+ All Categories
Home > Documents > CHAPTER 5 ENHANCEMENT OF POWER QUALITY USING...

CHAPTER 5 ENHANCEMENT OF POWER QUALITY USING...

Date post: 28-Apr-2018
Category:
Upload: ngoduong
View: 219 times
Download: 4 times
Share this document with a friend
30
CHAPTER 5 ENHANCEMENT OF POWER QUALITY USING DSTATCOM 5.1. INTRODUCTION The DSTATCOM consists of a current-controlled VSI which injects current at the PCC through the interface inductor. The operation of VSI is supported by a dc storage capacitor. The transient response of the DSTATCOM is very significant while compensating ac and dc loads [96]. In some of the electric power consumers, such as the telecommunications industry, power-electronics drive applications, etc., there is a constraint for ac as well as dc loads [3]. The telecommunication industry uses several parallel-connected switch-mode rectifiers to support dc bus voltage. Such an arrangement draws nonlinear load currents from the utility. This causes reduced power factor, more losses and less efficiency [57]. Obviously, there are Power Quality issues, such as unbalance, poor power factor, and harmonics produced by telecom equipment in power distribution networks. Therefore, the functionalities of the conventional DSTATCOM should be increased to mitigate the above mentioned PQ problems and to supply the dc loads from its DC Link as well [45]. A DSTATCOM simulation model has been created in MATLAB/Simulink, then analyze the dynamic and steady-state performance of DSTATCOM of two typical case studies have been
Transcript

CHAPTER 5

ENHANCEMENT OF POWER QUALITY USING DSTATCOM

5.1. INTRODUCTION

The DSTATCOM consists of a current-controlled VSI which

injects current at the PCC through the interface inductor. The

operation of VSI is supported by a dc storage capacitor. The transient

response of the DSTATCOM is very significant while compensating ac

and dc loads [96]. In some of the electric power consumers, such as

the telecommunications industry, power-electronics drive

applications, etc., there is a constraint for ac as well as dc loads [3].

The telecommunication industry uses several parallel-connected

switch-mode rectifiers to support dc bus voltage. Such an

arrangement draws nonlinear load currents from the utility. This

causes reduced power factor, more losses and less efficiency [57].

Obviously, there are Power Quality issues, such as unbalance,

poor power factor, and harmonics produced by telecom equipment in

power distribution networks. Therefore, the functionalities of the

conventional DSTATCOM should be increased to mitigate the above

mentioned PQ problems and to supply the dc loads from its DC Link

as well [45]. A DSTATCOM simulation model has been created in

MATLAB/Simulink, then analyze the dynamic and steady-state

performance of DSTATCOM of two typical case studies have been

79

simulated and the results of voltage and current waveforms are

present in this chapter.

5.2. BASIC CONCEPTS OF DSTATCOM

A distribution static compensator is a voltage source converter

based power electronic device. Usually, this device is supported by

short term energy stored in a dc capacitor. The DSTATCOM filters load

current such that it meets the specifications for utility connection

[134]. The DSTATCOM can fulfill the following points.

1. The result of poor load power factor such that the current drawn

from the supply has a near unity power factor.

2. The result of harmonic contents in loads such that current drawn

from the supply is sinusoidal.

3. The result of unbalanced loads such that the current drawn from

the supply is balanced.

4.The dc offset in loads such that the current drawn from the

supply has no offset.

One of the main features of DSTATCOM is the generation of the

reference compensator currents. The compensator, when it tracks

these reference currents, injects three-phase currents in the ac

system to cancel out disturbances caused by the load. Therefore, the

generation of reference currents from the measurements of local

variables has fascinated wide attention [5]. These methods carry an

inherent assumption that the source is stiff (i.e., the voltage at the

point of common coupling is tightly regulated and cannot be

80

influenced by the currents injected by the shunt device). This however

is not a valid assumption and the concert of the compensator will

reduce considerably with high impedance ac supplies.

The operation of VSI is supported by a dc storage capacitor with

appropriate dc the transient response of the voltage across it. The

transient response of the DSTATCOM is very significant while

compensating AC and DC loads [15].

Fig. 5.1 Basic Circuit Diagram of the DSTATCOM System.

