EUWA*5-24KZW1 R-407C ESIE-0302 EUWAC5-10FZW1 EUWY*5-24KZW1 Service Manual Small air-cooled water chillers
Transcript
Page 1: Chilere Daikin

EUWA*5-24KZW1R-407C

ESIE-0302

EUWAC5-10FZW1

EUWY*5-24KZW1

Service Manual

Small air-cooled water chillers

Page 2: Chilere Daikin

ESIE-0302

Table of Contents i

3

4

5

1Table of Contents

1 Introduction

1.1 About This Manual .................................................................................. i–vii

Part 1System Outline

1 General Outline

1.1 What Is in This Chapter? ........................................................................ 1–31.2 Technical Specifications: EUWAC5-10FZW1 ......................................... 1–51.3 Technical Specifications: EUWA*5-8KZW1 ............................................ 1–81.4 Technical Specifications: EUWA*10-12KZW1 ........................................ 1–111.5 Technical Specifications: EUWA*16-20KZW1 ........................................ 1–141.6 Technical Specifications: EUWA*24KZW1 ............................................. 1–171.7 Technical Specifications: EUWY5-8KZW1 ............................................. 1–201.8 Technical Specifications: EUWY*10-12KZW1 ........................................ 1–231.9 Technical Specifications: EUWY*16-20KZW1 ........................................ 1–261.10 Technical Specifications: EUWY*24KZW1 ............................................. 1–291.11 Correction factors for glycol .................................................................... 1–321.12 Electrical Specifications: EUWAC5-10FZW1.......................................... 1–341.13 Electrical Specifications: EUWA*5-8KZW1............................................. 1–361.14 Electrical Specifications: EUWA*10-12KZW1......................................... 1–381.15 Electrical Specifications: EUWA*16-20KZW1......................................... 1–401.16 Electrical Specifications: EUWA*24KZW1 .............................................. 1–421.17 Electrical Specifications: EUWY*5-8KZW1............................................. 1–441.18 Electrical Specifications: EUWY*10-12KZW1......................................... 1–461.19 Electrical Specifications: EUWY*16-20KZW1......................................... 1–481.20 Electrical Specifications: EUWY*24KZW1 .............................................. 1–501.21 Outlook Drawing: EUWAC5FZW1 .......................................................... 1–521.22 Outlook Drawing: EUWAC8-10FZW1 ..................................................... 1–531.23 Outlook Drawing: EUWAN5-8KZW1....................................................... 1–541.24 Outlook Drawing: EUWAP5-8KZW1 ....................................................... 1–551.25 Outlook Drawing: EUWAB5-8KZW1 ....................................................... 1–561.26 Outlook Drawing: EUWAN10-12KZW1................................................... 1–571.27 Outlook Drawing: EUWAP10-12KZW1 ................................................... 1–581.28 Outlook Drawing: EUWAB10-12KZW1 ................................................... 1–591.29 Outlook Drawing: EUWAN16KZW1 ........................................................ 1–601.30 Outlook Drawing: EUWAP16KZW1 ........................................................ 1–611.31 Outlook Drawing: EUWAB16KZW1 ........................................................ 1–621.32 Outlook Drawing: EUWAN20-24KZW1................................................... 1–631.33 Outlook Drawing: EUWAP20-24KZW1 ................................................... 1–641.34 Outlook Drawing: EUWAB20-24KZW1 ................................................... 1–651.35 Outlook Drawing: EUWYN5-8KZW1....................................................... 1–661.36 Outlook Drawing: EUWYP5-8KZW1 ....................................................... 1–671.37 Outlook Drawing: EUWYB5-8KZW1 ....................................................... 1–681.38 Outlook Drawing: EUWYN10-12KZW1................................................... 1–691.39 Outlook Drawing: EUWYP10-12KZW1 ................................................... 1–701.40 Outlook Drawing: EUWYB10-12KZW1 ................................................... 1–711.41 Outlook Drawing: EUWYN16KZW1 ........................................................ 1–721.42 Outlook Drawing: EUWYP16KZW1 ........................................................ 1–73

Page 3: Chilere Daikin

ESIE-0302

ii Table of Contents

3

1

4

5

1.43 Outlook Drawing: EUWYB16KZW1 ......................................................... 1–741.44 Outlook Drawing: EUWYN20-24KZW1.................................................... 1–751.45 Outlook Drawing: EUWYP20-24KZW1.................................................... 1–761.46 Outlook Drawing: EUWYB20-24KZW1.................................................... 1–77

2 Piping Layout

2.1 What Is in This Chapter? ......................................................................... 1–792.2 Installation outline .................................................................................... 1–802.3 Functional Diagram Refrigeration Circuit: EUWAC5-10FZW1................. 1–812.4 Functional Diagram Refrigeration Circuit: EUWA*5-24KZW1.................. 1–832.5 Functional Diagram Refrigeration Circuit: EUWY*5-24KZW1.................. 1–86

3 Wiring Layout

3.1 What Is in This Chapter? ......................................................................... 1–893.2 Main Functions of the EUWAC5-10FZW1 ............................................... 1–903.3 Main Functions of the EUWA*5-24KZW1 and EUWY*5-24KZW1........... 1–923.4 Switch Box Layout: EUWAC5-10FZW1................................................... 1–933.5 Switch Box Layout: EUWA*5-24KZW1 and EUWY*5-24KZW1............... 1–953.6 PCB Layout of the EUWA*5-24KZW1 and EUWY*5-24KZW1................ 1–973.7 Wiring Diagram: EUWAC5-10FZW1........................................................ 1–1013.8 Wiring Diagram: EUWA*5-24KZW1 and EUWY*5-24KZW1 ................... 1–102

Part 2Functional Description

1 Functional Description

1.1 What Is in This Chapter? ......................................................................... 2–31.2 Operational Range: EUWAC5-10FZW1 .................................................. 2–41.3 Operational Range: EUWA*5-24KZW1 ................................................... 2–51.4 Operational Range: EUWY*5-24KZW1 ................................................... 2–61.5 Operational Flow Chart ............................................................................ 2–81.6 Compressor Working Status.................................................................... 2–91.7 Compressor Timers ................................................................................. 2–101.8 Thermostat Control: EUWAC5-10FZW1.................................................. 2–111.9 Thermostat Control: EUWA*5-24KZW1 and EUWY*5-24KZW1 ............. 2–121.10 Head Pressure Control: EUWAC5-10FZW1............................................ 2–131.11 Head Pressure Control: EUWA*5-24KZW1 and EUWY*5-24KZW1........ 2–151.12 Fan Working: EUWAC5-10FZW1 ............................................................ 2–171.13 Fan Working: EUWA*5-24KZW1 and EUWY*5-24KZW1........................ 2–181.14 Crankcase Heater .................................................................................... 2–191.15 Evaporator Heater Tape Management: EUWA*5-24KZW1 and

EUWY*5-24KZW1 ................................................................................... 2–201.16 Pump Steering ......................................................................................... 2–211.17 Freeze-up Control: EUWAC5-10FZW1.................................................... 2–221.18 Freeze-up Control: EUWA*5-24KZW1 and EUWY*5-24KZW1 ............... 2–231.19 Defrost Management for EUWY*5-24KZW1............................................ 2–24

Page 4: Chilere Daikin

ESIE-0302

Table of Contents iii

3

4

5

12 The Digital Controller

2.1 What Is in This Chapter? ........................................................................ 2–312.2 The Digital Controller .............................................................................. 2–322.3 Start/Stop ................................................................................................ 2–342.4 What Happens in Case of an Alarm or a Warning .................................. 2–362.5 Settings: Direct and User Parameters .................................................... 2–372.6 Reading or Adjusting Parameter Settings: the Programming Procedure 2–39

Part 3Troubleshooting

1 Inputs and Outputs Overview

1.1 What Is in This Chapter? ........................................................................ 3–31.2 Inputs and Outputs Overview: EUWAC5-10FZW1 ................................. 3–41.3 Inputs and Outputs Overview: EUWA*5-24KZW1 and

EUWY*5-24KZW1................................................................................... 3–51.4 Inputs/outputs overview of the I/O PCB: EUWA*5-24KZW1 and

EUWY*5-24KZW1................................................................................... 3–6

2 Malfunction Indications and Safeties Overview

2.1 What Is in This Chapter? ........................................................................ 3–92.2 Malfunction Indications Overview: EUWAC5-10FZW1 ........................... 3–102.3 Malfunction Indications Overview: EUWA*5-24KZW1 and

EUWY*5-24KZW1................................................................................... 3–122.4 Safeties Overview: EUWAC5-10FZW1................................................... 3–142.5 Safeties Overview: EUWA*5-24KZW1 and EUWY*5-24KZW1 .............. 3–15

3 Checking the Inputs and Outputs

3.1 What Is in This Chapter? ........................................................................ 3–173.2 Checking the Temperature Sensors ....................................................... 3–183.3 Controller Sensors: R3T and R4T for EUWAC*5-10FZW1..................... 3–193.4 I/O PCB sensors: R3T and R4T for EUWA*5-24KZW1 and

EUWY*5-24KZW1................................................................................... 3–203.5 I/O PCB sensors: R6T, R7T and R8T for EUWA*5-24KZW1 and

EUWY*5-24KZW1................................................................................... 3–213.6 Checking the Digital Inputs and Outputs................................................. 3–223.7 Checking the Power Supply and Fuses: EUWAC5-10FZW1.................. 3–233.8 Checking the Power Supply and Fuses: EUWA*5-24KZW1 and

EUWY*5-24KZW1................................................................................... 3–243.9 Electrical Error Overview: EUWA*5-24KZW1 and EUWY*5-24KZW1.... 3–25

Page 5: Chilere Daikin

ESIE-0302

iv Table of Contents

3

1

4

5

4 Troubleshooting

4.1 What Is in This Chapter? ......................................................................... 3–294.2 Items to Be Checked ............................................................................... 3–304.3 General Repair Procedures ..................................................................... 3–324.4 Unlocking the Keyboard........................................................................... 3–334.5 Replacing the Controller: EUWAC5-10FZW1.......................................... 3–344.6 Replacing the Controller: EUWA*5-24KZW1........................................... 3–394.7 Replacing the Controller: EUWY*5-24KZW1........................................... 3–444.8 Replacing the PCB: EUWA*5-24KZW1 and EUWY*5-24KZW1.............. 3–50

Part 4Commissioning and Test Run

1 Pre-Test Run Checks

1.1 What Is in This Chapter? ......................................................................... 4–31.2 General Checks ....................................................................................... 4–41.3 Water Piping Checks ............................................................................... 4–51.4 External Static Pressure: EUWAC5FZW1 ............................................... 4–81.5 External Static Pressure: EUWA*5-12KZW1........................................... 4–101.6 External Static Pressure: EUWA*16-24KZW1......................................... 4–121.7 External Static Pressure: EUWY*5-12KZW1........................................... 4–141.8 External Static Pressure: EUWY*16-24KZW1......................................... 4–161.9 Static Pressure of the Pump for EUWA*5-24KZW1 and

EUWY*5-24KZW1 ................................................................................... 4–181.10 Motor Pulley Setting: EUWAC8FZW1...................................................... 4–201.11 Motor Pulley Setting EUWAC10FZW1..................................................... 4–221.12 Water Pressure Drop through Evaporator: EUWAC5-8-10FZW1............ 4–241.13 Water Pressure Drop through Evaporator: EUWA*5-12KZW1................ 4–251.14 Water Pressure Drop through Evaporator: EUWA*16-24KZW1.............. 4–271.15 Water Pressure Drop through Evaporator: EUWY*5-12KZW1................ 4–291.16 Water Pressure Drop through Evaporator: EUWY*16-24KZW1.............. 4–311.17 Setting of the Flow Switch ....................................................................... 4–331.18 Air fan adjustment.................................................................................... 4–351.19 Electrical Checks ..................................................................................... 4–361.20 Control of the function of the 4-way valve for EUWY5-24KZW1.............. 4–37

Page 6: Chilere Daikin

ESIE-0302

Table of Contents v

3

4

5

12 Test Run and Operation Data

2.1 What Is in This Chapter? ........................................................................ 4–432.2 Test Run and Operation Data for EUWAC5-10FZW1............................. 4–442.3 Test Run and Operation Data for EUWA*5-24KZW1 and

EUWY*5-24KZW1................................................................................... 4–45

Part 5Maintenance

1 Maintenance

1.1 What Is in This Chapter .......................................................................... 5–31.2 Maintenance of the Main Parts ............................................................... 5–41.3 Maintenance of the Control Devices ....................................................... 5–61.4 Periodical Checks ................................................................................... 5–7

Page 7: Chilere Daikin

ESIE-0302

vi Table of Contents

3

1

4

5

Page 8: Chilere Daikin

ESIE-0302 Introduction

vii

3

4

5

Part 0

1 Introduction

1.1 About This Manual

Target group This service manual is intended for and should only be used by qualified engineers.

