Catalogue ACB BT3 - Air Circuit Breaker BT3 Fuji - Beeteco.com

Date post: 14-Apr-2017
Category:
Upload: beeteco
View: 685 times
Download: 62 times
Share this document with a friend
7
New Product News 62D9-E-0164 Air Circuit Breakers, 1600 to 6300A BT3 Series Breaking Capacity Icu is equal to Ics up to 120kA at maximum and Icw 1s is up to 120kA at maximum under AC415V distribution. 0 20 40 60 80 100 120 50 50 BT3- 1600 BT3- 2500 BT3- 2500H BT3- 4000 BT3- 4000H BT3- 6300 BT3- 6300H 65 65 85 85 85 85 100 85 100 100 120 120 lcu = lcs lcw Selection guide Features • Compact design Satisfied Icu = 50kA or above at 440V for all of ampere frame size • Available Icu / Ics rating at 440V, rated current from 200A to 6300A, Ics = 100% of Icu • Conform to IEC 60947-2 (DEKRA (KEMA) certificate will be obtained.) Series BT3 series Frame size 1600, 2500, 4000, 6300 No. of poles 3, 4 Installation Fixed Available Draw-out Available Closing Mechanism Manual or motor spring charging mechanism Tripping Mechanism Shunt trip, Under-voltage trip Protection function Long time delay, Short time delay, Instantaneous, Ground fault, etc. BT3 New
Transcript

New Product News

62D9-E-0164

Air Circuit Breakers, 1600 to 6300A

BT3 Series

Breaking CapacityIcu is equal to Ics up to 120kA at maximum and Icw 1s is up to 120kA at maximum under AC415V distribution.

0

20

40

60

80

100

120

50 50

BT3-1600

BT3-2500

BT3-2500H

BT3-4000

BT3-4000H

BT3-6300

BT3-6300H

65 65

85 85 85 85

100

85

100 100

120 120

lcu = lcs lcw

Selection guide

Features• Compact design• Satisfied Icu = 50kA or above at 440V for all of ampere frame size• Available Icu / Ics rating at 440V, rated current from 200A to

6300A, Ics = 100% of Icu• Conform to IEC 60947-2 (DEKRA (KEMA) certificate will be

obtained.)

Series BT3 seriesFrame size 1600, 2500, 4000, 6300No. of poles 3, 4Installation Fixed Available

Draw-out AvailableClosing Mechanism Manual or motor spring charging mechanismTripping Mechanism Shunt trip, Under-voltage tripProtection function Long time delay, Short time delay, Instantaneous, Ground fault, etc.

BT3

New

Tư vấn chọn sản phẩm

Giao hàng tận nơi

Hỗ trợ kỹ thuật

Chính sách hậu mãi đa dạng

DỊCH VỤ CHĂM SÓC KHÁCH HÀNG TOÀN DIỆN

Nhà cung cấp thiết bị điện chuyên nghiệp

CÔNG TY TNHH THƯƠNG MẠI KỸ THUẬT ASTERSố 7 Đại lộ Độc Lập, KCN Sóng Thần, P. Dĩ An, Tx. Dĩ An, Bình Dương, VN.

Tel: (0650) 3617 012Fax: (0650) 3617 011www.beeteco.com

Clear indication of ready-for-switching-on to ensure safe manipulation and reliable operation.

More reliable safety protection with seconday terminals of protection grade IP30

Compact sizeBT3 series, Air Circuit Breakers, have four ampere frame sizes and physical dimensions.Ampere frame

1600 2500 4000 6300

Appearance

Width(3-poles, Draw-out type)

248mm 347mm 401mm 754mm

Installation The bus bar terminal of the BT3 series, Air Circuit Breakers, can be simply installed as follows:• Horizontal connection• Vertical connection• Composite connection

Safety performance Draw-out type BT3 series Air Circuit Breakers can be operated safety at 3 positions:1. Connected position2. Testing position3. Disconnected position

Indication of ready-for-switching-on:"ok"

21222324

21222324

21222324

21222324

Protection and selection BT3 Series, Air Circuit Breakers, can implement selective interlock of ZSI Region to ensure comprehensive selection of various protection and reduce the copper bar's bearing of thermodynamic.

