WAC (2/9/2016 10:36 AM) [ 1 ] NOT FOR FILING Chapter 296-46B WAC ELECTRICAL SAFETY STANDARDS, ADMINISTRATION, AND INSTALLATION Last Update: 5/20/14 PART A NEC INSTALLATION AMENDMENTS, STANDARDS, INSPECTIONS, AND DEFINITIONS WAC 296-46B-010 General. Adopted standards. (1) The 2014 2017 edition of the National Electrical Code (NFPA 70 - 20142017) including Annex A, B, and C; Commercial Building Tele- communications Cabling Standard (ANSI/TIA-568-C series, February 2009); Commercial Building Standard for Telecommunications Pathway and Spaces (TIA-569-B, October 2004); Commercial Building Grounding and Bonding Requirements for Telecommunications (ANSI-TIA-607-B, August 2011); Residential Telecommunications Cable Standard (ANSI/TIA/EIA 570-B-2004); and the National Electrical Safety Code (NESC C2-2012 ex- cluding Appendixes A and B) are hereby adopted by reference as part of this chapter. This chapter will be followed where there is any conflict between this chapter and the above adopted standards. The National Electrical Code will be followed where there is any conflict between the National Electrical Code and, ANSI/TIA/EIA 568-C, ANSI/TIA/EIA 569-B, ANSI/TIA/EIA 607-B, ANSI/TIA/EIA 570-B, or the NESC C2. Inspections - General. (6) The installation of all structural elements and mechanical systems (e.g., framing, plumbing, ducting, etc.) must be complete in the area(s) where electrical inspection is requested. Prior to comple- tion of an exterior wall cover inspection, either: (a) The exterior shear panel/sheathing nail inspection must be completed by the building code inspector and, where nail-on siding is to be used, all siding must be installed; or (b) All wiring and device boxes must be a minimum of 63 mm (2 1/2") from the exterior surface of the framing member; or (c) All wiring and device boxes must be protected by a steel plate a minimum of 1.6 mm (1/16") thick and of appropriate width and height installed to cover the area of the wiring or box. Commented [MR(1]: Adopts 2017 National Electrical Code Commented [MR(2]: Siding nails can penetrate cables, junction boxes and even electrical panels, especially in exterior walls of 2X4 construction. Pictures of this are in the May and June 2014 Electrical Currents newsletters
Transcript
Page 1: Chapter 296-46B WAC ELECTRICAL SAFETY … · electrical safety standards, administration, and installation ... ansi/tia/eia 569-b, ansi/tia/eia 607-b, ansi/tia/eia 570-b, or the

WAC (2/9/2016 10:36 AM) [ 1 ] NOT FOR FILING

Chapter 296-46B WAC

ELECTRICAL SAFETY STANDARDS, ADMINISTRATION, AND INSTALLATION

Last Update: 5/20/14

PART A

NEC INSTALLATION AMENDMENTS, STANDARDS, INSPECTIONS, AND DEFINITIONS

WAC 296-46B-010 General. Adopted standards.

(1) The 2014 2017 edition of the National Electrical Code (NFPA

70 - 20142017) including Annex A, B, and C; Commercial Building Tele-

communications Cabling Standard (ANSI/TIA-568-C series, February

2009); Commercial Building Standard for Telecommunications Pathway and

Spaces (TIA-569-B, October 2004); Commercial Building Grounding and

Bonding Requirements for Telecommunications (ANSI-TIA-607-B, August

2011); Residential Telecommunications Cable Standard (ANSI/TIA/EIA

570-B-2004); and the National Electrical Safety Code (NESC C2-2012 ex-

cluding Appendixes A and B) are hereby adopted by reference as part of

this chapter.

This chapter will be followed where there is any conflict between

this chapter and the above adopted standards.

The National Electrical Code will be followed where there is any

conflict between the National Electrical Code and, ANSI/TIA/EIA 568-C,

ANSI/TIA/EIA 569-B, ANSI/TIA/EIA 607-B, ANSI/TIA/EIA 570-B, or the

NESC C2.

Inspections - General.

(6) The installation of all structural elements and mechanical

systems (e.g., framing, plumbing, ducting, etc.) must be complete in

the area(s) where electrical inspection is requested. Prior to comple-

tion of an exterior wall cover inspection, either:

(a) The exterior shear panel/sheathing nail inspection must be

completed by the building code inspector and, where nail-on siding is

to be used, all siding must be installed; or

(b) All wiring and device boxes must be a minimum of 63 mm (2

1/2") from the exterior surface of the framing member; or

(c) All wiring and device boxes must be protected by a steel

plate a minimum of 1.6 mm (1/16") thick and of appropriate width and

height installed to cover the area of the wiring or box.

Commented [MR(1]: Adopts 2017 National Electrical Code

Commented [MR(2]: Siding nails can penetrate cables, junction boxes and even electrical panels, especially in exterior walls of 2X4 construction. Pictures of this are in the May and June 2014 Electrical

Currents newsletters

Page 2: Chapter 296-46B WAC ELECTRICAL SAFETY … · electrical safety standards, administration, and installation ... ansi/tia/eia 569-b, ansi/tia/eia 607-b, ansi/tia/eia 570-b, or the

WAC (2/9/2016 10:36 AM) [ 2 ] NOT FOR FILING

(15) See WAC 296-46B-406 for tamper-resistant receptacle re-

quirements in psychiatric patient care facilities.Listed tamper-

resistant receptacles are required in all licensed day care centers,

all licensed children group care facilities, and psychiatric patient

care facilities where accessible to children five years of age and un-

der. Listed tamper-resistant receptacles are required in psychiatric

patient care facilities where accessible to psychiatric patients over

five years of age and the public access areas in medical facilities.

WAC 296-46B-210 Wiring and protection—Branch circuits.

052(C) Countertops.

(7) If it is impracticable to install the outlet(s) required in

NEC 210.52 (C)(3), a receptacle is not required on any peninsular

counter surface as required by NEC 210.52 (C)(3) so long as the penin-

sular counter area extends no farther than 6' from the face of the ad-

joining countertop. Any outlet(s) eliminated using this subsection

must be installed in the wall space at the point where the peninsula

connects to the wall countertop in addition to the outlets required by

NEC 210.52 (C)(1).

WAC 296-46B-240 Overcurrent protection.

