationInterface

ControlCircuit

DCPower

Network

DC3-wireSensor

PNPOutput

DC2-wireSensor

Relay

PilotLight

++

––

OUT7

ControlCircuit

Pro

tect

ion

Circ

uit

Pro

tect

ion

Circ

uit

DCPower

CommunicationInterface

Network

OUT0

Communication Configuration ContinuedSX5L-SBM16P (outputs):

• Output is updated only when input network variables are received.(At power-up to the network, all outputs remain off until initial commu-nication starts.)

• When modifying the application program, please consult IDEC.

SX5L-SBM16P

Output

Input0

7

0

7

nv_o8[0]

nv_i8[0]

Output Network Variable

Input Network Variable

Input to SX5L

Output from SX5L

Wiring LONWORKS Cable

• Turn power off before wiring the SX5L to the LonWorks network. Make sure wiring is correct before turning power on. Supply power to each slave station or to each group of stations separately.

• The LONWORKS network uses a twisted-pair cable. The connector has no polarity and the core wires of the twisted-pair cable can be con-nected to either terminal of the connector.

• The LONWORKS network requires network management to enable communication between nodes, including the SX5L.

• The network management requires an XIF extension. For your XIF extension, find your XIF No., printed on the side of the SX5 module or on the shipping package. The network management is not completed successfully without the XIF extension.

Page 81: CATALOGO DE PLCS IDEC

Programmable Logic Controllers Micro3 Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-81

J

CE CertifiedEMC ApprovedFile No. B950913332312

The Benchmark for Micro-PLCs

Key features of the Micro3 include:• Built-in communications and networking• Input/output analog capability• User program password protection• Catch input, pulse output• Real-time clock and calendar available• Built-in power supply for sensors• Arithmetic, comparison, and Boolean computation• High-speed: 400µ/100 steps, 10kHz

The True Micro PLC Ambassador

Key features of the Micro3C include:• All the features of the Micro3

• Talks both ASCII and binary• Equipped with two serial ports, RS232 and RS485• Capable of connecting to dial-up modem, serial printer,

and bar code reader• Up to 500 data registers• Handles a wide range of analog input signals• Comes with an easy reset button• Available in 2 sizes: 16- and 24-I/O with relay output

UL ListedFile No. E102542

CSA CertifiedFile No. LR66809

Micro3C

Micro3

CE CertifiedEMC ApprovedFile No. B950913332312

UL ListedFile No. E102542

CSA CertifiedFile No. LR66809

Page 82: CATALOGO DE PLCS IDEC

Programmable Logic Controllers Micro3 Series

J-82 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Standard Mode High-Speed ModeG

ener

al S

peci

ficat

ions

Program Capacity 1012 steps 100 steps (approximately)

Processing 2.9ms/1k steps (average) 400µs/100 steps (average)

Internal Relay 232 points 40 points

Data Register Micro3: 100 pointsMicro3C: 500 points

32 points

Control Data Register 10 points —

Counter/Timer 32 points total 16 points total

Shift Register 64 points 32 points

Communication Channel

Data link channel: RS485Baud rate: 19,200 bps (fixed)Cable length: 656' (200m) (maximum)Data link: 6 slave stations (maximum)Expansion: 1 unit (maximum)

Programming channel: complies with EIA RS485 (Micro3)/RS232 (Micro3C) standardsBaud rate: 1,200/2,400/4,800/9,600/19,200 bps (selectable); Extension: 16.4' (5m) (maximum)

Instructions Micro3: 22 basic, 33 advancedMicro3C: 22 basic, 35 advanced

Memory EEPROM

I/O See configurations shown on page J-85

Catch Input Relays 8 points

Special Internal Relay 16 points

Power Failure Protection Internal relay, shift register, counter, data register; backup time, lithium battery fully charged— With clock: 30 days at 25°C (approximately); Without clock: 50 days at 25°C (approximately)

Self-Diagnostic Function CPU error (WDT), user program CRC error, user program sum check error, communication error, sensor power overload, transistor output overload

Catch Input 8 points; Minimum detectable pulse width (when hard filter is set to 10); Input I0 ON pulse = 28µs,OFF pulse = 30µs; Inputs I1 to I7 ON pulse = 37µs, OFF pulse = 120µs (depending on input filter settings)

Input Filter Function(DC input type only)

Normal input: 0ms, 3ms, 7ms, 10ms; Catch input: Input I0 ON pulse = 4 to 616µs, OFF pulse = 6 to 618µs; Input I1 to I7 ON pulse = 20 to 625µs, OFF pulse = 120 to 618µs

High-Speed Counter 1 point, single-phase, 10kHz (maximum), 32 bits

Analog Potentiometer Micro3: 1 point (10-point), 2 points (16-, 24-point)Micro3C: 1 point only

Pulse Output 1 channel, frequency/PWM output (not available in Micro3C)

Real Time Clock Clock accuracy ±30s/month (maximum) at 25°C (typical); year, month, day, hour, minute, second

Sensor Power Supply 24V ±3.6V DC, 150mA (maximum) including input current, overload detected

.

AC Power DC Power

Elec

tric

al S

peci

ficat

ions

Rated Power Range 100 to 240V AC, 50/60Hz (85 to 264V) 24V DC (19 to 30V DC)

Power Consumption Approximately 30VA (240V AC) Approximately 14W (24V DC)

Inrush Current 40A (maximum)

Power Disruption 25ms (momentary disruption) allowed

Dielectric StrengthBetween power terminal and ground: 2,000V AC, 1 minute

Between power terminal and ground: 1,500V AC, 1 minute

Between I/O terminal and ground: 1,500V AC, 1 minute

Temperature Operating: 0 to 60°C, Storage: –20 to +70°C

Operating Humidity 45 to 85% RH (avoid condensation)

Vibration Resistance 5 to 55Hz, 6G, 2 hours in each of 3 axes

Shock Resistance 30G, 3 shocks in each of 3 axes

Noise Resistance Between power terminal and ground: 1.3kV, 1µs; Between I/O terminal and ground: 1kV, 1µs (with noise simulator) — complies with IEC1131-2

Insulation Resistance Between power or I/O terminal and ground: 10MΩ (minimum), 500V DC

Ground Resistance 100Ω (maximum)

Micro3C only available in 16 I/O or 24

Page 83: CATALOGO DE PLCS IDEC

Programmable Logic Controllers Micro3 Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-83

J

Part Numbers: Micro3

Item Part Number Description Remarks

100 to 240V AC50/60HzPowerMicro3 CPU

Output: Relay240V AC, 2A30V DC, 2A

FC2A-CA16A1 16 I/O: 9 inputs and 7 outputs Inputs: 120V AC (85-132V AC) 50/60Hz(housing = 24 I/O size)

FC2A-C10A1FC2A-C16A1FC2A-C24A1

10 I/O: 6 inputs and 4 outputs16 I/O: 9 inputs and 7 outputs24 I/O: 14 inputs and 10 outputs

Inputs: 24V DC sink/source

Only the 16- and 24-I/O unitshave real-time clock/calendar

Output:Transistor Sink24V DC, 0.5A

FC2A-C10B1FC2A-C16B1FC2A-C24B1

10 I/O: 6 inputs and 4 outputs16 I/O: 9 inputs and 7 outputs24 I/O: 14 inputs and 10 outputs

24V DCPowerMicro3 CPU

Output: Relay240V AC, 2A30V DC, 2A

FC2A-C10A4FC2A-C16A4FC2A-C24A4

10 I/O: 6 inputs and 4 outputs16 I/O: 9 inputs and 7 outputs24 I/O: 14 inputs and 10 outputs

Output:Transistor Sink24V DC, 0.5A

FC2A-C10B4FC2A-C16B4FC2A-C24B4

10 I/O: 6 inputs and 4 outputs16 I/O: 9 inputs and 7 outputs24 I/O: 14 inputs and 10 outputs

Output:Transistor Source24V DC, 0.5A

FC2A-C10D4FC2A-C16D4FC2A-C24D4

10 I/O: 6 inputs and 4 outputs16 I/O: 9 inputs and 7 outputs24 I/O: 14 inputs and 10 outputs

Programming Starter Kits

MM-MICRO1MM-MICRO3-10MM-MICRO3-16MM-MICRO3-24MM-MICRO3C-16MM-MICRO3C-24MM-Cables

Micro-1 PLC, WindLDR, computer link cableMicro3 10 I/O, WindLDR, computer link cable, input switch simulatorMicro3 16 I/O, WindLDR, computer link cable, input switch simulatorMicro3 24 I/O, WindLDR, computer link cable, input switch simulatorMicro3C 16 I/O, WindLDR, computer link cable, input switch simulatorMicro3C 24 I/O, WindLDR, computer link cable, input switch simulatorWindLDR, 3 computer link cables for Micro-1, Micro3 and Micro3C

