+ All Categories
Home > Documents > Chapter4

Chapter4

Date post: 04-Aug-2015
Category:
Upload: ddhakar9
View: 38 times
Download: 4 times
Share this document with a friend
35
4.1 Chapter 4 Modelling of Exciter, Turbine and System Load 4.1 Exciter Excitation system provides the current required for the field winding of a synchronous generator to produce the rated terminal voltage at the generator terminals. The basic blocks that are involved in the excitation system [1] are shown in Fig. 4.1. Fig. 4.1: Excitation system block diagram Exciter Exciter can be of three types DC exciter, AC exciter and Static exciter. DC exciter: In this type of exciter a separately or self excited DC generator driven by a motor or connected to the same shaft as that of the main generator rotor is used. In case of separately excited DC generator the field winding of the DC generator is energised through a permanent magnet AC generator, the three-phase out of which is converted to DC through rectifiers. Example of DC excitation system is IEEE type Exciter Voltage Regulator Generator Voltage transducers Limiting and protecting circuit Power system stabilizer Rate Feedback Power System
Transcript

4.1

Chapter 4 Modelling of Exciter, Turbine and System Load

4.1 Exciter

Excitation system provides the current required for the field winding of a

synchronous generator to produce the rated terminal voltage at the generator

terminals. The basic blocks that are involved in the excitation system [1] are shown in

Fig. 4.1.

Fig. 4.1: Excitation system block diagram Exciter Exciter can be of three types DC exciter, AC exciter and Static exciter.

DC exciter: In this type of exciter a separately or self excited DC generator driven by

a motor or connected to the same shaft as that of the main generator rotor is used. In

case of separately excited DC generator the field winding of the DC generator is

energised through a permanent magnet AC generator, the three-phase out of which is

converted to DC through rectifiers. Example of DC excitation system is IEEE type

Exciter Voltage Regulator

Generator

Voltage transducers

Limiting and protecting circuit

Power system stabilizer

Rate Feedback

Power System

4.2

DC1A [1], [2]. This type of excitation was widely used up to 1960 but now-a-days

AC excitation or static excitation is being used. For older generating stations where

DC excitation is still used the voltage regulator alone is replaced with electronic

regulators.

AC exciter: In this type of exciter the AC generator whose armature is mounted on the

same shaft as that of the main generator, with its field stationary, is used for supplying

field current to the main generator field winding. The output of AC exciter generator

is converted to DC through rotating rectifiers, as the armature is now rotating at the

main generator rotor speed, and the output is directly connected to the main field

winding. The filed of the AC exciter generator itself is energised through a pilot

permanent magnet AC generator whose three-phase output is converted to DC

through rectification. Example IEEE type AC1A.

Static exciter: In this exciter the output of the main synchronous generator is

converted from AC to DC through static rectification and then the output is supplied

to the main generator field winding through slip rings. Example IEEE type ST1A.

Voltage transducers: Voltage transducers measure the three-phase terminal voltage

through potential transformers and convert them and filter them to DC which is

compared with the reference voltage and the error signal is used to control the main

exciter field winding current through the exciter.

Voltage Regulator: The voltage regulator can be of magnetic amplification type or

digital amplification type. At present digital amplification is widely used. The voltage

regulator amplifies the error signal generated by voltage transducers and the output of

the voltage regulator is used to control the pilot excitation there by controlling the

main generator field winding through the DC/AC excitation system.

Limiting and protection circuit: Limiting and protection circuits are used to limit main

generator field winding current, over excitation, under excitation, terminal voltage,

Volts-per-Hertz etc.

4.3

Rate feedback: Rate feedback is used to stabilize the excitation system and will be

explained shortly

Power system stabilizer: It is used to damp the power system oscillations through the

excitation system. Power system stabilizer will be explained in detail while discussing

small-signal stability.

4.1.1 IEEE Type DC1A

The modelling of IEEE Type DC1A [1], [2] will be discussed here. Though,

only DC excitation modelling is dealt here, the same approach can be extended to

IEEE Type AC1A and ST1A [1]. A separately excited DC generator excitation is

shown in Fig. 4. 2.

Fig. 4.2: Separately excited DC machine circuit

The output of the DC generator, 1oute , can be directly applied to the main

generator field winding and hence 1out fde v . DC generator field is excited through a

pilot generator as explained earlier. If 1ine is the voltage applied to the DC generator

field, with field current 1ini , then the following expression can be written

11 1 1 1

fin in f f

de i r N

dt

(4.1)

1ine

1fr

1fL

1aL ar

1 1 1a aK

1out fde v

1ini

4.4

Where, 1 1,f fr L are the resistance and inductance of the DC generator field

winding. 1fN is the number of turns of the DC generator field winding. If the flux

produced due to field current 1ini is 1f and a fraction of it 1/ links the armature of

the DC generator then the armature flux 1 11/a f . The induced emf in a DC

generator armature is directly proportional to the speed of the armature and the flux

linking it and can be written as

1 1 1a a ae k (4.2)

here, 1a is the speed of the armature and k is a proportionality constant

corresponding to specific machine. The leakage inductance of the DC generator

armature 1aL and resistance 1ar are negligible. Hence, the following expression can be

written

1 1 1 1 1a out fd a ae e v k (4.3)