024(C) Not Exposed to Physical Damage

(1) Outdoor enclosures containing overcurrent devices shall be

installed so the bottom of the enclosure containing the overcurrent

devices is not less than 24 inches above finished grade unless the

equipment enclosure is approved for pad- or floor-mounting.

Commented [rm3]: Moved to WAC 296-46B-406. Require-ments for child care facilities and medical facilities are now in 2017 NEC 406.12(C).

Commented [MR(4]: 2017 change to 210.52(C)(3) eliminates peninsular receptacle if one is installed on the wall within the penin-

sula space. Measurement of peninsula is now taken from the con-nected perpendicular wall. A stakeholder proposal would restore the

requirement to 2014 wording.

Commented [MR(5]: Currently, no minimum height is required for outdoor electrical panels. Mirrors requirements for outdoor

equipment supplying Manufactured Homes in NEC 550.32(F) and Recreational Vehicles in 551.77(D). Provides additional protection

for overcurrent devices which may be subject to damage from mois-

ture if mounted near the ground. Also provides additional accessibil-ity for workers.

Formatted: Font: Not Bold

Page 3: Chapter 296-46B WAC ELECTRICAL SAFETY … · electrical safety standards, administration, and installation ... ansi/tia/eia 569-b, ansi/tia/eia 607-b, ansi/tia/eia 570-b, or the

WAC (2/9/2016 10:36 AM) [ 3 ] NOT FOR FILING

WAC 296-46B-250 Wiring and protection—Grounding and bonding.

094 Bonding for other systems.

(8) NEC 250.94 is not adopted.

(9) An accessible means external to enclosures for connecting in-

tersystem bonding and grounding electrode conductors must be provided

at the service equipment and at the disconnecting means for any addi-

tional buildings or structures by at least one of the following means:

(a) Exposed nonflexible metallic raceways;

(b) Exposed grounding electrode conductor or electrode;

(c) Approved means for the external connection of a copper or

other corrosion-resistant bonding or grounding conductor to the

grounded raceway or equipment.

WAC 296-46B-348 Flexible Metal Conduit: Type FMC

012 Uses Not Permitted

NEC 348.12(1) is amended to read: In wet locations unless the

conductors are approved for the specific conditions and the installa-

tion is such that liquid is not likely to enter raceways or enclosures

to which the conduit is connected.

WAC 296-46B-406

004(D)(4) Replacements – Arc Fault Circuit Interrupter Protection

(1) Exception No. 3 is added to NEC 406.4(D)(4): Arc-fault cir-

cuit-interrupter protection shall not be required where the

replacement is due to wear, damage, cosmetic reasons, or

when replacing grounding- or non-grounding-type standard re-

ceptacles with GFCI receptacles, provided there are no modi-

fications to the existing branch circuit.

Commented [MR(6]: This proposal adopts the requirement for intersystem bonding termination in NEC 250.94. The allowances in

paragraph (9) are included in the NEC by exception for existing buildings. For new buildings, with the requirement for a concrete

encased electrode, it is unlikely there will be an exposed grounding

electrode conductor or electrode.

Commented [MR(7]: Restores the allowance for use of FMC in

wet locations which was removed in the 2008 NEC. Properly rated conductor types are approved for use in wet locations. There is no

safety risk if conductors are properly rated and FMC is routed so that

liquid is not likely to enter raceways or enclosures.

Commented [MR(8]: Current NEC requirements are not en-forceable, especially in older homes with knob & tube or two-wire

branch circuits.

Formatted: Numbered + Level: 1 + Numbering Style: 1, 2,3, … + Start at: 1 + Alignment: Left + Aligned at: 0.5" +Indent at: 1"

Formatted: Font: Not Bold

Page 4: Chapter 296-46B WAC ELECTRICAL SAFETY … · electrical safety standards, administration, and installation ... ansi/tia/eia 569-b, ansi/tia/eia 607-b, ansi/tia/eia 570-b, or the

WAC (2/9/2016 10:36 AM) [ 4 ] NOT FOR FILING

012 Tamper-Resistant Receptacles

(2) In addition to the requirements of NEC 406.12, listed tam-

per-resistant receptacles are required in all psychiatric

patient care facilities where accessible to psychiatric pa-

tients and children five years of age and under.

WAC 296-46B-424 Fixed electric space heating equipment.

019 Disconnecting means.

In one- and two-family dwelling units, a disconnecting means is

required for the indoor units(s) of a split system HVAC/R system, un-

less the outside unit's disconnecting means is lockable, disconnects

the indoor unit and an indoor disconnecting means is not required by

the manufacturer.

WAC 296-46B-440 Air conditioning and refrigerating equipment.

014 Disconnecting means.

In one- and two-family dwelling units, a disconnecting means is

required for the indoor units(s) of a split system HVAC/R system, un-

less the outside unit's disconnecting means is lockable, disconnects

the indoor unit and an indoor disconnecting means is not required by

the manufacturer.

WAC 296-46B-553 Special occupancies—Floating buildings.

004 Floating buildings and similar facilities - Services and

feeders.

(3) The second sentence of NEC 553.4 is amended to read: The

overcurrent protective devices that supply the floating building shall

have ground-fault protection not exceeding 30 mA.

Commented [MR(9]: Moved here from WAC 296-46B-010(15) and eliminated requirements for child care facilities that are now in

NEC 406.12.

Formatted: Numbered + Level: 1 + Numbering Style: 1, 2,3, … + Start at: 1 + Alignment: Left + Aligned at: 0.5" +Indent at: 1"

Formatted: Font: Not Bold

Commented [MR(10]: Moved the requirement to WAC 296-46B-440.

Commented [rm11]: Moved here from WAC 296-46B-424. Applies to Air conditioning and refrigerating equipment, not Fixed Electric Space Heating equipment.

Commented [MR(12]: Consistent with the 2017 change in NEC 555.3 for Marinas.

Page 5: Chapter 296-46B WAC ELECTRICAL SAFETY … · electrical safety standards, administration, and installation ... ansi/tia/eia 569-b, ansi/tia/eia 607-b, ansi/tia/eia 570-b, or the

WAC (2/9/2016 10:36 AM) [ 5 ] NOT FOR FILING

WAC 296-46B-680 Special equipment—Swimming pools, fountains and

similar installations.

