CHAPTER 8
UNSYMMETRICAL FAULTS
The sequence circuits and the sequence networks developed in the previous chapter will now be used for finding out fault current during unsymmetrical faults. Specifically we are going to discuss the following three types of faults:
• Single-line-to-ground (1LG) fault • Line-to-line (LL) fault • Double-line-to-ground (2LG) fault
For the calculation of fault currents, we shall make the following assumptions:
• The power system is balanced before the fault occurs such that of the three sequence
networks only the positive sequence network is active. Also as the fault occurs, the sequence networks are connected only through the fault location.
• The fault current is negligible such that the pre-fault positive sequence voltages are same at all nodes and at the fault location.
• All the network resistances and line charging capacitances are negligible. • All loads are passive except the rotating loads which are represented by synchronous
machines. Based on the assumptions stated above, the faulted network will be as shown in Fig. 8.1 where the voltage at the faulted point will be denoted by Vf and current in the three faulted phases are Ifa, Ifb and Ifc. We shall now discuss how the three sequence networks are connected when the three types of faults discussed above occur.
Fig. 8.1 Representation of a faulted segment.
8.1 SINGLE-LINE-TO-GROUND FAULT
Let a 1LG fault has occurred at node k of a network. The faulted segment is then as shown in Fig. 8.2 where it is assumed that phase-a has touched the ground through an impedance Zf. Since the system is unloaded before the occurrence of the fault we have
0== fcfb II (8.1)
3.35
Fig. 8.2 Representation of 1LG fault. Also the phase-a voltage at the fault point is given by
fafka IZV = (8.2)
From (8.1) we can write
=
00
11
111
31
2
2012
fa
fa
I
aaaaI (8.3)
Solving (8.3) we get
3210fa
fafafa
IIII === (8.4)
This implies that the three sequence currents are in series for the 1LG fault. Let us denote the zero, positive and negative sequence Thevenin impedance at the faulted point as Zkk0, Zkk1 and Zkk2 respectively. Also since the Thevenin voltage at the faulted phase is Vf we get three sequence circuits that are similar to the ones shown in Fig. 7.7. We can then write
222
111
000
fakkka
fakkfka
fakkka
IZV
IZVV
IZV
−=
−=
−=
(8.5)
Then from (8.4) and (8.5) we can write
( ) 0210
210
fakkkkkkf
kakakaka
IZZZVVVVV
++−=++=
(8.6)
Again since
( ) 0210 3 faffafafaffafka IZIIIZIZV =++== we get from (8.6)
3.36
fkkkkkk
ffa ZZZZ
VI
32100 +++
= (8.7)
The Thevenin equivalent of the sequence network is shown in Fig. 8.3.
Fig. 8.3 Thevenin equivalent of a 1LG fault.
Example 8.1: A three-phase Y-connected synchronous generator is running unloaded with rated voltage when a 1LG fault occurs at its terminals. The generator is rated 20 kV, 220 MVA, with subsynchronous reactance of 0.2 per unit. Assume that the subtransient mutual reactance between the windings is 0.025 per unit. The neutral of the generator is grounded through a 0.05 per unit reactance. The equivalent circuit of the generator is shown in Fig. 8.4. We have to find out the negative and zero sequence reactances.
Fig. 8.4 Unloaded generator of Example 8.1.
