+ All Categories
Home > Documents > CEM at the Prague Waste incinerator Martin Schlogl.pdf · Continuous measurement at the Prague...

CEM at the Prague Waste incinerator Martin Schlogl.pdf · Continuous measurement at the Prague...

Date post: 26-Mar-2018
Category:
Upload: doanthuy
View: 214 times
Download: 0 times
Share this document with a friend
10
Case study from the Czech Republic Martin Schlögl, Linde Gas CEM 2014, Istanbul, 15th May CEM at the Prague Waste incinerator
Transcript

Case study from the Czech Republic

Martin Schlögl, Linde Gas

CEM 2014, Istanbul, 15th May

CEM at the Prague Waste

incinerator

Prague Waste incineartor: Waste to

Energy Plant

2

Annual waste balance at the Prague

incinerator

3

Railway 20km

Ferrous waste

Roadway 12km

Heat for 25k

households

Clinker

213 387 tons of non sorted domestic waste per

year

4

Instrumentation for CEM, an

Automatic measuring system

5

Continuous measurement at the Prague waste

incinerator

Dust front scattering of infra-red light

SO2, NOx, CO, CO2 NDIR cross flow modulation

HCl adsorption spectroscopy in IR zone

TOC FID

In-situ measuring technology

Automatic measuring system (AMS) where the measurement is carried out directly in the gas duct, without sampling from

the process. If the measurement is undertaken across the diameter of the exhaust gas duct, then pollutants are detected

in a representative manner to a large extent. Refer to cross duct.

Calibration & Instrumentation gases

for CEM

6

Calibrations & instrumentation Specialty gases supplied

for Prague incinerator

Calibration gas mixtures as used :

25ppm HCl / N2

8ppm SO2 / N2

20 ppm C3H8 / N2

15% C02 / N2

180 ppm S02, 220 ppm NO, 180 ppm CO / N2

2% CH4, 2% CO / N2

Carrier & Detector gases:

Hydrogen 5.0, Nitrogen 5.0, Helium 5.0, Syntetic Air HC free

Specialty Equipment gas distribution system used at workplace

HiQ REDLINE® Specialty gases product line for high purity gases and

calibration mixtures

• Two stage cylinder regulators with stable outlet pressure equipped

with shut-off valve, tight membrane made from Hastelloy® and

the stainless steel body for corrosive mixtures components.

• The Semiautomatic gas supply panel with switch from empty to full

cylinder without interrupting of the gas flow and signal alarm

box announcing when cylinder is empty.

• The point of use as a second stage of the gas supply system for the

final working pressure adjustment.

Standards that have been applied to

CEM

-EN 14181:2012 “Stationary source emissions –

Quality assurance of automated measuring

systems´”

-EN 15267-1: "Air quality –Certification of automated

measuring systems –Part 1: General principles“

-EN 15267-2:2009Air quality –Certification of

automated measuring systems – Part 2: Initial

assessment of the AMS manufacturer´s quality

management system and post certification

surveillance for the manufacturing process

-EN 15267-3Air quality – Certification of automated

measuring systems – Part 3: Performance criteria

and test procedures for automated measuring

systems for monitoring emissions from stationary

sources

Regulation CZ 415 2012 -> EU 2010/75

Industrial emissions (integrated pollution prevention

and control)

8

Continues Emissions Monitoring from Prague waste incinerator [mg.m-3]

Average 2013 Limit CZ 415 2012 % of limit

Dust 3,59 10 36

SO2 0,7 50 1

NOx 137 200 69

CO 26 50 53

HCl 0,04 10 0

TOC 0,63 10 6

Screen shot from Control

room :

24/7 6x per min

measurement

Specialty Gases plant - Linde Gas

Czech Republic

9

• Calibration mixtures production (envi, automotive, food…applications)

• Gravimetric filling

• ISO 17025 accreditation, primary standards preparation

• Analytical instrumentation:

Gas Chromatography: TCD, FID, PDD

Analyzers: NDIR, Paramagnetic, Chemiluminiscence,

Photoacustic

Direct comparison to primary reference material (The Czech Metrology

Institute)

Thanks for your attention.


Recommended