NOTE! To the installer: Please make sure you provide this manual to the owner of the equip ment or to the responsible party who maintains the system.
MODELS CGL-01SW, CGL-01DW (2HP, 208V, 1PH)CGL-21SW, CGL-21DW (2HP, 230V, 1PH)CGL(LD)-21SW, CGL(LD)-21DW (2HP, 230V, 1PH)CGL-23SW, CGL-23DW (2HP, 208-230V, 3PH)CGL-43SW, CGL-43DW (2HP, 460V, 3PH)CGL CONTROL PANELSINSTALLATION AND SERVICE MANUAL For Simplex and Duplex.
Part # 23833A150 | © 2012 Pentair Pump Group, Inc. | 11/08/12
23833A150 11/08/12 2
CALIFORNIA PROPOSITION 65 WARNING:
This product and related accessories contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.
INDOOR USELocate the control box in a convenient location, preferably close to the pump installation. The box may be secured to a wall or other stable vertical support by use of the four mounting holes located in the mounting feet on the top and bottom of the box.
The box should be mounted approximately 5 feet from the floor to the circuit breaker handle. Care should be taken to avoid mounting the control box under sweating pipes, faucets or other damp locations.
OUTDOOR USEThe control box may be mounted at the location of the pump and basin or may be mounted in a remote location. The box should be secured to a stable vertical support which in turn should be secured to a concrete basin or footer. The box could also be mounted to the side of the house or other stationary support if available within a reasonable distance. When selecting a location, you should consider the visibility of the alarm light.
The box may be secured by the use of four mounting holes located in the mounting feet on the top and bottom of the box. The box should be mounted approximately 5 feet from the ground to the circuit breaker handle.
LOCATION AND MOUNTING
POWER SUPPLY
WARNINGDo not attempt to wire this control box unless you have a good working knowledge of electricity and are familiar with state and local codes. If you are in doubt about anything, contact an electrician.
The power supply for the control box will vary depending upon which particular model you have purchased. Do not attempt to operate this unit on any other voltage or power distribution other than what it was originally designed. Failure to comply with this will result in the immediate cancellation of all warranties and claims.It is advisable to put the pump on its own circuit using a circuit breaker adequately sized to protect the pump. Check state and local codes for the correct wire size and circuit protection to use. The wire should be sized large enough to handle the full load current of both pumps you are operating, and any voltage drop that might occur due to long service runs.
Run power supply lines to the control box and secure (knockouts are not supplied in this box). Select a convenient location on the bottom to enter the box with the power supply. Cut a hole with a chassis punch, caution should be taken not to get fiberglass chips in the components while cutting hole. After the hole is cut, any fiberglass particles must be removed from box. Failure to do so may result in premature component failure.
Connect incoming power to the circuit breaker top lugs and all necessary ground wires to the ground lug at the bottom of the box. The ground lug should be fastened to a good driven earth ground by one of the methods described in the National Electric Code.
NOTE: On single phase panels, the neutral terminal block (labeled “N” and located next to the circuit breaker) must be connected to the incoming power neutral line. If the incoming power does not have a neutral line, then the neutral terminal block should be jumpered to the ground lug.
23833A150 11/08/123
PUMP CORDRun the wires from both pumps to the bottom of the control box by means of one of the methods described in your pump or basin installation instructions. A hole must be cut into the control box (use the same procedure as that described for incoming power supply lines).Connect red, white and black wires to terminals marked M1, M2 and M3 (for 3 phase applications), or connect the red, white and black wires to terminals marked R, W and B (for 1 phase applications). Fasten green wire to ground lug.WGL pumps may have an additional brown wire in the pump cord. This is for the seal leak probe and it
should be connected to the terminal strip in the control box. See wiring diagram for the proper terminal connections.NOTE: On 3 phase installations check for proper pump rotation. See the “ROTATION OF 3 PHASE PUMPS” section in this manual.FLOAT CORDSSee basin instructions for the proper depth at which to set the floats. Strip the float cord wires 3/8", twist strands together, and connect black and white wires to terminal strip in the control box. See wiring diagram for proper terminal connections.
CONNECTING PUMPS AND FLOATS TO CONTROL BOX
OPERATING PUMPS 1. Make sure that all wires are inside the control box and not in a position to be pinched or shorted when the door is closed.2. Turn on power to the control box.3. Turn hand-off-auto switches to the “HAND” position. The pumps should start and the pump run lights should come on. (On duplex panels, this should be done for both pumps).4. To put into service, put the hand-off-auto switch in the “AUTO” position. (On duplex panels, this
should be done fore both pumps). See basin instructions.5. If unit does not operate as described, see troubleshooting chart.
NOTE: Addition of electrical components and circuitry to this unit is expressly forbidden unless written factory authorization is obtained. Failure to do so will result in warranty cancellation.
ROTATION OF THREE PHASE PUMPS IMPORTANTRotation of three phase pumps must be established by one of the two methods described below.CAUTIONKeep hands and feet clear of impeller when checking rotation. Be sure to disconnect power to the control box while handling pumps. Make sure pump is wired and readied for rotation test before the control box is energized. 1. Before positioning pump in basin, run wires to control box. Lay the pump unit on its side and secure so that the starting torque of the motor will not cause the pump to roll. Energize the pump by turning the circuit breaker on and the hand-off-auto to “HAND”. The rotation should be counterclockwise as observed facing the bottom of the pump.
If you do not get the proper rotation, disconnect the power to the control box and change the position of any two of the black motor leads in the terminal blocks.2. Install the pump in the basin and run in some water so the pump can operate. Energize the pump by turning the circuit breaker on and the hand-of-auto switch to “HAND”. Let the pump pull the water down in the basin, and when the water reaches the bottom of the pump the rotation of the water can be observed. The water should rotate in a clockwise direction if the pump rotation is correct.
If you do not get the proper rotation, disconnect the power to the control box and change the position of any two of the black motor leads in the terminal blocks.
23833A150 11/08/12 4
CHECKING PUMP CURRENT DRAW1 PHASE PUMPS1. Use an amprobe to check the amperage of the pump.2. Turn the hand-off-auto switch to the “HAND” position and compare the amperage reading to the values shown on the chart. (See page 9).3. If you get a reading of 0, make sure there is voltage to the motor leads. Push the Klixon overload reset button in the control panel. the on winding overload may be tripped. Wait 15 minutes and try again. If you still do not get a reading, either the motor has failed or there might be a wiring problem between the control panel and pump (improper connection in the junction box).
3 PHASE PUMPS1. Use an amprobe to check the amperage of any of the power leads going to the pump.2. Turn the hand-off-auto switch to the “HAND” position and compare the amperage reading to the values shown on the chart.
3. If you get a reading of 0, make sure there is voltage to the motor leads. Push the overload reset button on the overload relay in the control panel. If you still do not get a reading either the motor has failed or there might be a wiring problem between the control panel and pump (improper connection in the junction box).4. If you get high amperage readings on 2 wires and a zero reading on the third, you have a single phase condition which could be caused by one of the following: A. One motor lead is not connected properly. B. You have lost 1 phase of the 3 phase power coming into the panel. C. One winding in the motor is open.
CHECKING PUMP AND FLOAT RESISTANCETO CHECK PUMP OR FLOAT, DISCONNECT INCOMING POWER AND REMOVE WIRES
FROM THE TERMINAL BLOCK AND WITH AN OHMMETER CHECK THE MEASUREMENTS PER CHART.
CORD ITEM CORRECT OHMMETER IF YOU GET ANY OTHER READING MEASURED MEASURED READING SETTING CHECK FOR THE FOLLOWING:
(See Chart) R x 1 Damaged winding or cord
(See Chart) R x 1 Damaged winding or cord
Infinity to 200 R x 100K
Infinity to 200 R x 100K
Infinity to 200 R x 100K Water in float or damaged cord
R x 1 Switch has failed or damaged cord
NOTE: Readings may vary slightly depending on length of wire running to the motor and the accuracy of the measurement instrument.