A static synchronous compensator (STATCOM) is one of the

most operative solutions to regulate the line voltage. The STATCOM

consists of a voltage source converter connected in shunt with the

power system and permits to control a leading or lagging reactive

power by means of correcting its ac voltage [110]. A STATCOM for

installation on a distribution power system called DSTATCOM, has

been researched to clear voltage fluctuations and voltage flickers. A

81

shunt active filter intended for installation on a power distribution

system, with emphasis on voltage regulation capability. Theoretical

investigation as well as computer simulation provides the dynamic

performance of harmonic damping and voltage regulation. As a result,

harmonic damping has the capability to improve the stability of

voltage regulation.

Thus, modification of the feedback gains makes it possible to

decrease voltage fluctuation in transient states, when the active filter

has the function of combined harmonic damping and voltage

regulation. The simulation results are shown to verify the effectiveness

of the active filter capable of both harmonic damping and voltage

regulation [84].

5.3. CONTROL STRATEGIES

For the controlling of voltage source converter and DC Link

voltage, different types of controllers are included to control the main

module.

5.3.1. Harmonic Damping

There are several methods to extract the harmonic components

from the detected three-phase waveforms. Among them, the so-called

p - q theory based on time domain has been widely applied to the

harmonic extraction circuit of active filters [15]. The detected three-

phase voltage is transformed into the D – Q coordinates as shown in

82

Fig.5.2. Two first order digital high pass filters (HPFs) with the same

cut off frequency as 20 Hz extract the dc component Vhd*, Vhq

* and V0

which corresponds to the fundamental frequency in the coordinates.

Fig. 5.2 Block Diagram of the control circuit equipped with the

Function of voltage regulation and Harmonic Damping.

5.3.2. Voltage Regulation

In line voltage regulation part is performed by a feedback

control. Two co ordinates Vd and Vq is compared with harmonic

extracted voltage *

hdV and *

hqV . A gain KV amplifies and to produce

current references for harmonic damping Ihd, Ihq and I0 as given in

(5.1), (5.2) and (5.3). The current reference for the voltage source

inverter is the sum of the current references from the three parts, as

follows:

83

)()()( ***

dcdcdhdhVcd VVVVGKsI (5.1)

)()( **

qhqhVcq VVGKsI (5.2)

)(3

1)(*

cbao VVVsI (5.3)

The obtained current reference is converted three phase current

reference by inverse D – Q transformation*

caI , *

cbI and*

ccI . The

three phase reference compensating current is compared with the

active filter compensating current extracted from ac system. Thus

three phase compensating current Ica, Icb and Icc are produced. The

obtained reference current is given to a PWM scheme, which is used to

generate controlled gate signal for shunt active filter.

5.3.3. DC Bus Voltage Control and PWM Method

A critical issue in this hybrid active filter is the dc-bus voltage

control. The dc bus consists of a single capacitor charged from the

power supply. During operation, the active filter may absorb an

amount of active power into or release it from the dc capacitor.

Excessive active power absorption will increase the dc-bus voltage,

and may damage the active filter.

The strategy used to control the dc-bus voltage is based on

active power control. According to the D– Q theory, a dc component in

the D–Q coordinates corresponds to active power. No direct axis

84

current on the D–Q coordinates flows in the LC filter. Thus, the active

power is controlled by adjusting the quadrature axis component.

The direct axis is set to zero. Fig. 5.3 shows a block diagram for

the dc bus voltage control. The DC bus voltage is detected and

compared with a reference, amplifying the error signal by a control

gain of 0.12. A limiter is included in the dc-bus control loop. It is

designed to ensure a smooth transient response and to avoid sudden

increments or decrements in the dc-bus voltage.

It is also designed to prevent the control loop from numerical

saturation in the control signals. A DC bus controller is required to

regulate the DC bus voltage Vdc and to compensate the inverter losses

as shown in Fig. 5.2. The measured DC bus voltage Vdc of each phase

is compared with its reference value Vdc*. Similarly, the remaining

phases and added all the error signals. The resulting error is applied

to a PI regulator.