From equation (4.3) we can express 1f in terms of the DC generator output voltage,

armature speed and proportionality constant as

1 11 1

f a fda

vk

(4.4)

The DC generator field winding flux linkage is given as

11 1 1 1 1

1 1

ff f in f f fd

a

Nl i N v

k

(4.5)

1 11

1 1 1

fd af g

in f

V kl k

i N

(4.6)

Hence, without considering the effect of saturation,

4.5

1fd

ing

Vi

k (4.7)

Fig. 4.3: Excitation saturation characteristics

As can be observed from Fig. 4.3, field current 1fd

ing

vi

k lead to a DC generator

output voltage fdv without saturation. If saturation is considered then an additional

current 1ini is required to produce the same output voltage fdv . Hence

1 1 ( )fd fdin in sat fd fd

g g

v vi i f v v

k k (4.8)

Where, 1( ) insat fd

fd

if v

v

is the function representing the effect of saturation.

Substituting equations (4.4) and (4.8) in (4.1) lead to

1 11 1 ( )f f fd

in fd f sat fd fdg g

r l dve v r f v v

k k dt (4.9)

Since, the DC generator output is directly connected to the generator field

winding the base used for the field circuits to express parameters in per units can be

1ini

1ini

fd

g

v

k

gslope k

fdv

4.6

used here as well. Hence, divide both sides of equation (4.9) by _fd baseV and multiply

by md

fd

X

R (note md

fd fdfd

XE V

R ) and this lead to

( )

11 1 _

_ _

1

1 1

....

fd E fdER

E

E S EKV

f fdmd md mdin fd f sat fd base fd fd

fd base fd g fd base fd md fd

T

f mdfd

g fd

r RX X Xe V r f E V V

R V k R V X R

l XdV

k dt R

(4.10)

( )fdE R E E fd fd

dET V K S E E

dt (4.11)

In equation (4.11) ,E EK T are the gain and time constant of the DC exciter. The

saturation function ( )E fdS E can be mathematically approximated as

( ) fdBE

E fdS E Ae (4.12)

Where, ,A B are constants which can be computed. In the steady state a

maximum scaled DC field winding input voltage maxRV will lead to a maximum scaled

DC generator output armature voltage fdE hence

max max max0 ( )R E E fd fdV K S E E (4.13)

Usually the value of saturation function ( )E fdS E at two different values,

_ max max( )E fdS E and _ 0.75max max(0.75 )E fdS E for two different fdE is specified

max

max

_ max

0.75

0.75 _ max

( )

( )

fd

fd

BE

E fd

B E

E fd

S E Ae

S E Ae

(4.14)

4.7

The constants ,A B can be computed by solving equations (4.13) and (4.14).

The voltage regulator can be simply represented by a first order system with a

gain AK , by which it amplifies the error signal, and a time constant AT . If the input to

the voltage regulator is an error signal inV and the output of the voltage regulator is

the input to the DC generator field winding RV then the dynamic equation of the

voltage regulator can be expressed as

_ min _ maxR

A R A in R R R

dVT V K V V V V

dt (4.15)

So far a separately excited DC generator was considered. A self excited DC

generator can also be modelled in the same way. In case of self excited DC generator

since armatures it self supplies the field current as well assuming there is residual

field voltage to build up the armature voltage gradually. The voltage regulator output

comes in series with the field winding and hence

11 1 1 1

ffd in f f in

dv i r N e

dt

(4.16)

with this modification the dynamic equation of the exciter in per units can be written

as

( )fdE R E E fd fd

dET V K S E E

dt (4.17)

where, 1E EK K , and is a small negative number. From equation (4.17) it can

be observed that since EK is small negative number and with small positive ( )E fdS E

the closed loop transfer function, with input RV and output fdE , has a positive eigen

value making the system unstable. Even without this problem to make the entire open

loop excitation system with the voltage regulator and exciter stable a feedback system

is used to stabilize. A transformer as shown in Fig. 4.4 is used to feeds back the output

4.8

voltage fdE to the input. The transformer secondary side produces a voltage FV

which is then subtracted from the input voltage RV .

Fig. 4.4: Stabilizing transformer circuit

From Fig. 4.4, the following voltage equation can be written

11 1 1

tfd t t t tm

dIE R I L L

dt (4.18)

Where, 1 1, ,t t tmR L L are the resistance, leakage inductance and magnetising

inductance of the primary side of the feedback transformer. 1tI is the primary side

current. If the secondary side the leakage inductance 2tL is very large then the

secondary side current cannot change from its initial conditions and in this case it is

zero then with turns ratio 2 1:N N

12

1

tF tm

dINV L

N dt (4.19)

or

212

21

tFtm

d IdV NL

dt N dt (4.20)

Differentiating equation (4.18) and rearranging we get

FV

2tR

2 1:N N

1tL 1tr

tmL

fdE

2tL 2tI 1tI

4.9

2

1 1 12

2 1

1fdt tF

tm t tm

dEd I R NV

dt L N dt L L

(4.21)

Substituting equation (4.20) in (4.21) we get

1 12

1 2 1

1fdtFtm F

tm t tm

dER NdV NL V

dt N L N dt L L

(4.22)

let,

1 2

1 1 1

,t tm tmF F

t t

L L LNT K

R N R

(4.23)

Then, equation (4.22) can be written as

1( ) fdF F R

F E E fdF F E E

EdV K VV K S E

dt T T T T

(4.24)

Defining,

FF fd F

F

KR E V

T (4.25)

FR is called as the rate feedback. Differentiating equation (4.25) and rearranging we

get

F FF F fd

F

dR KT R E

dt T (4.26)

Finally the IEEE type DC1A exciter dynamics can be expressed by the following

three equations

4.10

( )fdE R E E fd fd

dET V K S E E

dt (4.27)

_ min _ max,R A FA R A F fd A ref t R R R

F

dV K KT V K R E K V V V V V

dt T (4.28)

F FF fd

F

dR KR E

dt T (4.29)

The control block diagram corresponding to the dynamics equations (4.27) to (4.29) is

given in Fig. 4.5.