Purpose of this manual

This service manual contains all the information you need to carry out the necessary repair and maintenance tasks for the EUWAC5-10FZW1, EUWA*5-24KZW1 and EUWY*5-24KZW1.

EUWAC5-10FZW1 The Daikin EUWAC5-10FZW1 air-cooled water chillers:

■ Are designed for indoor installation (centrifugal fan).

■ Are used for cooling applications.

■ Are available in three standard sizes with nominal cooling capacities ranging from 11.6 kW to 24.2 kW.

EUWA*5-24KZW1 The Daikin EUWA*5-24KZW1 air-cooled water chillers:

■ Are designed for outdoor installation.

■ Are used for cooling applications.

■ Are available in seven standard sizes with nominal cooling capacities ranging from 11.3 kW to 55.3 kW.

■ have three types of units:EUWAN5-24KZW1 = without hydraulic module, naked modelEUWAP5-24KZW1 = with hydraulic module: pump and expansion vesselEUWAB5-24KZW1 = with hydraulic module: buffer tank, pump and expansion vessel.

EUWY*5-24KZW1 The Daikin EUWY*5-24KZW1 heat pump water chillers:

■ Are designed for outdoor installation.

■ Are used for cooling and heating applications.

■ Are available in seven standard sizes with nominal cooling capacities ranging from 9.1 kW to 50 kW and heating from 11.9 kW to 54 kW.

■ have three types of units:EUWYN5-24KZW1 = without hydraulic module, naked modelEUWYP5-24KZW1 = with hydraulic module: pump and expansion vesselEUWYB5-24KZW1 = with hydraulic module: buffer tank, pump and expansion vessel.

Before starting up the unit

Before starting up the unit for the first time, make sure it has been properly installed. See "Pre-Test Run Checks" on page 4–3.

Page 9: Chilere Daikin

Introduction ESIE-0302

viii

3

1

4

5

Page 10: Chilere Daikin

ESIE-0302

Part 1 – System Outline 1–1

4

3

4

5

1

Part 1System Outline

Introduction This part contains an outline of all the relevant elements in the EUWAC5-10FZW1, EUWA*5-24KZW1 and EUWY*5-24KZW1 installation.

What is in this part? This part contains the following chapters:

Chapter See page

1–General Outline 1–3

2–Piping Layout 1–79

3–Wiring Layout 1–89

Page 11: Chilere Daikin

ESIE-0302

1–2 Part 1 – System Outline

3

11

5

Page 12: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–3

3

1

4

5

Part 1

1 General Outline

1.1 What Is in This Chapter?

Introduction This chapter contains the following information:

■ Technical specifications

■ Electrical specifications

■ Installation outline of a typical installation

■ Outlook drawings: Outlook, dimensions, installation and service space.

Overview This chapter contains the following topics:

Topic See page

1.2–Technical Specifications: EUWAC5-10FZW1 1–5

1.3–Technical Specifications: EUWA*5-8KZW1 1–8

1.4–Technical Specifications: EUWA*10-12KZW1 1–11

1.5–Technical Specifications: EUWA*16-20KZW1 1–14

1.6–Technical Specifications: EUWA*24KZW1 1–17

1.7–Technical Specifications: EUWY5-8KZW1 1–20

1.8–Technical Specifications: EUWY*10-12KZW1 1–23

1.9–Technical Specifications: EUWY*16-20KZW1 1–26

1.10–Technical Specifications: EUWY*24KZW1 1–29

1.11–Correction factors for glycol 1–32

1.12–Electrical Specifications: EUWAC5-10FZW1 1–34

1.13–Electrical Specifications: EUWA*5-8KZW1 1–36

1.14–Electrical Specifications: EUWA*10-12KZW1 1–38

1.15–Electrical Specifications: EUWA*16-20KZW1 1–40

1.16–Electrical Specifications: EUWA*24KZW1 1–42

1.17–Electrical Specifications: EUWY*5-8KZW1 1–44

1.18–Electrical Specifications: EUWY*10-12KZW1 1–46

1.19–Electrical Specifications: EUWY*16-20KZW1 1–48

1.20–Electrical Specifications: EUWY*24KZW1 1–50

1.21–Outlook Drawing: EUWAC5FZW1 1–52

1.22–Outlook Drawing: EUWAC8-10FZW1 1–53

Page 13: Chilere Daikin

General Outline ESIE-0302

1–4 Part 1 – System Outline

3

11

4

5

1.23–Outlook Drawing: EUWAN5-8KZW1 1–54

1.24–Outlook Drawing: EUWAP5-8KZW1 1–55

1.25–Outlook Drawing: EUWAB5-8KZW1 1–56

1.26–Outlook Drawing: EUWAN10-12KZW1 1–57

1.27–Outlook Drawing: EUWAP10-12KZW1 1–58

1.28–Outlook Drawing: EUWAB10-12KZW1 1–59

1.29–Outlook Drawing: EUWAN16KZW1 1–60

1.30–Outlook Drawing: EUWAP16KZW1 1–61

1.31–Outlook Drawing: EUWAB16KZW1 1–62

1.32–Outlook Drawing: EUWAN20-24KZW1 1–63

1.33–Outlook Drawing: EUWAP20-24KZW1 1–64

1.34–Outlook Drawing: EUWAB20-24KZW1 1–65

1.35–Outlook Drawing: EUWYN5-8KZW1 1–66

1.36–Outlook Drawing: EUWYP5-8KZW1 1–67

1.37–Outlook Drawing: EUWYB5-8KZW1 1–68

1.38–Outlook Drawing: EUWYN10-12KZW1 1–69

1.39–Outlook Drawing: EUWYP10-12KZW1 1–70

1.40–Outlook Drawing: EUWYB10-12KZW1 1–71

1.41–Outlook Drawing: EUWYN16KZW1 1–72

1.42–Outlook Drawing: EUWYP16KZW1 1–73

1.43–Outlook Drawing: EUWYB16KZW1 1–74

1.44–Outlook Drawing: EUWYN20-24KZW1 1–75

1.45–Outlook Drawing: EUWYP20-24KZW1 1–76

1.46–Outlook Drawing: EUWYB20-24KZW1 1–77

Topic See page

Page 14: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–5

3

1

4

5

1.2 Technical Specifications: EUWAC5-10FZW1

Technical specifications

The table below contains the technical specifications(1).

Model EUWAC5FZW1 EUWAC8FZW1 EUWAC10FZW1

Nominal cooling capacity

11.6 kW 18.4 kW 24.2 kW

Nominal cooling input

5.25 kW 7.78 kW 10.1 kW

Capacity steps 0% - 100%

Compressor

Type Hermetically sealed scroll

Speed 2900 rpm

Crankcase heater 33 W 50 W

No. x model 1 x JT140BF-YE 1 x JT212DA-YE 1 x JT265DA-YE

Evaporator

Type Brazed plate-heat exchanger

Min.water volume in

the system (2)

101 l 153 l 212 l

No. x model 1 x AC50-24 1 x AC50-34 1 x AC50-40

Water flow rate Min.: 16 l/minMax.: 64 l/min

Min.: 23 l/minMax.: 92 l/min

Min.: 28 l/minMax.: 112 l/min

Nominal water flow 33 l/min 53 l/min 69 l/min

Nominal water pressure drop

26 kPa 41 kPa 46 kPa

Insulation material PVC nitril foam

Condenser

Type Cross fin coil / Hi-X-tubes and PE coated waffle louvre fins

Rows x stages x fin pitch

3 x 6 + 2 x 2 mm 3 x 11 + 2 x 2 mm 3 x 13 + 2 x 2 mm

Face area 0.472 m² 0.772 m² 0.950 m²

Nominal air flow 70 m³/min 100 m³/min 120 m³/min

Discharge Horizontal

Fan type Centrifugal

Fan drive Direct drive Belt drive

No. of fans 1 1

Motor output 1.04 kW 1.58 kW 1.59 kW

Piping connections

Evap. water in/outlet FBSP 1”

Refrigerant circuit

Refrigerant type R-407C

Refrigerant charge 2.1 kg 3.9 kg 4.7 kg

Refrigerant control Thermostatic expansion valve

Oil type Idemitsu FVC 68D

Page 15: Chilere Daikin

General Outline ESIE-0302

1–6 Part 1 – System Outline

3

11

4

5 (1): The table below contains the conditions for the technical specification values.

(2): The table below contains the minimum water volume settings.

(3): The sound power level is an absolute value that does not depend on the surroundings or the distance (ISO 9614). It cannot be measured in the field

Dimensions(h x w x d)

1345 x 856 x 630 mm 1290 x 1180 x 630 mm 1395 x 1330 x 630 mm

Weight

Machine weight 164 kg 224 kg 261 kg

Operation weight 166 kg 228 kg 266 kg

Casing

Material Polyester coated / galvanised steel plate

Colour Ivory white / Munsell code 5Y7.5/1 / ± RAL 7044

Sound power level (3) 63 dB 66 dB 69 dB

Safety devices

■ Low-pressure switch

■ High-pressure switch

■ Evaporating temperature protection

■ Discharge temperature protection

■ Outlet water temperature protection

■ Compressor motor overcurrent relay

■ Fan thermal protector

■ Anti-recycling and guard timer

■ Digital display controller with electronic temperature control

■ Reverse phase protector

■ Internal fuses.

Al values are valid for an external static pressure of...

with factory pulley setting...

5 HP 50 Pa _

8 HP 60 Pa 0 turns open.

10 HP 72 Pa 0 turns open.

Setting EUWAC5-10FZW1

The minimum water volume for standard thermostat difference setting 3 K

For reduced setting multiply this water volume by 3/new setting

Minimum allowable setting 0.1 K

Model EUWAC5FZW1 EUWAC8FZW1 EUWAC10FZW1

Page 16: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–7

3

1

4

5

Nominal conditions The nominal conditions are as follows:

■ Entering/leaving evaporator water temperature 12/7°C

■ Ambient air temperature 35°C

■ Power input is total input: Compressor + control circuit + fan + pumps.

Operation range The nominal operation range covers a leaving evaporator water temperature from 4°C (-5°C/ -10°C with ZH/ ZL option) to 21°C (pull down condition to 25°C).

Page 17: Chilere Daikin

General Outline ESIE-0302

1–8 Part 1 – System Outline

3

11

4

5

1.3 Technical Specifications: EUWA*5-8KZW1

Technical specifications

The table below contains the technical specifications.