Power Motor Winding Cord (1 Phase)
Power Motor Winding Cord (3 Phase)
Power Ground to Motor Winding Cord (Green to Red, Black or White)
Power Ground to Seal Probe (Opt.) Cord (Green to Brown)
Float Ground to Float Contacts Cord (Green to Black or White)
Float Float Contacts Cord (Black to White)
0 - Float On Infinity-Float Off
Damaged winding or cordmoisture in motor
Water in seal chamber ordamaged cord
23833A150 11/08/125
TESTING COMPONENTS IN CONTROL BOXWARNINGTo prevent electrical shock, disconnect power entering the control box and turn the circuit breaker in the control box to the “OFF” position.CONTRACTOR1. Physically examine the contractor for badly burnt or sticking contacts. The contractor arm should move in and out freely.2. Remove the wires on the coil to the contactor and measure the resistance. Zero the ohmmeter, and on the R x 1 scale you should read approximately 138 ohms.3. Often a burnt coil can be spotted by merely looking to see if it is badly discolored or has a dark spot on it.TRANSFORMER (3 PHASE PANELS ONLY)208 VOLT1. Remove the wires from the primary side (H3-H4) and also from the secondary side (X2-XF-X1).2. With an ohmmeter on the R x 1 scale touch terminals H3 and H4 (primary), you should get a reading of approximately 15.6 ohms for Simplex panels, and 5.8 ohms for Duplex panels.3. With an ohmmeter on the R x 1 scale touch terminals X2 and X1 (secondary), you should get a reading of approximately 3.6 ohms for Simplex panels and 1.6 ohms for Duplex panels.4. With an ohmmeter on the R x 1 scale touch terminals XF and X1, you should get a reading of 0. If you do not, replace the fuse.
230 VOLT1. Remove the wires from the primary side (H2-H4) and also from the secondary side (X2-XF-X1).2. With an ohmmeter on the R x 1 scale touch terminals H2 and H4 (primary), you should get a reading of approximately 14 ohms for Simplex panels, and 6.5 ohms for Duplex panels.3. With an ohmmeter on the R x 1 scale touch terminals X2 and X1 (secondary), you should get a reading of approximately 3.6 ohms for Simplex panels and 1.6 ohms for Duplex panels.4. With an ohmmeter on the R x 1 scale touch terminals XF and X1, you should get a reading of 0. If you do not, replace the fuse.
460 VOLT1. Remove the wires from the primary side (H1-H4) and also from the secondary side (X2-XF-X1).2. With an ohmmeter on the R x 1 scale touch terminals H1 and H4 (primary), you should get a reading of approximately 49.7 ohms for Simplex panels, and 21.5 ohms for Duplex panels.
3. With an ohmmeter on the R x 1 scale touch terminals X2 and X1 (secondary), you should get a reading of approximately 3.6 ohms for Simplex panels and 1.6 ohms for Duplex panels.4. With an ohmmeter on the R x 1 scale touch terminals XF and X1, you should get a reading of 0. If you do not, replace the fuse.
OVERLOAD BLOCK (3 PHASE PANELS ONLY)1. Remove the wires from the terminals on the side of the overload block.2. With an ohmmeter on the R x 1 scale touch the two terminals, you should get a reading of 0. If you do not get this reading, push the large black reset button on the front of the overload block.3. You may test the inner switching mechanism by pushing the small black button on the front of the overload block to trip the switch and pushing the large black button to reset it. If the inner switch does not work properly replace the overload block.
OVERLOAD HEATERS (3 PHASE PANELS ONLY)1. Remove the heaters from the overload block and examine them for physical damage. A slight discoloration is normal, but if they are melted or warped they should be replaced.
FUSES1. Pull the fuse out of the fuse block and check for continuity with an ohmmeter.2. With an ohmmeter on the R x 1 scale, you should get a reading of 0. If you do not, replace it with the same type and rating that is shown on the decal located next to the fuse block.
OVERRIDE RELAY (DUPLEX PANELS ONLY)1. Physically examine the relay for burnt or stuck contacts and for a burnt or discolored coil.2. Remove the relay from the socket and with an ohmmeter on R x 1000 scale, you should read approximately 7.68 ohms on pins 13 and 14.
Often a burnt coil can be spotted by merely looking to see if it is badly discolored or has a dark spot on it.
ALARM LIGHT1. The light should activate when the alarm float con- nections are jumpered, if not replace the light bulb.
ALTERNATOR RELAY (DUPLEX PANELS ONLY)1. When power is on and the relay is functioning properly, one of the two lights on top of the relay should be on.2. With circuit breaker turned “off”, remove relay from socket. With an ohmmeter on the R x 1000 scale, touch the alternator coil terminals. The “black” lead
23833A150 11/08/12 6
TESTING COMPONENTS IN CONTROL BOX should be on pin 3, and the “red” lead should be on pin 5. You should have a reading of approximately 920-1020 ohms.3. If alternator shows physical damage or does not test properly, replace it.
KLIXON OVERLOAD (1 PHASE PANELS ONLY)1. Remove black wire from the bottom of contactor and the white wire from the “B” terminal for the pump.Clip ohmmeter leads to the black and white wires and with the ohmmeter on R x 1, you should have a reading of 0. If you do not, push in on the reset button and check again. If you still do not read 0, replace overload.
START AND RUN CAPACITORNOTE: A good sign of a failed capacitor is a bulged or swollen enclosure, leaking oil or a burnt smell. This is true on both types of capacitors. 1. With power shut off, short the terminals of the capacitors together with a screwdriver or jumper cables. This will discharge any voltage stored in the capacitor.2. Remove the wires from the ends of the capacitor.3. Set the ohmmeter on R x 10,000 (10K) and adjust needle to zero, after clipping the ohmmeter leads together.4. Clip one lead to one side of the capacitor terminal
and touch the other lead to the other capacitor terminal. If the capacitor is good, the needle will go towards zero and then drift slowly towards infinity. If the ohmmeter does not read as described, the capacitor is bad and must be replaced.5. If the capacity is checked a second time, be sure to reverse the ohmmeter leads to get a correct reading.
START RELAY1. With the power shut off, disconnect the wires going to the relay.2. Set the ohmmeter to R x 1,000 and adjust the needle to zero, after clipping the ohmmeter leads together.3. Check the resistance between terminals 1 and 2 on the relay. If the relay is good, the ohmmeter will read 0.4. Check the resistance between terminals 2 and 5. The ohmmeter should read approximately 6,000 ohms. If it reads 0 or infinity, the relay is bad.
NOTE: The relay can check good according to the above test and still not work properly. The contacts between terminals 1 and 2, that disconnect the start winding, may be stuck or burnt together, keeping the winding in the circuit until the overload trips. If this happens, replace the relay.
23833A150 11/08/127
TROUBLESHOOTING CHART(SIMPLEX PANELS)
Pos
ition
Han
d-
A
uto
Run
Pro
blem
S
witc
h Li
ght
Che
ck
Pum
p
Doe
s N
ot
Aut
o O
n H
-I
Turn
Off
Han
d O
ff A
-C-B
-
Pum
p
D
-F
Doe
s N
ot
R
un
A
uto
Off
A-F
-C-B
-
E-
D-H
Aut
o
O
r O
n G
-I
H
and
A
larm
A
ctiv
ates
Aut
o O
ff A
-H-D
-F
C
ircui
t A
uto-
B
reak
er
Off-
O
ff F-
J
Trip
ped
Han
d
Fu
se in
A
uto-
Con
trol C
ircui
t O
ff-
Off
G-H
-K-I
B
low
n H
and
C
ontro
l A
uto-
O
n
Box
O
ff-
Or
L
Buz
zes
Han
d O
ff
C
AU
SE
R
EM
ED
Y
A M
otor
ove
rload
trip
ped.
(1
PH
AS
E O
NLY
) Res
et b
y pu
shin
g K
lixon
ove
rload
rese
t but
ton.
If o
verlo
ad
trip
s ag
ain,
che
ck p
ower
sup
ply
volta
ge. C
heck
mot
or w
indi
ng re
sist
ance
, mak
e
sure
pum
p sh
aft i
s no
t loc
ked.
(3
PH
AS
E O
NLY
) Res
et b
y pu
shin
g ov
erlo
ad re
set b
utto
n. If
ove
rload
doe
s no
t
trip
aga
in p
robl
em m
ay b
e fix
ed. I
f ove
rload
trip
s ag
ain,
che
ck p
ower
sup
ply
vo
ltage
. Che
ck m
otor
win
ding
resi
stan
ce, m
ake
sure
pum
p sh
aft i
s no
t loc
ked.
