MLS OFICINA TECNICA Pol. Ind. Las Vías Parc 6A Nave 24 33199 Meres – Siero (Asturias) [email protected] Tfno.: 985 26 73 58 // Fax: 985 26 73 02 M M M E E E M M M O O O R R R I I I A A A J J J U U U S S S T T T I I I F F F I I I C C C A A A T T T I I I V V V A A A Y Y Y C C C A A A R R R A A A C C C T T T E E E R R R Í Í S S S T T T I I I C C C A A A S S S T T T É É É C C C N N N I I I C C C A A A S S S D D D E E E L L L A A A I I I N N N S S S T T T A A A L L L A A A C C C I I I Ó Ó Ó N N N S S S O O O L L L I I I C C C I I I T T T U U U D D D D D D E E E C C C L L L A A A R R R A A A C C C I I I Ó Ó Ó N N N D D D E E E U U U T T T I I I L L L I I I D D D A A A D D D P P P Ú Ú Ú B B B L L L I I I C C C A A A “MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTESUR” REFERENCIA LASAT 02210103684 . TÉRMINOS MUNICIPALES DE BARRAX Y ALBACETE ALBACETE CASTILLA – LA MANCHA Julio 2018
Transcript
Page 1: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

 

 

 

 

 

MMLLSS OOFFIICCIINNAA TTEECCNNIICCAA PPooll.. IInndd.. LLaass VVííaass PPaarrcc 66AA NNaavvee 2244

3333119999 MMeerreess –– SSiieerroo ((AAssttuurriiaass)) mmllss@@mmllss--ssll..eess

TTffnnoo..:: 998855 2266 7733 5588 //// FFaaxx:: 998855 2266 7733 0022

 

MMMEEEMMMOOORRRIIIAAA   JJJUUUSSSTTTIIIFFFIIICCCAAATTTIIIVVVAAA   YYY      

CCCAAARRRAAACCCTTTEEERRRÍÍÍSSSTTTIIICCCAAASSS   TTTÉÉÉCCCNNNIIICCCAAASSS   DDDEEE   LLLAAA   IIINNNSSSTTTAAALLLAAACCCIIIÓÓÓNNN   

   

SSSOOOLLLIIICCCIIITTTUUUDDD   DDDEEECCCLLLAAARRRAAACCCIIIÓÓÓNNN   DDDEEE   UUUTTTIIILLLIIIDDDAAADDD   PPPÚÚÚBBBLLLIIICCCAAA   

  

“MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE 

EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR” 

REFERENCIA LASAT 02210103684. 

 

TÉRMINOS MUNICIPALES DE BARRAX Y ALBACETE 

ALBACETE 

CASTILLA – LA MANCHA 

 

Julio  2018 

Page 2: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA JUSTIFICATIVA MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR  REFERENCIA LASAT 02210103684 

 MEMORIA JUSTIFICATIVA Y CARACTERÍSTICAS TÉCNICAS DE LA INSTALACIÓN 

 SOLICITUD DECLARACIÓN DE UTILIDAD PÚBLICA 

  

“MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR” 

REFERENCIA LASAT 02210103684  

TÉRMINOS MUNICIPALES DE BARRAX Y ALBACETE PROVINCIA DE ALBACETE CASTILLA – LA MANCHA 

 

 

 

 

 

 

IÍNDICE DE DOCUMENTOS 

 

 

1. MEMORIA 

DATOS GENERALES 

LÍNEA ELÉCTRICA DE EVACUACIÓN 132 kV 

  

2. PLANOS 

 

Page 3: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 

  

  

  

  

  

  

  

  

  

MMEEMMOORR IIAA

Page 4: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 

ÍÍ NN DD II CC EE   

    

DATOS GENERALES 

1  ANTECEDENTES .................................................................................................. 1 

2  OBJETO .............................................................................................................. 2 

3  PETICIONARIO .................................................................................................... 3 

4  JUSTIFICACIÓN DEL MODIFICADO DE PROYECTO ............................................... 3 

5  DESCRIPCIÓN DE LAS INSTALACIONES ................................................................ 3 

6  JUSTIFICACIÓN DE LA URGENTE OCUPACIÓN ..................................................... 4 

7  EMPLAZAMIENTO DE LAS INSTALACIONES ......................................................... 6 

 

LÍNEA ELÉCTRICA DE EVACUACIÓN 132 KV 

8  LÍNEA ELÉCTRICA DE EVACUACIÓN 132 KV. TRAMO SUBTERRÁNEO ................... 8 

8.1  DESCRIPCIÓN DEL TRAZADO ................................................................... 8 

8.2  CARACTERÍSTICAS ELÉCTRICAS .............................................................. 10 

8.3  CABLES DE FUERZA ............................................................................... 11 

8.4  EMPALMES ........................................................................................... 14 

8.5  TERMINALES ......................................................................................... 14 

8.6  PARARRAYOS ........................................................................................ 16 

8.7  CABLE DE FIBRA ÓPTICA ........................................................................ 18 

8.8  PUESTA A TIERRA .................................................................................. 19 

8.9  CANALIZACIONES .................................................................................. 20 

8.10  PUESTA A TIERRA DE LAS PANTALLAS ................................................... 22 

9  LÍNEA ELÉCTRICA DE EVACUACIÓN 132 KV. TRAMO AÉREO ............................. 24 

9.1  UBICACIÓN APOYOS Nº 20 Y 30 ............................................................ 25 

9.2  CARACTERÍSTICAS GENERALES DE LA INSTALACIÓN .............................. 25 

9.2.1  CONDUCTORES .......................................................................... 26 9.2.2  CABLE DE FIBRA ÓPTICA............................................................. 27 9.2.3  APOYOS Y ARMADOS ................................................................. 27 9.2.4  AISLAMIENTO‐CADENAS DE AISLADORES .................................. 29 9.2.5  PUESTAS A TIERRA ..................................................................... 30 9.2.6  PROTECCIÓN AVIFAUNA ............................................................ 32 

9.2.6.1  MEDIDAS CONTRA LA ELECTROCUCIÓN .......................... 32 9.2.6.2  MEDIDAS CONTRA LA COLISIÓN ...................................... 33 

10  ORGANISMOS AFECTADOS............................................................................... 34 

11  CONCLUSIONES ................................................................................................ 34 

Page 5: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 

  

 

 

 

 

 

 

 

 

 

DATOS GENERALES

Page 6: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 1 de 34 

1 ANTECEDENTES 

El proceso del aprovechamiento de recurso eólico en España, que es acorde con 

la  política  de  diversificación  energética  y  reducción  de  emisiones  de  la Unión 

Europea,  se ha visto apoyado desde  las administraciones autonómicas, en una 

apuesta  decidida  para  la  instalación  de  energía  eólica  en  su  territorio,  de 

acuerdo  a  unos  criterios  de  sostenibilidad  ambiental,  desarrollo  económico,  y 

marco legislativo adecuado. 

 

Consciente de este proceso y de  sus  limitaciones  la Sociedad ENERGÍA EÓLICA 

NOMADA S.L.U. está desarrollando estudios de localización y caracterización del 

potencial  eólico  en  el  ámbito  territorial  de  Castilla  La  Mancha.  Habiendo 

localizado un emplazamiento al suroeste de la población de Barrax, que cumple 

a priori, las condiciones de recurso suficiente, compatibilidad medioambiental, y 

posibilidad de evacuación de la energía producida, en la Provincia de Albacete. 

 

Así, tras una tramitación previa del Parque Eólico Barrax Norte Sur con 135 MW, 

que finalmente fue archivado, y recogiendo la información recabada durante su 

tramitación se redacto un nuevo proyecto y estudio de impacto ambiental con el 

que  el  19  de  febrero  de  2018,  se  solicitó  Autorización  Administrativa  Previa, 

Autorización  Administrativa  de  Construcción  y  Declaración  de  Impacto 

Ambiental para el Proyecto del Parque Eólico Barrax Norte Sur de 40 MW y su 

infraestructura de evacuación (Subestación 30/132 kV y línea 132 kV). 

 

Sobre este Proyecto ahora se confecciona un Modificado para soterrar el tramo 

de  línea  aérea  de  evacuación  comprendido  entre  los  apoyos  nº  20  y  nº  30, 

correspondiente al paralelismo  con  la  carretera provincial AB‐701 entre  los pk 

4+671 y 7+178 de la citada carretera. 

