1
CHAPTER – 5
INVESTIGATIONS OF VARIOUS METHODS FOR DESIGN OF
BTS
Optimised thermal design of BTS is carried out with many design options. Lot
of feasible thermal design decisions are made before arriving to the preliminary
thermal design .The most critical design is edge guide support where PWBs are
supported at the edges and bosses/stand offs are touched at the middle of the
PWBs.Edge guide option supports the PWBs more robustly so as to withstand severe
vibrations and shocks during transportation and also utilised for carrying large amount
of heat. In this work analysis is initiated without the conduction path at the critical
components. Later design is proceeded with conduction path and fan failure criteria
for different fan tray options.
5.1. BTS DESIGN WITHOUT CONDUCTION PATH
Design is carried out with three of 60 mm external fans and without any
conduction path to the critical components. This analysis case is performed for design
feasibility and also to identify what all the components require conduction path.
2
5.1.1. Temperature contours of System Board
Fig.5.1 Temperature profile of SB
Temperatures shown in the figure 5.1 refers to component junction temperatures.
Maximum temperature 133.7ºC is experienced on processor component in system
board.
Top side components Bottom sde components
3
5.1.2. Temperature contours of BB
Fig.5.2 Temperature profile of BB Top side
Fig.5.3 Temperature profile of BB Bottom side
Temperatures shown near the component are component junction temperatures.
Case temperature is considered for SFP cage. Maximum temperature of around 209°C
is reached in DSP component placed in baseband board.
4
5.1.3. Temperature contours of PB
Fig.5.4 Temperature profile of PB
Temperatures shown in the figure 5.4 explains the temperature contour on the
PB. The junction temperature of the components is mentioned near the components.
Maximum temperature of 166.6 ºC reached in Free wheel Mosfet component.
5
5.1.4. Temperature contours of Chassis
Fig.5.5 Surface temperature of chassis
Chassis surface temperature distribution is shown in the figure5.5. Maximum chassis
surface temperature of 81.2 °C is experienced near the base band board region.
6
5.1.5. External ambient temperature distribution
Fig.5.6 Outlet air temperature distribution
Maximum exit air temperature reached 76 °C.
5.1.6. Velocity profile
Fig.5.7 Velocity profile over the top heat sink of the chassis
7
Fig.5.8 Velocity profile through vent
5.1.7. Fan Operating Point
Table 5.1 Fan Operating pressure & flow
Fan Position Volume Flow(CFM) Volume Flow(m3/Sec) Static Pressure(Pa)
Middle Fan 17.17350 0.00810 27.56
Left Fan 17.38580 0.00820 26.696
Right Fan 17.30550 0.00816 27.021
Fig.5.9 Fan Operating curve details
Left Fan Middle Fan Right Fan
8
Individual fan operating flow and static pressure values are shown in the Tables
5.1 and 5.2. Effective flow through the system is around 0.02446 m3/sec (51.86 cfm)
and system pressure is maximum of 27.556 Pa
5.1.8. Summary of the results
Table 5.2 Component temperature details in System Board & PIU
9
Table 5.3 Component temperature details in BB
Derated component temperature values listed in the tables 5.3 and 5.4 are taken in
BTS thermal design to improve product reliability.This is as per MIL Standards.
Table 5.4 Component temperature details in PB
The summary of computed junction, case and ambient temperature values are listed in
the Tables 5.2, 5.3 and 5.4. Values that are marked in the red colur are above the
10
component specification and failed in the product design.Hence these components
require cooling for the robust design.
5.1.9. Observations and recommendations for the preliminary design
Majority of the critical components on all boards are failed while exceeding
vendor operating thermal margin in the preliminary design phase.As a deisgn
methodlogy,some middle mechanics which is so called heat towers will be introduced
to establish good conduction path between chassis body and components.This inturn
increases the conduction heat transfer to the outer ambient.
5.1.10. Coupling details SB, BB, PB
After the thermal feasibility design, it is decided to keep the towers on the
following devices to cool below the vendor specified temperature limit.Here towers as
metal protrusion are considred for coupling the components with chassis.
Table 5.5 Coupling details of SB & PIU
11
Table 5.6 Coupling details of BB
Table 5.7 Coupling details of PB
Components coupled to the chassis are tabulated in the Tables 5.5, 5.6 and 5.7.
During feasible study thermal simulation is carried out without heat towers. Based on
the study, power dissipation and surface area in consultation with H/W team, coupling
the components with mechanics are considered.
12
5.2. BTS DESIGN WITH CONDCUTION PATH
Assumptions and inputs are same as the previous section but the critical
components which are identified during initial feasibility have been coupled with the
chassis to enhance the conduction heat transfer path.This coupling method is termed
as heat towers.
5.2.1. Temperature contours of SB
Fig.5.10 Temperature profile of SB
Temperatures shown in the figure 5.10 refers to component junction
temperatures.Maximum temperature 127ºC is experienced on regulator (D193)
component in system board.
Top side components Bottom side components
13
5.2.2. Temperature contours of BB
Fig.5.11 Temperature profile of BB Top side
Fig.5.12 Temperature profile of BB Bottom side
Temperatures shown near the component are component junction temperatures.