Model EUWAN5KZW1 EUWAP5KZW1 EUWAB5KZW1 EUWAN8KZW1 EUWAP8KZW1 EUWAB8KZW1

Nominal cooling capacity

11.3 kW 17.9 kW

Nominal cooling input

4.52 kW 4.64 kW 7.38 kW 7.39 kW

Capacity steps 0-100% 0-100%

Compressor

Type Hermetically sealed scroll Hermetically sealed scroll

Speed 2900 rpm 2900 rpm

Crankcase heater 33 W 50 W

No. x model (W1) 1 x JT140BF-YE 1 x JT212DA-YE

Evaporator

Type Brased plate-heat exchanger Brased plate-heat exchanger

No. x model 1 x AC50-24HX 1 x AC50-34HX

Min.water volume

in the system (1)54 l 85 l

Water flow rate Min.: 16 l/minMax.: 65 l/min

Min.: 26 l/minMax.: 102 l/min

Nominal water flow 32 l/min 51 l/min

Nom. water pressure drop

24 kPa 38 kPa

Insulation material Climaflex

Condenser

Type Cross fin coil Hi-X tubes and PE coated waffle louvre fins

Rows x stages x fin pitch

2 x 40 x 2.0 mm

Face area 1.570 m²

Nominal air flow 160 m³/min 170 m³/min

Discharge Vertical

Fan type Direct drive

No. of fans 2

No. of motors x output

2 x 140 kW 1 x 190 kW and 1 x 230 kW

Piping connections

Evap. water in/outlet

FBSP 1-1/4” FBSP 1-1/4”

Refrigerant circuit

Refrigerant type R-407C

Refrigerant charge 3.9 kg 4.6 kg

Refrigerant control Thermostatic expansion valve

Oil type Idemitsu FVC 68D

Page 18: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–9

3

1

4

5

(1): The table below contains the minimum water volume settings.

Oil charge volume 1.5 l 2.7 l

No. of circuits 1

Pump

No. x type __ 1 x Horizontal multi-stage end-suction __ 1 x Horizontal multi-stage end-suction

Model __ CH4-30 CH4-30

Nominal static height pump

__ 238 kPa 216 kPa

Nominal static height unit

__ 205 kPa 154 kPa

Hydraulic components

Buffer tank __ 55 l __ 55 l

Unit water volume 2 l 3 l 59 l 3 l 3 l 59 l

Expansion vessel __ 12 l __ 12 l

Pre-pressureexpansion vessel

1.5 bar 1.5 bar

Safety valve __ 3 bar __ 3 bar

Dimensions(h x w x d)

1230 x 1290 x 734 mm 1230 x 1290 x 734 mm

Weight

Machine weight 150 kg 168 kg 180 kg 215 kg 229 kg 241 kg

Operation weight 152 kg 171 kg 239 kg 218 kg 232 kg 300 kg

Casing

Colour Ivory white / Munsell code 5Y7.5/1 / ± RAL 7044

Material Polyester coated galvanised steel plate

Sound power

level (2)67 dBA 76 dBA

Safety devices ■ Low-pressure switch

■ High-pressure switch

■ Pump motor overcurrent

■ Discharge temperature control

■ Outlet water temperature protection

■ Compressor motor overcurrent relay

■ Fan thermal protector

■ Anti-recycling and guard timer

■ Digital display controller with electronic temperature control

■ Reverse phase protector

■ Flow switch.

Model EUWAN5KZW1 EUWAP5KZW1 EUWAB5KZW1 EUWAN8KZW1 EUWAP8KZW1 EUWAB8KZW1

Setting EUWA5-12KZW1

The minimum water volume for standard thermostat difference setting 3 K

For reduced setting multiply this water volume by 3/new setting

Minimum allowable setting 0.1 K

Page 19: Chilere Daikin

General Outline ESIE-0302

1–10 Part 1 – System Outline

3

11

4

5

(2): The sound power level is an absolute value that does not depend on the surroundings or the distance. It cannot be measured in the field (ISO 9614).

Nominal conditions The nominal conditions are as follows:

■ Entering/leaving evaporator water temperature 12.5/7°C

■ Ambient air temperature 35°C

■ Power input is total input: Compressor + control circuit + fans + pump.

Operation range The nominal operation range covers a leaving evaporator water temperature from 5°C (-5°C/-10°C for ZH/ZL option) to 20°C (pull down condition to 25°C).

Page 20: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–11

3

1

4

5

1.4 Technical Specifications: EUWA*10-12KZW1

Technical specifications

The table below contains the technical specifications.

Model EUWAN10KZW1 EUWAP10KZW1 EUWAB10KZW1 EUWAN12KZW1 EUWAP12KZW1 EUWAB12KZW1

Nominal cooling capacity

22.5 kW 26.5 kW

Nominal cooling input

8.79 kW 8.74 kW 11.5 kW

Capacity steps 0-100%

Compressor

Type Hermetically sealed scroll

Speed 2900 rpm

Crankcase heater 50 W

No. x model (W1) 1 x JT265DA-YE 1 x JT335DA-YE

Evaporator

Type Brased plate-heat exchanger

No. x model 1 x AC50-40HX 1 x AC50-50HX

Min.water volume

in the system (1)108 l 126 l

Water flow rate Min.: 32 l/minMax.: 129 l/min

Min.: 38 l/minMax.: 152 l/min

Nominal water flow 64 l/min 76 l/min

Nom. water pressure drop

43 kPa 37 kPa

Insulation material Climaflex

Condenser

Type Cross fin coil Hi-X tubes and PE coated waffle louvre fins

Rows x stages x fin pitch

2 x 50 x 2.0 mm

Face area 1.970 m²

Nominal air flow 170 m³/min

Discharge Vertical

Fan type Direct drive

No. of fans 2

No. of motors x output

1 x 190 kW and 1 x 230 kW 1 x 190 kW and 1 x 230 kW

Piping connections

Evap. water in/outlet

FBSP 1-1/4”

Refrigerant circuit

Refrigerant type R-407C

Refrigerant charge 4.6 kg 6.0 kg

Refrigerant control Thermostatic expansion valve

Oil type Idemitsu FVC 68D

Page 21: Chilere Daikin

General Outline ESIE-0302

1–12 Part 1 – System Outline

3

11

4

5

(1): The table below contains the minimum water volume settings.

Oil charge volume 2.7 l

No. of circuits 1

Pump

No. x type __ 1 x Horizontal multi-stage end-suction __ 1 x Horizontal multi-stage end-suction

Model __ CH4-30 __ CH4-30

Nominal static height pump

__ 199 kPa __ 182 kPa

Nominal static height unit

__ 123 kPa __ 105 kPa

Hydraulic components

Buffer tank __ 55 l __ 55 l

Unit water volume 3 l 3 l 59 l 3 l 4 l 60 l

Expansion vessel __ 12 l __ 12 l

Pre-pressure expansion vessel

1.5 bar 1.5 bar

Safety valve __ 3 bar __ 3 bar

Dimensions(h x w x d)

1450 x 1290 x 734 mm

Weight

Machine weight 245 kg 259 kg 271 kg 248 kg 262 kg 274 kg

Operation weight 248 kg 262 kg 330 kg 251 kg 265 kg 335 kg

Casing

Colour Ivory white / Munsell code 5Y7.5/1 / ± RAL 7044

Material Polyester coated galvanised steel plate

Sound power

level (2)78 dBA

Safety devices ■ Low-pressure switch

■ High-pressure switch

■ Pump motor overcurrent

■ Discharge temperature control

■ Outlet water temperature protection

■ Compressor motor overcurrent relay

■ Fan thermal protector

■ Anti-recycling and guard timer

■ Digital display controller with electronic temperature control

■ Reverse phase protector

■ Flow switch.

Model EUWAN10KZW1 EUWAP10KZW1 EUWAB10KZW1 EUWAN12KZW1 EUWAP12KZW1 EUWAB12KZW1

Setting EUWA5-12KZW1

The minimum water volume for standard thermostat difference setting 3 K

For reduced setting multiply this water volume by 3/new setting

Minimum allowable setting 0.1 K

Page 22: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–13

3

1

4

5

(2): The sound power level is an absolute value that does not depend on the surroundings or the distance. It cannot be measured in the field (ISO 9614).

Nominal conditions The nominal conditions are as follows:

■ Entering/leaving evaporator water temperature 12.5/7°C

■ Ambient air temperature 35°C

■ Power input is total input: Compressor + control circuit + fans + pump.

Operation range The nominal operation range covers a leaving evaporator water temperature from 5°C (-5°C/-10°C for ZH/ZL option) to 20°C (pull down condition to 25°C).

Page 23: Chilere Daikin

General Outline ESIE-0302

1–14 Part 1 – System Outline

3

11

4

5

1.5 Technical Specifications: EUWA*16-20KZW1

Technical specifications

The table below contains the technical specifications.

Model EUWAN16KZW1 EUWAP16KZW1 EUWAB16KZW1 EUWAN20KZW1 EUWAP20KZW1 EUWAB20KZW1

Nominal cooling capacity

37.0 kW 46.6 kW

Nominal cooling input

15.2 kW 15.0 kW 18.1 kW 17.9 kW

Capacity steps 0%-50%-100%

Compressor

Type Hermetically sealed scroll

Speed 2900 rpm

Crankcase heater 50 W

No. x model (W1) 2 x JT212DA-YE 2 x JT265DA-YE

Evaporator

Type Brased plate-heat exchanger

No. x model 1 x AC130-38DQ 1 x AC130-50DQ

Min.water volume

in the system (1)88 l 111 l

Water flow rate Min.: 53 l/minMax.: 212 l/min

Min.: 67 l/minMax.: 267 l/min

Nominal water flow 106 l/min 134 l/min

Nom. water pressure drop

22 kPa

Insulation material Climaflex

Condenser

Type Cross fin coil Hi-X tubes and PE coated waffle louvre fins

Rows x stages x fin pitch

2 x 40 x 2 mm 2 x 50 x 2 mm

Face area 2 x 1.570 m² 2 x 1.970 m²

Nominal air flow 2 x 170 m³/min

Discharge Vertical

Fan type Direct drive

No. of fans 4

No. of motors x output

2 x 190 kW + 2 x 230 kW

Piping connections

Evap. water in/outlet

FBSP 2”

Refrigerant circuit

Refrigerant type R-407C

Refrigerant charge 2 x 4.6 kg __ 2 x 5.9 kg __

Refrigerant control Thermostatic expansion valve

Oil type Idemitsu FVC 68D

Page 24: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–15

3

1

4

5

(1): The table below contains the minimum water volume settings.

(2): The sound power level is an absolute value that does not depend on the surroundings or the distance. It cannot be measured in the field (ISO 9614).

Pump

No. x type __ 1 x Horizontal multi-stage end-suction __ 1 x Horizontal multi-stage end-suction

Model __ CH8-30 __ CH8-30

Nominal static height pump

__ 243 kPa __ 210 kPa

Nominal static height unit

__ 187 kPa __ 137 kPa

Hydraulic components

Buffer tank __ 55 l __ 55 l

Unit water volume 6 l 9 l 65 l 6 l 10 l 66 l

Expansion vessel __ 12 l __ 12 l

Pre-pressureexpansion vessel

1.5 bar

Safety valve __ 3 bar __ 3 bar

Dimensions(h x w x d)

1321 x 2580 x 734 mm 1541 x 2580 x 734 mm

Weight

Machine weight 430 kg 448 kg 460 kg 490 kg 508 kg 520 kg

Operation weight 436 kg 457 kg 525 kg 496 kg 518 kg 586 kg

Casing

Colour Ivory white / Munsell code 5Y7.5/1 / ± RAL 7044

Material Polyester coated galvanised steel plate

Sound power

level (2)79 dBA 81 dBA

Safety devices ■ Low-pressure switch

■ High-pressure switch

■ Pump motor overcurrent

■ Discharge temperature protection

■ Outlet water temperature protection

■ Compressor motor overcurrent relay

■ Fan thermal protector

■ Anti-recycling and guard timer

■ Digital display controller with electronic temperature control

■ Reverse phase protector

■ Flow switch.

Model EUWAN16KZW1 EUWAP16KZW1 EUWAB16KZW1 EUWAN20KZW1 EUWAP20KZW1 EUWAB20KZW1

Setting EUWA16-20KZW1

The minimum water volume for standard thermostat difference setting 3 K

For reduced setting multiply this water volume by 3/new setting

Minimum allowable setting 0.1 K

Page 25: Chilere Daikin

General Outline ESIE-0302

1–16 Part 1 – System Outline

3

11

4

5

Nominal conditions The nominal conditions are as follows:

■ Entering/leaving evaporator water temperature 12.5/7°C

■ Ambient air temperature 35°C

■ Power input is total input: Compressor + control circuit + fans + pump.

Operation range The nominal operation range covers a leaving evaporator water temperature from 5°C (-5°C/-10°C for ZH/ZL option) to 20°C (pull down condition to 25°C).

