Workshop 3 Room Temperature Study WS3-1 ANSYS, Inc. Proprietary © 2009 ANSYS, Inc. All rights reserved. April 28, 2009 Inventory #002599 Introduction to CFX
Transcript
Page 1: CFX Intro 12.0 WS3 Room Study

Workshop 3

Room Temperature Study

WS3-1ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

Introduction to CFX

Page 2: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementIntroduction

In this workshop you will be analyzing the effect of computers and workers on the temperature distribution in an office. In the first stage airflow through the supply air ducts will be simulated and the outlet conditions for the duct will be used to set the inlet conditions for the room. Although both components could be analyzed together, separating the two components allows different room configurations to be analyzed without solving the duct flow again.

WS3-2ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

Page 3: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementDuct Simulation

• The operating conditions for the flow are:

• The working fluid is Air Ideal Gas• Fluid Temperature = 21 [C]• Inlet: 0 [atm] Total Pressure• Outlet: 0.225 [kg/s] (per vent)

WS3-3ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

Inlet

vent1

vent2

Page 4: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementStarting CFX in Workbench

1. Open Workbench2. Drag CFX into the Project Schematic from the Component Systems

toolbox3. Change the name of the system to duct4. Save the project as RoomStudy.wbpj in an appropriate directory5. Double-click Setup

WS3-4ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

Page 5: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementImport Mesh

1. Right-click on Mesh in the Outline tree and select Import Mesh > ICEM CFD

2. Select the file duct_mesh.cfx53. Make sure Mesh Units are in m and click Open to import the mesh

The first step is to import the mesh that has already been created:

WS3-5ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

Page 6: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementCreate Domain

1. Double-click on Default Domain in the Outline tree to edit the domain2. On the Basic Settings tab, set the Fluid 1 Material setting to Air Ideal

Gas3. Switch to the Fluid Models tab4. Set the Heat Transfer Option to Isothermal

You can now create the computational domain:

WS3-6ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

4. Set the Heat Transfer Option to Isothermal– Heat Transfer is not modeled, but since the working fluid is an ideal gas

we need to provide a temperature so its properties can be calculated

5. Set the Fluid Temperature to 21 [C]6. Change the Turbulence Model Option to Shear Stress Transport7. Click OK to commit the changes to the domain

Page 7: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementCreate Boundary Conditions

1. INLET Boundary Condition– Name: INLET– Boundary Type: Inlet– Location: INLET– Mass and Momentum Option:

Total Pressure (stable)

Now create the following boundary conditions:

2. VENT1 Boundary Condition– Name: VENT1– Boundary Type: Outlet– Location: VENT1– Mass and Momentum Option:

Mass Flow Rate

WS3-7ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

– Relative Pressure: 0 [Pa]

3. VENT2 Boundary Condition– Name: VENT2– Boundary Type: Outlet– Location: VENT2– Mass and Momentum Option:

Mass Flow Rate– Mass Flow Rate: 0.225 [kg/s]

– Mass Flow Rate: 0.225 [kg/s]

Page 8: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementSolver Control

1. Double click on Solver Control from the Outline tree2. Enable the Conservation Target toggle

The default Conservation Target is 1%. This means that the global imbalance for each equation must be less than 1% (i.e. (flux in – flux out)/flux in < 1%). The solver will not stop until both the Residual Target and the Conservation Target have

WS3-8ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

3. Click OK to commit the settings

both the Residual Target and the Conservation Target have been met (or Max. Iterations is reached).

Page 9: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementMonitor Point

1. Double click on Output Control from the Outline tree2. Switch to the Monitor tab and enable the Monitor Options toggle

Monitor points are used to monitor quantities of interest during the solution. They should be used to help judge convergence. In this case you will monitor the velocity of the air that exits through the vent. One measure of a converged solution is when this air has reached a steady-state velocity.