The proportional and integral gains are set to 0.12 Ω-1 and

0.008Ω-1 s-1 respectively. Moreover, the DSTATCOM can build up and

regulate the DC capacitor voltage, the electrical quantity to be

controlled in the dc-voltage feedback loop is )( *

dcdc VV .The limiter

is set to ± 2.5 V in the digital controller which corresponds to 25% of

the maximum control signal. For a 200-V dc-bus voltage, the

maximum dc-bus control signal corresponds to a ± 10 V peak-to-peak

fundamental voltage for the inverter. The PWM gate pulses for

DSTATCOM are generated by using PWM method.

85

5.4. DC LINK VOLTAGE CONTROLLERS

The source supplies an unbalanced nonlinear ac load and a dc

load through the DC Link of the DSTATCOM, as shown in Fig. 5.1.

Due to transients on the load side, the dc bus voltage is significantly

affected. Any change in load directly affects the dc-link voltage. The

sudden removal of load would result in an increase dc-link voltage

above the reference value. The sudden increase of load would result in

reduce the dc-link voltage below the reference voltage. To regulate this

dc-link voltage, closed-loop controllers are used. The proportional-

integral-derivative (PID) control provides a generic and efficient

solution to many control problems. PID controller produces an output

signal consisting of three terms one proportional to the error signal,

another one proportional to the integral of error signal and the third

one proportional to the derivative of error signal. The control signal

from PID controller to regulate DC Link voltage is expressed in (5.4).

dtvVdKdtvVKvVKu dcdcrefddcdcrefidcdcrefpc

(5.4)

The proportional term provides overall control action

proportional to the error signal. An increase in proportional controller

gain reduces rise time and steady-state error but increases the

overshoot and settling time. An increase in integral gain reduces

steady state error but increases overshoot and settling time.

Increasing derivative gain will lead to improved stability.

86

5.4.1. Conventional DC Link voltage controller

Conventional PI Controller is used to maintain the DC Link

voltage at the reference value. To maintain the dc-link voltage at the

reference at the reference value, the DC Link capacitor needs a certain

amount of real power which is proportional to the difference between

the actual and reference voltages .The power required by the capacitor

can be expressed as

dtvVKvVKP dcdcrefidcdcrefpdc (5.5)

The dc-link capacitor has slow dynamics when compared to

the compensator. The drawback of this conventional controller is that

its transient response is slow, especially for fast-changing loads.

Also, the design of PI Controller parameters is quite difficult for

a complex system and hence these parameters are chosen by trial and

error. The disadvantage of the conventional PI Controller is the

transient response of this controller is very slow. Some work related to

the DC Link voltage controller and their stability is reported in [102].

Fig. 5.3 Conventional DC Link Voltage PI Controller.

87

5.4.2. Fast Acting DC Link Voltage Controller

In this an energy based DC Link voltage controller is proposed.

The energy required by the DC Link capacitor to charge from actual

value to the reference value can be computed as

dcdcrefdcdc vVCW 2

2

1 (5.6)

In general, the dc-link capacitor voltage has ripples with double

frequency with that of the supply frequency. The dc power required by

the dc capacitor can be computed as;

22'

2

1dcdcref

cc

dcdc vV

TT

WP (5.7)

However due to the lack of integral term there is steady state

error while compensating ac and dc loads. This is eliminated by

including integral term. The input this controller is error between the

squares of reference and actual capacitor voltages [96]. The controller

is shown in Fig. 5.4.

Fig. 5.4 Fast Acting DC Link Voltage based PI Controller.

88

An energy based controller it gives fast response compared to

the conventional PI Controller. The total power required by the DC

Link capacitor can be computed as;

dtvVKvVKP dcdcrefiedcdcrefpedc 2222 (5.8)

The transient response of the fast acting dc-link voltage

controller is very fast when compared to that of the conventional DC

Link voltage controller. By using Fuzzy Logic Controller instead of PI

Controller we will get the better result.

5.4.3. Fuzzy Logic Controller

Fuzzy control is a control method based on fuzzy logic. Just as

fuzzy logic can be described as “computing with words rather than

numbers. Fuzzy control can be simply described as “control with

sentence rather than equations”. Controllers based on fuzzy logic give

the linguistic strategies control conversion from expert knowledge in

automatic control strategies [52]. The development of control system

based on fuzzy logic involves the following steps:

a. Fuzzification strategy

b. Knowledge base

c. Rule base elaboration

d. Fuzzy inference

e. Defuzziffication strategy.

