    Temperature Indicating Controller, Model CF1H

    WIKA Operating Instructions CF1H V 1.2 01/2007

    Operating Instructions

  • 8/13/2019 CF1H_manual_V12_6351

    2/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 2 -

    ***** Note to users *****

    Before operating this controller, make sure you have understood the following.

    WarningTurn the power supply to the instrument OFF before wiring or

    checking. Working or touching the terminal with the power switched

    ON may result in Electr ic Shock, which can cause severe injury

    or death.

    Moreover, the instrument must be grounded before the power supply

    to the instrument is turned on.

    CautionDo not apply a commercial power source to the sensor connecting to the input terminal

    nor allow the power source to come into contact with the sensor, as the input circuit

    may be burnt out.

    Set-up by the DIP switch and the rotary switch inside of the controller is required

    before the power is turned on.

    The product is factory adjusted as [Sensor input: K, Control action: Fuzzy self-tuning

    PID, Heating action, Alarm (A1): No alarm action, no standby function, Unit: Cand Program starting form: manual]. Refer to page 9 Setup.

    It is recommended that the PID auto-tuning be performed on the trial run.

    It is advised to provide the protective device against such environmental conditions

    which may cause damage to the device or contribute to the deterioration of its parts.

    If you are mounting this controller to the control panel or machine, read this manual from

    Chapter 10 Mounting to control panel or 11 Wiring connection after checking the model

    name by 1 Model names.

    If you are operating this controller already mounted, read this manual from Chapter 2 Name

    and functions of the sections or 4 Operations.

  • 8/13/2019 CF1H_manual_V12_6351

    3/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 3 -

    --- CONTENTS ---

    1 Model names ---------------------------------------------------------------------------------------------------- 6

    2 Name and functions of the sections

    2.1 Names and displays ---------------------------------------------------------------------------------------- 72.2 Keys ------------------------------------------------------------------------------------------------------------ 8

    3 Setup3.1 Taking the internal assembly out ------------------------------------------------------------------------ 9

    3.2 Switch setting (multi-function) ---------------------------------------------------------------------------- 9

    3.3 Insertion of the internal assembly ----------------------------------------------------------------------- 12

    4 Operations

    4.1 Operating flow chart ---------------------------------------------------------------------------------------- 13

    4.2 Operations

    (1) PV/SV display mode ------------------------------------------------------------------------------------- 16

    (2) Main setting mode ---------------------------------------------------------------------------------------- 17(3) Sub setting mode

    Setting value memory number selection ------------------------------------------------------------ 17

    Auto-tuning Perform/Cancel --------------------------------------------------------------------------- 17

    Main proportional band setting ------------------------------------------------------------------------ 18

    Cooling proportional band setting -------------------------------------------------------------------- 18

    Integral time setting -------------------------------------------------------------------------------------- 18

    Derivative time setting ----------------------------------------------------------------------------------- 18

    Main control proportional cycle setting -------------------------------------------------------------- 19

    Cooling control proportional cycle setting ---------------------------------------------------------- 19

    Manual reset setting ------------------------------------------------------------------------------------- 19Alarm 1 setting -------------------------------------------------------------------------------------------- 20

    Alarm 2 setting -------------------------------------------------------------------------------------------- 20

    Heater burnout alarm setting -------------------------------------------------------------------------- 20

    Loop break alarm time setting ------------------------------------------------------------------------- 21

    Loop break alarm span setting ------------------------------------------------------------------------ 21

    (4) Auxiliary function setting mode 1

    Setting value lock designation ------------------------------------------------------------------------- 22

    Main setting value high limit setting ------------------------------------------------------------------ 23

    Main setting value low limit setting ------------------------------------------------------------------- 23

    Sensor correction setting ------------------------------------------------------------------------------- 23Overlap band/Dead band setting --------------------------------------------------------------------- 24

    Remote/Local changing --------------------------------------------------------------------------------- 24

    Instrument number setting ------------------------------------------------------------------------------ 24

    Transfer rate selection ----------------------------------------------------------------------------------- 25

    Communication protocol--------------------------------------------------------------------------------- 25

  • 8/13/2019 CF1H_manual_V12_6351

    4/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 4 -

    (5) Auxiliary function setting mode 2

    Scaling high limit value setting ----------------------------------------------------------------------- 26

    Scaling low limit value setting ------------------------------------------------------------------------ 26

    Decimal point place selection ------------------------------------------------------------------------ 26

    PV filter time constant setting ------------------------------------------------------------------------ 27Main output high limit setting ------------------------------------------------------------------------- 27

    Main output low limit setting -------------------------------------------------------------------------- 27

    Main output ON/OFF action hysteresis setting -------------------------------------------------- 27

    Cooling action mode selection ----------------------------------------------------------------------- 28

    Cooling output high limit setting --------------------------------------------------------------------- 28

    Cooling output low limit setting ---------------------------------------------------------------------- 28

    Cooling output ON/OFF action hysteresis setting ---------------------------------------------- 28

    Alarm 1 (A1) action Energized/Deenergized selection ---------------------------------------- 29

    Alarm 2 (A2) action Energized/Deenergized selection ---------------------------------------- 29

    Alarm 1 (A1) hysteresis setting ---------------------------------------------------------------------- 29

    Alarm 2 (A2) hysteresis setting ---------------------------------------------------------------------- 29

    Alarm 1 (A1) action delayed timer setting --------------------------------------------------------- 30

    Alarm 2 (A2) action delayed timer setting --------------------------------------------------------- 30

    External setting input high limit setting ------------------------------------------------------------- 30

    External setting input low limit setting -------------------------------------------------------------- 30

    Transmission output selection ------------------------------------------------------------------------ 31

    Transmission output high limit setting -------------------------------------------------------------- 31

    Transmission output low limit setting --------------------------------------------------------------- 31

    Display selection when control output is off ------------------------------------------------------- 32

    Main setting value rising rate setting ---------------------------------------------------------------- 32

    Main setting value falling rate setting --------------------------------------------------------------- 32

    Output selection when input burnout ---------------------------------------------------------------- 33

    (6) Program mode

    Program control change -------------------------------------------------------------------------------- 35

    Step 1 to 4 time setting --------------------------------------------------------------------------------- 35

    Step 5 to 7 time setting --------------------------------------------------------------------------------- 36

    (7) Auto/Manual control change ------------------------------------------------------------------------------ 36

    (8) Control output OFF function ------------------------------------------------------------------------------ 37

    (9) Output manipulating value and Step rest time indication mode --------------------------------- 38

    5 Setting value memory function ---------------------------------------------------------------------- 39

    6 Running

    6.1 When using the CF1H as a Temperature controller ------------------------------------------------- 40

    6.2 When using the CF1H as a Simplified program controller ----------------------------------------- 41

  • 8/13/2019 CF1H_manual_V12_6351

    5/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 5 -

    7 Action explanations7.1 Standard action drawings --------------------------------------------------------------------------------- 42

    7.2 Heater burnout alarm action drawing ------------------------------------------------------------------ 42

    7.3 ON/OFF action drawings ---------------------------------------------------------------------------------- 43

    7.4 Pattern end action drawing ------------------------------------------------------------------------------- 437.5 Heating/Cooling action drawings ------------------------------------------------------------------------ 44

    7.6 Alarm 1 (A1) and 2 (A2) action drawings -------------------------------------------------------------- 50

    8. Control actions8.1 Fuzzy self-tuning --------------------------------------------------------------------------------------------- 52

    8.2 Explanations of PID ----------------------------------------------------------------------------------------- 53

    8.3 PID auto-tuning of this controller ------------------------------------------------------------------------- 54

    9. Other funct ions ---------------------------------------------------------------------------------------------- 55

    10. Mounting to control panel10.1 Site selection ------------------------------------------------------------------------------------------------- 56

    10.2 External dimension drawing ------------------------------------------------------------------------------ 56

    10.3 Panel cutout drawing --------------------------------------------------------------------------------------- 57

    10.4 Current transformer (CT) dimension drawing -------------------------------------------------------- 57

    10.5 Mounting ------------------------------------------------------------------------------------------------------- 58

    11. Wiring connection11.1 Terminal arrangement -------------------------------------------------------------------------------------- 59

    11.2 Wiring connection examples ------------------------------------------------------------------------------ 60

    12. Specifications12.1 Standard specifications ------------------------------------------------------------------------------------- 63

    12.2 Optional specifications -------------------------------------------------------------------------------------- 67

    13. Troubleshooting ---------------------------------------------------------------------------------------------- 71

    14. Character table ----------------------------------------------------------------------------------------------- 74

  • 8/13/2019 CF1H_manual_V12_6351

    6/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 6 -

    1. Model names

    CF1H -3 A- / M - - - - ..... Series name CF1H

    3 Control action PID(1)

    Alarm A Process value monitoring, output relay(2)

    R Relay

    S Logic level (DC 0/12 V) for solid state relay

    Output

    A Analogue current signal (4 ... 20 mA)

    Input M Multi-function input (input configuration settable)

    H AC 100 ... 240 V, 50 ... 60 HzPower supply

    L AC/DC 24 V

    FT One-touch mounting bracket (for mounting panel

    thickness 1 to 3 mm)

    Mounting provision

    FS Screw bracket (for mounting panel thickness 1 to 15

    mm)

    B Factory adjustment, device will be configured by the

    operator

    Instrument configuration

    ?/# To customers specification

    2AS(3)

