ABOUT THIS CATALOGUEWe created this catalogue as a partial visual display of the many products that we carry from our main manufacturers with whom we have strategic partnerships. We hope it will help you understand the vast scope of our offering and that it will help you select the correct components to get the job done . Please contact us and use the catalogue page numbers to facilitate a meaningful discussion with our Technical Sales Advisors. They will be more than happy to provide you with advice and /or further documentation and obviously price & delivery for any items you may need whether they be in the catalogue or not. We will be able to provide this catalogue in the form of a CD Rom and via a link to www.prokontrol.com. Thank You for your continuing support.

Note:

Prokontrol cannot be held responsible for any omissions or errors contained within this catalogue.

1989 Michelin Street, Laval, QC H7L 5B7 Laval (450) 973-7765 Montreal (514) 990-2768 1-800-461-1381 Fax (450) 973-6186 100-420 Desrochers Street, Vanier, QC G1M 1C2 (418) 682-2421 1-800-465-7413 Fax (418) 687-956 4500 Alden road, suite 19, Markham, Ontario L3R 5H5 (905) 475-9888 1-888-687-7247 Fax (905) 475-9030 Internet: http://www.prokontrol.com Email: [email protected]

Canadas leading HVAC/R controls wholesalerMore than a supplier... A solution!In business since 1985

The Pro Kontrol family of productsTemperature, humidity, pressure, air flow & velocity and fluids sensors, relays, transformers, turn key solutions for ModBus, BACnet, Lon and N2, engineering services, panel assembly, graphic interfaces and Web.

Electronic (DDC) controls

Electrical controls

Thermostats, valves, actuators, controllers.

Pneumatic controls

Thermostats, valves, controllers, transmitters, relays, accessories, plastic and copper tubing, compressors, compressor oil, calibration and repair kits, replacement parts.

Ventilation products

Zoning systems, VAV boxes, duct heaters, dampers (parallel and opposed), actuators, direct coupled actuators, pneumatic actuators, foot mount actuators, dumping and air valve boxes.

Control valves and actuators Temperature Humidity Pressure

Ball, butterfly, globe, thermostatic and zone valves, solenoid valves, pneumatic and electronic actuators, butterfly gate, universal retrokits. Controllers, transmitters, thermistors, RTDs, indicators, digital thermometers. Humidity control, dehumidification, enthalpy, dew point. Air and fluid pressure control, transmitters, displays, converters, controllers, probes, pressure gauge.

Measurement and control of electrical consumptionPower/voltage switches and transmitters, phase lost, power factor.

Gas detection

CO, CO2, NO2, NH4 gas monitoring and measurement, refrigerants, VOCs.

Power supplies

PMS: 3155 et Noir

Control transformers, power supplies.

Relays and contactors

Plug-in, power, time delay, alternator relay, ice cube, solid state (SSR).

Other controls and accessories

Timers, time clocks, SCR, triacs, thermostat guards, smoke detectors, flow switches, firestats, freezestats, control cabling, and many more.

Take advantage of our wide range of technical services Proposals Engineering Shop drawings Wiring plans Programming Testing Panel and ventilation box assembly Commissioning assistancewww.prokontrol.com | [email protected]

C

A

B

L

Ew w w. n e p t r o n i c . c o m

Exclusive distributor

We also distribute the following brands: Columbus Electric Dekoron De Vilbiss/Omega Drainview McDonnell and Miller Paragon Robertshaw Uni-Line (Enerstat) Uni Guard Polaris Erie Miniveil Vapac and many more! Laval1989 rue Michelin Laval,Qubec, Canada, H7L 5B7 Tel: 450-973-7765 Fax: 450-973-6186 Toll-free: 1-800-461-1381

Longueuil908 Trans Canada Longueuil, Qubec Canada, J4G 2M1 Tel: 450-679-0203 Fax: 514-845-6186 Toll-free: 1-800-461-1381

Qubec100-420 rue Desrochers Qubec, Qubec Canada, G1M 1C2 Tel: 418-682-2421 PMS: 3155 et Noir Fax: 418-687-9564 Toll-free: 1-800-465-7413

Markham500 Alden Road, Suite 19 Markham, Ontario Canada, L3R 5H5 Tel: 905-475-9888 Fax: 905-475-9030 Toll-free: 1-888-687-7247

Dartmouth100 Wright Avenue, Unit 10 Dartmouth, Nova Scotia Canada, B3B 1L2 Tel: 902-482-5788 Fax: 902-468-1722 Toll-free: 1-800-461-1381

www.prokontrol.com | [email protected]

D.D.C. PERIPHERALS INDEXTEMPERATURE & HUMIDITY SENSORSACI Room Temperature Sensors DDC -1 ACI Micro & Stainless Steel Plate Sensors DDC -2 ACI Outdoor Air Temperature Sensor DDC -3 ACI Duct Temperature Sensor DDC -4 ACI Immersion Temperature Sensor DDC -5 ACI Duct AVG. Temperature sensors DDC -6 ACI Award Winning Humidity Transducer (wall/duct/LCD) DDC -7 ACI Award Winning Humidity/Temp Sensor(wall/duct/LCD) DDC -8 FUNCTIONAL DEVICES [RIB]-relay in a box VERIS Electronic to Pneumatic Pressure Transducer ( HOT) DDC -9,10 VERIS (Alta Labs) Low Pressure DPT (multi range/output) DDC -11,12 VERIS (Alta Labs) Gauge Pressure Transducer (multi range) DDC -13,14 GREYSTONE PRODUCTS (in stock at PK) DDC -15 to 19 HAWKEYE by VERIS CURRENT SENSORS H600 go no go DDC -24 H608 Split Core GNG DDC -25 H708/908 Solid Core/Split Core Adj. STPT Digital Output DDC -26 H730 Solid Core Fixed STPT Digital Output c/w Relay DDC -27 H735 Solid Core Adj. STPT with Relay DDC -28 GREYSTONE CURRENT SWITCHES DDC -29 to31 Carlo Gavazzi Relays & Bases DDC -32 to 35 OMRON-General Purpose Relays DDC -36 SPARTAN Control Valves DDC -37 to 41 SPARTAN Thermoelectric(WAX) Valves 10 year warranty! DDC -42, 43

www.prokontrol.com

DDC -

1

www.prokontrol.com

DDC - 2

www.prokontrol.com

DDC -

3

www.prokontrol.com

DDC -

4

www.prokontrol.com

DDC -

5

www.prokontrol.com

DDC -

6

www.prokontrol.com

DDC -

7

www.prokontrol.com

DDC -

8

Functional Devices, Inc. 310 South Union Street Russiaville, IN 46979 www.FunctionalDevices.com

Office Sales Fax Email

765.883.5538 800.888.5538 765.883.7505 [email protected]

TR100VA001

TRANSFORMERTransformer 100 VA, 120 to 24 Vac, Circuit Breaker, Foot and Single Threaded Hub Mount

1.800"CLASS II

Wht - 120 Vac

Yel/Wht - 24 Vac*

2.000"

PRIMARY WIRESBlk - Comm

SECONDARY WIRESYel - Comm

*Secondary Yel/Wht wire in phase with Primary Blk wire.

SPECIFICATIONSVA Rating: Frequency: Mounting: Over Current Protection: Dimensions: Wire Length: Operating Temperature: MTBF: Construction: Weight: Approvals: 100 50/60 Hz Foot & Single Threaded Hub Circuit Breaker 3.000 x 2.500 x 4.000 (w/ .500 NPT Hub) 9.5 Typical w/ .5 Strip -30 to 140 F 100,000 Hours @ 77 F Split-Bobbin 4.06 lbs. Class II UL5085-3 Listed, C-UL, CE, RoHS

2.550" 4.000"

Mounting Hole = .350" x .175" 2.500"

9.50"

.50"

NOTES

3.000"

Functional Devices, Inc. 310 South Union Street Russiaville, IN 46979 www.FunctionalDevices.com

Office Sales Fax Email

765.883.5538 800.888.5538 765.883.7505 [email protected]

TR100VA002

TRANSFORMERTransformer 100 VA, 120 to 24 Vac, Circuit Breaker, Foot and Dual Threaded Hub Mount

1.800"CLASS II

Wht - 120 Vac

Yel/Wht - 24 Vac*

2.00"

PRIMARY WIRESBlk - Comm

SECONDARY WIRESYel - Comm

*Secondary Yel/Wht wire in phase with Primary Blk wire.

SPECIFICATIONSVA Rating: Frequency: Mounting: Over Current Protection: Dimensions: Wire Length: Operating Temperature: MTBF: Construction: Weight: Approvals: 100 50/60 Hz Foot & Dual Threaded Hubs Circuit Breaker 3.000 x 2.500 x 4.000 (w/ .500 NPT Hubs) 9.5 Typical w/ .5 Strip -30 to 140 F 100,000 Hours @ 77 F Split-Bobbin 4.13 lbs. Class II UL5085-3 Listed, C-UL, CE, RoHS

2.550" 4.000"

Mounting Hole = .350" x .175" 2.500"

.50"

9.50"

9.50"

.50"

NOTES

3.000"

Functional Devices, Inc. 310 South Union Street Russiaville, IN 46979 www.FunctionalDevices.com

Office Sales Fax Email

765.883.5538 800.888.5538 765.883.7505 [email protected]

TR75VA002

TRANSFORMERTransformer 75 VA, 120 to 24 Vac, Circuit Breaker, Foot and Dual Threaded Hub Mount

1.625"CLASS II

Wht - 120 Vac

Yel/Wht - 24 Vac*

2.00"

PRIMARY WIRESBlk - Comm

SECONDARY WIRESYel - Comm

*Secondary Yel/Wht wire in phase with Primary Blk wire.

SPECIFICATIONSVA Rating: Frequency: Mounting: Over Current Protection: Dimensions: Wire Length: Operating Temperature: MTBF: Construction: Weight: Approvals: 75 50/60 Hz Foot & Dual Threaded Hubs Circuit Breaker 3.000 x 2.500 x 3.900 (w/ .500 NPT Hubs) 9.5 Typical w/ .5 Strip -30 to 140 F 100,000 Hours @ 77 F Split-Bobbin 3.70 lbs. Class II UL5085-3 Listed, C-UL, CE, RoHS

2.400" 3.900"

Mounting Hole = .350" x .175" 2.500"

.50"

9.50"

9.50"

.50"

NOTES

3.000"

Functional Devices, Inc. 310 South Union Street Russiaville, IN 46979 www.FunctionalDevices.com

Office Sales Fax Email

765.883.5538 800.888.5538 765.883.7505 [email protected]

TR50VA005

TRANSFORMERTransformer 50 VA, 120 to 24 Vac, Circuit Breaker, Foot and Single Threaded Hub Mount

1.260"CLASS II

Wht - 120 Vac

Yel/Wht - 24 Vac*

2.00"

PRIMARY WIRESBlk - Comm

SECONDARY WIRESYel - Comm

*Secondary Yel/Wht wire in phase with Primary Blk wire.

