+ All Categories
Home > Documents > Ch.12 Condensers and Evaporators

Ch.12 Condensers and Evaporators

Date post: 03-Apr-2022
Category:
Upload: others
View: 6 times
Download: 0 times
Share this document with a friend
40
Topic4-3 Condensers Condensers reject heat (Q e + P c ) from refrigeration system to heat sink. 1 Temperature, K Entropy, kJ/kgK 1 2 3 4 Refrigerant phase change (condensing) in shell, tube, plate Water-cooled Air-cooled air liquid (water, brine, antifreeze) air Heat sink Evaporative
Transcript

Topic4-3 Condensers

Condensers reject heat (Qe + Pc) from refrigeration system to heat sink.

1

Tem

per

atu

re, K

Entropy, kJ/kgK

1

2

3

4

Refrigerant phase change (condensing) in shell, tube, plate

• Water-cooled

• Air-cooled air

liquid (water, brine, antifreeze) air

Heat sink

• Evaporative

1. Types of Condensers

Air Cooled Condenser

• Finned coil

Water Cooled Condenser with water Cooling Tower

• Shell and tube

• Plate-type

Evaporative Condenser (refrigerant Cooling tower)

• Evaporative

• Plate-type evaporative

*Widely used in industry

2

3

2. Required condensing capacity

Rate of heat transfer in condenser is a function of Refrigerating capacity, qe

Temp. of evaporation, te

Temp. of condensation, tc

kW ,evaporator at absorbed heatof rate

kW condenser, at rejected heatof rateratio rejection-Heat

+ heat of compression added by inefficiencies of compressor

Cannot find from P-h diagram

A graph of Heat-rejectio ration & Condensing temp is needed.

4

2. Required condensing capacity

Typical values of the ratio of heat rejected at the condenser to the refrigerating capacity for Ammonia and halocarbon refrigerants.

Hermetically sealed compressorproduce more heat than open-typeExternal cooling reciprocating and screw compressor produce less heat

Knowledge of the Carnot cycleHRR Tc/Te (T, K = °C + 273)HRR = (Tc/Te)1.7

Ex1: Estimate the HRR when the condensingtemperature is 35°C (95°F) and theevaporating temperature is -10°C (14°F).HRR = (Tc/Te)1.7 = (308/263)1.7 = 1.31

Hermetic compressor: HRR = 1.33hermatic HRR = (Tc/Te)1.7 + (Tc/Te – 1.05)1.7

5

3. Condensing coefficient outside plate/tube

Nusselt W. (1916) has developed the basic equation to calculate mean heat transfer coefficient of vapor condensing over total height of outside vertical plate L by conductance through the condensate film:

hcv = local condensing coefficient on vertical plate, W/m2 Kx = vertical distance measure d from top of plate, mg = acceleration due to gravity = 9.81 m/s2

= density of condensate, kg/m3

hfg = latent heat of vaporization, J/kg = viscosity of condensate, Past = (tvapor -ttube) = temperature difference between vapor and the plate, K

KW/m

0.943 2

/

4132

0

Lt

khg

L

dxhh fg

L

cv

cv

tvapor

ttube

Vertical plate – old design, water flowed by gravity down inside tubes to ease their cleaning.

6

3. Condensing coefficient outside plate/tube

Widely used horizontal shell-and-tube condensermean condensing coefficient on outside of horizontal tubes:

KW/m

0.725 2

/

4132

NDt

khgh fg

ct

Modification: t L = t ND N = number of tubes in vertical rowD = OD of tube, m

White (1948) 0.63Goto (1962) 0.65Use 0.64 instead of 0.725

Eqs. of mean condensing coefficients – combine of motion & energy eqs.- expression of heat transfer across liquid film continuously condensing on surface and continuously draining away

hct increase by -increase k-high -low -high hfg

-low t

Heat flow rate

Rapid draining

Film thickness

Heat/small mass

Film thickness

Low rate of condensation needed

7

3. Condensing coefficient outside plate/tube

– condensing outside tubes low vapor velocityEqs. of mean condensing coefficients – filmwise condensation

hcv , W/m2 KRefrigerant

For six-25 mm tubes in a vertical row (N = 6)