    Alarm output 2: process value monitoring

    2AR(3)

    Alarm output 2: control loop monitoring

    2AL(3)

    Alarm output 2: process value and control loop

    monitoring with common terminals

    DR2(4)

    2. control output relay

    DS2(4)

    2. control output logic level DC 0/12 V

    DA2(4)

    2. control output analogue current signal 4 20 mATA4

    (5) Retransmission output 4 20 mA

    TV1(5)

    Retransmission output 0 1 V

    W12(6)

    Heater burnout alarm for 1 phase (max. 20 A)

    W15(6)

    Heater burnout alarm for 1 phase (max. 50 A)

    W32(6)

    Heater burnout alarm for 3 phase (max. 20 A)

    W35(6)

    Heater burnout alarm for 3 phase (max. 50 A)

    CR2(7)

    Serial communication RS 232C

    CR5(7)

    Serial communication RS 485

    EA0(8)

    Remote setting 0 20 mA

    EA4

    (8)

    Remote setting 4 20 mAEV0

    (8) Remote setting 0 1 V

    EV1(8)

    Remote setting 1 5 V

    SM7 Parameter memory: single parameter settings

    external selectable by connection terminals

    KAB Terminal cover

    IP4(9)

    IP 54 front protection

    Options

    P24 Transmitter supply DC 24 V max. 30 mA

    (1) Fuzzy self-tuning PID, PID, PD and ON/OFF action are selectable by internal DIP switch.

    (2) 12 types of alarm action and no alarm action are selectable by internal rotary switch and DIP switch.

    (3) - (8) Please note that only one option from every group can be selected.

    (9) Condition for this option is the screw type mounting bracket (FS).

  • 8/13/2019 CF1H_manual_V12_6351

    7/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 7 -

    2 Name and functions of the sections2.1 Names and Displays

    [Fig. 2.1-1]

    (1) PV display

    Indicates the Process variable (PV) with red LED.

    (2) SV display

    Indicates the Setting value (SV), Manipulating value (MV) or Time (TIME) with green LED.

    (3) Setting value memory number display

    Indicates the Setting value memory number with yellow LED.

    (4) SV indicator (SV)

    The green LED is lit when the Setting value (SV) is being displayed on the SV display.

    (5) MV indicator (MV)

    The red LED is lit when the Manipulating value (MV) is being displayed on the SV display.(6) Time indicator (TIME)

    The red LED is lit when the Time (TIME) is being displayed on the SV display.

    (7) Manual control indicator (Manual)

    The red LED is lit in Manual control.

    (8) Control output or Heating output action indicator (OUT 1)

    The green LED is lit when the Control output or Heating output is on. (For the current output type, it blinks

    corresponding to the manipulating value at 0.125 seconds of period.)

    (9) Cooling output action indicator (OUT 2) [Option]

    The yellow LED is lit when the Cooling output is on. (For the current output type, it blinks corresponding to

    the manipulating value at 0.125 seconds of period.)

    AUTO

    MAN

    lrq

    lccjlab

    c^pq

    CF1H

    (1)

    (2)

    (3)

    (7)

    (8)

    (9)

    (10)

    (4)

    (5)

    (6)

    (11)

    (12)

    (13)

    (14)

    (15)

    (16)

    (17)

  • 8/13/2019 CF1H_manual_V12_6351

    8/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 8 -

    (10) Serial communication output indicator (TX/RX) [Option]

    The green LED is lit when transmitting serial communication TX.

    (11) Alarm 1 (A1) output action or Pattern end 1 output indicator (A1)

    The red LED is lit when the Alarm 1 (A1) output or Pattern end (A1) output is on.(12) Alarm 2 (A2) output action or Pattern end 2 output indicator (A2) [Option]

    The red LED is lit when the Alarm 2 (A2) output or Pattern end 2 output is on.

    (13) Heater burnout alarm output action indicator (HB) [Option]

    The red LED is lit when the Heater burnout alarm output is on.

    (14) Sensor burnout indicator (SB)

    The red LED is lit when the Sensor is burnt out.

    (15) Remote indicator (REM) [Option]

    The red LED is lit during Remote action.

    (16) Loop break alarm output action indicator (LA) [Option]

    The red LED is lit when the Loop break alarm output is on.

    (17) Auto-tuning action indicator (AT)

    The yellow LED blinks during auto-tuning.

    2.2 Keys

    Main functions are described below, however, the keys have other functions in various

    modes. Refer to Section 4.1 Operating flow chart (Page 15ff).

    key : Increases the numeric value on the SV display during

    setting mode.

    key : Decreases the numeric value on the SV display during

    setting mode.

    MODEkey : Selects the setting mode.OUT/OFFkey : Performs the control output ON or OFF.AUTO/MANkey : Switches the control between Automatic and Manual.

    FASTkey : Makes the numerical value change faster by pressing the

    FASTkey and the (or ) key simultaneously.

    In any mode, if the OUT/OFFkey is pressed for approx. 1 second, the Control output OFF

    function will work.

    When the function is working, the function cannot be released. Even if the insrument

    power is turned off and on again, and the function is not released.To release the function, press the OUT/OFFkey for 1 second.

    The setting value is registered by pressing the MODEkey.

    In any setting item, if the MODEkey is pressed for approx. 3 seconds, the mode returns to

    the PV/SV display.

  • 8/13/2019 CF1H_manual_V12_6351

    9/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 9 -

    3. Setup3.1 Taking the internal assembly out

    Before the power supplied to this instrument is on, take the internal assembly out from

    the case by pushing the hook (bottom of the instrument) in the direction indicated by

    the arrow and holding the notches.

    [Fig. 3.1-1]

    WarningDo not take the inner assembly out nor touch the terminal with

    the power supply on.

    Touching the terminal with the power switched ON may result in

    Electric Shock, which can cause severe injury or death.

    3.2 Switch setting (multi -function)

    Using a small slotted screwdriver and tweezers, set the Sensor input, Alarm 1 action, Alarm 2 action,

    Control action, Heating (reverse)/Cooling (direct) action, Alarm 1 and 2 standby functions, Unit C/F and

    Program starting form Auto/Manual change by rotary switch and DIP switch by the following procedure.

    If the option A2 is not applied, the rotary switch A2 (SW301) will not be equipped.

    Control action designation Alarm 2 action type designation

    Heating/Cooling action designation Alarm 1 action type designation

    Alarm 1 standby action designation Sensor input designation

    Alarm 2 standby action designation

    C/F designation

    Sensor input designation

    Program start Auto/Manual

    designation

    [Fig. 3.2-1]DIP switch

    Rotary switch

  • 8/13/2019 CF1H_manual_V12_6351

    10/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 10 -

    The following items can be designated by the DIP switch (SW304).

    Factory adjusted as all switches OFF [ ].

    [Table 3.2-1]

    Item Sw. No. Designation Switch statusFuzzy self-tuning PID action No.1: OFF No.2: OFF

    PID action No.1: ON No.2: OFF

    PD action No.1: OFF No.2: ONControl action

    1and2

    ON/OFF action No.1: ON No.2: ON

    Heating (reverse) action No.3: OFFHeating/Coolingaction 3 Cooling (direct) action No.3: ON

    No standby action No.4: OFFAlarm 1 (A1)standbyaction

    4 Standby action No.4: ON

    No standby action No.5: OFFAlarm 2 (A2)standby

    action (*1)

    5 Standby action No.5: ON

    C No.6: OFFC/F 6

    F No.6: ON

    K, J, R, B, N, PL-ll, Pt100, JPt100 No.7: OFFSensor input

    (*2)7 S, E, T, C, 4 to 20mA, 0 to 20mA,

    0 to 1V, Pt100No.7: ON

    Manual start No.8: OFFProgram startAuto/Manual

    8Automatic start No.8: ON

    *1: The standby function will not work if the option A2 is not applied.

    *2: The sensor input can be designated by the combination of this item and the rotary

    switch sensor input (SW303). (See page 11.)

    Program start: This item is available for the program control.

    Manual start : Program starts by pressing the OUT/OFFkey.

    Automatic start : Program is automatically started by turning the power supply to the

    instrument on (after 2 seconds of warm-up status).

  • 8/13/2019 CF1H_manual_V12_6351

    11/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 11 -

    Select the sensor type by rotary switch sensor input (SW303).

    Factory adjusted as K, [ ].

    [Table 3.2-2]

    Rotary Sw.No.

    DIP Sw.No. 7

    Type ofsensor

    Scale range

    0 OFF K -200 to 1370C -320 to 2500F

    1 OFF J -200 to 1000C -320 to 1800F

    2 OFF R 0 to 1760C 0 to 3200F

    3 OFF B 0 to 1820C 0 to 3300F

    4 OFF PL-ll 0 to 1390C 0 to 2500F

    5 OFF N 0 to 1300C 0 to 2300F

    6 OFF Pt100 -199.9 to 850.0C -199.9 to 999.9F

    7 OFF JPt100 -199.9 to 500.0C -199.9 to 900.0F

    0 ON S 0 to 1760C 0 to 3200F

    1 ON E 0 to 1000C 0 to 1800F

    2 ON T -199.9 to 400.0C -199.9 to 750.0F

    3 ON C (W/Re5-26) 0 to 2315C 0 to 4200F

    4 ON 4 to 20mAdc -1999 to 9999

    5 ON 0 to 20mAdc -1999 to 9999

    6 ON 0 to 1Vdc -1999 to 9999

    7 ON Pt100 -200 to 850C -320 to 1560F

  • 8/13/2019 CF1H_manual_V12_6351

    12/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 12 -

    The alarm action type and the pattern end output when program control can be

    designated by the rotary switch A1 (SW302) and A2 (SW301).