025 Feeders.

(10) NEC 680.25(A) is amended to read: A feeder between the ser-

vice equipment and the remote panelboard is permitted to run in flexi-

ble metal conduit, an approved cable assembly that includes an equip-

ment grounding conductor within its outer sheath (the equipment

grounding conductor must comply with NEC 250.24 (A)(5)), rigid metal

conduit, intermediate metal conduit, liquidtight flexible nonmetallic

conduit, rigid polyvinyl chloride conduit, reinforced thermosetting

resin conduit, electrical metallic tubing (when installed on or within

a building or crawl space), and electrical nonmetallic tubing (when

installed within a building or crawl space). Aluminum conduit is not

permitted.

WAC 296-46B-705 Interconnected electric power production sources.

031 Location of Overcurrent Protection

(2) In addition to the requirements of NEC 705.31, electric power

production source conductors connected to the supply side of the ser-

vice disconnecting means must be installed using wiring methods speci-

fied for service conductors in WAC 296-46B-230(7).

PART B - ELECTRICAL PLAN REVIEW

WAC 296-46B-900 Electrical plan review. Definition of occupan-

cies.

Plan review for educational, institutional or health care facili-

ties/buildings.

(2) Plan review is a part of the electrical inspection process;

its primary purpose is to determine:

(a) That service/feeder conductors are calculated and sized ac-

cording to the proper NEC or WAC article or section;

(b) The classification of hazardous locations; and

(c) The proper design of emergency and standby systems.

Commented [MR(13]: 2017 NEC change allows Chapter 3 wiring methods unless in a corrosive environment.

Formatted: Font: Not Bold

Commented [MR(14]: Clarifies these unfused conductors must

be installed using the wiring methods specified for service conduc-

tors. Technically they don’t meet the definition of service conduc-

tors.

Formatted: Font: (Default) Courier New, 12 pt

Page 6: Chapter 296-46B WAC ELECTRICAL SAFETY … · electrical safety standards, administration, and installation ... ansi/tia/eia 569-b, ansi/tia/eia 607-b, ansi/tia/eia 570-b, or the

WAC (2/9/2016 10:36 AM) [ 6 ] NOT FOR FILING

(3) Electrical plan review.

(a) Electrical plan review is not required for:

(i) Low voltage systems;

(ii) Lighting specific projects that result in an electrical load

reduction on each feeder involved in the project;

(iii) Heating and cooling specific retrofit projects that result

in an electrical load reduction on each existing feeder involved in

the project, provided there is not a corresponding increase in the

available fault current in any feeder.

(iv) Stand-alone utility fed services that do not exceed 250

volts, 400 amperes where the project's distribution system does not

include:

(A) Emergency systems other than listed unit equipment per NEC

700.12(F);

(B) An essential electrical system defined in NEC 517.2; or

(C) A required fire pump system.; or

(D) An onsite electric power production source(s) such as Solar

Photovoltaic (PV), Fuel Cell, or Wind Electric system(s).

(v) Modifications to existing electrical installations where all

of the following conditions are met:

(A) Service or distribution equipment involved is rated not more

than 400 amperes and does not exceed 250 volts or for lighting cir-

cuits not exceeding 277 volts to ground;

(B) Does not involve emergency systems other than listed unit

equipment per NEC 700.12(F);

(C) Does not involve branch circuits or feeders of an essential

electrical system as defined in NEC 517.2; and

(D) Does not involve an onsite electric power production

source(s) such as Solar Photovoltaic (PV), Fuel Cell, or Wind Electric

systems; and

(DE) Service and feeder load calculations are increased by 5% or

less.

Commented [MR(15]: Clarifies that alternate power production

sources require plan review. These projects are more complex than

most small projects in educational, health care, or institutional facili-

ties which do not require plan review.

Page 7: Chapter 296-46B WAC ELECTRICAL SAFETY … · electrical safety standards, administration, and installation ... ansi/tia/eia 569-b, ansi/tia/eia 607-b, ansi/tia/eia 570-b, or the

WAC (2/9/2016 10:36 AM) [ 7 ] NOT FOR FILING

PART C - PERMITS AND FEES

WAC 296-46B-901 General—Electrical work permits and fees.

General.

(2) Except as allowed for annual permits and two-family dwell-

ings, an electrical work permit is valid for only one specific job

site address.

Permit - Requirements for.

(7) As required by chapter 19.28 RCW or this chapter, an electri-

cal work permit is required for the installation, alteration, or

maintenance of all electrical systems or equipment except for:

(a) Travel trailers;

(b) Class A basic electrical work which includes:

(i) The like-in-kind replacement of lamps; a single set of fuses;

a single battery smaller than 150 amp hour; contactors, relays, tim-

ers, starters, circuit boards, or similar control components; one

household appliance; circuit breakers; single-family residential lumi-

naires; a maximum of five snap switches, dimmers, receptacle outlets,

thermostats, heating elements, luminaire ballasts or drivers/power

supplies for single LED luminaires with an exact same ballast or driv-

er/power supply; component(s) of electric signs, outline lighting, or

skeleton neon tubing when replaced on-site by an appropriate electri-

cal contractor and when the sign, outline lighting or skeleton neon

tubing electrical system is not modified; one ten horsepower or small-

er motor.

For the purposes of this section, "circuit breaker" means a cir-

cuit breaker that is used to provide overcurrent protection only for a

branch circuit, as defined in NEC 100.

Inspection and approval.

(9) Requests for inspections.

(a) Requests for inspections must be made no later than three

business days after an entity completesion it’sof the electri-

cal/telecommunications installation or one business day after any part

of the installation has been energized, whichever occurs first.

(b) Requests for after hours, or weekend inspections, or tempo-

rary installations that will be energized for less than 48 hours must

be made by contacting the local electrical inspection supervisor at

least three working days prior to the requested date of inspection.

Commented [MR(16]: The permit fee schedule allows one permit to cover a two-family dwelling even though the units may have different addresses.

Commented [MR(17]: Adds LED power supplies to the Class A permit exempt list. Similar to a ballast replacement.

Commented [rm18]: Clarifies that a request must be made if an entity’s work is complete even if other work on the project by other

entities is not complete.

Commented [MR(19]: Requires permit holder to give prior

notice to allow inspections of installations such as temporary load

banks, concerts and stage shows.

Page 8: Chapter 296-46B WAC ELECTRICAL SAFETY … · electrical safety standards, administration, and installation ... ansi/tia/eia 569-b, ansi/tia/eia 607-b, ansi/tia/eia 570-b, or the

WAC (2/9/2016 10:36 AM) [ 8 ] NOT FOR FILING

The portal-to-portal inspection fees required for after hours or week-

end inspections are in addition to the cost of the original electrical

work permit.

