CGVision OPC-interface for BMS .Klepper – 01/04/11 Rev.B 6.2
Transcript

CGVisionOPC-interface for BMS

A.Klepper – 01/04/11 Rev.B

6.2

A.Klepper – 01/04/11 Rev.B 2

LAN-connection between PC with CGVision and PC with BMS Software

LAN (RJ45)

Ethernet (LAN)with TCP/IP

USB

Building Managment System (BMS)

(e.g. TAC – Vista)

PC Workstation withCGVision

LAN (RJ45)

IP-InterfaceClient 1

ZB-S

ZB-S

ZB-S

CG-S Bus / FTT10A

ZB-S

ZB-S Systems

BMSas OPC-Client

IP-InterfaceClient 2

ZB-S

ZB-S

ZB-S

CG-S Bus / FTT10A

ZB-S

ZB-S Systems

incl. OPC-Server

CG-S/IP-Interface

A.Klepper – 01/04/11 Rev.B 3

Ethernet LAN

IP-InterfaceClient 1

ZB-S

ZB-S

ZB-S

CG-S Bus / FTT10A

ZB-S

BMSas OPC-Client

IP-InterfaceClient 2

ZB-S

ZB-S

ZB-S

CG-S Bus / FTT10A

ZB-S

Incl. OPC-Server

Explanation:BMS software has access, directly via LAN, to the BMS variable of the OPC-Server:

nviStatusBMS SNVT_state_64

A.Klepper – 01/04/11 Rev.B 4

Possible messages of each device:nviStatusBMS SNVT_state_64

1. Operation Bit 02. Failure priority 1 Bit 13. Failure priority 2 Bit 24. Communication failure CG-S Bit 75. Manual reset necessary Bit 86. Battery operation Bit 97. Durationtest active Bit 108. Device is blocked Bit 119. Battery failure Bit 1210. Circuit failure Bit 1311. Mains failure Bit 1412. Sum failure Bit 1513. Communication failure internal Bit 1614. Deep disharge protection Bit 1715. Interruption battery circuit Bit 1816. Charging failure Bit 1917. ISO failure Bit 20

18. Min. operation time not reached Bit 2119. Emergency light failure Bit 2220. Functiontest active Bit 2321. Battery overvoltage Bit 2422. Battery sum failure Bit 2523. Failure charging unit Bit 2624. Failure booster Bit 2725. ISO failure + Bit 3026. ISO failure - Bit 3127. SMC (smart media card) failure Bit 3228. Mains failure device Bit 3329. Mains failure S3/S4 Bit 3430. Mains failure LON RS485 Bit 3531. Failure config. DLS/TLS Bit 3632. Device blocked via S1/S2 Bit 3733. Device blocked via menu Bit 3834. Device blocked via BMS (LON) Bit 3935. Delay on mains return Bit 40

A.Klepper – 01/04/11 Rev.B 5

Example for BMS visualisation :

BIT: 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ....0 0 0 0No.: 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40........61 62 63 64

BMSvisualisation

nviStatusBMS SNVT_state_64

Example :Operation Bit 0Emergency light failure Bit 22

Luminiare failure

Device 1in operation

A.Klepper – 01/04/11 Rev.B 6

Detailed information:Described in the interface description of OPC interface for BMS


Recommended