Case temperature is considered for SFP cage. Maximum temperature of around
115.5°C is reached in dual bidirectional I2C bus component placed in base
band board.
14
5.2.3. Temperature contours of PB
Fig.5.13 Temperature profile of PB
Temperatures shown in the figure 5.13 explains the temperature contour on the
PB. The junction temperature of the components is mentioned near the components.
Maximum temperature of 99.1ºC reached in power board component.
15
5.2.4. Temperature contours of Chassis
Fig.5.14 Surface temperatures of chassis
Chassis surface temperature distribution is shown in the figure 5.14. Maximum
chassis surface temperature of 81.2 °C is experienced near the base band board
region.
5.2.5. Internal ambient temperature distribution
Fig.5.15 Internal ambient temperature of chassis
16
Maximum internal ambient temperature reached above SB and BB is 79.3 and 84.2°C
Maximum internal ambient temperature above PB is 84.8°C and PIU is 84.9°C.
5.2.6. External ambient temperature distribution
Fig.5.16 Outlet air temperature distribution
Maximum exit air temperature reached 76 °C.
5.2.7. Velocity profile
Fig.5.17 Velocity profile over the top heat sink of the chassis
17
Fig.5.18 Velocity profile through vent
Velocity profile profile above and below are as same as the as the preliminary
design as outer ressitance is not changed.
5.2.8. Fan Operating Point
Table 5.8 Fan Operating pressure & flow
Fan Position Volume Flow(CFM) Volume Flow(m3/Sec) Static Pressure(Pa)
Middle Fan 17.17350 0.00810 27.56
Left Fan 17.38580 0.00820 26.696
Right Fan 17.30550 0.00816 27.021
Fig.5.19 Fan Operating curve details Left Fan Middle Fan Right Fan
18
Individual Fan operating flow and static pressure values are shown in the Tables
5.8 and Figure 5.19. Effective flow through the system is around 0.02446 m3/sec
(51.86cfm). System pressure experiencing maximum of 27.556 Pa.The static pressure
and flow have not varied with respect to the preliminary design case as external
resistance is un altered.
5.2.9. Summary of the results
Table 5.9 Component temperature details in SB & PIU
19
Table 5.10 Component temperature details in BB
Derated value of component in sl.number1 is same as vendor datasheet because
the junction temperature of that component is less than 110°C. Hence same value as
vendor specified value is considered as derated value.
Table 5.11 Component temperature details in PB
20
The Summary of computed junction, case and ambient temperature values are
listed in the Tables 5.9, 5.10 and 5.11 for System/plug-in, base band and power board
respectively. The sign in the Table 5.9 denotes the storage temperature considered as
junction temperature for the corresponding components.
5.2.10. Observations and recommendation with heat towers
The observations and recommendations with conduction path are listed in the Table
5.12, given below.
Table 5.12 Observations for further activities
Description Observations Further Activities
System
Board(SB)
In SB, except Regulator
component (Sl.No.16,MCOMPO
No.4344594), all components are
within the allowable junction
temperature as per vendor data
sheet
In system board (SB),
components having Sl.Nos
3,6,7,9,10,11,13,16,17 and 18 are
above the derated temperature
values
Simulation will be carried
out with further design
improvement on mechanics
to meet regulator
component (Sl.No.16,
MCOMPO NO. 4344594)
cooling requirement to
achieve vendor data
temperature.
Discussion is required on
derating values.
Base band
Board(BB)
In Base band board (BB),
components having
Sl.Nos.4,12,13,15,20,22 and 23
are above the derated temperature
Values.
Power
Board(PB)
All components in power board
(PB) are below Derating guideline
temperature Values and vendor
21
Recommednations of the thermal analysis are tabulated in the above Table 5.12.
This table also gives the further activities to be carried out in order to achieve the
derated temperature values of the components in the respective boards.
5.3. BTS DEIGN WITH FAN FAILURE CONDITION FOR
3*60MM
The results of temperature distribution in SB, BB and PB for fan failed conditions are
explained below.
data sheet value
Plug-in
Unit(PIU)
In Plug in unit (PIU) board
LIUcomponent is above the
derated temperature limit but
within vendor specified
temperature.
Simulation will be carried
out with further design
improvement on mechanics
to meet the Derating
values
System level Effective flow through the system
is around 0.02446 m3/sec
(51.86cfm).
System pressure experiencing
maximum of 27.556 pa
Maximum surface temperature of
chassis reached 81.2 °C, which
qualifies as ‘hot’. Due to higher
temperature experienced on the
surface of the chassis it is
advisable to have a warning
sticker for safety consideration.
22
Table 5.13 Fan failure condition for SB & PIU
5.3.1. Observations of Fan fail condition in SB and PIU
Majority of critical components are above the vendor datasheet temperature
and derating temperature limit.
In fan failed condition components temperature is relatively more in middle
fan failure condition. (i.e. Middle fan failure is worst than left and right fan
failure condition).
Critical component in PIU board is below the vendor data sheet and above the
derated temperature value in all fan fail condition.
23
Table 5.14 Fan failure condition for BB
5.3.2. Observations of Fan fail condition in BB
Components temperature in BB board is higher in fan failed condition.