 

Page 7: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 2 de 34 

2 OBJETO 

El Modificado del Proyecto Constructivo, tiene por objeto una doble finalidad: 

 

a) Desde el punto de vista técnico, pretende evidenciar el cumplimiento de  la 

Reglamentación y Normativa vigente que  le es de aplicación, e  informar de 

las características de la instalación y sus condiciones. 

 

b) A efectos administrativos, la descripción básica y comprensiva de las obras e 

instalaciones necesarias para el soterramiento del tramo de la línea aérea de 

evacuación 132kV del parque eólico Barrax de 40MW comprendido entre los 

apoyos nº 20 y 30.  

 

Con el presente Modificado de Proyecto, se pretende solicitar ante el Servicio de 

Industria  y  Energía  de  la  Delegación  Provincial  de  Albacete  Autorización 

Administrativa  Previa,  la  Autorización  Administrativa  de  Construcción  y 

Declaración  de Utilidad  Pública  de  las  instalaciones  del  “Parque  Eólico  Barrax 

Norte‐Sur  de  40MW  y  su  infraestructura  de  evacuación  (Subestación  Barrax 

Norte‐Sur  30/132  kV  y  línea  de  evacuación  de  132  kV)”,  contenidas  en  este 

documento. 

 

La tramitación del presente Modificado de Proyecto se realizará, por tanto, bajo 

la normativa establecida en el Decreto 34/2017, de 2 de mayo, por el que  se 

modifica  el  Decreto  80/2007,  de  19  de  junio,  por  el  que  se  regulan  los 

procedimientos de autorización de  instalaciones de energía eléctrica a tramitar 

por  la  Junta de Comunidades de Castilla‐La Mancha y su régimen de revisión e 

inspección y por el que se deroga el Decreto 20/2010, de 20 de abril , por el que 

se regulaba el aprovechamiento de la energía eólica en la Comunidad Autónoma 

de Castilla‐La Mancha. 

 

Page 8: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 3 de 34 

3 PETICIONARIO 

Es peticionario de  la presente propuesta y  tiene domicilio a efectos de envío de 

correspondencia relacionada con este Proyecto: 

 

Titular:   ENERGIA EÓLICA NOMADA S.L.U. 

Cif:     B‐98350325   

Dirección:  c/Embajador Vich nº3‐3Q,  

46002 Valencia 

 

 

4 JUSTIFICACIÓN DEL MODIFICADO DE PROYECTO  

La sociedad ENERGÍA EÓLICA NÓMADA S.L.U. ha determinado la existencia de un 

potencial eólico aprovechable al Oeste de  la población de Barrax, Provincia de 

Albacete, Castilla La Mancha. 

 

La línea de evacuación es necesaria para el transporte de la energía eólica hasta 

el punto de conexión, en la Subestación Romica. 

 

El tramo subterráneo de la línea se construye en sustitución un tramo aéreo de 

la citada línea subterránea. 

 

 

5 DESCRIPCIÓN DE LAS INSTALACIONES 

Las  instalaciones eléctricas necesarias para  la correcta  instalación y explotación 

del Parque Eólico BARRAX NORTE‐SUR de 40MW, son las siguientes: 

 

16  aerogeneradores  de  2,5MW  y  sus  centros  de  transformación 

interiores 0,69/30kV. 

3 líneas de interconexión de 30kV de 38.033 metros de longitud total.  

Red de tierras interior del parque  

Page 9: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 4 de 34 

Subestación Transformadora 30/132kV 

Línea de evacuación 132kV  

Red de Fibra óptica  interior del parque (construcción subterránea) y de 

comunicaciones. 

Torre de medición de recurso eólico de hasta 129 m de altura 

 

En cuanto a la obra civil necesaria, esta se agrupa en los siguientes trabajos: 

 

Viales de acceso e interiores hasta cada posición de aerogenerador 

Zanjas paras las líneas de interconexión del parque 

Plataformas y cimentación para los 16 aerogeneradores proyectados 

Adecuación de  la parcela para  la construcción de  la Subestación Barrax 

Norte‐Sur 30/132 kV 

Excavación y hormigonado de los apoyos de la línea de evacuación 

Zanja para el tramo subterráneo de la línea de evacuación  

 

De  las  citadas  instalaciones,  aquellas  objeto  del  Modificado  del  Proyecto 

Constructivo,  son  el  tramo  aéreo  de  la  línea  eléctrica  de  evacuación  132  kV, 

comprendido entre los apoyos nº20 y nº30, que pasarán a ser subterráneas y el 

vano aéreo entre los apoyos nº30 – nº31 que se verá acortado. 

 

 

6 JUSTIFICACIÓN DE LA URGENTE OCUPACIÓN 

Para el establecimiento de  la Servidumbre sobre  las fincas con cuyos propietarios 

no  se  ha  podido  alcanzar  un  mutuo  acuerdo,  será  necesario  recurrir  a  un 

expediente de expropiación. 

 

A tenor de lo establecido en el artículo 54.1 de la Ley 24/2013, de 26 de diciembre, 

del Sector Eléctrico, se declaran de Utilidad Pública las instalaciones de generación, 

transporte y distribución de energía eléctrica, a los efectos de expropiación forzosa 

de  los bienes y derechos necesarios para su establecimiento, y de  la  imposición y 

ejercicio de la servidumbre de paso. 

Page 10: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 5 de 34 

El artículo 56.1 del mismo texto legal, añade que la declaración de Utilidad Pública 

llevará  implícita  en  todo  caso,  la  necesidad  de  ocupación  de  los  bienes  o  de 

adquisición  de  los  derechos  afectados,  e  implicará  la  urgente  ocupación  a  los 

efectos del artículo 52 de la Ley de Expropiación Forzosa. 

 

En  el  presente Modificado  de  Proyecto,  la  "causa  expropiandi",  o  lo  que  es  lo 

mismo,  la  necesidad  de  la  ocupación  de  las  fincas  incluidas  en  el  expediente 

expropiatorio asociado al mismo, viene dada por la necesidad de evacuar la energía 

generada  por  el  Parque  Eólico  Barrax  Norte‐Sur  de  40MW  hasta  el  punto  de 

conexión otorgado.  

 

Todas las infraestructuras proyectadas responde al propósito del autor del mismo, 

de  ocasionar  los menores  perjuicios  posibles  a  los  propietarios  afectados,  cuyo 

número  se ha procurado que  sea  también el menor posible,  tratando  al mismo 

tiempo  de  armonizar  los  intereses  de  todos  ellos,  con  los  condicionantes 

orográficos,  medioambientales,  técnicos  y  reglamentarios,  que  siempre  están 

presentes en la elaboración de cualquier Proyecto de estas características. 

 

El  mencionado  expediente  expropiatorio  deberá  de  tramitarse  por  la  vía  de 

urgencia, toda vez que así lo exige la necesidad de evacuar la energía generada por 

la infraestructura eólica indicada. 

 

Se  tratará  además,  de  minimizar  los  perjuicios  que  puedan  ocasionarse  a  los 

propietarios  afectados,  como  consecuencia  de  que  el  expediente  vaya  a  ser 

tramitado  por  la  vía  de  urgencia,  ofreciéndoles  el  pago  de  indemnizaciones 

compensatorias,  calculadas  conforme  a  los  criterios  que  tradicionalmente  viene 

utilizando  el  Jurado  Provincial  de  Expropiación  para  el  establecimiento  del 

justiprecio, las cuáles se abonarán de forma inmediata a los titulares de las fincas, 

incluso en el caso de que estén en desacuerdo con la valoración realizada por esta 

Entidad Beneficiaria, siempre que autoricen la ocupación, y acepten recibirlas como 

cantidad  concurrente,  y  a  cuenta  de  la  indemnización  que  finalmente  pueda 

corresponderles o,  incluso en el caso de que no quieran recibirlas, se consignarán 

en  la  Caja  General  de  Depósitos,  dependiente  del  Ministerio  de  Economía  y 

Page 11: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 6 de 34 

Hacienda; cantidades éstas, es de destacar, que sobrepasan de manera importante 

las  cuantías mínimas  establecidas  legalmente  para  la  constitución  del  depósito 

previo a la ocupación. 

 

 

7 EMPLAZAMIENTO DE LAS INSTALACIONES 

Se  indica  a  continuación  la  ubicación  de  las  instalaciones  objeto  el  presente 

Modificado  de  proyecto,  el  resto  de  instalaciones  no  se  ven  afectadas  por  el 

cambio y por tanto no modifican su ubicación. 