B
Trip
ped
circ
uit b
reak
er o
r R
eset
bre
aker
s or
repl
ace
fuse
s. If
they
con
tinue
to b
low
, che
ck a
mp
capa
city
of
fuse
at p
ower
sup
ply
wire
and
bre
aker
s. M
ake
sure
it is
wire
d pr
oper
ly a
nd th
at y
ou h
ave
the
corr
ect
pane
l. po
wer
sup
ply
syst
em. (
See
inst
ruct
ions
“P
ower
Sup
ply”
).
C
Trip
ped
circ
uit b
reak
er
Res
et b
y pu
shin
g ha
ndle
dow
n to
“O
FF”
posi
tion
and
rese
ttin
g to
“O
N”
posi
tion.
in c
ontr
ol p
anel
. M
ake
sure
that
wire
s ar
e no
t sho
rted
and
that
the
box
is w
ired
prop
erly
.
D
Con
trol
circ
uit f
use
blow
n.
Che
ck fu
se p
er in
stru
ctio
ns. R
epla
ce fu
se w
ith s
ame
type
and
ratin
g.
E
Lev
el in
bas
in m
ay n
ot b
e C
heck
bas
in. R
un p
ump
man
ually
to s
ee if
pum
p op
erat
es p
rope
rly.
high
eno
ugh
to tu
rn
sw
itch
on.
F
May
not
be
wire
d pr
oper
ly.
Che
ck w
iring
per
wiri
ng d
iagr
am. M
ake
sure
pum
p is
con
nect
ed to
term
inal
bl
ock
prop
erly
.
G
Too
muc
h w
ater
com
ing
Red
uce
wat
er fl
ow. P
ump
may
nee
d se
rvic
ing.
into
bas
in.
H
Flo
at s
witc
h m
ay h
ave
Ope
rate
man
ually
to s
ee if
bas
in p
umps
dow
n an
d al
arm
goe
s of
f. R
epai
r floa
t if
faile
d.
nece
ssar
y.
I
Pum
p or
dis
char
ge li
ne
Pul
l pum
p an
d ch
eck
disc
harg
e lin
e an
d pu
mp
inle
t. (C
AU
TIO
N: N
ever
put
may
be
plug
ged.
ha
nds
on g
rinde
r im
pelle
r unl
ess
pow
er is
turn
ed o
ff).
J
May
be
shor
t circ
uit i
n C
heck
wiri
ng. (
Sho
rt w
ill n
ot b
e lo
cate
d in
con
trol
cuc
uit u
nles
s co
ntro
l circ
uit
wiri
ng o
r pum
p po
wer
fu
se is
blo
wn)
. Che
ck m
otor
. (S
ee c
hart
for c
heck
ing
pum
p ca
bles
).
su
pply
–Sho
rt in
mot
or.
K
May
be
faile
d co
mpo
nent
C
heck
com
pone
nts
per i
nstr
uctio
ns.
oper
atin
g co
il.
L
Wro
ng o
pera
ting
volta
ge
Che
ck v
olta
ge a
nd m
ake
sure
rela
ys a
nd c
onta
ctor
s ar
e of
pro
per v
olta
ge.
or w
rong
vol
tage
com
pone
nts.
23833A150 11/08/12 8
TROUBLESHOOTING CHART(DUPLEX PANELS)
C
AU
SE
R
EM
ED
Y
A M
otor
ove
rload
trip
ped.
(1
PH
AS
E O
NLY
) Res
et b
y pu
shin
g K
lixon
ove
rload
rese
t but
ton.
If o
verlo
ad
trip
s ag
ain,
che
ck p
ower
sup
ply
volta
ge. C
heck
mot
or w
indi
ng re
sist
ance
, mak
e
sure
pum
p sh
aft i
s no
t loc
ked.
(3
PH
AS
E O
NLY
) Res
et b
y pu
shin
g ov
erlo
ad re
set b
utto
n. If
ove
rload
doe
s no
t
trip
aga
in p
robl
em m
ay b
e fix
ed. I
f ove
rload
trip
s ag
ain,
che
ck p
ower
sup
ply
vo
ltage
. Che
ck m
otor
win
ding
resi
stan
ce, m
ake
sure
pum
p sh
aft i
s no
t loc
ked.
B
Trip
ped
circ
uit b
reak
er o
r R
eset
bre
aker
s or
repl
ace
fuse
s. If
they
con
tinue
to b
low
, che
ck a
mp
capa
city
of
fuse
at p
ower
sup
ply
pane
l. w
ire a
nd b
reak
ers.
Mak
e su
re it
is w
ired
prop
erly
and
that
you
hav
e th
e co
rrec
t
–
wro
ng s
uppl
y vo
ltage
po
wer
sup
ply
syst
em. (
See
inst
ruct
ions
“P
ower
Sup
ply”
).
C
Trip
ped
circ
uit b
reak
er
Res
et b
y pu
shin
g ha
ndle
dow
n to
“O
FF”
posi
tion
and
rese
ttin
g to
“O
N”
posi
tion.
in c
ontr
ol p
anel
. M
ake
sure
that
wire
s ar
e no
t sho
rted
and
that
the
box
is w
ired
prop
erly
.
D
Ove
rrid
e re
lay
not w
orki
ng
Try
oper
atin
g bo
th p
umps
in “
HA
ND
” po
sitio
n. If
the
run
light
com
es o
n an
d
pr
oper
ly
pum
ps o
pera
te p
rope
rly, r
epla
ce o
verr
ide
rela
y.
E
Con
trol
circ
uit f
use
blow
n.
Che
ck fu
se p
er in
stru
ctio
ns. R
epla
ce fu
se w
ith s
ame
type
and
ratin
g.
F
Leve
l in
basi
n m
ay n
ot b
e C
heck
bas
in. R
un p
ump
man
ually
to s
ee if
pum
p op
erat
es p
rope
rly.
high
eno
ugh
to tu
rn
sw
itch
on.
G
May
not
be
wire
d pr
oper
ly.
Che
ck w
iring
per
wiri
ng d
iagr
am. M
ake
sure
pum
p is
con
nect
ed to
term
inal
bl
ock
prop
erly
.
H
Too
muc
h w
ater
com
ing
Red
uce
wat
er fl
ow. P
ump
may
nee
d se
rvic
ing.
into
bas
in.
I
Floa
t sw
itch
may
hav
e O
pera
te m
anua
lly to
see
if b
asin
pum
ps d
own
and
alar
m g
oes
off.
Rep
air fl
oat i
f
fa
iled.
ne
cess
ary.
J
Pum
p or
dis
char
ge li
ne
Pul
l pum
p an
d ch
eck
disc
harg
e lin
e an
d pu
mp
inle
t. (C
AU
TIO
N: N
ever
put
may
be
plug
ged.
ha
nds
on g
rinde
r im
pelle
r unl
ess
pow
er is
turn
ed o
ff).
K
May
be
faile
d co
mpo
nent
C
heck
com
pone
nts
per i
nstr
uctio
ns.
oper
atin
g co
il.
L
Wro
ng o
pera
ting
volta
ge
Che
ck v
olta
ge a
nd m
ake
sure
rela
ys a
nd c
onta
ctor
s ar
e of
pro
per v
olta
ge.
or w
rong
vol
tage
com
pone
nts.
M
May
not
be
lead
pum
p in
Le
t floa
t sw
itche
s cy
cle
basi
n to
see
if a
ltern
ator
is a
ltern
atin
g pu
mps
. If n
ot
al
tern
atin
g ph
ase
—
chec
k al
tern
ator
rela
y pe
r ins
truc
tions
.
al
tern
ator
may
not
be
wor
king
pro
perly
.
N
May
be
shor
t in
circ
uit i
n C
heck
wiri
ng. (
Sho
rt w
ill n
ot b
e lo
cate
d in
con
trol
circ
uit u
nles
s co
ntro
l circ
uit
wiri
ng o
r pum
p po
wer
fu
se is
blo
wn)
. Che
ck m
otor
. (S
ee c
hart
for c
heck
ing
pum
p ca
bles
).
su
pply
—S
hort
in m
otor
.