In BB components temperature is relatively less with right fan failure
condition compared to left and middle fan failure condition.
In fan fail condition left fan failure is worst effect compared to middle and
right fan fail condition
24
Table 5.15 Fan failure condition for PB
5.3.3. Observations of Fan fail condition in PB
All components in PB are within vendor specified temperature value and
derated temperature value with fan fail condition (left, middle and right).
In PB components temperature is relatively less with right fan failure
condition compared to left and middle fan failure condition.
In fan fail condition left fan failure is worst effect compared to middle and
right fan fail condition.
25
5.4. BTS THERMAL DESIGN WITH 2*92MM FAN
Two of 92mm fan tray is used to study the thermal performance of the BTS
mechanics.
5.4.1. Thermal model
Thermal Model of BTS with 2*92mm fan tray is shown in below Figure 5.20.
Fig.5.20 Thermal model with 2*92mm Fan assembly
Fig.5.21 Block diagram of fan position considered for Thermal simulation
Figure 5.21 represents the block representation of fan position from left and right
corner.
26
5.4.2. Thermal Model Considerations
All thermal model assumptions are same as previous sections.
Figure 5.21 shows the horizontal as well as axial distance of fans and obstruction.
5.4.3. Mechanical Model Considerations
Fan details considered for dimensions having 2*92mm fan assembly.Fan curve
is scaled down to 85% of maximum speed. Fan curve based on vendor
datasheet.Vents near fan are approximated with rectangular geometry of equal area.
5.4.4. Fan details (92mm) considered for thermal simulation
Fig.5.22 Vendor data fan curve 92mm fan
27
Table 5.16 Flow Vs Static pressure for 92mm fan
Fig.5.22 shows the flow Vs static pressure curve of 92mm fan specified by vendor.
This fan curve points are used for thermal simulation. The Table 5.16 shows the
values provided in the data sheet and calculated value for 85% of the maximum speed
which is calculated. The value considered for the simulation is the calculated value
for 85% of the fan speed.
5.4.5. Temperature contour details of SB
Top Side Bottom Side
Fig.5.23 Temperature contour for SB
28
Fig.5.24 Temperature contour for BB
Fig.5.25 Temperature contour for PB
Bottom side Top side
29
Fig.5.26 Temperature contour for Exit air
Fig.5.27 Temperature contour for Chassis
Figures 5.26 and 5.27 describe the temperature contours of all three PCB’s, exit
air temperature and temperature distribution on chassis surface. The summary of the
each component temperature on the board is discussed in the section 5.4.9
5.4.6. Observations on Exit Air Temperature and Chassis Temperature
The air temperature reaches maximum value of 73.1°C at exit of the chassis.
The temperature rise from inlet to exit is around 8.1°C. Maximum surface
temperature of chassis is reaching up to 79°C. The maximum value of surface
temperature is reaching near the base band board region (BB region)
30
Fig.5.28 Flow distribution through upper chassis
5.4.7. Flow Distribution Pattern
Fig.5.29 Flow distribution through Vents & near obstructions
The air flow distribution from the fan throw the chassis is in figures 5.28 and 5.29.
Figure 5.28 shows the velocity vector throw the heat sink of the upper chassis (i.e
below top cover) in isometric view and top view.
Flow distribution through upper
Chassis (Top View)
Flow distribution through upper
Chassis (Isometric View)
Flow distribution through Vents Flow distribution near Obstructions
31
Figure5.29 explains the flow distribution through the vents and near the
obstruction.The maximum velocity through the heat sink of the upper chassis is
reaching 10.6 m/sec. Flow distribution through the vents shows the maximum
velocity of 10.9 m/sec.
The space below the vents will be obstruction for the flow. The air flow coming
from the fan will be obstructed and the flow path gets deviated. The maximum flow
velocity reached when the flow get obstructed is 7.64 m/sec.
5.4.8. Fan Operating curve
Fig.5.30 Fan operating curve for Left & Right Fan
Fan operating curve for left and right fan is shown inFigure 5.30. The operating
pressure of left fan is 71.6 Pa and flow rate for that pressure is 0.016 m3/sec. The right
fan has the flow rate of 0.026 m3/sec for the operating pressure of 44.2 Pa.
Mechanical obstruction is same for both the fans. The flow from two fans is
getting obstructed at different places. The system resistance, obstructing geometry and
location of fans are also affecting the operating pressure. Hence there is difference in
operating pressure.
Left Fan Right Fan
32
5.4.9. Comparision of Simulation Results with 3*60 & 2*92mm fan
Table 5.17 Temperature results of SB & PIU
In SB all components are well below the vendor specified maximum
temperature when working with 92 mm fan
Components marked with red colour are above the derating temperature
values.
Components like processor (Mcompo No.4332632) is within the limit when
derating temperature values are reconsidered.
In PIU component temperature is within vendor specified temp, but
marginally is above by 0.5°C than derating temp.
33
Table 5.18 Temperature results of BB
All components in BB are within vendor specified temperature values.
Components marked with red color are not meeting the derating guidelines.
34
Table 5.19 Temperature results of PB
All Components in PB are within vendor specified maximum junction
temperature and derating guideline values.