SPECIFICATIONSVA Rating: Frequency: Mounting: Over Current Protection: Dimensions: Wire Length: Operating Temperature: MTBF: Construction: Weight: Approvals: 50 50/60 Hz Foot & Single Threaded Hub Circuit Breaker 3.000 x 2.525 x 3.475 (w/ .500 NPT Hub) 9 Typical w/ .5 Strip -30 to 140 F 100,000 Hours @ 77 F Split-Bobbin 2.60 lbs. Class II UL5085-3 Listed, C-UL, CE, RoHS

1.950" Mounting Hole = .350" x .175" 3.475" 2.525"

9.00"

.50"

NOTES

3.000"

Functional Devices, Inc. 310 South Union Street Russiaville, IN 46979 www.FunctionalDevices.com

Office Sales Fax Email

765.883.5538 800.888.5538 765.883.7505 [email protected]

TR50VA004

TRANSFORMERTransformer 50 VA, 480/277/240/120 to 24 Vac, Circuit Breaker, Foot and Dual Threaded Hub Mount

1.200"CLASS II

PRIMARY WIRESGry - 480 Vac Brn - 277 Vac Org - 240 Vac Wht - 120 Vac Blk - Comm

SECONDARY WIRESYel/Wht - 24 Vac*

2.000"

Yel - Comm*Secondary Yel/Wht wire in phase with Primary Blk wire.

SPECIFICATIONSVA Rating: Frequency: Mounting: Over Current Protection: Dimensions: Wire Length: Operating Temperature: MTBF: Construction: Weight: Approvals: 50 50/60 Hz Foot & Dual Threaded Hubs Circuit Breaker 3.000 x 2.525 x 3.475 (w/ .500 NPT Hubs) 9.5 Typical w/ .5 Strip -30 to 140 F 100,000 Hours @ 77 F Split-Bobbin 3.04 lbs. Class II UL5085-3 Listed, C-UL, CE, RoHS

1.950" 3.475"

Mounting Hole = .350" x .175" 2.525"

.50"

9.50"

9.50"

.50"

NOTES

3.000"

Functional Devices, Inc. 310 South Union Street Russiaville, IN 46979 www.FunctionalDevices.com

Office Sales Fax Email

765.883.5538 800.888.5538 765.883.7505 [email protected]

TR75VA001

TRANSFORMERTransformer 75 VA, 120 to 24 Vac, Circuit Breaker, Foot and Single Threaded Hub Mount

1.625"CLASS II

Wht - 120 Vac

Yel/Wht - 24 Vac*

2.000"

PRIMARY WIRESBlk - Comm

SECONDARY WIRESYel - Comm

*Secondary Yel/Wht wire in phase with Primary Blk wire.

VA Rating: Frequency: Mounting: Over Current Protection: Dimensions: Wire Length: Operating Temperature: MTBF: Construction: Weight: Approvals:

SPECIFICATIONS

2.400"75 50/60 Hz Foot & Single Threaded Hub Circuit Breaker 3.000 x 2.500 x 3.900 (w/ .500 NPT Hub) 9.5 Typical w/ .5 Strip -30 to 140 F 100,000 Hours @ 77 F Split-Bobbin 3.66 lbs. Class II UL5085-3 Listed, C-UL, CE, RoHS

Mounting Hole = .350" x .175" 2.500"

3.900"

9.50"

.50"

NOTES

3.000"

Functional Devices, Inc. 310 South Union Street Russiaville, IN 46979 www.FunctionalDevices.com

Office Sales Fax Email

765.883.5538 800.888.5538 765.883.7505 [email protected]

RIBU1C

10 Amp Pilot Control RelayEnclosed Relay 10 Amp SPDT with 10-30 Vac/dc/120 Vac CoilContact Ratings: 10 Amp Resistive @ 120-277 Vac 10 Amp Resistive @ 28 Vdc 480 VA Pilot Duty @ 240-277 Vac 480 VA Ballast @ 277 Vac 600 Watt Tungsten @ 120 Vac N/O 240 Watt Tungsten @ 120 Vac N/C 1/3 HP for N/O @ 120-240 Vac 1/6 HP for N/C @ 120-240 Vac 1/4 HP for N/O @ 277 Vac 1/8 HP for N/C @ 277 Vac Coil Current: 30 mA @ 10 Vac 32 mA @ 12 Vac 42 mA @ 24 Vac 50 mA @ 30 Vac 25 mA @ 120 Vac

Wht/Blk 120 Vac

Blu N/C

c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c

Wht/Blu 10-30 Vac/dc

Yel Comm

SPECIFICATIONS# Relays & Contact Type: Expected Relay Life: Operating Temperature: Operate Time: Relay Status: Dimensions: Wires: Approvals:

MADE IN USA

One (1) SPDT Continuous Duty Coil 10 million cycles minimum mechanical -30 to 140 F 20mS LED On = Activated 1.70 x 2.80 x 1.50 with .50 NPT nipple 16, 600V Rated UL Listed, UL916, UL864, C-UL California State Fire Marshal, CE Housing Rating: Plenum, NEMA 1 Gold Flash: Yes Override Switch: No

12 mA 14 mA 16 mA 18 mA

@ @ @ @

10 Vdc 12 Vdc 24 Vdc 30 Vdc

Wht/Yel Comm

Org N/O

Coil Voltage Input: 10-30 Vac/dc ; 120 Vac ; 50-60 Hz Drop Out = 2.1 Vac / 2.8 Vdc Pull In = 9 Vac / 10 Vdc

RIBU1C-RD Red housing

RIBU1C-N4 NEMA 4X housing

NOTES

Functional Devices, Inc. 310 South Union Street Russiaville, IN 46979 www.FunctionalDevices.com

Office Sales Fax Email

765.883.5538 800.888.5538 765.883.7505 [email protected]

RIBU1S

10 Amp Pilot Control RelayEnclosed Relay 10 Amp SPST-N/O + Override with 10-30 Vac/dc/120 Vac CoilContact Ratings: 10 Amp Resistive @ 277 Vac 480 VA Pilot Duty @ 240-277 Vac 480 VA Ballast @ 277 Vac 600 Watt Tungsten @ 120 Vac N/O 240 Watt Tungsten @ 120 Vac N/C 1/3 HP for N/O @ 120-240 Vac 1/6 HP for N/C @ 120-240 Vac 1/4 HP for N/O @ 277 Vac 1/8 HP for N/C @ 277 Vac Coil Current: 30 mA @ 10 Vac 12 mA @ 10 Vdc 32 mA @ 12 Vac 14 mA @ 12 Vdc 42 mA @ 24 Vac 16 mA @ 24 Vdc 50 mA @ 30 Vac 18 mA @ 30 Vdc 25 mA @ 120 Vac Coil Voltage Input: 10-30 Vac/dc ; 120 Vac ; 50-60 Hz Drop Out = 2.1 Vac / 2.8 Vdc Pull In = 9 Vac / 10 Vdc Notes: Order Normally Closed by adding -NC to end of model number Order with Momentary Override Switch by adding -MNO to end of model number

Wht/Blk 120 Vac

c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c

Wht/Blu 10-30 Vac/dc

CLOSED OPEN AUTO

SPECIFICATIONS# Relays & Contact Type: Expected Relay Life: Operating Temperature: Operate Time: Relay Status: Dimensions: Wires: Approvals:

MADE IN USA

One (1) SPST Continuous Duty Coil 10 million cycles minimum mechanical -30 to 140 F 20mS LED On = Activated 2.30 x 3.20 x 1.80 with .50 NPT nipple 16, 600V Rated UL Listed, UL916, UL864, C-UL California State Fire Marshal, CE Housing Rating: Plenum, NEMA 1 Gold Flash: Yes Override Switch: Yes

Wht/Yel Comm

Org

Org

NOTES

Functional Devices, Inc. 310 South Union Street Russiaville, IN 46979 www.FunctionalDevices.com

Office Sales Fax Email

765.883.5538 800.888.5538 765.883.7505 [email protected]

RIBXK SERIES

CURRENT SENSOREnclosed Solid Core Current Sensors 1.460

.500 Diameterc c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c

1.863 2.050

1.008 1.508 LEDS

RIBXKA

MADE IN USA

WIRE CLAMPRIBXKTF

THRESHOLD ADJUSTSPECIFICATIONSOperating Temperature: Max Sense Voltage: Approvals: Housing Rating: Mounting/Installation: -30 to 140 F 600 Vac UL Listed, UL916, UL864, C-UL, CE Plenum, NEMA 1 Removable mounting tab provided. The wire clamp locks against the load wire, securing the unit in place.

REMOVABLE MOUNTING TAB

SENSOR OUTPUT Solid State Contact 30 Vac/dc, .4 Amp Max. RIBXKF, RIBXKTF .8 Amp Max. RIBXKA, RIBXKTAWhen current sensor status is off (open), leakage 100:1 2-1/2 to 3-inch are available with a 3/4-inch stroke 4-, 5-, and 6-inch are available as 1-1/2-inch stroke ANSI Leakage Class IV (0.01% of Cv) Cartridge-type packing for easy service

Option Service flange for easy removal of stem and plug through bottom port

www.valves-actuators.comwww.prokontrol.com SIEMENS -

C-111

76

Valves

OverviewDamper Actuators provide control, either electronically or pneumatically, for a variety of HVAC applications, including: VAV Systems Mixing Boxes Central Fan Systems Exhaust Dampers

Damper Actuators

Overview Damper Actuators

Selection GuideElectronic Spring Return Application Terminal Units Face and Bypass Multi-zone Mixing Boxes Bypass Damper Makeup Air Damper Outside Air Dampers Small Rooftop Units (RTU) Rooftop Units (RTU) Zone Isolation Dampers Vortex Dampers Inlet Vane Dampers Return Air Dampers Zone Isolation Dampers Central VAV Fans GMA GCA GDE/GLB Non-spring Return GEB GBB/GIB No. 3 Pneumatic Spring Return No. 4 No. 6

Damper Actuators

**LC Model Damper Torque for Approach Air of 1200 ft./min. (6 m/s) or less 2.5 lb.-in./ft.2 (0.3 Nm/m2) 5.0 lb.-in./ft.2 (0.6 Nm/m2)

Damper Type Standard Leakage Low Leakage Very Low Leakage

Damper Leakage at 1 H2O (240 Pa) Static Pressure More than 10 CFM/ft.2 (50.8 l/s per m2) 5 to 10 CFM/ft.2 (25.4 to 50.8 l/s per m2)

Less than 5 CFM/ft.2 7.0 lb.-in./ft.2 (0.8 Nm/m2) (Less than 25.4 l/s per m2)

For detailed damper actuator sizing information, please refer to the Engineering Section, I.

D-2

For assistance, contact Customer Care at:

1.888.593.787683

www.prokontrol.com

SIEMENS -

OpenAir

GMA Series

Spring Return Electric Damper Actuator

New!

Easily Replaces: Belimo LN/NF Series

62 lb.-in. 24 Vac/Vdc, 2-position Control 120 Vac, 2-position Control 120 Vac/Vdc, 3-position Control 0 to 10 Vdc, Modulating Control

GMA Series Spring Return Direct-coupled Electric Damper Actuator.

OpenAir GMA Series

DescriptionThe OpenAir GMA Series Direct-coupled, Spring Return Electronic Damper Actuators provide modulating, twoposition and three-position control of building HVAC dampers.

ApplicationsThe OpenAir GMA Series Damper Actuators are ideal for Constant or Variable Air Volume installations for the control of return air, mixed air, exhaust, and face and bypass dampers that require up to 62 lb.-in. of torque. The actuators are designed for application where the damper is required to return to a fail-safe position when there is a power failure. Models are available with either a universal cable for wiring in conduit or a plenum-rated cable.