Program Loader FC2A-HL1EC Program loader with cable

Loader Cable FC2A-KL1FC2A-KL2

6.56' (2m) long16.4' (5m) long Connects program loader to Micro3

Loader Adaptor PSR-GA05005 5V power supply adaptor for using program loader when not connected to CPU

Computer Link Cable FC2A-KC2 Connects Micro3 or loader to PC (1:1 link), 6.56' (2m)

Memory Card FC2A-MC1 Used with program loader to store user programs in SRAM memory

Expansion Cable FC2A-KE1 Close proximity Micro3 link expansion, 9.84" (250mm) long

1:N Computer Link Interface Unit FC2A-LC1 One required to connect each Micro3 in a 1:N computer link system (all connected to one central RS232C/RS485 converter)

1:N Computer Link Interface Cable FC2A-KC3 One required to connect each Micro3 in a 1:N computer link system(connected to each interface unit), 32.8' (10m) long

1:N RS232C/RS485 Converter HD9Z-T11 One required to connect all Micro3 units in a 1:N computer link system

1:N RS232C/RS485 Converter HD9Z-T11-DS783One required to connect all Micro3 units in a 1:N computer link system;Additionally, the DS783 should be used in applications requiring PC to Micro3

communications via modem

1:N PC Cable HD9Z-C52 Connects RS232C/RS485 converter to PC in a 1:N computer link system, 4.92' (1.5m) long (D-sub 9-pin female computer connector)

Analog Input Unit

FC2A-AD1FC2A-AD2FC2A-AD3FC2A-AD4FC2A-AD5

0 to 5V0 to 10V±5V4 to 20mA±10V

Converts analog signals to digital andsends to input I0 of Micro3

(not for use with AC input type units)

Analog Output Unit

FC2A-DA1FC2A-DA2FC2A-DA3FC2A-DA4FC2A-DA5

0 to 5V0 to 10V±5V4 to 20mA±10V

Converts digital (PWM) signal from output Q0 of Micro3 to analog(not for use with relay output type units)

Analog Timer Unit PFA-1U11 For fine adjustment of analog timer preset value

Input SwitchesFC2A-SW6FC2A-SW9FC2A-SW14

Input simulator switches (6) for 10 I/O Micro3sInput simulator switches (9) for 16 I/O Micro3sInput simulator switches (14) for 24 I/O Micro3s

WindLDR™ WINDLDR Windows-based application software, performs ladder programming and monitors all IDEC PLCs including the Micro series, FA series, and Open NET controllers.

Page 84: CATALOGO DE PLCS IDEC

Programmable Logic Controllers Micro3 Series

J-84 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Optional Item Part Number DescriptionLoader Cable (2m) FC2A-KL3C Connects basic unit (loader port) and program loader

Loader Cable (2m) FC2A-KL4C Connects basic unit (data link terminal) and program loaderModem Cable (3m) FC2A-KM1C Connects basic unit (loader port) and modem (1:1 communications)PC Interface Cable (3m) FC2A-KC4C Connects basic unit (loader port) and PC (1:1 communications)PC Interface Cable (2m) FC2A-KC6C Connects basic unit (data link terminal) and PC (1:1 communications)User Communication Cable (2.4m) FC2A-KP1C Connects basic unit (loader port) and user’s equipmentPC Connect Cable (5m) HG9Z-XC183 Connects basic unit (loader port) and Micro O/I™Memory Card (RAM) FC2A-MC1 Memory to store user’s programs (64K)AC Adaptor PSR-GA05005 Connects basic unit (data link terminal) and program loader/PCExpansion Cable (25cm) FC2A-KE1 Connects basic unit and expansion function unit1:N Link Adaptor FC2A- MD1 Connects basic unit (data link terminal) and PCRS232C Cable (4 lines, 1.5m) HD9Z-C52 Connects link adaptor and PC (1:N communications), D-sub 9-pin

WindLDR™ WINDLDRWindows-based application software, performs ladder programmingand monitors IDEC’s Micro-1, Micro3, and Micro3C PLCs

Part Numbers: Micro3C

Item Part Number DescriptionAC Power

(100 to 240V AC, 50/60Hz power supply)FC2A-C24A1C 24 I/O (14 in, 10 out)

FC2A-C16A1C Base units:Input (24V DC sink/source)Relay output (240V AC/30V DC, 2A)

16 I/O (9 in, 7 out)

DC Power(24V DC, 19 to 30V DC)

FC2A-C24A4C 24 I/O (14 in, 10 out)

FC2A-C16A4C 16 I/O (9 in, 7 out)

Program Loader FC2A-HL1EC Version 2.0+; also compatible with Micro3C

Page 85: CATALOGO DE PLCS IDEC

Programmable Logic Controllers Micro3 Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-85

J

A data link network is simple to set up. No special cables or junctions arerequired. Just wire up to 6 Micro3s or Micro3Cs in a bus configuration, over atotal distance of 656’ (200m).

Using a built-in data link, the master initiates communication automati-cally—no special programming is required. Values from 2 read registers and2 write registers are exchanged between the master and each slave.

Data link channel 19200, RS485 is fixed.

3. The expansion link and data link cannot be used concurrently.

6 Inputs4 Outputs

9 Inputs7 Outputs

12 Inputs8 Outputs

14 Inputs10 Outputs

15 Inputs11 Outputs

18 Inputs14 Outputs

20 Inputs14 Outputs

23 Inputs17 Outputs

28 Inputs20 Outputs

10

16

20

24

26

32

34

40

48

9 Inputs7 Outputs

16

14 Inputs10 Outputs

24

32

48

40

Master:

Slave #1 Slave #2 Slave #3

Slave #6 Slave #5 Slave #4

Slave #1 Slave #2 Slave #3

Slave #6 Slave #5 Slave #4

Master

Micro3 I/O Expansion

18 Inputs14 Outputs

28 Inputs20 Outputs

23 Inputs17 Outputs

2. These Micro3 expansions listed are examples. You may create your owncombinations as well.

FA3S

1. These Micro3C expansions listedare examples. You may createyour own combinations as well.

Micro3 and Micro3C Link with FA3S Master

A high-performance FA3S CPU an PF3S-SIF4 interface module can managedata transfer with up to 6 Micro3s. Two interface modules can be used witheach FA3S CP12 or CP13, making it possible to network up to 12 Micro3stotal.

Using a built-in data link, the master initiates communication automaticallywhen executing a network communication program. Values from 2 read regis-ters and 2 write registers are exchanged between the master and each slave.

Micro3C I/O Expansion Micro3 and Micro3C Data Link

Page 86: CATALOGO DE PLCS IDEC

Programmable Logic Controllers Micro3 Series

J-86 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

RS232 Cable

WindLDR combines the logic of ladder programming with theintuitive approach of a Windows environment. IDEC providesthe ideal PLC programming and monitoring solution.

IDEC’s WindLDR™ includes all the advantages of our CLIPand CUBIQ software, plus a Window-based, graphic inter-face. With extensive new features such as an icon-driventoolbar, on-line help, cross reference cut and paste, programcompass, line dialog screens, and debugging tools.

At an enticingly low price, there is no question—WindLDR isthe solution.

Currently, WindLDR supports the programming configurationfor IDEC’s Micro series. WindLDR is the bridge between olderapplications’ software/hardware and future generations ofIDEC PLCs.