 

El tramo a soterrar de la línea de evacuación del Parque Eólico BARRAX NORTE‐

SUR DE 40MW se sitúa al Este de  la población de Barrax Término Municipal de 

Barrax, entre los apoyos nº 20 y nº 30, en su paralelismo con la carretera AB‐701, 

entre los pks 4+671 y 7+178, de la citada carretera. 

 

El  nuevo  tramo  subterráneo  de  la  línea  eléctrica  afecta  a  los  Términos 

Municipales  de  Barrax  y  Albacete,  según  se  observa  en  el  plano  PG‐01 

LOCALIZACIÓN  Y  EMPLAZAMIENTO  y  PG‐02  PLANTA  GENERAL  DE 

INSTALACIONES. 

 

Page 12: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 7 de 34 

 

 

 

 

 

 

 

 

LÍNEA ELÉCTRICA DE EVACUACIÓN 132 KV. 

 

 

Page 13: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 8 de 34 

La  línea de evacuación del parque eólico BARRAX NORTE‐SUR DE 40MW,  será 

una  línea eléctrica de 132kV de  tensión nominal,  simple  circuito,  simplex,  con 

origen en la Subestación Barrax Norte‐Sur 30/132kV del Parque Eólico y final en 

la subestación Romica propiedad de Iberdrola donde el parque tiene concedido 

el punto de conexión.  

 

Con el soterramiento del tramo de línea comprendido entre los apoyos 20 y 30, 

objeto del Modificado de Proyecto la línea de evacuación quedará formada por 4 

tramos claramente diferenciados, estructurados de la siguiente manera: 

 

Tramo 1: aéreo, del origen en la Subestación Barrax Norte‐Sur 30/132 kV del 

Parque Eólico hasta el apoyo nº 20, con una longitud de: 4.284 metros. 

Tramo 2: subterráneo de 2.720 metros, entre los apoyos nº 20 y nº 30. 

Tramo 3: aéreo, del apoyo nº 30 hasta el apoyo nº 142, con una longitud total 

de 31.508 metros. 

Tramo 4: subterráneo de 375 metros entre el apoyo nº 142 y hasta la posición 

prevista en la Subestación Romica, propiedad de Iberdrola donde el parque tiene 

concedido el punto de conexión 

 

 

8 LÍNEA ELÉCTRICA DE EVACUACIÓN 132 KV. TRAMO SUBTERRÁNEO 

8.1 DESCRIPCIÓN DEL TRAZADO 

 

El tramo a soterrar de la línea de evacuación del Parque Eólico BARRAX NORTE‐

SUR DE 40MW objeto del Modificado del Proyecto Constructivo, se sitúa al Este 

de la población de Barrax Término Municipal de Barrax, entre los apoyos nº 20 y 

nº 30, en su paralelismo con la carretera AB‐701, entre los pks 4+671 y 7+178, de 

la citada carretera. 

Page 14: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 9 de 34 

El apoyo nº 20 mantiene su ubicación, retranqueándose 3 metros, ajustando  la 

posición  a  sus  nuevas  dimensiones  de  final  de  línea  y  conversión  aéreo 

subterráneo,  para  evitar  afectar  el  dominio  público  de  la  Cañada  Real  de  La 

Mancha Murcia, que hace las veces de límite municipal entre Barrax y Albacete y 

que cruzará en subterráneo. Desde el apoyo nº 20, la línea subterránea se dirige 

casi perpendicularmente hacia  la  carretera AB‐701, para  colocarse a más de 8 

metros  de  la  arista  exterior  de  su  explanación,  cruzar  bajo  la  Cañada  Real  y 

establecer un paralelismo con ella hasta que  la cruza, mediante una hinca a  la 

altura  del  pk  5,478  de  la  carretera  provincial,  ya  en  el  Término Municipal  de 

Albacete. 

 

Desde ese pk, el paralelismo continuará por el margen contrario de la carretera, 

siempre  a más  de  8 metros  de  la  arista  exterior  de  su  explanación,  según  se 

muestra en los planos adjuntos LSAT‐02 y LSAT‐03. 

 

El nuevo tramo subterráneo de la línea finaliza en el apoyo nº 30, de conversión 

aéreo subterráneo, después de circunvalar Blancares Viejos por el norte y cruzar 

bajo  dos  líneas  aéreas  de  media  tensión  de  Iberdrola  y  bajo  el  gasoducto 

ALCAZAR DE  SAN  JUAN‐MONTESA  dependiente  de  ENAGAS  a  la  altura  del  pk 

112H4R. 

 

El apoyo nº 30 se tranqueará hacia el este, acortando sensiblemente el vano 30‐

31 y variando ligeramente el cruzamiento con la carretera AB‐701 al pk 7+272.  

 

Los  armados  de  los  nuevos  apoyos  final  de  línea,  han  sido  previstos  para  la 

instalación  de  tres  conversiones  aéreo‐subterráneas  (una  por  fase),  según  se 

refleja en el detalle incluido en el plano adjunto LSAT‐11.  

 

La longitud total de la línea subterránea simple circuito será de 2.720 metros, de 

los cuales 162 metros se ubican en el Término Municipal de Barrax. 

 

Page 15: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 10 de 34 

El tramo subterráneo discurrirá por canalización de nueva construcción prevista 

con  un  tubo más  de  reserva  de  2.674 metros  de  longitud,  de  los  cuales  139 

metros se ubican en el Término Municipal de Barrax. 

 

8.2 CARACTERÍSTICAS ELÉCTRICAS 

 

Las características eléctricas de la línea subterránea de acuerdo con ITC‐LAT 06 y 

las normas UNE‐211435 y UNE‐EN 60071‐1, son las siguientes: 

 

Clase de corriente  Alterna trifásica 

Frecuencia  50 Hz 

Tensión nominal (Un)  132 kV 

Tensión más elevada para el material (Um)  145 kV 

Categoría de la red  A Según UNE 20‐435 A 

Tensiones asignadas (Uo/U)  76/132 kV 

Tensión soportada (Up)  650 kVcr. 

Tensión soportada (U)  190 kVef. 

Distancia mínima de aislamiento 

  Fase‐Tierra/Fase‐Fase  1.300 mm. 

 

Siendo: 

 

Uo:  Tensión asignada eficaz a frecuencia industrial entre cada conductor 

y  la  pantalla  del  cable,  para  la  que  se  ha  diseñado  el  cable  y  sus 

accesorios. 

U:  Tensión asignada eficaz a frecuencia industrial entre dos conductores 

cualquiera, para la que se ha diseñado el cable y sus accesorios. 

Up:  Valor  de  cresta  a  impulsos  tipo  rayo  aplicada  entre  conductor  y 

pantalla. 

 

Page 16: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 11 de 34 

8.3 CABLES DE FUERZA 

Los  materiales  y  su  montaje  cumplirán  con  la  ITC‐LAT  06  y  los  requisitos  y 

ensayos de las nomas ENE aplicables incluidas en la ITC‐LAT 02, así como demás 

normas y especificaciones aplicables UNE, EN (HD) o en su defecto CEI. 

 

Las características esenciales para el cable de 132 kV son:  

Tipo: Unipolar.  

Conductor: Aluminio compacto, sección circular, clase 2 UNE 21‐022  

Semiconductora  interna:  Capa  de  mezcla  semiconductora  aplicada,  por 

extrusión, sobre el conductor. 

Aislamiento: Polietileno reticulado (XLPE).  

Semiconductora externa: Una capa de mezcla semiconductora no metálica 

y pelable en caliente, aplicada, por extrusión, sobre el aislamiento. 

Pantalla: Constituida por una corona de alambre de Cu dispuesto en hélice 

a paso largo y una contraespira ( un fleje de Cu) adherida a la cubierta. 

Capa metálica de estanqueidad. 

Cubierta: Compuesto  termoplástico a base de poliolefina y  sin contenido 

de componentes clorados u otros contaminantes.  

 

Tendrá  la  resistencia mecánica  suficiente  para  las  acciones  de  la  instalación  y 

tendido con  la devanadora, máquina de  tendido  freno, máquinas auxiliares de 

apoyo al tendido en las calas, etc., y las habituales después de la instalación. 

 

El cable elegido para este soterramiento, que pretende mantener  la capacidad 

de transporte de la línea aérea a soterrar, permitirá unas intensidades máximas 

admisibles  semejantes,  en  servicio  permanente.  Para  ello  las  temperaturas  a 

alcanzar serán soportadas sin alteraciones en sus propiedades. 