Fig. 4.5: Control block diagram of IEEE type DC1A exciter

4.2 Model of Turbine

So far the modelling of synchronous machine along with the exciter was

explained. Now, modelling of prime mover will be explained. Prime mover can be a

diesel generator, gas turbine, hydro turbine or steam turbine. Prime mover provides

the mechanical power required as input to the synchronous machine to rotate the rotor

refV

1A

A

K

sT1

EsT

EK

( )E fdS E

1A

A

K

sT

F

F

K

T

FV

fR

tV

inV fdE RV

maxRV

minRV

4.11

of the synchronous machine at synchronous speed. Here, we will discuss about hydro

and steam turbine.

4.2.1 Hydro Turbine

Hydro generating stations consists of a reservoir, gate to release water to

generating station, penstock (a conduit) to carry water from the reservoir up to the

hydro turbine. The turbine can be impulse-type (Pelton wheel) or reaction turbine

(Francis or propeller). The water which flows from the reservoir through the

penstock is directed on to the turbine blades, which are spoon-shaped buckets, and

this force makes the turbine rotate. The hydro turbine and the rotor of the synchronous

machine are mounted on the same shaft.

Hydro turbine modelling

Let H be the height from the gate to the water level in the reservoir also called

as head, U the water velocity and G the gate position (full open means full rated

mechanical power input to the hydro turbine and full close means nil power to the

hydro turbine). The velocity of the water and be expressed as

uU K G H (4.30)

Where uK is a constant of proportionality. If there is a small change in the velocity

of water it can be expressed as a sum of linear changes in the gate position and head

as

U UU H G

H G

(4.31)

The partial derivatives in equations (4.31) should be evaluated at an initial operating

condition from which speed of the water changed by a small amount. The initial speed

of water, for a given initial gate position oG and head oH , is given as

4.12

o u o oU K G H (4.32)

Hence, equation (4.31) can be written as

1

2u o u o

o

U K G H K H GH

(4.33)

Equation (4.33) can be normalized by dividing it with equation (4.32)

2o o o

U H G

U H G

(4.34)

Let / oU U be represented as a normalized value as U . Similarly, H and G

represents the normalized values of small changes in head and gate positions. So,

equation (4.34) can be written as

1

2U H G (4.35)

The turbine mechanical power is proportional to the product of pressure and flow and

hence, with proportionality constant PK

m PP K HU (4.36)

Again a small change in mP can be expressed in a normalized form with the initial

condition mo P o oP K H U , as

1.5mP H U H G (4.37)

From Newton’s second law ( Force=Mass×acceleration ), the acceleration in water

column due to change in water head can be written as

4.13

g

d ULA A a H

dt

(4.38)

Where, , ,L A are the length of the conduit, area of the pipe and the mass

density of the water. ga is the acceleration due to gravity. LA represents the mass of

the water in conduit and ga H represents the incremental force. To normalize

equation (4.38) divide both sides by g o oA a H U . After rearranging the normalized

equation (4.38) is written as

WT

o

g o

LU d UH

a H dt

or W

d UT H

dt

(4.39)

WT has seconds as its units which can be verified from equation (4.39). It is called as

water starting time and it the time required for a head oH to accelerate the water to a

velocity oU . If equation (4.39) is converted in to Laplace domain then

( ) ( )WT s U s H s (4.40)

Substituting, 2H U G , from equation (4.35) in equation (4.39) and

rearranging leads to

1( ) ( )

11

2 W

U s G sT s

(4.41)

From equation (4.35) and (4.37) it can be observed that

3 2mP U G (4.42)

Substituting equation (4.42) in (4.41) and eliminating U lead to

4.14

1( ) ( )

11

2

Wm

W

T sP s G s

T s

(4.43)

Now this model is a linear model and hence is only valid for slow gradual small

changes and not for sudden large changes. Equation (4.43) can be represented in time

domain as

2mW m W

d P d GT P G T

dt dt

(4.44)

The gate position G is the corresponding power output of the turbine that is a per unit

change in gate position leads to per unit change in the mechanical power output mP .

Also, since the model is valid for perturbations around an operating point we can

write the actual parameters as

,

,m mo m

o

P P P

G G G

(4.45)

With the assumption given in (4.45) we can write equation (4.44) as

2mW m W

dP dGT P G T

dt dt

(4.46)

Since the synchronous machine model is represented in per units the turbine model

should also be presented in per units. To do this we can divide both sides of equation

(4.46) by base MVA or the rating of the synchronous machine. Also it can be noted

that in per units power and torque are same hence

2 puMW M pu W

dGdTT T G T

dt dt

(4.47)

4.15

It has to be noted that MT is the per unit mechanical torque output of the hydro

turbine. Equation (4.47) represents the dynamic behaviour of hydro-turbine [3].