Page 26: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–17

3

1

4

5

1.6 Technical Specifications: EUWA*24KZW1

Technical specifications

The table below contains the technical specifications.

Model EUWAN24KZW1 EUWAP24KZW1 EUWAB24KZW1

Nominal cooling capacity

55.3 kW

Nominal cooling input

24.0 kW 24.0 kW

Capacity steps 0%-50%-100%

Compressor

Type Hermetically sealed scroll

Speed 2900 rpm

Crankcase heater 50 W

No. x model (W1) 2 x JT335DA-YE

Evaporator

Type Brased plate-heat exchanger

No. x model 1 x AC130-58DQ

Min.water volume in

the system (1)132 l

Water flow rate Min.: 79 l/minMax.: 317 l/min

Nominal water flow 158 l/min

Nom. water pressure drop

22 kPa

Insulation material Climaflex

Condenser

Type Cross fin coil Hi-X tubes and PE coated waffle louvre fins

Rows x stages x fin pitch

2 x 50 x 2 mm

Face area 2 x 1.970 m²

Nominal air flow 2 x 170 m³/min

Discharge Vertical

Fan type Direct drive

No. of fans 4

No. of motors x output

2 x 190 kW + 2 x 230 kW

Piping connections

Evap. water in/outlet FBSP 2”

Refrigerant circuit

Refrigerant type R-407C

Refrigerant charge 2 x 6.0 kg

Refrigerant control Thermostatic expansion valve

Oil type Idemitsu FVC 68D

Page 27: Chilere Daikin

General Outline ESIE-0302

1–18 Part 1 – System Outline

3

11

4

5

(1): The table below contains the minimum water volume settings.

(2): The sound power level is an absolute value that does not depend on the surroundings or the distance. It cannot be measured in the field (ISO 9614).

Model EUWAN24KZW1 EUWAP24KZW1 EUWAB24KZW1

Pump

No. x type __ 1 x Horizontal multi-stage end-suction

Model __ CH8-40

Nominal static height pump

__ 191 kPa

Nominal static height unit

__ 100 kPa

Hydraulic components

Buffer tank __ 55 l

Unit water volume 7 l 10 l 66 l

Expansion vessel __ 12 l

Pre-pressureexpansion vessel

1.5 bar

Safety valve __ 3 bar

Dimensions(h x w x d)

1541 x 2580 x 734 mm

Weight

Machine weight 496 kg 514 kg 526 kg

Operation weight 503 kg 524 kg 592 kg

Casing

Colour Ivory white / Munsell code 5Y7.5/1 / ± RAL 7044

Material Polyester coated galvanised steel plate

Sound power level (2) 81 dBA

Safety devices ■ Low-pressure switch

■ High-pressure switch

■ Pump motor overcurrent

■ Discharge temperature protection

■ Outlet water temperature protection

■ Compressor motor overcurrent relay

■ Fan thermal protector

■ Anti-recycling and guard timer

■ Digital display controller with electronic temperature control

■ Reverse phase protector

■ Flow switch.

Setting EUWA24KZW1

The minimum water volume for standard thermostat differ-ence setting

3 K

For reduced setting multiply this water volume by 3/new setting

Minimum allowable setting 0.1 K

Page 28: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–19

3

1

4

5

Nominal conditions The nominal conditions are as follows:

■ Entering/leaving evaporator water temperature 12.5/7°C

■ Ambient air temperature 35°C

■ Power input is total input: Compressor + control circuit + fans + pump.

Operation range The nominal operation range covers a leaving evaporator water temperature from 5°C (-5°C/-10°C for ZH/ZL option) to 20°C (pull down condition to 25°C).

Page 29: Chilere Daikin

General Outline ESIE-0302

1–20 Part 1 – System Outline

3

11

4

5

1.7 Technical Specifications: EUWY5-8KZW1

Technical specifications

The table below contains the technical specifications.

Model EUWYN5KZW1 EUWYP5KZW1 EUWYB5KZW1 EUWYN8KZW1 EUWYP8KZW1 EUWYB8KZW1

Nominal cooling capacity

Cooling: 9.1 kWHeating: 11.9 kW

Cooling: 17.1 kWHeating: 18.5 kW

Nominal cooling input

Cooling: 3.78 kWHeating: 4.59 kW

Cooling: 7.45 kWHeating: 7.10 kW

Cooling: 7.46 kWHeating: 7.10 kW

Capacity steps 0-100%

Compressor

Type Hermetically sealed scroll

Speed 2900 rpm

Crankcase heater 33 W 50 W

No. x model (W1) 1 x JT140BF-YE 1 x JT212DA-YE

Evaporator

Type Brased plate-heat exchanger

No. x model 1 x AC50-34HX 1 x AC50-40HX

Min.water volume

in the system (1)43 l 82 l

Water flow rate Min.: 21 l/minMax.: 68 l/min

Min.: 31 l/minMax.: 106 l/min

Nominal water flow Cooling: 26 l/minHeating: 34 l/min

Cooling: 49 l/minHeating: 53 l/min

Nom. water pressure drop

Cooling: 10 kPaHeating: 17 kPa

Cooling: 25 kPaHeating: 29 kPa

Insulation material Climaflex

Condenser

Type Cross fin coil Hi-X tubes and PE coated waffle louvre fins

Rows x stages x fin pitch

2 x 40 x 2

Face area 1.570 m²

Nominal air flow 160 m³/min 170 m³/min

Discharge Vertical

Fan type Direct drive

No. of fans 2

No. of motors x output

2 x 140 kW 1 x 190 kW and 1 x 230 kW

Piping connections

Evap. water in/outlet

FBSP 1-1/4”

Refrigerant circuit

Refrigerant type R-407C

Refrigerant charge 4.6 kg 4.7 kg

Refrigerant control Thermostatic expansion valve

Oil type Idemitsu FVC 68D

Page 30: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–21

3

1

4

5

(1): The table below contains the minimum water volume settings.

Oil charge volume 1.5 l 2.7 l

No. of circuits 1

Pump

No. x type __ 1 x Horizontal multi-stage end-suction __ 1 x Horizontal multi-stage end-suction

Model __ CH4-30 __ CH4-30

Nominal static height pump

__ Cooling: 244 kPaHeating: 236 kPa

__ Cooling: 219 kPaHeating: 214 kPa

Nominal static height unit

__ Cooling: 223 kPaHeating: 205 kPa

__ Cooling: 171 kPaHeating: 160 kPa

Hydraulic components

Buffer tank __ 55 l __ 55 l

Unit water volume 2 l 3 l 59 l 3 l 3 l 59 l

Expansion vessel __ 12 l __ 12 l

Pre-pressureexpansion vessel

1.5 bar 1.5 bar

Safety valve __ 3 bar __ 3 bar

Dimensions(h x w x d)

1230 x 1290 x 734 mm

Weight

Machine weight 163 kg 181 kg 193 kg 227 kg 241 kg 253 kg

Operation weight 165 kg 184 kg 252 kg 230 kg 244 kg 312 kg

Casing

Colour Ivory white / Munsell code 5Y7.5/1 / ± RAL 7044

Material Polyester coated galvanised steel plate

Sound power

level (2)67 dBA 76 dBA

Safety devices ■ Low-pressure switch

■ High-pressure switch

■ Pump motor overcurrent

■ Discharge temperature control

■ Outlet water temperature protection

■ Compressor motor overcurrent relay

■ Fan thermal protector

■ Anti-recycling and guard timer

■ Digital display controller with electronic temperature control

■ Reverse phase protector

■ Flow switch.

Model EUWYN5KZW1 EUWYP5KZW1 EUWYB5KZW1 EUWYN8KZW1 EUWYP8KZW1 EUWYB8KZW1

Setting EUWY5-12KZW1

The minimum water volume for standard thermostat difference setting 3 K

For reduced setting multiply this water volume by 3/new setting

Minimum allowable setting 0.1 K

Page 31: Chilere Daikin

General Outline ESIE-0302

1–22 Part 1 – System Outline

3

11

4

5

(2): The sound power level is an absolute value that does not depend on the surroundings or the distance. It cannot be measured in the field (ISO 9614).

Nominal conditions The nominal conditions are as follows:

■ Entering/leaving evaporator water temperature 12.5/7°C

■ Ambient air temperature 35°C

■ Power input is total input: Compressor + control circuit + fans + pump.

Operation range The nominal operation range covers:

■ A leaving evaporator water temperature from 5°C (-5°C/-20°C for ZH/ZL option) to 20°C (pull down condition to 25°C).

■ A leaving condensor water temperature from 35°C to 50°C.

Page 32: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–23

3

1

4

5

1.8 Technical Specifications: EUWY*10-12KZW1

Technical specifications

The table below contains the technical specifications.

Model EUWYN10KZW1 EUWYP10KZW1 EUWYB10KZW1 EUWYN12KZW1 EUWYP12KZW1 EUWYB12KZW1

Nominal cooling capacity

Cooling: 21.0 kWHeating: 24.0 kW

Cooling: 25.0 kWHeating: 27.0 kW

Nominal cooling input

Cooling: 8.57 kWHeating: 9.10 kW

Cooling: 11.4 kWHeating: 10.8 kW

Capacity steps 0-100%

Compressor

Type Hermetically sealed scroll

Speed 2900 rpm

Crankcase heater 50 W

No. x model (W1) 1 x JT265DA-YE 1 x JT335DA-YE

Evaporator

Type Brased plate-heat exchanger

No. x model 1 x AC50-50HX

Min.water volume

in the system (1)100 l 119 l

Water flow rate Min.: 38 l/minMax.: 137 l/min

Min.: 45 l/minMax.: 155 l/min

Nominal water flow Cooling: 60 l/minHeating: 69 l/min

Cooling: 72 l/minHeating: 77 l/min

Nom. water pressure drop

Cooling: 24 kPaHeating: 31 kPa

Cooling: 33 kPaHeating: 38 kPa

Insulation material Climaflex

Condenser

Type Cross fin coil Hi-X tubes and PE coated waffle louvre fins

Rows x stages x fin pitch

2 x 50 x 2

Face area 1.970 m²

Nominal air flow 170 m³/min

Discharge Vertical

Fan type Direct drive

No. of fans 2

No. of motors x output

1 x 190 kW and 1 x 230 kW

Piping connections

Evap. water in/outlet

FBSP 1-1/4”

Refrigerant circuit

Refrigerant type R-407C

Refrigerant charge 5.4 kg

Refrigerant control Thermostatic expansion valve

Oil type Idemitsu FVC 68D

Page 33: Chilere Daikin

General Outline ESIE-0302

1–24 Part 1 – System Outline

3

11

4

5

(1): The table below contains the minimum water volume settings.

Oil charge volume 2.7 l

No. of circuits 1

Pump

No. x type __ 1 x Horizontal multi-stage end-suction __ 1 x Horizontal multi-stage end-suction

Model __ CH4-30 __ CH4-30

Nominal static height pump

__ Cooling: 205 kPaHeating: 193 kPa

__ Cooling: 188 kPaHeating: 180 kPa

Nominal static height unit

__ Cooling: 151 kPaHeating: 127 kPa

__ Cooling: 118 kPaHeating: 100 kPa

Hydraulic components

Buffer tank __ 55 l __ 55 l

Unit water volume 3 l 3 l 59 l 3 l 3 l 59 l

Expansion vessel __ 12 l __ 12 l

Pre-pressure expansion vessel

1.5 bar 1.5 bar

Safety valve __ 3 bar __ 3 bar

Dimensions(h x w x d)

1450 x 1290 x 734 mm

Weight

Machine weight 258 kg 272 kg 284 kg 258 kg 272 kg 284 kg

Operation weight 261 kg 275 kg 343 kg 261 kg 275 kg 343 kg

Casing

Colour Ivory white / Munsell code 5Y7.5/1 / ± RAL 7044

Material Polyester coated galvanised steel plate

Sound power

level (2)78 dBA

Safety devices ■ Low-pressure switch

■ High-pressure switch

■ Pump motor overcurrent

■ Discharge temperature control

■ Outlet water temperature protection

■ Compressor motor overcurrent relay

■ Fan thermal protector

■ Anti-recycling and guard timer

■ Digital display controller with electronic temperature control

■ Reverse phase protector

■ Flow switch.