    The rotary switch A2 (SW301) is equipped only when the option A2 is applied.

    Rotary switch A1 (SW302): Alarm 1 (A1) action or Pattern end 1 output.

    Rotary switch A2 (SW301): Alarm 2 (A2) action or Pattern end 2 output.

    Factory adjusted as No alarm action, [ ].

    [Table 3.2-3]

    Alarm 1 actionA1 Rotary Sw.(Sw302) No.

    Alarm 2 actionA2 Rotary Sw.(Sw301) No.

    No alarm action 0 No alarm action 0

    High limit alarm 1 High limit alarm 1

    Low limit alarm 2 Low limit alarm 2

    High/Low limits alarm 3 High/Low limits alarm 3

    Hi/Lo limit range alarm 4 Hi/Lo limit range alarm 4

    Process high alarm 5 Process high alarm 5

    Process low alarm 6 Process low alarm 6

    Pattern end 1 output 7 Pattern end 2 output 7

    3.3 Insertion of the internal assembly

    When the setup is completed, insert the internal assembly into the case.

    Firmly insert the assembly until it is locked by the hook at the bottom of the instrument.

    (There will be a clicking sound.)

    CautionDo not confuse the top and bottom of the internal assembly.If inserting the assembly into the case by force in the wrong direction, the PCB

    may be damaged.

  • 8/13/2019 CF1H_manual_V12_6351

    13/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 13 -

    4 Operations4.1 Operating f low chart

    Instrument power ON

    Warm-up status (For approx. 2s, displays as shown on page 18.)

    Control output OFF function

    Manual control

    PV/SV display mode

    Output manipulating value

    MODE MODE

    Step rest time *1

    MODE + MODE

    [Main setting mode] [Sub setting mode]

    Main setting Setting value memory No. selection Alarm 1 (A1) setting

    PV MODE PV MODE PV MODE

    Auto-tuning Perform/Cancel Alarm 2 (A2) setting

    *2 PV MODE PV MODE

    Main proportional band setting Heater burnout alarm setting

    PV MODE PV MODE

    Cooling proportional band setting Loop break alarm timesetting

    PV MODE PV MODE

    Integral time setting Loop break alarm span setting

    PV MODE PV MODE

    Derivative time setting

    PV MODE

    Main proportional cycle setting

    PV MODE

    Cooling proportional cycle setting

    PVMODE

    Manual reset setting

    PV MODE

    MODE3s

    AUTO/MAN

    OUT/OFF1s

    MO

  • 8/13/2019 CF1H_manual_V12_6351

    14/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 14 -

    : Options

    +MODE: Press the MODEkey while the key is being pressed.

    +MODE3s: Press the MODEkey for approx. 3 seconds while the key is being pressed.

    + +MODE3s: Press the MODEkey for approx. 3 seconds while the and keys are being

    pressed.

    + 3s : Pressing the key, press the key for approx. 3 seconds.*1: Step rest time is indicated only during program control.*2: If the Auto-tuning is performed, the mode reverts to the PV/SV display.

    If the Auto-tuning is released, the mode will move to Proportional band setting.*3: In the mode Program control change, if is selected and the MODEkey is

    pressed, the display reverts to the PV/SV display mode.

    +MODE3s + +MODE3s

    [Auxiliary function [Auxiliary function

    setting mode 1] setting mode 2]

    Setting value lock Scaling high limit Cooling output high limitdesignation setting settingPV

    MODEPV MODE PV MODE

    Main setting value Scaling low limit Cooling output low limithigh limit setting setting settingPV

    MODEPV MODE PV MODE

    Main setting value Decimal point place Cooling output ON/OFFlow limit setting selection action hysteresis settingPV

    MODEPV MODE PV MODE

    Sensor correcting PV filter time constant Alarm 1 (A1) actionvalue setting setting Energized/DeenergizedPV

    MODEPV MODE PV MODE

    Overlap/Dead band Main output high limit Alarm 2 (A2) actionsetting setting Energized/DeenergizedPV

    MODEPV MODE PV MODE

    Remote/Local changing Main output low limit Alarm 1 (A1) actionsetting hysteresis selection

    PV MODE PV MODE PV MODE

    Instrument number Main output ON/OFF Alarm 2 (A2) actionsetting action hysteresis setting hysteresis setting

    PVMODE PV MODE PV MODE

    Transfer rate selection Cooling action modeselection

    PVMODE

    PV MODE

    Communication protocolselectionPV

    MODE

  • 8/13/2019 CF1H_manual_V12_6351

    15/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 15 -

    Set the temperature of the program in the Sub setting mode, Auxiliary function

    setting mode 1 and 2.

    + 3s[Program mode]

    Alarm 1 (A1) action Main setting value Program control *3

    delayed timer setting rising rate setting changePV MODE PV MODE PV MODE

    Alarm 2 (A2) action Main setting value Step 1 time setting

    delayed timer setting falling rate settingPV MODE PV MODE PV MODE

    External setting input Output selection when Step 2 time setting

    high limit setting input burnoutPV MODE PV MODE PV MODE

    External setting input Step 3 time settinglow limit settingPV

    MODE PV MODE

    Transmission output Step 4 time setting

    selectionPV

    MODE PV MODE

    Transmission output Step 5 time setting

    high limit settingPV MODE PV MODE

    Transmission output Step 6 time setting

    low limit settingPV MODE PV MODE

    Display selection when Step 7 time setting

    control output is offPV MODE PV MODE

  • 8/13/2019 CF1H_manual_V12_6351

    16/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 16 -

    4.2 Operations

    The PV display indicates the sensor type and the SV display indicates the rated value

    selected by Sensor input designation (page 10, 11) for approx. 2 seconds after the power

    is turned on. See [table 4.2-1].

    During this time, all outputs and LED indicators are in their off status.

    After that, the actual temperature is displayed on the PV display, main setting value

    on the SV display and starts control.

    (1) PV/SV display mode

    Instrument power ON

    Warm-up status (For 2s)

    [Table 4.2-1] Rated value

    [Table 4.2-1]

    C FInput

    PV display SV display PV display SV display

    K

    J

    R

    B

    PL-ll

    N

    S

    E

    T

    C

    Pt100

    JPt100

    Pt100

    420 mA DC

    020 mA DC

    01 V DC

    Scaling highlimit value

    Scaling highlimit value

    PV/SV display mode Mode during control.

    Actual Main The contents of setting items nor setting values

    Temperature setting value cannot be changed.

  • 8/13/2019 CF1H_manual_V12_6351

    17/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 17 -

    (2) Main setting mode

    In the PV/SV display mode, if the MODEkey is pressed, the Main setting mode will be selected.

    The setting value can be increased or decreased by pressing the , and FASTkeys.

    If the MODEkey is pressed, the setting value will be registered and the controller will

    revert to the PV/SV display.

    PV/SV display mode

    Actual Main setting

    Temperature value

    MODE

    Main setting

    Setting Mode to set the setting value of the main control.

    value

    MODE Setting range: From Main setting value low limitto Main setting value high limit

    [Factory adjusted as 0 C]

    (3) Sub setting mode

    In the PV/SV display mode, if the MODEkey is pressed while the key is being pressed, Sub setting mode

    will be selected. The setting value can be increased or decreased by pressing the , and FASTkeys. If

    the MODEkey is pressed, the setting value is registered and the next setting item will be selected.

    PV/SV display mode

    Actual Main setting

    temperature value

    + MODE

    Setting value memory Mode to select the memory number (file)number selection to be set or to be called.

    Selected Selecting items: 1 to 7value [Factory adjusted as Memory number 1.]

    MODE

    Auto-tuning Perform/ Mode to designate the auto-tuning Perform or Cancel.

    Cancel If Auto-tuning Perform is designated, and the MODEDesignation key is pressed, the controller reverts to PV/SV display mode.

    MODE MODE

    (When Perform) To set the other values, cancel the Auto-tuning.

    When the ON/OFF action or PD action is selected in

    the Control action designation (page 10), this display is

    not available.

  • 8/13/2019 CF1H_manual_V12_6351

    18/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 18 -

    SV (Auto-tuning Cancel)

    SV (Auto-tuning Perform)

    [Factory adjusted as Auto-tuning Cancel]

    If the Auto-tuning is released during the process,

    the PID value reverts to the former value.

    Main proportional band setting Mode to set the proportional band for Main control.

    Setting value Setting range: 0.1 999.9 %

    [Factory adjusted as 2.5 %]

    MODE When the ON/OFF action is selected in control

    action designation (Page 10), this display is not

    available.

    Cool proportional band setting Mode to set the proportional band for cooling control.

    Setting value

    Setting range: 0.0 10.0

    MODE (Multiplying factor to the main control proportional band value)

    [Factory adjusted as 1.0 times (2.5 %)]

    This display is not available when the option (code: D 2) is not

    applied or when the ON/OFF action is selected in Control action

    designation (page 10).

    Integral time setting Mode to set the integral time.

    Setting value Setting range: 0 3600 s

    [Factory adjusted as 200 s]

    MODE Setting the value to 0 disables the function.