4.2.2 Steam Turbine

The steam generating system consists of a boiler to generate steam, steam chest

with a valve to store the steam and release it in to the turbine as shown in Fig. 4.6 [3].

The steam from the steam chest initially enters a high pressure turbine through the

steam valve nozzle at high temperature and pressure with a high velocity and this gets

converted in to rotational kinetic energy through blades connected to the turbine shaft.

Now as in the case of hydro turbine the position of the steam valve is proportional to

the mechanical power output of the turbine. Only part of the input power gets

converted into mechanical power at the high pressure turbine shaft and the steam then

enters reheater were the temperature and pressure of the steam are increased and then

again this reheated steam is forced in to a low pressure or a series of intermediate and

low pressure turbines. Each of these turbines convert the steam into rotational energy

through their blades connected on the shaft. The connection can be tandem connected

that is all the high pressure, intermediate pressure, low pressure turbine and the

generator are on the same shaft as is shown in Fig. 4.6 or cross connected that is there

may be two shafts cross connected with same steam input valve and two generators

connected to each shaft respectively.

Fig. 4.6: Steam generation system schematic diagram

The steam chest with a valve and the high pressure turbine can be modelled as a

linear first order system. Let SVP be the change in the steam valve position and

CHP is the change in the output power of the steam chest which gets converted in to

4.16

the mechanical power at the turbine shaft. If CHT is the time delay of the steam chest

then we can represent the dynamics of the steam chest along with steam valve as

CHCH CH SV

d PT P P

dt

(4.48)

A fraction of the power output of the steam chest, HP CHK P , gets converted in to

mechanical power at the high pressure turbine shaft and the remaining power that is

1 HP CHK P enters the reheat chamber. The reheat chamber itself has a time delay

RHT . After the time delay the steam output from the rehear chamber is forced into the

low pressure turbine (or a series of intermediate turbines followed by a low pressure

turbine. But here only low pressure turbine is taken and the explanation can extended

to any number of turbines in tandem or cross connected) where it gets converted into

incremental mechanical power RHP . The reheat chamber can also be represented as

a linear first order system as

1RHRH RH HP CH

d PT P K P

dt

(4.49)

The total shaft mechanical power or torque (as torque and power in per units on the

generator MVA basis are same) is the summation of high pressure and low pressure

turbine mechanical power and can be written as

M RH HP CHT P K P (4.50)

Substituting equation (4.50) in (4.49) by eliminating RHP we can represent the

dynamics of steam turbine system as

1M HP RH HP RHRH M CH SV

CH CH

d T K T K TT T P P

dt T T

(4.51)

4.17

CHCH CH SV

d PT P P

dt

(4.52)

In case reheater dynamics are not considered then RHT is zero and the dynamic

equations can be written as

MCH M SV

d TT T P

dt

(4.53)

Where, M CHT P . Equations (4.51) and (4.52) can be converted to equations (4.54)

and (4.55); by defining actual variables as

0 0 0, ,M M M CH CH CH SV SV SVT T T P P P P P P , where 0 0 0, ,M CH SVT P P are the

initial operating conditions,

1M HP RH HP RHRH M CH SV

CH CH

dT K T K TT T P P

dt T T

(4.54)

CHCH CH SV

dPT P P

dt (4.55)

4.2.3 Turbine governor

The gate position G or the steam valve position SVP can be automatically

controlled to change the power input according to the output power required through

governor mechanism. The speed governor mechanism [4] is shown in Fig. 4.7. The

speed governor mechanism consists of a fly ball mechanism which detects the change

in the shaft speed above the reference speed. Levers with connecting rods and a main

piston operated through high pressure oil to either open or close the value or gate. If

the speed of the shaft increases above the reference speed the centrifugal force on the

fly balls will increase and they move away from each other there by moving the point

b downwards and this lead to lowering of point c and hence point d. As point d move

down wards the high pressure oil enters the main piston chamber through the lower

opening and hence pushes the point e and piston upwards and there by reducing the

steam input. Increases in shaft speed above the reference speed indicates that the input

power is more than the output power required and hence speed increasing and to bring

back to the reference speed the input mechanical power should be reduced i.e. the gate

4.18

or valve should position should change to reduced the input power and this is what

happen in the governor mechanism.

Fig. 4.7: Speed governor mechanism

Similarly if speed is decreasing then more input power is required and it can be

observed that with decrease in speed the fly balls will move towards each other and

the point c moves upwards and leads to movement of point d upwards now the high

pressure oil will enter the main piston chamber through upper opening and there by

forcing the piston downwards and opening the valve. The actual mechanical power

input reference can also be changed at reference speed by changing the set point

through speed changer i.e. moving point a downwards or upwards and thereby

decreasing or increasing the power input.