Since the generator is unloaded the internal emfs are
°∠=°−∠== 1200.11200.10.1 cnbnan EEE Since no current flows in phases b and c, once the fault occurs, we have from Fig. 8.4
3.37
( ) 0.405.02.0
1 jj
I fa −=+
=
Then we also have
2.0−=−= fann IXV From Fig. 8.4 and (7.34) we get
°∠=+−=++=
°−∠=−−=++==
72.1240536.1866.06.0025.0
72.1240536.1866.06.0025.00
jIjVEV
jIjVEVV
fancnc
fanbnb
a
Therefore
−
−=
°∠°−∠=
3.07.04.0
72.1240536.172.1240536.1
0
012 CVa
From (7.38) we can write Z1 = jω(Ls + Ms) = j0.225. Then from Fig. 7.7 we have
3333.1225.0
7.011
11 j
jZVEI aan
fa −=−
=−
=
Also note from (8.4) that
210 fafafa III == Therefore from Fig. 7.7 we get
( ) 15.015.03.030
00 jjZ
IVZ n
a
ag =−=−−=
225.02
22 j
IVZ
a
a =−=
Comparing the above two values with (7.37) and (7.39) we find that Z0 indeed is equal to jω(Ls − 2Ms) and Z2 is equal to jω(Ls + Ms). Note that we can also calculate the fault current from (8.7) as
( ) 3333.105.0315.0225.0225.0
10 j
jI fa −=
×+++=
∆∆∆
3.38
8.2 LINE-TO-LINE FAULT
The faulted segment for an L-L fault is shown in Fig. 8.5 where it is assumed that the fault has occurred at node k of the network. In this the phases b and c got shorted through the impedance Zf. Since the system is unloaded before the occurrence of the fault we have
0=faI (8.8)
Fig. 8.5 Representation of L-L fault. Also since phases b and c are shorted we have
fcfb II −= (8.9) Therefore from (8.8) and (8.9) we have
( )( )
−−=
−=
fb
fb
fb
fbfa
IaaIaa
IICI
2
2012
0
31
0 (8.10)
We can then summarize from (8.10)
21
0 0
fafa
fa
III
−=
= (8.11)
Therefore no zero sequence current is injected into the network at bus k and hence the zero sequence remains a dead network for an L-L fault. The positive and negative sequence currents are negative of each other.
Now from Fig. 8.5 we get the following expression for the voltage at the faulted point
fbfkckb IZVV =− (8.12) Again
( ) ( )( ) ( )( )( )21
22
21
22211
210210
kaka
kaka
kckbkckb
kckckckbkbkbkckb
VVaa
VaaVaa
VVVVVVVVVVVV
−−=
−+−=
−+−=−−−++=−
(8.13)
3.39
Moreover since Ifa0 = Ifb0 = 0 and Ifa1 = − Ifb2, we can write
( ) 12
212
21 fafbfafbfbfb IaaaIIaIII −=+=+= (8.14) Therefore combining (8.12)-(8.14) we get
121 fafkaka IZVV =− (8.15) Equations (8.12) and (8.15) indicate that the positive and negative sequence networks are in parallel. The sequence network is then as shown in Fig. 8.6. From this network we get
fkkkk
ffafa ZZZ
VII
++=−=
2121 (8.16)
Fig. 8.6 Thevenin equivalent of an LL fault.
Example 8.2: Let us consider the same generator as given in Example 8.1. Assume that the generator is unloaded when a bolted (Zf = 0) short circuit occurs between phases b and c. Then we get from (8.9) Ifb = − Ifc. Also since the generator is unloaded, we have Ifa = 0. Therefore from (7.34) we get
0.1== anan EV
fbfbbnbn IjIjEV 225.01201225.0 −°−∠=−=
fbfccncn IjIjEV 225.01201225.0 +°∠=−= Also since Vbn = Vcn, we can combine the above two equations to get
849.345.0
12011201−=
°∠−°−∠=−=
jII fcfb
Then
−=
−=
2222.22222.2
0
849.3849.30
012
jjCI fa
We can also obtain the above equation from (8.16) as
2222.2225.0225.0
121 j
jjII fafa −=
+=−=
3.40
Also since the neutral current In is zero, we can write Va = 1.0 and
5.0−=== bncb VVV Hence the sequence components of the line voltages are
=
−−=
5.05.0
0
5.05.0
0.1
012 CVa
Also note that
5.0225.00.1 11 =−= faa IjV 5.0225.0 22 =−= faa IjV
which are the same as obtained before.