5.4.10. Observations with 92mm Fan
Based on the summary of temperature results, the components temperature in all
boards can be compared in two cases (i.e. for 3*60mm fan and 2*92 mm fan).
In SB there is a reduction in temperature by using 2*92 than 3*60mm. The
temperature reduction in SB is more than 2.2°C for all components junction
temperature.
Junction temperature of component located in PIU is reduced around 4.9°C.
In BB, the least temperature reduction is around 2.0°C for components
junction temperature.
In PB, temperature reduction in component junction temperature is between
1.7 to 3.6°C.
35
From the above simulation results, reduction in temperature for all
components in all boards (SB/PIU, BB and PB) with 2*92mm fan assembly is
noticeed. Hence it can be concluded that the performance of 2*92mm fan is
better than the 3*60mm fan.
5.4.11. Fan comparison details
Single fan comparison
60 mm Fan 92 mm fan
Dimensions 60x60x25.5 mm Dimensions 92x92x38.5mm
Max flow 29.3 CFM Max flow 77.7 CFM
Max static pressure 150 Pa Max static pressure 270 Pa
Acoustic level 49 dB Acoustic level 55 dB
System fan comparison
3 *60 mm Fans 2 *92 mm fan 3 * 92 mm fan
Dimensions 60x60x25.5
mm
Dimensions
92x92x38.5mm
Dimensions
92x92x38.5mm
Max flow 87.9 CFM
(Parallel flow)
Max flow 155.4
CFM(Parallel flow)
Max flow 233.1
CFM(Parallel flow)
Max static pressure 150
Pa
Max static pressure 270
Pa
Max static pressure 270
Pa
Acoustic level 58.6 dB
based on 3 similar
sources
Acoustic level 61 dB
based on two similar
sources
Acoustic level 64.6 dB
based on three similar
sources
2*92 mm fan is able to deliver more volumetric flow with marginally increased
acoustic level (approx 2 dB) compared with the 3*60 mm fans.
36
5.5. BTS DESIGN FOR FAN FAILURE CONDITION WITH
2*92MM FAN ASSEMBLY
Fan failure condition is simulated to ensure when one of the fan fails in its
function.During fan failure, the failed fan will act as a vent where air flow can happen
from functioning fan. This is modeled and simulated.
Fan Failure condition is required to determine the temperature raise of the
component when one of the fans stops functioning.
Fig.5.31 Block diagram of Left fan failure
Fig.5.32 Block diagram of Right fan failure
Figures 5.31 and 5.32 shows the block diagram of left fan and right fan failure
in 2*92 mm fan tray respectively.
37
Fig.5.33 Flow distribution through the fan (Left fan failure)
Fig.5.34 Flow distribution through the fan (Right fan failure)
Figures 5.33 and 5.34 show the flow distribution during left and right fan failed
condition. The failed fans are acting as vent where it allows air to flow.
The results of components temperature in SB, BB and PB for fan failure conditions
are explained in this section
Left fan Right fan
Left fan Right fan
38
Table 5.20 Fan failure condition for SB & PIU
5.5.1. Analysis on fan fail condition in SB and PIU
During left fan failure condition the rise in SB components are relatively less
compared to right fan failure condition.
The minimum temperature rise due to left fan failure is 2.2°C where as for
right fan failure condition the minimum temperature rise is 3.5°C.
In PIU board the component temperature is relatively high during left fan
failure condition than right fan failure condition.
The temperature rise in PIU component is around 4.5°C during left fan failure
condition and temperature rise due to right fan failure condition is 3.3°C.
39
Table 5.21 Fan failure condition for BB
5.6. OBSERVATIONS OF FAN FAIL CONDITION IN BB
The minimum temperature rise due to left fan fail condition is 4.8°C and for
that of right fan failure condition minimum temperature rise is 2.1°C
Few components are within derating temperature values during right fan
failure condition. But they are above the limit during left fan failure condition
(Please refer Sl.No.16 and17).
Thermal impact is more due to left fan failure condition than right fan failure
condition for components in BB.
40
Table 5.22 Fan failure condition for PB
5.6.1. Observations of Fan fail condition in PB
During left fan failure condition the minimum temperature rise is around 4.9°C.
During the right fan failure condition the minimum temperature rise is 1.8°C.
PB components have more impact due to left fan failure condition than right
fan failure condition.
5.7. BTS THERMAL DESIGN WITH 3*92MM FAN ASSEMBLY
The thermal performance of BTS mechanics with 3*92mm fan assembly is
provided data sheet.
41
5.7.1. Thermal model
Front Isometric View Rear Isometric View
Fig.5.35 Thermal model with 3*92mm Fan assembly
Fig.5.36 Block diagram of fan position in 3*92mm Fan Assembly
Figure 5.36 shows the block diagram of fan position considered in 3*92 mm fan tray.
5.7.2. Thermal Model Considerations:
All thermal Model assumptions are as per the section 4.2.1. Figure 5.36 shows
the horizontal as well as axial distance of fans and obstruction.