The governor can be mathematically modelled by assuming that the change in

the positions of the points a, b, c, d and e can be related to each other linearly

depending on the length of the rods separating them. If the point b moves a distance

by then it is related to the change in point a ( ay ) and c ( cy ), as it is directly

connected to them, as

b ba a bc cy K y K y (4.56)

4.19

where, ,ba bcK K are constants. Similarly we can write

d dc c de ey K y K y (4.57)

The point a is related to the change in the reference power and if the reference power

is refP then

ref a aP K y (4.58)

The point b changes according to the change in the speed of the shaft and is

proportional to it and hence

base b bK y (4.59)

Point d effects point e through the high pressure oil servo mechanism. The point e

moves according to the rate of change of oil flow in the main piston chamber and the

flow in turn is effected by point e. Also it can be noted that point d and e move in

opposite directions and hence the following expression can be written

ee d

d yK y

dt

(4.60)

Substituting, equation (4.57) in (4.60) lead to

ee d dc e c e de e

d yK y K K y K K y

dt

(4.61)

From equation (4.56), cy can be expressed in terms of ,a by y and this can be

substituted in equation (4.61) which lead to

4.20

e b ba adc e e de e

bc

dc e dc e bab a e de e

bc bc

d y y K yK K K K y

dt K

K K K K Ky y K K y

K K

(4.62)

,a by y can be represented in terms of ,refP from equations (4.58) and (4.59)

this when substituted in (4.62) lead to

e dc e dc e baref e de e

base b bc bc a

d y K K K K KP K K y

dt K K K K

or

1/

1SVDSV PRT

bc a de e a bc a deref e

e de dc ba b ba base dc ba

K K K d y K K K KP y

K K K K dt K K K K

(4.63)

1SVSV SV ref

D base

d PT P P

dt R

(4.64)

If we define the variables as 0 0, ,SV SV SV ref ref ref baseP P P P P P then

we can express equation (4.64) as, with limits on the valve position included,

11 , 0 MaxSV

SV SV ref SV SVD s

dPT P P P P

dt R

(4.65)

DR is the speed regulation and it depends on the droop, the amount by which the

frequency falls from no load to full load without change in the input power. DR can

be defined in terms of droop as

2D

base

droopR

(4.66)

4.21

Where, droop has units of Hz/per megawatts. If droop is defined in terms of

percentage i.e. the percentage by which the frequency falls from no load to full load

then

%

100D

droopR (4.67)

So far we have discussed about the modelling of the synchronous generator along

with exciter, hydro/steam turbine and turbine governor. Next we will discuss about

modelling of loads.

4.3 Load Representation

The loads can be represented as either static or dynamic loads. Lighting and

heating loads can be represented by static models. Whereas, to represent motor loads

like synchronous motors and induction motors the motor dynamics have to be taken

into consideration.

4.3.1 Static load representation

Static load representation is a simple way of representing the effect of load on

the system stability. The effect of change in voltage and system frequency can be

incorporated in the static load model. Usually instead of representing each static load

separately an aggregate load is represented like all loads at particular distribution

station can be clubbed together and represented as a single load. The typical way of

representing static loads is either as a constant impedance load or constant current

load or constant power load. If , ,o o oP Q V are the initial real power, reactive power

and voltage then the effect of change in the voltage on the static load can be

represented as [5]

np

oo

VP P

V

(4.68)

4.22

nq

oo

VQ Q

V

(4.69)

Where, ,P Q are the real and reactive powers at changed voltage V . In case

equation (4.68) and (4.69) are representing single loads then ,np nq when taken as 0

represents constant power load, taken as 1 represents constant current and taken as 2

represents constant impedance loads. For aggregate loads ,np nq may be chosen to

approximate the actual behaviour of the load and may be in the range of 0.5 to 1.8 for

np and in the range of 1.5 to 6 for nq . A polynomial mode of load representation [5]

can also be used which includes all the types i.e. constant impedance (Z), current (I)

and power (P) called as ZIP load as shown in equation (4.70) and (4.71)

2

o Z I Po o

V VP P P P P

V V

(4.70)

2

o Z I Po o

V VQ Q Q Q Q

V V

(4.71)

Where, , , , ,,Z I P Z I PP Q are constants representing the approximated fraction of the

aggregated load taken as constant impedance, current and power loads. Though

constant impedance are practical loads like lighting and heating, constant current and

power loads are not real loads but are used to represent dynamic loads like motors as

static loads assuming that after a disturbance the motor loads will reach their steady

state rapidly. Hence it is necessary to take the effect of frequency variation also on the

loads to improve the accuracy and can be represented as

2

1o Z I P Pfo o

V VP P P P P K f

V V

(4.72)

2

1o Z I P qfo o

V VQ Q Q Q Q K f

V V

(4.73)

4.23

In equations (4.72) and (4.73), the effect of change in the bus frequency from

the steady state frequency, 0f f f , is included in the static load model with

constant pfK taking a value between 0 to 3.0 and qfK a value between -2 to 0 [6].

The bus frequency information is not available but can be obtained by the rate of

change of the bus angle which can be computed. For a very wide variation in voltage

the aggregate static load is converted into constant impedance load for computational

simplicity. In fact constant impedance load representation has several computational

benefits which will be discussed later. Though IP part of ZIP load represents the static

model of motor loads this representation is not accurate and can lead to erroneous

conclusions. Hence, for large motor loads it is better to take the dynamics of the

motors into consideration for stability studies. In this context we will discuss the

modelling of synchronous motor and induction motor.