Pos
ition
Han
d-
A
uto
Run
Pro
blem
S
witc
h Li
ght
Che
ck
H
and
On
G-A
-L-K
Han
d O
ff C
-E-B
-G
Aut
o O
n A
-G-L
-K
Aut
o O
ff
Han
d O
n A
-G-K
Han
d O
ff C
-G-L
Aut
o O
n A
-G-K
-L
Aut
o O
ff M
-F-G
B
oth
Aut
o Li
ghts
H
-I-J
O
n
Aut
o
G-D
Aut
o
E-L
C
ircui
t A
uto-
Bre
aker
O
ff-
Off
G-N
Tr
ippe
d H
and
Fu
se in
A
uto-
C
ontro
l Circ
uit
Off-
O
ff H
-I-J
-K
Blo
wn
Han
d
C
ontro
l A
uto-
O
n
Box
O
ff-
or
L
Buz
zes
Han
d O
ff
Pum
p1
AN
D 2
Will
Not
Run
Pum
p1
OR
2W
ill N
ot R
un
Ala
rmA
ctiv
ates
F-I-
C-
B-E
-G
Onl
yO
neLi
ght
On
No
Run
Ligh
t O
n
23833A150 11/08/129
PUMP CURRENT DRAW, WINDING RESISTANCEOVERLOAD HEATER SELECTION*
RESISTANCE MODEL HP VOLTAGE PHASE RPM F.L.A. L.R.A. BLK-WH BLK-RED WH-RED HEATER HEATER NO.
WGL20-01 2 208 1 3450 15.0 52.5 1.14-1.26 4.63-5.11 5.77-6.37 — — WGL20-21 2 230 1 3450 12.5 44.0 1.46-1.62 7.20-8.00 8.66-9.62 — —
WGL20-03 2 208 3 3450 9.5 34.0 2.65-2.93 2.65-2.93 2.65-2.93 K50 13621A091 WGL20-23 2 230 3 3450 8.4 32.5 3.12-3.45 3.12-3.45 3.12-3.45 K49 13621A062 WGL20-43 2 460 3 3450 4.2 16.3 12.5-13.8 12.5-13.8 12.5-13.8 K34 13621A104
*WARNING: On 3 phase panels, overload heater elements are not factory installed in the overload relay. Elements must be purchased separately and correspond with the above chart. This must be done before the panel is put into service. Failure to install the elements before the panel is put into service, or failure to install the correct size elements, may result in pump failure. All pump and panel warranties will be void if the above guidelines are not followed
NOTICE
All standard CGL (Simplex) Series control panels manufactured afterJuly 1, 1993 will have the following changes:
Previous Part No. New Part No. Pump Run 21973A002 (Holder) 21973A013 Light Ass’y. 21974A001 (Bulb) Seal Leak 21973A001 (Holder) 21973A012 Light Ass’y. 21974A001 (Bulb)
USE COPPER WIRE ONLY
OVERLOAD
PUSH INTO RESET
PUMP
AUTO
OFF
HAND
SEALLEAK
LIGHT
LIGHT
PUMPRUN
GRD.
1 2 3 4 5 6 7 R W B
1 AM
P, 23
0V, A
BC-1
ALAR
M C
IRCU
IT F
USE
1 AM
P, 23
0V, A
BC-1
CONT
ROL
CIRC
UIT
FUSE
23833A150 11/08/12 10
USE COPPER WIRE ONLY
OVERLOAD
PUSH INTO RESET
PUMP
AUTO
OFF
HAND
SEALLEAK
LIGHT
LIGHT
PUMPRUN
GRD.
1 2 3 4 5 6 7 R W B
1 AM
P, 23
0V, A
BC-1
ALAR
M C
IRCU
IT F
USE
1 AM
P, 23
0V, A
BC-1
CONT
ROL
CIRC
UIT
FUSE
13-3/8
10
5/16 DIA.
15-5/1614-5/8
15-1/2
7-23/32
ENCLOSURE(21981C106A)
U.L. LABEL
WIRING DIAGRAM
ALARM LIGHT(22000A020 OR 22000A011)FLASHER
(22002A001)END SECTION(21996A000)
TERMINAL BLK.(21995A000)
CIRCUIT BREAKER(21985A001)
BACK PANEL(21981C110A) START RELAY
(21990A000)
CAPACITOR BRACKET (2)(21989A002)
MOUNTING BRACKET(21997B024)START CAPACITOR(12141A005)KLIXON OVERLOAD(20704A008)
TOGGLE SWITCH(21979A003)LIGHT ASSEMBLY(21973A002)LIGHT BULB (2)(21974A001)RUN CAPACITOR(23185A000)LIGHT ASSEMBLY(21973A001)
END SECTION(21996A000)
GROUND LUG(21994A001)
TERMINAL BLK. (10)(21995A000)
CONTACTOR(22914A005)
FUSE (2)(20514A009)
FUSE HOLDER (2)(21991A001)CAT. NO. CGL-021SW
23833A150 11/08/1211
USE COPPER WIRE ONLY
OVERLOAD
PUSH INTO RESET
PUMP
AUTO
OFF
HAND LIGHT
PUMPRUN
GRD.
1 2 3 4 5 6 R W B
1 AM
P, 23
0V, A
BC-1
ALAR
M C
IRCU
IT F
USE
1 AM
P, 23
0V, A
BC-1
CONT
ROL
CIRC
UIT
FUSE
13-3/8
10
5/16 DIA.
15-5/1614-5/8
15-1/2
7-23/32
ENCLOSURE(21981C106A)
U.L. LABEL
WIRING DIAGRAM
ALARM LIGHT(22000A020 OR 22000A011)FLASHER
(22002A001)END SECTION(21996A000)
TERMINAL BLK.(21995A000)
CIRCUIT BREAKER(21985A001)
BACK PANEL(21981C110A) START RELAY
(21990A000)
CAPACITOR BRACKET (2)(21989A002)
MOUNTING BRACKET(21997B024)START CAPACITOR(12141A005)KLIXON OVERLOAD(20704A008)
TOGGLE SWITCH(21979A003)LIGHT ASSEMBLY(21973A002)LIGHT BULB(21974A001)RUN CAPACITOR(23185A000)
END SECTION(21996A000)
GROUND LUG(21994A001)
TERMINAL BLK. (9)(21995A000)
CONTACTOR(22914A005)
FUSE (2)(20514A009)
FUSE HOLDER (2)(21991A001)CAT. NO. CGL(LD)-21SW
23833A150 11/08/12 12
PUMP
AUTO
OFF
HAND LIGHT
PUMPRUN
GRD.
1 2 3 4 5 6 7 M1 M2 M3
1 AM
P, 25
0V, A
BC-1
ALAR
M C
IRCU
IT F
USE
LIGHT
SEALLEAK
1 AMP, 250V, FNM-1CONTROL CIRCUIT FUSE
15-27/64
12
5/16 DIA.
17-7/1616-3/4
17-1/2
7-11/16
ENCLOSURE(21981C107A)
U.L. LABEL
WIRING DIAGRAM
ALARM LIGHT(22000A020 OR 22000A011)
FLASHER(22002A001)
CIRCUIT BREAKER(21985A003)
BACK PANEL(21981C111A)
MOUNTING BRACKET(21997B022)
TOGGLE SWITCH(21979A003)
LIGHT ASSEMBLY(21973A002)
LIGHT BULB (2)(21974A001)
FUSE HOLDER(21991A001)
FUSE(20514A000)
TRANSFORMER(22053A010)
FUSE(22514A007)
TERMINAL BLK. (10)(21995A000)
FUSE (2)(20514A014)
AUX. CONTACT(22913A010)
CAT. NO. CGL-23SW
LIGHT ASSEMBLY(21973A001)
GROUND LUG(21994A001)
END SECTION(21996A000)
MAGNETIC STARTER(24024A008)
23833A150 11/08/1213
PUMP
AUTO
OFF
HAND LIGHT
PUMPRUN
GRD.
1 2 3 4 5 6 7 M1 M2 M3
1 AM
P, 25
0V, A
BC-1
ALAR
M C
IRCU
IT F
USE
LIGHT
SEALLEAK
1 AMP, 250V, FNM-1CONTROL CIRCUIT FUSE
ON
OFF
15-27/64
12
5/16 DIA.
17-7/1616-3/4
17-1/2
7-11/16
ENCLOSURE(21981C107A)
U.L. LABEL
WIRING DIAGRAM
ALARM LIGHT(22000A020 OR 22000A011)
FLASHER(22002A001)
CIRCUIT BREAKER(22362A001)
BACK PANEL(21981C111A)
MOUNTING BRACKET(21997B022)
TOGGLE SWITCH(21979A003)
LIGHT ASSEMBLY(21973A002)
LIGHT BULB (2)(21974A001)
FUSE HOLDER(21991A001)
FUSE(20514A009)
TRANSFORMER(22053A010)
FUSE(20514A007)
TERMINAL BLK. (10)(21995A000)
FUSE (2)(20514A012)
AUX. CONTACT(22913A010)
CAT. NO. CGL-43SW
LIGHT ASSEMBLY(21973A001)
GROUND LUG(21994A001)
END SECTION(21996A000)
MAGNETIC STARTER(24024A008)
23833A150 11/08/12 14
PUMP
AUTO
OFF
HAND
PUMP 1SEAL LEAK
GRD.