∆∆∆
8.3 DOUBLE-LINE-TO-GROUND FAULT
The faulted segment for a 2LG fault is shown in Fig. 8.7 where it is assumed that the fault has occurred at node k of the network. In this the phases b and c got shorted through the impedance Zf to the ground. Since the system is unloaded before the occurrence of the fault we have the same condition as (8.8) for the phase-a current. Therefore
( ) ( )fcfbfa
fcfbfcfbfafa
III
IIIIII
+=⇒
+=++=
0
0
331
31
(8.17)
Fig. 8.7 Representation of 2LG fault. Also the voltages of phases b and c are given by
( ) 03 fafcbfkckb IZIIZVV =+== (8.18)
3.41
Therefore
( )( )
++++
+=
=
kbka
kbka
kbka
kb
kb
ka
ka
VaaVVaaV
VV
VVV
CV2
2012
2
31 (8.19)
We thus get the following two equations from (8.19)
21 kaka VV = (8.20)
kbkakakakbkaka VVVVVVV 223 2100 +++=+= (8.21) Substituting (8.18) and (8.20) in (8.21) and rearranging we get
0021 3 fafkakaka IZVVV −== (8.22) Also since Ifa = 0 we have
0210 =++ fafafa III (8.23)
The Thevenin equivalent circuit for 2LG fault is shown in Fig. 8.8. From this figure we get
( ) ( )fkkkk
fkkkkkk
f
fkkl
kkkk
ffa
ZZZZZZ
Z
VZZZZ
VI
333
02
021
0211
+++
+
=++
= (8.24)
The zero and negative sequence currents can be obtained using the current divider principle as
++−=
fkkkk
kkfafa ZZZ
ZII302
210 (8.25)
+++
−=fkkkk
fkkfafa ZZZ
ZZII
33
02
012 (8.26)
Fig. 8.8 Thevenin equivalent of a 2LG fault.
3.42
Example 8.3: Let us consider the same generator as given in Examples 8.1 and 8.2. Let us assume that the generator is operating without any load when a bolted 2LG fault occurs in phases b and c. The equivalent circuit for this fault is shown in Fig. 8.9. From this figure we can write
fcfbnnbn IjIjVVE 025.02.01201 −=+°−∠=+
fbfcnncn IjIjVVE 025.02.01201 −=+°∠=+ ( )fcfbn IIjV +−= 05.0
Fig. 8.9 Equivalent circuit of the generator in Fig. 8.4 for a 2LG fault in phases b and c. Combining the above three equations we can write the following vector-matrix form
°∠°−∠
=
12011201
25.0025.0025.025.0
fc
fb
II
j
Solving the above equation we get
8182.1849.38182.1849.3
jIjI
c
b
+=+−=
Hence
−=
+−+−=
6162.18283.2
2121.1
8182.1849.38182.1849.3
0
012
jj
j
jjCi fa
We can also obtain the above values using (8.24)-(8.26). Note from Example 8.1 that
( ) 0 and 3.005.0315.0,225.0 021 ==×+=== fZjjZjZZ Then
3.43
8283.2
525.03.0225.0225.0
0.11 j
jjjj
I fa −=
×+
=
6162.1525.0
3.012 j
jjII fafa =−=
2121.1525.0225.0
10 jjjII fafa =−=
Now the sequence components of the voltages are
3636.0225.00.1 11 =×−= faa IjV
3636.0225.0 22 =×−= faa IjV 3636.03.0 00 =×−= faa IjV
Also note from Fig. 8.9 that
( ) 0909.10225.0 =+++= fcfbnana IIjVEV and Vb = Vc = 0. Therefore
=
=
3636.03636.03636.0
00
0909.1
012 CVa
which are the same as obtained before.
∆∆∆
8.4 FAULT CURRENT COMPUTATION USING SEQUENCE NETWORKS
In this section we shall demonstrate the use of sequence networks in the calculation of fault currents using sequence network through some examples.