1142R22

1046R134a

5096Ammonia

But Dropwise condensation – higher coefficient of heat transfer-- occur only on clean surface-- but predicted on basis of filmwise condensation for safe

Ammonia have a higher condensing coefficient—five times that of the halocarbons in one study

8

4. Condensing coefficient inside tube

Max. hc:annular flow

In air-cooled and evaporative condensers

Mechanism of condensation inside tubes complexFlow regime continue to change reduction in condensing area

Flow regime 1. Spray- Convection with gas2. Annular- Surface condensation- Liquid flow with gas3. Wavy/Stratification- Liquid flow4. Slug or plug

At the end: backing liquid into condenser shifts some heat-transfer area into the liquid subcooling mode low hc

9

High vapor velocitySpray flow regime

Low vapor velocitySlug flow regime

10

5. Performance of Air- and Water-Cooled Condenser

iimopefiniioo Ahk A

x

hAA AU AU

1

)(

111

Air-cooled condensers; refrigerant condenses in tube, air flows pass finned-coil:

Water-cooled condensers; refrigerant condenses outside tube, water flows in tube:

mL

mLcconvection

)tanh(

ckA

hPm

Lc = L + Ac/PP = perimeterh = 38V0.5 (ARI/AHRI)

Nu = 0.023 Re0.8 Prn

for turbulent flow in tube Re > 10,000

n = 0.3 for cooling, 0.4 for heating

Nu = hD/k

Re = VD/

Pr = / = cp/k

Rcyl = ln(ro/ri)/(2Lk)

x/(Amk) for thin metal

ii

o

iff

o

m

o

oo Ah

A

Ah

A

k A

xA

h U

11(1/Uo) designed = (1/Uo) factory + 0.000176 (Ao/Ai)

U decreases by fouling from impurities in water. Some standard (1972) use fouling factor of 1/hff = 0.000176 (m2/KW)

*Tube cleaning can improve performance

Ap = Prime areaAe = Extended area

11

6. LMTD and Desuperheating

/ln

LMTDocic

ocic

tttt

tttt

Idealized temperature is constant throughout the condenser, even though temperature is constantonly in condensing portion

qc = UA(LMTD)(LMTD)actual > (LMTD)idealized by desuperheating (UA)actual < (UA)idealized

(LMTD)idealized can be used with justification of compensation of lower (UA)actual

by real condenser rarely strictly for counter-flow or parallel-flow.

Manufacturers provide performance data directed toward selecting equipment.By applying some fundamentals of heat transfer, a user can frequently translate catalog data to non-design conditions.UA-value remains essentially constant for constant water flow rate (low hiAi)

12

Ex2: The catalog for a Vilter 0.2 m×2.13 m (8 in×7 ft) R-22 condenser specifies a

condensing capacity that accommodates a refrigeration load of 204 kW (58.1 tons) at the evaporator when the evaporating temperature is 4.4°C (40°F), the condensing temperature is 40.6°C (105°F), and a 9.8 L/s (156 gpm) flow rate of cooling water enters at 29.4°C (85°F). What condensing temperature would prevail if the cooling water flow rate and its entering temperature remain constant, but the refrigeration capacity is half of the catalog value?

1.Data: R22 condenser204 kW of capacity = qe

R22 in shell: 4.4 C = te , 40.6 C = tc

Water in tubes: Qw = 9.8 L/s, 29.4 C = ti

tc = ? For qe/2 at same Qw and ti

2.Assume: 1.same (UA) at Qw and ti

2. LMTD =(to - ti)/ln[(tc - ti)/(tc - to)]3. Open-type compressor

tc

Qw, ti

to

4.Equations: qc = UA(LMTD)UA = [qc/(LMTD)]1 = [qc/(LMTD)]2

qc1 = HRR1qe , HRR1 = (Tc1/Te)1.7 , T = t + 273qc2 = HRR2qe/2 , HRR2 = (Tc2/Te)1.7, assume Tc2

qc1 = wQwcpw(to1 - ti) find w, cpw to1

(LMTD)1 =(to1 - ti)/ln[(tc1 - ti)/(tc1 – to1)]