1 2 3 4 5 6 7
1 AM
P, 25
0V, A
BC-1
ALAR
M C
IRCU
IT F
USE
1 AM
P, 25
0V, A
BC-1
CONT
ROL
CIRC
UIT
FUSE
PUMP 1RUN
GRD.
1 2 3 4 5 6 7
PUMP
AUTO
OFF
HAND
PUMP 2RUN
PUMP 2SEAL LEAK
OVERLOAD OVERLOAD
PUSH INTO RESET
PUSH INTO RESET
LOAD 1
LOAD 2
USE COPPER WIRE ONLY
17-31/64
12
5/16 DIA.
19-31/6418-7/8
19-5/8
10-5/8
ENCLOSURE(21981C108A)
U.L. LABEL
WIRING DIAGRAM
ALARM LIGHT(22000A020 OR 22000A011)
FLASHER(22002A001)
CIRCUIT BREAKER (2)(21985A001) BACK PANEL
(21981C112A)
START RELY (2)(21990A002)
END CAP (2)(20332A004)
CAPACITOR BRACKET (2)(16754A003)
START CAPACITOR (2)(22747A000)
CAPACITOR BRKT. (2)(16754A002)
RUN CAPACITOR (2)(23185A000)
KLIXON OVERLOAD (2)(20704A008)
TOGGLE SWITCH (2)(21979A003)
LIGHT ASSEMBLY (2)(21973A002)
LIGHT ASSEMBLY (2)(21973A001)
LIGHT BULB (4)(21974A001)
TERMINAL BLK. (16)(21995A000)
FUSE (2)(20514A009)
RELAY SOCKET(23527A002)
CAT. NO. CGL-01DW
MOUNTING BRKT.(21997C025)
GROUND LUG (2)(21994A001) END SECTION (2)
(21996A000)
OVERRIDE RELAY(23634A005)
END SECTION(21996A000)
TERMINAL BLK.(21995A000)
ALTERNATOR RELAY(22045A001)
FUSE HOLDER (2)(21991A001)
RELAY SOCKET(23527A000)
CONTACTOR (2)(22914A005)
23833A150 11/08/1215
PUMP
AUTO
OFF
HAND
PUMP 1SEAL LEAK
GRD.
1 2 3 4 5 6 7
1 AM
P, 25
0V, A
BC-1
ALAR
M C
IRCU
IT F
USE
1 AM
P, 25
0V, A
BC-1
CONT
ROL
CIRC
UIT
FUSE
PUMP 1RUN
GRD.
1 2 3 4 5 6 7
PUMP
AUTO
OFF
HAND
PUMP 2RUN
PUMP 2SEAL LEAK
OVERLOAD OVERLOAD
PUSH INTO RESET
PUSH INTO RESET
LOAD 1
LOAD 2
USE COPPER WIRE ONLY
17-31/64
12
5/16 DIA.
19-31/6418-7/8
19-5/8
10-5/8
ENCLOSURE(21981C108A)
U.L. LABEL
WIRING DIAGRAM
ALARM LIGHT(22000A020 OR 22000A011)
FLASHER(22002A001)
CIRCUIT BREAKER (2)(21985A001) BACK PANEL
(21981C112A)
START RELY (2)(21990A002)
CAPACITOR BRKT (4)(16754A002)
START CAPACITOR (2)(12141A005)
RUN CAPACITOR (2)(23185A000)
KLIXON OVERLOAD (2)(20704A008)
TOGGLE SWITCH (2)(21979A003)
LIGHT ASSEMBLY (2)(21973A002)
LIGHT ASSEMBLY (2)(21973A001)
LIGHT BULB (4)(21974A001)
TERMINAL BLK. (16)(21995A000)
FUSE (2)(20514A009)
RELAY SOCKET(23527A002)
CAT. NO. CGL-21DW
MOUNTING BRKT.(21997C025)
GROUND LUG (2)(21994A001) END SECTION (2)
(21996A000)
OVERRIDE RELAY(23634A005)
END SECTION(21996A000)
TERMINAL BLK.(21995A000)
ALTERNATOR RELAY(22054A001)
FUSE HOLDER (2)(21991A001)
RELAY SOCKET(23527A000)
CONTACTOR (2)(22914A005)
23833A150 11/08/12 16
PUMP
AUTO
OFF
HAND
PUMP 1SEAL LEAK
GRD.
R W B 1 2 3 4
1 AM
P, 25
0V, A
BC-1
ALAR
M C
IRCU
IT F
USE
1 AM
P, 25
0V, A
BC-1
CONT
ROL
CIRC
UIT
FUSE
PUMP 1RUN
GRD.
5 6 7 8 9 W B
PUMP
AUTO
OFF
HAND
PUMP 2RUN
PUMP 2SEAL LEAK
OVERLOAD OVERLOAD
PUSH INTO RESET
PUSH INTO RESET
LOAD 1
LOAD 2
USE COPPER WIRE ONLY
17-31/64
12
5/16 DIA.
19-31/6418-7/8
19-5/8
10-5/8
ENCLOSURE(21981C108A)
U.L. LABEL
WIRING DIAGRAM
ALARM LIGHT(22000A020 OR 22000A011)
FLASHER(22002A001)
CIRCUIT BREAKER (2)(21985A001) BACK PANEL
(21981C112A)
START RELY (2)(21990A000)
CAPACITOR BRKT. (4)(16754A002)
START CAPACITOR (2)(12141A005)
RUN CAPACITOR (2)(23185A000)
KLIXON OVERLOAD (2)(20704A008)
TOGGLE SWITCH (2)(21979A003)
LIGHT ASSEMBLY (2)(21973A002)
LIGHT BULB (2)(21974A001)
TERMINAL BLK. (14)(21995A000)
FUSE (2)(20514A009)
RELAY SOCKET(23527A002)
CAT. NO. CGL(LD)-21DW
MOUNTING BRKT.(21997C025)
GROUND LUG (2)(21994A001) END SECTION (2)
(21996A000)
OVERRIDE RELAY(23634A005)
END SECTION(21996A000)
TERMINAL BLK.(21995A000)
ALTERNATOR RELAY(22054A001)
FUSE HOLDER (2)(21991A001)
RELAY SOCKET(23527A000)
CONTACTOR (2)(22914A005)
23833A150 11/08/1217
PUMP 1
AUTO
OFF
HAND
PUMP 1SEAL LEAK
GRD.
M1 M2 M3 1 2 3 4 5
1 AMP, 250V, ABC-1ALARM CIRCUIT FUSE
PUMP 1RUN
PUMP 2
AUTO
OFF
HAND
PUMP 2RUN
PUMP 2SEAL LEAK
LOAD 1
LOAD 2
USE COPPER WIRE ONLY
GRD.
6 7 8 9 10 M1 M2 M3
1 AMP, 250V, FNM-1CONTROL CIRCUIT FUSE
17-31/64
12
5/16 DIA.
19-31/6418-7/8
19-5/8
10-5/8
ENCLOSURE(21981C108A)
U.L. LABEL
WIRING DIAGRAM
ALARM LIGHT(22000A020 OR 22000A011)
FLASHER(22002A001)
CIRCUIT BREAKER (2)(21985A003)
BACK PANEL(21981C112A)
MOUNTING BRKT.(21997C027)
ALTERNATOR RELAY(22054A001)
OVERRIDE RELAY(23634A005)FUSE (2)(20514A014)
RELAY SOCKET(23527A002)
TOGGLE SWITCH (2)(21979A003)
LIGHT ASSEMBLY (2)(21973A002)
LIGHT BULB (4)(21974A001)
TERMINAL BLK. (16)(21995A000) CAT. NO. CGL-23DW
TRANSFORMER(22053A001)
GROUND LUG (2)(21994A001)
END SECTION (2)(21996A000)
FUSE HOLDER(21991A001)
MAGNETIC STARTER (2)(24024A008)
AUX. CONTACT (2)(22913A010)
LIGHT ASSEMBLY (2)(21973A001)
FUSE(20514A007)
RELAY SOCKET(23527A000)
FUSE (20514A009)
23833A150 11/08/12 18
PUMP 1
AUTO
OFF
HAND
PUMP 1SEAL LEAK
GRD.