Example 8.4: Consider the network shown in Fig. 8.10. The system parameters are
given below:
Generator G: 50 MVA, 20 kV, X′′ = X1 = X2 = 20%, X0 = 7.5% Motor M: 40 MVA, 20 kV, X′′ = X1 = X2 = 20%, X0 = 10%, Xn = 5% Transformer T1: 50 MVA, 20 kV∆/110 kVY, X = 10% Transformer T2: 50 MVA, 20 kV∆/110 kVY, X = 10% Transmission line: X1 = X2 = 24.2 Ω, X0 = 60.5 Ω
We shall find the fault current for when a (a) 1LG, (b) LL and (c) 2LG fault occurs at bus-2.
3.44
Fig. 8.10 Radial power system of Example 8.4.
Let us choose a base in the circuit of the generator. Then the per unit impedances of the generator are:
075.0,2.0 021 === GGG XXX The per unit impedances of the two transformers are
1.021 == TT XX The MVA base of the motor is 40, while the base MVA of the total circuit is 50. Therefore the per unit impedances of the motor are
0625.0405005.0,125.0
40501.0,25.0
40502.0 021 =×==×==×== nMMM XXXX
For the transmission line
Ω== 24250
1102
baseZ
Therefore
25.0242
5.60,1.0242
2.24021 ===== LLL XXX
Let us neglect the phase shift associated with the Y/∆ transformers. Then the positive, negative and zero sequence networks are as shown in Figs. 8.11-8.13.
Fig. 8.11 Positive sequence network of the power system of Fig. 8.10.
3.45
Fig. 8.12 Negative sequence network of the power system of Fig. 8.10.
Fig. 8.13 Zero sequence network of the power system of Fig. 8.10.
From Figs. 8.11 and 8.12 we get the following Ybus matrix for both positive and negative sequences
−−
−
==
14100010201000102010001015
21 jYY busbus
Inverting the above matrix we get the following Zbus matrix
==
1667.01333.01000.00667.01333.01867.01400.00933.01000.01400.01800.01200.00667.00933.01200.01467.0
21 jZZ busbus
Again from Fig. 8.13 we get the following Ybus matrix for the zero sequence
−−
−−
=
2.300001440041400003333.13
0 jYbus
Inverting the above matrix we get
=
3125.000000778.00222.0000222.00778.00000075.0
0 jZbus
3.46
Hence for a fault in bus-2, we have the following Thevenin impedances
0778.0,18.0 021 jZjZZ === Alternatively we find from Figs. 8.11 and 8.12 that
18.045.03.021 jjjZZ l ===
0778.035.01.00 jjjZ l ==
(a) Single-Line-to-Ground Fault: Let a bolted 1LG fault occurs at bus-2 when the system is unloaded with bus voltages being 1.0 per unit. Then from (8.7) we get
( ) 2841.20778.018.02
1210 j
jIII fafafa −=
+×=== per unit
Also from (8.4) we get
8524.63 0 jII fafa −== per unit Also Ifb = Ifc = 0. From (8.5) we get the sequence components of the voltages as
4111.018.0
5889.018.01
1777.00778.0
222
112
002
−=−=
=−=
−=−=
faa
faa
faa
IjV
IjV
IjV
Therefore the voltages at the faulted bus are
°∠°−∠=
=
−
11.1079061.011.1079061.0
0
22
12
021
a
a
a
c
b
a
VVV
CVVV
(b) Line-to-Line Fault: For a bolted LL fault, we can write from (8.16)
7778.218.02
121 j
jII fafa −=
×=−= per unit
Then the fault currents are
−=
=
−
8113.48113.400
2
11
fa
fa
fc
fb
fa
IIC
III
Finally the sequence components of bus-2 voltages are
3.47
5.018.0
5.018.010
222
112
02
=−=
=−==
faa
faa
a
IjV
IjVV
Hence faulted bus voltages are
−−=
=
−
5.05.0
0.1
22
12
021
a
a
a
c
b
a
VVV
CVVV
(c)Double-Line-to-Ground Fault: Let us assumes that a bolted 2LG fault occurs at
bus-2. Then
0543.00778.018.0 jjjZ leq ==