Computer Link 1:1 Communication

Computer Link 1:N Communication (Micro3 only)

WindLDR™ Software Solution — One Application for All PLCs

Computer Link CableFC2A-KC27.87’ (2m) long To RS232C Port

The Micro3 and Micro3C can be programmed from a PC usingWindLDR ladder programming software. A computer linkcable is required to connect the PC’s RS232 serial port withthe Micro’s programming port.

A network of Micro3s can be set up for programming and monitoringwith WindLDR. The network can also be used for supervisory controland data acquisition (SCADA). Up to 32 Micro3s can be networks witha PC as the master. Each Micro3 should be programmed with a spe-cific device number in FUN9. FUN9 can be set with a program loaderor with a PC in 1:1 mode running WindLDR.

Slave #1 Slave #2

N ≤ 32

Link InterfaceFC2A-LC1

Link CableFC2A-KC3

AC Adaptor

RS232C/RS485ConverterHD9Z-T11

Slave #3 Slave #N

Tag Name Editor Advanced InstructionsMultiplication (MUL)

Computer Link CableFC2A-KC4C

9.84’ (3m) long

To RS232C Port To Loader Port(RS232C)

D-sub 9-pinFemale Connector

HD9Z-C52

or 24V DC P/S

Programming Port

Micro3

RS485

Built-inRS232/RS485

Converter

Micro3C

Page 87: CATALOGO DE PLCS IDEC

Programmable Logic Controllers Micro3 Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-87

J

1st UnitFunction selector switch: 0

Protocol selector switch: 2, 3, or 4

RS232C/RS485 Converter FC2A-MD1(H x W x D)

5.92” x 4.33” x 1.34”(132 x 110 x 34mm)

RS232C CableHD9Z-C52

4.92’ (1.5m) long

D-sub 9-pin Female

Connector

To RS232C PortTo RS232C Port

–+24V DC or AC Adapter (9V DC, 350 mA)

Shielded twisted pair cable 656’ (200m) maximum

D-sub 25-pin Male

Connector

A B SG

2nd UnitFunction selector switch: 0

Protocol selector switch: 2, 3, or 4

A B SG

Nth Unit (N≤32)Function selector switch: 0

Protocol selector switch: 2, 3, or 4

A B SG

3rd UnitFunction selector switch: 0

Protocol selector switch: 2, 3, or 4

A B SG

1

T2

A3

B4

SG5

FG6

+7

SD

RD

POWER

DC IN

RS485SERIAL PORT

POWER SUPPLY24V DC

RS

232C

SE

RIA

L P

OR

T

RS232C/RS485CONVERTER

Type FC2A-MD1

Computer Link 1:N Communication (Micro3C only)

To set up a 1:N computer link system, connect your PC to the RS232C/RS485converter using RS232C cable HD9Z-C52. Connect the RS232C/RS485 con-verter to Micro3C units using shielded twisted pair cables.

Supply power to the RS232C/RS485 converter by connecting a 24V DC sourceto terminals 6 and 7 or by plugging an AC adapter to the DC IN jack.

Page 88: CATALOGO DE PLCS IDEC

Programmable Logic Controllers Micro3 Series

J-88 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Micro3CMicro3

Micro3 programs can be created or modified withthe hand held program loader. The loader programsin Boolean commands and displays four lines. It canbe programmed by using a PC or off line with a 5volt adaptor (PSR-GA05005). The loader also can beused to monitor and change all internal registersincluding timers and counters. An optional SRAMmemory card can also be used with the loader tostore up to 31 programs with alphanumeric filenames.

Spec

ifica

tions

Display 4 lines × 16 charactersBack-lit LCD with auto turn-off

Program Key 35 keys

Control Switch RUN/STOP for Micro operation

Power Supply From Micro through loader cable;From AC adaptor (5 to 6.5V DC, 4W) during off-line programming

Power Consumption 1.5W

Connection to Micro3 Loader cable FC2A-KL1, 6.56' (2m) or FC2A-KL2, 16.4' (5m)

Connection to Micro3C Loader cable to RS232 loader port FC2A-KL3C

Connection to Micro3C Loader cable to RS485 data link port FC2A-KL4C

Power Failure Protection Approximately 1 hour at 25°C

User Program Storage SRAM memory card stores up to 31 programs

Operating Temperature 0 to 50°C

Weight Approximately 300g

Dimensions (HxWxD) 7.283" × 3.740" × 1.181" (185 × 95 × 30mm)

FC2A-MC1Optional memory cardstores up to 31 programs

ProgramLoader

Program Loader

Program Loader Cables for Micro3 and Micro3C

Micro3C

AC Adapter (output: 5V DC)The loader cable 4C is not sup-plied with an AC adapter, which

must be prepared by the user

With Loader CableFC2A-KL1 (2m)FC2A-KL2 (5m)

With Loader Cable 3CFC2A-KL3C

The loader cable 3C has anRS232C/RS458 converter

in the middle

With Loader Cable 4CFC2A-KL4C

The loader cable 4Chas a power supply box in the middle

Page 89: CATALOGO DE PLCS IDEC

Programmable Logic Controllers Micro3 Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-89

J

To connect a modem to the loader port on the Micro3C, use the modem cableFC2A-KM1C. Set the protocol selector switch to 1 or 3 to select user protocolfor the loader port.

Cable Connector Pinouts

Pin Description

1 FG Frame Ground

2 TDX Transmit Data

3 RXD Receive Data

4 RTS Request to Send

5 –– ––

6 –– ––

7 SG Signal Ground

8 DCD Data Carrier Detect

20 DTR Data Terminal Ready

To connect equipment with an RS232C communication port to the loader porton the Micro3C, use the user communication cable FC2A-KP1C. One end of theuser end communication cable 1C is not provided with a connector. It can beterminated with a proper connector to plug in to communicate with theRS232C port.

When the protocol selector switch is set to 1 or 3, the Micro3C can communi-cate with RS232C equipment through the loader port using the user protocol.When the protocol selector switch is set to 0, 2, or 4, the Micro3C can commu-nicate through the loader port using the loader protocol.

Cable Connector Pinouts

Pin Description AWG # # Color

1 RTS Request to Send 28 Black

2 DTR Data Terminal Ready 28 Yellow

3 TDX Transmit Data 28 Blue

4 RXD Receive Data 28 Green

5 DSR Data Set Ready 28 Brown

6 SG Signal Ground 28 Gray

7 SG Signal Ground 26 Red

8 NC No Connection 26 White

Cover –– Shield –– ––

Twisted

Twisted

Modem Cable FC2A-KM1C

9.84’ (3m) long

To RS232C Port

D-sub 25=pinMale Connector

To Loader Port(RS232C)

Modem

RS232C EquipmentUser Communication Cable FC2A-KP1C7.78’ (2.4m) long

To Loader Port(RS232C)

To RS232C Port

Attach a proper connector to the open end referring tothe cable connector pinouts

Micro3C: Connecting the Modem through the Loader Port

Micro3C: Connecting RS232C Equipment through the Loader Port

Micro3C

Micro3C

Page 90: CATALOGO DE PLCS IDEC

Programmable Logic Controllers Micro3 Series

J-90 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

The system setup demonstrates a program to send data to a printerusing the user communication TXD (transmit) instruction. Serialprinters used in this example are Seiko Electronic’s DPU-201GSand Citizen’s iDP3110 printers.