4.3.2 Model of synchronous motor

The dynamic equations (3.149)-(3.157) and (3.162) given in Chapter 3

representing the synchronous generator can also be used for representing the

synchronous motor as well with a modification in equation (3.162) given in Chapter 3

as shown in equation (4.74)

2e base m

base

H dT D T

dt

(4.74)

This change is required because in a motor electrical energy is converted to

mechanical energy and hence electrical torque is the input whereas mechanical torque

is the output. The converse is true of a synchronous generator. It has to be also noted

that in case of a synchronous motor current into the stator should be taken as positive

unlike the case of synchronous generator. The IEEE type DC1A exciter model can

also be used for the synchronous motor.

4.24

4.3.4 Model of induction motor

The stator of the induction machine is similar to a synchronous machine with a

three-phase winding distributed symmetrically with 120 separation. The rotor of an

induction machine also has three phase windings distributed symmetrically with 120

separation with same number of poles as that of stator (a set of three phase windings

distributed symmetrically with 120 separation produces a pair of poles in the air gap

rotating at synchronous speed). The three-phase rotor windings terminals are brought

out to be connected to external resistance in case of a wound rotor induction machine

and short circuited in case of a squirrel cage induction machine. For modelling

purpose both can be considered same with some assumptions. Some points to be

noted which can help us in modelling induction machine are [7]

The 0dq transformation used for modelling synchronous machine can also be

used for modelling induction machine as well.

The rotor is cylindrical and hence has a uniform air-gap due to which there

will be no difference between d -axis or q -axis inductances and time

constants.

In case of synchronous machine the d -axis was aligned with the rotor of the

machine as it rotates at synchronous speed in steady state for varying loads. In

case of induction machine the rotor speed is not synchronous speed and its

speed depends on the load torque required. Even though the rotor of induction

machine rotates at slip speed the rotor winding produces a synchronously

rotating field with the same number of poles as that of the stator winding field.

Hence, a synchronously rotating dq -axis can be taken which is neither fixed

to rotor or fixed to stator and the three-phase rotor and stator quantities can be

referred to this axis.

The current in the rotor of an induction machine does not depend on the

excitation system like in the case of synchronous machine but instead depends

on the relative speed between the synchronously rotating stator field and the

rotor speed that is the slip speed.

4.25

The same model can be used for induction motor and generator and the main

difference lies in the slip.

With these assumptions let us look in to the modelling of an induction machine.

The basic diagram of induction machine with all the relevant windings represented is

shown in Fig. 4.8. The stator three-phase voltages and currents are represented by

, ,a b cv v v and , ,a b ci i i . Similarly, rotor three-phase voltage and currents are represented

by , ,A B Cv v v and , ,A B Ci i i . The rotor along with its windings will rotate at a speed r .

Let the angle with which the field axis of rotor A-phase leads the field axis of stator a-

phase be then with continuous time we can write

Fig. 4.8: Induction machine with all the windings represented

rt (4.75)

The slip is defined as the ratio of the difference between the synchronous speed and

the rotor speed to the synchronous speed. Hence, slip can be expressed as

s r

s

s

(4.76)

bvav

cv

Av

Cv

Bv

Ai

Bi

Ci

bi

ai

ci

d axis

rr

s

4.26

From equation (4.76), the angle in equation (4.75) can be represented in terms of

slip and synchronous speed as

1r st s t (4.77)

If now we consider dq -axis rotating in the air-gap at synchronous speed and is

separated by an angle r with the field axis of rotor A-phase. Then the following

expression can be written

r s st s t (4.78)

rs

ds

dt

(4.79)

In the same way we have written voltage equations for synchronous machine stator

windings we can also write voltage equations for the windings shown in Fig. 4.8 as

0 0

0 0

0 0

a s a a

b s b b

c s c c

v r id

v r idt

v r i

(4.80)

0 0

0 0

0 0

A r A A

A r B B

C r C C

v r id

v r idt

v r i

(4.81)

Where, ,s rr r are the stator and rotor winding resistances. , , , ,,a b c A B C are the

flux linkage of the three-phase stator and rotor windings, respectively. Let the self

inductance of the stator a-phase winding be aal and this can be assumed to the same

for all the three-phases. The mutual inductance between any two phases, let it be abl ,

of the stator will be same and independent of the rotor position as the air-gap is

uniform. Let the maximum value of the mutual inductance between any rotor and

4.27

stator winding be aAl then the flux linkage equation of stator and rotor can be written

as

cos cos 120 cos 120

cos 120 cos cos 120

cos 120 cos 120 cos cos

aA aA aAa aa ab ab a A

b ab aas ab b aA aA aA B

Cc ab ab aa c aA aA aA

l l ll l l i i

l l l i l l l i

il l l i l l l

(4.82)

cos cos 120 cos 120

cos 120 cos cos 120

cos 120 cos 120 cos cos

aA aA aA a AA AB AbA A

B aA aA aA b AB AA AB B

C AB AB AA CcaA aA aA

l l l i l l l i

l l l i l l l i

l l l iil l l

(4.83)

The Park’s transformation used in synchronous machine modelling can also be used

here but a separate transformation has to be used for stator and rotor windings. Let

rotor Park’s transformation be 0r

dqT and that of stator be 0s

dqT and can be expressed as

0

cos( ) cos( 120) cos( 120)2

sin( ) sin( 120) sin( 120)3

1 1 1

2 2 2

s s s

sdq s s s

t t t

T t t t

(4.84)