    This display is not available when the ON/OFF action or

    PD action is selected in Control action designation (page 10).

    Derivative time setting Mode to set the derivative time.

    Setting value Setting range: 0 3600 s

    [Factory adjusted as 50 s]

    MODE Setting the value to 0 disables the function.

    This display is not available when the ON/OFF action is

    selected in Control action designation (page 10).

  • 8/13/2019 CF1H_manual_V12_6351

    19/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 19 -

    Main control Mode to set the proportional cycle of Main control.proportional cycle setting Setting range: 1 120 s

    Setting value [Factory adjusted as 30 s to Relay contact outputtype, and 3 s to Non-contact voltage output type]

    MODE This setting item is not available to Current output type.

    When the ON/OFF action is selected in Control action

    designation (page 10), this display is not available.

    With the Relay contact output type, if the Proportionalcycle time is decreased, the frequency of the relayaction increases, and the life of the relay contactis shortened.

    Cooling control Mode to set the proportional cycle of Cooling

    proportional cycle setting control.Setting value Setting range: 1 120 s

    [Factory adjusted as 30 s for Relay contact output

    MODE type, and 3 s for Non-contact voltage output type]

    This display is indicated only when the option [DR2] or [DS2]

    is applied.

    When the ON/OFF action is selected in Control action

    designation (page 10), this display is not available.

    Manual reset setting Mode to set the reset value to correct the offset

    Setting value (Deviation between SV and PV when equilibrium status).

    MODE Setting range: proportional band converted value

    However, when TC or RTD input, in the range,

    199.9 999.9 C (F)

    when DC input, in the range,

    1999 9999

    [Decimal point place follows the selection.]

    [Factory adjusted as 0.0 C]

    This display is indicated only when PD action is designated in

    the Control action designation (page 10).

    Manual reset setting method:

    When SV>PV, set the positive + value (SVPV).When SV

  • 8/13/2019 CF1H_manual_V12_6351

    20/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 20 -

    Alarm 1 (A1) setting Mode to set the action point of the Alarm 1 (A1) output.

    Setting value

    This item is not displayed if setting the rotary switchMODE to No. 0 or No. 7 (See page 12.)

    Setting range: See [table 4.2-2].

    [Factory adjusted as 0 C]

    Alarm 2 (A2) setting Mode to set the action point of the Alarm 2 (A2) output.

    Setting value

    This item is not displayed if the option [2AS or 2AL] is not

    MODE applied or even if it is applied, when setting the

    rotary switch to No. 0 or No. 7 (See page 12.)

    Setting range: See [table 4.2-2].

    [Factory adjusted as 0C]

    Setting range of A larm 1 and 2

    (The setting range is the same when the standby function is added.)

    [Table 4.2-2]

    Alarm type Setting range

    High limit alarm Input span to Input span *1

    Low limit alarm Input span to Input span *1

    High/Low limits alarm 0 to Input span *1

    High/Low limit range alarm 0 to Input span *1

    Process high alarm Input range minimum to Input range maximum *2

    Process low alarm Input range minimum to Input range maximum *2

    For RTD input, the minimum value of the negative side is 199.9.

    For DC input, the minimum value of the negative side is 1999. (Decimal point place

    follows the selection.)

    *1: For DC input, the Input range span is the same as the Input range scaling span.

    *2: For DC input, Input range maximum (minimum) is the same as the Input range

    scaling maximum (minimum) value.

    Heater burnout alarm setting Mode to set the Heater current value for Heater burnout alarm.

    Setting value

    Setting range: When [W12 or W32] 0.0 20.0 AMODE (However, the indication is 0.0 50.0.)

    When [W15 or W35] 0.0 50.0 A

    [Factory adjusted as 0.0 A]

    This display is indicated only when the option [W ] is applied.

    Setting the value to 0.0 disables the function.

    It is recommended to set approx. 80 % of the Heater current

    value considering the voltage fluctuation.

    Self-holding is not available to the alarm output.

  • 8/13/2019 CF1H_manual_V12_6351

    21/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 21 -

    Loop break alarm Mode to set the time for Loop break alarmtime setting activation assessment.

    Setting value Setting range: 0 200 minutes[Factory adjusted as 0 min.]

    MODE This display is indicated only when the option [2AR or 2AL] is applied.

    Loop break alarm Mode to set the span for Loop Break Alarmspan setting activation assessment.

    Setting value Setting range:

    0 150 C (Thermocouple, except T and RTD

    MODE without a decimal point)

    0.0 150.0 C (Thermocouple T and RTD

    with a decimal point)

    0 1500 (DC input, current or voltage)(Decimal point place follows the selection.)

    [Factory adjusted as 0 C]

    This display is indicated only when the option [2AR or 2AL] is applied.

    PV/SV display mode

    Actual Main settingTemperature value

    Loop break alarm

    The alarm will be activated when the process variable (PV) does not rise as much as the span or greaterwithin the time it takes to assess the loop break alarm after the manipulating value has reached 100 % or

    the output high limit value.

    The alarm will also be activated when the process variable (PV) does not fall as much value as the span or

    greater within the time it takes to assess loop break alarm after the manipulating value has reached 0 % or

    the output low limit value.

    When the control action is Direct (Cooling), the alarm acts conversely.

  • 8/13/2019 CF1H_manual_V12_6351

    22/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 22 -

    (4)Auxi liary function set ting mode 1

    In PV/SV display mode, if the MODEkey is pressed for approx. 3 seconds while the key is being pressed,

    Auxiliary function setting mode 1 can be selected.

    The setting value can be increased or decreased by pressing the , and FASTkeys.

    If the MODEkey is pressed, the setting value is registered and the next setting item is selected.

    PV/SV display mode

    Actual Main setting

    Temperature value

    + MODEfor approx. 3 s

    Setting value lock Mode to lock the setting value to prevent error.

    designation The setting item to be locked depends on the designation.

    Designation

    MODE [Factory adjusted as Unlock status.]

    Unlock status. All setting values are changeable.

    None of the setting items can be changed.

    Only main setting value is changeable.

    All setting items can be changed, however, the

    value returns to the former value after the power

    off because the value is not written on the non volatile memory.

    This mode is used when changing the value temporarily.

    Since it has no relation to the memory life,

    it is suitable when the option [CR2 or CR5] is applied.

    Fuzzy self-tuning or Auto-tuning PID action will not

    function if [ ] or [ ] is designated.

    When designating Lock, designate Lock 1, 2 or 3 after

    setting the necessary items in the status Unlock.

  • 8/13/2019 CF1H_manual_V12_6351

    23/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 23 -

    As to the Lock mode 3

    When using the CF1H as a Fixed value cont roller.

    The setting values can temporarily be changed by the selected

    setting value memory number, however, when the number ischanged, the setting values changed by the previous number are

    canceled and returns to the former values.

    When using the CF1H as a Program controller.

    The setting values can temporarily be changed by the step

    number performing, however, when the step number is changed,

    the setting values are canceled and returns to the former values.

    Setting value change is null when the controller is waiting for

    running. The running starts by the values memorized.

    Main setting value Mode to set the high limit of main setting value.

    high limit setting (If scaling high limit value is changed,

    Setting value this setting value will be changed as well.)

    Setting range: Main setting value low limit to

    MODE scaling high limit value

    (The decimal point place follows the selection.)

    [Factory adjusted as 400 C]

    Main setting value Mode to set the low limit of main setting value.

    low limit setting (If scaling low limit value is changed,

    Setting value this setting value will be changed as well.)Setting range: Scaling low limit value to

    MODE main setting value high limit

    (The decimal point place follows the selection.)

    [Factory adjusted as 0 C]

    Sensor correction setting Mode to set the correct value of the sensor.

    Setting value Setting range: 100.0 100.0 C

    [Factory adjusted as 0.0 C]

    MODE

  • 8/13/2019 CF1H_manual_V12_6351

    24/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 24 -

    Sensor correction function

    Corrects the input value from the sensor. When a sensor cannot be set at a location

    where control is desired, the sensor measuring temperature may deviate from the

    temperature in the controlled location. When controlling with multiple controllers,

    the accuracy of sensors have influence on the control. Therefore, sometimes the

    measuring temperature (input value) does not concur with the same setting value.

    In such a case, the control can be set with desired temperature by shifting the input

    value of sensors.

    Overlap band/Dead band Mode to set the Overlap band and Dead band

    setting between Heating control output and Cooling control output.

    Setting value

    + setting value: Dead band

    MODE setting value : Overlap band

    Setting range: Heating proportional bandconverted value

    [Factory adjusted as 0.0 %, Indication: C]

    When the option [D 2] is not applied, or if setting the control

    action as ON/OFF, this display is not available.

    Remote/Local changing Mode to change the method (Remote or Local)

    Method to set the Main setting value.

    MODE [Factory adjusted as Local]

    Local status. The main setting value can be set

    by the front key operation as usual.

    Remote status. The main setting value can be

    set in analog value by the remote control from external operation.

    This display is available only when the option

    [EA or EV ] is applied.

    Instrument number setting Mode to set the Instrument number individually

    Setting value to each instrument when communicating by

    connecting plural instruments in serial communication.

    MODE

    Setting range: 0 95 [Factory adjusted as 0]

    This display is available only when the option [CR2 or CR5]

    is applied.

  • 8/13/2019 CF1H_manual_V12_6351

    25/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 25 -

    Transfer rate selection Mode to select a communication transfer rate

    Selection to meet the rate of the host computer.