Model EUWYN10KZW1 EUWYP10KZW1 EUWYB10KZW1 EUWYN12KZW1 EUWYP12KZW1 EUWYB12KZW1

Setting EUWY5-12KZW1

The minimum water volume for standard thermostat difference setting 3 K

For reduced setting multiply this water volume by 3/new setting

Minimum allowable setting 0.1 K

Page 34: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–25

3

1

4

5

(2): The sound power level is an absolute value that does not depend on the surroundings or the distance. It cannot be measured in the field (ISO 9614).

Nominal conditions The nominal conditions are as follows:

■ Entering/leaving evaporator water temperature 12.5/7°C

■ Ambient air temperature 35°C

■ Power input is total input: Compressor + control circuit + fans + pump.

Operation range The nominal operation range covers:

■ A leaving evaporator water temperature from 5°C (-5°C/-20°C for ZH/ZL option) to 20°C (pull down condition to 25°C).

■ A leaving condensor water temperature from 35°C to 50°C.

Page 35: Chilere Daikin

General Outline ESIE-0302

1–26 Part 1 – System Outline

3

11

4

5

1.9 Technical Specifications: EUWY*16-20KZW1

Technical specifications

The table below contains the technical specifications.

Model EUWYN16KZW1 EUWYP16KZW1 EUWYB16KZW1 EUWYN20KZW1 EUWYP20KZW1 EUWYB20KZW1

Nominal cooling capacity

Cooling: 34.2 kWHeating: 37.0 kW

Cooling: 40.0 kWHeating: 46.0 kW

Nominal cooling input

Cooling: 14.9 kWHeating: 14.2 kW

Cooling: 16.3 kWHeating: 17.4 kW

Capacity steps 0-100%

Compressor

Type Hermetically sealed scroll

Speed 2900 rpm

Crankcase heater 50 W

No. x model (W1) 2 x JT212DA-YE 2 x JT265DA-YE

Evaporator

Type Brased plate-heat exchanger

No. x model 1 x AC130-50DQ 1 x AC130-58DQ

Min.water volume

in the system (1)82 l 100 l

Water flow rate Min.: 61 l/minMax.: 212 l/min

Min.: 75 l/minMax.: 275 l/min

Nominal water flow Cooling: 98 l/minHeating: 106 l/min

Cooling: 120 l/minHeating: 137 l/min

Nom. water pressure drop

Cooling: 12 kPaHeating: 14 kPa

Cooling: 13 kPaHeating: 17 kPa

Insulation material Climaflex

Condenser

Type Cross fin coil Hi-X tubes and PE coated waffle louvre fins

Rows x stages x fin pitch

2 x 40 x 2 mm 2 x 50 x 2 mm

Face area 2 x 1.570 m² 2 x 1.970 m²

Nominal air flow 2 x 170 m³/min

Discharge Vertical

Fan type Direct drive

No. of fans 4

No. of motors x output

2 x 190 kW + 2 x 230 kW

Piping connections

Evap. water in/outlet

FBSP 2”

Refrigerant circuit

Refrigerant type R-407C

Refrigerant charge 2 x 5.1 kg 2 x 5.2 kg

Refrigerant control Thermostatic expansion valve

Oil type Idemitsu FVC 68D

Page 36: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–27

3

1

4

5

(1): The table below contains the minimum water volume settings.

Oil charge volume 2 x 2.7 l

No. of circuits 2

Pump

No. x type __ 1 x Horizontal multi-stage end-suction __ 1 x Horizontal multi-stage end-suction

Model __ CH8-30 __ CH8-30

Nominal static height pump

__ Cooling: 251 kPaHeating: 243 kPa

__ Cooling: 227 kPaHeating: 204 kPa

Nominal static height unit

__ Cooling: 209 kPaHeating: 195 kPa

__ Cooling: 171 kPaHeating: 134 kPa

Hydraulic components

Buffer tank __ 55 l __ 55 l

Unit water volume 6 l 9 l 65 l 6 l 10 l 66 l

Expansion vessel __ 12 l __ 12 l

Pre-pressureexpansion vessel

1.5 bar

Safety valve __ 3 bar __ 3 bar

Dimensions(h x w x d)

1321 x 2580 x 734 mm 1541 x 2580 x 734 mm

Weight

Machine weight 455 kg 473 kg 485 kg 516 kg 534 kg 546 kg

Operation weight 461 kg 482 kg 550 kg 522 kg 544 kg 612 kg

Casing

Colour Ivory white / Munsell code 5Y7.5/1 / ± RAL 7044

Material Polyester coated galvanised steel plate

Sound power

level (2)79 dBA 81 dBA

Safety devices ■ Low-pressure switch

■ High-pressure switch

■ Pump motor overcurrent

■ Discharge temperature protection

■ Outlet water temperature protection

■ Compressor motor overcurrent relay

■ Fan thermal protector

■ Anti-recycling and guard timer

■ Digital display controller with electronic temperature control

■ Reverse phase protector

■ Flow switch.

Model EUWYN16KZW1 EUWYP16KZW1 EUWYB16KZW1 EUWYN20KZW1 EUWYP20KZW1 EUWYB20KZW1

Setting EUWY*16-20KZW1

The minimum water volume for standard thermostat difference setting 3 K

For reduced setting multiply this water volume by 3/new setting

Minimum allowable setting 0.1 K

Page 37: Chilere Daikin

General Outline ESIE-0302

1–28 Part 1 – System Outline

3

11

4

5

(2): The sound power level is an absolute value that does not depend on the surroundings or the distance. It cannot be measured in the field (ISO 9614).

Nominal conditions The nominal conditions are as follows:

■ Entering/leaving evaporator water temperature 12.5/7°C

■ Ambient air temperature 35°C

■ Power input is total input: Compressor + control circuit + fans + pump.

Operation range The nominal operation range covers:

■ A leaving evaporator water temperature from 5°C (-5°C/-20°C for ZH/ZL option) to 20°C (pull down condition to 25°C).

■ A leaving condensor water temperature from 35°C to 50°C.

Page 38: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–29

3

1

4

5

1.10 Technical Specifications: EUWY*24KZW1

Technical specifications

The table below contains the technical specifications.

Model EUWYN24KZW1 EUWYP24KZW1 EUWYB24KZW1

Nominal cooling capacity

Cooling: 50.0 kWHeating: 54.0 kW

Nominal cooling input

Cooling: 22.8 kWHeating: 21.6 kW

Capacity steps 0%-100%

Compressor

Type Hermetically sealed scroll

Speed 2900 rpm

Crankcase heater 50 W

No. x model (W1) 2 x JT335DA-YE

Evaporator

Type Brased plate-heat exchanger

No. x model 1 x AC130-58DQ

Min.water volume in

the system (1)119 l

Water flow rate Min.: 89 l/minMax.: 309 l/min

Nominal water flow Cooling: 149 l/minHeating: 155 l/min

Nom. water pressure drop

Cooling: 19 kPaHeating: 22 kPa

Insulation material Climaflex

Condenser

Type Cross fin coil Hi-X tubes and PE coated waffle louvre fins

Rows x stages x fin pitch

2 x 50 x 2 mm

Face area 2 x 1.970 m²

Nominal air flow 2 x 170 m³/min

Discharge Vertical

Fan type Direct drive

No. of fans 4

No. of motors x output

2 x 190 kW + 2 x 230 kW

Piping connections

Evap. water in/outlet FBSP 2”

Refrigerant circuit

Refrigerant type R-407C

Refrigerant charge 2 x 5.6 kg

Refrigerant control Thermostatic expansion valve

Oil type Idemitsu FVC 68D

Oil charge volume 2 x 2.7 l

Page 39: Chilere Daikin

General Outline ESIE-0302

1–30 Part 1 – System Outline

3

11

4

5

(1): The table below contains the minimum water volume settings.

No. of circuits 2

Pump

No. x type __ 1 x Horizontal multi-stage end-suction

Model __ CH8-40

Nominal static height pump

__ Cooling: 222 kPaHeating: 199 kPa

Nominal static height unit

__ Cooling: 146 kPaHeating: 111 kPa

Hydraulic components

Buffer tank __ 55 l

Unit water volume 6 l 10 l 66 l

Expansion vessel __ 12 l

Pre-pressureexpansion vessel

1.5 bar

Safety valve __ 3 bar

Dimensions(h x w x d)

Weight

Machine weight 516 kg 534 kg 546 kg

Operation weight 522 kg 544 kg 612 kg

Casing

Colour Ivory white / Munsell code 5Y7.5/1 / ± RAL 7044

Material Polyester coated galvanised steel plate

Sound power level (2) 81 dBA

Safety devices ■ Low-pressure switch

■ High-pressure switch

■ Pump motor overcurrent

■ Discharge temperature protection

■ Outlet water temperature protection

■ Compressor motor overcurrent relay

■ Fan thermal protector

■ Anti-recycling and guard timer

■ Digital display controller with electronic temperature control

■ Reverse phase protector

■ Flow switch.

Setting EUWY24KZW1

The minimum water volume for standard thermostat differ-ence setting

3 K

For reduced setting multiply this water volume by 3/new setting

Minimum allowable setting 0.1 K

Model EUWYN24KZW1 EUWYP24KZW1 EUWYB24KZW1

Page 40: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–31

3

1

4

5

(2): The sound power level is an absolute value that does not depend on the surroundings or the distance. It cannot be measured in the field (ISO 9614).

Nominal conditions The nominal conditions are as follows:

■ Entering/leaving evaporator water temperature 12.5/7°C

■ Ambient air temperature 35°C

■ Power input is total input: Compressor + control circuit + fans + pump.

Operation range The nominal operation range covers:

■ A leaving evaporator water temperature from 5°C (-5°C/-20°C for ZH/ZL option) to 20°C (pull down condition to 25°C).

■ A leaving condensor water temperature from 35°C to 50°C.

Page 41: Chilere Daikin

General Outline ESIE-0302

1–32 Part 1 – System Outline

3

11

4

5

1.11 Correction factors for glycol

Correction factors The illustration below shows the correction factors for glycol for EUWAC5-10FZW1, EUWA*5-24KZW1 and EUWY*5-24KZW1.

Page 42: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–33

3

1

4

5

Legend The table below describes the patterns and symbols used for the correction factors illustration above.

Glycol freezing point

The table below contains glycol freezing points for different glycol concentrations.

Pattern Description

Ethylene glycol

Propylene glycol

Kc Correction on cooling capacity

Ki Correction on power input

Kf Correction on flow rate

Kp Correction on pressure drop

Type Concentration (wt%) 0 10 20 30 40

Ethylene glycol Freezing point °C 0 -4 -9 -16 -23

Minimum LWE °C 5 2 0 -5 -11

Propylene glycol Freezing point °C 0 -3 -7 -13 -22

Minimum LWE °C 5 3 -2 -4 -10

Page 43: Chilere Daikin

General Outline ESIE-0302

1–34 Part 1 – System Outline

3

11

4

5

1.12 Electrical Specifications: EUWAC5-10FZW1

Electrical specifications

The table below contains the electrical specifications (1).

(1): The table below contains the conditions for the electrical specification values.

Model EUWAC5FZW1 EUWAC8FZW1 EUWAC10FZW1

Power supply

Phase 3N~

Frequency 50 Hz

Voltage 400 V

Voltage tolerance ± 10 %

Unit

Starting current 81 A 110 A 145 A

Nominal running current

9.0 A 14.0 A 17.0 A

Max. running current 16.8 A 21.4 A 25.5 A

Recommended fuses 3 x 25 gG 3 x 32 gG 3 x 32 gG

Fans

Phase 1~ 3~

Voltage 230 V 400 V

Nom. running current 4.6 A 3.3 A

Max. running current 6.8 A 3.4 A 3.5 A

Starting current DOL 20.7 A 14.9 A

Compressor

Phase 3~

Voltage 400 V

Starting current DOL(2) 60.0 A 95.0 A 130 A

Nom. running current 6.70 A 10.7 A 13.7 A

Max. running current (1)

10 A 18 A 22 A

Starting method Direct on line

Control circuit

Phase 1~

Voltage 230/ 24 V AC (supplied by factory installed transformers)

Recommended fuses Factory installed

Crankcase heater (E1/2 HC)

33 W 50 W

Al values are valid for an external static pressure of...

with factory pulley setting...