 

En  el  cálculo  de  dicho parámetro  se  han  tenido  en  cuenta  las  condiciones  de 

instalación (enterrado/entubado y hormigonado), disposición de los conductores 

Page 17: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 12 de 34 

(tresbolillo  lo más  próximos)  y  el  sistema  de  conexión  de  las  pantallas  de  los 

cables (Cross Bonding). 

 

Instalación          Enterrada/Entubada. 

Temperatura ambiente        40ºC. 

Temperatura del terreno      25ºC. 

Resistividad térmica del terreno     1,5 K m/w. 

Instalación           1 terna. 

Colocación          Tresbolillo en contacto. 

Tubos            200 mm>1,5 Ø del cable 

Profundidad de instalación      según planos. 

Conexión de pantallas        Cross Bonding. 

 

Dado que  los  cables del  soterramiento pertenecen  a una evacuación,  tendrán 

por  tanto,  el  ciclo  de  carga  de  una  generación  eólica,  lo  cual  implica  que  las 

intensidades máximas admisibles  serán  superiores a  las correspondientes a un 

servicio permanente. 

 

8.3.1 CABLE DE POTENCIA 

El cable seleccionadopara el presente soterramiento es: 

 

RHZ1‐RA‐2OL 76/132 kV (1x800Al + H205) unipolar 

 

Cuyas características son las siguientes: 

 

 

CARACTERÍSTICAS IEC 60840 

UNIDADES  DENOMINACIÓN 

TIPO DE CABLE    RHZ1‐RA+20L 

NORMA     IEC 60840 

TENSIÓN NOMINAL  kV  76/132 

Page 18: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 13 de 34 

Nº CONDUCTORES POR SECCIÓN    1x800 mm2 

MATERIAL CONDUCTOR     Al 

Forma     Circular 

Clase / Norma    2/CEI 60228 

Diámetro Nominal  mm2   34 

Conductor obturado    SI 

Cinta semiconductora obturante sobre conductor  

  SI 

MATERIAL  PANTALLA  SOBRE 

CODUCTOR 

  Capa semiconductora extruída 

Espesor nominal   mm  1,6  

MATERIAL AISLAMIENTO    XLPE 

Espesor nominal / mínimo en cualquier 

punto 

mm  14,6/‐‐ 

Diámetro sobre aislamiento  mm  67,8 

MATERIAL PANTALLA SOBRE AISLAMIENTO (NO METÁLICO) 

  Capa semiconductora extruída 

Espesor nominal   mm   1,4 

Cinta  semiconductora  obturante  bajo 

pantalla metálica 

   

MATERIAL PANTALLA SOBRE AISLAMIENTO (PARTE METÁLICA) 

  Hilos de Cu 

Formación de la pantalla  N x mm  59x2,12 

Sección de la pantalla (hilos de Cu)  mm2  205 

Pantalla obturada (hilo obturante)    NO 

Cinta obturante sobre pantalla metálica    SI 

Cinta metal / copolímero.    SI 

Sección nominal  total  (hilos Cu +  cinta 

metal/copolímero) 

mm2  235 

MATERIAL CUBIERTA    HDPE 

Espesor nominal / mínimo en cualquier 

punto 

mm  3,5/‐‐ 

DIÁMETRO NOMINAL EXTERIOR  mm  85,1 

PESO NOMINAL  Kg/km  8465 

RADIO MÍNIMO DE CURVATURA  mm  1205 

DATOS ELÉCTRICOS  Ohm/km  0,0367 

Page 19: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 14 de 34 

Resistencia máxima CC del conductor a 

20 ºC. 

Ohm/km  0,117 

Reactancia estrella, a 50 Hz  μF/km  0,227 

Corriente de carga por fase, a Uo, 50 Hz  A/km  5,411 

Temp. Máx. conductor en régimen permanente / en cortocircuito 

ºC  90/250 

Intensidad máxima admisible en cortocircuito adiabático (0,1/ 0,5/ 1.0 s) 

kA  239/107/75,6 

 

8.4 EMPALMES  

Los empalmes seleccionados para el presente soterramiento son los preparados 

para  el  cruzamiento  de  pantallas  (cross  bonding).  Serán  premoldeados 

adecuados  a  la  naturaleza,  composición  y  sección  de  los  cables.  No  deberán 

aumentar la resistencia eléctrica de estos. 

 

Los  empalmes  se  instalarán  dentro  de  las  cámaras  construidas  al  efecto.  Se 

adjunta plano de detalle. 

 

8.5 TERMINALES 

Serán de exterior, sobre apoyo para conectar a línea aérea. Serán premoldeados 

adecuados  a  la  naturaleza,  composición  y  sección  de  los  cables.  No  deberán 

aumentar  la  resistencia  eléctrica  de  estos  y  con  línea  de  fuga  similar  a  las 

autoválvulas. 

 

En  la  figura  adjunta  se  representa,  con  carácter  general,  la  constitución  y 

estructura  de  un  terminal  con  aislador  de  porcelana  o  polimérico,  con  cono 

deflector premoldeado y relleno con fluido aislante. 

 

 

 

Page 20: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 15 de 34 

 

 

 

 

 

Los  terminales  se  instalarán  en  los  extremos  de  los  cables  para  garantizar  la 

unión eléctrica con otras partes de una red y mantener el aislamiento hasta el 

punto de conexión. 

 

Para  la  instalación  correspondiente  al Modificado  al  Proyecto,  se  opta  por  la 

utilización de Terminales de exterior de composite.  

 

Características básicas: 

 

Tensión máxima entre fases Um (kV.)  145 

Nivel básico de aislamiento al impulso tipo rayo (kV.)  650 

Altura aproximada (mm).  2.150 

 

Los terminales de exterior se  instalarán en  las crucetas rectangulares  instaladas 

para ello en los apoyos nº 20 y nº 30, ambos final de línea, en los que se realizará 

una triple conversión aéreo subterráneo, se montarán tres terminales: uno por 

fase.  

 

La  subida  de  los  conductores  a  los  Terminales  se  efectuará  protegiendo  los 

cables desde la base de la torre hasta al menos 3 metros de altura. 

Figura: Constitución y 

estructura de un terminal con 

aislador. 

Page 21: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 16 de 34 

8.6 PARARRAYOS 

Entre el  tramo aéreo y el  subterráneo  se  intercalarán pararrayos/autoválvulas. 

Se instalarán un elemento en cada uno de los extremos de los cables unipolares. 

Estarán constituidos por óxido de cinc como elemento activo. Cada autoválvula 

poseerá  un  cable  de  puesta  a  tierra  independiente,  en  el  que  se  instalará  un 

contador de descargas. 

 

No se realizará la conexión a tierra a través de la estructura del apoyo.  

 

Dichas  autoválvulas,  que  serán  de  óxido  de  zinc,  como  ya  se  ha  dicho,  con 

recubrimiento exterior de polímero, se instalarán sobre soporte metálico aislado 

independiente,  sobre  la  cruceta  de  la  columna  próxima  al  terminal  del  cable 

aislado a proteger. Serán con limitador de presión que impida la rotura violenta 

de  la  envuelta,  provocada  por  un  posible  defecto  interno  eléctrico  del 

pararrayos, y que provoque daños en elementos del terminal a proteger. 

 

Las características principales de las autoválvulas serán las siguientes: 

 

 

 

 

 

 

 

 

 

 

 

Page 22: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 17 de 34 

Servicio .......................................................................................................... exterior. 

Tensión de servicio nominal asignada (Un) ................................................. 132 kVef. 

Tensión de aislamiento nominal (Um) .......................................................... 145 kVef. 

Tensión asignada nominal (Ur) ................................................................. 120 kV rms. 

Tensión de servicio continuo IEC (Uc) .......................................................... 92 kVrms. 

Frecuencia ........................................................................................................ 50 Hz. 

Longitud línea de fuga (25 mm/kV) .......................................................... 3.625 mm. 

Intensidad de descarga (8/20 µs) (In) ............................................................ 10 kAcr. 

Corriente de prueba del limitador de presión 0,2 seg .................................. 31,5 kA. 

Clase de descarga de línea ..................................................................................... 3. 

Condiciones de funcionamiento .......................................................... ‐50ºC/+45 ºC. 

Tensión máxima de operación continua ANSI/IEEE (UMCOV) .......................... 98 kVef. 