R W B 1 2 3 4
1 AMP, 250V, ABC-1ALARM CIRCUIT FUSE
PUMP 1RUN
PUMP 2
AUTO
OFF
HAND
PUMP 2RUN
PUMP 2SEAL LEAK
LOAD 1
LOAD 2
USE COPPER WIRE ONLY
GRD.
R W B 1 2 3 4
1 AMP, 250V, FNM-1CONTROL CIRCUIT FUSE
ON
OFF
ON
OFF
17-31/64
12
5/16 DIA.
19-31/6418-7/8
19-5/8
10-5/8
ENCLOSURE(21981C108A)
U.L. LABEL
WIRING DIAGRAM
ALARM LIGHT(22000A020 OR 22000A011)
FLASHER(22002A001)
CIRCUIT BREAKER (2)(22362A001)
BACK PANEL(21981C112A)
MOUNTING BRKT.(21997C027)
ALTERNATOR RELAY(22054A001)
OVERRIDE RELAY(23634A005)FUSE (2)(20514A012)
RELAY SOCKET(23527A002)
TOGGLE SWITCH (2)(21979A003)
LIGHT ASSEMBLY (2)(21973A002)
LIGHT BULB (4)(21974A001)
TERMINAL BLK. (16)(21995A000) CAT. NO. CGL-43DW
TRANSFORMER(22053A011)
GROUND LUG (2)(21994A001)
END SECTION (2)(21996A000)
FUSE HOLDER(21991A001)
MAGNETIC STARTER (2)(24024A008)
AUX. CONTACT (2)(22913A010)
LIGHT ASSEMBLY (2)(21973A001)
FUSE(20514A007)
RELAY SOCKET(23527A000)
FUSE (20514A009)
23833A150 11/08/1219
INC
OM
ING
200
V 1
PH
L1L2
20A
BR
EAKE
RKL
IXO
N O
VER
LOAD
PUM
P M
OTO
R
RU
N C
APAC
ITO
R
STAR
T C
APAC
ITO
R
B W RSR
SR
1 AM
P FU
SEH
IGH
WAT
ER
1 AM
PFU
SE
HAN
DO
FFAU
TO
PUM
P O
FF
PUM
P O
N
TO S
EAL
LEAK
PRO
BE
IN P
UM
P7
12
34
R
56 M1
F
M1
AL Y M1
N
M1
M1
START
MAIN
RED
BLK
WH
BLK BL
K
BLK
BLK BL
K
BLUE
52
1
RED
YEL
WH/
GRA
YYE
L
BLUE OR
BRN
WH/
RED
WH
YEL/
RED
WH
GRA
Y
WH/
VIO
VIO
VIO
OR
WH/
YEL
NO
TE: D
EPEN
DIN
G O
N P
UM
P M
OD
EL, S
EAL
LEA
KC
IRC
UIT
MAY
OR
MAY
NO
T B
E U
SED
NO
TE: C
ON
NEC
T A
LL G
REE
N W
IRES
TO G
RO
UN
D B
AR
FLO
AT C
ON
TRO
LS M
US
T B
E R
ATED
FOR
2 A
MP
S A
T 11
5 VO
LTS
PUMP OFF
PUMP ON
HIGH WATER
POWER COR D
12
34
56
7R
WB
BLK
BLK
BLK
WH
WH
WH
GR
N
AL-A
LAR
M L
IGH
T (R
ED)
F-FL
ASH
ER
Y-R
UN
LIG
HT
(YEL
LOW
)
M1-
MO
TOR
CO
NTA
CTO
R
R-S
EAL
LEAK
LIG
HT
(RED
)
CAT
. NO
. CG
L-01
SW20
8 VO
LT, 1
PH
ASE
INC
OM
ING
230
V 1
PH
L1L2
20A
BR
EAKE
RKL
IXO
N O
VER
LOAD
PUM
P M
OTO
R
RU
N C
APAC
ITO
R
STAR
T C
APAC
ITO
R
B W RSR
SR
1 AM
P FU
SEH
IGH
WAT
ER
1 AM
PFU
SE
HAN
DO
FFAU
TO
PUM
P O
FF
PUM
P O
N
TO S
EAL
LEAK
PRO
BE
IN P
UM
P7
12
34
R
56 M1
F
M1
AL Y M1
N
M1
M1
START
MAIN
RED
BLK
WH
BLK BL
K
BLK
BLK BL
K
BLUE
52
1
RED
YEL
WH/
GRA
YYE
L
BLUE OR
BRN
WH/
RED
WH
YEL/
RED
WH
GRA
Y
WH/
VIO
VIO
VIO
OR
WH/
YEL
NO
TE: C
ON
NEC
T A
LL G
REE
N W
IRES
TO G
RO
UN
D B
AR
FLO
AT C
ON
TRO
LS M
US
T B
E R
ATED
FOR
2 A
MP
S A
T 11
5 VO
LTS
PUMP OFF
PUMP ON
HIGH WATER
POWER COR D
12
34
56
7R
WB
BLK
BLK
BLK
WH
WH
WH
GR
N
AL-A
LAR
M L
IGH
T (R
ED)
F-FL
ASH
ER
Y-R
UN
LIG
HT
(YEL
LOW
)
M1-
MO
TOR
CO
NTA
CTO
R
R-S
EAL
LEAK
LIG
HT
(RED
)
CAT
. NO
. CG
L-21
SW23
0 VO
LT, 1
PH
ASE
BRNREDWHBLK
BRNREDWHBLK
23833A150 11/08/12 20
INC
OM
ING
230
V 1
PH
L1L2
20A
BR
EAKE
RKL
IXO
N O
VER
LOAD
PUM
P M
OTO
R
RU
N C
APAC
ITO
R
STAR
T C
APAC
ITO
R
B W RSR
SR
1 AM
P FU
SEH
IGH
WAT
ER
1 AM
PFU
SE
HAN
DO
FFAU
TO
PUM
P O
FF
PUM
P O
N
12
345
6 M1
F
M1
AL Y M1
N
M1
M1
START
MAIN
RED
BLK
WH
BLK BL
K
BLK
BLK BL
K
BLUE
52
1
RED
YEL
WH/
GRA
YYE
L
BLUE OR
BRN
WH/
RED
WH
YEL/
RED
WH
GRA
Y
WH/
VIO
VIO
VIO
OR NO
TE: C
ON
NEC
T A
LL G
REE
N W
IRES
TO G
RO
UN
D B
AR
FLO
AT C
ON
TRO
LS M
US
T B
E R
ATED
FOR
2 A
MP
S A
T 11
5 VO
LTS
PUMP OFF
PUMP ON
HIGH WATER
POWER COR D
12
34
56
RW
B
BLK
BLK
BLK
WH
WH
WH
GR
N
AL-A
LAR
M L
IGH
T (R
ED)
F-FL
ASH
ER
Y-R
UN
LIG
HT
(YEL
LOW
)
M1-
MO
TOR
CO
NTA
CTO
R
CAT
. NO
. CG
L(LD
)-21S
W23
0 VO
LT, 1
PH
ASE
INC
OM
ING
3 P
H20
8V, 2
30V,
460
V
L1L2
CIR
CU
IT B
REA
KER
208
- 230
V -
15 A
MP
460V
- 15
AM
PO
VER
LOAD
ELE
MEN
TSPU
MP
MO
TOR
100V
ATR
ANSF
OR
MERM
1
M2
M3
1 AM
P FU
SE
HIG
H W
ATER
HAN
DO
FFAU
TO
PUM
P O
FF
PUM
P O
N
TO S
EAL
LEAK
PRO
BE
IN P
UM
P7
12
34
R
56 M1
FAL Y
M1
M1
M1
BLK
BLK
BLK
52
1
H1
BLUE
OR
XF
WH/
RED
WHI
TE
YEL/
RED
WH
GRA
Y
WH/
VIO
VIO
VIO
OR
WH/
YEL
NO
TE: C
ON
NEC
T A
LL G
REE
N W
IRES
TO G
RO
UN
D B
AR
FLO
AT C
ON
TRO
LS M
US
T B
E R
ATED
FOR
2 A
MP
S A
T 11
5 VO
LTS
PUMP OFF
PUMP ON
HIGH WATER
POWER COR D
12
34
56
7M
1
BLK
BLK
BLK
WH
WH
WH
GR
N
AL-A
LAR
M L
IGH
T (R
ED)
F-FL
ASH
ER
Y-R
UN
LIG
HT
(YEL
LOW
)
M1-
MO
TOR
CO
NTA
CTO
R
R-S
EAL
LEAK
LIG
HT
(RED
)
CAT
. NO
. CG
L-23
SW O
R C
GL-
43SW
208,
230
OR
460
VO
LT, 3
PH
ASE
BRNREDWHBLK
REDWHBLK
L3
M1
PRIM
ARY
FUSE
S
1 AM
P FU
SE
H3H2
H4
OR
X1X2
GRN
M1
T.O
.C.