WS3-9ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

2. Switch to the Monitor tab and enable the Monitor Options toggle3. Under Monitor Points and Expressions, click the New icon4. Keep the default name Monitor Point 15. Set the Option to Expression

Page 10: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementMonitor Point

6. In the Expression Value field, type in:areaAve(Velocity w)@VENT1

WS3-10ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

7. Click OK to create the Monitor Point

Page 11: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementWrite Solver File

1. Close CFX-Pre to return to Project window2. Save the project3. Right-click on Solution and select Edit4. Choose Start Run

You can now save the project and proceed to write a definition file for the solver:

WS3-11ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

4. Choose Start Run

Page 12: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop Supplement

1. Examine the residual plots for Momentum and Mass and Turbulence2. Examine the User Points plot

CFX Solver Manager

Monitor point

Residual plot

WS3-12ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

3. When the run finished close the Solver Manager4. View the results in CFD-Post by double-clicking Results in the Project

window

Page 13: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementCFD-Post

1. Select File > Export2. Change the file name to vent1.csv3. Use the browse icon to set an appropriate

directory4. Set as and as

Now we will export a Boundary Condition profile from the outlet regions for use in the next simulation.

WS3-13ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

4. Set Type as BC Profile and Locations as VENT1

5. Leave Profile Type as Inlet Velocity and click Save

6. Similarly export a BC profile of VENT2 to the file named vent2.csv

7. Quit CFD-Post and return to the Project Schematic

Page 14: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementOperating Conditions

• The working fluid is Air Ideal Gas• Computer Monitor Temperature = 30 [C]• Computer Vent Flow Rate: 0.033 [kg/s] @ 40 [C] (per computer)• Ceiling Vents: Profile Data, Temperature=21 [C]

The operating conditions for the flow in the room are:

WS3-14ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

outlet

vent1

vent2

Page 15: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementStarting Room Simulation in Workbench

1. Drag CFX into the Project Schematic from the Component Systemstoolbox

2. Change the name of the system to room3. Double-click Setup in the room system

WS3-15ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

Page 16: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementImport Mesh

1. Right-click on Mesh in the Outline tree and select Import Mesh > ICEM CFD

2. Select the file room.cfx53. Make sure the Mesh Units are in m and click Open to import the mesh

The first step is to import the mesh that has already been created:

WS3-16ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

Page 17: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementCreate Domain

1. Edit Default Domain from the Outline tree2. On the Basic Settings tab, set the Fluid 1 Material setting to Air Ideal

Gas3. Set the Buoyancy Option to Buoyant. Set the Buoyancy settings as

shown:• Gravity X Dirn. = 0 [ m s^-2 ]

You can now create the computational domain:

WS3-17ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

• Gravity X Dirn. = 0 [ m s^-2 ]• Gravity Y Dirn. = 0 [ m s^-2 ]• Gravity Z Dirn. = -g (first, click the Enter Expression icon )• Buoy. Ref. Density = 1.185 [ kg m^-3 ]

Enabling Buoyancy allows for natural convection due to density variations. The buoyancy force is a function of density variations relative to the buoyancy reference density. Since density variations can be very small, using a reference density help avoid round-off errors. The reference density should be a typical fluid density in the domain.

Page 18: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementCreate Domain

4. Switch to the Fluid Models tab5. Change the Heat Transfer Option to Thermal Energy6. Change the Turbulence Model Option to Shear Stress Transport7. Switch to the Initialisation tab8. Check the Domain Initialisation box 9. Set the Temperature Option to Automatic with Value. Set the

Temperature to 21 [C]

WS3-18ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

Temperature to 21 [C]

10. Click OK to commit the changes to the domain

For most cases, setting an initial condition for domain temperature is not necessary since the solver can automatically calculate initial conditions. However, if you input a value that is closer to the final solution than what the solver would automatically calculate, you will reach a converged solution faster.

Page 19: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementProfile data initialization

1. Select Tools >Initialise Profile Data and choose the Data File as vent1.csv. Click OK

– CFX-Pre reads the file and creates functions that point to the variables available in the file (see the User Functions section in the Outline tree). Boundary conditions can be set by referencing these functions. E.g.

WS3-19ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

referencing these functions. E.g. VENT1.Velocity u(x,y,z) refers to the Velocity u value in the VENT1 function with the local coordinate values x, y and z passed in as the arguments. Any value with the correct dimensions can be passed in as an argument, but usually the local coordinates are used.