    [Factory adjusted as 9600 bps]

    MODE

    2400 bps

    4800 bps

    9600 bps

    19200 bps

    This display is available only when the option [CR2 or CR5] is

    applied.

    Communication protocol Mode to select a communication protocol.

    Selection [Factory adjusted as ]

    WIKA standard protocol

    Based on Modbus, ASCII mode

    This display is available only when the option [CR2 or CR5]

    is applied.

    PV/SV display mode

    Actual Main settingTemperature value

  • 8/13/2019 CF1H_manual_V12_6351

    26/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 26 -

    (5)Auxi liary function set ting mode 2

    In PV/SV display mode, if the MODEkey is pressed for approx. 3 seconds while the

    and keys are being pressed, Auxiliary function setting mode 2 can be selected.

    The setting value can be increased or decreased by pressing the , and FASTkeys.If the MODEkey is pressed, the setting value is registered and the next setting item is selected.

    PV/SV display mode

    Actual Main setting

    Temperature value

    + + MODEfor approx. 3 s

    Scaling high limit setting Mode to set the high limit value of the scaling.

    Setting value If scaling high limit value is changed, main settinghigh limit value will be changed to the scaling

    MODE high limit value as well.

    Setting range: Scaling low limit value to

    input range maximum value

    [Factory adjusted as 1370 C]

    Scaling low limit setting Mode to set the low limit value of the scaling.

    Setting value If scaling low limit value is changed, main setting

    low limit value will be changed to the scaling

    MODE low limit value as well.Setting range: Input range minimum value to

    scaling high limit value

    [Factory adjusted as 200 C]

    Decimal point place selection Mode to select the Decimal point place.

    Selection [Factory adjusted as XXXX. (No decimal point)]

    MODE

    XXXX. (No decimal point)

    XXX.X (1-digit below the decimal point)

    XX.XX (2-digit below the decimal point)

    X.XXX (3-digit below the decimal point)

    This display is indicated only when the input

    type is selected to DC.

  • 8/13/2019 CF1H_manual_V12_6351

    27/75

  • 8/13/2019 CF1H_manual_V12_6351

    28/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 28 -

    Cooling action mode selection Mode to select the Cooling action,

    Selection Air cooling, Oil cooling or Water cooling.

    [Factory adjusted as Air cooling]MODE This display is indicated only when the option [D 2]

    is applied.

    Air cooling (linear characteristic)

    Oil cooling (The 1.5th power of Air cooling characteristic)

    Water cooling (The 2nd power of Air cooling characteristic)

    Cooling output Mode to set high limit value of the cooling output.

    high limit setting Setting range:

    Setting value Cooling output low limit value to 105 %

    Setting greater than 100 % is effective to the type

    MODE Current output.

    [Factory adjusted as 100 %]

    This display is not indicated when the option [D 2]

    is not applied, or when ON/OFF action of cooling side.

    Cooling output Mode to set the low limit value of the cooling output.

    low limit setting Setting range: 5 % to cooling output high limit value

    Setting value Setting less than 0 % is effective to the type Current output.

    [Factory adjusted as 0 %]

    MODE This display is not indicated when the option [D 2]

    is not applied or when ON/OFF action of cooling side.

    Cooling output ON/OFF Mode to set the ON/OFF action hysteresis of the

    action hysteresis setting cooling control output.Setting value Setting range: 0.1 100.0 C

    [Factory adjusted as 1.0 C]

    MODE This display is indicated when the ON/OFF action is

    designated in Control action designation and when the

    option [D 2] is applied.

  • 8/13/2019 CF1H_manual_V12_6351

    29/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 29 -

    Alarm 1 (A1) action Mode to select the action Energized or Deenergized

    Energized/Deenergized for Alarm 1.

    Selection [Factory adjusted as Energized]

    MODE This display is not indicated when the rotary switch is set to No. 0

    or No. 7 in Alarm 1 action designation (page 12).

    Energized

    Deenergized

    Alarm 2 (A2) action Mode to select the action Energized or Deenergized

    Energized/Deenergized for Alarm 2.

    Selection [Factory adjusted as Energized]

    MODE This display is not indicated when the rotary switch is set to No. 0

    or No. 7 in Alarm 2 action designation (page 12), or the option

    [2AS or 2AL] is not applied.

    Selection items: The same as those of the alarm 1 (A1) action

    Energized/Deenergized selection.

    Alarm 1 hysteresis setting Mode to set the hysteresis value for Alarm 1.

    Setting value Setting range: 0.1 100.0 C (for TC, RTD inputs)

    1 1000 (for DC input)

    MODE (Decimal point place follows the selection.)

    [Factory adjusted as 1.0 C]

    This display is not indicated when the rotary switch is set to No. 0

    or No. 7 in Alarm 1 action designation (page 12).

    Alarm 2 hysteresis setting Mode to set the hysteresis value for Alarm 2.

    Setting value Setting range: 0.1 100.0 C (for TC, RTD inputs)1 to 1000 (for DC input)

    MODE (Decimal point place follows the selection.)

    [Factory adjusted as 1.0 C]

    This display is not indicated when the option [2AS or 2AL] is not

    applied and when the rotary switch is set to No. 0 or No. 7 in Alarm 2

    action designation (page 12) even if the option [2AS or 2AL] is

    applied.

  • 8/13/2019 CF1H_manual_V12_6351

    30/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 30 -

    Alarm 1 (A1) action Mode to set the action delayed timer for Alarm 1.

    delayed timer setting Setting range: 0 999 9s

    Setting value [Factory adjusted as 0 s]Alarm output is turned on when the setting time has passed

    MODE after the input gets into the alarm output range.

    This display is not indicated if the rotary switch is set to

    No. 0 or No. 7 in Alarm 1 action designation (page 12).

    Alarm 2 (A2) action Mode to set the action delayed timer for Alarm 2.

    delayed timer setting Setting range: 0 9999 s

    Setting value [Factory adjusted as 0 s]

    Alarm output is turned on when the setting time has passed

    MODE after the input gets into the alarm output range.This display is not indicated when the option [2AS or 2AL] is not

    applied and when the rotary switch is set to No. 0 or No. 7 in

    Alarm 2 action designation even if the option [2AS or 2AL] is applied.

    External setting input Mode to set the high limit value of external setting input.

    high limit setting

    Setting value (In the case of Option [EA4] (4 20 mA), the value

    corresponds to 20 mA input.)

    MODE Setting range: External setting input low limit value

    to Input range maximum value[Factory adjusted as 400 C]

    This display is indicated only when the option

    [EA0, EA4, EV0 or EV1] is applied.

    External setting input Mode to set the low limit value of external setting

    low limit setting input.

    Setting value (In the case of Option [EA4] (4 20 mA), the value

    corresponds to 4 mA input.)

    MODE Setting range: Input range minimum value to

    External setting input high limit value[Factory adjusted as 0 C]

    This display is indicated only when the option

    [EA0, EA4, EV0 or EV1] is applied.

  • 8/13/2019 CF1H_manual_V12_6351

    31/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 31 -

    Transmission output selection Mode to select the type of Transmission output.

    Selection [Factory adjusted as PV transmission]

    This display is indicated only when the optionMODE [TA4 or TV1] is applied.

    Process variable (PV) transmission

    Main setting value (SV) transmission

    Manipulating value (MV) transmission

    Transmission output Mode to set the high limit value of Transmission

    high limit setting output.

    Setting value (In the case of option TA4, the value correponds

    to 20mA output.)

    MODE Setting range: Transmission output low limit value

    to Input range maximum value

    [Factory adjusted as 400 C]

    This display is indicated only when the option

    [TA4 or TV1] is applied.

    Transmission output when standby:

    PV PV, SV 0 value, MV 0 value

    Transmission output Mode to set the low limit value of Transmission

    low limit setting output.

    Setting value (In the case of option TA4, the value corresponds

    to 4mA output.)

    MODE Setting range: Input range minimum value to

    Transmission output high limit value

    [Factory adjusted as 0 C]

    This display is indicated only when the option

    [TA4 or TV1] is applied.

    Transmission output when standby:

    PV PV, SV 0 value, MV 0 value

  • 8/13/2019 CF1H_manual_V12_6351

    32/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 32 -

    Display selection when Mode to select the display when the control output is off.

    control output is off

    Selection [Factory adjusted as indicating OFF on the PV display]

    MODE

    OFF is indicated on the PV display.

    No indication (all unlit).

    Only PV is indicated.

    Main setting value Mode to set the rising rate of the main setting

    rising rate setting value. (Rising value per minute)

    Setting value Setting the value to 0 or 0.0 disables the function.

    MODE Setting range:

    0 9999 C/min. Thermocouple, except T and RTD without

    a decimal point

    0.0 999.9 C/min. Thermocouple T and RTD with

    a decimal point

    0 9999, DC input (Decimal point place follows

    the selection.)

    [Factory adjusted as 0C/min.]

    Main setting value Mode to set the falling rate of the main setting

    falling rate setting value. (Falling value per minute)

    Setting value Setting the value to 0 or 0.0 disables the function.

    MODE Setting range:

    0 9999 C/min. Thermocouple, except T and RTD without

    a decimal point

    0.0 999.9 C/min. Thermocouple T and RTD with

    a decimal point

    0 9999 DC input (Decimal point place follows

    the selection.)

    [Factory adjusted as 0 C/min.]