24 Vac/dc compatible Integral 1/2-inch conduit connector Small actuator footprint with 62 lb.-in. of torque Bi-directional fail-safe spring return Floating control models available with feedback potentiometer Manual override Mechanical range adjustment capability Easily visible position indicator Brushless DC motor technology Precabled UL873 and C-UL (C22.2 No. 24-93) listed Unique self-centering shaft coupling

features

Options Dual independently adjustable auxiliary switch Adjustable offset and span

www.valves-actuators.comwww.prokontrol.com SIEMENS 84

D-3

Damper Actuators

OpenAir

GCA Series

Spring Return Electric Damper Actuator

Easily Replaces: Belimo AF Series

142 lb.-in. torque 24 Vac, 2-position Control 120 Vac, 2-position Control 24 Vac, 3-position Control 4 to 20 mA, Modulating Control 0 to 10 Vdc, Modulating Control

GCA Series Spring Return Electric Damper Actuator.

OpenAir GCA Series

DescriptionDesigned for control of building HVAC dampers, the OpenAir GCA Series Direct-coupled, Spring Return Electric Actuators are available in 0 to 10 Vdc or 4 to 20 mA modulating, three-position (floating) and two-position (on/off) control models.

ApplicationsThe OpenAir GCA Series Damper Actuators are ideal for Constant or Variable Air Volume installations for the control of return air, mixed air, exhaust, and face and bypass dampers that require up to 142 lb.-in. (16 Nm) torque. The actuators are designed for applications where the damper is required to return to a fail-safe position when there is a power failure. Models are available with either a universal cable for wiring in conduit or a plenum-rated cable for applications where conduit is not required.

features

Self-centering shaft coupling Bidirectional fail-safe spring return Rugged all metal housing, rated NEMA 2 Accepts shaft diameters up to 1 (25 mm) Quiet, low-power operation Brushless DC motor technology with stall protection Assembled in the U.S.A. Manual override Options Independently adjustable dual auxiliary switches Potentiometer for 3-position models Adjustable span and offset

www.valves-actuators.comwww.prokontrol.com SIEMENS 86

D-7

Damper Actuators

OpenAirEasily Replaces: Belimo LM Series

GDE Series

Non-spring Return Electric Damper Actuator

44 lb.-in. torque 24 Vac, 3-position Control 0 to 10 Vdc, Modulating Control

GDE Series Non-spring Return Electric Damper Actuator.

OpenAir GDE Series

DescriptionThe OpenAir GDE Series Direct-coupled 24 Vac Nonspring Return Rotary Electric Actuator is designed for 0 to 10 Vdc or three-position (floating) control of building HVAC dampers.

ApplicationsThe OpenAir GDE Series Damper Actuators are used in Constant or Variable Air Volume installations for the control requiring up to 44 lb.-in. (5 Nm) torque. Models are available with either a universal cable for wiring in conduit or a plenum-rated cable for applications where conduit is not required.

features

Compact design Easy-to-see position indicator 0 to 10 V or 3-position models Self-adapting capability for maximum flexibility in damper positioning UL, CSA, CE listed Quiet, low-power operation Rated NEMA 2 Assembled in the U.S.A. Manual override

Options Independently adjustable dual auxiliary switches Adjustable start/span Standard or plenum cable Available in bulk packs for additional savings

www.valves-actuators.comwww.prokontrol.com SIEMENS 88

D-11

Damper Actuators

OpenAir

GLB Series

Non-spring Return Electric Damper Actuator

Easily Replaces: Belimo NM Series

88 lb.-in. torque 24 Vac, 3-position Control 0 to 10 Vdc, Modulating Control

GLB Series Non-spring Return Electric Damper Actuator.

OpenAir GLB Series

DescriptionThe OpenAir GLB Series Direct-coupled 24 Vac Nonspring Electric Actuator is designed for 0 to 10 Vdc or three-position (floating) control of building HVAC dampers.

ApplicationsThe OpenAir GLB Series Damper Actuators are used in Constant or Variable Air Volume installations for the control requiring up to 88 lb.-in. (10 Nm) torque.

features

Compact design Easy-to-see position indicator 0 to 10 V or 3-position models Self-adapting capability for maximum flexibility in damper positioning UL, CSA, CE listed Quiet, low-power operation Rugged all metal housing, rated NEMA 2 Assembled in the U.S.A. Manual override Plenum-rated cable

Options Independently adjustable dual auxiliary switches Adjustable start/span

www.valves-actuators.comwww.prokontrol.com SIEMENS 90

D-15

Damper Actuators

OpenAir

GBB Series

Non-spring Return Rotary Electric Damper Actuator

Easily Replaces: Belimo SM/AM Series

177 lb.-in. torque 0 to 10 Vdc, Modulating Control 4 to 20 mA, Modulating Control 3-position/2-position Control

GBB Series Non-spring Return Electric Damper Actuator.

OpenAir GBB Series

DescriptionDesigned for control of building HVAC dampers, the 24 Vac OpenAir GBB Series Direct-coupled 24 Vac Non-spring Return Electric Damper Actuators are available in 0 to 10 Vdc, 4 to 20 mA, two- and three-position control.

ApplicationsThe OpenAir GBB Series Damper Actuators are used in Constant or Variable Air Volume installations for the control of return air, mixed air, exhaust, and face and bypass dampers that require up to 177 lb.-in. (20 Nm) torque. Models are available with either a universal cable for wiring in conduit or a plenum-rated cable for applications where conduit is not required.

features

Brushless DC motor technology with stall protection Self-centering shaft coupling Quiet, low-power operation Accepts shaft diameters up to 1 (25 mm) Manual override Assembled in the U.S.A.

Options Independently adjustable dual auxiliary switches Adjustable offset and span Potentiometer for 3-position models

www.valves-actuators.comwww.prokontrol.com SIEMENS 92

D-19

Damper Actuators

Rugged all metal housing, rated NEMA 2

Accessories & Service KitsSeries

OpenAir

Description Actuator Commissioning Tool. A portable instrument for exercising, calibrating, and testing resistive, proportional (voltage/current), incremental (floating), and On/Off actuators.

GDE GLB

GEB GMA

GCA GIB GBB GKB

GGD

Quantity 1

Part No. 985-047Tools

Adjustment Tool.

1

985-098

Hex Key.

Pkg. of 24 985-054P24

OpenAir Reference

Crank Arm Kit. Allows a directcoupled actuator to provide an auxiliary linear drive; can be used to simultaneously drive a set of opposing or adjacent dampers with a single actuator.

1 1

ASK71.13 ASK71.3

Damper Shaft Cranks

155-176P25 155-173P25

Crank Arm Kit with Bracket. For use in applications where the actuator can be rigidly surface-mounted and a linear stroke output is required.

1 1

ASK71.14 ASK71.4

Rotary to Linear Kit. 1 ASK71.5

Damper Actuators

Rotary to Linear Kit with Universal Mounting Bracket.

1

ASK71.6

Universal Crank Arm. For linear applications requiring connection to damper shaft when ball joint connection is not possible. Shaft sizes 3/8 to 1.

1

ASK71.9

D-42

For assistance, contact Customer Care at:

1.888.593.787694

www.prokontrol.com

SIEMENS -

331

No. 3 Pneumatic Actuator

331-4314 Actuator with fixed mounting bracket and clevis.

331-4312 Actuator with pivot mounting bracket.

331-4311 Actuator, clevis and rocker arm. Mounting for extended shaft.

DescriptionDesigned with a 2-3/8-inch (60 mm) stroke, the No. 3 Pneumatic Actuator is a rugged, metal-fabricated device that provides gradual or positive actuation of HVAC dampers. The actuator is available in a variety of spring ranges for energy optimizing and sequencing with other devices.

ApplicationsRecommended for control of mixing box dampers or air valves and damper control for unit ventilators, unit conditioners and small HVAC systems, the No. 3 Pneumatic Actuator is also available with 2-3/4-inch (70 mm) stroke in the three spring ranges. For more information, contact your local Siemens Building Technologies representative.

331No. 3 Pneumatic

features features

Ozone-resistant rolling rubber diaphragm Variety of installation options, including: Fixed bracket mounting Direct front mounting Pivot mounting for extended shaft Available with positioning relay

Max. Thrust lb. (N) Spring Return Full Stroke Forward (No Stroke) 15 psi 18 psi 25 psi 0 psig Gradual (103 kPa) (124 kPa) (172 kPa) (0 kPa) Operation 64 (285) 40 (178) 16 (71) 88 (391) 64 (285) 40 (178) 144 (641) 120 (534) 96 (427) 24 (107) 40 (178) 64 (285) 10 (1.1) 10 (1.1) 10 (1.1)

Torque Rating lb.-in (Nm) 2-position Operation or with Positioner 15 psi 18 psi 25 psi (103 kPa) (124 kPa) (172 kPa) 20.2 (2.3) 33.6 (3.8) 13.4 (1.5) 20.2 (2.3) 33.6 (3.8) 33.6 (3.8) 20.2 (2.3) 33.6 (3.8) 53.8 (6.1)

Thrust/Torque Ratings

Nominal Spring Rating

3 to 7 psi (21 to 48 kPa) 5 to 10 psi (35 to 69 kPa) 8 to 13 psi (55 to 90 kPa)

With maximum hysteresis of 2.5 psi (17.2 kPa) @ 90 rotation.

www.valves-actuators.comwww.prokontrol.com SIEMENS 98

D-31

Damper Actuators

331

No. 4 Pneumatic Actuator

331-2929 No. 4 Pneumatic Actuator and clevis for frame mounting.

331-2904 No. 4 Pneumatic Actuator with pivot mounting bracket.

331-2973 No. 4 Pneumatic Actuator with clevis, and crank. Universal Mounting Plate for extended shaft or frame mounting.

331-2974 No. 4 Pneumatic Actuator with non-pivot bracket for unit ventilator.

DescriptionDesigned with a 4-inch (102 mm) stroke, the No. 4 Pneumatic Actuator is a rugged, metal-fabricated device that provides gradual or positive actuation of HVAC and fire/smoke dampers.

ApplicationsRecommended for control of outdoor, return air, exhaust, face and bypass, fan discharge, and static pressure control dampers, the No. 4 Pneumatic Actuator also is excellent for controlling specialized dampers and air valves in terminal units, such as unit ventilators and mixing boxes. The No. 4 actuator hesitation model is frequently used to operate the outdoor air damper on unit ventilators and mixing boxes. An actuator marked with an asterisk (*) is a component recognized under ULs Damper Actuator category (EMKU2) for use on fire dampers and leakage-related dampers.