89

In addition, design of Fuzzy Logic Controller can provide

desirable both small signal and large signal dynamic performance at

same time, which is not possible with linear control technique. The

development of fuzzy logic approach here is limited to the design and

structure of the controller. Here the input is voltage and its variations;

the output constrain as the refI . The inputs of FLC are defined as the

voltage error and change of error.

The fuzzy controller ran with the input and output normalized

universe (-1,1). Fuzzy sets are defined for each input and out put

variable. There are seven fuzzy levels [NL-negative large, NM-negative

medium, NS-negative small Z-zero, PS-positive small, PM-positive

medium, PL-positive large) the membership functions for input and

output variables are triangular.

The min-max method interface engine is used. The fuzzy

method used in this FLC is center of area. The complete set of control

rules is shown in Table 5.1. Each of the 49 control rules represents

the desired controller response to a particular situation. The block

diagram presented in Fig. 5.5 shows a Fuzzy Logic Controller. The

simulation parameters are shown in Table 5.2. In this work to control

the DC Link voltage following controllers are used.

1. PI Controller

2. Fuzzy Logic Controller

3. Fast acting Fuzzy Logic Controller

90

By using the Fast acting Fuzzy Logic Controller instead of PI

Controller and Fuzzy Logic Controller the transient response of the

DSTATCOM is very fast.

Fig. 5.5 Block Diagram of Fuzzy Logic Controller.

The fuzzy logic based DC Link voltage controller gives fast

transient response than that of PI based DC Link voltage controllers.

The transient response of the conventional and fast acting fuzzy logic

DC Link controllers are discussed in test case 2.

Table 5.1 Linguistic rules table

Є/ΔЄ NL NM NS Z PS PM PL

NL NL NL NL NM NM NS Z

NM NL NM NM NS NS Z PS

NS NL NM NS NS Z PS PM

Z NL NM NS Z PS PM PL

PS NM NS Z PS PS PM PL

PM NS Z PS PM PM PM PL

PL Z PS PM PL PL PL PL

91

5.5. SIMULATION OF DSTATCOM WITH PI CONTROLLER

AND FUZZY LOGIC CONTROLLER

Computer simulation has become a crucial part of the power

electronics design procedure. DSTATCOM is a complex power

electronics device and the analysis of its behavior, which leads to

improved understanding, would be very difficult without computer

simulations (if possible at all).

The overall design process can be shortened through the use of

computer simulations, since it is usually easier to study the influence

of a parameter on the system behavior in simulation. The dynamic

and steady-state performance of DSTATCOM is observed for two

typical case studies.

In test case 1 Voltage Regulation and Harmonic Suppression of

Transformerless based DSTATCOM and in test case 2 Transient

response of the PI & Fuzzy Logic DC Link voltage controller of 3-phase

DSTATCOM while compensating AC & DC Loads the results of voltage

and current waveforms are presented below.

5.5.1. Voltage Regulation and Harmonic Suppression of

Transformerless Based DSTATCOM

Table 5.2 shows the circuit parameters used in the DSTATCOM

(shunt active filter). The simulation is carried for distribution system

92

with and without shunt active filter. Total harmonic distortion is

calculated for the system voltage and current.

Table 5.2 Circuit parameters used for the DSTATCOM.

Source voltage Va = Vb = Vc 1000 V

Power P 20KVA

Frequency F 50 Hz

Line inductance La = Lb = Lc 22.7 mH

DC - Capacitor C 4700µF

DC - voltage Vdc ref 200V

Load Diode

Rectifier & R

10Ω

Table 5.3 shows the THD for with and without shunt active

filter. From the Table 5.3, THD for with shunt active filter is very low

compared to without filter. In Fig. 5.8 shows the three phase voltages

of distribution system without shunt active filter. It can be seen that

the harmonic is disturbed in voltages. In Fig. 5.9 shows the three

phase voltages of distribution system with DSTATCOM. It could be

found that the wave shapes of the voltages are pure sinusoidal form.

Fig. 5.6 Main system without DSTATCOM.

93

Fig. 5.7 Main system with DSTATCOM.

Table 5.3 Comparison of Total harmonic distortion.