System Setup Protocol Selector SwitchSet to 1 or 3 to select user protocol

for the loader port

User Communication Cable 1CFC2A-KP1C

7.87’ (2.4m) long

Attach a connector to the open end of the usercommunication cable 1C referring to the cableconnector pinouts shown below

Cable Connections for Seiko Electronic’s DPU201GS

Mini DIN Connector Pinouts

Description Color Pin

Shield –– Cover

NC No Connection Black 1

NC No Connection Yellow 2

TXD Transmit Data Blue 3

NC No Connection Green 4

DSR Data Set Ready Brown 5

SG Signal Ground Gray 6

SG Signal Ground Red 7

NC No Connection White 8

D-Sub 9-pin Connector Pinouts

Pin Description

1 NC No Connection

2 NC No Connection

3 DATA Receive Data

4 NC No Connection

5 GND Ground

6 NC No Connection

7 NC No Connection

8 BUSY Busy Signal

9 NC No Connection

••

Micro3C: User Communication TXD

To RS232C Port

To Loader Port(RS232C)

Printer3

7 0 126

5 4

Micro3C

Page 91: CATALOGO DE PLCS IDEC

Programmable Logic Controllers Micro3 Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-91

J

DC Input AC Input (Micro3 only)

Inpu

t Spe

cific

atio

ns

Rated Input Voltage(allowable range)

24V DC(19 to 30V DC)

100 to 120V AC(85 to 132V AC)

Rated Input Current 7mA (input I/0: 13mA) 10mA/point

Input Impedance 3.3kΩ (input I/0: 1.8kΩ) 13kΩ

On/Off Current On: 2.5mA (minimum) at 11V DCOff: 1.2mA (maximum)

On: 4mA (minimum) at 79V AC Off: 2mA (maximum)

On/Off Voltage On: 11V DC (minimum)Off: 5V DC (maximum)

On: 79V AC (minimum)Off: 20V AC (maximum)

On/Off Time Depends on input filter setting (see note) On: 20ms (maximum)Off: 20ms (maximum)

Rela

y O

utpu

t Spe

cific

atio

ns Configuration

10 I/O(Micro3 only)

4 outputs: Independent NO = 1 point, Common NO = 3 points

16 I/O7 outputs: Independent NO = 1 pointCommon NO = 2 points + 4 points

24 I/O10 outputs: Independent NO = 2 pointsCommon NO = 4 points + 4 points

AC in(Micro3 only)

7 outputs: Independent NO = 3 pointsCommon NO = 4 points

Switching CapacityIndependent contact: 240V AC or 30V DC, 2A (resistive load)Common contact: 240V AC or 30V DC, 2A × output points (resistive load)

Minimum Applicable Load 5V DC, 1mA (reference value)

Contact Resistance 30mΩ maximum (initial value)

Life RatingsMechanical: 20,000,000 operations (no load) at 1,800 operations/hourElectrical: 100,000 operations (rated load) at 1,800 operations/hour

Each unit can be used as a CPU or expansion I/O using a selection switch. Sink/source inputs can be used with NPN- or PNP-output sensors. Input on and off times can be selected using the input filter function (FUN7 setting).

CPU Input/Output

Key features of the Micro3 and Micro3C input include:• AC or DC inputs (Micro3) or DC inputs (Micro3C)• Expandable from 10 to 48 I/O points• Configure inputs: Sink or source for NPN or PNP devices• Each unit selectable: CPU or expansion I/O• LED indicators• Optical isolation

Page 92: CATALOGO DE PLCS IDEC

Programmable Logic Controllers Micro3 Series

J-92 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

G NC NC 20 1 3

COMGND

L N

GND100 to

240V AC

100 to120V

AC

C

AC Inputs(Micro3 only)

C0 1 2 3COM

COM

0 C1

LL

L L

Relay Outputs 10 I/O

External Power240V AC/30V DC2A x Output Points

0 1 2 3 64 5 +V––COM

COM

LL

LL

LL

L

+

0 1 2 3 64 5 -V++COM

COM

LL

LL

LL

L+

–ExternalPower24V DC

C0 1 2 3 64 5COM

COM

0 C1 C2COM

LL

LL

LL

L

C0 1 2 3 64 5COM

COM

0 C1 C2COM

LL

LL

LL

L

7 10 11C3COM

LLL

16 I/O24 I/O

ExternalPower24V DC

Transistor Outputs

DC Input Circuit Diagrams

Transistor and Relay Output Circuit Diagrams

G 20 1 3C

COMGND4 5

GND

+ – NC NC

ExternalPower

24V DC

+

G 20 1 3C

COMGND4 5

GND

+ – NC NC

ExternalPower

24V DC+

G 24V 0V 20 1 3C

COMGND4 5L N

GND

G 24V 0V 20 1 3C

COMGND4 5L N

GND

G 24V 0V 20 1 3C

COMGND4 5L N

GND

G 24V 0V 20 1 3C

COMGND4 5L N

GND

Using Sensor P/S

Using External P/S

100 to240V AC

100 to240V AC

100 to240V AC

100 to240V AC

24V DC 24V DC+– +

Sen

sor

Sen

sorDC Inputs

(AC power)

DC Inputs(DC power)

(Micro3 only)

Page 93: CATALOGO DE PLCS IDEC

Programmable Logic Controllers Micro3 Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-93

J

Tran

sist

or O

utpu

t Spe

cific

atio

ns

Configuration10 I/O 4 outputs: Common NO = 4 points

16 I/O 7 outputs: Common NO = 3 points + 4 points24 I/O 10 outputs: Common NO = 5 points + 5 points

Rated Load 0.5A, 24V DC — Maximum: 0.625A/circuit (30V DC)Inrush Current 5A, 1ms (maximum)Leakage Current 0.1mA (maximum)On Voltage Sink: 1.5V DC (maximum)

On/Off Time On: 500µs (output Q0: 5µs),Off: 500µs (output Q0: 5µs)

External Current Draw 24V DC, 100mA (maximum)

16 I/O 24 I/O10 I/O

CPU: Transistor Output (Micro3 only)

Each unit can be used as a CPU or expansion I/O using a selection switch. Sink/source inputs can be used with NPN- or PNP-output sensors. Input on and off times can be selected using the input filter function (FUN7 setting).

DC

Inpu

t Spe

cific

atio

ns

Rated Input Voltage(allowable range)

24V DC(19 to 30V DC)

Rated Input Current 7mA (input I0: 13mA)

Input Impedance 3.3kΩ (input I0: 1.8kΩ)

On/Off Current On: 2.5mA (minimum) at 11V DC Off: 1.2mA (maximum)

On/Off Voltage On: 11V DC (minimum)Off: 5V DC (maximum)

On/Off Time Depends on input filter setting (see note)

Page 94: CATALOGO DE PLCS IDEC

Programmable Logic Controllers Micro3 Series

J-94 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Key features of the analog input and output units include:• Micro supports one analog in and one analog out• Input/output units accept a variety of signals • Units connect to input Ø and/or output Ø

AD Converter Unit DA Converter Unit

Spec

ifica

tions

Number of Inputs 1 channel 1 channel

Resolution 250 (see chart below) 245 (see chart below)

Total Accuracy ± 1% of the maximum value ± 1% of the maximum value

Conversion Time 125ms 0 to 95%: 500ms

Maximum Applicable Input 16V DC 30V DC

Maximum Applicable Output 30V DC Voltage output: 12V DC

Current output: 12V DC or –0.6V DC

Output Short Circuit Not allowed Allowed (infinite period of time)

Recommended Output LoadImpedance

—Voltage output: 5kΩ or moreCurrent output: 250Ω or less (300Ω maxi-mum)

Input Frequency — 312.5Hz (PWM mode must be set to MODE3)

Output Ripple — 1 LSB or less

Analog Input/Output Units

Analog output is only available for the Micro3.

Increments

PWM Operand S10 249

Minimum

Maximum

245

5

InputMinimum Maximum

0

249

250Increments

A/D Converted Value

D/A Converted Value

Analog/Digital Conversion Charts

Type Input Signal Range

AD

0 to 5V DC

0 to 10V DC

±5V DC

4 to 20mA DC

±10V DC

DA

0 to 5V DC

0 to 10V DC

±5V DC

4 to 20mA DC

±10V DC

Page 95: CATALOGO DE PLCS IDEC

Programmable Logic Controllers Micro3 Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-95

J

+ –24V DC

A/D UNIT

INPUT4-20mA

POWER

SINK

SCE

+ –ANALOG WIRE TO

IN 0

INPUT OUTPUT

DC OUT24V 0V

DC INCOM 0

24V DCPower

+–

FG

AnalogInput

Shield Wire

Set the output selector switch to SCE.

When using the Micro inthe sink input connec-tion, select the sourceoutput from the A/Dconverter unit.

3A Fuse

1

PNP

+ –24V DC

A/D UNIT

INPUT4-20mA

POWER

SINK

SCE

+ –ANALOG WIRE TO

IN 0

INPUT OUTPUT

DC OUT24V 0V

DC INCOM 0

24V DCPower

+–

FG

Set the output selector

AnalogInput

Shield Wire

switch to SINK.