Tensión residual (10 kA con onda 8/20 µs)) ............................................... 282 kV cr. 

Clase 3. 

Tecnología .......................................................................................................... OZn. 

Envolvente ............................................................................................... polimérica. 

Momento flector mínimo .......................................................................... 6.000 Nm. 

Tratamiento del neutro de la red ....................................................... rígido a tierra. 

Designación ...................................................................................... POM‐C 132/10. 

Denominación comercial ......................................................... PEXLIM Q120‐XH145. 

Placa de características .......................................................................................... si. 

Tensión soportada a impulso tipo rayo1,2/50 µs ........................................ 650 kVcr. 

Tensión soportada a frecuencia industrial .................................................. 275 kVef. 

Base aislante ........................................................................................................... si. 

Contador de descargas ........................................................... si (mismo fabricante). 

Terminales  ..................................................................................... tipo 1HSA410‐M. 

Terminal de tierra  ........................................................................... tipo 1HSA420‐B. 

 

Se ha elegido en principio el modelo PEXLIM Q120‐XH145 de ABB o similar. 

 

Page 23: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 18 de 34 

8.7 CABLE DE FIBRA ÓPTICA 

Para dar continuidad a la red de telecomunicación prevista con el cable de fibra 

óptica aéreo OPWG, en el tramo subterráneo de la línea se incorpora un cable de 

fibra  óptica  tipo  PVT,  ambos  con  el mismo  número  de  fibras.  El  empalme  de 

ambos tipos de fibra óptica se realizará en cajas de empalme previstas para tal 

propósito. 

 

El cable de fibra óptica que se contemplaba en el presente Proyecto, y que es el 

mismo  que  se  incluye  en  el  Modificado,  es  tipo  PVT,  y  está  especialmente 

diseñado para su tendido por zanja canalizada. Se trata de un cable totalmente 

dieléctrico, estanco, de fibras ópticas monomodo. 

 

Estos son cables no metálicos reforzados con material sintético. Compuesto por 

un núcleo central, como elemento resistente, formado por un cordón de fibra de 

vidrio compactada con resina. Alrededor del cordón van cableados  los tubos de 

poliéster conteniendo las fibras ópticas en posición holgada y con compuesto de 

relleno antihumedad en su interior. El núcleo va protegido de un compuesto de 

relleno de antihumedad que ocupará todos  los  intersticios del núcleo del cable. 

Sobre  el  núcleo  óptico  se  colocará  una  cubierta  interior  de  polietileno.  Sobre 

esta  y  helicoidalmente  llevará  un  número  adecuado  de  hilaturas  de  vidrio 

antiroedores  que  proporciona  la  suficiente  protección  y  resistencia mecánica 

especificada,  con  el  fin  de  que  se  mantenga  un  mínimo  de  resistencia  a  la 

tracción  y  compresión  suficientes  para  no  verse  afectado  por  las  acciones  de 

tendido  y  aplastamiento  en  las  condiciones  de  servicio,  lo  que  se  ratificará  al 

someterse a los ensayos correspondientes. Esta capa también se protege contra 

el  agua  al  ir  taponada  con  gel  antihumedad.  Finalmente,  la  cubierta 

termoplástica de polietileno recubre todo el cable. 

 

Para comprender mejor la fisonomía de los cables aquí mencionados, en la figura 

adjunta se reseñan las secciones transversales y longitudinales, según los casos, 

como también sus elementos componentes. 

 

 

Page 24: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 19 de 34 

 

 

 

 

 

 

 

Características: 

 

Características:  PVT 48 fibras 

Número de Fibras  48 

Número de fibras por tubo  12 

Nº tubos  4 

Diámetro externo del tubo (mm)  2,5 

Espesor radial de cubierta interior/exterior  1,0/1,5 

Diámetro del cable (mm)  14,1 

Peso del cable (daN/Km)  147 

Resistencia a la tracción (daN)  270 

Radio de curvatura (mm)  20 ø cable 

Margen de temperatura  ‐20ºC  +70ºC 

Estanqueidad  3m cable, 1 m agua 24h 

 

8.8 PUESTA A TIERRA 

Se dispondrá de una  línea de tierra propia a través de un cable de unipolar de 

puesta a tierra aislado hasta la malla de tierra en la base del apoyo y cámaras de 

empalme,  formada  tres  cuadrados  separados  1 metro  cada  uno  y  8  picas  de 

puesta  a  tierra.  De  esta  forma  se  minimiza  la  impedancia  para  el  caso  de 

PVT 

Page 25: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 20 de 34 

descarga de  intensidades. Se  comprobará  la existencia de  tensiones de paso y 

contacto, antes de la puesta en tensión de la instalación. 

 

8.9 CANALIZACIONES 

En el Modificado al Proyecto los cables aislados de Alta Tensión de instalarán en 

tres  tubos  (un  cable  por  tubo)  hormigonados,  en  triangulo  de  forma  que 

permitan  una  disposición  al  tresbolillo,  con  los  conductores  lo más  próximos 

posibles.  

 

En  estas  canalizaciones  el  cable  irá  entubado  en  todo  de  su  trazado  y  se  ha 

proyectado teniendo en cuenta las siguientes consideraciones:  

 

El radio de curvatura después de colocado el cable, posición definitiva, será 

como  mínimo  de  15  veces  el  diámetro  del  cable.  Para  los  cables 

seleccionados los radios de curvatura serán: 1,5 m para la línea de 132 kV. 

Los radios de curvatura en operaciones de tendido serán como mínimo el 

doble de las indicadas en el punto anterior, para su posición definitiva.  

Los cruces de calzadas serán perpendiculares al eje de la calzada o vial en 

forma  de  HINCA,  procurando  evitarlos,  si  es  posible  sin  perjuicio  del 

estudio económico de la instalación en proyecto, y si el terreno lo permite.  

Deberán  cumplir  las  especificaciones  de  los  diferentes  Organismos 

Gestores.  

Estarán  constituidas por  tubos  termoplásticos, hormigonados en  toda  su 

longitud  y debidamente  enterrados  en  zanja.  El diámetro  interior de  los 

tubos,  de  acuerdo  con  las  instrucciones  de montaje D  tubo  >  1,7 D  del 

cable,  será  de  200 mm  para  la  línea  de  132  kV,  y  160 mm  polietileno 

reticulado para el cable de comunicaciones. 

En cada uno de los tubos se instalará un cable, correspondiente a una sola 

fase. Se evitará en lo posible los cambios de dirección de los tubos. En los 

puntos  donde  estos  se  produzcan  se  dispondrán,  para  facilitar  la 

manipulación, calas de tiro.  

Page 26: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 21 de 34 

Las canalizaciones entubadas deberán quedar debidamente selladas en sus 

extremos.  

Los tubos irán colocados en triángulo. 

La  profundidad  de  la  zanja  será  la  suficiente  para  que  el  tubo  superior 

quede  a  una  profundidad mayor  de  1 m  en  la  línea  de  132  kV,  tomada 

desde  la  rasante  del  terreno  a  la  parte  inferior  del  tubo  superior.  Se 

adjunta plano de detalle. 

Se instalará un tubo adicional de 160 mm∅, como conducto para cables de 

control,  red  multimedia.  En  los  planos  del  Anexo  de  Planos,  se  da  la 

disposición de tubos y valores de las dimensiones de la zanja.  

En el  fondo de  la  zanja y en  toda  la extensión  se colocará una  solera de 

limpieza  de  0,05  m  de  espesor  de  hormigón  HM  20,  sobre  la  que  se 

depositarán  los tubos. A continuación, se colocará otra capa de hormigón 

HM  20 dispuesto  en  tongadas  y  vibrado,  con un  espesor de  0,10 m por 

encima  de  los  tubos  y  envolviéndolos  completamente  (esta  capa  de 

hormigón hace la función de inmovilización de los tubos y para soportar los 

esfuerzos  de  dilatación‐contracción  térmica  o  incluso  esfuerzos  de 

cortocircuito en los cables).  

Seguidamente se  rellenará  la zanja, dejando  libre el espesor del  firme de 

hormigón, asfalto o del pavimento, con tierra procedente de la excavación, 

o todo‐uno normal, según el terreno por donde discurra  la  instalación en 

capas compactadas de 0,20 m a PM 95%. 

Dentro de esta capa de  relleno y a una profundidad de 0,55 m, desde el 

firme,  se  tenderán  las  cintas  plásticas,  una  por  circuito,  indicativas  de 

presencia de cables eléctricos de alta tensión. 