Hence from (8.24) we get the positive sequence current as
2676.418.0
11 j
ZjI
eqfa −=
+= per unit
The zero and negative sequence currents are then computed from (8.25) and (8.26) as
( ) 9797.20778.018.0
18.010 j
jjII fafa =+
−= per unit
( ) 2879.10778.018.0
0778.012 j
jjII fafa =
+−= per unit
Therefore the fault currents flowing in the line are
°∠°∠=
=
−
89.42657.611.137657.6
0
2
1
01
fa
fa
fa
fc
fb
fa
III
CIII
Furthermore the sequence components of bus-2 voltages are
2318.018.0
2318.018.01
2318.00778.0
222
112
002
=−=
=−=
=−=
faa
faa
faa
IjV
IjV
IjV
Therefore voltages at the faulted bus are
3.48
=
=
−
00
6954.0
22
12
021
a
a
a
c
b
a
VVV
CVVV
∆∆∆
Example 8.5: Let us now assume that a 2LG fault has occurred in bus-4 instead of the one in bus-2. Therefore
3125.0,1667.0 021 jXjXX === Also we have
1087.03125.01667.0 jjjZ leq ==
Hence
631.31667.0
11 j
ZjI
eqfa −=
+= per unit
Also
( ) 2631.13125.01667.0
1667.010 j
jjII fafa =
+−= per unit
( ) 3678.23125.01667.0
3125.012 j
jjII fafa =
+−= per unit
Therefore the fault currents flowing in the line are
°∠°∠=
=
−
04.205298.596.1595298.5
0
2
1
01
fa
fa
fa
fc
fb
fa
III
CIII
We shall now compute the currents contributed by the generator and the motor to the
fault. Let us denoted the current flowing to the fault from the generator side by Ig, while that flowing from the motor by Im. Then from Fig. 8.11 using the current divider principle, the positive sequence currents contributed by the two buses are
2103.175.025.0
11 jjjII faga −=×= per unit
4206.275.05.0
11 jjjII fama −=×= per unit
Similarly from Fig. 8.12, the negative sequence currents are given as
3.49
7893.075.025.0
22 jjjII faga =×= per unit
5786.175.05.0
22 jjjII fama =×= per unit
Finally notice from Fig. 8.13 that the zero sequence current flowing from the
generator to the fault is 0. Then we have
00 =gaI 2631.10 jIma = per unit
Therefore the fault currents flowing from the generator side are
°∠°∠
°−∠=
=
−
93.67445.107.1737445.1
904210.0
2
1
01
ga
ga
ga
gc
gb
ga
III
CIII
and those flowing from the motor are
°∠°∠
°∠=
=
−
93.258512.307.1548512.3
904210.0
2
1
01
ma
ma
ma
mc
mb
ma
III
CIII
It can be easily verified that adding Ig and Im we get If given above.
∆∆∆
In the above two examples we have neglected the phase shifts of the Y/∆ transformers. However according to the American standard, the positive sequence components of the high tension side lead those of the low tension side by 30°, while the negative sequence behavior is reverse of the positive sequence behavior. Usually the high tension side of a Y/∆ transformer is Y-connected. Therefore as we have seen in Fig. 7.16, the positive sequence component of Y side leads the positive sequence component of the ∆ side by 30° while the negative sequence component of Y side lags that of the ∆ side by 30°. We shall now use this principle to compute the fault current for an unsymmetrical fault.
Example 8.6: Let us consider the same system as given in Example 8.5. Since the phase shift does not alter the zero sequence, the circuit of Fig. 8.13 remains unchanged. The positive and the negative sequence circuits must however include the respective phase shifts. These circuits are redrawn as shown in Figs. 8.14 and 8.15.