331No. 4 Pneumatic

features features

Replaceable diaphragm Positioning relay (optional) Forward travel stops (optional) Hesitation model (provides minimum ventilation without separate damper/ actuator Variety of spring ranges for sequencing with other control devices Stainless steel actuator shaftMax. Thrust lb. (N)

Thrust/Torque Ratings

Nominal Spring Rating 3 to 7 psi (21 to 48 kPa) 3 to 13 psi (21 to 90 kPa) 5 to 10 psi (35 to 90 kPa) 8 to 13 psi (55 to 90 kPa) 2 to 3, 8 to 13 psi (14 to 20, 55 to 90 kPa) Hesitation

Spring Return Full Stroke Forward (No Stroke) 15 psi 18 psi 25 psi 0 psig (103 kPa) (124 kPa) (172 kPa) (0 kPa) 88 (391) 22 (198) 55 (245) 22 (98) 22 (98) 21 (145) 55 (245) 88 (391) 55 (245) 55 (245) 198 (881) 132 (587) 165 (734) 132 (587) 132 (587) 33 (147) 33 (147) 55 (245) 88 (391) 22 (98)

Gradual Operation 30 (3.4) 30 (3.4) 30 (3.4) 30 (3.4) 23 (2.6)

2-position Operation or with Positioner 15 psi 18 psi 25 psi (103 kPa) (124 kPa) (172 kPa) 46 (5.2) 30 (3.4) 77 (8.7) 30 (3.4) 46 (5.2) 46 (5.2) 77 (8.7) 77 (8.7) 46 (5.2) 46 (5.2) 77 (8.7) 124 (855)

With maximum hysteresis of 2.5 psi (17.2 kPa) @ 90 rotation.

www.valves-actuators.comwww.prokontrol.com SIEMENS - 100

D-33

Damper Actuators

Torque Rating lb.-in. (Nm)

331

No. 6 Pneumatic Actuator

331-2792 and 331-3060 No. 6 Pneumatic Actuator, pivot mounting type.

331-2856 No. 6 Pneumatic Actuator and clevis for frame mounting.

331-3011 No. 6 Pneumatic Actuator, clevis, crank and rocker arm. Universal mounting for extended shaft or frame mounting.

DescriptionDesigned with a 4-inch (102 mm) stroke, the No. 6 Pneumatic Actuator is a rugged, metal-fabricated device that provides gradual or positive actuation of HVAC and fire/smoke dampers.

ApplicationsRecommended for multiple applications, the No. 6 Pneumatic Actuator is excellent for control of outdoor air, return air, mixed air, exhaust, face and bypass, fan discharge, multisection, static pressure control, fan inlet vanes and other special applications. An actuator marked with an asterisk is recognized under ULs Damper Actuator category (EMKU2) for use on fire dampers and leakage-rated dampers.

331No. 6 Pneumatic

features features

Replaceable diaphragm Variety of spring ranges for sequencing with other control devices High torque

Options Positioning relay Forward travel stops

Max. Thrust lb. (N) Spring Return Full Stroke Forward (No Stroke) 15 psi 18 psi 25 psi 0 psig (103 kPa) (124 kPa) (172 kPa) (0 kPa) 125 (556) 36 (160) 36 (160) 179 (796) 89 (396) 89 (396) 304 (1352) 214 (952) 214 (952) 54 (240) 54 (240) 144 (640)

Torque Rating lb.-in. (Nm) 2-position Operation or with Positioner 15 psi 18 psi 25 psi (103 kPa) (124 kPa) (172 kPa) 75 (8.5) 50 (5.6) 50 (5.6) 75 (8.5) 75 (8.5) 125 (14.1) 75 (8.5) 75 (8.5) 202 (22.8)

Thrust/Torque Ratings

Nominal Spring Rating 3 to 8 psi (21 to 55 kPa) 3 to 13 psi (21 to 90 kPa) 8 to 13 psi (55 to 90 kPa)

Gradual Operation 50 (5.6) 50 (5.6) 50 (5.6)

With maximum hysteresis of 2.5 psi (17.2 kPa) @ 90 rotation.

www.valves-actuators.comwww.prokontrol.com SIEMENS - 102

D-35

Damper Actuators

134/251

Pressure Electric Switches

134 Pressure Electric Switch.

251 Pressure Electric Switch.

251 Multi-input Pressure Static Switch

Description134 Pressure Electric SwitchesThe 134 Pressure Electric Switches are heavy duty pressure-actuated, mechanical contact type switches used to open or close electrical circuits from pressure signals in pneumatic control systems.

Applications134 Pressure Electric SwitchThe 134 Pressure Electric Switches are used wherever it is necessary to close (or open) an electrical circuit on the basis of a predetermined air pressure signal. This switch is to be used in areas protected from the weather. Typical applications include the control of air compressors, fans, pilot lights, resistance heating elements, control of electric heating loads or motors on fans, pumps or small air compressors.

134 251

251 Pressure Electric SwitchesThe 251 Pressure Electric Switches are pressure-actuated snap switches that open or close electrical circuits from pneumatic control signals.

Pressure Electric Switches

251 Pressure Electric SwitchThe 251 Pressure Electric Switches are used to start and stop fans, pumps and chillers or to energize and deenergize electric heating elements and pilot lights.

features

134 Pressure Electric Switches DPST or SPDT snap-acting External adjustment and indication of set point and differential Screw terminals are easily accessible for field wiring Long life, heavy duty contact mechanism Normally open or normally closed contacts models available Not position sensitive, can be mounted in any position Mounting bracket included

Note: Pilot ratings for 251 switches are as follows: 251-0006 .................................... 360 VA, 120 to 480 Vac Other Part Numbers ................... 125 VA, 120 to 277 Vac

251 Pressure Electric Switches SPDT, snap-acting except 251-006, which is SPST, NO; 251-0009 and 251-0001, which are SPST, NC 1 and 2 stage models available Dual pressure input models available Available with fixed or adjustable differentials Accuracy 2 psi

www.valves-actuators.comwww.prokontrol.com SIEMENS - 104

E-17

Switches & Relays

243

Multi-purpose RelaysCommercial and Heavy Duty

243-0046 Commercial Duty Multi-purpose Relay.

243-0009 Heavy Duty Multi-purpose Relay.

DescriptionThe 243 Multi-purpose Relays are pneumatic auxiliary devices designed to provide a variety of pneumatic control functions for the typical control system.

ApplicationsThe 243 Multi-purpose Relays are used as direct and reverse acting, amplifying, signal advancing, minimum pressure relay, and lower pressure transfer.

243Multi-purpose Relays/Pneumatic

Typical Connections

features

Use for your most common applications Available as commercial-duty (plastic) or heavy-duty (metal) High accuracy/repeat-ability Two-valve design prevents constant air loss Internal relief mechanism for fail safe operationR TD TR S = = = = output direct acting input reverse acting input air supply

For more detailed information on applications, refer to the Engineering section.

www.valves-actuators.comwww.prokontrol.com SIEMENS - 106

E-23

Switches & Relays

265

Three-way EP Valves

265-1001 Three-way EP Valve-Junction Box Type.

265-1007 Three-way EP Valve-Open Frame Type.

DescriptionA general purpose, electrically-operated, two-position three-way valve designed to control air flow, the 265 ThreeWay Valve can be used for interlock between an electrical system and a pneumatic control system; available in open frame (yoke) and junction box (splice box) types.

ApplicationsThe 265 EP Three-way Valves are commonly-used to alternately apply pressure to and exhaust pressure from pneumatically-controlled devices, such as valves and damper actuators, by an electrical input energizing or deenergizing the solenoid of the valve. A standard method is shown in the Application Drawings below. The input air is connected to port 1 (normally closed) and the output is connected to port 3 (common). Thus when the solenoid is energized, port 1 connects to port 3 permitting the thermostat to control the damper actuator. When the solenoid is de-energized, port 2 (normally open) is connected to port 3, exhausting air from the actuator permitting it to return to its normal position.

265Three-way EP Valves

features

UL and CSA approved for general purpose Valve may be mounted in any position Universal replacement for many competitive models Mounting holes provided in the yoke Wide selection of AC voltages

Application Drawings

www.valves-actuators.comwww.prokontrol.com SIEMENS - 109

E-21

Switches & Relays

Air Station Equipment

656-0009 High Capacity, 3-way Pilot Valve.

201-1001 Single-stage, Compressed Air Pressure Reducing Valve.

908-048 Single-stage PRV Station.

201-1000 Single-stage, Compressed Air Pressure Reducing Valve.

908-051 Compressed Air Filter.

908-049 Dual-stage PRV Station.

DescriptionProviding pneumatic control, Air Station Equipment, which includes Single- and Dual-stage Pressure Reducing Valves and High Capacity, 3-way Pilot Valves, responds rapidly to large volume demands and supply pressure variations. The Compressed Air Filter removes water or oil to 0.025 particle size.

ApplicationsAir Station equipment and compressor systems are available for schools, hospitals, commercial office and industrial buildings, and other facilities. Compressed air systems include: Single (low) pressure Dual (low and high) pressure Dual, low pressure for two pressure systems Your local Siemens Building Technologies representative can assit you in selecting the appropriate air compressors and accessories for optimum efficiency and duty cycling.

features

Pressure Reducing Valves 200 mesh stainless strainer Locking handle Dual tappings for right or left-hand gauge (201-1000) Gauge plug and bushing (201-1000) 2-1/2 (64 mm) gauge with 0 to 30 psig (0 to 207 kPa) (201-1001, 201-1002) Integral safety relief valve (201-1001, 201-1002)

Compressed Air Filter 10 scfm (17 m3/hr) capacity Drain port Replaceable cartridge

www.valves-actuators.comwww.prokontrol.com SIEMENS - 121

F-5

Auxiliary Equipment Air Station Equipment

Single Pressure.

Low and High Pressure.

Dual Pressure.

www.valves-actuators.comwww.prokontrol.com SIEMENS - 123

F-7

Auxiliary EquipmentAir Station Equipment

Application Drawings

142AP

Pressure Gauges

1-1/2, 2-1/2 and 3-1/2 Pressure Gauges.

DescriptionPneumatic pressure gauges are used wherever visual indication of pressure is required.

ApplicationsThe 142 AP Pressure Gauges are generally used in applications such as air compressor stations and central control panels.

features

Accuracy 2.5% of full scale for the middle half of scale; 3.5% elsewhere Available in 1-1/2-inch (38 mm), 2-1/2-inch (64 mm) and 3-1/2-inch (89 mm) diameter sizes Mounting hardware for panel mounted gauges included

www.valves-actuators.comwww.prokontrol.com SIEMENS - 124

F-9

Auxiliary Equipment

142APPressure Gauges

JOHNSON CONTROLS PRODUCTS System 350 Electronic Controllers T600 Programmable Thermostats T600 Non-Programmable Line Voltage Thermostats A419 Electronic Temperature Controller A25 High Limit Control W43A Humidistat A70 Freeze Stat P10 Low Pressure Control V11 3 Way Solenoid A11 Low Temperature Cut Out Control A19 Remote Bulb Temperature Control A28 Two Stage Temperature Controller V47 Temperature Activated Modulating Valve F61 Flow Switch P32 Sensitive Differential Pressure Switch P70 Pressure Control (Low, High or Dual) T4002 Pneumatic Stats H4100 Pneumatic Humidistats T4002 Pneumatic Thermostat High Volume H5100 Pneumatic Humidity Transmitter T5002 Pneumatic Temperature Transmitter T4752 Pneumatic Heat/Cool Thermostat T4516 Pneumatic Dual Temp High Output Thermostat Accessories, Accessories, Accessories. Pneumatic Receiver Controllers, Switches, Relays, Transmitters Pneumatic Piston Damper Actuators Valve Body Selection Chart Accessories for M9000 Series Actuators M9000 Series Damper Actuators NG1000 Series Ball Valves J Series Zone Valves Butterfly Valves JCI - 1 to 9 JCI - 10 JCI - 11 JCI - 12 JCI - 13 JCI - 14 JCI - 15,16 JCI - 17 JCI - 18 JCI - 19 JCI - 20 JCI - 21, 22 JCI - 23, 24 JCI - 25, 26 JCI - 27 JCI - 28 JCI - 29 to 31 JCI - 32 JCI - 33 JCI - 34 JCI - 35 JCI - 36 JCI - 37 JCI - 38 JCI - 39 to 44 JCI - 45 to 51 JCI - 52 to 54 JCI - 55 JCI - 56 to58 JCI - 59, 60 JCI - 61 to 63 JCI - 64 to 71 JCI - 72, 73