Reposición del terreno (de 10 a 30 cm, aproximadamente), puesto que  la 

canalización discurre por tramos de campo abierto con rasantes definidas, 

el acabado superficial se realizará mediante una capa de tierra. Si cruzara 

carreteras  o  caminos  o  acera  se  realizaría  con  hormigón  HM20  y  la 

reposición del pavimento asfalto, baldosa etc. será de la misma naturaleza 

que  la del entorno. Cuando se precise mayor resistencia a  la compresión, 

se  incorporará a  la capa de hormigón un mallazo de acero, dimensionado 

de acuerdo con las necesidades.  

Page 27: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 22 de 34 

Después  se  repondrá el pavimento, del mismo  tipo  y  calidad que existía 

antes de realizar la apertura.  

Para  cruzar  zonas  en  las  que  no  sea  posible  o  suponga  graves 

inconvenientes  y  dificultades  la  apertura  de  zanjas  (carreteras  con  gran 

densidad  de  circulación,  etc.),  pueden  utilizarse máquinas  perforadoras 

"topos" de tipo  impacto, hincadora de tuberías o taladradora de barrena; 

en estos casos se prescindirá del diseño de zanja descrito anteriormente, 

puesto  que  se  utilizará  el  proceso  de  perforación  que  se  considere más 

adecuado. Su  instalación precisa zonas amplias despejadas a ambos  lados 

del obstáculo a atravesar para la ubicación de la maquinaria, por lo que no 

debemos considerar este método como aplicable de forma habitual, dada 

su complejidad. Este método de cruzamiento, concretamente el tipo hinca, 

será el utilizado para cruzar la carretera AB‐701 

 

8.10 PUESTA A TIERRA DE LAS PANTALLAS 

Para  reducir y/o eliminar pérdidas de potencia en el  transporte,  se emplea un 

procedimiento especial de instalación, que anula las pérdidas en las pantallas. De 

los  procedimientos  existentes  para  esta  reducción  de  pérdidas  hemos 

seleccionado  este  debido  únicamente  a  la  longitud  de  la  línea  a  tender,  y  la 

posibilidad de longitud de las bobinas (tema absolutamente logístico).  

 

El  procedimiento  por  emplear  será  el  CROSS  BONDING.  Las  pantallas  van 

conectadas a tierra en los dos extremos de la línea. Este procedimiento consiste 

en  dividir  la  línea  en  3  o múltiplo  de  3  tramos  iguales.  Los  cables  que  van  al 

tresbolillo,  no  hacen  la  transposición  de  los  mismos,  pero  sí  de  pantallas, 

realizando  únicamente  la  interconexión  de  las  pantallas mediante  empalmes 

seccionados. Se elimina  la circulación de corriente por  las pantallas en régimen 

permanente, pero generan sobretensiones en los empalmes y cajas de conexión. 

 

En  la  siguiente  figura  se muestra  esquema  de  conexión  con  el  sistema  Cross‐

Bonding formado por cuatro secciones mayores:  

 

Page 28: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 23 de 34 

 

En  la  siguiente  figura  se muestra  esquema  de  conexión  con  el  sistema  Cross‐

Bonding  formado  por  una  sola  sección  mayor,  es  el  caso  del  presente 

Modificado:  

 

 

 

Para  la  transposición  de  pantallas,  los  enlaces  entre  las  pantallas  y  los 

limitadores de sobretensión serán, como máximo, de 3m y deben realizarse con 

cables coaxiales en un 80%, como mínimo, de su longitud.  

 

Con esto lo que se consigue es que la tensión total inducida cada 3 tramos sea 0, 

y por tanto la corriente que circula por las pantallas sea 0.  

 

Page 29: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 24 de 34 

La  transposición  de  pantallas  se  realiza mediante  empalmes  seccionados  y  tal 

como se reseña en la siguiente figura.  

 

La puesta a tierra de  las pantallas se realiza a través de cables concéntricos, tal 

como se indica en la siguiente figura.  

 

 

 

 

 

9 LÍNEA ELÉCTRICA DE EVACUACIÓN 132 KV. TRAMO AÉREO 

 

El tramo aéreo de la línea de evacuación del parque eólico BARRAX NORTE‐SUR 

DE 40MW,  será una  línea aérea de 132kV de  tensión nominal,  simple circuito, 

simplex, con una longitud total de 35.792  metros. Divida en dos tramos de 4.284 

metros  y  31.508 metros,  separados  por  el  tramo  subterráneo  descrito  en  el 

apartado anterior. 

 

Page 30: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 25 de 34 

9.1 UBICACIÓN APOYOS Nº 20 Y 30 

 

Se  modifica  la  posición  de  los  apoyos  nº  20  y  nº  30  según  se  indica  a 

continuación. 

 

El  apoyo  nº  20  se  retranquea  3  metros,  ajustando  la  posición  a  sus 

nuevas  dimensiones  de  final  de  línea  y  conversión  aéreo  subterráneo, 

para evitar afectar el dominio público de  la Cañada Real de La Mancha 

Murcia. 

El apoyo nº 30 se  tranqueará hacia el este, acortando sensiblemente el 

vano  30‐31  y  variando  ligeramente  el  cruzamiento  con  la  carretera                   

AB‐701 al pk 7+272 

 

Los apoyos se ubicarán en las coordenadas UTM, X e Y, indicadas a continuación. 

La  coordenada  Z  corresponde  con  la  cota  topográfica  del  terreno  donde  se 

asienta el apoyo. 

 

Nº APOYO  X  Y  Z 

20  573.805,22  4.324.224,32  705,22 

30  576.024,51  4.325.294,44  696,80 

 

9.2 CARACTERÍSTICAS GENERALES DE LA INSTALACIÓN 

 

Las principales características de la Línea a realizar, que NO HA VARIADO frente 

al  proyecto  original,  únicamente  la  longitud  de  la  línea  aérea  total,  son  las 

siguientes: 

 

Longitud  35.792   metros  (después  del 

soterramiento) 

Tensión nominal  132 kV 

Tensión más elevada para el material  145 kV 

Categoría  1ª 

Page 31: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 26 de 34 

Altitud  entre 500 y 1.000 m (Zona B)  

Nº de Circuitos  Uno trifásico. 

Nº de conductores por fase  Uno (simplex) 

Disposición conductores  Tresbolillo con cúpula  

Tipo de conductor    Aluminio–Acero, tipo 242‐AL1/39‐ST1A  

(LA–280 HAWK) 

Aislamiento  Cadenas horizontales y verticales de aisladores formadas 

por  simple  columna  de  11  elementos  de  vidrio  tipo  E100/127  (VICASA) 

(U100 BS). Con contrapesos de bucle en los ángulos mas fuertes 

Apoyos  Metálicos  de  celosía  galvanizada,  basados  en  la  serie  Haya 

(monobloque), Arce y Drago (tetrabloque) del fabricante Made (o similar).  

Cimentaciones  Monobloques  (Cálculo  a  ángulo  de  giro)  y  tetrabloques 

de patas separadas (Calculo a arrancamiento con ángulo de fricción) 

Protección contra sobretensiones  OPWG  48  (Cable  de  Tierra  y  Fibra 

Óptica), dispuesto en la cúpula sobre los conductores.  

Tomas de tierra  Tomas  de  tierra  normales  formadas  por  1  ó  2  picas  de 

acero  cobrizado  (2000  mm    18  mm  /  300  micras  de  recubrimiento 

electrolítico), unidas con los montantes del apoyo, a base de cable desnudo 

de cobre de 95 mm2 de sección.  

Antiescalo aislado se  instalará  en  aquellos  apoyos  considerados  como 

frecuentados 

Contaminación ambiental  Baja 

Nivel de niebla  Medio 

Tensión soportada nominal a los impulsos tipo rayo      650 kV 

Tensión soportada de corta duración a frecuencia industrial    275 kV 

 

9.2.1 CONDUCTORES 

No han variado con respecto al proyecto original, se utilizarán conductores del 

tipo 242‐AL1/39‐ST1A (LA–280 HAWK), que cumplirán la norma UNE 21016:1976 

y 21018:198.  Las principales  características de dicho  conductor  se muestran  a 

continuación: 

Page 32: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 27 de 34 

Tipo  242‐AL1/39‐ST1A (LA–280 HAWK) 

Sección total  281,19 mm2 

Sección equivalente en Cu  152 mm2 

Composición  26 hilos de Al + 7 hilos de Acero 

Diámetro  21,80 mm 

Peso  0,977 kg/m 

Carga de rotura  8.620 kg 

Módulo elástico  7.700 kg/mm2 

Coeficiente de dilatación  18,9 mm x 10‐6 ºC‐1 

 

Se  mantiene  la  misma  tracción  máxima  de  los  conductores,  prevista  en  el 

proyecto original. 