WAC 296-46B-903 Equipment standards.

General.

Industrial control panel and industrial utilization equipment in-

spection.

(5) Specific definitions for this section:

(a) "Department evaluation" means a review in accordance with

subsection (6)(b) of this section.

PART E - CLASS B PERMITS

WAC 296-46B-908 Class B permits.

Class B electrical work permit - Use.

(2) The Class B random inspection process is only available if

the label is validated and posted Bbefore beginning the work:.

(a) For Class B labels obtained after February 28, 2013:

(i) Prior to, or Iimmediately upon posting the Class B la-

bel/number, the purchaser must use the department's online Class B

system to enter the job site information for an unused Class B label

obtained by the purchaser. If the posting occurs on a weekend or a

federal/state holiday, the purchaser must use the online system to en-

ter the information no later than the first business day after posting

the label/number;

(ii) The person identified as the installer on the Class B label

must post the Class B label or label number, in a conspicuous perma-

nent manner, at the:

(A) Main service/feeder location supplying the structure or sys-

tem; or

(B) Purchaser's equipment, or on the equipment conductors if the

equipment is not in place.

(iii) The Class B label is valid immediately upon the purchaser

completing the job site information in the department's online Class B

system, and posting of the Class B label or label number per sub-

section (2)(a)(ii) above.

Commented [rm20]: This term was replaced in a previous WAC revision with “Normal Department Inspection”.

Commented [rm21]: Clarifies that if Class B eligible work is begun without a valid Class B label, a regular permit is required to

be obtained and an inspection must be performed.

Commented [MR(22]: Corrects a conflict with requirement that

permits or permit numbers must be posted on jobsite prior to begin-

ning the work.

Page 9: Chapter 296-46B WAC ELECTRICAL SAFETY … · electrical safety standards, administration, and installation ... ansi/tia/eia 569-b, ansi/tia/eia 607-b, ansi/tia/eia 570-b, or the

WAC (2/9/2016 10:36 AM) [ 9 ] NOT FOR FILING

(10) Class B work includes the following:

(a) Extension of not more than one branch electrical circuit lim-

ited to 120 volts and 20 amps each where:

(i) No cover inspection is necessary. For the purposes of this

section, cover inspection does not include work covered by any surface

that may be removed for inspection without damaging the surface; and

(ii) The extension does not supply more than two outlets as de-

fined by the NEC.

(b) Single like-in-kind replacement of:

(i) A motor larger than 10 horsepower; or

(ii) The internal wiring of a furnace, air conditioner, refriger-

ation unit or household appliance; or

(iii) An electric/gas/oil furnace not exceeding 240 volts and 100

amps and associated Class 2 low voltage wiring when the furnace is

connected to an existing branch circuit. For the purposes of this sec-

tion, a boiler is not a furnace; or

(iv) An individually controlled electric room heater (e.g., base-

board, wall, fan forced air, etc.), air conditioning unit, heat pump

unit, or refrigeration unit not exceeding 240 volts, 40 minimum cir-

cuit amps and associated Class 2 low voltage wiring when the unit is

connected to an existing branch circuit; or

(v) Circuit modification required to install not more than five

residential load control devices in a residence where installed as

part of an energy conservation program sponsored by an electrical

utility and where the circuit does not exceed 240 volts and 40 amps.

(vi) A single, line-voltage flexible supply whip associated with

(10)(b)(i), (b)(iii), or (b)(iv) above, not over six feet in length,

provided there are no modifications to the branch circuit/feeder load

being supplied by the whip. May be done on the same Class B label with

the replacement unit if done at the same time.

(c) The following low voltage systems:

(i) Repair and replacement of devices not exceeding 100 volt-

amperes in Class 2, Class 3, or power limited low voltage systems in

one- and two-family dwellings; or

(ii) Repair and replacement of devices not exceeding 100 volt-

amperes in Class 2, Class 3, or power limited low voltage systems in

other buildings, provided the equipment is not for fire alarm or nurse

Commented [MR(23]: Current rule would require a regular

permit for replacement of the whip even though a Class B may be used to replace the unit.

Page 10: Chapter 296-46B WAC ELECTRICAL SAFETY … · electrical safety standards, administration, and installation ... ansi/tia/eia 569-b, ansi/tia/eia 607-b, ansi/tia/eia 570-b, or the

WAC (2/9/2016 10:36 AM) [ 10 ] NOT FOR FILING

call systems and is not located in an area classified as hazardous by

the NEC; or

(iii) The installation of Class 2 or 3 device(s) or wiring for

thermostat, audio, security, burglar alarm, intercom, amplified sound,

public address, or access control systems where the installation does

not exceed twenty devices or five thousand square feet. This does not

include fire alarm, nurse call, lighting control, industrial automa-

tion/control or energy management systems; or

(iv) Telecommunications cabling and equipment requiring inspec-

tion in RCW 19.28.470 where the installation does not exceed twenty

devices or five thousand square feet;

(d) The replacement of not more than ten standard receptacles

with GFCI or AFCI receptacles;

(e) The conversion of not more than ten snap switches to dimmers

or occupancy sensors for the use of controlling a luminaire(s) conver-

sion; (f) The like-in-kind replacement of a maximum of twenty: Paddle

fans, luminaires not exceeding 277 volts and 20 amperes; snap switch-

es, dimmers, receptacle outlets, line voltage thermostats, heating el-

ements, or luminaire ballasts, or drivers/power supplies for single

LED luminaires;

(j) The installation or replacement of a single electric sign on

an existing single 120-volt, 20-amp maximum branch circuit.

WAC 296-46B-915 Civil penalty schedule.

Notes: Each day that a violation occurs on a job site may be a separate offense. Once a violation of chapter 19.28 RCW or chapter 296-46B WAC becomes a final judgment, any additional violation within three years

becomes a "second" or "additional" offense subject to an increased penalty as set forth in the following tables. In case of serious noncompliance or a serious violation of the provisions of chapter 19.28 RCW or as described in WAC 296-46B-990, the

department may double the penalty amount, up to ten thousand dollars shown in subsections (1) through (13) of this section. A person, firm, partnership, corporation or other entity who violates a provision of chapter 19.28 RCW or chapter 296-46B WAC is liable for a

civil penalty based upon the following schedule.