5 HP 50 Pa _

8 HP 60 Pa 0 turns open.

10 HP 72 Pa 0 turns open.

Page 44: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–35

3

1

4

5

(2): The value is measured when one compressor is ON and the other compressors of the chiller are OFF.

Nominal conditions The nominal conditions are as follows:

■ Entering/leaving evaporator water temperature 12/7°C

■ Ambient air temperature 35°C

■ Power input is total input: Compressor + control circuit + fan +pumps.

Operation range The operation range covers a leaving evaporator water temperature from 4°C (-5°C/ -10°C with ZH/ ZL option) to 21°C (pull down condition to 25°C).

Page 45: Chilere Daikin

General Outline ESIE-0302

1–36 Part 1 – System Outline

3

11

4

5

1.13 Electrical Specifications: EUWA*5-8KZW1

Electrical specifications

The table below contains the electrical specifications (1).

Model EUWAN5KZW1 EUWAP5KZW1 EUWAB5KZW1 EUWAN8KZW1 EUWAP8KZW1 EUWAB8KZW1

Power supply

Phase 3N~

Frequency 50 Hz

Voltage 400 V

Voltage tolerance ± 10 %

Unit

Starting current 62.2 A 63.5 A 97.9 A 99.2 A

Nominal running current

7.7 A 9.0 A 13.6 A 14.9 A

Max. running current

11.2 A 12.5 A 16.9 A 18.2 A

Recommended fuses

3 x 20 gL/gG 3 x 20 gL/gG 3 x 25 gL/gG 3 x 25 gL/gG

Fans

Phase 1~

Voltage 230 V

Max. runningcurrent

2.2 A 2.9 A

Compressor

Phase 3~

Voltage 400 V

Starting current 60.0 A 95 A

Nom. running current

5.5 A 10.7 A

Max. running

current

9.0 A 14 A

Starting method Direct on line

Control circuit

Phase 1~

Voltage 230 V

Recommended fuses

Factory installed

Pump

Phase __ 3~ __ 3~

Voltage __ 400.0 V __ 400.0 V

Max. running current

__ 1.3 A __ 1.3 A

Page 46: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–37

3

1

4

5

Nominal conditions The nominal conditions are as follows:

■ Entering/leaving evaporator water temperature 12.5/7°C

■ Ambient air temperature 35°C

■ Power input is total input: Compressor + control circuit + fan +pumps.

Operation range The operation range covers a leaving evaporator water temperature from 5°C to 20°C (pull down condition to 25°C).

Page 47: Chilere Daikin

General Outline ESIE-0302

1–38 Part 1 – System Outline

3

11

4

5

1.14 Electrical Specifications: EUWA*10-12KZW1

Electrical specifications

The table below contains the electrical specifications (1).

Model EUWAN10KZW1 EUWAP10KZW1 EUWAB10KZW1 EUWAN12KZW1 EUWAP12KZW1 EUWAB12KZW1

Power supply

Phase 3N~

Frequency 50 Hz

Voltage 400 V

Voltage tolerance ± 10 %

Unit

Starting current 113 A 114 A 139 A 140 A

Nominal running current

15.9 A 17.2 A 20.5 A 21.8 A

Max. running current

19.9 A 21.2 A 26.9 A 28.2 A

Recommended fuses

3 x 25 gL/gG 3 x 32 gL/gG 3 x 32 gL/gG 3 x 40 gL/gG

Fans

Phase 1~

Voltage 230 V

Max. runningcurrent

2.9 A 2.9 A

Compressor

Phase 3~

Voltage 400 V

Starting current 110.0 A 136.0 A

Nom. running current

13.0 A 17.6 A

Max. running

current

17.0 A 24.0 A

Starting method Direct on line Direct on line

Control circuit

Phase 1~

Voltage 230 V

Recommended fuses

Factory installed

Pump

Phase __ 3~ __ 3~

Voltage __ 400.0 V __ 400.0 V

Max. running current

__ 1.3 A __ 1.3 A

Page 48: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–39

3

1

4

5

Nominal conditions The nominal conditions are as follows:

■ Entering/leaving evaporator water temperature 12.5/7°C

■ Ambient air temperature 35°C

■ Power input is total input: Compressor + control circuit + fan +pumps.

Operation range The operation range covers a leaving evaporator water temperature from 5°C to 20°C (pull down condition to 25°C).

Page 49: Chilere Daikin

General Outline ESIE-0302

1–40 Part 1 – System Outline

3

11

4

5

1.15 Electrical Specifications: EUWA*16-20KZW1

Electrical specifications

The table below contains the electrical specifications.

Model EUWAN16KZW1 EUWAP16KZW1 EUWAB16KZW1 EUWAN20KZW1 EUWAP20KZW1 EUWAB20KZW1

Power supply

Phase 3N~

Frequency 50 Hz

Voltage 400 V

Voltage tolerance ± 10 %

Unit

Starting current 97.9 A 99.9 A 113 A 115 A

Nominal running current

27.2 A 29.2 A 31.8 A 33.8 A

Max. running current

33.8 A 35.8 A 39.8 A 41.8 A

Recommended fuses

3 x 40 gL/gG 3 x 50 gL/gG 3 x 50 gL/gG 3 x 50 gL/gG

Fans

Phase 1~

Voltage 230 V

Max. runningcurrent

5.8 A

Compressor

Phase 3~

Voltage 400 V

Starting current 95.0 A 110.0 A

Nom. running current

10.7 A 13.0 A

Max. running current

14.0 A 17.0 A

Starting method Direct on line

Control circuit

Phase 1~

Voltage 230/ 24 V AC (supplied by factory installed transformers)

Recommended fuses

Factory installed

Crankcase heater (E1/2 HC)

50 W

Pump

Phase __ 3~ __ 3~

Voltage __ 400.0 V __ 400.0 V

Max. running current

__ 2.0 A __ 2.0 A

Page 50: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–41

3

1

4

5

Nominal conditions The nominal conditions are as follows:

■ Entering/leaving evaporator water temperature 12.5/7°C

■ Ambient air temperature 35°C

■ Power input is total input: Compressor + control circuit + fan +pumps.

Operation range The operation range covers a leaving evaporator water temperature from 5°C to 20°C (pull down condition to 25°C).

Page 51: Chilere Daikin

General Outline ESIE-0302

1–42 Part 1 – System Outline

3

11

4

5

1.16 Electrical Specifications: EUWA*24KZW1

Electrical specifications

The table below contains the electrical specifications.

Model EUWAN24KZW1 EUWAP24KZW1 EUWAB24KZW1

Power supply

Phase 3N~

Frequency 50 Hz

Voltage 400 V

Voltage tolerance ± 10 %

Unit

Starting current 139 A 142 A

Nominal running current

41.0 A 43.7 A

Max. running current

53.8 A 56.5 A

Recommended fuses 3 x 63 gL/gG 3 x 63 gL/gG

Fans

Phase 1~

Voltage 230 V

Max. runningcurrent

5.8 A

Compressor

Phase 3~

Voltage 400 V

Starting current 136.0 A

Nom. running current

17.6 A

Max. running current

24.0 A

Starting method Direct on line

Control circuit

Phase 1~

Voltage 230/ 24 V AC (supplied by factory installed transformers)

Recommended fuses Factory installed

Crankcase heater (E1/2 HC)

50 W 50 W

Pump

Phase __ 3~

Voltage __ 400.0 V

Max. running current

__ 2.7 A

Page 52: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–43

3

1

4

5

Nominal conditions The nominal conditions are as follows:

■ Entering/leaving evaporator water temperature 12.5/7°C

■ Ambient air temperature 35°C

■ Power input is total input: Compressor + control circuit + fan +pumps.

Operation range The operation range covers a leaving evaporator water temperature from 5°C to 20°C (pull down condition to 25°C).

Page 53: Chilere Daikin

General Outline ESIE-0302

1–44 Part 1 – System Outline

3

11

4

5

1.17 Electrical Specifications: EUWY*5-8KZW1

Electrical specifications

The table below contains the electrical specifications (1).

Model EUWYN5KZW1 EUWYP5KZW1 EUWYB5KZW1 EUWYN8KZW1 EUWYP8KZW1 EUWYB8KZW1

Power supply

Phase 3N~

Frequency 50 Hz

Voltage 400 V

Voltage tolerance ± 10 %

Unit

Starting current 62.2 A 63.5 A 97.9 A 99.2 A

Nominal running current cooling

7.7 A 9.0 A 13.6 A 14.9 A

Max. running current

11.2 A 12.5 A 16.9 A 18.2 A

Recommended fuses

3 x 20 gL/gG 3 x 20 gL/gG 3 x 25 gL/gG 3 x 25 gL/gG

Fans

Phase 1~

Voltage 230 V

Max. runningcurrent

2.2 A 2.9 A

Compressor

Phase 3~

Voltage 400 V

Starting current 60.0 A 95.0 A

Nom. running current cooling

5.5 A 10.7 A

Max. running

current

9.0 A 14.0 A

Starting method Direct on line

Control circuit

Phase 1~

Voltage 230 V

Recommended fuses

Factory installed

Pump

Phase __ 3~ __ 3~

Voltage __ 400.0 V __ 400.0 V

Max. running current

__ 1.3 A __ 1.3 A

Page 54: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–45

3

1

4

5

Nominal conditions The nominal conditions are as follows:

■ Entering/leaving evaporator water temperature 12.5/7°C

■ Ambient air temperature 35°C

■ Power input is total input: Compressor + control circuit + fans + pump.

Operation range The nominal operation range covers:

■ A leaving evaporator water temperature from 5°C (-5°C/-20°C for ZH/ZL option) to 20°C (pull down condition to 25°C).

■ A leaving condensor water temperature from 35°C to 50°C.

Page 55: Chilere Daikin

General Outline ESIE-0302

1–46 Part 1 – System Outline

3

11

4

5

1.18 Electrical Specifications: EUWY*10-12KZW1

Electrical specifications

The table below contains the electrical specifications (1).

Model EUWYN10KZW1 EUWYP10KZW1 EUWYB10KZW1 EUWYN12KZW1 EUWYP12KZW1 EUWYB12KZW1

Power supply

Phase 3N~

Frequency 50 Hz

Voltage 400 V

Voltage tolerance ± 10 %

Unit

Starting current 113 A 114 A 139 A 140 A

Nominal running current cooling

15.9 A 17.2 A 20.5 A 21.8 A

Max. running current

19.9 A 21.2 A 26.9 A 28.2 A

Recommended fuses

3 x 25 gL/gG 3 x 32 gL/gG 3 x 32 gL/gG 3 x 40 gL/gG

Fans

Phase 1~

Voltage 230 V

Max. runningcurrent

2.9 A

Compressor

Phase 3~

Voltage 400 V

Starting current 110.0 A 136.0 A

Nom. running current cooling

13.0 A 17.6 A

Max. running

current

17.0 A 24.0 A

Starting method Direct on line

Control circuit

Phase 1~

Voltage 230 V

Recommended fuses

Factory installed

Pump

Phase __ 3~ __ 3~

Voltage __ 400.0 V __ 400.0 V

Max. running current

__ 1.3 A __ 1.3 A

Page 56: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–47

3

1

4

5

Nominal conditions The nominal conditions are as follows:

■ Entering/leaving evaporator water temperature 12.5/7°C

■ Ambient air temperature 35°C

■ Power input is total input: Compressor + control circuit + fans + pump.

Operation range The nominal operation range covers:

■ A leaving evaporator water temperature from 5°C (-5°C/-20°C for ZH/ZL option) to 20°C (pull down condition to 25°C).

■ A leaving condensor water temperature from 35°C to 50°C.