Controls Group 507 E. Michigan Street P.O. Box 423, Milwaukee, WI 53202 Code No. LIT-1922645temp less 1922645 9thcc:2-103 Electric System 350 TM

System 350TM Temperature Controlsa350e.tif a350p.tif a350r_2.tif a350r.tif s350.tif s350c.tif s350p.tif d350.tif

Rev: 07/18/97 logo: JCI left ft: elec right ft: standard Sect# = 2 seQ# = 339

a350.tif

A350E

A350P

A350R

A350S

S350

S350C

S350P

y350.tif

D350

The System 350. Temperature family includes On/Off (SPDT), proportional (0 to 10 VDC and 0 to 20 mA output), and reset (SPST) controls in addition to stage, display, and power modules. The controls are used in conjunction with the A99B Series Temperature Sensors and TE-6001 Series Sensor Mounting Accessories. Applications include: A350A/B frozen/refrigerated display cases ventilation control space temperature control temperature reset for single or multistage boilers modulating dampers Y350R temperature indication cooling tower control beverage/milk coolers modulating chilled/hot water valves

Features!

BenefitsProvides reliable performance Covers a wide range of applications with minimal inventory investment Provides versatility for a wide range of applications; enables user to match equipment cycle rate and/or sequencing for a given application Provides flexible installation capabilities Eliminates wiring between modules Gives convenient, cost-effective, prepackaged options Holds setpoint regardless of load on system and its rate of change Provides flexible and customizable application solutions

Electronic Accuracy and Repeatability Field Selectable Modes Heating/Cooling Temperature Adjustable Settings Over a Wide Range Surface-Mount or DIN Rail-Mounting Ability Plug-Together, 5-Pin Connectors Sensors Included with Most Models ProportionaI/Integral Selectable Option on Some Controls Modular Design

!

!

!

! ! !

!

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond t hese specifications, consult the local Johnson 03/02 Johnson Controls, Inc Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

1/1

www.prokontrol.com

JCI -

1

Controls Group 507 E. Michigan Street P.O. Box 423, Milwaukee, WI 53202 Code No. LIT-1922655350_hum whole 1922655 9thcc:2-116 Electric System 350TM

System 350TM Humidity Controlsw351.tif w351p.tif s351.tif d351.tif y351.tif

Rev: 07/18/97 logo: JCI left ft: elec right ft: standard Sect# = 2 seQ# = 341

W351he6300.tif

W351P

S351he6310.tif

D351

Y350R

HE-67S3-0N00P The System 350. Humidity family includes on/off SPDT and proportional ( 0 t o10 VDC a n d 0 t o20mA output) controls, as well as stage, display, and power modules. The HE-67S3-0N0BT and HE-67S3-0N00P Series Humidity Transmitters are used with the W351 Series Humidity Control for precise humidity sensing. Applications include: clean rooms computer rooms pharmaceutical manufacturing process high/low humidity alarm museums libraries space humidity control humidity monitoring and display paper manufacturing process and storage greenhouses churches

HE-67S3-0N0BT

Features! !

BenefitsProvides reliable performance Covers a wide range of applications with minimal inventory investment Provides versatility for a wide range of applications; enables user to match equipment cycle rate and/or sequencing for a given application Provides flexible installation capabilities Eliminates wiring between modules Gives convenient, cost-effective, pre-packaged options Holds setpoint regardless of load on system and its rate of change Provides flexible and customizable application solutions

Electronic Accuracy and Repeatability Field Selectable Modes Dehumidification/Humidification Humidity Adjustable Settings Over a Wide Range Surface-Mount or DIN Rail-Mounting Ability Plug-Together, 5-Pin Connectors Sensors Included with Most Models ProportionaI/Integral Selectable Option on Some Controls Modular Design

! ! ! ! !

!

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond t hese specifications, consult the local Johnson 03/02 Johnson Controls, Inc Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

1/1

www.prokontrol.com

JCI -

2

Controls Group 507 E. Michigan Street P.O. Box 423, Milwaukee, WI 53202 Code No. LIT-1922665350_pres whole 1922665 9thcc:2-126 Electric System 350TM

System 350TM Pressure Controlsp352.tif p352p.tif s352.tif d352.tif p399v.tif dpt2064.tif y350.tif

Rev: 07/18/97 logo: JCI left ft: elec right ft: standard Sect# = 2 seQ# = 343

P352

P352P

S352

D352

P399

DPT-2640

Y350R

The System 350. Pressure family includes on/off SPDT and proportional ( 0 t o10 VDC a n d 0 t o20 mA output) controls, as well as stage, display, and power modules. A P399 Pressure Transducer or DPT-2640 Pressure Transmitter provides input to the P352 Pressure Control. Applications include: condenser fan cycling (multiple) high pressure indication room or building static pressure supply side static pressure

Features! !

BenefitsProvides reliable performance Covers a wide range of applications with minimal inventory investment Provides versatility for a wide range of applications; enables user to match equipment cycle rate and/or sequencing for a given application Provides flexible installation capabilities Eliminates wiring between modules Gives convenient, cost-effective, prepackaged options Holds setpoint regardless of load on system and its rate of change Provides flexible and customizable application solutions

Electronic Accuracy and Repeatability Field Selectable Modes Heating/Cooling Temperature Adjustable Settings Over a Wide Range Surface-Mount or DIN Rail-Mounting Ability Plug-Together, 5-Pin Connectors Sensors Included with Most Models ProportionaI/Integral Selectable Option on Some Controls Modular Design

!

! ! ! !

!

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond t hese specifications, consult the local Johnson 09/01 Johnson Controls, Inc Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

1/1

www.prokontrol.com

JCI -

3

Controls Group 507 E. Michigan Street P.O. Box 423, Milwaukee, WI 53202 Code No. LIT-1922610350_bcon

Basic Controlsa350.tif

less

1922610

9thcc:2-97B

Electric

System 350 TM

A350A/BElectronic On/Off Temperature ControlThe A350 on/off Control has a single-pole, double-throw (SPDT) relay with LED indication of the relay status for use with heating and cooling equipment. Adjustments include: setpoint, differential, and heat/cool mode of operation. Applications include staging compressors for frozen food or dairy cases, chilled water, and space thermostat control of rooftop packages for heating/air conditioning. Refer to A350A/B Series Electronic On/Off Temperature Control Product Data for more details.

Rev: 07/18/97 logo: JCI left ft: elec right ft: standard Sect# = 2 seQ# = 332

a350e.tif

A350EElectronic On/Off Cooling ControlThe A350E is an on/off electronic, cooling only control with SPDT relay output, LED indication, and both Fahrenheit and Celsius temperature scales. Besides being a cooling only control, the A350E has two features that differentiate it from the A350A/B Electronic Temperature Control: an adjustable minimum setpoint and sensor short/open circuit protection. Refer to A350E Electronic On/Off Cooling Control Product Data for more details.a350p.tif

A350PElectronic Proportional Plus Integral Temperature Control

The A350P is a proportional or proportional plus integral control that has both Fahrenheit and Celsius temperature scales and a unique ten-segment LED that displays percentage of output. Adjustments include setpoint (Fahrenheit or Celsius), throttling range, minimum output, and reverse or direct acting mode of operation (for heating or cooling applications). The control also provides two simultaneous analog outputs of 0 to 10 VDC and 0 to 20 mA. The output is jumper-selectable for direct- or reverse-acting output. Application capabilities include mixing valves for chilled or hot water control and modulating dampers for air flow. Refer to A350P Series Electronic Proportional Plus Integral Temperature Control Product Data for more details.a350r_2.tif

A350RElectronic Temperature Reset Control (with Relay)

The A350R is an electronic reset control with an SPST (normally open) relay with LED indication for relay operation. The A350R raises or lowers (resets) the temperature of the supply water or supply air based on a proportional drop or rise in temperature at the outdoor sensor. Adjustments include reset ratio (1:5 to 3:1), differential (1 to 30F), minimum supply temperature (50 to 160F), maximum supply temperature (160 to 220F), adjustable master reset setpoint temperature (40 to 70F), jumper selectable relay on-time (off, 1, 2, or 3 minutes), adjustable setback temperature (0 to 30F), and selectable warm weather shutdown temperature settings. Typical applications include on/off control of single or multi-stage boilers. Refer to A350R Electronic Temperature Reset Control (With Relay) Product Data for more details.

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond t hese specifications, consult the local Johnson 03/02 Johnson Controls, Inc Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

1/3

www.prokontrol.com

JCI -

4

Controls Group 507 E. Michigan Street P.O. Box 423, Milwaukee, WI 53202 Code No. LIT-1922610

Basic Controls (Continued)a350s_a.tif

A350SElectronic Temperature Reset Module (without Relay)The A350S requires the use of an S350 to provide either on/off (S350A) or proportional (S350P) output. There are two A350S models with different reset ratio adjustment ranges (1:5 to 10:1, or 1:30 to 1:1) for different applications. Other adjustments include: minimum supply temperature (35 to 80F), maximum supply temperature (45 to 140F), and adjustable master reset setpoint (30 to 90F). Refer to A350S Electronic Temperature Reset Module (Without Relay) Product Data for more details.

w351.tif

W351Electronic On/Off Humidity ControlThe W351 Humidity Control contains an SPDT relay with LED indication of relay status, for use with humidification and dehumidification equipment. Adjustments include setpoint (10 to 90% RH), differential (2 to 10% RH), and humidify/dehumidify mode of operation. Typical applications include humidity control of clean rooms, computer rooms, office space, and warehouses. Refer to W351 Series Electronic On/Off Humidity Control Product Data for more details.

w351p.tif

W351PElectronic Proportional Plus Integral Humidity ControlThe W351P is a proportional or proportional plus integral humidity control with a unique 10 segment LED that displays percent of output. Adjustments include: setpoint, integration constant, throttling range, minimum output, and reverse and direct acting mode of operation. The control provides two simultaneous analog outputs of 0 to 10 VDC and 0 to 20 mA. A typical application includes modulating steam valves for humidification. Refer to W351P Series Electronic Proportional Plus Integral Humidity Control Product Data for more details.

p352.tif

P352ABElectronic On/Off Pressure ControlThe P352AB control is an automatic reset, electronic pressure control with SPDT relay output and LED indication. Typical applications include condenserfan cycling, compressor unloading , as well as other high and low pressure cutout applications. It is designed for use as either a direct or reverse-acting control. Three models provide control over a 0 to100, 90 to 250, or 240 to 600 psi pressure range. The 0 to 100 psi model has an adjustable differential of 2 to 50 psi, and the 90 to 250 and 240 to 600 psi models have an adjustable differential of 10 to 100 psi. The P352AB controls use a (specified) P399 Electronic Pressure Transducer and a WHA-P399 Wiring Harness which must be ordered separately. Refer to P352AB Electronic On/Off Pressure Control Product Datafor more details.