(1) Offering to perform, submitting a bid for, advertising, installing

or maintaining cables, conductors or equipment:

(a) That convey or utilize electrical current without having a valid

electrical contractor's license.; or

(b) Used for information generation, processing, or transporting of signals optically or electronically in telecommunications systems

without having a valid telecommunications contractor's license.

Commented [rm24]: Existing policy per September 2014 Elec-trical Currents newsletter article

Commented [MR(25]: LED power supplies are similar to lumi-naire ballasts. Same change as that made with Class A permit ex-

empt list.

Commented [rm26]: Existing policy from May 2005 Electrical Currents newsletter.

Commented [MR(27]: “Serious noncompliance” is defined in WAC 296-46B-990 and includes a serious violation as well as other

serious offenses such as obtaining a certificate through fraud, sub-mitting a fraudulent document to the department, continuous non-

compliance, submitting a false affidavit, etc.

Commented [rm28]: Penalty applies to (a) or (b)

Page 11: Chapter 296-46B WAC ELECTRICAL SAFETY … · electrical safety standards, administration, and installation ... ansi/tia/eia 569-b, ansi/tia/eia 607-b, ansi/tia/eia 570-b, or the

WAC (2/9/2016 10:36 AM) [ 11 ] NOT FOR FILING

First offense: $500

Second offense: $1,500

Third offense: $3,000

Each offense thereafter: $6,000

(2) Employing an individual for the purposes of chapter 19.28

RCW who does not possess a valid certificate of competency or

training certificate to do electrical work.

First offense: $250

Each offense thereafter: $500

(3) Performing electrical work without having a valid certificate of

competency or electrical training certificate.

(a) Failing to visibly display a certificate (must possess a valid, active

certificate)

First offense: $50

Each offense thereafter: $100

(b) Performing electrical work while not possessing a valid certificate

or working outside the scope of a certificate.

First offense: $250

Each offense thereafter: $500

(13) Causing or failing to correct a serious violation. A serious

violation is a violation of chapter 19.28 RCW or chapter 296-46B WAC that creates a hazard of fire or a danger to life safety.

First offense: $500

Second offense: $1,500

Each offense thereafter: $3,000

WAC 296-46B-925 Electrical/telecommunications contractor's li-

cense. General.

(4) The department may deny application, renewal, change of as-

signment of administrator/master electrician, or reinstatement, or is-

suance of an electrical/telecommunications contractor's license if a

firm, an owner, partner, member, or corporate officer owes money as a

result of an outstanding final judgment(s) to the departmentunder

chapter 19.28 RCW.

(10) Firms who install listed plug and cord connected utiliza-

tion equipment are not included in the requirements for licensing in

chapter 19.28 RCW. The plug and cord must be a single listed unit con-

sisting of a molded plug and cord and not exceeding 250 volt 60 ampere

single phase. The plug and cord can be field installed per the manu-

facturer's instructions and the product listing requirements. The uti-

Commented [rm29]: Allows a penalty amount for possessing a

valid certificate but failing to display it. Currently, there is only a

penalty specified for performing electrical work without having a certificate.

Formatted: Left, Line spacing: single

Commented [MR(30]: No penalty category currently exists for

creating a serious violation. Allows for a higher penalty than current practice of issuing a general citation at $250 first offense penalty

amount.

Commented [rm31]: Aligns with denial of change of assign-ment in WAC 296-46B-935.

Commented [rm32]: Allows denial of issuance if penalty is affirmed after application but before issuance of license.

Commented [rm33]: Aligns rule with statute. See RCW 19.28.381.

Page 12: Chapter 296-46B WAC ELECTRICAL SAFETY … · electrical safety standards, administration, and installation ... ansi/tia/eia 569-b, ansi/tia/eia 607-b, ansi/tia/eia 570-b, or the

WAC (2/9/2016 10:36 AM) [ 12 ] NOT FOR FILING

lization equipment must be a single manufactured unit, including the

plug and cord, that does not require any electrical field assembly ex-

cept for the installation of the plug and cord and is allowed to be

plug and cord connected by the NEC. Firms who perform field electrical

servicing, maintaining, or repairing of plug-in and cord connected

utilization equipment or other than household appliances are not in-

cluded in this exemption.

Exemptions - Manufacturers of electrical/telecommunications products.

(22) Manufacturers of electrical/telecommunications systems prod-

ucts will be allowed to utilize a manufacturer's authorized factory-

trained technician to perform initial calibration, testing, adjust-

ment, modification incidental to the startup and checkout of the

equipment, or replacement of components within the confines of the

specific product, without permit or required licensing:

(a) Provided the product:

(i) Has not been previously energized;

(ii) Has been recalled by the Consumer Product Safety Commission;

(iii) Is within the manufacturer's written warranty period, a pe-

riod not to exceed one year from date of original installation; or

(iv) The manufacturer is working under the written request and

supervision of an appropriately licensed electrical contractor.

(b) Except for the replacement of individual components, as al-

lowed above, this exemption does not include the initial installation,

removal, or replacement of the electrical product. Modifications to

the equipment, as designated above, must not include any changes to

the original intended configuration nor changes or contact with exter-

nal or field-connected components or wiring.

(c) The manufacturer will be responsible for obtaining any re-

quired reapproval/recertification from the original listing or field

evaluation laboratory.

(d) The manufacturer must notify the department if any modifica-

tions have been made or reapproval/recertification is required.

Commented [MR(34]: Plug-in household appliances are ex-

empt per RCW 19.28.008 definition of “equipment).

Commented [rm35]: Allows warranty replacement of compo-nents within a normal warranty period, but prevents manufacturers

from selling “service agreements” and performing repairs on an

unlimited basis and calling it a “warranty”.

Page 13: Chapter 296-46B WAC ELECTRICAL SAFETY … · electrical safety standards, administration, and installation ... ansi/tia/eia 569-b, ansi/tia/eia 607-b, ansi/tia/eia 570-b, or the

WAC (2/9/2016 10:36 AM) [ 13 ] NOT FOR FILING

WAC 296-46B-935 Administrator certificate. General.

(1) The department will deny application, renewal, change of as-

signment, or reinstatement, or issuance of an administrator or master

electrician certificate if an individual owes money as a result of an

outstanding final judgment(s) to the departmentunder chapter 19.28

RCW.