UA = qc1/(LMTD)1 , (LMTD)2 = UA/qc2

qc2 = mwcpw(to2 - ti) to2

(LMTD)2 =(to2 - ti)/ln[(tc2 - ti)/(tc2 – to2)] compute tc2

13

Ex2: R22 condenser204 kW of capacity = qe

R22 in shell: 4.4 C = te , 40.6 C = tc

Water in tubes: Qw = 9.8 L/s, 29.4 C = ti

tc = ? For qe/2 at same Qw and ti

6.Calculation: HRR1 = (Tc1/Te)1.7 = (313.6/277.4)1.7 = 1.232qc1 = HRR1qe = 1.232*204 = 251.3 kWto1 = qc1/(mwcpw)+ti

= 251.3/(9.8*4.19)+29.4 = 35.5 C to1 - ti = 35.5- 29.4 = 6.12 Ctc1 – ti = 40.6- 29.4 = 11.2 Ctc1 – to1 = 40.6- 35.5 = 5.08 C(LMTD)1 =6.12/ln[11.2/5.08] = 7.74 CUA = 251.3/7.7= 32.5 kW/C

assume Tc2 = Tc1 –0.7(LMTD) = 35.2 CHRR1 = (308.2/277.4)1.7 = 1.196qc2 = 1.199*204/2 = 122 kW(LMTD)2 = 32.5/122 = 3.76 Cto2 = 122.3/(9.8*4.19)+29.4 = 32.4 C to2 - ti = 32.4- 29.4 = 2.98 Ce = exp[(to2 - ti)/(LMTD)2] = exp(2.98/3.77) = 2.205 tc2 = (ti – e*to2)/(1– e) = (29.4-2.205*32.4)/(1-2.205) = 34.8 C

5.Properties: w=1 kg/L, cpw=4.19 kJ/kgC

7.Analysis: check assume Tc2 = 35.2 Cdiff = 35.2-34.8 C = 0.4 C -OKIf diff > 2 C – iteration requiredHalf load tc decrease 5.8C

14

7. Condenser design

Ex3: The condensing area is to be specified for a refrigerant 22 condenser of a refrigerating system that provides a capacity of 80 kW for air conditioning. The evaporating temperature is 5C, and the condensing temperature is 45C at design conditions. Water from a cooling tower enters the condenser at 30C andleaves at 35C. A two-pass condenser with 42 tubes, arranged as shown, will be used, and the length of tubes is to be specified to provide the necessary area. The tubes are copper and are 14 mm ID and 16 mm OD.

1. Data: condenser: R2280 kW of capacity = qe

two-pass, 42 tubes (as shown)Water in tubes: 30 C = ti , 35 C = to

R22 in shell: 5 C = te , 45 C = tc

copper tubes 14 mm ID, 16 mm DO Compute condensing area Ao = ?

Cold Water inletCondensate outlet

Gas inletDischarge water outlet

2.Assume: 1. turbulent water flow2. LMTD =(to - ti)/ln[(tc - ti)/(tc - to)]3. Open-type compressor HRR = (Tc/Te)1.7

4.new,Fouling; 1/hff = 0.000176 m2/KW

15

to = 35 C

ti = 30 Cรศ.ดร.สมหมาย ปรีเปรม 185 496 MSD III

Discharge water outlet

Water Box

Condenser Shell

Air-Vapor outlet

Cold Water inlet

Condensate outlet

Gas inlet

two-Pass Condenser diagram

tc = 45 C

16

4.Equations: qc = UoAo(LMTD)LMTD =(to - ti)/ln[(tc - ti)/(tc - to)] qc = HRRqe , HRR= (TcTe)1.7 , T = t + 273(LMTD) =(to - ti)/ln[(tc - ti)/(tc – to)]Rtot = Ro + Rtube + Rff + Ri

Rtot = 1/(UoAo) 1/(UoAo) = 1/(hoAo) + x/(kAm) + 1/(hffAi) + 1/(hiAi) 1/Uo= 1/ho + (Ao/Am)x/k+ (Ao/Ai)/hff+ (Ao/Ai)/hi

1. Data: condenser: R2280 kW of capacity = qe

two-pass, 42 tubes (as shown)Water in tubes: 30 C = ti , 35 C = to

R22 in shell: 5 C = te , 45 C = tc

copper tubes 14 mm ID, 16 mm DO Compute condensing area Ao = ?