0

cos cos 120 cos 1202

sin sin 120 sin 1203

1 1 1

2 2 2

s r s r s r

rdq s r s r s r

t t t

T t t t

(4.85)

Applying transformation given in (4.84) and (4.85) to flux linkage equations (4.82)

and (4.83) and also assuming that ss aa abl l l , rr AA ABl l l and 3

2m aAl l we get

flux linkage equations in 0dq reference frame as

4.28

0 0 0

0 0 0 0

0 0 0 0

0 0 0 0 0 0

ds ss ds m dr

qs ss qs m qr

s s r

l i l i

l i l i

i i

(4.86)

0 0 0

0 0 0 0

0 0 0 0

0 0 00 0 0

dr m ds drrr

qr m qs rr qr

r s r

l i il

l i l i

i i

(4.87)

Similarly, applying transformations to voltage equations given in (4.80) and (4.81)

leads to

0 0 0 0

0 0 0 0

0 0 0 0

0 0 0 0 0

ds s ds s ds ds

qs s qs s qs qs

ss s s s

v r id

v r idt

rv i

(4.88)

0 0 0 0

0 00 0

0 0 0 0

0 0 0 0 0

s rdr dr dr drr

qr r qr s r qr qr

rr r r r

v ird

v r idt

rv i

(4.89)

The rotor power input can be expressed in dq -axis by using equation (4.89) as

1

0 0

0 0

2 23 3

2 2

TT

dr drA A Tr r

rotor B B qr dq dq qr

C C r r

qrdrr dr qr dr qr qr dr s r dr qr

v iv i

S v i v T T i

v i v i

ddr i i i i i i

dt dt

(4.90)

In the steady state , qrdrdd

dt dt

are zero, then from equation (4.90) it can

observed that there are two parts of which the first part corresponds to the rotor

copper losses and the second part corresponds to the product of torque produced and

the difference of the rotor speed with respect to the synchronous speed. If the torque is

defined at the relative speed of the rotor speed with respect to the speed of dq -axis,

4.29

r s , then from equation (4.90) the torque can be expressed for a P number of

poles as

3

2 2e qr dr dr qr

Pt i i (4.91)

Per unit representation

The same base quantities can be taken for both stator and rotor.

Let,

baseV = peak value of rated phase voltage, V

baseI = peak value of rated current, A

basef = rated frequency, Hz

basebase

base

VZ

I , 2 elec.rad/sbase s basef , Hbase

basebase

ZL

, base

basebase

V

,

3

2base base bases V I , 3

N.m2 2base base base

PT I

With the base voltage and current defined as above and given the transformations in

(4.85) and (4.86) it can be observed that a per unit phase voltage and current in abc-

reference frame leads to per unit voltage and current in 0dq -reference frame as well

hence same base quantities can be used in both and 0abc dq -reference frames.

, , ,

, , , ,

, , , ,

, ,

qs qrds drds qs dr qr

base base base base

qs qrds drds qs dr qr

base base base base

qs qrds drds qs dr qs

base base base base

base ss base rr base ms r m

base base

v vv vV V V V

V V I I

i ii iI I I I

I I I I

l l lX X X

Z Z Z

_

, ,

, 1

ss

base base

er rr e r pu

base base base

rR

Z

trR T s

Z T

(4.92)

4.30

Then equations (4.86) to (4.89) can be written in per units as

1 dsds s ds qs

base

dV R I

dt

(4.93)

1 qsqs s qs ds

base

dV R I

dt

(4.94)

1 drdr r dr qr

base

dV R I s

dt

(4.95)

1 qrqr r qr dr

base

dV R I s

dt

(4.96)

ds s ds m drX I X I (4.97)

qs s qs m qrX I X I (4.98)

dr m ds r drX I X I (4.99)

qr m qs r qrX I X I (4.100)

The stator transients of the induction machine can be neglected as was done for the

synchronous machine stator transients. Hence, equations (4.93) and (4.94) are

simplified to

ds s ds qsV R I (4.101)

qs s qs dsV R I (4.102)

Eliminating ,dr qrI I from equations (4.99) and (4.100), substituting them in (4.97) and

(4.98) and in turn substituting them in equations (4.95) and (4.96), noting that for a

squirrel cage rotor 0dr qrV V , leads to

'

' ' ' ' '0 0

dd s s qs base q

dVT V X X I sT V

dt (4.103)

'

' ' ' ' '0 0

qq s s ds base d

dVT V X X I sT V

dt (4.104)

4.31

Where,

2' ' ' ', , ,m m m r

d qr q dr s s or r r base r

X X X XV V X X T

X X X R

The per unit torque is give as

32 2

32 2

qr dr dr qre

e qr dr dr qrbase

base sbase

Pi it

T I IPT I

(4.105)

The equation of motion of the induction machine is given as

me m

dJ t t

dt

(4.106)

Where, m is the speed of the rotor in mechanical radians per second. Dividing both

side by 2

base base baseS TP

we get

2m

base e mbase

base base base base

J t td PS dt T T

(4.107)

let,

212 base

base

JH

S

and also noting that

2r mP

we get

_2 2r pue m

d dsH H T T

dt dt

(4.108)