(10) All applicants for certificate renewal must:

(a) Submit a complete renewal application;

(b) Pay all appropriate fees as listed in WAC 296-46B-909; and

(c) Provide accurate evidence on the renewal form that the indi-

vidual has completed Complete the continuing education requirements

described in WAC 296-46B-970 prior to renewal. Continuing education

classes are only valid when all the requirements of WAC 296-46B-970

are completed. If an individual files inaccurate or false evidence of

continuing education information when renewing a certificate, the in-

dividual's certificate may be suspended or revoked.

(12) An individual may renew a suspended administrator's certif-

icate by submitting a complete renewal application including obtaining

and submitting the continuing education required for renewal. However,

the certificate will remain in a suspended status for the duration of

the suspension period. Before the suspended administrator’s certifi-

cate can be activated, the holder must pass the appropriate adminis-

trator examination in accordance with RCW 19.28.211(2).

WAC 296-46B-940 Electrician/certificate of competency required.

General.

(1) The department will deny application, renewal, or reinstate-

ment, or issuance of a certificate or permit if an individual owes

money as a result of an outstanding final judgment(s) to the depart-

mentunder chapter 19.28 RCW.

(10) All applicants for certificate of competency renewal must:

(a) Submit a complete renewal application;

Commented [rm36]: Allows denial of issuance if penalties are affirmed after application but before issuance of certificate.

Commented [rm37]: Aligns rule with statute. See RCW

19.28.381.

Commented [rm38]: Left over from a previous requirement for the certificate holder to provide evidence of classes. Now the course

providers must do so per WAC 296-46B-970(7).

Commented [rm39]: This sentence added for consistency with current wording in WAC 296-46B-940 and 942 for certificate of

competency and training certificate renewal requirements.

Commented [rm40]: Corrects a conflict with RCW 19.28.211 which requires retest before activating a suspended certificate.

Commented [rm41]: Allows denial of issuance if penalties are

affirmed after application and before issuance of certificate.

Commented [rm42]: Align rule with statute. See RCW 19.28.381.

Page 14: Chapter 296-46B WAC ELECTRICAL SAFETY … · electrical safety standards, administration, and installation ... ansi/tia/eia 569-b, ansi/tia/eia 607-b, ansi/tia/eia 570-b, or the

WAC (2/9/2016 10:36 AM) [ 14 ] NOT FOR FILING

(b) Pay all appropriate fees; and

(c) Provide accurate evidence on the renewal form that the indi-

vidual has completed Complete the continuing education requirements

described in WAC 296-46B-970 prior to renewal. Continuing education

classes are only valid when all the requirements of WAC 296-46B-970

are completed. If an individual files inaccurate or false evidence of

continuing education information when renewing a certificate of compe-

tency, the individual's certificate of competency may be suspended or

revoked.

(12) An individual may renew a suspended certificate of compe-

tency by submitting a complete renewal application including obtaining

and submitting the continuing education required for renewal. However,

the certificate will remain in a suspended status for the duration of

the suspension period. Before the suspended certificate if competency

can be activated, the holder must pass the appropriate electrician or

master electrician competency examination in accordance with RCW

19.28.211(2).

WAC 296-46B-942 Training certificate required.

General.

(2) An active training certificate is required for all individu-

als throughout the individual's enrollment and matriculation in an ap-

proved construction electrician training school program described in

RCW 19.28.191.

(8) All applicants for training certificate renewal must:

(a) Submit a complete renewal application;

(b) Pay all appropriate fees; and

(c) Provide accurate evidence on the renewal form that the indi-

vidual has completed Complete the approved basic trainee classescon-

tinuing education requirements described in required by WAC 296-46B-

970 prior to renewal. Basic trainee classes are only valid when all

the requirements of WAC 296-46B-970 are completed. If an individual

files inaccurate or false evidence of basic trainee class information

Commented [rm43]: Left over from a previous requirement for the certificate holder to provide evidence of classes. Now the course providers must do so per WAC 296-46B-970(7).

Commented [rm44]: Corrects a conflict with RCW 19.28.211 which requires retest before activating a suspended certificate.

Commented [rm45]: Current language does not require the certificate to be active.

Commented [rm46]: Left over from a previous requirement for

the certificate holder to provide evidence of classes. Now the course

providers must do so per WAC 296-46B-970(7).

Page 15: Chapter 296-46B WAC ELECTRICAL SAFETY … · electrical safety standards, administration, and installation ... ansi/tia/eia 569-b, ansi/tia/eia 607-b, ansi/tia/eia 570-b, or the

WAC (2/9/2016 10:36 AM) [ 15 ] NOT FOR FILING

when renewing a training certificate, the individual's training cer-

tificate may be suspended.

(11) An individual will not be issued a renewed or reinstated

training certificate if the individual owes the department money as a

result of an outstanding final judgment under chapter 19.28 RCW.

Trainees seeking a journey level electrician certificate - Working

with no supervision.

(16) Trainee seeking a general (01) journey level electrician

certificate of competency. After review by the department, a trainee

may be issued a six-month, nonrenewable unsupervised electrical train-

ing certificate that will allow the individual to work without super-

vision if the trainee:

(a) Has submitted a complete application for an unsupervised

electrical training certificate;

(b) Has worked over seven thousand hours properly supervised not

to include more than four thousand of specialty experience;

(c) Has successfully completed or is currently enrolled in an ap-

proved apprenticeship program or an electrical construction trade pro-

gram in a school approved by the board of community and technical col-

leges;

(d) Has paid all appropriate training certificate fees listed in

WAC 296-46B-909; and

(e) Is currently working for and continues to work for a licensed

electrical contractor that employs at least one certified journey lev-

el or specialty electrician in the appropriate specialty; and

(f) Has not previously failed a journey level electrician certif-

icate of competency examination (see WAC 296-46B-960(11)).

Commented [rm47]: Align WAC with statute. See RCW

19.28.381

Commented [rm48]: Coordinate this section with WAC 296-

46B-960(11)

Page 16: Chapter 296-46B WAC ELECTRICAL SAFETY … · electrical safety standards, administration, and installation ... ansi/tia/eia 569-b, ansi/tia/eia 607-b, ansi/tia/eia 570-b, or the

WAC (2/9/2016 10:36 AM) [ 16 ] NOT FOR FILING

WAC 296-46B-970 Continuing education and classroom education re-

quirements.