Parameters

THD for Source

current Is

THD for Load

Voltage VL

Isa Isb Isc Va Vb Vc

Without shunt

active filter

16%

18

%

17% 25% 25% 25%

With shunt

active filter

3.16% 3% 3% 4% 4% 4%

.

94

Fig. 5.8 Three Phase Voltages of Distribution System without

DSTATCOM.

Fig. 5.10 shows the three phase source current of distribution system

without shunt active filter. It can be seen that wave shapes are non

sinusoidal (the harmonic is affected in the source currents). Fig. 5.9

shows the three phase source current of distribution system with

shunt active filter. It can be seen that wave shapes are almost nearly

sinusoidal (the harmonic is suppressed in the source currents).

Fig. 5.9 Three Phase Voltages of Distribution System with

DSTATCOM.

95

Fig. 5.10 Three Phase Source Currents of Distribution System

with out DSTATCOM.

Fig. 5.11 Three Phase Source Currents of Distribution System with

DSTATCOM.

96

Fig. 5.12 Compensating Currents with DSTATCOM.

Fig. 5.12 shows the three phases compensated currents for shunt

active filter. In Fig. 5.13 shows the constant and small ripple dc

capacitor voltage of shunt active filter without startup-transient

overshoot.

Fig. 5.13 DC Voltage of DSTATCOM.

97

Fig. 5.14 Harmonic Spectrum of Phase-A Source Current.

In Fig. 5.14 shows that the harmonic spectrum of phase-A

source current. It can be seen that the Total Harmonic Distortion of

source current of phase-A is 3.16 %. In this case the investigation

with a DSTATCOM for installation on a power distribution system with

mainly focus on harmonic reduction and voltage regulation

performance has been successfully demonstrated in

MatLab/Simulink.

Harmonics generated in the distribution system through non

linear diode rectifier load, which is significantly reduced by Shunt

Active Filter. Simulated results were showed good dc bus voltage

regulation, reduced source harmonic currents, improved power factor

98

and stable operation. In future, intelligent control scheme is developed

to study the proposed system.

5.5.2. Transient Response of the PI & Fuzzy Logic DC-Link

Voltage Controller of 3-Phase DSTATCOM

By using MATLAB/Simulink the load compensator with VSI is

realized. The ac load consists of three-phase unbalanced load and

universal bridge. The system parameters and compensator parameters

are given in Table 5.4. Simulink diagrams of main system without and

with DSTATCOM are shown in Fig.5.15 and Fig.5.16 respectively. The

simulation studies of all the DC Link voltage controllers are analyzed.

Table 5.4 Simulation parameters for DSTATCOM

System parameters

Values

Supply voltage 400V,50 HZ

Unbalanced loads az =25, bz =44+j25.5, cz =50+j86.6

Nonlinear load Universal bridge

DC load dcR =100

DC capacitor dcC =30e-6

Reference dc-link voltage

refV =700

Gains of conventional DC-

link voltage controller

pK =40, Ki =20

Gains of fast acting dc-link

voltage controller

peK =0.11, ieK =0.055

5.5.2.1. Transient Response of the Conventional DC-Link

Voltage Controller

The transient response of the compensator is shown in Fig.

5.22. The total load which is combination of unbalanced and

99

nonlinear load is halved at the instant of t = 0.4s. Due to the sudden

decrease of the load the DC Link voltage is suddenly increase.

Therefore there is an increase in DC Link capacitor voltage above the

reference value.

Fig. 5.15 Main system without DSTATCOM.

The DC Link capacitor voltage is brought back to the reference

value based on the values of PI Controller gains after at t = 0.44s as

shown in Fig. 5.18. At 0.8s the capacitor produces power to the load

and the DC Link voltage is suddenly decrease below the reference

value.

So, the DC Link voltage is suddenly increases by removal of the

load and suddenly decreases by increasing the load. The capacitor

voltage is brought back to the reference value at t = 0.84s due to the

PI Controller action. Transient response of the conventional DC Link

voltage controller is very slow as shown in the Fig. 5.22.

100

Fig. 5.16 Main system with DSTATCOM.

Fig. 5.17 (a) Source Voltage, Fig. 5.17 (b) Source Current

Fig. 5.17 Source Voltage and Current.