Algebraic equations relating the stator voltage dsV , qsV to the dynamic state 'dV , '

qV can

be obtained by eliminating ,dr qrI I from equations (4.99) and (4.100), substituting

4.32

them in (4.97) and (4.98) and in turn substituting them in equations (4.101) and

(4.102) leads to

' 'ds s ds s qs dV R I X I V (4.109)

' 'qs s qs s ds qV R I X I V (4.110)

If the three-phase stator voltage are given as

2 cos

2 cos 120

2 cos 120

a t s

b t s

c t s

v V t

v V t

v V t

(4.111)

Where, tV is the rms phase voltage. Applying parks transformation defined in

equation (4.84) to equation (4.111) and dividing both sides by base voltage lead to

_

__

cos, where,

sin

t puds tt pu

qs t pu sbase

VV VV

V V V

(4.112)

Hence, the dq components of the voltages can be used to represent a phasor with real

and imaginary parts in per units as

_ _cos sin jds qs t pu t puV jV V j V e (4.113)

With the same argument the stator currents in dq -axis can be represented in per units

as

_ _cos sin jds qs t pu t puI jI I j I e (4.114)

4.33

Where, _t puI is the stator current in per units with a phase angle . Since stator

voltage in dq -axis can be expressed as phasors we can add equations (4.109) and

(4.110) by multiplying equation (4.110) with complex number 1j , then we get

' ' '_

jt pu ds qs s s ds qs d qV e V jV R jX I jI V jV (4.115)

Hence, a simple electrical equivalent circuit can be formed for the induction machine

with an internal transient voltage behind the transient reactance 'sX as shown in Fig.

4. 9.

Fig. 4.9: Electrical equivalent circuit of an induction motor

Hence, the complete induction machine dynamic model in per units is defined by

1 base rr

base base

ds

dt

(4.116)

2 e m

dsH T T

dt (4.117)

'

' ' ' ' '0 0

dd s s qs base q

dVT V X X I sT V

dt (4.118)

'

' ' ' ' '0 0

qq s s ds base d

dVT V X X I sT V

dt (4.119)

' 'e qr dr dr qr d ds q qsT I I V I V I (4.120)

' ' '_

jt pu ds qs s s ds qs d qV e V jV R jX I jI V jV (4.121)

_j

d q t puI jI I e 'dX sR

d qV jV _j

ds qs t puV jV V e

4.34

Initial Conditions

To find the initial conditions of a induction motor, the dynamics given by equations

(4.118) and (4.119) can be equated to zero, which lead to

' ' ' '0 0d s s qs base qV X X I sT V (4.122)

' ' ' '0 0q s s ds base dV X X I sT V (4.123)

Now multiply equation (4.123) by complex number 1j on both sides and add this to

equation (4.122).

' ' ' ' ' '0 0d q s s ds qs base d qV jV j X X I jI j sT V jV (4.124)

Now, ' 'd qV V jV , _

jt pu ds qsI e I jI and _

jt pu d qV e V jV , then equation

(4.124) leads to

' ' '

'_ 01

d q s s

jt pu ds qs base

V jV X XVj

I e I jI j sT

(4.125)

Substituting equation (4.125) in equation (4.115) lead to

'

'_ _'

01

s sj jt pu s s t pu

base

X XV e R jX j I e

j sT

(4.126)

Equation (4.126) can be further simplified and expressed as

'0

_ _' ' '0 0

1 basej jt pu t pu

s base s base s s

j sTI e V e

R sT X j sT R X

(4.127)

The real power input to the induction machine is given as

4.35

*

_ _

' ' ' '0 0 0 2

_2 2' ' '0 0

Real j jt t pu t pu

s base s base base s s

t pu

s base s base s s

P V e I e

R sT X sT sT R XV

R sT X sT R X

(4.128)

If from load flow analysis the _, ,t t t puP Q V are defined then from equation

(4.128) the slip can be found out. Equation (4.128) lead to a quadratic expression of

slip and hence there will be two solutions of which the feasible solution should be

considered if it exists for the given conditions. The other way is if we define a slip

with terminal voltage given then real power can be computed from (4.128) and

similarly reactive power can also be computed.

References

1. IEEE Standards 421.4, IEEE Recommended Practice for excitation system

models for power system stability studies, 1992.

2. IEEE Committee report, “Excitation system models for power system stability

studies,” IEEE Trans. Power Appar. Syst., PAS-100, pp. 494-509, February

1981.

3. IEEE Committee Report, “Dynamic models for steam and hydro turbines in

power system studies,” IEEE Trans., Vol. PAS-92, pp. 1904-1915, December

1973.

4. O. I. Elgerd, Electric Energy System Theory, an Introduction, McGraw-Hill

Book Co., New York, 1982.

5. IEEE Task Force Report, “Load representation for dynamic performance

analysis,” IEEE PES winter meeting, New York, January 26-30, 1992.

6. C. Concordia and S. Ihara, “Load representation in power system stability

studies,” IEEE Trans., Vol. PAS-101, pp. 969-977, April 1982.

7. D. S. Brereton, D. G. Lewis and C. C. Young, “Representation of induction

motor loads during power system stability studies,” AIEE Tans., Vol. 76, Part

III, pp. 451-460, August 1957.


Recommended