  • 8/13/2019 CF1H_manual_V12_6351

    33/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 33 -

    Output selection when Mode to select the control output OFF or not when

    input burnout DC input is over scale or under scale.

    Selected value

    MODE

    Control output OFF

    Control output ON

    [Factory adjusted as Control output ]

    PV/SV display modeActual Main setting

    temperature value

    Energized/Deenergized function

    [If the alarm action energized is selected]

    When the alarm output action indicator is lit, the alarm output (terminal - , - ) is conducted (ON).

    When the alarm output action indicator is unlit, the alarm output is not conducted (OFF).

    [If the alarm action deenergized is selected]

    When the alarm output action indicator is lit, the alarm output (terminal - , - ) is not

    conducted (OFF). When the alarm output action indicator is unlit, the alarm output is conducted (ON).

  • 8/13/2019 CF1H_manual_V12_6351

    34/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 34 -

    (6) Program mode

    In PV/SV display mode, if the key is pressed for approximately 3 seconds while the key is being

    pressed, the Program mode can be selected.

    The setting value can be increased or decreased by pressing the , and FASTkeys.If the MODEkey is pressed, the setting value is registered and the next setting item is selected.

    As to the setting values of the step 1 to 7, each setting value for setting value memory number 1 to 7 set

    during the Fixed value control is assigned respectively. For example, values in memory number 1 are

    assigned to the values for step 1, and number 2 for step 2.

    If the Pattern end output is designated and the program control is performed, the Pattern end output is

    turned on when the program is completed.

    When the Pattern end output is on and if the OUT/OFFkey is pressed, the Pattern end output is turned off. If theOUT/OFFkey is pressed again, the program will be performed.

    If some steps are unnecesary, set the times 00.00 for the step numbers not used.

    Program Example

    Step number (Settingvalue memory number)

    1 2 3 4 5 6 7

    Main setting value 500 500 1000 1000 200 200 100

    Proportional band 2.0 1.8 2.0 1.8 2.5 1.8 2.0

    Integral time 180 80 180 80 200 80 200

    Derivative time 30 20 30 20 50 20 50

    Proportional cycle 30 30 30 30 30 30 30

    Alarm 1 2 5 2 5 10 0 5

    Alarm 2 2 5 2 5 10 0 5Step time 00:30 01:00 00:40 01:00 02:00 00:30 01:00

    0

    500

    1000

  • 8/13/2019 CF1H_manual_V12_6351

    35/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 35 -

    PV/SV display mode

    Actual Main setting

    temperature value

    + for approx. 3 s

    Program control change Control form is changed between Fixed value

    Setting value of and Program.

    fixed value control

    MODE MODE In Fixed value control, if the MODEkey is pressed,

    the mode will revert to the PV/SV display mode.

    (Fixed value

    control)

    Fixed value control

    Program control

    [Factory adjusted as Fixed value control]

    Following dislay is available only when Program control.

    Step 1 Time setting Mode to set the Time for step 1.

    Setting value 00.00

    Minute indication

    MODE Hour indication

    For example, when setting 1 hour 58 minutes,

    set as [ ].

    Setting range: 00.00 99.59

    [Factory adjusted as 00.00]

    Step 2 Time setting Mode to set the Time for step 2.

    Setting value [The setting range and the factory adjusted value

    are the same as Step 1.]

    MODE

    Step 3 Time setting Mode to set the Time for step 3.

    Setting value [The setting range and the factory adjusted value

    are the same as Step 1.]

    MODE

    Step 4 Time setting Mode to set the Time for step 4.

    Setting value [The setting range and the factory adjusted value

    are the same as Step 1.]

    MODE

  • 8/13/2019 CF1H_manual_V12_6351

    36/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 36 -

    Step 5 Time setting Mode to set the Time for step 5.

    Setting value [The setting range and the factory adjusted value

    are the same as Step 1.]

    MODE

    Step 6 Time setting Mode to set the Time for step 6.

    Setting value [The setting range and the factory adjusted value

    are the same as Step 1.]

    MODE

    Step 7 Time setting Mode to set the Time for step 7.

    Setting value [The setting range and the factory adjusted valueare the same as Step 1.]

    MODE

    PV/SV display mode

    Actual Main setting

    temperature value

    (7) Auto/Manual contro l change

    A mode to change the output manipulating value by manual.

    In the case of proportional action, the manipulating value in proportion to the deviation

    is automatically generated. This is called an automatic control.

    As compared with the above, it is called manual control that the function to get the

    fixed amount of output by front key operation regardless of the deviation.

    This function provides the balanceless-bumpless function, not to change the output

    suddenly when the control mode is changed from automatic to manual and vice versa.

    Each time the AUTO/MANkey is pressed, the control form changes Auto Manual.

    PV/SV display mode Automatic controlActual Main setting

    temperature value

    AUTO/MAN

    Manual control Manual control (to set the Manipulating value by manual)

    Actual Manipulating

    temperature value Setting range: Main output low limit value to

    Main output high limit value

    AUTO/MANIf the option [D 2] is applied,

    Cooling output low limit value to

    Heating output high limit value

  • 8/13/2019 CF1H_manual_V12_6351

    37/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 37 -

    (8) Contro l output OFF function

    A function to turn the control output OFF even if the power to the instrument is supplied. The function is

    used when required to halt the control action or when the CF1H is not being used in multiple controllers.

    Control output OFF function can be selected from any mode by pressing the OUT/OFFkey for approx. 1

    second.The display is the same as when [Display selection when control output is off] is selected. (See page 32.)

    PV/SV display mode

    Actual Main setting

    temperature value

    OUT/OFFfor approx. 1 s [From any mode, as an example]

    Control output OFF functionOUT

    /OFF1 s Cooling action mode selection(*) [Unlit] Selection

    OUT/OFFfor approx. 1 s

    (*): PV display indicates [OFF indication], [No indication] or

    [Only PV] selected in Display selection when control output is off (page 32).

    NoticesOnce the Control output OFF function is enabled, the function cannot be released

    even if the power to the instrument is turned OFF and turned ON again.

    To cancel the function, press the OUT/OFFkey again for approx. 1 second.

    In the program control, the Control output OFF function cannot be used because

    the OUT/OFFkey functions as Program Start/Stop key.

  • 8/13/2019 CF1H_manual_V12_6351

    38/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 38 -

    (9) Output manipulating value and Step rest time ind ication mode

    In the PV/SV display mode, press the MODEkey for approx. 3 seconds.

    The display will be changed to main setting mode in the process, however, keep

    pressing it until the Output manipulating value is displayed.If the MODEkey is pressed again, the mode reverts to the PV/SV display.

    During program control, if the MODEkey is pressed in Output manipulating value

    indication, the Step rest time indication will be selected.

    If the MODEkey is pressed again, the mode reverts to the PV/SV display.

    PV/SV display mode

    Actual Main setting

    temperature value

    MODEfor approx. 3 s

    Output manipulating

    value indication mode

    Actual manipulating Manipulating value is indicated on the SV display

    temperature value by the blinking the decimal point and the MV indicator is lit.

    MODE MODE

    (Fixed value (Program control)control)

    Step rest time indication

    Actual Step Step rest time is indicated on the SV display,

    temperature rest time and the TIME indicator is lit.

    MODE

  • 8/13/2019 CF1H_manual_V12_6351

    39/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 39 -

    5. Setting value memory function [Option code: SM7]If the option [SM7] is applied, a maximum of 7 files of data can be memorized, and when selecting a desired

    file, the desired control can be performed.

    In one (1) file are 14 kinds of data: Main setting value, PID each value, Cooling control proportional band

    value, Alarm setting values (A1 to A4), Overlap band/Dead band value, Main output high limit, Main output

    low limit, Cooling output high limit and Cooling output low limit can be memorized and selected.

    To select the setting value memory number (File number), connect the terminals between each of 13to 16

    as shown below table.

    Up to approximately 50 units of CF1H can be connected in parallel.

    Terminal connection table for Setting value memory number selectionSetting valuememory No.

    Connectingterminal

    1 2 3 4 5 6 7

    13 - 16(b0-COM) C O C O C O C

    14 - 16(b1-COM) O C C O O C C15 - 16(b2-COM) O O O C C C C

    C: Closed O: Open

    When the Setting value memory number is selected by external operation,

    the number cannot be selected by front key operation.

    When selecting the memory number by front key operation, all terminals

    (b0, b1, b2and COM) should be open.

    Memory number cannot be changed during setting mode or PID auto-tuning.

    Setting value memory funct ion operating procedure(1) In the PV/SV display mode, select the setting value memory number by

    connecting the terminals.

    (2) In the setting mode, set each setting value; Main setting, PID each value,

    Cooling control proportional band value, Alarm setting values (A1 and A2),

    Overlap band/Dead band value, Main output high limit, Main output low

    limit, Cooling output high limit, Cooling output low limit.

    (3) After setting, press the MODEkey to revert to the PV/SV display mode.

    RegistrationThe setting data is registered to the file whose number is indicatedon the Setting value memory number display.

    When the number is called up, the selected number by terminal connectionis displayed, and the control is performed by the data (setting value) of the file.

    To change the setting values, repeat the operation above-mentioned, and

    the values will be changed to new values.

  • 8/13/2019 CF1H_manual_V12_6351

    40/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 40 -

    6 RunningAfter the controller has been mounted to the control panel and wiring is

    completed, it can be started in the following manner.