Note from Figs. 8.14 and 8.15 that we have dropped the √3α vis-à-vis that of Fig. 7.16. This is because the per unit impedances remain unchanged when referred to the either high tension or low tension side of an ideal transformer. Therefore the per unit impedances will also not be altered.
3.50
Fig. 8.14 Positive sequence network of the power system of Fig. 8.10 including transformer phase shift.
Fig. 8.15 Negative sequence network of the power system of Fig. 8.10 including transformer phase shift.
Since the zero sequence remains unaltered, these currents will not change from those computed in Example 8.6. Thus
00 =gaI and 2631.10 jIma = per unit Now the positive sequence fault current from the generator Iga1, being on the Y-side of the Y/∆ transformer will lead Ima1 by 30°. Therefore
°−∠=°∠×−= 602103.13012103.11 jI ga per unit 4206.21 jIma −= per unit
Finally the negative sequence current Iga2 will lag Ima2 by 30°. Hence we have
°∠=°−∠×= 607893.03017893.02 jjI ga per unit 5786.12 jIma = per unit
Therefore
°∠°−∠°−∠
=
=
−
04.200642.11809996.1
04.200642.1
2
1
01
ga
ga
ga
gc
gb
ga
III
CIII
3.51
Also the fault currents flowing from the motor remain unaltered. Also note that the currents flowing into the fault remain unchanged. This implies that the phase shift of the Y/∆ transformers does not affect the fault currents.
∆∆∆
Example 8.7: Let us consider the same power system as given in Example 1.2, the sequence diagrams of which are given in Figs. 7.18 to 7.20. With respect to Fig. 7.17, let us define the system parameters as:
Generator G1: 200 MVA, 20 kV, X″ = 20%, X0 = 10% Generator G2: 300 MVA, 18 kV, X″ = 20%, X0 = 10% Generator G3: 300 MVA, 20 kV, X″ = 25%, X0 = 15% Transformer T1: 300 MVA, 220Y/22 kV, X = 10% Transformer T2: Three single-phase units each rated 100 MVA, 130Y/25 kV,
X = 10% Transformer T3: 300 MVA, 220/22 kV, X = 10% Line B-C: X1 = X2 = 75 Ω, X0 = 100 Ω Line C-D: X1 = X2 = 75 Ω, X0 = 100 Ω Line C-F: X1 = X2 = 50 Ω, X0 = 75 Ω
Let us choose the circuit of Generator 3 as the base, the base MVA for the circuit is
300. The base voltages are then same as those shown in Fig. 1.23. Per unit reactances are then computed as shown below.
Generator G1: 3.02003002.0 =×=′′X , X0 = 0.15
Generator G2: 1312.022.22
182.02
=
×=′′X , X0 = 0.0656
Generator G3: 2.0=′′X , X0 = 0.15
Transformer T1: 121.02002201.0
2
=
×=X
Transformer T2: 1266.022.22
251.02
=
×=X
Transformer T3: 121.020221.0
2
=
×=X
Line B-C: 5625.033.133
7521 === XX , 75.0
33.133100
0 ==X
Line C-D: 5625.033.133
7521 === XX , 75.0
33.133100
0 ==X
3.52
Line C-F: 375.033.133
5021 === XX , 5625.0
33.13375
0 ==X
Neglecting the phase shifts of Y/∆ connected transformers and assuming that the system is unloaded, we shall find the fault current for a 1LG fault at bus-1 (point C of Fig. 7.17).
From Figs. 7.18 and 7.19, we can obtain the positive and negative sequence Thevenin impedance at point C as (verify)
X1 = X2 = j0.2723 per unit Similarly from Fig. 7.20, the Thevenin equivalent of the zero sequence impedance is
X0 = j0.4369 per unit Therefore from (8.7) we get
( ) 0188.14369.02723.02
10 j
jI fa −=
+×= per unit
Then the fault current is Ifa = 3Ifa0 = 3.0565 per unit.
∆∆∆