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond t hese specifications, consult the local Johnson 03/02 Johnson Controls, Inc Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

2/3

www.prokontrol.com

JCI -

5

Controls Group 507 E. Michigan Street P.O. Box 423, Milwaukee, WI 53202 Code No. LIT-1922610

Basic Controls (Continued)p352p.tif

P352PElectronic Proportional Plus Integral Pressure Controls: Static Pressure (W.C.) and PSI SeriesThe P352P Series Controls may be setup as proportional-only or proportional plus integral pressure controls, which generate analog output signals based on the sensed pressure. These controls feature a 10 segment LED that displays percent of output, and they generate a 0 to 10 VDC and a 0 to 20 mA signal simultaneously. Adjustments include: setpoint, reverse or direct operation throttling range, minimum signal output, and integration constant (recovery rate). The P352PQ control models are designed for static pressure applications (W. C.) and use a DPT2640 Series Static Pressure Sensor which must be ordered separately. The P352PN series are designed for refrigerant pressure applications and come in three model pressure ranges: 0 to 100, 90 to 250, or 240 to 600 psi. The P352PN series models use a P399 Electronic Pressure Transducer and WHA-P399 Wiring Harness which must be ordered separately. Refer to P352P Series Electronic Proportional Plus Integral Pressure Controls: Static Pressure (W.C.) and PSI Series Product Data for more details.

r353s353.tif

R353 / S353Modular Electronic SequencerThe R353 is a signal input module that accepts 0 to 10 VDC, 0 to 20 mA, or 135 to 10k ohm slidewire potentiometer inputs to drive up to ten S353 Stage Modules. The S353 Stage Modules contain an SPDT relay with LED indication of relay status. Field selectable jumpers allow for direct, reverse, or mixed acting applications. The R353 / S353 works in any combination of heating, cooling, humidity, and/or pressure applications. Refer to R353/S353 Modular Electronic Sequencer Product Data for more details.

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond t hese specifications, consult the local Johnson 03/02 Johnson Controls, Inc Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

3/3

www.prokontrol.com

JCI -

6

Controls Group 507 E. Michigan Street P.O. Box 423, Milwaukee, WI 53202 Code No. LIT-1922615350_amod

Accessory Moduless350.tif

less

1922615

9thcc:2-99

Electric

System 350 TM

Rev: 07/18/97 logo: JCI left ft: elec right ft: standard Sect# = 2 seQ# = 333

S350 / S351 / S352Temperature, Humidity, and Pressure Stage ModulesSystem 350 Stage Modules can be used with respective Temperature (A350), Humidity (W351), and Pressure (P352) Controls. The stage modules have three adjustments: reverse or direct-acting operation; differential (1 to 30F, 0.5 to 17C, 2 to 10% RH; or 2 to 50 psi), and offset (1 to 30F, 0.6 to 16.7C, 2 to 30% RH, 2 to 50 psi). All stage modules have an SPDT relay output with LED indication. Applications include any job requiring multiple staging when used in conjunction with its respective System 350 control. Refer to S350A Series Temperature Stage ModulePage 17, S351 Humidity Stage ModulePage 28, and S352 Pressure Stage ModulePage 37 for more details.

s350c.tif

S350CTemperature Slave Stage ModuleThe S350C is used in conjunction with the A350 Temperature Control to add multiple stage capability with independently adjustable setpoints. The module is an electronic control with a single-pole, double-throw (SPDT) relay output. The S350C receives its power and sensor inputs from the A350 Temperature Control to which it is connected. Refer to S350C Temperature Slave Stage ModulePage 18 for more details.s350p.tif

S350PProportional Plus Integral Temperature Stage ModuleThe S350P is used in conjunction with the A350 Series Temperature Controls to add proportional or proportional plus integral staging capability with analog 0 to 10 VDC and 0 to 20 mA outputs. Refer to S350P Proportional Plus Integral Temperature Stage ModulePage 19 for more details.d350.tif

D350 / D351 / D352Temperature, Humidity, and Pressure Display ModulesSystem 350 Display Modules have a 3-digit LCD display that provides continuous sensor output information (read-only) for use with A350, W351, and P352 Controls. Display modules feature a setpoint button located on front of the module to obtain actual space conditions or setpoint readings. Display modules can be helpful when making accurate setpoint adjustments to System 350 controls. Refer to D350 Series Temperature Display ModulePage 20, D351 Humidity Display ModulePage 29, and D352 Series Pressure Display ModulePage 38 for more details.

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond t hese specifications, consult the local Johnson 09/01 Johnson Controls, Inc Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

1/2

www.prokontrol.com

JCI -

7

Controls Group 507 E. Michigan Street P.O. Box 423, Milwaukee, WI 53202 Code No. LIT-1922615

Accessory Modules (Continued)c-7355di.tif

CLK350-2Time Clock (for use with A350R)The CLK350-2 Time Clock is for use with A350R Electronic Temperature Reset Control. It is programmable in blocks of days or from day to day, or both. Refer to CLK350-2 Time Clock (Accessory Module for Use With A350R)Page 16 for more details.y350.tif

Y350RPower ModuleThe Y350R provides a convenient means of powering System 350 modules in situations where Class 2 power is not available. Input voltage is 120/240 VAC. Output voltage is 24 VDC unfiltered. Refer to Y350R Power ModulePage 46 for more details.

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond t hese specifications, consult the local Johnson 09/01 Johnson Controls, Inc Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

2/2

www.prokontrol.com

JCI -

8

Controls Group 507 E. Michigan Street P.O. Box 423, Milwaukee, WI 53202 Code No. LIT-1922255t22_s whole 1922255 9thcc:2-72 Electric Sensors and Stats

T22 / T25 / T26 Series

Line Voltage Wall Thermostat (Heating, Cooling, or Heating and Cooling)t26.epsSeriesT26 3Y

Rev: 07/18/97 logo: JCI left ft: elec right ft: standard Sect# = 2 seQ# = 281

t26.tif

t22.tif

t25.epsSeries T25 Y

t25.tif

2 1 Action on Increase of Temperature

B RHigh Stage

B RLow Stage

Action on Increase of Temperature

T26

T22 close differential without the need for anticipators bi-metal thermometer supplied as standard except where indicated equipped with adjustable dial stops (T26 Series)

DescriptionFor line voltage control of residential, commercial, or industrial heating or yearround air conditioning. Heat or cold anticipators are not required. The liquidcharged temperature sensing element and highly efficient diaphragm and leverage provides close temperature control.

T25

Applications line voltage control of heating and cooling equipment

SpecificationsTemperature range is 40 to 90F (5 to 30C), except energy conservation models.

Features attractive beige colored, high-impact plastic enclosure (T26 Series)

Accessories replacement knobs and faceplates for double trim plate for mounting two T22s or T26s

To OrderSpecify the code number from the following selection chart. For the thermostat guard, refer to G Series Thermostat and Humidistat GuardsG Series Thermostat and Humidistat GuardsG Series Thermostat and Humidistat Guards. Differential Approximately C (F) Heating Cooling Ship Wt. (lb)

Selection ChartCode NumberT22AAA-1C T22ABC-1C T22ABC-3C T22BBC-1C T22CBC-1C T22CBC-3C T26A-14C (No thermometer) T26A-15C (No thermometer) T22JAA-1C T22JCC-1C T26J-7C (No thermometer) T26J-9C (No thermometer) Knob

Type of Adjustment

ApplicationHeating

Selector SwitchOff-Auto

Knob Concealed Knob Concealed Knob

SPST SPST, Medium Duty SPST, Heavy Duty SPST, Energy Conservation Heating model, max. setting 75F (24C) SPST, Energy Conservation Heating model, max. setting 65F (18C) Cooling SPST SPST, Energy Conservation Cooling model, min. setting 75F (24C) SPST, Energy Conservation Cooling model, min. setting 78F (26C) Off-Auto Auto-Off-Fan Auto-Off-Fan

1 3/4 (1) 1.3 3 (1.7)

None

2 (1.1)

1.0

2 1/4 (1.3)

1.3

None 2 (1.1) 1.0

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond t hese specifications, consult the local Johnson 08/02 Johnson Controls, Inc Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

1/2

www.prokontrol.com

JCI - 12

Controls Group 507 E. Michigan Street P.O. Box 423, Milwaukee, WI 53202 Code No. LIT-1927385a419s p; 1927385 9thcc:na Refrigeration Temperature Controls

A419 Series

Electronic Temperature Controls with NEMA 1 or NEMA 4x Watertight EnclosuresA419NEMA1&4.tif

Rev: 09/30/98 logo: standard left ft: none right ft: standrd Sect# = 7 seQ# = 71

new photo pending

The controls feature remote sensing capability and interchangeable sensors. The A419 controls are available in either NEMA 1, high-impact plastic enclosure suitable for surface or DIN rail mounting or NEMA 4X Watertight surface-mount enclosures.

lockable front-panel touchpad allows easy set up and adjustment of the A419 control setpoint, differential, and other functions; a concealed jumper locks the touchpad, and deters unauthorized adjustment of the control settings low- and line-voltage models provides options for almost any refrigeration or HVAC control-voltage application

Features easy-to-read LCD displays the sensed temperature and control-function status clearly and custom icons on the display indicate the control and system status at a glance the 30 (F or C) temperature differential adjustment range allows precise (1F or C) temperature differential settings that are much tighter than electromechanical controls the Adjustable Anti-Short Cycle Delay (0 to 12 Minutes in 1-Minute Increments) ensures that the output relay remains off for a user-set time delay, and helps avoid hard starts, nuisance overload outages, and unnecessary equipment wear the Temperature Offset Function shifts the cut-in and cut-in setpoints by an adjustable offset when a user-installed, external switch closes the A419 controls binary input circuit the high-impact thermoplastic type NEMA 1 allows surface or snap-fit DIN rail mount; the Noryl high-impact thermoplastic type NEMA 4X enclosures allow watertight surface mount

ApplicationsThe A419 can be used to control a wide variety of single-stage refrigeration or HVAC equipment. Typical applications include: freezer control in convenience stores reach-in coolers supermarket display cases for produce or meats restaurant or convenience store walk-in coolers boiler control compressor lockout (disables the compressor when temperature exceeds limits) condensor fan cycling pump control for cooling towers space and return air temperature

A419 Control and Sensor

DescriptionThe A419 series controls are single-stage, electronic temperature controls with a Single Pole, Double Throw output relay. They feature a lockable front-panel touchpad for setup and adjustment, and a Liquid Crystal Display for viewing the temperature and status of other functions. A Light-Emitting Diode indicates the controls output relay (On/Off) status. The A419 controls are available in 24 VAC or 120/240 VAC models. The A419 controls have heating and cooling modes, adjustable setpoint and differential, an adjustable anti-short cycle delay, and a temperature offset (setback) function. The setpoint range is -30 to 212F (-34 to 100C).

To OrderSpecify the code number from the following selection chart.