42
5.8. TEMPERATURE CONTOUR DETAILS
Top Side Bottom Side
Fig.5.37 Temperature contour for SB
Top Side Bottom Side
Fig.5.38 Temperature contour for BB
43
Fig.5.39 Temperature contour for PB
Fig.5.40 Temperature contour for Exit air
Fig.5.41 Temperature contour for Chassis
Temperature contours of all three PCB’s, exit air temperature of the chassis and
temperature distribution on chassis surface are shown in above Figures. The summary
of the each component temperature on the board is discussed in the section 5.8.4.
44
5.8.1. Observations on Exit Air Temperature and Chassis Temperature
The air temperature reaches maximum value of 72.1°C at exit of the chassis.
The temperature raise from inlet to exit is around 7.1°C.Maximum surface
temperature of chassis is reaching up to 79.5°C. The maximum value of surface
temperature is reaching near the base band board region (BB region).
5.8.2. Air flow Distribution
Fig.5.42 Flow distributions through upper chassis
Flow distribution through upper Chassis (Isometric View)
45
Fig.5.43 Flow distributions through Vents & near obstructions
The air flow distribution from the fan through the chassis is shown in Figures
5.42 and 5.43. The velocity vector through the heat sink of the upper chassis
(i.e.below top cover) is shown in Figure 5.42. The figure represents both the isometric
view and top view. The flow distribution through the vents and near the obstruction is
shown in Figure 5.43. The maximum velocity through the heat sink of the upper
chassis is reaching around 11.7 m/sec. Flow distribution through the vents shows the
maximum velocity of 12.1 m/sec. The air flow coming from the fan will get
Flow distribution through Vents Flow distribution near Obstructions
Flow distribution through upper Chassis (Top View)
46
obstructed by the space below the vents. The maximum flow velocity reached when
the flow get obstructed is around 9.41 m/sec.
5.8.3. Fan Operating curve
Fig.5.44 Operating Condition for Left, Middle and Right fan
Fan operating curve for left, middle and right fan is shown in Figure 5.44. The
operating pressure of left fan is 73.8 Pa and flow rate for that pressure is
0.0152m3/sec. The middle fan has the flow rate of 0.0146 m3/sec for the operating
pressure of 75.0 Pa. Right Fan operating pressure is 74.2 m3/sec with flow rate of
0.0147 m3/sec.
Right Fan Middle Fan Left Fan
47
5.8.4. Summary – Simulation results of 3*92mm fan Assembly
Table 5.23 Temperature results of SB & PIU
In SB all components are well below the vendor specified maximum
temperature
Components marked with red colour are above the derating temperature
values.
Components like processor (Mcompo No.4332632) will be within the limit
when derating temperature values are reconsidered.
48
In PIU board the LIU component is marginally higher by 0.9°C than derating
temperature value.
Effective flow of 2*92mm and 3*92mm fan assembly is more or less same.
Components temperature of Sl.no.16, 17 and 18 are little higher with 3*92mm
fan compared to 2*92 mm fan. These components are cooled by means of
natural convection inside the chassis, and temperature is governed by flow
pattern over the chassis. This determines local internal ambient for cooling of
the components which resulted in a little rise in temperature.
Table 5.24 Temperature results of BB
All components in BB are within vendor specified temperature values.
Components marked with red color are not meeting the derating guidelines.
49
Table 5.25 Temperature results of PB
All components in PB are within vendor specified maximum junction
temperature and derating guideline values.
5.8.5. Comparison between 3*92mm and 2*92mm fan
Effective flow through the chassis is almost same for both 3*92 and 2*92 mm
fan assembly
Most of the component temperatures are same for both fan assembly.
3*92mm fans are not operating in the optimum range in the system due to
flow condition between fans.
Few components with 3*92 mm assembly are slightly higher than 2*92mm
fan due to flow pattern above the upper chassis.
50
5.8.6. Observations with 3*92mm Fan
Based on the summary of temperature results and above observations
All components in SB, BB, PB and PIU are well below vendor specified
maximum values.
The operating flow is not upto the mark due to the system resistance,
obstruction to the flow and placement location of the fans.
However, there is a marginal improvement on cooling of all components in all
boards as compared with 2*92mm fan assembly and considerable
improvement compared with 3*60mm fan assembly
Note: Even the temperature results of components with 3*92mm assembly are
better. The temperature results of the components in 3*92mm fan assembly will be
simulated with fan failed conditions. The fan failed condition simulation results will
give the information of rise in components temperature when either of the fan stops its
function.
5.9. FAN FAILURE CONDITION FOR 3*92MM FAN ASSEMBLY
Fan failure condition is carried out to ensure when one of the fan fails in its
function. During fan failure, the failed fan will act as a vent where air flow can
happen from functioning fan. The model of the failed fan will remain the same but
flow will not happen from the failed fan. Fan failure condition simulation is required
to determine the temperature rise of the component when one of the fans stop
functioning.