When using the Microin the source inputconnection, select thesink output from theA/D converter unit.

1

NPN

3A Fuse

Analog Input and Wiring Diagrams (Micro3 and Micro3C)

The A/D converter unit is used with the Micros to perform an 8-bitA/D conversion. The A/D converter unit reads an analog input sig-nal from an analog output device such as an analog distance sen-sor. The output from the A/D converter unit is entered to the Microinput I0 and converted into a digital value (0 through 249) using theA/D (analog/digital conversion) instruction. If the input to the A/D converter unit exceeds the input range, thenan overflow occurs, and 250 is set to the destination operand of theA/D instruction. Only one A/D converter unit can be connected tothe Micro base unit.

When the A/D converter unit is connected to the Micro, the HSC (high-speed counter) function cannot be used.

Source Input

Sink Input

Page 96: CATALOGO DE PLCS IDEC

Programmable Logic Controllers Micro3 Series

J-96 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

The D/A converter unit is used with the transistor output typeMicro3 base unit to perform an 8-bit D/A conversion. The pulsewidth modulation instruction is used to convert the digital value toa pulse output signal. The output from the Micro3 output Q0 isentered to the D/A converter unit to generate an analog current orvoltage output to control an inverter. Only one D/A converter unitcan be connected to the Micro3 base unit.

24V DCPower

+–FG

Set the input selector

Analog

Shield Wire

+ –24V DC

D/A UNIT

OUTPUT4-20mA

POWER

SCE

SINK

+ –ANALOG WIRE TO

OUT 0

OUTPUT INPUT

Ground the FG terminal.

switch to SINK.

Output

OUTCOM0(+) 0 1 2 3 OUT

COM1(+) 4 5 6 –V

When using a transistor protect source output type Micro3 base unit, select the sink input to the D/A converter unit.

1A Fuse

24V DCPower

+–FG

Set the input selector

Analog

Shield Wire

+ –24V DC

D/A UNIT

OUTPUT4-20mA

POWER

SCE

SINK

+ –ANALOG WIRE TO

OUT 0

OUTPUT INPUT

Ground the FG terminal.

switch to SCE.

Output

OUTCOM0(–) 0 1 2 3 OUT

COM1(–) 4 5 6 +V

When using a transistor sink out-put type Micro3 base unit, selectthe source input to the D/A con-verter unit.

1A Fuse

Analog Output and Wiring Diagrams (Micro3 only)

Transistor Sink Output

Transistor Protection Source Output form Micro3

Page 97: CATALOGO DE PLCS IDEC

Programmable Logic Controllers Micro3 Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-97

J

Steps Instruction Description

Adv

ance

d In

stru

ctio

ns

1 0 NOP No operation

3 – 43 – 45 – 65 – 6

11121314

MOVMOVNIMOVIMOVN

Word moveWord move notWord indirect moveWord indirect move not

4 – 54 – 54 – 54 – 54 – 54 – 5

212223242526

CMP=CMP<>CMP<CMP>CMP<=CMP>=

Equal compareNot equal compareLess than compareGreater than compareLess than or equal compareGreater than or equal compare

4 – 54 – 54 – 54 – 5

31323334

ADDSUBMULDIV

AdditionSubtractionMultiplicationDivision

4 – 54 – 54 – 5

414243

ANDWORWXORW

And wordOr wordExclusive or word

3333

51525354

SFTLSFTRROTLROTR

Shift leftShift rightRotate leftRotate right

22221

7172737475

CALRCALWCLKRCLKWADJ

Calendar read*Calendar write*Clock read*Clock write*Adjust*

442

818283

DISPDGRDANR0

DisplayDigital switch readAnalog potentiometer 0 read

2 84 ANR1 Analog potentiometer 1 read*

332

919293

PULSPWMA/D

Pulse outputPulse width modulationConvert analog to digital

4242

A1A2A3A4

HSC0HSC1HSC2HSC3

H/S counter 0 (32 bits)H/S counter 1 (32 bits)H/S counter 2 (32 bits)H/S counter 3 (16 bits)

5 – 404 B1 TXD Transmit (Micro3C only)

5 – 404 B2 RXD Receive (Micro3C only)

4 – 5 B3 COMP2 Double word compare (Micro3C only)

Steps Instruction Description

Bas

ic In

stru

ctio

ns

111

ANDAND LODANDN

AndAnd loadAnd not

111

BPPBPSBRD

Bit popBit pushBit read

222

CNTCC=CC≥

CounterCounter compare =Counter compare ≥

1 END End11

JENDJMP

Jump endJump

11

LODLODN

LoadLoad not

11

MCSMCR

Master control setMaster control reset

— NOT Not111

OROR LODORN

OrOr loadOr not

11

OUTOUTN

OutputOutput not

11

RSTSET

ResetSet

22

SFRSFRN

Shift registerShift register not

11

SOTDSOTU

Single output fallingSingle output rising

222

TIMTMTMS

100ms timer10ms timer1ms timer

Instruction Set

Instructions designated by * are not affected by the change to the year 2000.

Page 98: CATALOGO DE PLCS IDEC

Programmable Logic Controllers Micro3 Series

J-98 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Dimensions

Key to Dimensions

AC Input Units W C

10 I/O 4.134" (105mm) 3.386" (86mm)

16 I/O 5.315" (135mm) 4.567" (116mm)

24 I/O* 6.496" (165mm) 5.748" (146mm)*

3.740"(95mm)

3.150"(80mm)

1.181"(30mm)

0.984"(25mm)

7.283"(185mm)

Program Loader

3.031"(77mm)

M4 tapped orØ 0.177" (Ø 4.5mm)

C

Mounting Hole Layout

1.77"(45mm)

2.76"(70mm)

2.76"(70mm)

3.15"(80mm)

1.38"(35mm)

Ø 0.17"

2 holes(4.3mm)

A/D and D/A Analog Converters

3.346"

(85mm)

W

2.362"

(60mm)

Micro3 and Micro3C Base Units

*Dimensions are the same for the 16 I/O AC input unit.

Page 99: CATALOGO DE PLCS IDEC

Programmable Logic Controllers Micro-1 Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-99

J

Gen

eral

Spe

cific

atio

ns

Programming Boolean or ladder logic

Available Instructions 15 basic instructions, 2 FUN instructions

Program Capacity 600 steps

Memory EEPROM memory built-in to base unit

Scan Time Average: 8µs per basic instruction

Input Base unit: 8 points, Expansion: 8, 4, or 2 points

Output Base unit: 6 points, Expansion: 6, 3, or 2 points

Total I/O Points 28 points (maximum)

Internal Relay 160 points (all points can be maintained)

Special Internal Relay 96 points

Shift Register 128 points

Catch Input 1 point, 0.5ms pulse

Single Shot Output 96 points

Timer 80 points, subtracting (0 to 999.9s)

Counter 45 points, adding (0 to 9999)(all points can be maintained)

Reversible Counter 2 points (all points can be maintained)

Computer Link Via RS232 interface unit

External Control Input Start/stop using switch on program loader

Power Failure Protection Capacitor back-up: 3 days; internal relay, shift register, counter, reversible counter

Self-Diagnostics CPU error (WDT), CRC error, check sumerror, communication error

Auto Start Function Operation starts after power-up

FA Series Compatibility Program loaders are interchangeable using special cables

Micro-1:The Original Micro-PLCEl

ectr

ical

Spe

cific

atio

ns

Rated Supply Voltage AC CPU base unit and (8 in/6 out) expansion: 100 to 240V AC, 50/60Hz (47.5–63Hz)24V DC base unit and all expansion units: 12V DC CPU base unit and (8 in/6 out) expansion

Voltage Range AC: 85 to 110% of rated voltage 24V DC: 80 to 120%; 12V DC: 70 to 120%

Dielectric Strength Between power or I/O terminal and ground: 1,500V AC, 1 minute

Insulation Resistance Between power or I/O terminal and ground: 10MΩ (500V DC megger)

Temperature Operating: 0 to +55°C; Storage: – 20 to +70°C

Operating Humidity 45 to 85% RH (avoid condensation)

Vibration Resistance 5 to 55Hz, 6G for 2 hours in each of 3 axes

Shock Resistance 30G, 3 shocks in each of 3 axes

Noise Resistance Between power or I/O terminal and ground: AC: ±1.3kV, 1µs; 24V DC: ±1.0kV, 1µs; 12V DC: ±500V, 1µs

Ground Resistance 100Ω (maximum)

Mounting Style 35mm DIN rail and panel mount

UL ListedFile No. E102542

CSA CertifiedFile No. LR66809

CE Certified

The CPU base unit suppliespower to the micro-expansionunits and program loader.Micro-expansion units are notcompatible with 12V DC CPU.