2.Assume: 1. turbulent water flow2. LMTD =(to - ti)/ln[(tc - ti)/(tc - to)]3. Open-type compressor HRR = (Tc/Te)1.7

4.new,Fouling; 1/hff = 0.000176 m2/KW

tc

Ro

Rtube

Rff

Ri

1. ho = 0.64[g2k3hfg/(tND)]1/4

, k, hfg, of R22 @ tc =45Ct = tvapor -ttube, tvapor = tc, assume tc -ttube

D = OD = 16 mmN = average number of tube in vertical row

N = average in 13 rows = (2*2+6*3+5*4)/13= 3.23 tubes/row

fouling

17

1/Uo= 1/ho + (Ao/Am)x/k+ (Ao/Ai)/hff+ (Ao/Ai)/hi

2. (Ao/Am)x/kcu

Ao/Am = OD/[(OD+ID)/2]copper tube kcu@tave = (to + ti)/2 x = (OD-ID)/2

3. (Ao/Ai)/hff

1/hff = 0.000176 m2/KWAo/Ai = OD/ID

4. (Ao/Ai)/hi

Nu = hiD/kw

Nu = 0.023 Re0.8 Prn, n = 0.4 for heatingRe = VD/Pr = / = cp/kV = mw/(Ac), Ac = (no. of tubes/pass)(ID)2/4qc = mwcpw(to - ti) mw

water , kw , ,, , cp @tave = (to + ti)/2

L

mw= AcV

Ao= (no. of tubes) (ID)L

5.Properties: Water: cpw=4.19 kJ/kgC, w= 1000 kg/m3

k = 0.611 W/mK, = 0.000845 Pa.sCopper: k = 390 W/mKR22: hfg = 166.6 kJ/kg , r = 1130 kg/m3

k r = 0.0805 W/mK, r = 0.000182 Pa.s

18

2. (Ao/Am)x/kcu = (16/15)(0.001/390) = 2.735E-06 W/mm2K

3. (Ao/Ai)/hff = (16/14)/0.000176 = 2.011E-04 W/m2K

4. (Ao/Ai)/hi

HRR = (Tc/Te)1.7 = (318/278)1.7 = 1.257qc1 = HRR1qe = 1.257*80 = 100.5 kWmw = qc/(cpw(to - ti)) = 100.5/(4.19(35-30))=4.812 kg/sAc = (42/2)(0.014)2/4 = 0.003233 m2

V = mw/(Ac) = 4.812/(1000*0.003233) = 1.488 m/sRe = VD/ = 1.493(0.014)(1000)/0.000845 = 24,670 > 10,000 turbulentPr = cp/k = 4.19(0.000845)/0.611 = 5.77Nu = 0.023(24700)0.8(5.77)0.4 = 151.4hi = Nukw/D = 151.4(0.611)/0.014 = 6608 W/m2K

6.Calculation: 1. ho = 0.64[g2k3hfg/(tND)]1/4

assume t = tc -ttube = (45-33)/2 = 6CtND = 0.000182(6)(3.23)(0.016) = 5.654E-05g2k3 = 9.8(1130)2(0.0805)3 = 6531hfg = 166600 J/kgho = 0.64[6531(166600)/(5.654E-05)]1/4 = 1340 W/m2K

45C

35C

30C

ttube

Assume 2.1: Hermetic/open

Assume 2.2: Condensation at tc Assume 2.5: Turbulent

Assume 2.4: New condenser

Assume 2.3: Horizontal tube

19

Steps in Problem Solving

HRR = (Tc/Te)1.7

qc = Uo Ao (LMTD)

LMTD = f(tc , ti , to)

ii

o

iff

o

m

o

oo Ah

A

Ah

A

k A

xA

h U

11

Fouling factor: 1/hff = 0.000176 (m2/KW)