Page 57: Chilere Daikin

General Outline ESIE-0302

1–48 Part 1 – System Outline

3

11

4

5

1.19 Electrical Specifications: EUWY*16-20KZW1

Electrical specifications

The table below contains the electrical specifications.

Model EUWYN16KZW1 EUWYP16KZW1 EUWYB16KZW1 EUWYN20KZW1 EUWYP20KZW1 EUWYB20KZW1

Power supply

Phase 3N~

Frequency 50 Hz

Voltage 400 V

Voltage tolerance ± 10 %

Unit

Starting current 97.9 A 99.9 A 113 A 115 A

Nominal running current cooling

27.2 A 29.2 A 31.8 A 33.8 A

Max. running current

33.8 A 35.8 A 39.8 A 41.8 A

Recommended fuses

3 x 40 gL/gG 3 x 50 gL/gG 3 x 50 gL/gG 3 x 50 gL/gG

Fans

Phase 1~

Voltage 230 V

Max. runningcurrent

5.8 A

Compressor

Phase 3~

Voltage 400 V

Starting current 95.0 A 110.0 A

Nom. running current cooling

10.7 A 13.0 A

Max. running current

14.0 A 17.0 A

Starting method Direct on line

Control circuit

Phase 1~

Voltage 230 V

Recommended fuses

Factory installed

Pump

Phase __ 3~ __ 3~

Voltage __ 400.0 V __ 400.0 V

Max. running current

__ 2.0 A __ 2.0 A

Page 58: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–49

3

1

4

5

Nominal conditions The nominal conditions are as follows:

■ Entering/leaving evaporator water temperature 12.5/7°C

■ Ambient air temperature 35°C

■ Power input is total input: Compressor + control circuit + fans + pump.

Operation range The nominal operation range covers:

■ A leaving evaporator water temperature from 5°C (-5°C/-20°C for ZH/ZL option) to 20°C (pull down condition to 25°C).

■ A leaving condensor water temperature from 35°C to 50°C.

Page 59: Chilere Daikin

General Outline ESIE-0302

1–50 Part 1 – System Outline

3

11

4

5

1.20 Electrical Specifications: EUWY*24KZW1

Electrical specifications

The table below contains the electrical specifications.

Model EUWYN24KZW1 EUWYP24KZW1 EUWYB24KZW1

Power supply

Phase 3N~

Frequency 50 Hz

Voltage 400 V

Voltage tolerance ± 10 %

Unit

Starting current 139 A 142 A

Nominal running current cooling

41.0 A 43.7 A

Max. running current

53.8 A 56.5 A

Recommended fuses 3 x 63 gL/gG 3 x 63 gL/gG

Fans

Phase 1~

Voltage 230 V

Max. runningcurrent

5.8 A

Compressor

Phase 3~

Voltage 400 V

Starting current 136.0 A

Nom. running current cooling

17.6 A

Max. running current

24.0 A

Starting method Direct on line

Control circuit

Phase 1~

Voltage 230 V

Recommended fuses Factory installed

Pump

Phase __ 3~

Voltage __ 400.0 V

Max. running current

__ 2.7 A

Page 60: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–51

3

1

4

5

Nominal conditions The nominal conditions are as follows:

■ Entering/leaving evaporator water temperature 12.5/7°C

■ Ambient air temperature 35°C

■ Power input is total input: Compressor + control circuit + fans + pump.

Operation range The nominal operation range covers:

■ A leaving evaporator water temperature from 5°C (-5°C/-20°C for ZH/ZL option) to 20°C (pull down condition to 25°C).

■ A leaving condensor water temperature from 35°C to 50°C.

Page 61: Chilere Daikin

General Outline ESIE-0302

1–52 Part 1 – System Outline

3

11

4

5

1.21 Outlook Drawing: EUWAC5FZW1

EUWAC5FZW1 The illustration below shows the outlook, the dimensions and the installation and service space of the unit (mm).

Components The table below lists the components.

Centre of gravity

Required space around the unit for service and air intake

Air

Air

No. Component No. Component

1 Evaporator 10 Power supply intake

2 Condensor 11 Switch box

3 Compressor 12 Digital display controller

4 Chilled water in (FBSP 1” ) 13 Field wiring intake

5 Chilled water out (FBSP 1” ) 14 Low-pressure gauge

6 Leaving water temperature sensor 15 High-pressure gauge

7 Entering water temperature sensor 16 Fan

8 Filter 17 Drain pipe (Ø25)

9 Expansion valve 18 Serviceplate

Page 62: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–53

3

1

4

5

1.22 Outlook Drawing: EUWAC8-10FZW1

EUWAC8-10FZW1 The illustration below shows the outlook, the dimensions and the installation and service space of the unit (mm).

Components The table below lists the components.

Centre of gravity

Required space around the unit for service and air intake

Item A B C

8HP 1122 1290 1125

10HP 1272 1395 1275

Air

Air

No. Component No. Component

1 Evaporator 10 Power supply intake

2 Condensor 11 Switch box

3 Compressor 12 Digital display controller

4 Chilled water in (FBSP 1” ) 13 Field wiring intake

5 Chilled water out (FBSP 1” ) 14 Low-pressure gauge

6 Leaving water temperature sensor 15 High-pressure gauge

7 Entering water temperature sensor 16 Fan

8 Filter 17 Drain pipe (Ø25)

9 Expansion valve 18 Serviceplate

Page 63: Chilere Daikin

General Outline ESIE-0302

1–54 Part 1 – System Outline

3

11

4

5

1.23 Outlook Drawing: EUWAN5-8KZW1

EUWAN5-8KZW1 The illustration below shows the outlook, the dimensions and the installation and service space of the unit (mm).

Components The table below lists the components.

FREE SPACE B1/B2

FREE SPACE MIN 3m

CAUTION FOR FAN

FIXATION4XØ15

SERVICE SPACE

No. Component No. Component

1 Air heat exchanger 10 Drain

2 Compressor 11 Air purge

3 Switch box 12 Pressure port

4 Main switch 13 Ball valve

5 Digital display controller 14 Water filter

6 Evaporator 15 Flow switch

7 Water IN connection: 1 1/4” BSP 16 High pressure gauge (optional)

8 Water OUT connection: 1 1/4” BSP 17 Low pressure gauge (optional)

9 Power supply intake

Page 64: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–55

3

1

4

5

1.24 Outlook Drawing: EUWAP5-8KZW1

EUWAP5-8KZW1 The illustration below shows the outlook, the dimensions and the installation and service space of the unit (mm).

Components The table below lists the components.

FREE SPACE B1/B2

FREE SPACE MIN 3m

CAUTION FOR FAN

FIXATION4XØ15

SERVICE SPACE

No. Component No. Component

1 Air heat exchanger 13 Expansion vessel

2 Compressor 14 Safety valve + pressure gauge

3 Switch box 15 Pressure port

4 Main switch 16 Ball valve

5 Pump Switch 17 Water filter

6 Digital display controller 18 Pump

7 Evaporator 19 Regulation valve

8 Water IN connection: 1 1/4” BSP 20 Flow switch

9 Water OUT connection: 1 1/4” BSP 21 High pressure gauge (optional)

10 Power supply intake 22 Low pressure gauge (optional)

11 Drain 23 Pump drain

12 Air purge

Page 65: Chilere Daikin

General Outline ESIE-0302

1–56 Part 1 – System Outline

3

11

4

5

1.25 Outlook Drawing: EUWAB5-8KZW1

EUWAB5-8KZW1 The illustration below shows the outlook, the dimensions and the installation and service space of the unit (mm).

Components The table below lists the components.

FREE SPACE B1/B2

FREE SPACE MIN 3m

CAUTION FOR FAN

FIXATION4XØ15

SERVICE SPACE

No. Component No. Component

1 Air heat exchanger 14 Safety valve + pressure gauge

2 Compressor 15 Pressure port

3 Switch box 16 Ball valve

4 Main switch 17 Water filter

5 Pump Switch 18 Pump

6 Digital display controller 19 Regulation valve

7 Evaporator 20 Flow switch

8 Water IN connection: 1 1/4” BSP 21 Buffer tank

9 Water OUT connection: 1 1/4” BSP 22 High pressure gauge (optional)

10 Power supply intake 23 Low pressure gauge (optional)

11 Drain 24 Pump drain

12 Air purge 25 Needle valve

13 Expansion vessel

Page 66: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–57

3

1

4

5

1.26 Outlook Drawing: EUWAN10-12KZW1

EUWAN10-12KZW1 The illustration below shows the outlook, the dimensions and the installation and service space of the unit (mm).

Components The table below lists the components.

FREE SPACE B1/B2

FREE SPACE MIN 3m

CAUTION FOR FAN

FIXATION4XØ15

SERVICE SPACE

No. Component No. Component

1 Air heat exchanger 10 Drain

2 Compressor 11 Air purge

3 Switch box 12 Pressure port

4 Main switch 13 Ball valve

5 Digital display controller 14 Water filter

6 Evaporator 15 Flow switch

7 Water IN connection: 1 1/4” BSP 16 High pressure gauge (optional)

8 Water OUT connection: 1 1/4” BSP 17 Low pressure gauge (optional)

9 Power supply intake

Page 67: Chilere Daikin

General Outline ESIE-0302

1–58 Part 1 – System Outline

3

11

4

5

1.27 Outlook Drawing: EUWAP10-12KZW1

EUWAP10-12KZW1 The illustration below shows the outlook, the dimensions and the installation and service space of the unit (mm).

Components The table below lists the components.

FREE SPACE B1/B2

FREE SPACE MIN 3m

CAUTION FOR FAN

FIXATION4XØ15

SERVICE SPACE

No. Component No. Component

1 Air heat exchanger 13 Expansion vessel

2 Compressor 14 Safety valve + pressure gauge

3 Switch box 15 Pressure port

4 Main switch 16 Ball valve

5 Pump Switch 17 Water filter

6 Digital display controller 18 Pump

7 Evaporator 19 Regulation valve

8 Water IN connection: 1 1/4” BSP 20 Flow switch

9 Water OUT connection: 1 1/4” BSP 21 High pressure gauge (optional)

10 Power supply intake 22 Low pressure gauge (optional)

11 Drain 23 Pump drain

12 Air purge

Page 68: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–59

3

1

4

5

1.28 Outlook Drawing: EUWAB10-12KZW1

EUWAB10-12KZW1 The illustration below shows the outlook, the dimensions and the installation and service space of the unit (mm).

Components The table below lists the components.

FREE SPACE B1/B2

FREE SPACE MIN 3m

CAUTION FOR FAN

FIXATION4XØ15

SERVICE SPACE

No. Component No. Component

1 Air heat exchanger 14 Safety valve + pressure gauge

2 Compressor 15 Pressure port

3 Switch box 16 Ball valve

4 Main switch 17 Water filter

5 Pump Switch 18 Pump

6 Digital display controller 19 Regulation valve

7 Evaporator 20 Flow switch

8 Water IN connection: 1 1/4” BSP 21 Buffer tank

9 Water OUT connection: 1 1/4” BSP 22 High pressure gauge (optional)

10 Power supply intake 23 Low pressure gauge (optional)

11 Drain 24 Pump drain

12 Air purge 25 Needle valve

13 Expansion vessel

Page 69: Chilere Daikin

General Outline ESIE-0302

1–60 Part 1 – System Outline

3

11

4

5

1.29 Outlook Drawing: EUWAN16KZW1

EUWAN16KZW1 The illustration below shows the outlook, the dimensions and the installation and service space of the unit (mm).

Components The table below lists the components.

FREE SPACE B1/B2

FREE SPACE MIN 3m

CAUTION FOR FAN

FIXATION4XØ15

CAUTION FOR FAN

SERVICE SPACE

No. Component No. Component

1 Air heat exchanger 10 Drain

2 Compressor 11 Air purge

3 Switch box 12 Pressure port

4 Main switch 13 Ball valve

5 Digital display controller 14 Water filter

6 Evaporator 15 Flow switch

7 Water IN connection: 2” BSP 16 High pressure gauge (optional)

8 Water OUT connection: 2” BSP 17 Low pressure gauge (optional)

9 Power supply intake

Page 70: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–61

3

1

4

5

1.30 Outlook Drawing: EUWAP16KZW1

EUWAP16KZW1 The illustration below shows the outlook, the dimensions and the installation and service space of the unit (mm).