RED
WH
TOC
-TH
ERM
AL O
VER
LOAD
C
ON
TAC
T
NO
TE: D
EPEN
DIN
G O
N P
UM
P M
OD
EL, S
EAL
LEA
KC
IRC
UIT
MAY
OR
MAY
NO
T B
E U
SED
M3
M2
23833A150 11/08/1221
L1L2
KLIX
ON
OVE
RLO
ADPU
MP
MO
TOR 1
AMP
FUSE
HIG
H W
ATER
HAN
D
OFF
AUTO PU
MP
OFF
PUM
P O
N
TO S
EAL
LEAK
PRO
BE
IN P
UM
P 1
1R
BLK
BLK
2
1 WH/
BRN
NO
TE: C
ON
NEC
T A
LL G
REE
N W
IRES
TO G
RO
UN
D B
AR
FLO
AT C
ON
TRO
LS M
US
T B
E R
ATED
FOR
2 A
MP
S A
T 11
5 VO
LTS
PUMP OFF
PUMP ON
HIGH WATER
POWER COR D PUMP 1
23
45
67
BLK
BLK
BLK
WH
WH
WH
GR
N
AL-A
LAR
M L
IGH
T (R
ED)
F-FL
ASH
ER
Y-R
UN
LIG
HT
(YEL
LOW
)
M1-
MO
TOR
CO
NTA
CTO
R
AR- A
LTER
NAT
OR
REL
AY
CAT
. NO
. CG
L-01
DW
208
VOLT
, 1 P
HAS
E
REDWHBLKBRN
1 AM
P FU
SE
NO
TE: D
EPEN
DIN
G O
N P
UM
P M
OD
EL, S
EAL
LEA
KC
IRC
UIT
MAY
OR
MAY
NO
T B
E U
SED
10
POWER COR D PUMP 2
OVERRIDE
BLK
WH
GR
N
BRNREDWHBLK
89
1R
WB
RW
B
WH/
VIO
10TO
SEA
L LE
AKPR
OB
E IN
PU
MP
2R
PUM
P M
OTO
RKL
IXO
N O
VER
LOAD
START
MAIN
START
MAIN
20A
BR
EAKE
R20
AB
REA
KER
M1
M1
M2
M2
B W RS
R
INC
OM
ING
208
V 1
PH
SR
N
AL Y M1
M1
F
SR
SR
RU
N C
AP.
STAR
T C
AP.
B W R
89
5
WH
RED
BLK
BLK
BLK
YEL
YEL
RED
WH/
GRAY
BLK
WH/
RED
ORAN
GE
23
45
OR
RED
VIOL
ET
WH/
BLUE
YEL/
RED
WH W
H
2
1
5
BLK
BLK
BLK
BLK
YEL
YEL
RED
WH/
GRAY
BLK
RU
N C
AP.
STAR
T C
AP.
WH
RED
M1
M2
AR AR
OR
AR
WH/
BLUE
WH/
BLK
OR OR OR
OR
OVE
RR
IDE
67
OR
ORM2Y
M2
HAN
D
OFF
AUTO
RED
WH/
YEL
WH/
YEL
WH/
BRN
WH/
BLK GR
AYW
H
BLUE
/RED
WH/
GRAY
WH
15
3
4
28
126
914
13
BRN
M2-
MO
TOR
CO
NTA
CTO
R
OR
-OVE
RR
IDE
REL
AY
R- S
EAL
LEAK
LIG
HT
(RED
)
L1L2
KLIX
ON
OVE
RLO
ADPU
MP
MO
TOR 1
AMP
FUSE
HIG
H W
ATER
HAN
D
OFF
AUTO PU
MP
OFF
PUM
P O
N
TO S
EAL
LEAK
PRO
BE
IN P
UM
P 1
1R
BLK
BLK
2
1 WH/
BRN
NO
TE: C
ON
NEC
T A
LL G
REE
N W
IRES
TO G
RO
UN
D B
AR
FLO
AT C
ON
TRO
LS M
US
T B
E R
ATED
FOR
2 A
MP
S A
T 11
5 VO
LTS
PUMP OFF
PUMP ON
HIGH WATER
POWER COR D PUMP 1
23
45
67
BLK
BLK
BLK
WH
WH
WH
GR
N
AL-A
LAR
M L
IGH
T (R
ED)
F-FL
ASH
ER
Y-R
UN
LIG
HT
(YEL
LOW
)
M1-
MO
TOR
CO
NTA
CTO
R
AR- A
LTER
NAT
OR
REL
AY
CAT
. NO
. CG
L-21
DW
230
VOLT
, 1 P
HAS
E
REDWHBLKBRN
1 AM
P FU
SE
10
POWER COR D PUMP 2
OVERRIDE
BLK
WH
GR
N
BRNREDWHBLK
89
1R
WB
RW
B
WH/
VIO
10TO
SEA
L LE
AKPR
OB
E IN
PU
MP
2R
PUM
P M
OTO
RKL
IXO
N O
VER
LOAD
START
MAIN
START
MAIN
20A
BR
EAKE
R20
AB
REA
KER
M1
M1
M2
M2
B W RS
R
INC
OM
ING
208
V 1
PH
SR
N
AL Y M1
M1
F
SR
SR
RU
N C
AP.
STAR
T C
AP.
B W R
89
5
WH
RED
BLK
BLK
BLK
YEL
YEL
RED
WH/
GRAY
BLK
WH/
RED
ORAN
GE
23
45
OR
RED
VIOL
ET
WH/
BLUE
YEL/
RED
WH W
H
2
1
5
BLK
BLK
BLK
BLK
YEL
YEL
RED
WH/
GRAY
BLK
RU
N C
AP.
STAR
T C
AP.
WH
RED
M1
M2
AR AR
OR
AR
WH/
BLUE
WH/
BLK
OR OR OR
OR
OVE
RR
IDE
67
OR
OR
M2Y
M2
HAN
D
OFF
AUTO
RED
WH/
YEL
WH/
YEL
WH/
BRN
WH/
BLK GR
AYW
H
BLUE
/RED
WH/
GRAY
WH
15
3
4
28
126
914
13
BRN
M2-
MO
TOR
CO
NTA
CTO
R
OR
-OVE
RR
IDE
REL
AY
R- S
EAL
LEAK
LIG
HT
(RED
)
23833A150 11/08/12 22
L1L2
KLIX
ON
OVE
RLO
ADPU
MP
MO
TOR
1 AM
P FU
SEH
IGH
WAT
ER
HAN
D
OFF
AUTO PU
MP
OFF
PUM
P O
N
BLK
BLK
2
1
NO
TE: C
ON
NEC
T A
LL G
REE
N W
IRES
TO G
RO
UN
D B
AR
FLO
AT C
ON
TRO
LS M
US
T B
E R
ATED
FOR
2 A
MP
S A
T 11
5 VO
LTS
PUMP OFF
PUMP ON
HIGH WATER
POWER COR D PUMP 1
23
45
67
BLK
BLK
BLK
WH
WH
WH
GR
N
AL-A
LAR
M L
IGH
T (R
ED)
F-FL
ASH
ER
Y-R
UN
LIG
HT
(YEL
LOW
)
M1-
MO
TOR
CO
NTA
CTO
R
AR- A
LTER
NAT
OR
REL
AY
CAT
. NO
. CG
L(LD
)-21D
W23
0 VO
LT, 1
PH
ASE
REDWHBLK
1 AM
P FU
SE
POWER COR D PUMP 2
OVERRIDE
BLK
WH
GR
N
REDWHBLK
81
RW
BR
WB
PUM
P M
OTO
RKL
IXO
N O
VER
LOAD
START
MAIN
START
MAIN
20A
BR
EAKE
R20
AB
REA
KER
M1
M1
M2
M2
B W RS
R
INC
OM
ING
230
V 1
PH
SR
N
AL Y M1
M1
F
SR
SR
RU
N C
AP.