Condensing heat-transfer coefficient

Water-side heat-transfer coefficient

)(

0.725

4/132

ODNt

khgh

fg

o

Ao /Ai = OD/ID

Nu = 0.023 Re0.8 Pr0.4

)(

0.023

4.00.8

k

cIDV

ID

kh

p

i

4.Properties of R22, k, hfg, of R22 @ tc =45CAssume t = tvapor -ttube, N = rowave

4.Properties of copper tubek @ (to + ti)/2 x = (OD-ID)/2 mAo /Am = OD*2/(OD+ID)

4.Properties of water , , k, cp

Resistance of copper tube

V = mw/(Ac) mw = qc/(cpw(to - ti))

20

ii

o

iff

o

m

o

oo Ah

A

Ah

A

k A

xA

h U

11

2.011E-47.460E-4

2.735E-6

1.730E-4

1.123E-3

66.4% 17.9%

0.24%

15.4%

100%

LMTD =(to - ti)/ln[(tc - ti)/(tc - to)]to - ti = 35-30 = 5C tc – ti = 45-30 = 15C tc - to = 45-35 = 10C LMTD = 5/ln(15/10) = 12.33 C

Check for t = tc -ttube = 6C(tc- ttube) = qc/(hoAo) = 100.5/(1340*9.155) = 8.2C {diff 2.2C}Iteration: t = 8.2C 1/ho = 1/1240 = 8.066E-04Uo= 845 W/m2K Ao = 9.65 m2 L = 4.57 m(tc- ttube) = qc/(hoAo) = 100.5/(1240*9.65) = 8.4C {diff 0.2C} OKNo fouling: Uo = 1085 W/m2K, Ao = 7.51 m2, L = 3.56 m Uo 22%

1/ho = 1/1340 = 7.46E-04(Ao/Am)x/k = 2.735E-06(Ao/Ai)/hff = 2.011E-04(Ao/Ai)/hi = 1.730E-41/Uo= 7.46E-04+2.735E-06+2.011E-04+1.730E-04 = 1.23E-03 m2K/WUo = 891 W/m2KAo = qc/Uo/(LMTD) = 100.5/891/12.33 = 9.155 m2

L = Ao/((OD)*42) = 9.155/(*0.016*42) = 4.34 m

66%<1%18%15%

Fouling decrease capacity: frequent tube cleaning can improve system performance

21

Ex4: R22 condenser from Ex280 kW of capacity = qe

R22 in shell: 5C = te , 45C = tc

Water in tubes: Qw = 4.8 L/s, 30C = ti

tc = ? For qe/2 at same Qw and ti

6.Calculation: HRR1 = (Tc1/Te)1.7 = (318/278)1.7 = 1.257qc1 = HRR1qe = 1.257*80 = 100.5 kWto1 = qc1/(mwcpw)+ti

= 100.5/(4.8*4.19)+30 = 35C to - ti = 35-30 = 5C tc – ti = 45-30 = 15C tc - to = 45-35 = 10C LMTD = 5/ln(15/10) = 12.33 CUA = 100.5/12.33= 8.153 kW/C

assume Tc2 = Tc1 –0.7(LMTD) = 36.4 CHRR1 = (309.4/278)1.7 = 1.199qc2 = 1.199*80/2 = 48 kW(LMTD)2 = 8.153/48 = 5.88 Cto2 = 48/(4.8*4.19)+30 = 32.4 C to2 - ti = 32.4- 30 = 2.4 Ce = exp[(to2 - ti)/(LMTD)2] = exp(2.4/5.88) = 1.5 tc2 = (ti – e*to2)/(1– e) = (29.4-1.5*32.4)/(1-1.5) = 37.2 C

5.Properties: w=1 kg/L, cpw=4.19 kJ/kgC

7.Analysis: check assume Tc2 = 36.4 Cdiff = 36.4-37.2 C = -0.8 C -OKIf diff > 2 C – iteration requiredHalf load tc decrease 7.8C