2. Similarly initialise profile data for vent 2 by choosing vent2.csv

Page 20: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementCreate Boundary Conditions

1. vent1 Boundary Condition– Name: vent1– Boundary Type: Inlet– Location: VENT1– Select Use Profile Data and choose

VENT1 as the Profile Name

Now create the following boundary conditions:

WS3-20ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

– Click Generate Values– This will create expressions for the

Mass and Momentum option on the Boundary Details tab that reference the profile functions

– On the Boundary Details tab check that the expressions make sense

– Heat Transfer Option: Static Temperature

– Static Temperature: 21 [C]

Page 21: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop Supplement

2. vent2 Boundary Condition– Name: vent2– Boundary Type: Inlet– Location: VENT2– Select Use Profile Data and choose VENT2 as the Profile Name– Click Generate Values

• The Mass and Momentum Option will be automatically updated

– Heat Transfer Option: Static Temperature

Create Boundary Conditions

WS3-21ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

– Heat Transfer Option: Static Temperature– Static Temperature: 21 [C]

3. workers Boundary Condition– Name: workers– Boundary Type: Wall– Location: WORKERS– Heat Transfer Option: Temperature– Fixed Temperature: 37 [C]

Page 22: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop Supplement

4. outlet Boundary Condition– Name: outlet– Boundary Type: Opening– Location: OUTLET– Mass and Momentum Option: Opening Pres. and Dirn– Relative Pressure: 0 [Pa]– Heat Transfer Option: Opening Temperature

Create Boundary Conditions

WS3-22ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

– Heat Transfer Option: Opening Temperature– Opening Temperature: 21 [C]

5. monitors Boundary Condition– Name: monitors– Boundary Type: Wall– Location: monitors– Heat Transfer Option: Temperature– Fixed Temperature: 30 [C]

Page 23: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop Supplement

6. computerVent Boundary Condition– Name: computerVent– Boundary Type: Inlet– Location: COMPUTER1VENT, COMPUTER2VENT,

COMPUTER3VENT, COMPUTER4VENT– Mass and Momentum Option: Mass Flow Rate– Mass Flow Rate: 0.132 [kg/s]– Heat Transfer Option: Static Temperature

Create Boundary Conditions

WS3-23ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

– Heat Transfer Option: Static Temperature– Static Temperature: 40 [C]

Page 24: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop Supplement

7. computerIntake Boundary Condition– Name: computerIntake– Boundary Type: Outlet– Location: COMPUTER1INTAKE, COMPUTER2INTAKE,

COMPUTER3INTAKE, COMPUTER4INTAKE– Mass and Momentum Option: Mass Flow Rate– Mass Flow Rate: 0.132 [kg/s]– Mass Flow Update Option: Constant Flux

Create Boundary Conditions

WS3-24ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

– Mass Flow Update Option: Constant Flux• This enforces a uniform mass flow across the entire boundary region, rather

than letting a natural velocity profile develop. It is used here to make sure the flow rate through each intake is the same.

Page 25: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementSolver Control

1. Edit Solver Control from the Outline tree– Due to nature of this flow it will take a long time for a steady-state condition

to be reached

2. Increase the Max. Iterations to 750

3. Change the Timescale Control to Physical Timescale

WS3-25ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

4. Set a Physical Timescale of 2 [s]

5. Enable the Conservation Target toggle

6. Click OK to commit the settings

Page 26: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementMonitor Point

1. Edit Output Control from the Outline tree

Monitor points are used to monitor quantities of interest during the solution. They should be used to help judge convergence. In this case you will monitor the temperature of the air that exits through the outlet. One measure of a converged solution is when this air has reached a steady-state temperature.