Key features of the Micro-1 PLC include:• Intelligent control economically replaces hard-wired systems • 8 inputs, 6 outputs• DC inputs, relay or transistor outputs• Expansion unit doubles I/O (16 inputs, 12 outputs)• Micro-expansion I/O for incremental I/O increases• 80 timers, 47 counters, 160 internal relays• CPU base unit supplies power for input signals• Program capacity 600 steps• Computer link, networking

EMC ApprovedFile No. E951113332321

Page 100: CATALOGO DE PLCS IDEC

Programmable Logic Controllers Micro-1 Series

J-100 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Part Numbers: Micro-1

CPU Base Unit

ACRelay Output

Source Input FC1A-C1A1E Power: 100–240V AC; NPN transistor inputs, relay outputsSink Input FC1A-C2A1E Power: 100–240V AC; PNP transistor inputs, relay outputs

Transistor OutputSource Input/Sink Output FC1A-C1B1E Power: 100–240V AC; NPN transistor inputs, NPN transistor outputsSink Input/Source Output FC1A-C2C1E Power: 100–240V AC; PNP transistor inputs, PNP transistor outputs

DC

Relay OutputSource Input

FC1A-C1A4E Power: 24V DC; NPN transistor inputs, relay outputsFC1A-C1A2E Power: 12V DC; NPN transistor inputs, relay outputs

Sink InputFC1A-C2A4E Power: 24V DC; PNP transistor inputs, relay outputsFC1A-C2A2E Power: 12V DC; PNP transistor inputs, relay outputs

Transistor OutputSource Input/Sink Output

FC1A-C1B4E Power: 24V DC; NPN transistor inputs, NPN transistor outputsFC1A-C1B2E Power: 12V DC; NPN transistor inputs, NPN transistor outputs

Sink Input/Source OutputFC1A-C2C4E Power: 24V DC; PNP transistor inputs, PNP transistor outputsFC1A-C2C2E Power: 12V DC; PNP transistor inputs, PNP transistor outputs

Expansion I/O

Relay OutputSource Input FC1A-E1A1E Power: 100–240V AC, NPN transistor inputs, relay outputs

Sink Input FC1A-E2A1E Power: 100–240V AC, PNP transistor inputs, relay outputs

Transistor OutputSource Input/Sink Output FC1A-E1B1E Power: 100–240V AC; NPN transistor inputs, NPN transistor outputs

Sink Input/Source Output FC1A-E2C1E Power: 100–240V AC; PNP transistor inputs, PNP transistor outputs

Relay OutputSource Input FC1A-E1A4E

FC1A-E1A2EPower: 24V DC, NPN transistor inputs, relay outputsPower: 12V DC, NPN transistor inputs, relay outputs

Sink Input FC1A-E2A4EFC1A-E2A2E

Power: 24V DC, PNP transistor inputs, relay outputsPower: 12V DC, PNP transistor inputs, relay outputs

Transistor OutputSource Input/Sink Output FC1A-E1B4E

FC1A-E1B2EPower: 24V DC, NPN transistor inputs, NPN transistor outputsPower: 12V DC, NPN transistor inputs, NPN transistor outputs

Sink Input/Source Output FC1A-E2C4EFC1A-E2C2E

Power: 24V DC, PNP transistor inputs, PNP transistor outputsPower: 12V DC, PNP transistor inputs, PNP transistor outputs

Accessories

Program Loader FC1A-HL1E 24 keys, 16-character LCD

Data Preset LoaderStandard FC1A-PL1E Change timer/counter presets, monitor I/O, internal relay, timer, counter

Multi-Function FC1A-PL2E Change preset values, monitor, direct set/reset, read program, and more

Loader Extension CableFC1A-KL1AFC1A-KL2AFC1A-KL3AFC1A-KL4A

5' (1.5m), connects program loader to base unit2.75" (70mm) curl cord (attached to loader)5' (1.5m), connects FA series program loader to Micro-1 base unit5' (1.5m), connects Micro-1 program loader to FA series CPU

I/O Expansion Cable FC1A-KE1PFA-1A*

1.57" (40mm) (attached to expansion unit)*21: 19.7" (0.5m), 22: 29.53" (0.75m), 23: 39.37" (1m)

Connect expansionunit to base unit

Micro Expansion Unit

FC1A-M1XEFC1A-M2XEFC1A-MXAEFC1A-M1BEFC1A-M2CE

4-point source input4-point sink input3-point relay output2-point source input, 2-point sink output2-point sink input, 2-point source output

Micro Expansion Cable FC1A-KM* *1: 19.7" (0.5m), 2: 39.37" (1m)

Serial I/O Module FC1A-SM1E 8 inputs and 8 outputs with serial cable (order FC1A-KS*A separately)

Serial Cable FC1A-KS*A *1: 39.37" (1m), 2: 78.74" (2m), 3: 118.11" (3m) Connect serial I/O module to CPU base unit (with shield terminal—one end)

Serial I/O Transition 20-pin interface to discrete terminal blocks (simplify installation of serial I/O)

Analog Timer UnitExternal Power SupplyDigital Display Mother Board

FC1A-TA1PSR-AD07*EFC1A-PD1

Contains 4 analog timers (8 time ranges from 1 second to 10 minutes)*12: 12V DC, 0.63A output, 24: 24V DC, 0.32A outputTo mount a serial I/O module and digital displays such as IDEC’s DD33 series

Link Adaptor CableFC Link CableComputer Link Cable

PF2-CLAFC1A-KC1APFA-1A54A

Interface PC to Micro-1 CPU base unit for 1:1 communication5.91" (150mm) curl cord: CPU base unit to PFJ-U11, PFJ-U21, or PF2-CLA78.74" (2m), connects PC to PFJ-U12, PFJ-U22, or PF2-CLA

Software WINDLDR Windows-based programming software

Micro-1 Starter Kit MM-MICRO-1 Micro-1 PLC, WindLDR™ software, computer link cable

Page 101: CATALOGO DE PLCS IDEC

Programmable Logic Controllers FA2J Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-101

J

Key features of the FA2J flat-pack modular include:• 6ms/K processing• Up to 128 inputs, 128 outputs• DC inputs, relay or transistor outputs• Low profile for shallow panels• 8-bit or 12-bit analog input, multiplexer• Replaceable relays• Memory: 1K, 4K• High-speed counter• Computer link, networking

Flat-Pak ModularSp

ecifi

catio

ns

Programming Boolean or ladder logic

Available Instructions 15 basic, 57 advanced instructions [FA1J: 27 advanced instructions]

Capacity 964 steps (1K memory) 3,300 steps (4K memory)

Memory 1K, 4K CMOS-RAM (with battery) 4K EEPROM

Processing 6ms per 1K (basic instructions) [FA1J: 32ms per 1K]

Input 128 points (maximum)

Output 128 points (maximum)

Total I/O 256 points (maximum)

Internal Relay 608 points (240 can be maintained) [FA1J: 240 points; all can be maintained]

Special I/R 16 points

Shift Register 128 points (all can be maintained)

Single Shot Output 96 points

10ms Timer 80 points, subtracting, 0 to 999.9s 80 points [FA1J: not available]

Counter 45 points, adding, 0 to 9,999 (all can be maintained)

Reversible Counter 2 points (all can be maintained)

Data Register 400 points (all can be maintained) [FA1J: 100 points; all can be maintained]