22

8. Wilson plots determine individual hi, ho

A Wilson plot: A graph of 1/Uo & 1/V0.8

For a water-cooled condenser, a tests series is run to determine U values for various cooling-water flow rate

ii

o

m

o

oo Ah

A

k A

xA

h U

11 const 0.8Vhi

8.0

1slope

11

V k A

xA

h U m

o

oo

Assume constant properties within not large temp. range

intercept 1/ho is calcultaed by subtractingxAo/kAm from the intercept

loading/heat removal of condenser t ho

@1/V0.8 = 0 (infinite V) – high velocity flow

For an air-cooled condenser The abscissa is 1/V0.5 hf = 38 V 0.5

23

Ex5: R22 condenser from Ex280 kW of capacity = qe

R22 in shell: 5C = te , 45C = tc

Water in tubes: 30 C = ti , 35 C = to

Make a Wilson plots

1/ho = 7.46E-04(Ao/Am)x/k = 2.735E-06(Ao/Ai)/hff = 2.011E-041/ho+( Ao/Am)x/k+(Ao/Ai)/hff = 9.5E-04 V = 1.488 m/s, hi = 6608 W/m2K (Ao/Ai)/hi = 1.730E-4 = 2.377E-04/V0.8

1/Uo= 9.5E-04 + (Ao/Ai)/hi

1/Uo= 9.5E-04 +2.377E-04/V0.8

At 1/V0.8 = 0.728, 1/Uo= 1.23E-03

1/ho+( Ao/Am)x/k+(Ao/Ai)/hff = 9.5E-04

For constant ho

Uo increases with water flow rate as logarithm function

24

9. Cooling Tower

A cooling tower cools water by spraying water through a stream of ambient air.• Induced- draft Counter flow tower• Induced- draft Crossflow tower• Natural-draft tower

Range – (ti – tw,out )

Approach -- (to – twb,air in)

ti

to

twb,i

25

Transfer of sensible and latent heat with a wetted surface

water

Air

Wi, ti, ps,i

Wa, ta, ps,a

dA

When air flows (ta) past a wetted surface (ti)

Rate of sensible heat, dqs = hcdA(ti – ta)

hc = convective coefficient, kW/m2 K

Rate of mass transfer (ps,i – ps,a)

Wi = humidity ratio of saturated air at ti, (kJ of water vapor)/(kg dry air)

hD = proportional constant, kg/m2

Rate of mass transfer = hDdA(Wi – Wa)

(Wi – Wa)

mass transfer causes a transfer of heat due to condensation or evaporation

Rate of latent heat, dqL = hDdA(Wi – Wa)hfg

hfg = latent heat of water at ti, J/kg

Boundary-layer analysis, Stoecker (1968): hD = hc /cpm

cpm = specific heat of moist air, kJ/kg K = cpm +Wacps 1.00+1.88Wa

26

Principles of enthalpy potential

ai

pm

c hhc

dAhdq

Transfer of sensible and latent heat in direct contact of air and water

fgafgiapmipm

pm

c hWhWtctcc

dAhdq

fgaipsaapsaapfgiip

pm

c hWtcWtcWtchWtcc

dAhdq

pm

cD

c

hh

psappm cWcc

0 fafi hWhW

)()( ipsapsfgfaapfgfiip

pm

c tctchhWtchhWtcc

dAhdq

hi ha

fgaiDaicLs hWWdAhttdAhdqdqdq

27

Inlet air tdb

a) ti = twb

b) ti > twb

c) ti > twb

Straight-line law

a) ti = twbha = constant, ti = constantEvaporative cooling

b) c) ti > twb ha increase, ti decreaseCooling towerThe leaving water temperature can approach the wet-bulb temperature of entering air.For constant heat load and water flow rate:to increases as ambient twb,air increases

Approach -- (to – twb,air in)

Counter flow of air and water, a frequently used.Some water evaporates into the air, a supply of makeup water must be provided.Makeup water contains some dissolved minerals, blowdown must be provided.

28

10. Condenser types in comparison

Water-cool condenser is favored over Air-cool condenser+in large refrigeration system+heat rejected by cooling tower – low tcond

and long distance from compressor+centrifugal-compressor is closed couple to condenser– large pipe, low-r

Air-cool condenser+in air-condition system+lowest first cost+least maintenance cost

29

Evaporative condenser is favored over Water- and air-cool condenser+ in large refrigeration system+ compact+ low condensing temperature power + compressor tdischarge (for ammonia)Eliminator plates: avoid blowing water droplets out of the condenser

Blow-down: to limit the buildup of mineralsin the spray water

30

11. Evaporative Condensers

Most evaporative condensers are of the blow-through type using an axial flow fan in preference to a centrifugal type.