51
Fig.5.45 Block diagram of Left fan failure in 3*92mm fan assembly
Fig.5.46 Block diagram of Middle fan failure in 3*92mm fan assembly
Figures 5.45 and 5.46 are the block diagrams representing the left and middle
fan failed condition in 3*92 fan assembly
Fig.5.47 Block diagram of Right fan failure in 3*92mm fan assembly
52
Figure 5.47 represents the block diagram of right fan failed condition in
3*92mm fan assembly
Fig.5.48 Flow distribution through Left failed fan
Fig.5.49 Flow distribution through Middle failed fan
Fig.5.50 Flow distribution through Right failed fan
53
Figures 5.48, 5.49 and 5.50 shows the flow distribution when left, middle and
right fans are failed. The failed fan acts as vent and allows air to flow through the
failed fan.
Table 5.26 Fan failure condition for SB & PIU in 3*92mm fan assembly
Table 5.26 is tabulated with the components temperature results of SB due to
fan failed conditions (left, middle and right fan failed conditions). Components
marked with red colour in tables 5.26 and 5.27 are more than the derated value.
Below tables are provided with components temperature in BB and PB
54
Table 5.27 Fan failure condition for BB in 3*92mm fan assembly
Table 5.28 Fan failure condition for PB in 3*92mm fan assembly
55
5.9.1. Observations of fan failed conditions in 3*92 mm Fan assembly
All the components in SB are below the vendor specified value with fan failed
conditions (left, middle and right fan failure)
Middle fan failure has more impact in SB components temperature than left
and right fan failure. In SB components of Sl.no.16 have temperature rise of
5.4 °C due to middle fan failure compared to all fans running condition.
In SB, components of Sl.no.16, 17 and 18 are having more temperature rise
due to middle fan failure.
LIU component in PIU is below vendor specified value.
In PIU board LIU component is having more impact by left fan failure than
middle fan and right fan failure. Right fan failure is having least impact on
component in PIU board.
All the components in BB are well below the vendor specified value with fan
failed conditions (left, middle and right fan failure).
For BB components left fan failure is having more impact than middle and
right fan failure.
Components of Sl.no.12 and 13 in BB have temperature rise of around 5°C
due to left fan failure compared to all fans running condition.
Middle fan failure is having relatively more impact than right fan failure for
all components in BB.
All the components in PB are well below the vendor specified and derated
values with fan failed conditions (left, middle and right fan failure).
56
Even though all components are well within safe limit, due to fan failure there
is relative rise in all component temperatures in PB compared with all fans
running condition.
Heat towers are provided for components of Sl.no.16, 17 and 18 in SB inorder
to reduce the temperature. This will be finalized after thermal Validation test
in proto2.
Thermal simulation can be performed by increasing the vents in the bottom to
enhance the flow of air through bottom vents which will increase convective
heat transfer.
Due to the increase in bottom vent the fan operating point is shifted to
optimum range. This is finalized based on the thermal validation testing
sample.
5.10. BTS THERMAL DESIGN WITH SPEED REDUCTION OF
92MM FAN
To obtain the equivalent thermal results of 3*60mm fan by reducing the speed
of 3*92mm fan
5.10.1. Details of 60mm and 92mm fan
Vendor curve details (60mm fan) Vendor curve details (92mmfan)
Fig.5.51 Vendor specified curve details for 60mm and 92mm fan
57
Figure 5.51 explains the curve details specified from vendor for 60mm and
92mm fan. The curve is given for 100% of maximum speed. The maximum
rotational speed of 60mm fan is 6800 rpm and that of 92mm fan is 5400rpm. The
flow discharge Vs static pressure points for 60mm and 92mm fan at 85% of maximum
speed is considered based on above curves for previous analysis. In present analysis
the above curve points for 92mm fan is used for calculating the flow discharge and
static pressure for lower rotational rpm.
5.10.2. Assumptions for present analysis
System resistance for both cases with 3*60mm fan assembly and 3*92mm fan
assembly are assumed same.
Fan laws are applicable to both 60mm and 92mm diameter fans.
5.10.3. Procedure
As initial step airflow and static pressure points for 60mm fan at 85% of
maximum speed is obtained using fan law. For same condition (85% of max.Speed),
points are obtained for 92mm fan. Based on the air flow rate, as first cut trial, points
are obtained for 70% of maximum speed using fan law. Next, flow points are obtained
for reduced speeds in steps of 10% from previous rotational rpm. (i.e Flow points
obtained for 60%, 50% , 40% and 30% of maximum speed). For 92mm fan the flow
rate at 30% of maximum speed is less than 85% of maximum speed of 60mm fan.
Hence for analysis rotational speed with 40 to 70 % of maximum speed of 92mm fan
is considered. Thermal simulation is carried out for 40, 50, 60 and 70% of maximum
speed for 92mm fan and temperature results are compared with 60mm fan thermal
results which runs at 85% maximum speed . The flow discharge Vs static pressure
58
points for 60mm fan and for 92mm fan with different speeds are tabulated in below
tables. The points are used for obtaining fan curve for different rotational speed.
Table 5.29 Flow discharge Vs Static pressure points for 60mm fan
Table 5.30 Flow discharge Vs Static pressure points for 92mm fan
Tables 5.29 and 5.30 are tabulated with flow discharge and static pressure
points at 85% of maximum speed for 60mm and 92mm fan.