Selection ChartCode NumberA419ABC-1C A419AEC-1C A419GBF-1C A419GEF-1C

Item

Description

Line Voltage, NEMA 1 Enclosure A419 Series Electronic Temperature Control with Display, A99 Sensor Included Supply Voltage: 120 or 240 VAC Range: -30 to 212F (-34 to 100C) Line Voltage, NEMA 4X Enclosure A419 Series Differential: 1 to 30F (1 to 30C) Electronic Temperature Control with Display, A99 Sensor Included 24 VAC, NEMA 1 Enclosure A419 Series Electronic Temperature Control with Display, A99 Sensor Included 24 VAC, NEMA 4X Enclosure A419 Series Electronic Temperature Control with Display, A99 Sensor Included Supply Voltage: 24 VAC, Class 2 Range: -30 to 212F (-34 to 100C) Differential: 1 to 30F (1 to 30C)

Accessories A99BB-200C A99BA-200C A99BB-25C BKT287-1R BKT287-2R PLT344-1R CLK350-2C WEL11A-601R Digital Clock Immersion Well Accessory Mounting Hardware Replacement Temperature Sensors PTC Sensor with 6-1/2 ft (2 m) Leads PTC Sensor with 6-1/2 ft (2 m) Shielded Leads PTC Sensor with 9 in (0.25 m) 12 in. (305 mm) long DIN Rail 36 in. (914 mm) long DIN Rail Two End Clamps for DIN Rail Mounting 7-Day Programmable Digital Clock for controlling Temperature Offset Function Immersion Well for applying sensor in fluid applications

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson 02/03 Johnson Controls, Inc Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

1/2

www.prokontrol.com

JCI - 13

Controls Group 507 E. Michigan Street P.O. Box 423, Milwaukee, WI 53202 Code No. LIT-1927105a25s whole 1927105 9thcc:7-19 Refrigeration Temperature Controls

A25 Series a25an1c.tif

Warm Air Limit Control with Manual Reseta25ap1c.tif

a25.epsSeries A25A25 SeriesY YR

Rev: 07/18/97 logo: JCI left ft: refrig right ft: standard Sect# = 7 seQ# = 21

R

B

B

Action on Increase Action on Increase of Temperature

of Temperature

A25AN-1

A25AP-1

DescriptionThe A25 warm air control locks out on a temperature increase to the control set point. Manual reset is required before the electrical contacts can be reclosed. The A25 is normally located in a return air duct and is wired to shut down air conditioning or ventilating fans when the temperature of the air becomes excessively hot.

Features trip-free reset lever does not permit restarting until the reset lever is manually released the rod and tube type sensing element provides positive control action

Specifications maximum element temperature: 300F (149C)

To OrderSpecify the code number from the following selection chart.

Applications high temperature cut-out

Selection ChartCode Number

Switch ActionSPST Open High SPDT

Range F (C)25 to 215 (-4 to 102) 25 to 215 (-4 to 102) 25 to 215 (-4 to 102) 25 to 215 (-4 to 102)

Range AdjusterKnob Knob

Dial Stop F (C)High Limit Set at 125 (52) High Limit Set at 125 (52) High Limit Set at 125 (52) High Limit Set at 125 (52)

Electrical RatingsMotor Ratings VAC 12016.0 96.0

2089.2 55.2

2408.0 48.0

277

A25AN-1C A25CN-1C

AC Full Load Amp AC Locked Rotor Amp Non-Inductive Amp

Factory Mutual Approved ModelsA25AP-1C A25CP-1C SPST Open High SPDT Concealed Screwdriver Slot Concealed ScrewdriverSlot

16.0 Amp at 120/277 VAC

Pilot Duty125 VA, 24 to 600 VAC

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond t hese specifications, consult the local Johnson 12/01 Johnson Controls, Inc Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

1/1

www.prokontrol.com

JCI - 14

Installation Sheets Manual Temperature Controls Section Technical Bulletin Issue Date

121 A70, A72 0591

A70, A72 Series Temperature Controls A70 Single-Pole and Four-Wire Two-Circuit A72 Two-Pole ConstructionApplicationThe A70 single-pole and A72 two-pole controls incorporate a load-carrying, contact structure which provides direct control of AC motors within the control rating. (See cover label for electrical rating.) All Series A70, A72 controls are designed for use only as operating controls. Where an operating control failure would result in personal injury and/or loss of property, it is the responsibility of the installer to add devices (safety, limit controls) or systems (alarm, supervisory systems) that protect against, or warn of, control failure. contact, the auxiliary contact closes to actuate a signal or other auxiliary circuit at the same time the main contact opens. (See Fig. 6.)

InstallationMounting The A70 control in the NEMA 1 enclosure must be located in areas protected from the direct effects of weather. If the control is directly exposed to the weather or other wet environments, it must be equipped with an outdoor enclosure. Mount the control on a flat surface or panel board by two screws or bolts through the holes in the back of the case. Controls are supplied without brackets unless specified. The standard bracket is Part Number 271-350. The desired mounting position is with the element bellows pointing down. Fig. 1 -- A70 Temperature Control with a style 1 sensing element.

OperationControls are available with either CLOSE high -- OPEN low or OPEN high -- CLOSE low contact action for heating or refrigeration applications. The snap-acting contacts are operated by a temperature sensing element. On the A70 controls with auxiliary

General Instructions1. Avoid sharp bends or kinks in the capillary tubing.

1991 Johnson Controls, Inc. Code No. LIT-121121 Part No. 997-202

1

www.prokontrol.com

JCI - 17

Controls Group 507 E. Michigan Street P.O. Box 423, Milwaukee, WI 53202 Code No. LIT-1927175p10s_lpc p;w 1927175 9thcc:7-33 Refrigeration Pressure Controls

P10 Series

Low Pressure Control (Single or 2-Stage)p10bc7.tif p10.epsP10 SeriesY R B B Y R

Rev: 07/18/97 logo: JCI left ft: frig right ft: standard Sect# = 0 seQ# = 1

Specifications model P10BJ-1 is rated for 24 amp noninductive when used as an SPST (R-Y). (See Electrical Ratings.) maximum allowable pressure is 150 psig (1034 kPa). maximum ambient temperature is 140F (60C)

Action on Increase of PressureP10BC-7 (With Bracket No. BKT16A-600R)

To OrderSpecify the code number from the following selection chart.

DescriptionThese pressure controls open or close electrical circuits from a change in operating air pressure. R to Y terminals make (cut-in) on pressure rise.

Accessories A universal mounting bracket No. BKT16A-600R as well as a barbed fitting is supplied as standard. Model P10FC-4 has a jumper installed on the common terminals.

Electrical RatingsMotor Ratings VAC 12016.0 16.0

2089.2 55.2 9.2

240 277 6008.0 8.0 7.0 7.2

P10BC-7 AC Full Load Amp Non-Inductive Amp AC Locked Rotor Amp 96.0 48.0 42.0

Features visible calibrated adjustable range scale snap-acting switch in a dust protected enclosure easily accessible wiring terminals

Applications pneumatic systems control of pumps or small air compressors

Pilot Duty 125 VA at 24 to 277 VAC P10BG-3 AC Full Load Amp Non-Inductive Amp 6.0 6.0 3.4 20.4 3.4 3.0 18.0 3.0 2.6 AC Locked Rotor Amp 36.0

Pilot Duty 125 VA at 24 to 277 VAC P10BJ-1

Selection ChartCode NumberP10BC-7C P10BG-3C

AC Full Load Amp

16.0

9.2 55.2 16.0 24.0

8.0 48.0

7 42

No. of Contact Stages Action1 1 SPDT SPDT

Range psig (kPa)3 to 20 (21 to 138) 2 to 20 (15 to 138) 3 to 20 (21 to 138)

Factory Setting psig (kPa)12 (R to Y Cut-in) 12 (R to Y Cut-in)

Pressure Switch Diff Connector psi (kPa)2 0.2 Barbed Fitting 1/8 in. Female NPSF 1/8 in. Female NPSF High Stage 2 (14) 1/8 in. Barbed Fitting 1/8 in. Barbed Fitting

AC Locked Rotor Amp 96.0 NonInd. Amp Double Throw 16.0 Single Throw 24.0

16.0 16.0 16.0 24.0 24.0 24.0

Pilot Duty 125 VA at 24 to 600 VAC P10FC-4 AC Full Load Amp Non-Inductive Amp 16.0 16.0 9.2 55.2 9.2 8.0 8.0 7.0 7.2 AC Locked Rotor Amp 96.0 48.0 42.0

P10BJ-1C

1

SPDT

12 (R to Y Cut-in)

2

P10FC-4C

2

SPDT

(R-Y Cutout) (R-Y Cut-in) Low 3 to 20 Low Stage High Stage Stage (21 to 138) 8 (55) 12 (82) 2 (14) 3 to 20 (21 to 138)

Pilot Duty 125 VA at 24 to 277 VAC On 2- and 3-stage models, the maximum connected load shall not exceed 2000 VA P10PA-11 AC Full Load Amp Non-Inductive Amp 6.0 6.0 3.4 20.4 3.4 3.0 18.0 3.0 AC Locked Rotor Amp 36.0

P10PA-11C

3

SPST

Stage 1 Stages 2 & 3 Stage Stages Open High Open High 1 2&3 6 (41) 18 (120) 3 (21) 0.4 (3)

Pilot Duty 125 VA at 24 to 277 VAC On 2- and 3-stage models, maximum connected load shall not exceed 2000 VA

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond t hese specifications, consult the local Johnson 12/01 Johnson Controls, Inc Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

1/1

www.prokontrol.com

JCI - 18

Controls Group 507 E. Michigan Street P.O. Box 423, Milwaukee, WI 53202 Code No. Lit-1921510Y ZKROH WKFF 3QHXPDWLFV 6ROHQRLG$LU9DOYHV

V11

Three-Way Solenoid Air ValveYHSL DescriptionThe V11 Three-Way Solenoid Valve is used in applications where an electrical circuit operates a pneumatic control device.

5HY ORJR -&, OHIWIW QRQH ULJKWIW VWDQGDUG 6HFW VH4

ApplicationAll V11 Series Air Valves are designed for use as operating devices. Where an operating control failure would result in personal injury and/or loss of property, it is the responsibility of the installer to add devices or systems to protect against, or warn of, control failure.

Features two-position action three piping connections marked: - N.O. (normally open) - N.C. (normally closed), and COM (common) can be operated manually by removing the plug and inserting a key furnished with an attached bracket operates in any position positive air seal

Repair PartsIf the product fails to operate within its specifications, unit replacement is required.

To OrderSpecify the code number from the following selection chart.