The design of an efficient evaporative condenser requires optimizing of • tube size• tube length• tube spacing• refrigerant circuiting• air-flow rate• casing size• spray-water flow rate

The manufacturer/designer must draw on knowledge of • refrigerant heat transfer• wetted-surface heat transfer • fabrication economics • end-user operation

The condenser user makes decisionsand understands of how three variables affect the performance : • wet-bulb temperature• air-flow rate• spray-water flow rate

31

Nominal sizes and rates for evaporative condensers:Heat-transfer area: 0.25 m2/kW of heat rejection (0.8 ft2/1000 Btu/hr)Spray water circulating rate: 0.018 L/s/kW of heat rejection (5 gph/1000 Btu/hr)Air volume flow rate: 0.03 m3/s/kW of heat rejection (18 cfm/1000 Btu/hr)Air pressure drop through the condenser: 250–375 Pa (1 to 1–1/2 in.water)Rate of water evaporated: 1.5 L/hr/kW of heat rejection (0.12 gph/1000 Btu/hr)Total rate of water consumption: with good quality makeup water 2.2 L/hr/kW of heat rejection (0.18 gph/1000 Btu/hr).Flow rate of spray water: 4 L/s/m2 (6 gpm/ft2) The practical limit is reached when the spray water flow rate is so high that itrestricts the air flow rate.

32

12. Evaporative Condenser and Water-cooled Condenser

548 kWtc = 40.6C

ti = 35.8C

to = 28.9C

twb,i = 25.6C

548 kWtc = 35C

ti = 35.8C

to = 28.9C

twb,i = 25.6C

ti = 35.8C

to = 28.9C

Water-cool condenser with cooling tower tc = 40.6C

Evaporative condenser tc = 35C

qc = m’wcpw(to - ti)+ m’a(ha,o – ha,i)tc = 35C twb,i = 25.6C

qc = qw= mwcpw(to - ti)qw= qa = ma(ha,o – ha,i)tc = 40.6C to = 35.8C

+ m’w < mw+ m’a < ma- higher p in refrigerant line

Data: heat rejection of 548 kWambient wet-bulb twb,i = 25.6CWater ti = 28.9C, to = 35.8C

33

Same qc, twb,i and water (ti, to)Evaporative condenser+ lower condensing temperature tc

+ lower water pumping cost typically about one-third, m’w < mw

+ m’a < ma but larger pressure drop p than in cooling-tower+ compact size- higher pressure drop p in refrigerant line- long distances between compressor and condenser

The air-conditioning application chooses water-cooled condensersBecause long distances between compressor and heat rejecter.The compressor and condenser may be in the basement and the cooling tower on the roof of a multistory building.In many industrial refrigeration plants the evaporative condenser is on the roof of the machine room that houses the compressors, and the distance separating them may be only 6 to 12 m (20 to 40 ft). Also, when a centrifugal compressor serves a water chilling system, the refrigerant chosen has a high specific volume, making condensing in the tubes less practical (condensing in the shell).

34

13. Wet-bulb Temperature on Evaporative Condenser Capacity

Wet-bulb temperature - dominant influence on evaporative condensers capacity

Relative heat-rejection capacity of an ammonia evaporative condenser as F(tc, twb), Ref. at tc = 35°C, twb = 25°C.

qc increases as tc increases or twb decreases

qc = UA(LMTD), 1/(UA) = 1/(hoAo)+1/(hiAi),Air-cooled influenced by (tc – tdb, air inlet)LMTD = (ta,o - ta,i)/(ln(tc - ta,i)/(tc - ta,o))Water-cooled influenced by (tc – ti,water)LMTD = (tw,o - tw,i)/(ln(tc - tw,i)/(tc - tw,o))

Evaporative influenced by (tc – twb, i)But qc not proportional to (tc – twb, i)As (tc,twb) = (40,25°C) qc/qc,ref = 1.6While (tc,twb) = (30,15°C) qc/qc,ref = 1.2Because qc = m’wcpw(to - ti)+ m’a(ha,o – ha,i)mainly by vaporization of water from the condenser tubes