59
Table 5.31 Discharge Vs Static pressure points for 92mm fan at different speeds
Table 5.31 gives the information of discharge Vs static pressure points of 92mm
fan at different speed (i.e 30, 40, 50, 60 and 70% of maximum speed). For obtaining
the curve the units for discharge and static pressure are used as cfm and inches of
water respectively. However, the results are given in SI units in the later section
5.10.5. The above embedded excel sheet gives the information of Tables 5.29, 5.30
and 5.31.
Fig.5.52 Fan curve at different speed
Figure 5.52 shows the Flow Vs static pressure curve for 85% of maximum
speed of 60mm fan and 40 to 70 % maximum speed of 92mm fan. From the graph it
60
can be seen that all fan speeds from 40 to 70% maximum speed of 92mm fan has flow
rate more than 85% maximum speed of 60mm fan.
5.10.4. Temperature Results
Table 5.32 Components temperature comparison in SB for 60 and 92mm fan
Table 5.32 shows the temperature values of components in SB for various speed
of 92mm fan assembly and 85% maximum speed of 60mm fan assembly. In SB 40
and 50% speed of 92mm fan results in more or less same temperature as 85% of
60mm fan.
61
Table 5.33 Components temperature comparison in BB for 60 and 92mm fan
Table 5.33 shows the temperature values of components in BB for various speed
of 92mm fan assembly and 85% maximum speed of 60mm fan assembly. In BB 50%
speed of 92mm fan results in more or less same temperature as 85% of 60mm fan.
62
Table 5.34 Components temperature comparison in PB for 60 and 92mm fan
Table 5.34 shows the temperature values of components in BB for various speed
of 92mm fan assembly and 85% maximum speed of 60mm fan assembly. In BB 50%
speed of 92mm fan results in more or less same temperature as 85% of 60mm fan.
5.10.5. Fan operating point
Left fan Right fan Middle fan
Fig.5.53 Operating curve for 60mm fan at 85% of maximum speed
63
Left fan Right fan Middle fan
Fig.5.54 Operating curve for 92mm fan at 40% of maximum speed
Left fan Right fan Middle fan
Fig.5.55 Operating curve for 92mm fan at 50% of maximum speed
The Figure 5.53 shows the operating point of left, middle and right fan of 60mm
fan assembly. The Figures 5.54 and 5.55 shows the operating point of left, middle
and right fan of 92mm fan assembly with 40 and 50% of maximum speed.
64
Left fan Right fan Middle fan
Fig.5.56 Operating curve for 92mm fan at 60% of maximum speed
Left fan Right fan Middle fan
Fig.5.57 Operating curve for 92mm fan at 70% of maximum speed
The Figures 5.56 and 5.57 shows the operating point of left, middle and right fan of
92mm fan assembly with 60 and 70% of maximum speed.
Table 5.35 Operating point for 60mm fan
Fan Possition Volume Flow (m3/sec)
Static Pressure(Pa)
Left Fan 0.00820 26.70
Middle Fan 0.00810 27.56
Right Fan 0.00810 27.02
65
Table 5.36 Operating point for 92mm fan
The Table 5.35 gives the operating point of 60mm fan operating at 85% of
maximum speed. The operating point is tabulated for left, middle and right fan. Table
5.36 shows the operating point for left, middle and right fan of 92mm fan assembly
with various speeds from 40 to 70% of maximum speed.
5.10.6. Observations
By comparing the temperature of the components in all the boards it is observed that
50% of maximum speed for 92mm fan experiences the thermal distribution in
the BTS unit as same as the 60mm fan with 85% of maximum speed.
However, all speeds more than 50% of maximum speed (i.e 60 and 70% of
maximum speed) are having better thermal margin as compared with 60mm
fan running at 85% of maximum speed.
Fan speed should not be set less than 50% of maximum speed for 92mm fan as
the operating flow will not be adequate for further reduction in fan speed.
Please refer Table 5.35 and Table 5.36. (In 92mm fan 40% of maximum speed
operating flow is less than the 60mm fan running at 85% of maximum speed)
The operating point of 92mm fan for all considered percentage of maximum
speed is not in the optimum operating range.
66
The operating point has to be shifted to optimum range by reducing the system
resistance
5.11. THERMAL VALIDATION OF BTS
Objective of thermal validation is as follows
To measure the case/ambient temperature of selected components located in
PIU board for below mentioned cases
CASE 1: BTS unit with 65°C ambient all fan running condition (60% fan
speed) with 65 mm fan assy.
CASE 2: BTS unit with 65°C ambient all fan running condition (60% fan
speed) with 92 mm fan assy.
To compare the results with computed temperature.
5.11.1. Test Configuration
BTS unit is run at 65°C thermal chamber ambient condition.
Testware (Traffic) for stressing the components for max power dissipation
Measurements carried out at 65°C ambient condition and components
temperature measured during all three fans running.
5.11.2. System Configuration for 92 mm Fan Assy
The system configuration is as following for BTS mechanics
SB (System board) and BB (Base band board) will be placed in upper chassis
of BTS mechanics.
Power board will be placed in lower chassis in BTS mechanics
67
Components which possess heat tower in SB and BB will be attached to upper
chassis heat sink of BTS mechanics.
Components which possess heat tower in PB will be attached to lower chassis
heat sink.
Stressing software (Traffic) will be used to exercise all the components to the
maximum power for measurement.