(3) CLASS AND INSTRUCTOR - GENERAL APPROVAL PROCESS.

(a) The department will:

(i) Rreview the application for completeness and conformance with

the requirements in this section.

(ii) If the application is incomplete, notify the applicant with-

in seven working days of the status of the review and if additional

information is required.

(iii) Complete the review and approval/denial process within fif-

teen working days upon receipt of a complete application or additional

requested information.

(b) The department will deny approval of applications that do not

meet the minimum requirements.

(c) All applications will be considered to be new applications

(i.e., Classes and instructors may not be renewed. All applications

must include all information necessary to show conformance with the

minimum requirements).

(d) Application process:

(i) The applicant must submit a complete application to the de-

partment at least thirty calendar days prior to offering or instruct-

ing a class.

(ii) The department will only consider material included with the

application when reviewing an application.

(iii) All applications must include:

(A) Applicant's name, address, contact name, e-mail address, and

telephone number;

(B) All required fees;

(e) Review process:

(i) When the application is received:

(A) The department must review the application for completeness

within seven working days after receipt.

(B) If the application is incomplete, the department must, within

two working days, notify the applicant of the status of the review and

what additional information is required.

• The applicant must provide any additional information requested

by the department within five working days after the date of notifica-

tion.

Commented [rm49]: Repeat of Review process details in (e)

below. Suggestion from Bethany Rivera.

Page 17: Chapter 296-46B WAC ELECTRICAL SAFETY … · electrical safety standards, administration, and installation ... ansi/tia/eia 569-b, ansi/tia/eia 607-b, ansi/tia/eia 570-b, or the

WAC (2/9/2016 10:36 AM) [ 17 ] NOT FOR FILING

• The department will deny the application if the additional re-

quired information is not received within the five working days after

the date of notification for additional information.

(C) The department must complete the review and approval/denial

process within fifteen working days upon receipt of a complete appli-

cation or additional requested information and within two working days

notify the applicant of the approval/denial in writing or electroni-

cally.

WAC 296-46B-971 Training schools.

(5) Within thirty days after beginning a program, the program

sponsor must supply the department with a roster of individuals en-

rolled in the program. The roster must show each student's name, date

of enrollment, Washington training or electrician certificate number,

and the training program number. Within thirty days after each gradua-

tion cycle, approved training school programs must provide the depart-

ment with a roster of individuals that have successfully completed the

program. The roster must show each student's name, date of completion,

Washington training or electrician certificate number, and the train-

ing program title. An individual must provide a copy of the certifi-

cate of completion or proof of graduation from the electrical training

program when making application to the department for an electrician

examination.

WAC 296-46B-980 Enforcement—Installations, licensing, and certi-

fication requirements. (1) The department inspects the electrical

worksites of individuals, employers, and employees with respect to the

methods and installation requirements of chapter 19.28 RCW and this

chapter. The department's electrical inspectors and electrical audi-

tors make electrical work inspections. The department’s electrical in-

spectors/auditors verify that all required electrical work permits or

labels are obtained prior to beginning any electrical work which re-

quires an inspection. The department's electrical inspectors, electri-

cal auditors, and compliance officers make electrical licens-

ing/certification inspections.

Commented [rm50]: Not needed. When the training school provides the department with a roster of completion, the individual’s

records are updated electronically.

Commented [rm51]: Recommended by AAG Nancy Kellogg. Clarifies that the department’s inspectors/auditors also enforce per-mitting requirements.

Page 18: Chapter 296-46B WAC ELECTRICAL SAFETY … · electrical safety standards, administration, and installation ... ansi/tia/eia 569-b, ansi/tia/eia 607-b, ansi/tia/eia 570-b, or the

WAC (2/9/2016 10:36 AM) [ 18 ] NOT FOR FILING

WAC 296-46B-990 Failure to comply with the electrical contractor

licensing, administrator certification, or electrician certification

laws. General.

(1) If the compliance officer or electrical inspector/auditor de-

termines that an individual, employer, or employee has violated chap-

ter 19.28 RCW or this chapter, the department will issue a citation

that describes the violation.

Suspension or revocation - Of an electrical contractor's license, ad-

ministrator's certificate, master electrician's certificate of compe-

tency, electrician's certificate of competency, or training certifi-

cate. (2) The department may revoke or suspend, for such time as it de-

termines appropriate, an electrical contractor's license, administra-

tor's certificate, master electrician's certificate of competency,

electrician's certificate of competency, or training certificate if:

(a) The license, certificate, or permit was obtained through er-

ror or fraud;

(b) The license, certificate, or permit holder is judged to be

incompetent to work in the electrical construction trade as a master

electrician, journey level electrician, specialty electrician, elec-

trical technician, or electrical trainee;

(c) For serious noncompliance as described below. See RCW

19.28.241 and 19.28.341 for other grounds and procedures.

(d) The license or certificate holder incompletely or inaccurate-

ly reported continuing or basic trainee class education units on an

application for renewal; or

(e) The certificate holder falsely, incompletely, or inaccurately

reported previous work experience.

The department will deny an application for any li-

cense/certificate during the period of revocation or suspension of the

same or another license/certificate under chapter 19.28 RCW.

(3) For the purposes of this section, serious noncompliance in-

cludes, but is not limited to, any of the following:

(a) Causing or Ffailingure to correct a serious violation. A se-

rious violation is a violation of chapter 19.28 RCW or chapter 296-46B

WAC that creates a hazard of fire or a danger to life safety. A seri-

ous violation is also a violation that presents imminent danger to the

public. Imminent danger to the public is present when installations of

Commented [rm52]: Suggested by AAG Nancy Kellogg.

Page 19: Chapter 296-46B WAC ELECTRICAL SAFETY … · electrical safety standards, administration, and installation ... ansi/tia/eia 569-b, ansi/tia/eia 607-b, ansi/tia/eia 570-b, or the

WAC (2/9/2016 10:36 AM) [ 19 ] NOT FOR FILING

wire and equipment that convey or utilize electric current have been

installed in such a condition that a fire-hazard or a life-safety haz-

ard is present. Imminent danger to the public is also present when un-

qualified, uncertified, or fraudulently certified electricians or ad-

ministrators; or unlicensed or fraudulently licensed contractors are

continuously or repeatedly performing or supervising the performance

of electrical work covered under chapter 19.28 RCW. For the purposes

of this section, a certified electrician is considered qualified, pro-

vided the electrician is working within his or her certification;

WAC 296-46B-995 Electrical board—Appeal rights and hearings.