35

14. Catalog Selection – Two Methods

Catalogs of evaporative condensers:1. Condenser capacity or heat-rejection method2. Refrigeration capacity method

Actual heat transfer rate at condenser

For quick selections

ModelABCDEFGHIJ

Heat rejection rateThousands of Btu/hr15441764 19112058220524262720301433813675

kW4525175616036467117978839911077

Graph qc&twb: Capacity factors for selection of an evaporative condenser in conjunction with Table 7.2 using the condenser heat-rejection method

Table 7.2 Nominal capacity of a line of evaporative condensers

36

Ex4: Using Table 7.2 and Graph qc&twb, select a condenser to reject 586 kW (2,000,000 Btu/hr) while operating at a condensing temperature of 35°C (95°F) and a wet-bulb temperature of 25°C (77°F).

1. Data: qc = 586 kW (2,000,000 Btu/hr) tc = 35Ctwb = 25CSelect a condenser

ModelGHI

Heat rejection rateThousands of 272030143381

kW797883991

Graph qc&twb

(tc,twb) = (35,25°C) qc Factor = 1.4586*1.4 = 820 kW or2000*1.4 = 2800 thousands of Btu/hrTable 7.2 Model H 883 kW 3014000 Btu/hr

Graph qc&twb the capacity factor is low when tc is high and twb lowwhen the capacity factor is low, a smaller condenser will be adequate

37

If the Refrigeration capacity method is chosen.Assume te = 5C, Te = 278HRR = (Tc/Te)1.7 = (308/278)1.7 = 1.19qc = HRRqe = 1.19*460 = 586 kWThen Graph qc&twb influence of tc on HRRNeed a separate table correcting for te from manufacturer.

The heat-rejection method is more powerful in accommodating system complexities, such as might occur in two-stage plants. The refrigeration capacity method is useful for quick estimates of the condenser size.

38

15. Capacity Control

When the condenser operates at full capacity, tc is follow twb as it drops, and thus the compressor power will be reduced.Dropping tc for keep full capacity, until limited by

p, kPa

h, kJ/kg• pc is too low to adequately feed level-control valves and expansion valves• the pressure of defrost gas is too low to achieve a satisfactory defrost, i.e. tsat > 15C• if the plant uses screw compressors with their oil cooled by direct injection of refrigerant, the pressure of the liquid must be high enough to force an adequate flow rate of liquid into the compressor, i.e. tc > 21C• savings in compressor power by further lowering of tc are less than savings that would be possible in pump and fan motors of the condensers

pc mass flow qe

pc te

Reducing the condenser capacity (for to minimum pc) by• to reduce the flow of spray water• to reduce the flow of air flow

39

16. Capacity Control – Varying Flow rate of Spray Water

qc constant(spray water flow rate)0.22

Reducing the flow rate of spray water 20% capacity of the condenser drop to 95%

Reducing the flow rate of spray water is not recommended.If the rate is dropped much below the design value, areas of the tubes may become alternately dry and wet. The result is excessive scaling on that tube surface.Avoidance of scale is also one of the reasons for opposing cycling of the pump for capacity control.The second reason is that the frequent stopping and starting of the motor accelerates its wear.

Reducing the flow rate of spray water by • throttling the flow with a regulating valve or • reducing the speed of the pump motor will lower the heat-transfer capacity of the condenser.

40

17. Capacity Control – Varying Air Flow rate

qc constant(air flow rate)0.48

Reducing the air flow rate :

Reducing the flow rate of spray water 50% capacity of the condenser drop to 72%

Reducing the air flow rate by:• Variable-frequency drive of fan motor+ most precise regulation, - first cost

• Two speed fan motor1800/1200 rpm with a two-winding (expensive motor, low-cost starter)1800/900 rpm with a single-winding(low-cost motor, expensive starter)

• Pony motors arrangement mounts a different-speed motor on each end of the shaft and only one is powered while the other idles.

• Fan dampers, the parts sometimes fail to move easily in the hostile environment

• Fan cycling on a single-fan unit, but pc oscillates and may cause control problems

• Shutting down one fan in a multiple-fan condenser, most widely used


Recommended