WS3-26ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

1. Edit Output Control from the Outline tree2. Switch to the Monitor tab and enable the Monitor Options toggle3. Under Monitor Points and Expressions, click the New icon4. Enter the Name as temp5. Set the Option to Expression

Page 27: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementMonitor Point

6. In the Expression Value field, type in:massFlowAve(Temperature)@outlet

WS3-27ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

7. Click OK to create the Monitor Point

Page 28: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementWrite Solver File

1. Close CFX-Pre to return to the Project window and save the project

You can now save the project and proceed to write a definition file for the Solver:

The solution will take several hours to solve on one processor. To save time, a results file is provided with this workshop. The Project Schematic shows that the room Solution has not been completed, so

WS3-28ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

2. Select File > Import from the main menu in Workbench3. Set the file filter to CFX-Solver Results File4. Select the results file provided with this workshop, room_001.res5. Change the name of the system to room results …

Schematic shows that the room Solution has not been completed, so you cannot view the results in CFD-Post yet. To view the results for the file provided you’ll need to add the results to the project.

Page 29: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementProject Schematic

WS3-29ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

Page 30: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementCFX Solver Manager

1. Right-click on Solution in the room results system and select Display Monitors

2. Examine the residual plots for Momentum and Mass, Heat Transfer and Turbulence• The Residual Target of 1e-4 was met at about 270 iterations, but the solver

Now you can view the solution for the previously solved case.

WS3-30ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

• The Residual Target of 1e-4 was met at about 270 iterations, but the solver did not stop because the Conservation Target had not been met

3. Examine the User Points plot• Air temperature leaving through the outlet did not start to reach a steady

temperature until >650 iterations. Using residuals as the only convergence criteria is not always sufficient.

Page 31: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementResidual and Monitor plot

WS3-31ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

Residual plot Monitor points

Page 32: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementCFX Solver Manager

6. Check the Domain Imbalances at the end of the .out file for each equation• You can right click in the text monitor, select Find… and search for

“Domain Imbalance” to find the appropriate section• An imbalance is given for the U-Mom, V-Mom, W-Mom, P-Mass and H-

Energy equations• It took 653 iterations to satisfy the Conservation Target of 1% for the H-

Energy equation – see the Plot Monitor 1 tab

WS3-32ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

Energy equation – see the Plot Monitor 1 tab

7. Close the Solver Manager

8. View the results in CFD-Post by double-clicking Results in the Project Schematic from the room system

Page 33: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementCFD-Post

1. Select Location > Plane from the toolbar

2. In the Details windows on the Geometry tab, set the Definition Method to ZX Plane

3. Set Y to 1.2 [m]

Start by creating a ZX Plane at Y = 1.2 [m]

WS3-33ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

3. Set Y to 1.2 [m]

4. On the Colour tab set Mode to Variable

5. Set Variable to Temperature

6. Set Range to Local and click Apply• Observe the temperature distribution (for example, how the warm air

collects under the table)

Page 34: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementCFD-Post

1. ZX Plane at Y = 2 [m]

2. ZX Plane at Y = 5.1 [m]

Using the same procedure, create several other planes displaying the temperature profile:

WS3-34ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

3. XY Plane at Z = 0.25 [m]

4. When finished observing the temperature distribution, uncheck the visibility boxes of the planes that you created

Page 35: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementCFD-Post

1. Click Insert > Vector from the main menu

2. In the Details windows on the Geometry tab, set Location to Plane 2 and Symbols Size to 3.0 in Symbol tab

Plot vector plots on the planes that you created:

WS3-35ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

3. Click Apply

4. After observing the flow behavior on Plane 2, switch the Location to Plane 4

Page 36: CFX Intro 12.0 WS3 Room Study

WS3: Room Temperature Study

Workshop SupplementFurther Steps (Optional)

1. Observe the density variation at various planes

2. Create a streamline from each of the vents• You may want to adjust the values on the Limits tab (Max. Segments)

Time permitting, you may want to try the following:

WS3-36ANSYS, Inc. Proprietary© 2009 ANSYS, Inc. All rights reserved.

April 28, 2009Inventory #002599

3. Animate the streamlines• Right-click on the Streamlines in the 3D viewer and select Animate

4. Create an isosurface based on different temperatures (e.g., 22 [C], 24 [C], etc.)

5. Calculate the areaAve of Wall Heat Flux on the workers• Click Tools > Function Calculator