Computer Interface RS-232 link adaptor

External Control Start: input 0; Stop and reset: function settings

Power Failure Protection Internal relay, shift register, counter, reversible counter, data register

Diagnostics CPU error (WDT), communication error, CRC error in user programs, operation code error

Auto Start After power-up, automatic run state using function setting

Rated Voltage 100 to 240V AC 50/60Hz; Allowable: 85 to 110% of rated voltage;24V DC ±20% (ripple 10% maximum)

Dielectric Strength Between power or I/O terminal and ground: 1,500V AC, 1 minute (500V AC for analog lines)

Insulation Resistance Between power or I/O terminal and ground: 10MΩ (500V DC megger)

Temperature Operating: 0 to +55°C; Storage: – 20 to +70°C

Operating Humidity 45 to 85% RH (avoid condensation)

Vibration Resistance 2G, 1 hour in each of 3 axes

Shock Resistance 10G

Noise Resistance Between power or I/O terminal and ground: ±1.3kV p-p, 1µs (1kV DC pulse generator)

Ground Resistance 100Ω (maximum)

Mounting Style Panel mount

UL ListedFile No. E102542

CSA CertifiedFile No. LR66809

Page 102: CATALOGO DE PLCS IDEC

Programmable Logic Controllers FA2J Series

J-102 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Part Numbers: FA2J

Item Part Number Description

CPUAC PF2J-CPU1E

PFJ-CR1EFA2J CPU; power: 100 to 240V ACFA1J CPU; power: 100 to 240V AC

DC PF2J-CPU1DCEPFJ-CR1DCE

FA2J CPU; power: 24V DCFA1J CPU; power: 24V DC

PowerACDC

PFJ-PS1PFJ-PS1DC

Internal power supply for I/O expansion (100 to 240V AC)Internal power supply for I/O expansion (24V DC)

External PFJ-PU2 External power supply for DC inputs, sensors (24V DC/0.5A)

Expansion

Base Plate PFJ-EB1 For installing two I/O modules

Double-Stack Expan-sion

PFJ-DP1 Mount CPU or expansion power, plus “piggyback” mountingcapacity for two I/O modules (order one PFJ-EB1 separately)

PFJ-DP2 Mount two I/O modules, plus “piggyback” mounting capacityfor two more I/O modules (order two PFJ-EB1s parts separately)

Input

8-Point DCTransistor (source) PFJ-N081 24V DC NPN transistor inputsTransistor (sink) PFJ-N082 24V DC PNP transistor inputs

8-Point AC100V AC PFJ-N083

PFJ-N083A100 to 120V AC inputs, standard response100 to 120V AC inputs, fast response

200V AC PFJ-N084PFJ-N084A

200 to 240V AC inputs, standard response200 to 240V AC inputs, fast response

16-Point DCTransistor (source) PFJ-N161

PFJ-N161A24V DC NPN transistor inputs5V DC NPN transistor inputs

Transistor (sink) PFJ-N162 24V DC PNP transistor inputs

AnalogInput

8-BitVoltage PFJ-N012

PFJ-N012A0 to 10V DC inputs, 8-bit resolution, fast response0 to 10V DC inputs, 8-bit resolution, standard response

Current PFJ-N013PFJ-N013A

4 to 20mA DC inputs, 8-bit resolution, fast response4 to 20mA DC inputs, 8-bit resolution, standard response

12-BitVoltage PFJ-N112A

PFJ-N113A0 to 10V DC analog input, 1 point, 12-bit resolution1 to 5V DC analog input, 1 point, 12-bit resolution

Current PFJ-N114A 4 to 20mA DC analog input, 1 point, 12-bit resolution

Multiplexer 12-BitAnalog Input

VoltageCurrent

PFJ-4MPVPFJ-4MPI

Analog multiplexer module, 4 points, voltageAnalog multiplexer module, 4 points, current

Output

8-PointRelay PFJ-T081 1NO contact, rated load 110V AC, 5A; 220V AC, 2ATransistor (sink) PFJ-T082 Rated load 12 to 48V DC, 1A per pointSSR PFJ-T083 Rated load 100 to 240V AC 1A per point

16-PointTransistor

Transistor (sink) PFJ-T162PFJ-T162A

Rated load 12 to 28V DC, 0.5A per pointRated load 5 to 12V DC, 20mA per point

Transistor (source) PFJ-T162BPFJ-T162C

Rated load 12 to 28V DC, 50mA per pointRated load 12 to 28V DC, 0.5A per point

Analog VoltageCurrent

PFJ-T012PFJ-T013

0 to 10V DC output, 8-bit resolution4 to 20mA DC output, 8-bit resolution

Program Loader LoaderExtension Cable

PF2-2H4REPFA-1A11

Program loader with built-in PROM burner 59" (1.5m) —not included with program loader

Memory Packs(see details on page J-103)

PFA-1M14PFA-1M21PFA-1M24

4K EEPROM (compatible with FA3S)1K CMOS-RAM (compatible with FA3S)4K CMOS-RAM (compatible with FA3S)

High Performance Input High-Speed Counter PFA-N011APFA-N011B

Single-phase, for high-frequency inputsTwo-phase, for quadrature rotary encoder inputs

Blank Module PFJ-DM Occupies unused slot on base plate

Computer Interface

PF2-CLAPFJ-U21PFJ-U22PFA-1A51PFA-1A54ACLIP

Link adaptor for 1:1 communications to IBM-compatible PCLink for 1:N communication (use with twisted-pair cable)Main unit for 1:N communication (use with twisted-pair cable)Link cable, FA series CPU to link adapter 12” (300mm)Link cable, PC to link adapter, 78.74” (2m)Ladder diagram software for programming and monitoring

Page 103: CATALOGO DE PLCS IDEC

Programmable Logic Controllers FA3S Series

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-103

J

Standard CPUS High-Performance CPU

Gen

eral

Spe

cific

atio

ns

Available Instructions 15 basic, 57 advancedCP11T: plus 6 clock and protect instructions

15 basic122 advanced

Program CapacityCP11: 964 steps (1K memory)3,300 steps (4K memory)CP11T: 3,300 steps (built-in EEPROM)

964 steps (1K memory)4,036 steps (4K memory)CP13: 8,072 steps (8K memory)

MemoryCP11: 1K and 4K CMOS-RAM (with battery);4K EEPROM; 4K EPROMCP11T: Built-in 4K EEPROM memory

1K and 4K CMOS-RAM (with battery);4K EEPROMCP13: 8K CMOS-RAM or EEPROM

Average Scan Time 6µs per basic instruction 0.3µs per basic instruction

Input 128 points (maximum) I/O configurable

Output 128 points (maximum) I/O configurable

Total I/O Points 256 points 256 points

Internal Relay 608 points (240 points can be maintained) 1,024 points (240 points can be maintained)

Special Internal Relay CP11: 16 points; CP11T: 18 points 32 points

Shift Register 128 points 224 points

Single Shot Output 96 points 256 points

Timer 80 points, subtracting (0–999.9s) 256 points

10ms Timer 80 points 80 points

Counter 45 points, adding (0–9,999)(all points can be maintained)

100 points, adding (0–9,999) (all points can be maintained)

Reversible Counter 2 points (all points can be maintained) 2 points (all points can be maintained)

Data Register 400 points (all points can be maintained) 1,000 points (all points can be maintained)

Forced I/O Not available Available (50 points simultaneously)

Remote I/O Not available 1,024 points (plus 256 points basic capacity)

Runtime Program Modify Not available Available

Real-Time Clock/Calendar Runtime Available on CP11T only Not available

Program Protection Available on CP11T only Available

High-Performance Modules High-speed counter (PF3S-HSC2) High-speed counters (PF3S-HSC1 and -HSC2),high-speed interrupt I/O, remote I/O, RS232, RS485

External Control Start: input 0 (release possible); Stop/reset: function designated

Power Failure Protected: Internal relay, shift register, counter, reversible counter, data register

Self-Diagnostics CPU error (WDT), communication error, CRC error in user programs, operation code error

Auto Start Function After power-up, automatic run, function designated

Key features of the FA3S include:• Up to 256 local I/O points• Up to 1,024 fiber optic remote I/O points,

from up to 3,280’ (1km) away• 8-channel analog module• RS232 and RS485 modules available• Modem communications• Real-time clock and calendar available• High-speed interrupt I/O (16 or 32 points)• Average Boolean scan: 0.3ms/K• Up to 8K program steps• Built-in programming/ASCII port

UL ListedFile No. E102542

CSA CertifiedFile No. LR66809

CE CertifiedEMC Approved*File No. E9960513332*Some modules excepted

The FA2 loader (PF2-2H4RE) and FA3 loader (PF3S-HL161E) are compatible with all FA series PLCs and the Micro-1.