General.

(11) All notices of appeal, with a certified check payable to

the department in the sum of two hundred dollarsamount specified in

subsections (12), (14), (15), or (17) of this section if required,

must be received in the office of the chief electrical inspector, as

secretary to the board, at least forty-five days before the regularly

scheduled board meeting at which the hearing would occur. A separate

two hundred dollar appeal fee is required for each entity's appeal of

a specific violation type (e.g., for a single entity, the designated

administrator, multiple alleged violations of RCW 19.28.061 (5)(a) -

Designated administrator not available, RCW 19.28.061 (5)(d) - Desig-

nated administrator fails to ensure proper permit is purchased, and

RCW 19.28.061 (5)(e) - Designated administrator fails to ensure cor-

rections are made would require a six hundred dollar appeal fee three

of the applicable appeal amounts; one for each specific violation

type). The total appeal fee for each entity seeking an appeal hearing

is one thousand dollars maximum for all violation types. For original

appeals to the board, the appellant must submit twenty copies of any

written argument, briefs, testimony, or documents for the board's con-

sideration at least forty-five days prior to the scheduled hearing.

When appeals, written argument, briefs, testimony, or documents are

received after the deadlines, the appeals, written argument, briefs,

testimony, or documents will be presented to the board at the second

regularly scheduled board meeting.

Appeals

(12) Appeals of penalties issued by the department.

Commented [MR(53]: Aligns rule with amended appeal bond limitations in Statute per 2014 HB 2146

Commented [MR(54]: Aligns rule with amended appeal bond limitations in Statute per 2014 HB 2146

Page 20: Chapter 296-46B WAC ELECTRICAL SAFETY … · electrical safety standards, administration, and installation ... ansi/tia/eia 569-b, ansi/tia/eia 607-b, ansi/tia/eia 570-b, or the

WAC (2/9/2016 10:36 AM) [ 20 ] NOT FOR FILING

(a) A party may appeal a penalty issued by the department, pursu-

ant to chapter 19.28 RCW and this chapter, to the board. The appeal

will be assigned to the office of administrative hearings.

(b) The appeal must be filed within twenty days after the notice

of the decision or penalty is given to the assessed party either by

personal service or by certified mail, return receipt requested,using

a method by which the mailing can be tracked or the delivery can be

confirmed, sent to the last known address of the assessed party and

must be made by filing a written notice of appeal with the chief elec-

trical inspector, as secretary to the board. The request for an appeal

must be accompanied with a certified check payable to the department

in the sum of two hundred dollars or ten percent of the penalty

amount, whichever is less, but in no event less than one hundred dol-

lars. (14) Appeals of suspension, revocation, or nonrenewal.

(a) An appeal of the suspension or revocation of a license or

certificate of competency under RCW 19.28.241 and 19.28.341 or of non-

renewal of a license or certificate of competency under this chapter

will be heard by the board in accordance with chapter 34.05 RCW and

not assigned to the office of administrative hearings. The board will

conduct the hearing and may elect to have the assistance of an admin-

istrative law judge in the proceeding.

(b) The notice of appeal, with the certified check payable to the

department in the sum of two hundred dollars for appeals of a revoca-

tion or suspension of a contractor's or administrator's license, must

be filed within twenty days after the notice of suspension or revoca-

tion is served on the subject of said action, either by personal ser-

vice or using a method by which the mailing can be tracked or the de-

livery can be confirmedby certified mail, return receipt requested,

sent to the last known address of the subject and must be filed by

written notice of appeal with the chief electrical inspector, as sec-

retary to the board. The request for an appeal must be accompanied

with a certified check payable to the department in the sum of two

hundred dollars or, for appeals of nonrenewal due to outstanding final

judgements owed to the department, the amount shall be two hundred

dollars or ten percent of the outstanding penalty amount, whichever is

less, but in no event less than one hundred dollars.

Commented [rm55]: Language was revised in RCW 19.28.131,

.271, .341, and .490.

Commented [MR(56]: Aligns rule with amended appeal bond limitations in Statute per 2014 HB 2146

Commented [MR(57]: Aligns rule with amended appeal bond limitations in Statute per 2014 HB 2146

Commented [rm58]: Language was revised in RCW 19.28.131,

.271, .341, and .490.

Commented [MR(59]: Aligns rule with amended appeal bond limitations in Statute per 2014 HB 2146

Formatted: Font: Courier New, 12 pt, Font color: Black,Raised by 8 pt

Page 21: Chapter 296-46B WAC ELECTRICAL SAFETY … · electrical safety standards, administration, and installation ... ansi/tia/eia 569-b, ansi/tia/eia 607-b, ansi/tia/eia 570-b, or the

WAC (2/9/2016 10:36 AM) [ 21 ] NOT FOR FILING

(17) Appeals pertaining to engineer approval or electrical test-

ing laboratory recognition and accreditation.

(a) A party may appeal a decision issued by the department pursu-

ant to WAC 296-46B-997 or 296-46B-999. The appeal will be heard by the

board in accordance with chapter 34.05 RCW and not assigned to the of-

fice of administrative hearings. The board will conduct the hearing

and may elect to have the assistance of an administrative law judge in

the proceeding.

(b) The notice of appeal, with the certified check payable to the

department in the sum of two hundred dollars for appeals pertaining to

engineer approval or recognition and accreditation of an electrical

testing laboratory, must be filed within twenty days after the notice

of the department's decision is served on the subject of said action,

either by personal service or using a method by which the mailing can

be tracked or the delivery can be confirmedby certified mail, return

receipt requested, sent to the last known address of the subject and

must be filed by written notice of appeal with the chief electrical

inspector, as secretary to the board.

WAC 296-46B-997 Engineer approval.

(24) Within ten calendar days after affixing the evaluation mark,

the engineer must submit a copy of the evaluation report to their:

(a) Local electrical inspection office submitted electronically

in a format approved by the department; and

(b) Cclient submitted in any format acceptable to the client and

engineer.

WAC 296-46B-999 Electrical testing laboratory requirements. Gen-

eral. (27) Within thirty calendar days after affixing the evaluation

mark, the laboratory must submit a copy of the evaluation report to

their:

(a) Local electrical inspection office submitted electronically

in a format approved by the department; and

(b) Cclient submitted in any format acceptable to the client and

testing laboratory.