External air flow in BTS will be with 3*92mm fan assembly (all fans
running).
For easy change of the actual interface according to customer’s need it has
Plug-in unit
On top of the main frame power distribution Unit (PB) is located.
5.11.3. Temperature measurement with 92 mm fan assy
Fig.5.58 TC placements on System board (SB) Components
Figure 5.58 explains the placement of thermocouple on the components considered
for measuring the temperature in System board (SB).
T-Type (36 AWG) thermocouples are used to measure case temperature of the
components.
68
Table 5.37 TC locations in SB/PIU
Table 5.37 shows the temperature measuring place of the components located in
SB/PIU.
Picture below explains the placement of thermocouple on the components
considered for measuring the temperature in Base band board (BB).
Fig.5.59 TC placement on Base band board (BB) components
69
Table 5.38 TC locations in BB
Table 5.38 shows the temperature measuring place of the components located in BB
Figure 5.60 explains the placement of thermocouple on the components considered
for measuring the temperature in Power board (PB).
Fig.5.60 TC placement on Power board (PB) components
70
Table 5.39 TC locations in PB
Table 5.39 shows the temperature measuring place of the components located in PB
TC location 317, 318, and 319 are measured for chassis surface temperature of BB,
air inlet and air exit of unit.
Fig 5.61 TC placement on General PIU
5.11.4. Thermal Validation Test Procedure
Components considered for measurements are cleaned with isoproponal
solution which removes dust and other particles. Thermocouples are attached to the
surface of the components using thermal paste(Loctite 384) and thermal tape.Thermal
71
gel (Putty 304) is used to couple the component surface and heat tower. Checked for
proper fitting and IP protected condition.The data path during the thermal test is
network Processor LLP LIU External loopback. All devices in system,
baseband and power board are powered on and stressed as per the requirement.
Working condition of thermocouple is checked by measuring the ambient temperature
before the system is powered on.
The below given instructions are followed for conducting the test
• The system is stressed using the software tools so that all components are at
required loading condition. In this test the components are stressed partially.
• “Engineering investigation" testing - the system is kept power on for a
minimum of two hour to reach steady state.
• Once the system is stabilized, the temperature measurement is logged for
analysis.
• Measurements are carried out as per the test configuration.
In baseband board traffic path are stressed and all interfaces are initialized. The
power drawn by the unit without applying external load to PB is around 98Watts.
(Voltage of 48V and Current of 2.04 amp).To get the exact temperature inside,
external loads are driven by PB. PB power ports are connected with passive loads.
The power consumption of passive loads are 4 numbers of 48V, 20A and 1 number of
48V, 5 A.The extra power in PB added due to drop by connected passive loads is 17
Watts.The total power supplied to the unit including external loading is around
115Watts.
After the measurements the working condition of the system is ensured through
hardware input
72
5.11.5. Thermal Validation Test Results with 92 mm Fan Assy
The system is tested for the required test cases and data is recorded as per the
requirement.
The component temperatures are checked against the allowable limit to verify
pass/fail criteria. Summary of test results will be represented in table form to ensure
the pass file criteria.
Table 5.40 Validated results for the components in the SB/PIU
The system board components validated temperature and simulated
temperatures are tabulated in Table 5.40.
73
Table 5.41Validated results for the components in the BB
The table 5.41 gives the validated temperature values of the components located
in base band board (BB) and simulated value.
Table 5.42 Validated results for the components in the PB
The table 5.42 is provided with the validated temperature results of the
components located in the power board (PB) and the simulated temperature.
Table 5.43 Chassis Case, Inlet and Exit Air Temperature
74
Sl.No. TC location Temperature (°C)
1 Chassis case (BB side) 70.7
2 Air temperature at the chassis outlet 68.2
3 Inlet air/thermal chamber 65.0
Chassis case temperatures and inlet/outlet air temperature are mentioned in the
Table 5.43. The inlet air temperature/thermal chamber air temperature at steady state
condition and chassis case temperature at BB side are mentioned in the Table 5.43.
The junction temperatures for validated component are obtained from measured
case temperature.
The junction temperature is calculated from measured case temperature using
below relation.
Junction temperature (Tj) = Case Temperature (Tc) + Junction to case resistance
(Rjc) times the power (P)
i. e. Tj = Tc + Rjc *P
Where Tj, Tc are in °C,
Rjc in °C/W and
P in watts.
Components whose Rjc values are not given in data sheet are calculated using
below equation.
Rjc = t / (K*A)
75
Where t is the half thickness of the component (m),
K is thermal conductivity (W/m°K),
A is cross section area (m2)
5.11.6. Thermal Validation Results and Discussions of 92 mm fan assy
All the critical components measured during testing are well below the
allowable vendor data sheet.
In SB, all components are within the limit of NSN derated values except
processor component (MCOMPO NO: 4332632).
In baseband board except L2 switch component (MCOMPO NO: 4331812) all
other components are within derated values.
All components in power board are within limit of derated values.
Difference in temperatures in the components with respect to the simulation
values are due to power dissipation.
The temperature difference between the inlet and exit air temperature is
around 3.2°C and case temperature is around 70.7°C near BB side.