 

9.2.2 CABLE DE FIBRA ÓPTICA 

No ha variado con respecto al proyecto original, se ha seleccionado un  cable de 

tierra compuesto por fibra óptica (OPGW),  tipo OPGW 48 (106/62) 26. 

 

9.2.3 APOYOS Y ARMADOS 

Los apoyos a  instalar contemplados en el Modificado de Proyecto  son de  tipo 

Metálico están compuestos por armaduras de celosía con perfiles de alas iguales 

y  los  materiales  constituyentes,  son  piezas  férreas,  protegidas  contra  la 

corrosión mediante galvanización en caliente por inmersión.  

 

Los  armados  de  los  apoyos  serán  metálicos,  compuestos  por  armaduras  de 

celosía  con  perfil  angular  de  alas  iguales.  El material  será  acero  no  aleado  y 

estará  protegido  contra  la  corrosión, mediante  galvanización  en  caliente  por 

inmersión. 

 

Los  apoyos  se  han  calculado  mecánica  y  en  cuanto  a  distancias  entre 

conductores para que sean adecuados para un doble circuito, si bien en principio 

se instalará un armado en tresbolillo. 

Page 33: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 28 de 34 

Los armados de  los apoyos se han seleccionado de manera que se cumplan  las 

distancias  reglamentarias entre  conductores  y  la distancia  reglamentaria entre 

éstos y masa.  

 

Para ello se han tenido en cuenta los siguientes criterios: 

 

o las  distancias  reglamentarias  de  los  conductores  a masa  1,2 m  valor 

reglamentario  para  132kV  considerando  la  inclinación  de  la  cadena 

vertical  debida  al  viento  (ángulo  de  desviación  vertical  máximo 

permitido de 45º).  

o las distancias reglamentarias de  los conductores a masa  (1,2 m), en el 

caso más desfavorable  (ángulo más  fuerte de  la  traza de  la  línea para 

cada  tipo  de  armado  y  apoyo)  y  desplazamiento  del  puente  de  la 

cadena de amarre por efecto del viento (ángulo de desplazamiento de 

20 º) 

o el ángulo de recubrimiento para el cable de tierra (ángulo de 35º entre 

la  vertical  y  la  línea  ficticia  que  une  la  cúpula  con  el  conductor más 

desfavorable) 

 

Se  han  previsto  apoyos  tetrabloque  tipo Drago  con  armado  adecuado  para  la 

conversión aéreo subterránea, del fabricante Made o similar. 

 

La determinación de los tipos de apoyo, en cuanto a su resistencia mecánica, se 

ha  basado  en  datos  del  fabricante  Made.  Los  esfuerzos  necesarios  se  han 

calculado  siguiendo el Reglamento de  Líneas Aéreas de Alta Tensión de 2008, 

incluyendo en  la 2ª hipótesis una sobrecarga de viento de 60km/h, como ya se 

ha comentado. 

 

En cada apoyo se  indicará el número de orden que  le corresponda, de acuerdo 

con el criterio de origen de la línea que se haya establecido. 

 

Page 34: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 29 de 34 

De  igual  forma  todos  los  apoyos  llevarán  una  placa  de  señalización  de  riesgo 

eléctrico,  situada  a una  altura  visible  y  legible desde  el  suelo,  a una distancia 

mínima de 2 metros. 

 

La cimentación de los apoyos incluidos en el Modificado de Proyecto es de tipo: 

tetrabloque de 4 patas separadas, constituidas por cuatro bloques de hormigón 

de  sección  cuadrada,  y  las mismas  han  sido  calculas  por  su  fabricante,  para 

resistir el esfuerzo de arrancamiento y distribuir el de compresión en el terreno. 

 

Todos  los  apoyos  dispondrán  de  una  peana  de  protección  en  su  base,  con  el 

objeto  de  proteger  el  acero  contra  la  corrosión  e  impactos mecánicos.  Dicha 

peana será de hormigón, y tendrá forma de “punta de diamante”, con una altura 

mínima de 0,2 metros en la parte lateral y 0,3 metros en el centro. Se evitará el 

remanso de agua en la parte inferior de los angulares de los montantes. 

 

La  cimentación  del  apoyo  (conjunto  poste+armado),  alturas,  esfuerzos, 

disposiciones  de  los  distintos  armados,  están  recogidos  en  los  planos 

correspondientes del Proyecto. 

 

9.2.4 AISLAMIENTO‐CADENAS DE AISLADORES 

Las cadenas de aisladores, a través de las cuales se amarrarán o se suspenderán 

los conductores de los apoyos, serán aquellas previstas en el Proyecto original. 

 

Las  cadenas  horizontales  y  verticales  dispondrán  de  una  serie  simple  de  11 

aisladores  tipo  U100BS,  resultando  un  conjunto  con  las  siguientes 

características: 

Page 35: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 30 de 34 

9.2.5 PUESTAS A TIERRA 

De  acuerdo  con  el  capítulo  7  de  la  ITC‐LAT‐07  del  RD  223/2008,  de  15  de 

febrero,  cada  apoyo  de  Línea  Aérea  de  Alta  Tensión  contemplado  en  el 

siguiente Proyecto, dispondrá de un electrodo de tierra subterráneo específico, 

con el propósito de  limitar  las tensiones peligrosas de paso y de contacto a  las 

que pudieran verse sometidas  las personas que permanezcan o circulen en sus 

proximidades. 

 

Como medida de seguridad, cuando se tenga un electrodo de tierra subterráneo 

con anillo, éste se conectará a la Línea de Tierra aérea en dos puntos opuestos. 

 

Los electrodos de tierra para cada uno de los apoyos se han diseñado en base a 

los siguientes puntos: 

 

Resistencia a los esfuerzos mecánicos y a la corrosión. 

Resistencia térmica a la corriente de falta más elevada. 

Garantizar la seguridad de las personas durante una falta a tierra. 

Proteger de daños a propiedades y equipos y garantizar la fiabilidad de la 

Línea. 

Material constitutivo del apoyo. 

Ubicación del apoyo :  

No frecuentados. 

Frecuentados con calzado. 

Frecuentados sin calzado. 

Tiempo de la desconexión automática en caso de defecto a tierra. 

Aumento del potencial de tierra en caso de defecto a tierra. 

Actuación de las protecciones en caso de defecto a tierra. 

 

En  base  a  los  tres  primeros  puntos  anteriores,  para  la  configuración  del 

electrodo de  tierra para  los apoyos 20 y 30 de  la  Línea Aérea de Alta Tensión 

será el siguiente: 

Page 36: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 31 de 34 

Doble Anillo cuadrado a 1 y 2 metros de la cimentación del apoyo y con 1 

pica dispuesta en cada vértice. 

 

En  el  presente  proyecto  todos  los  electrodos  de  tierra  estarán  formados  por 

picas de acero cobreado, con recubrimiento de 300 micras, de 2 m de longitud y 

18 mm de diámetro. 

Los  anteriores  electrodos  de  tierra  deberán  de  unirse  directamente  con  las 

partes metálicas del apoyo, mediante Líneas de Tierra formadas por conductor 

de cobre de 95 mm2 de sección, evitando trazados tortuosos y curvas de poco 

radio.  

 

Las  uniones  entre  el  conductor  y  las  picas  se  realizarán mediante  soldaduras 

aluminotérmicas. 

 

DESPUES  DE  CONSTRUIDO  EL  ELECTRODO  DE  TIERRA,  EL  DIRECTOR  DE OBRA 

VERIFICARA EL VALOR DE LA RESISTENCIA DE TIERRA. 

 

SE VERIFICARA ASIMISMO LA NO TRANSFERENCIA DE POTENCIAL PELIGROSO A 

TUBERIAS,  VALLAS METALICAS,  CABLES  DE  BAJA  TENSION,  ETC.,  QUE  PUEDA 

HABER EN LAS PROXIMIDADES. 