Intelligent Controller (OCR)Selecting OCR's, it can be classified into ten types

Type EN35 EN36 EA35 EA36 EP35 EP36Option Option Standard Option Option Option

Pic

Display/setting LED indication LED indication LCD indicaiton LCD indication LCD indication LCD indicationProtection/function

t

I

Three levels protection

t

I

Three levels protection

t

I

Ground-fault-protection

t

I

Three levels protection

t

I

Three levels protection

t

I

Ground-fault-protection

t

I

Three levels protection

t

I

Three levels protection

t

I

Ground-fault-protection

Measurement CurrentOptional function(Voltage, Energy, Frequency, Power)

CurrentOptional function(Voltage, Energy, Frequency, Power)

Current Current CurrentVoltagePowerFrequencyEnergyPhase sequenceDemand value

CurrentVoltagePowerFrequencyEnergyPhase sequenceDemand value

EQ35 EQ36 EG35 EG36Option Option Option Option

LCD indication LCD indication LCD indication LCD indicationt

I

Three levels protection

t

I

Three levels protection

t

I

Ground-fault-protection

t

I

Three levels protection

t

I

Three levels protection

t

I

Ground-fault-protection

CurrentVoltagePowerFrequencyEnergyPhase sequenceDemand valueHarmonic analysis functionHarmonic capture function

CurrentVoltagePowerFrequencyEnergyPhase sequenceDemand valueHarmonic analysis functionHarmonic capture function

CurrentVoltagePowerFrequencyEnergyPhase sequenceDemand valueHarmonic analysis functionHarmonic capture functionOver frequencyUnder frequencyInverse power

CurrentVoltagePowerFrequencyEnergyPhase sequenceDemand valueHarmonic analysis functionHarmonic capture functionOver frequencyUnder frequencyInverse power

Intelligent controller (OCR) functions

Type EN35 EN36 EA35 EA36 EP35 EP36 EQ35 EQ36 EG35 EG36Option Option Standard Option Option Option Option Option Option Option

Display LED LED LCD LCD LCD LCD LCD LCD LCD LCDOvercurrent protection (Long-time, Short-time, instantaneous)Ground fault protection – – – – –Neutral protectionOverload pre-alarmCurrent-unbalance protectionPhase-loss protectionDemand current protection – – – –Over-voltage protection – – – –Under-voltage protection – – – –Voltage-unbalance protection – – – –Over-frequency protection – – – – – – – –Under-frequency protection – – – – – – – –Phase sequence protection – – – –Reverse power protection – – – – – – – –Current shedding Zone selective interlocking (ZSI)MCR function

Note: Reprensents fundamental functions, Represents optional functions, – Represent no such functions

Type number nomenclature

OCR type or Additional accessories

Frame size1600, 2500, 4000, 6300

PerformanceNone: StandardH : High breaking capacity

InstallationP: Fixed typeX: Draw-out type

Number of poles3: 3 poles4: 4 poles

Rated current1600AF: 0200, 0400, 0630, 0800, 1000, 1250, 16002500AF: 0630, 0800, 1000, 1250, 1600, 2000, 25004000AF: 1000, 1250, 1600, 2000, 2500, 2900, 3200

3600, 40006300AF: 4000, 5000, 6300

Basic type

English version

BT3-2500HP / 32500E

• Accessories

Type Code RemarksManual operated M1 For BT3-1600

M2 For BT3-2500M3 For BT3-4000,6300

Under voltage release R11 Instananeous : AC220V-AC240VR12 Instananeous : AC380V-AC415VR21 Time delay (0.5s, 1s, 2s, 3s) : AC220V-AC240VR22 Time delay (0.5s, 1s, 2s, 3s) : AC380V-AC415V

Switching OFF lock device Q1 One lock and one keyQ2 Two lock and one keyQ3 Three lock and two key

Mechanical interlock device(Two sets of ACB's)

MW1 Steel lock interlockMB1 Link rod interlock

Mechanical interlock device(Three sets of ACB's : for BT3-2500 and over)

MW2 Steel lock interlockMB2 Pattern one of rod interlockMB3 Pattern two of rod interlockMB4 Pattern three of rod interlock

Pushbutton lock mechanism LInterphase barriers B3 Three-phase

B4 Four-phaseCounter CMElectrical module for indication of ready-for-switching-on E1Remote reset RMR AC220-240VElectrical indication mechanism of socket's position D1Electrical indication mechanism of storage signal S1Accessories monitoring units AMCurrent transformer with the neutral line N connected externally