STAR
T C
AP.
B W R
87
5
WH
RED
BLK
BLK
BLK
YEL
YEL
RED
WH/
GRAYBL
K
WH/
RED
ORAN
GE
2
34
1OR
RED
VIOL
ET
WH/
BLUE
YEL/
RED
WH WH
2
1
5
BLK
BLK
BLK
BLK
YEL
YEL
RED
WH/
GRAY
BLK
RU
N C
AP.
STAR
T C
AP.
WH
RED
M1
M2
AR AR
OR
AR
WH/
BLUE
WH/
BLK
OR OR
OVE
RR
IDE
65
OR
OR
M2Y
M2
HAN
D
OFF
AUTO
RED
WH/
YEL
WH/
YEL
WH/
BRN
WH/
BLK
GRAY
WH
BLUE
/RED
WH/
GRAY
WH
15
3
4
2
8
126
9
1413
BRN
M2-
MO
TOR
CO
NTA
CTO
R
OR
-OVE
RR
IDE
REL
AY
L1L2
PUM
P M
OTO
R
1 AM
P FU
SE
HIG
H W
ATER
HAN
D
OFF
AUTO PU
MP
OFF
PUM
P O
N
TO S
EAL
LEAK
PRO
BE
IN P
UM
P 1
1R
BLK
WH/
BRN
NO
TE: C
ON
NEC
T A
LL G
REE
N W
IRES
TO G
RO
UN
D B
AR
FLO
AT C
ON
TRO
LS M
US
T B
E R
ATED
FOR
2 A
MP
S A
T 11
5 VO
LTS
PUMP OFF
PUMP ON
HIGH WATER
POWER COR D PUMP 1
23
45
67
BLK
BLK
BLK
WH
WH
WH
GR
N
AL-A
LAR
M L
IGH
T (R
ED)
F-FL
ASH
ER
Y-R
UN
LIG
HT
(YEL
LOW
)
M1-
MO
TOR
CO
NTA
CTO
R
AR- A
LTER
NAT
OR
REL
AY
CAT
. NO
. CG
L-23
DW
OR
CG
L-43
DW
208,
230
, OR
460
VO
LT, 3
PH
ASE
REDWHBLKBRN
1 AM
P FU
SE
10
POWER COR D PUMP 2
OVERRIDE
BLK
WH
GR
N
BRNREDWHBLK
89
1M
1M
2M
3
WH/
VIO
10TO
SEA
L LE
AKPR
OB
E IN
PU
MP
2R
CIR
CU
IT B
REA
KER
208V
, 230
V - 1
5 AM
P46
0V -
15 A
MP
M1
M1
M2
M2
INC
OM
ING
3 P
H20
8V, 2
30V,
460
V
AL Y
M1
M1
F
89
BLK
BLK
BLK
XF
BLK
WH/
RED
ORAN
GE
23
45
OR
RED
VIOL
ET
WH/
BLUE
YEL/
RED
WH W
H
H3H4
H2
BLK
BLK
BLUE
BLK
GRN
WH
ITE
M1
M2
AR AR
OR
AR
WH/
BLUE
WH/
BLK
OR OR OR
OR
OVE
RR
IDE
67
OR
OR
M2
Y
M2
HAN
D
OFF
AUTO
RED
WH/
YEL
WH/
YEL
WH/
BRN
WH/
BLK GR
AYW
H
BLUE
/RED
WH/
GRAY
WH
15
3
4
2
H1
126
914
13
BRN
M2-
MO
TOR
CO
NTA
CTO
R
OR
-OVE
RR
IDE
REL
AY
R- S
EAL
LEAK
LIG
HT
(RED
)5
M1
M2
M3
NO
TE: D
EPEN
DIN
G O
N P
UM
P M
OD
EL, S
EAL
LEA
KC
IRC
UIT
MAY
OR
MAY
NO
T B
E U
SED
5
RED
T.O
.C.
T.O
.C.
RED
OVE
RLO
AD E
LEM
ENTS
M1
M2
M3
M1
PRIM
ARY
FUSE
S15
0 VA
TRAN
SFO
RM
EROVE
RLO
AD E
LEM
ENTS
ORAN
GE
CIR
CU
IT B
REA
KER
208V
, 230
V - 1
5 AM
P46
0V -
15 A
MP
L3
M2
PUM
P M
OTO
R
M1
M2
M3
TOC
- TH
ERM
AL O
VER
LOAD
CO
NTA
CT
X2
X1
23833A150 11/08/1223
1101 MYERS PARKWAY 490 PinEbuSh RoAd, unit #4 AShLAnd, ohio, uSA 44805 CAMbRidGE, ontARio, CAnAdA n1t 0A5 419-289-1144 800-363-PuMP
WWW.FEMYERS.CoM
Warranty Rev. 12/13
STANDARD LIMITED WARRANTY
Pentair Myers® warrants its products against defects in material and workmanship for a period of 12 months from the date of shipment from Pentair Myers or 18 months from the manufacturing date, whichever occurs first – provided that such products are used in compliance with the requirements of the Pentair Myers catalog and technical manuals for use in pumping raw sewage, municipal wastewater or similar, abrasive-free, noncorrosive liquids.
during the warranty period and subject to the conditions set forth, Pentair Myers, at its discretion, will repair or replace to the original user, the parts that prove defective in materials and workmanship. Pentair Myers reserves the right to change or improve its products or any portions thereof without being obligated to provide such a change or improvement for prior sold and/or shipped units.
Start-up reports and electrical schematics may be required to support warranty claims. Submit at the time of start- up through the Pentair Myers website: http://forms.pentairliterature.com/startupform/startupform.asp?type=m. Warranty is effective only if Pentair Myers authorized control panels are used. All seal fail and heat sensing devices must be hooked up, functional and monitored or this warranty will be void. Pentair Myers will cover only the lower seal and labor thereof for all dual seal pumps. under no circumstance will Pentair Myers be responsible for the cost of field labor, travel expenses, rented equipment, removal/reinstallation costs or freight expenses to and from the factory or an authorized Pentair Myers service facility.
this limited warranty will not apply: (a) to defects or malfunctions resulting from failure to properly install, operate or maintain the unit in accordance with the printed instructions provided; (b) to failures resulting from abuse, accident or negligence; (c) to normal maintenance services and parts used in connection with such service; (d) to units that are not installed in accordance with applicable local codes, ordinances and good trade practices; (e) if the unit is moved from its original installation location; (f) if unit is used for purposes other than for what it is designed and manufactured; (g) to any unit that has been repaired or altered by anyone other than Pentair Myers or an authorized Pentair Myers service provider; (h) to any unit that has been repaired using non factory specified/oEM parts.
Warranty Exclusions: PEntAiR MYERS MAKES no EXPRESS oR iMPLiEd WARRAntiES thAt EXtEnd bEYond thE dESCRiPtion on thE FACE hEREoF. PEntAiR MYERS SPECiFiCALLY diSCLAiMS thE iMPLiEd WARRAntiES oF MERChAntAbiLitY And FitnESS FoR AnY PARtiCuLAR PuRPoSE.
Liability Limitation: in no EVEnt ShALL PEntAiR MYERS bE LiAbLE oR RESPonSibLE FoR ConSEQuEntiAL, inCidEntAL oR SPECiAL dAMAGES RESuLtinG FRoM oR RELAtEd in AnY MAnnER to AnY PEntAiR MYERS PRoduCt oR PARtS thEREoF. PERSonAL inJuRY And/oR PRoPERtY dAMAGE MAY RESuLt FRoM iMPRoPER inStALLAtion. PEntAiR MYERS diSCLAiMS ALL LiAbiLitY, inCLudinG LiAbiLitY undER thiS WARRAntY, FoR iMPRoPER inStALLAtion. PEntAiR MYERS RECoMMEndS inStALLAtion bY PRoFESSionALS.
Some states do not permit some or all of the above warranty limitations or the exclusion or limitation of incidental or consequential damages and therefore such limitations may not apply to you. no warranties or representations at any time made by any representatives of Pentair Myers shall vary or expand the provision hereof.