 

En  los  apoyos  No  Frecuentados,  con  desconexión  automática  inferior  a  1 

segundo, no será obligatorio garantizar valores de tensión de contacto inferiores 

a los máximos admisibles. Sin embargo, el valor de la resistencia de puesta tierra 

será lo suficientemente bajo para garantizar la actuación de las protecciones en 

caso de defecto a tierra. 

 

El  plano  con  la  toma  de  tierra  descrita  es  lo  correspondiente  a  LAT‐31,  del 

Proyecto original. 

 

Page 37: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 32 de 34 

9.2.6 PROTECCIÓN AVIFAUNA 

Según la Resolución de la Secretaría de Estado de Medio Ambiente por la que se 

formula  el  documento  de  alcance  para  la  evaluación  ambiental  del  presente 

Proyecto,  la  línea  eléctrica  132  kV  contará  con  las  medidas  de  contra  la 

electrocución  y  colisión  de  aves  de  acuerdo  con  lo  establecido  en  el  RD 

1432/2008, de 29 de agosto. 

 

9.2.6.1 MEDIDAS CONTRA LA ELECTROCUCIÓN 

Todas las cadenas de aisladores se componen de aisladores suspendidos de 

vidrio templado, es decir, compuestos por caperuza y vástago, no se utilizan 

aisladores rígidos. 

 

En  los  armados  verticales,  tipo  tresbolillo,  bandera  y  doble  circuito,  la 

distancia  entre  la  parte  superior  de  cualquier  cruceta  y  el  conductor 

dispuesto sobre ella, no será inferior a 1,5 metros. 

 

En  las  cadenas  de  suspensión,  la  distancia  vertical  entre  la  cruceta  y  la 

grapa de amarre del conductor, será como mínimo 0,6 metros. Se cumple, 

ver figura siguiente. 

 

En  los armados horizontales, tipo bóveda, deberá de aislarse el conductor 

central 1 metro a cada lado del punto de amarre. 

 

Las cadenas de amarre dispondrán de una alargadera antiposada de aves, 

con el objeto de que la distancia horizontal entre la punta de la cruceta y la 

grapa  de  amarre  sea  como  mínimo  de  1  metro.  Dicha  alargadera  se 

colocará entre el último aislador y  la grapa de amarre del conductor, por 

considerar que esta ubicación es  la que mejor protege a  las aves contra  la 

electrocución. La longitud de la cadena de amarre asegura ya una longitud 

superior  a  la  requerida  de  1m,  en  concreto:  1,890 m,  no  es  por  tanto 

necesaria la incorporación de alargaderas antiposada.  

Page 38: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 33 de 34 

 

 

9.2.6.2 MEDIDAS CONTRA LA COLISIÓN 

El cable de tierra‐óptico todo a lo largo de la línea y los conductores de fase 

en  los  tramos  de  línea  incorporados  en  el Modificado,  irán  provistos  de 

señalizadores visuales, tipo espiral, de 30cm de diámetro mínimo y 1 metro 

de  longitud. Las características de  los mismos  se  incluirán en el Pliego de 

Condiciones  Técnicas:  Línea  Eléctrica  de  Evacuación  132kV  de  este 

Proyecto.  

 

 

Dichos  señalizadores  se  dispondrán  sobre  el  cable  de  tierra  ‐  fibra  óptica, 

previsto para la línea, de manera que la distancia entre dispositivos consecutivos 

será de 10 metros. 

 

Y alternativamente, en  los conductores de  fase, de manera que  la señalización 

en conductores genere un efecto visual equivalente a una señal cada 10 metros, 

para lo cual se dispondrán de forma alterna en cada conductor. 

Page 39: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

MEMORIA MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 34 de 34 

En ambos casos según se muestra en los planos de planta y perfil adjuntos. 

 

No obstante, las anteriores distancias podrán ser modificadas, si así lo considera 

el Órgano ambiental competente. 

 

 

10 ORGANISMOS AFECTADOS 

El  soterramiento  de  la  Línea  de  Evacuación  descrita  en  el  Modificado  de 

Proyecto, afecta a los siguientes organismos: 

 

AYUNTAMIENTO DE BARRAX  

AYUNTAMIENTO DE ALBACETE 

DIPUTACIÓN  PROVINCIAL  DE  ALBACETE_  SERVICIO  DE  CARRETERAS  (CARRETERA 

PROVINCIAL AB‐701) 

IBERDROLA DISTRIBUCIÓN ELÉCTRICA S.A.U._OTRAS LÍNEAS ELÉCTRICAS 

SERVICIO PERIFÉRICO DE AGRICULTURA EN ALBACETE _VÍAS PECUARIAS (CAÑADA REAL 

DE LA MANCHA, CORDAL DE LA GINETA, VEREDA DEL AJIIBARRO, CORDEL DEL CAMINO 

ANCHO Y LA CAÑADA REAL DEL VILLAR DE POZORRUBIO)  

SUBDELEGACIÓN DEL GOBIERNO EN ALBACETE. DEPENDENCIA DEL ÁREA DE INDUSTRIA 

Y ENERGÍA (ENAGAS ‐ GASODUCTO ALCÁZAR DE SAN JUAN–MONTESA) 

 

 

11 CONCLUSIONES 

El presente documento describe  suficientemente  las  instalaciones  incluidas en el 

Modificado  de  Proyecto.  Así  mismo  evidencia  el  cumplimiento  de  la 

Reglamentación que rige para este tipo de instalaciones. 

 

 

 

 

Page 40: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

PLANOS MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 

PPLLAANNOOSS   

Page 41: CCAARRAACCTTEERRÍÍSSTTIICCAASS TTÉÉCCNNIICCAASS DDEE LLAA ... - Castilla-La … · 2018-08-13 · Para el establecimiento de la Servidumbre sobre las fincas con cuyos propietarios

  

PLANOS MEMORIA JUSTIFICATIVA 

MODIFICACIÓN DE LA LÍNEA ELÉCTRICA DE 132 KV DE EVACUACIÓN DEL PARQUE EÓLICO BARRAX NORTE‐SUR. REFERENCIA LASAT 02210103684 Página 1 de 1 

  

 

TÍTULO DE PLANO  NÚMERO DE PLANO 

GENERALES 

LOCALIZACIÓN, EMPLAZAMIENTO Y ACCESO  PG‐01 (Hoja 1 de 1) 

PLANTA GENERAL DE INSTALACIONES  PG‐02 (Hoja 1 de 1) 

PLANO CALIFICACIÓN URBANÍSTICA BARRAX  PG‐03 (Hoja 1 de 1) 

PLANO CALIFICACIÓN URBANÍSTICA ALBACETE  PG‐04 (Hoja 1 de 1) 

PARCELARIOS 

PARCELARIO BARRAX NORTE‐SUR (PLANO 1 DE 2)  DUP‐01 

PARCELARIO BARRAX NORTE‐SUR (PLANO 2 DE 2)  DUP‐02 

LAT 132kV SET BARRAX NORTE‐SUR – SET ROMICA 

SITUACION 1  LAT‐01 

SITUACION 2  LAT‐02 

PLANO DE PLANTA Y PERFIL (APOYOS 9 AL 17)  LAT‐06 

PLANO DE PLANTA Y PERFIL (APOYOS 17 AL 20)  LAT‐07 

PLANO DE PLANTA Y PERFIL (APOYOS 30 AL 32)  LAT‐08 

TRAZADO DE LINEA SUBTERRANEA 132 kV 

PK 0+000 A PK 1+530 DE EJE DE LINEA LSAT‐02 

TRAZADO DE LINEA SUBTERRANEA 132 kV 

PK 1+480 A PK 2+673 DE EJE DE LINEA LSAT‐03 

CAMARA DE EMPALME  LSAT‐04 

SECCIONES TRANSVERSALES LINEA SUBTERRANEA   LSAT‐05 

DETALLE DE CRUZAMIENTO HINCA CON CARRETERA AB‐701 PK 

5+540 LSAT‐06 

DETALLE CRUZAMIENTO GASODUCTO  ALCAZAR DE SAN JUAN‐

MONTESA PK 112H4R LSAT‐07 

PLANTA REPLANTEO TRAZA SUBTERRANEA 1  LSAT‐08 

PLANTA REPLANTEO TRAZA SUBTERRANEA 2  LSAT‐09 

PLANTA REPLANTEO TRAZA SUBTERRANEA 3  LSAT‐10 

PLANO DE DETALLE APOYOS Nº 20 Y Nº 30  LSAT‐11 

 

 