Selection ChartCode NumberV11HAA-100 V11HBA-100 V11HCA-100 V11HDA-100 V11HFA-100 V11HGA-100 V11HAA-115 V11PNA-105

SpecificationsDescription V11 Three-Way Solenoid ValveAir Connections Alternating Current Models Direct Current Models 1/4 in. Barb Connections in Common Port and Normally Closed Port; Normally Open Port is 1/8 in. NPT (Internal) Minimum 32F (0C) Maximum 140F (60C) Minimum 32F (0C) Maximum 104F (40C) 7/8 in. Diameter Valve Body Dull Gray (Iridate) Cover and Case Zinc Plated Valve Body Die Cast Aluminum Cover and Case Cold, Rolled Steel 30 psig (210 kPa) 0 to 25 psig (0 to 175 kPa)

110/120 V, 50/60 Hz 220/240 V, 50/60 Hz 208 V, 50/60 Hz 440/480 V, 50/60 Hz 277 V, 50/60 Hz 24 V, 50/60 Hz 110/120 V, 50/60 Hz Includes Internal Grounding Lug 24 VDC

Ambient Temperatures Conduit Opening Finish Material

AccessoriesCode NumberY99AA-4C

DescriptionManual Opener Key

Maximum Pressure Rating Operating Pressure (All Three Ports) Power Consumption

Alternating Current Models 6 Watts 24 VDC Models 9 Watts With a 15 psig (103 kPa) Inlet and 0 psig (0 kPa) Outlet. The valve will pass 1.5 cfm (2592 scim) of air from the Common to the Normally Closed connection (when energized) or from the Common to the Normally Open connection (when de-energized). 18 in. Wire Leads

Pressure and Flow Ratings

Wiring Connections

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson 02/99 Johnson Controls, Inc Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

1/1

www.prokontrol.com

JCI - 19

Controls Group 507 E. Michigan Street P.O. Box 423, Milwaukee, WI 53202 Code No. LIT-1927005a11s_ltc Less-M/a11-a19 1927005 9thcc:7-5A Refrigeration Temperature Controls

A11 Series a11b1c.tif

Low Temperature Cutout Controla11coil.eps

a11wire.epsA11 Se r ie s

Rev: 07/18/97 logo: JCI/Penn left ft: frig right ft: standard Sect# = 0 seQ# = 1

A11B-1

Mount Coils Horizontally ONLY

DescriptionThe A11 Series low temperature cutout controls incorporate a 20 foot long, vapor charged, sensing element. The A11 reacts to the coldest 18 inch section of the controls sensing element. The A11 is suitable for monitoring the face temperature of hot water coils for freeze protection.

Accessories replacement cover: CVR30A-601R

Action on Increase of Temperature

Applications

To Order

low temperature cut-out for coils and/or pipe liquid sensing

Specify the code number from the following selection chart.

Specifications ambient temperature of control: 0-140F (-17.8 - 60C) maximum element temperature: 250F (121C)

Electrical RatingsMotor Ratings VACAC Full Load Amp AC Locked Rotor Amp Non-Inductive or Resistance Load Amp (Not Lamp Loads)

Features snap-acting switch external temperature scale easy setpoint adjustment with top or bottom access

12016.0 96.0 16.0

2089.2 55.2 9.2

2408.0 48.0 8.0

Pilot Duty 125 VA, 24 to 277 VAC

Selection ChartCode Number

Switch Action

Range F (C)35 to 45 (2 to 7) 35 to 45 (2 to 7)

Diff F (C)Manual Reset 8 (4.4) (Fixed)

Bulb and Capillary20 ft of 1/8 in. O.D. Tubing, 4 ft Cap. 20 ft of 1/8 in. O.D. Tubing, 4 ft. Cap.

Range AdjusterScrewdriver Slot Screwdriver Slot

A11A-1C A11B-1C

SPST Open Low SPST Open Low

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond t hese specifications, consult the local Johnson 08/02 Johnson Controls, Inc Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

1/1

www.prokontrol.com

JCI - 20

Controls Group 507 E. Michigan Street P.O. Box 423, Milwaukee, WI 53202 Code No. LIT-1927010a19s_rbc Less,M/a11-a19 1927010 9thcc:7-5B Refrigeration Temperature Controls

A19 Series

Remote Bulb Controla19abc24.tifYR

a19.epsA19 Series Terminal Arrangement for SPDT

Rev: 07/18/97 logo: JCI/Penn left ft: none right ft: standard Sect# = 6 seQ# = 489

ApplicationsThe A19 is suitable for temperature control in heating, ventilating, and refrigeration.

Replacement PartsCode NumberCVR28A-617R CVR28A-618R KNB20A-602R

B

Description

Concealed adjustment Visible scale Replacement Knob Kit

A19ABC-24

Action on Increase of Temperature fixed or adjustable differential available variety of sensing element styles unaffected by cross-ambient conditions

To OrderSpecify the code number, packing nut number (if required), and bulb well number (if required). See the following selection chart.

DescriptionThe A19 Series are single stage temperature controls that incorporate liquid filled sensing elements.

Features wide temperature ranges available constant differential throughout the entire range compact enclosure

AccessoriesA packing nut is available for closed tank application. Specify the part number FTG13A-600R. Bulb wells (WEL14A Series) are available for liquid immersion applications. Refer to the following selection chart or to Bulb Wells.

Selection ChartCode Number Switch ActionSPST Open Low SPDT(b)

Range F (C)

Diff F (C)

Bulb and Capillary

Bulb Well No. (order separately)WEL14A-602R WEL14A-603R WEL14A-602R WEL14A-602R WEL14A-602R WEL14A-602R WEL14A-602R WEL14A-602R WEL14A-602R

Range Adjuster

Max. Bulb Temp. F (C)140 (60) 170 (77) 140 (60) 140 (60) 140 (60) 140 (60) 275 (135) 140 (60) 140 (60)

Adjustable Differential (Wide Range) A19ABA-40C A19ABC-4C(a)

-30 to 100 (-34 to 38) 50 to 130 (10 to 55) -30 to 100 (-34 to 38) -30 to 100 (-34 to 38) -30 to 100 (-34 to 38) -30 to 100 (-34 to 38) 25 to 225 (-4 to 107) 0 to 80 (-18 to 27) -30 to 50 (-34 to 10)

3 to 12 (1.7 to 6.7)

3/8 in. x 4 in., 6 ft Cap.

Screwdriver Slot Knob Convertible Convertible Screwdriver slot Screwdriver slot Screwdriver slot Screwdriver slot Screwdriver slot

3 1/2 to 14 (1.9 to 8) 3/8 in. x 5 in., 8 ft Cap. 3 to 12 (1.7 to 6.7) 3 to 12 (1.7 to 6.7) 3 to 12 (1.7 to 6.7) 3 to 12 (1.7 to 6.7) 3 1/2 (1.9) 5 (2.8) 2 1/2 (1.4) 3/8 in. x 4 in., 8 ft Cap. 3/8 in. x 4 in., 20 ft Cap. 3/8 in. x 4 in., 10 ft Cap. 3/8 in. x 4 in., 6 ft Cap. 3/8 in. x 3 in., 10 ft Cap. 3/8 in. x 4 in., 6 ft Cap. 3/8 in. x 4 in., 7 ft Cap.

v A19ABC-24C v A19ABC-36CA19ABC-37C A19ABC-74C A19AAF-12C A19AAC-4C A19AAD-12C

SPDT SPDT SPDT SPDT SPDT SPDT SPST Open Low SPST Open Low SPDT SPDT

Fixed Differential Fixed Differential (Case Compensated)

Fixed Differential (Close) A19AAD-5C (c) A19AAF-20C A19AAF-21C 30 to 50 (-1 to 10) (Bulk Milk Cooler) -30 to 100 (-34 to 38) 40 to 90 (4 to 32) 2 1/2 (1.4) 2 1/2 (1.4) 1 1/2 (0.8) 3/8 in. x 2 5/8 in., 6 ft Cap. 3/8 in. x 4 in., 6 ft Cap. WEL16A-601R WEL14A-602R Screwdriver slot Screwdriver slot Screwdriver slot 190 (88) 140 (60) 140 (60)

3/8 in. x 5 3/4 in., 6 ft Cap. WEL14A-603R

(a) Replaces White-Rodgers 1609-101 (b) Replaces White-Rodgers 1609-12, -13; Ranco 010-1408, -1409, - 1410, -1490, 060-110; Honeywell L6018C-1006, L6021A-1005, T675A-1011, -1508, -1516, -1821, T4301A-1008, T6031A-1011, T6031A-1029 (c) Case-Compensated

v Universal Replacement, Multi-Mount.

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond t hese specifications, consult the local Johnson 08/02 Johnson Controls, Inc Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

5 Non-Stock Item. Built to Order.1/2

(R) For Refrigerants Not Listed, Contact Application Engineering

www.prokontrol.com

JCI - 21

Controls Group 507 E. Michigan Street P.O. Box 423, Milwaukee, WI 53202 Code No. Lit-1921715W SZ WKFF 3QHXPDWLFV 7KHUPRVWDWV

T-4002-30x

Single Temperature Thermostat with Cover and Two-Pipe Conversion KitsW[WLI DescriptionThe T-4002-30x Thermostat with Cover and Two-Pipe Conversion Kits feature a T-4002-201 (D.A.) or a T-4002-202 (R.A.) Thermostat. The kits also contain a white or beige cover and cover plate, a selection of faceplates, and all other necessary parts and mounting hardware required to convert a wide array of two pipe competitors thermostats.

5HY ORJR -&, OHIWIW QRQH ULJKWIW VWDQGDUG 6HFW VH4

Features reduces the number of stocked items simplifies the ordering process includes: - T-4002-201 (D.A.) or T-4002-202 (R.A.) Thermostat - White or Beige Cover - Terminal Connector and Tubing - Tube Couplings and Clamps Description - Installation Instructions - Faceplates (horizontal w/window, horizontal w/logo, vertical w/logo, and blank) - Cover Plate/Subplate - Adjustable Pipehead - Mounting Hardware

Selection ChartCode NumberT-4002-301 Direct Acting Thermostat and White Cover with Two-Pipe Conversion Kit

To OrderSpecify the code number from the following selection chart.

T-4002-302

Reverse Acting Thermostat and White Cover with Two-Pipe Conversion Kit

Direct Acting Thermostat and Beige T-4002-303 Cover with Two-Pipe Conversion Kit T-4002-304 Reverse Acting Thermostat and Beige Cover with Two-Pipe Conversion Kit

Non-Johnson Controls Conversions

Converts the Following Non-Johnson Controls Thermostats:Landis & Gyr Powers TH192 Series Wallbox and Drywall Mounting Robertshaw T-15 (Metal) Early Wallbox and Mortar Joint Robertshaw T-15 Later Wallbox and Mortar Joint Robertshaw 2212 Series (a) Robertshaw T-18 (Plastic) Drywall Mounting UPC

Barber-Colman TK Series or TKR Series Wallbox and Mortar Joint Honeywell TO900 or TP900 Series Wallbox Honeywell TO910 or TP910 Series Wallbox and Mortar Joint Honeywell TP970 Series Shallow and Deep Wallboxes Landis & Gyr Powers TH832 D Series Wallbox and Ground Plate Landis & Gyr Powers TH180 Series Wallbox and Drywall Mounting (a) Converts dead band thermostat to single temperature control.

Landis & Gyr Powers T-21 Series Ground Plate, Wallbox and Mortar Joint Draeger (ITT/Essen/Johnson Controls) Wallbox

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson 02/99 Johnson Controls, Inc Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

1/1

www.prokontrol.com

JCI - 32

Controls Group 507 E. Michigan Street P.O. Box 423, Milwaukee, WI 53202 Code No. Lit-1921255K ZKROH WKFF 3QHXPDWLFV +XPLGLW\,QVWUXPHQWV

H-4100

Pneumatic Room HumidistatKHSLresponse to changes in relative humidity. The humidistat can be ordered in direct or reverse acting models. mounts on virtually any wall surface with available accessories use with T-4000 covers

5HY ORJR -&, OHIWIW QRQH ULJKWIW VWDQGDUG 6HFW VH4

Features includes a Cellulose Acetate Butyrate (CAB) sensing element features a shock and vibration resis


Recommended