    6.1 When using the CF1H as a Temperature cont rol ler

    (1) Turn the power suppl y to the CF1H ON.

    For approx. 2s after the power is switched ON, the type of sensor and the unit

    designated in Sensor input designation (page 10, 11) will be indicated on the

    PV display, and the rated maximum value will be indicated on the SV display.

    See [table 6.1-1].

    During this time, all outputs and LED indicators are in their OFF status.

    After that, the display turns to the PV/SV display.

    When the Control output OFF function is working, the item selected in

    Display selection when control output is off is displayed on the PV display.

    (See page 32.)

    [Table 6.1-1]

    C FInput

    PV display SV display PV display SV display

    K

    J

    R

    B

    PL-ll

    N

    SE

    T

    C

    Pt100

    JPt100

    Pt100

    4 20 mA DC

    0 20 mA DC

    0 1 V DC

    Scaling highlimit value

    Scaling highlimit value

    (2) Inpu t the sett ing value, referring t o Chapter 4. Operations (page 13ff).

    When controlling by Fuzzy self-tuning PID action, designate [Perform] in the

    Auto-tuning Perform/Cancel function to start the control in optimum conditions.

    (3) Turn the load circuit power ON.

    Starts the control action so as to keep the controlled object at the main setting value.

  • 8/13/2019 CF1H_manual_V12_6351

    41/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 41 -

    6.2 When using the CF1H as a simp lified p rogram control ler

    (1) Turn the pow er supply to the CF1H on.

    For approx. 2s after the power is turned ON, the type of sensor and the unit designated in Sensor input

    designation (page 12, 13) are indicated on the PV display, and the rated maximum value is indicated on

    the SV display.

    See [table 6.1-1].

    During this time, all outputs and LED indicators are in their OFF status.

    After that, the display reverts to the PV/SV display.

    When the Control output OFF function is working, the item selected in Display selection when control

    output is off is displayed on the PV display. (See page 32.)

    (2) Input each setting value and each step timereferring to Chapter 4. Operations

    (page 13ff), especially page 17 (Setting value memory) and page 35 (Program control

    change, Step time setting). Then the PV display will indicate the actual temperature

    and the status turns standby.(3) Turn the load ci rcu it power ON.

    (4) Program control start

    If Automatic start is designated in the Program start Auto/Manual designation (page 10), it will switch to

    warm-up status for approx. 2 seconds after the power is turned on, and then will automatically start the

    program control from step 1.

    If Manual start is designated in Program start Auto/Manual designation (page 10), it will switch to

    warm-up status for approx. 2 seconds after the power is turned on, and then it reverts to standby status.

    In this status, if the OUT/OFFkey is pressed, it starts the program control from the step 1.

    While the program control is being performed, the change of Step number (by Setting value memory

    number) is ineffective.

    To make the step time progress faster.

    The step time progress becomes 60 times as fast as usual when the FASTkey is pressed.

    To end the program cont rol during the process.

    The program control is ended if the OUT/OFFkey is pressed for approx. 1 second or longer.

    To change the displays.

    In the PV/SV display, if the MODEkey is pressed for approximately 3 seconds, the Output manipulating

    value display mode is activated, and if the MODEkey is pressed again, the Step rest time display will be

    indicated (see page 38.).

    Instrument status when power failure is restored.

    When power is restored after a power failure occurs during program control, the CF1H performs theprogram continuously.

    The PV display blinks until the step at which the power failure occurs is finished.

  • 8/13/2019 CF1H_manual_V12_6351

    42/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 42 -

    7 Action explanations7.1 Standard action drawings

    (*1) Cycle action is performed according to deviation.

    (*2) Changes continuously according to deviation.

    7.2 Heater burnout alarm action d rawing

    Action Heating (reverse) action

    Control

    action

    Cooling (direct) action

    ON

    OFF

    Proportional band

    Setting

    ON

    OFF

    Proportional band

    Setting

    Output

    Relaycontact

    Non-contact

    voltage

    Current

    5

    4

    6

    H

    C

    L

    (*1)

    5

    4

    6

    H

    C

    L

    5

    4

    6

    H

    C

    L

    5

    4

    6

    H

    C

    L

    5

    4

    6

    H

    C

    L

    5

    4

    6

    H

    C

    L

    (*1)

    5

    6

    12Vdc

    + 5

    6

    12/0Vdc

    +5

    6

    0Vdc

    + 5

    6

    0Vdc

    + 5

    6

    0/12Vdc

    + 5

    6

    12Vdc

    +

    (*1)(*1)

    5

    6

    20mAdc

    + 5

    6

    20 to 4mAdc

    +5

    6

    4mAdc

    + 5

    6

    4mAdc

    + 5

    6

    4 to 20mAdc

    + 5

    6

    20mAdc

    +

    (*2)(*2)

    [OUT1] Green

    Indicator

    Lit Unlit LitUnlit

    ON

    OFF

    Setting

    Small LargeLoad current UnlitLit

  • 8/13/2019 CF1H_manual_V12_6351

    43/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 43 -

    7.3 ON/OFF action drawings

    part: Acts ON or OFF.

    7.4 Pattern end action drawing

    Pattern end output is turned ON when the program control is ended, and it is not released until theOUT/OFFkey is pressed.

    Act ion Heating (reverse) action

    Control

    action

    Cooling (direct) action

    ON

    OFF

    Hysteresis

    Main setting

    Output

    Relayc

    ontact

    Non-contact

    voltage

    Current

    5

    4

    6

    5

    4

    6

    5

    4

    6

    5

    4

    6

    5

    6

    12Vdc

    + 5

    6

    0Vdc

    + 5

    6

    0Vdc

    + 5

    6

    12Vdc

    +

    5

    6

    20mAdc

    + 5

    6

    4mAdc

    + 5

    6

    4mAdc

    + 5

    6

    20mAdc

    +

    [OUT1] Green

    Indicator

    Lit Unlit LitUnlit

    ON

    OFF

    Main setting

    Hysteresis

    ON

    OFF

    [Time] UnlitLit

    Program control end Pattern end output isreleased by pressingthe OUT/

    OFFkey.

    9

    10

    9

    10

    9

    10

    Unlit

  • 8/13/2019 CF1H_manual_V12_6351

    44/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 44 -

    7.5 HeatingCooling action drawings [Option D 2]

    Heating (reverse) action in Heating control

    (*1) Cycle action is performed according to deviation.

    (*2) Changes continuously according to deviation.

    Action

    Relaycontact

    Non-contactvoltage

    Current

    5

    4

    6

    5

    4

    6

    5

    4

    6

    5

    6

    12Vdc

    +5

    6

    0Vdc

    +

    5

    6

    20mAdc

    + 5

    6

    4mAdc

    +

    [OUT1] Green

    Indicator

    Lit Unlit

    Setting

    Heating (Cooling)

    HHH

    CCC

    LLL

    (*1)

    5

    6

    12/0Vdc

    +

    (*1)

    (*2)

    5

    6

    20 to 4mAdc

    +

    Heating P-band (Cooling P-band)

    Heatingoutput

  • 8/13/2019 CF1H_manual_V12_6351

    45/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 45 -

    Cooling (direct) action in Heating control

    (*1) Cycle action is performed according to deviation.

    (*2) Changes continuously according to deviation.

    Action

    Relay

    contact

    Non-contactvoltage

    Current

    0Vdc

    +

    12Vdc

    +

    4mAdc

    +

    20mAdc

    +

    [OUT2] Yellow

    Indicator

    LitUnlit

    Setting

    (Heating) Cooling

    0/12Vdc

    +

    (*1)

    (*2)

    4 to 20mAdc

    +

    (Heating P-band) Cooling P-band

    Coolingoutput

    8

    7

    8

    7

    (*1)

    8

    7

    8

    77

    8

    7

    8

    8

    77

    8

    7

    8

  • 8/13/2019 CF1H_manual_V12_6351

    46/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 46 -

    Heating (reverse) action in Cooling contro l

    (*1) Cycle action is performed according to deviation.(*2) Changes continuously according to deviation.

    Action

    Relay

    contact

    Non-contactvoltage

    Current

    5

    4

    6

    5

    4

    6

    5

    4

    6

    5

    6

    0Vdc

    +5

    6

    12Vdc

    +

    5

    6

    4mAdc

    + 5

    6

    20mAdc

    +

    [OUT1] Green

    Indicator

    LitUnlit

    Setting

    Heating(Cooling)

    HHH

    CCC

    LLL

    (*1)

    5

    6

    0/12Vdc

    +

    (*1)

    (*2)

    5

    6

    4 to 20mAdc

    +

    Heating P-band(Cooling P-band)

    Heatingoutput

  • 8/13/2019 CF1H_manual_V12_6351

    47/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 47 -

    Cooling (direct) action in Cooling control

    (*1) Cycle action is performed according to deviation.

    (*2) Changes continuously according to deviation.

    Action

    Relay

    contact

    Non-contactvoltage

    Current

    12Vdc

    +

    0Vdc

    +

    20mAdc

    +

    4mAdc

    +

    [OUT2] Yellow

    Indicator

    Lit Unlit

    Setting

    (Heating)

    12/0Vdc

    +

    (*1)

    (*2)

    20 to 4mAdc

    +

    (Heating P-band)Cooling P-band

    Coolingoutput

    8

    7

    8

    7

    (*1)

    8

    7

    8

    77

    8

    7

    8

    8

    77

    8

    7

    8

    Cooling

  • 8/13/2019 CF1H_manual_V12_6351

    48/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 48 -

    When setting Dead band

    (*1) Cycle action is performed according to deviation.