N1 For BT3-1600N3 For BT3-2500N4 For BT3-4000N6 For BT3-6300

Unit with transformer's center erath extermaily connected. UTProgrammable output expansion module EM6 6 lines Communication choices of accessories S1 Components of draw-out socket communication module

S2 Signal of ready-for-closeS3 Signal of under-voltageS4 Signal of fault releaseS5 Signal of charging

Normal power supply module PD1 DC24VPA1 AC220-240VPA2 AC380-415V

DC power supply module PD2 DC110VPD3 DC220V

Automatic Transfer Switch (ATS)(included automatic controller, connector and 1.8m cable)

AS1 R typeAS2 S typeAS3 F type

3 lines over-current fault output module OCF

• OCR type (note: EA35 is standard), refer to in the Intelligent controller (OCR) functions

Type Code RemarksEN35 N35EN36 N36EA35 – (None)EA36 A36EP35 P35EP36 P36EQ35 Q35EQ36 Q36EG35 G35EG36 G36

Information in this catalog is subject to change without notice.

5-7, Nihonbashi Odemma-cho, Chuo-ku, Tokyo, 103-0011, Japan

URL http://www.fujielectric.co.jp/fcs/eng

2014-09 PDF FOLS 62D9-E-0164

Specifications

Operation environments

Frame size 1600A 2500A 2500A 4000A 4000A 6300A 6300ABasic type BT3-1600 BT3-2500 BT3-2500H BT3-4000 BT3-4000H BT3-6300 BT3-6300H No. of poles 3 4 3 4 3 4 3 4 3 4 3 4 3 4Rated current (A) 200, 400, 630,

800, 1000, 1250, 1600

630, 800, 1000, 1250, 1600, 2000, 2500

630, 800, 1000, 1250, 1600, 2000, 2500

1000, 1250, 1600, 2000, 2500, 2900, 3200, 3600, 4000

1000, 1250, 1600, 2000, 2500, 2900, 3200, 3600, 4000

4000, 5000, 6300

4000, 5000, 6300

Rated current of the neutral pole (IN) 100% In 100% In 100% In 100% In 100% In 100% In 100% InRated insulation voltage (Ui) 1000 1000 1000 1000 1000 1000 1000Rated operational volage (Ue) 690 690 690 690 690 690 690Rated ultimate short-circuit breaking capacity(Icu kA, sym)

AC690V 50 55 65 75 85 85 100AC415/440V 50 65 85 85 100 100 120AC400V 65 65 85 85 100 120 135

Rated service short-circuit breaking capacity(Ics kA, sym)

AC690V 42 55 65 75 85 85 100AC415/440V 50 65 85 85 100 100 120AC400V 55 65 85 85 100 120 135

Rated making current(kA, peak)

AC690V 105 121 143 165 187 187 220AC415/440V 105 143 187 187 220 220 264AC400V 143 143 187 187 220 264 297

Rated short time withstand current (Icw) (kA, rms) -1s

AC690V 42 55 65 75 75 85 100AC415/440V 50 65 85 85 85 100 120AC400V 50 65 85 85 85 120 135

Rated impulse withstand voltage (Uimp) (kV)

12 12 12 12 12 12 12

InstallationsFixed PDraw-out X

Main circuit terminal connectionFixed Horizontal

Vertical – – – – – – – – – – – –

Draw-out HorizontalVertical

DimensionsFixed W 259 329 362 457 362 457 414 527 414 527 769 995 769 995

H 320 320 395 395 395 395 395 395 395 395 395 395 395 395D 195 195 290 290 290 290 290 290 290 290 290 290 290 290

Draw-out W 248 318 347 442 347 442 401 514 401 514 754 980 754 980H 351.5 351.5 438 438 438 438 438 438 438 438 475.5 475.5 475.5 475.5D 297 297 395 395 395 395 395 395 395 395 395 395 395 395

Available, – Not Available

Note: If the ACB is used in IT distribution system at AC415V or above, please inform to Fuji at the time of ordering.

Ambient temperature -5°C to +40°CAltitude < 2000mRelative humidity Not exceed 50% at +40°CPollution degree 3Vertical gradient no more than 5°


Recommended