FA3S: The Powerhouse

Page 104: CATALOGO DE PLCS IDEC

Programmable Logic Controllers FA3S Series

J-104 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

JThe power requirements listed are maximums. For input modules, all inputs are on. For output modules, all outputs are on. For combination I/O modules, all inputs and outputs are on.

Pow

er R

equi

rem

ents

Standard CPU PF3S-CP11with program loader

130mA 480mA

Standard CPU withClock Protection

PF3S-CP11Twith program loader

80mA 430mA

High-Performance CPUs PF3S-CP12, -CP13with program loader

120mA 470mA

In: 16-Point Transistor PF3S-N16B 80mAIn: 32-Point Transistor PF3S-N32B, -N325B 160mAIn: 16-Point AC PF3S-N16A1, -N16A2 90mAIn: 8 Channel Analog Input PF3S-AD8B1, -AD8B2 150mAIn: Analog PF3S-AD121, -AD122 40mAMultiplexer PF3S-MP41 60mACombination I/O PF3S-M32K, -M325K 190mAOut: 8-Point Relay PF3S-R081 170mAOut: 16-Point Relay PF3S-R161 330mAOut: 16-Point SSR PF3S-S161 280mAOut: 16-Point Transistor PF3S-T16K, -T16S 130mAOut: 32-Point Transistor PF3S-T32K, -T325K, -T32S 240mAOut: Analog PF3S-DA121 40mAHigh-Speed Counter PF3S-HSC1, -HSC2 30mAHigh-Speed I/O PF3S-HSL1 200mA

Serial Interface PF3S-SIF2PF3S-SIF4

60mA110mA

Remote I/O Master PF3S-RMP1, -RMQ1 180mARemote I/O Slave PF3S-RTP1, -RTQ1 250mAAC Power Supply (standard) PF3S-PSA1 50VAAC Power Supply (large capacity) PF3S-PSA2 85VADC Power Supply PF3S-PSD1 32WExternal Power Supply PF3S-EPA1 85VABackplane 2 slot PF3S-BP12Backplane 3 slot PF3S-BP13

Part Numbers: FA3S Series

Page 105: CATALOGO DE PLCS IDEC

Programmable Logic Controllers Programming Software

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-105

J

WindLDR™ Programming Software

Where Logic and Intuition ConvergeWindLDR, IDEC’s Windows-based, Ladder programming tool successfully com-bines logic and intuition. IDEC’s WindLDR includes a graphic interface, icon-driven tool bar, on-line help, and debugging tools. In its first release, WindLDRprograms the Micro-1, Micro3, Micro3C, FA Series, ONC and MicroSmart.

WindLDR is your icon-driven, multi-window, all-inclusive tool.

Key features of the WindLDR software package include:• Use the Tag Editor to access and edit all coil data in one

convenient option• Customize toolbars, ladder file characteristics, and more• Access the most common commands with the context-sensitive

right mouse button• Open and use unlimited ladder files• Monitor and de-bug PLC functionality on-line• Edit ladders simply, with a drag and drop toolbar

Tag Name Editor

Tag Name Editor

Gen

eral

Spe

cific

atio

ns

Cut and Paste Function Select one rung or multiple rungs

Tag Editor Access and edit all coil data in one convenient option

Customization For toolbars, ladder file characteristics, and many program features

Right Mouse Button Context-sensitive for convenient access to most commonly used commands

On-Line MonitoringDe-bug and observe real-time PLC functionality,right from your PC.Write new values to counters, timers, and data registers.

Multiple Ladder Files Open unlimited ladder files to compare and reuse instantly, even if they are written for different PLCs

Drag and Drop User friendly toolbar makes ladder creation andediting simple

Find String Searches for text in various ways; large ladder filesare easy to manage

Multi-Level Undo Limited only by available memory

CLIP and CUBIQ Fully compatible for upgrade

On-Line Help Context-sensitive; extensive coverage of WindLDRand PLC functionality

ManualsThe WindLDR Tutorial provides a quick, simple way to get up and running; the comprehensive WindLDR Reference Manual answers basic through advanced questions

Support IDEC engineers maintain an excellent level of customerservice and software support

Platforms Microsoft® Windows 95, 98, 2000, Me, NT 4.0

System RequirementsCPU: Pentium 75MHz or higher; 24MB available RAM on Win95 and Win98; 32MB available RAM on Win2000, NT20MB free hard disk space

Installation Software CD-ROM

Page 106: CATALOGO DE PLCS IDEC

Programmable Logic Controllers Programming Software

J-106 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC

J

Programming Instruction Set

Instruction Set Mic

ro-3

Mic

ro-3

C

ON

C

Mic

roSm

art

Basic Instruction ListAND And • • • •ANDLOD And load • • • •ANDN And Not • • • •BPP Bit Pop • • • •BPS Bit Push • • • •BRD Bit Read • • • •CC= Counter Comparison (=) • • • •CC≥ Counter Comparison (≥) • • • •CDP Dual Pulse Reversible Counter • • • •CNT Counter • • • •DC= Data Register Comparison (=) • •DC≥ Data Register Comparison (≥) • •END End • • • •JEND Jump End • • • •JMP Jump • • • •LOD Load • • • •LODN Load Not • • • •MCR Master Control Reset • • • •MCS Master Control Set • • • •OR Or • • • •OR LOD Or Load • • • •ORN Or Not • • • •OUT Output • • • •OUTN Output Not • • • •RST Reset • • • •SET Set • • • •SFR Shift Register • • • •SFRN Shift Register Not • • • •SOTD Single Output Down • • • •SOTU Single Output Up • • • •TIM Timer • • • •Advanced Instruction ListGroup Symbol • •NOP NOP • • • •

Move

MOV • • • •MOVN • • • •IMOV • • • •IMOVN • • • •BMOV • •IBMV • •IBMVN • •

Data Comparison

CMP= • • • •CMP<> • • • •CMP< • • • •CMP> • • • •CMP<= • • • •CMP>= • • • •ICMP>= • •

Binary Arithmetic

ADD • • • •SUB • • • •MUL • • • •DIV • • • •ROOT • •

BooleanComputation

ANDW • • • •ORW • • • •XORW • • • •

Shift and Rotate

SFTL • • • •SFTR • • • •BCDLS • •WSFT •ROTL • • • •ROTR • • • •

Instruction Set Mic

ro-3

Mic

ro-3

C

ON

C

Mic

roSm

art

Advanced Instruction List, continuedHTOB Hex to BCD • •BTOH BCD to Hex • •HTOA Hex to ASCII • •ATOH ASCII to Hex • •BTOA BCD to ASCII • •ATOB ASCII to BCD • •ENCO Encode •DECO Decode •BCNT Bit Count •ALT Alternate Output •WKTIM Week TImer •WKTBL Week Table • •DISP Display • • • •DGRD Digital Read • • • •TXD Transmit • • •RXD Receive • • •LABEL Label • •LJMP Label Jump • •LCAL Label Call • •LRET Label Return • •IOREF I/O Refresh •DI Disable Interrupt •EI Enable Interrupt •XYFS XY Format Set • •CVXTY Convert X to Y • •CVYTX Convert Y to X • •PULS Pulse Output • •PWM Pulse Width Modulation • •RAMP Ramp Pulse Output •ZRN1 Zero Return 1 •ZRN2 Zero Return 2 •PID PID Control • •DTML 1-sec Dual Timer • •DTIM 100-msec Dual Timer • •DTMH 10-msec Dual Timer • •DTMS 1-msec Dual Timer • •TTIM Timer • •


Recommended