    (*2) Changes continuously according to deviation.

    Action Heating act ion

    Control action

    Cooling action

    Proportional band

    Setting

    Output

    Relay

    contact

    Non-contactvoltage

    Current

    5

    4

    6

    (*1)

    5

    4

    6

    5

    4

    6

    (*1)

    5

    6

    12Vdc

    + 5

    6

    12/0Vdc

    + 5

    6

    0Vdc

    +

    0Vdc

    +

    0/12Vdc

    +

    12Vdc

    +

    (*1)(*1)

    5

    6

    20mAdc

    +

    5

    6

    20 to 4 mAdc

    +

    5

    6

    4mAdc

    +

    4mAdc

    +

    4 to 20mAdc

    +

    20mAdc

    +

    (*2)(*2)

    [OUT1] Green

    Indicator

    Lit Unlit

    Dead band Proportional band

    8

    7

    8

    7

    8

    7

    7

    8

    7 7

    8 8

    777

    8 8 8

    [OUT2] Yellow Unlit Lit

    Indicator

  • 8/13/2019 CF1H_manual_V12_6351

    49/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 49 -

    When setting Overlap band with Relay contact output .

    (*1) Cycle action is performed according to deviation.

    Control action

    Setting

    Relay

    contact

    output

    5

    4

    6

    (*1)

    5

    4

    6

    5

    4

    6

    (*1)

    [OUT1] Green

    Indicator

    Lit Unlit

    Overlap band

    Cooling proportional band

    8

    7

    8

    7

    8

    7

    [OUT2] Yellow Unlit Lit

    Indicator

    Heating

    output

    Cooling

    output

    Heating proportional band

  • 8/13/2019 CF1H_manual_V12_6351

    50/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 50 -

    7.6 Alarm 1 (A1) and 2 (A2) action drawings

    Standby function works at part.

    and shows the action point of the alarm output.

    Output terminals for Alarm 2: 7 - 8

    Temperature

    alarm action

    LitUnlit

    Output

    Indication

    High limit alarm Low limit alarm

    9

    10

    9

    10

    Hysteresis

    ON

    OFF

    Mainsetting

    Alarmsetting

    ON

    OFF

    Mainsetting

    Alarmsetting

    Hysteresis

    Lit Unlit

    9

    10

    9

    10

    Temperature

    alarm action

    LitUnlit

    Output

    Indication

    High limit alarm with standby Low limit alarm with standby

    9

    10

    9

    10

    Hysteresis

    ON

    OFF

    Mainsetting

    Alarmsetting

    ON

    OFF

    Mainsetting

    Alarmsetting

    Hysteresis

    Lit Unlit

    9

    10

    9

    10

    Temperature

    alarm action

    Output

    Indication

    High/Low limits alarm High/Low limit range alarm

    Alarmsetting

    Hysteresis

    LitUnlit

    9

    10

    9

    10

    ON

    OFF

    Mainsetting

    Alarmsetting

    Hysteresis

    ON

    OFF

    Mainsetting

    Alarmsetting

    Alarmsetting

    9

    10

    UnlitLit Unlit

    9

    10

    9

    10

    9

    10

    Lit

  • 8/13/2019 CF1H_manual_V12_6351

    51/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 51 -

    Standby function works at part.

    and shows the action point of the alarm output.

    Output terminals for Alarm 2: 7 8

    Temperature

    alarm action

    Output

    Indication

    High/Low limits alarm with standby

    Temperature

    alarm action

    LitUnlit

    Output

    Indication

    Process high alarm Process low alarm

    9

    10

    9

    10

    Hysteresis

    ON

    OFF

    Alarmsetting

    ON

    OFF

    Alarmsetting

    Hysteresis

    Lit Unlit

    9

    10

    9

    10

    Temperature

    alarm action

    Output

    Indication

    Process high alarm with standby Process low alarm with standby

    High/Low limit range alarm with standby

    ON

    OFF

    Mainsetting

    Alarmsetting

    Hysteresis

    Alarmsetting

    Hysteresis

    LitUnlit

    9

    10

    9

    10

    ON

    OFF

    Mainsetting

    Alarmsetting

    Alarmsetting

    9

    10

    UnlitLit Unlit

    9

    10

    9

    10

    9

    10

    Lit

    Lit

    9

    10

    9

    10

    Hysteresis

    ON

    OFF

    Alarmsetting

    ON

    OFF

    Alarmsetting

    Hysteresis

    Lit Unlit

    9

    10

    9

    10

    Unlit

  • 8/13/2019 CF1H_manual_V12_6351

    52/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 52 -

    8. Control actions8.1 Fuzzy self-tuning

    Fuzzy self-tuning is a function to perform a fine adjustment of PID values automatically. The stable

    control can be carried out even if the conditions of the process are changed due to things like changein types and rates of production.

    (1) When the control is rising, the controller performs the control by the PID

    values tuned in advance.

    (2) When the control result is disordered by the disturbance or a change in the process, the controller

    checks the converging status, and performs a fine adjustment of PID values if necessary.

    (a) If the convergence is performed smoothly, the PID values are not changed.

    (b) If the convergent speed is slow, the controller corrects the PID values

    to accelerate the convergence.

    (c) When overshoot is generated during the convergence, the controller corrects

    the PID values so as not to generate the overshoot.

    (d) When hunting is generated, the controller checks the waveform and performs

    a fine adjustment of PID values.

    (3) The controller can be used without Fuzzy self-tuning by designating the internal switch.

    (4) When using the controller for the first time, performing the PID auto-tuning

    or setting the proper PID values by key operation is recommended.

    The instrument is always in self-tuning status itself, and when deviation is created, it starts the tuning.

    Even if in Fuzzy self-tuning status, when very large hunting is caused and the control is not stabilized,

    it starts auto-tuning automatically.

    When the auto-tuning performance is designated by the key operation, tuning is initiated, and when the

    control is stabilized, the auto-tuning is released and returns to self-tuning status.

    When lock mode [ ] or [ ] is designated, Fuzzy self-tuning

    or Auto-tuning PID action cannot work.

    With the control system in which load fluctuation periodically occurs,

    the Fuzzy self-tuning may fall into malfunction.

    In such a case, use the controller with the PID auto-tuning mode.

  • 8/13/2019 CF1H_manual_V12_6351

    53/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 53 -

    8.2 Explanations of PID

    (1) Proportional band (P)

    Proportional action is the action which the control output varies in proportion to the deviation between

    the setting value and the processing temperature.If the proportional band is narrowed, even if the output changes by a slight variation of the processing

    temperature, better control results can be obtained as the offset decreases.

    However, if when the proportional band is narrowed too much, even slight disturbances may cause

    variation in the processing temperature, and control action changes to ON/OFF action and the so

    called hunting phenomenon occurs.

    Therefore, when the processing temperature comes to the balanced position near the setting value

    and a constant temperature is maintained, the most suitable value is selected by gradually narrowing

    the proportional band while observing the control results.

    (2) Integral time (I)

    Integral action is used to eliminate offset. When the integral time is shortened, the returning speed to

    the setting point is quickened. However, the cycle of oscillation is also quickened and the control

    becomes unstable.

    (3) Derivative time (D)

    Derivative action is used to restore the change in the processing temperature according to the rate of

    change. It reduces the amplitude of overshoot and undershoot width.

    If the derivative time is shortened, restoring value becomes small, and if the derivative time is made

    longer, an excessive returning phenomenon may occur and the control system may be oscillated.

  • 8/13/2019 CF1H_manual_V12_6351

    54/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 54 -

    8.3 PID auto-tuning o f this controllerIn order to decide each value of P, I, D and ARW automatically, this systemgives the fluctuation to the controlling object by force.

    (1) When the difference between setting value and proc essing temperature

    is l arge when the temperature rises.Fluctuation is given at the temperature 1.5 % of scaling span less than the setting value.

    (2) When the control is stable or when control temperature is w ithin 1.5 %of scaling span.Fluctuation is given at the setting value.

    (3) When the contro l temperature is 1.5 % or greater of scaling span higherthan the setting value.

    Fluctuation is given at the temperature 1.5 % of scaling span higher than the setting value.

    1.5% of scaling span

    Controlling action is performedwith the values set by PIDauto-tuning.

    Setting value

    Time

    Temperature

    [Figure 8.3-1]

    Temperature

    Setting value

    Time

    Controlling action is performedwith the values set by PIDauto-tuning.

    [Figure 8.3-3]

    1.5% of scaling span

    Temperature

    Setting value

    Starting point of auto-tuning

    [Figure 8.3-2]Time

    Controlling action is performedwith the values set by PIDauto-tuning.

  • 8/13/2019 CF1H_manual_V12_6351

    55/75

    Operating Instructions Temperature Indicating Controller CF1H

    V 1.2 01/2007 - 55 -

    9. Other functions(1) Burnout alarm

    (Upscale)

    When the thermocouple or RTD is burnt out or the input value exceeds

    [Rated scale maximum value +1 % of rated scale span], the control outputis turned OFF(main output low limit value for the current output type)

    and the PV display blinks [ ].

    With the input RTD Pt100 (F), if the input value is greater than 999.9, the

    PV display blinks [ ], however, the control is performed to