101

5.5.2.2. Transient performance of the Fast-Acting DC-Link

Voltage Controller

Transients in the load are considered the same as in the above

simulation study. At t = 0.4s the load is suddenly decrease and the

DC Link voltage is suddenly increased above the reference value and it

is brought back to its reference value based on the values of the PI

Controller gains. The fast acting DC Link voltage controller takes place

at the next instant and it is brought back to its reference value at t =

0.42s as shown in the Fig. 5.23. At t = 0.8s the capacitor produces

power to the load and the DC Link voltage is suddenly decrease below

the reference value. The fast acting DC Link voltage controller takes

place and the DC Link voltage is brought back to the reference value

at t = 0.82s as shown in the Fig. 5.23.

Fig. 5.18 DSTATCOM with PI Controller.

102

5.5.2.3. Transient Response of the Conventional Fuzzy Logic

Controller

By using the Fuzzy Logic Controller instead of the PI Controller

gives better transient response. The load is halved at t = 0.4s. So the

DC Link voltage is suddenly increased above the reference value. And

it is brought back to its reference value due to the Fuzzy Logic

Controller action at the instant of t = 0.42s as shown in the Fig. 5.24

and when the load is switched back to the full load at instant t = 0.8s,

the dc capacitor supplies power to the load. Hence DC Link voltage is

falls below the reference value and it is brought back to the reference

value at t = 0.82s as shown in the Fig. 5.24.

Fig. 5.19 DSTATCOM subsystem.

103

.

Fig. 5.20 Injected Currents.

Fig. 5.21 (a) load voltages, Fig.5.21 (b) load currents

Fig. 5.21 Load Voltage and Current.

Fig. 5.22 Transient Response of the Conventional DC Link

Voltage Controller.

104

Fig. 5.23 Transient Response of the Fast Acting DC Link Voltage

Controller.

Fig. 5.24 Transient Response of the Conventional Fuzzy Logic

Controller.

Fig. 5.25 .Transient Response the Fast Acting Fuzzy Logic Controller.

105

5.5.2.4. Transient Response of the Fast-Acting Fuzzy Logic

Controller

At t = 0.4s the load is halved and the DC Link voltage is

suddenly increased above the reference value and it is brought back to

its reference value due to the Fuzzy Logic Controller. The Fuzzy Logic

Controller takes fast action and it is brought back to the reference

value at the instant of t = 0.402s as shown in the Fig. 5.25. At the

instant of t = 0.8s the load is brought back to its position. At the

instant of t = 0.8s the DC Link voltage is suddenly decreased below

the reference value and it is brought back to its position by using

Fuzzy Logic Controller at the instant of t = 0.802s as shown in the Fig.

5.25.

Fig. 5.26 DSTATCOM with FLC Subsystem.

106

A VSI topology for DSTATCOM compensating ac unbalanced

loads and a dc load supplied by the DC Link of the compensator is

presented. The transient response of the DSTATCOM is very important

while compensating fast varying loads. When there is any change in

the load it will directly affect the DC Link voltage. The transient

response of the conventional DC Link voltage controller is very slow.

So, an energy based DC Link voltage controller is taken for the fast

transient response. By using Fuzzy Logic Controller instead of these

two controllers the transient response is very fast. The conventional

Fuzzy Logic Controller gives the better transient response than that of

the conventional PI Controller. The Fast Acting Fuzzy Logic Controller

gives the fast transient response than that of all previous controllers

which are discussed above. The efficacy of the proposed controller is

established.

5.6. SUMMARY

In first case the research with a DSTATCOM for mechanism on

a power distribution system with mainly focus on harmonic reduction

and voltage regulation performance has been successfully

demonstrated. Harmonics generated in the distribution system

through non linear diode rectifier load, which is significantly reduced

by DSTATCOM. Simulated results demonstrate good dc bus voltage

regulation, reduced source harmonic currents, improved power factor

and stable operation.

107

In second case the transient response of the conventional DC

Link voltage controller is very slow. So, energy based DC Link voltage

controller is taken for the fast transient response. By using Fuzzy

Logic Controller instead of these two controllers the transient

response is very fast. The conventional Fuzzy Logic Controller gives

the better transient response than that of the conventional PI

controller. The fast acting Fuzzy Logic Controller gives the fast

transient response than that of all previous controllers which are

discussed above.


Recommended