Components The table below lists the components.

FREE SPACE B1/B2

FREE SPACE MIN 3m

CAUTION FOR FAN

FIXATION4XØ15

CAUTION FOR FAN

SERVICE SPACE

No. Component No. Component

1 Air heat exchanger 13 Expansion vessel

2 Compressor 14 Safety valve + pressure gauge

3 Switch box 15 Pressure port

4 Main switch 16 Ball valve

5 Pump Switch 17 Water filter

6 Digital display controller 18 Pump

7 Evaporator 19 Regulation valve

8 Water IN connection: 2” BSP 20 Flow switch

9 Water OUT connection: 2” BSP 21 High pressure gauge (optional)

10 Power supply intake 22 Low pressure gauge (optional)

11 Drain 23 Pump drain

12 Air purge

Page 71: Chilere Daikin

General Outline ESIE-0302

1–62 Part 1 – System Outline

3

11

4

5

1.31 Outlook Drawing: EUWAB16KZW1

EUWAB16KZW1 The illustration below shows the outlook, the dimensions and the installation and service space of the unit (mm).

Components The table below lists the components

FREE SPACE B1/B2

FREE SPACE MIN 3m

CAUTION FOR FAN

FIXATION4XØ15

CAUTION FOR FAN

SERVICE SPACE

No. Component No. Component

1 Air heat exchanger 13 Expansion vessel

2 Compressor 14 Safety valve + pressure gauge

3 Switch box 15 Pressure port

4 Main switch 16 Ball valve

5 Pump Switch 17 Water filter

6 Digital display controller 18 Pump

7 Evaporator 19 Regulation valve

8 Water IN connection: 2” BSP 20 Flow switch

9 Water OUT connection: 2” BSP 21 Buffer tank

10 Power supply intake 22 High pressure gauge (optional)

11 Drain 23 Low pressure gauge (optional)

12 Air purge 24 Pump drain

Page 72: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–63

3

1

4

5

1.32 Outlook Drawing: EUWAN20-24KZW1

EUWAN20-24KZW1 The illustration below shows the outlook, the dimensions and the installation and service space of the unit (mm).

Components The table below lists the components.

FREE SPACE B1/B2

FREE SPACE MIN 3m

CAUTION FOR FAN

FIXATION4XØ15

CAUTION FOR FAN

SERVICE SPACE

No. Component No. Component

1 Air heat exchanger 10 Drain

2 Compressor 11 Air purge

3 Switch box 12 Pressure port

4 Main switch 13 Ball valve

5 Digital display controller 14 Water filter

6 Evaporator 15 Flow switch

7 Water IN connection: 2” BSP 16 High pressure gauge (optional)

8 Water OUT connection: 2” BSP 17 Low pressure gauge (optional)

9 Power supply intake

Page 73: Chilere Daikin

General Outline ESIE-0302

1–64 Part 1 – System Outline

3

11

4

5

1.33 Outlook Drawing: EUWAP20-24KZW1

EUWAP20-24KZW1 The illustration below shows the outlook, the dimensions and the installation and service space of the unit (mm).

Components The table below lists the components.

FREE SPACE B1/B2

FREE SPACE MIN 3m

CAUTION FOR FAN

FIXATION4XØ15

CAUTION FOR FAN

SERVICE SPACE

No. Component No. Component

1 Air heat exchanger 13 Expansion vessel

2 Compressor 14 Safety valve + pressure gauge

3 Switch box 15 Pressure port

4 Main switch 16 Ball valve

5 Pump switch 17 Water filter

6 Digital display controller 18 Pump

7 Evaporator 19 Regulation valve

8 Water IN connection: 2” BSP 20 Flow switch

9 Water OUT connection: 2” BSP 21 High pressure gauge (optional)

10 Power supply intake 22 Low pressure gauge (optional)

11 Drain 23 Pump drain

12 Air purge

Page 74: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–65

3

1

4

5

1.34 Outlook Drawing: EUWAB20-24KZW1

EUWAB20-24KZW1 The illustration below shows the outlook, the dimensions and the installation and service space of the unit (mm).

Components The table below lists the components.

FREE SPACE B1/B2

FREE SPACE MIN 3m

CAUTION FOR FAN

FIXATION4XØ15

CAUTION FOR FAN

SERVICE SPACE

No. Component No. Component

1 Air heat exchanger 13 Expansion vessel

2 Compressor 14 Safety valve + pressure gauge

3 Switch box 15 Pressure port

4 Main switch 16 Ball valve

5 Pump switch 17 Water filter

6 Digital display controller 18 Pump

7 Evaporator 19 Regulation valve

8 Water IN connection: 2” BSP 20 Flow switch

9 Water OUT connection: 2” BSP 21 Buffer tank

10 Power supply intake 22 High pressure gauge (optional)

11 Drain 23 Low pressure gauge (optional)

12 Air purge 24 Pump drain

Page 75: Chilere Daikin

General Outline ESIE-0302

1–66 Part 1 – System Outline

3

11

4

5

1.35 Outlook Drawing: EUWYN5-8KZW1

EUWYN5-8KZW1 The illustration below shows the outlook, the dimensions and the installation and service space of the unit (mm).

Components The table below lists the components.

���

FREE SPACE B1/B2

FREE SPACE MIN 3m

CAUTION FOR FAN

FIXATION4XØ15

SERVICE SPACE

No. Component No. Component

1 Air heat exchanger 11 Air purge

2 Compressor 12 Pressure port

3 Switch box 13 Ball valve

4 Main switch 14 Water filter

5 Digital display controller 15 Flow switch

6 Evaporator 16 High pressure gauge (optional)

7 Water IN connection: 1 1/4” BSP 17 Low pressure gauge (optional)

8 Water OUT connection: 1 1/4” BSP 18 4-way valve

9 Power supply intake 19 Accumulator

10 Drain 20 Liquid receiver

Page 76: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–67

3

1

4

5

1.36 Outlook Drawing: EUWYP5-8KZW1

EUWYP5-8KZW1 The illustration below shows the outlook, the dimensions and the installation and service space of the unit (mm).

Components The table below lists the components.

������

FREE SPACE B1/B2

FREE SPACE MIN 3m

CAUTION FOR FAN

FIXATION4XØ15

SERVICE SPACE

No. Component No. Component

1 Air heat exchanger 14 Safety valve + pressure gauge

2 Compressor 15 Pressure port

3 Switch box 16 Ball valve

4 Main switch 17 Water filter

5 Pump Switch 18 Pump

6 Digital display controller 19 Regulation valve

7 Evaporator 20 Flow switch

8 Water IN connection: 1 1/4” BSP 21 High pressure gauge (optional)

9 Water OUT connection: 1 1/4” BSP 22 Low pressure gauge (optional)

10 Power supply intake 23 Pump drain

11 Drain 24 4-way valve

12 Air purge 25 Accumulator

13 Expansion vessel 26 Liquid receiver

Page 77: Chilere Daikin

General Outline ESIE-0302

1–68 Part 1 – System Outline

3

11

4

5

1.37 Outlook Drawing: EUWYB5-8KZW1

EUWYB5-8KZW1 The illustration below shows the outlook, the dimensions and the installation and service space of the unit (mm).

Components The table below lists the components.

����

FREE SPACE B1/B2

FREE SPACE MIN 3m

CAUTION FOR FAN

FIXATION 4XØ15

SERVICE SPACE

No. Component No. Component

1 Air heat exchanger 15 Pressure port

2 Compressor 16 Ball valve

3 Switch box 17 Water filter

4 Main switch 18 Pump

5 Pump Switch 19 Regulation valve

6 Digital display controller 20 Flow switch

7 Evaporator 21 Buffer tank

8 Water IN connection: 1 1/4” BSP 22 High pressure gauge (optional)

9 Water OUT connection: 1 1/4” BSP 23 Low pressure gauge (optional)

10 Power supply intake 24 Pump drain

11 Drain 25 Needle valve

12 Air purge 26 4-way valve

13 Expansion vessel 27 Accumulator

14 Safety valve + pressure gauge 28 Liquid receiver

Page 78: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–69

3

1

4

5

1.38 Outlook Drawing: EUWYN10-12KZW1

EUWYN10-12KZW1 The illustration below shows the outlook, the dimensions and the installation and service space of the unit (mm).

Components The table below lists the components.

��

FREE SPACE B1/B2

FREE SPACE MIN 3m

CAUTION FOR FAN

FIXATION4XØ15

SERVICE SPACE

No. Component No. Component

1 Air heat exchanger 11 Air purge

2 Compressor 12 Pressure port

3 Switch box 13 Ball valve

4 Main switch 14 Water filter

5 Digital display controller 15 Flow switch

6 Evaporator 16 High pressure gauge (optional)

7 Water IN connection: 1 1/4” BSP 17 Low pressure gauge (optional)

8 Water OUT connection: 1 1/4” BSP 18 4-way valve

9 Power supply intake 19 Accumulator

10 Drain 20 Liquid receiver

Page 79: Chilere Daikin

General Outline ESIE-0302

1–70 Part 1 – System Outline

3

11

4

5

1.39 Outlook Drawing: EUWYP10-12KZW1

EUWYP10-12KZW1 The illustration below shows the outlook, the dimensions and the installation and service space of the unit (mm).

Components The table below lists the components.

����

FREE SPACE B1/B2

FREE SPACE MIN 3m

CAUTION FOR FAN

FIXATION4XØ15

SERVICE SPACE

No. Component No. Component

1 Air heat exchanger 14 Safety valve + pressure gauge

2 Compressor 15 Pressure port

3 Switch box 16 Ball valve

4 Main switch 17 Water filter

5 Pump Switch 18 Pump

6 Digital display controller 19 Regulation valve

7 Evaporator 20 Flow switch

8 Water IN connection: 1 1/4” BSP 21 High pressure gauge (optional)

9 Water OUT connection: 1 1/4” BSP 22 Low pressure gauge (optional)

10 Power supply intake 23 Pump drain

11 Drain 24 4-way valve

12 Air purge 25 Accumulator

13 Expansion vessel 26 Liquid receiver

Page 80: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–71

3

1

4

5

1.40 Outlook Drawing: EUWYB10-12KZW1

EUWYB10-12KZW1 The illustration below shows the outlook, the dimensions and the installation and service space of the unit (mm).

Components The table below lists the components.

����

FREE SPACE B1/B2

FREE SPACE MIN 3m

CAUTION FOR FAN

SERVICE SPACE

FIXATION4XØ15

No. Component No. Component

1 Air heat exchanger 15 Pressure port

2 Compressor 16 Ball valve

3 Switch box 17 Water filter

4 Main switch 18 Pump

5 Pump Switch 19 Regulation valve

6 Digital display controller 20 Flow switch

7 Evaporator 21 Buffer tank

8 Water IN connection: 1 1/4” BSP 22 High pressure gauge (optional)

9 Water OUT connection: 1 1/4” BSP 23 Low pressure gauge (optional)

10 Power supply intake 24 Pump drain

11 Drain 25 Needle valve

12 Air purge 26 4-way valve

13 Expansion vessel 27 Accumulator

14 Safety valve + pressure gauge 28 Liquid receiver

Page 81: Chilere Daikin

General Outline ESIE-0302

1–72 Part 1 – System Outline

3

11

4

5

1.41 Outlook Drawing: EUWYN16KZW1

EUWYN16KZW1 The illustration below shows the outlook, the dimensions and the installation and service space of the unit (mm).

Components The table below lists the components.

����

FREE SPACE B1/B2

FREE SPACE MIN 3m

CAUTION FOR FAN CAUTION FOR FAN

SERVICE SPACE

FIXATION4XØ15

No. Component No. Component

1 Air heat exchanger 11 Air purge

2 Compressor 12 Pressure port

3 Switch box 13 Ball valve

4 Main switch 14 Water filter

5 Digital display controller 15 Flow switch

6 Evaporator 16 High pressure gauge (optional)

7 Water IN connection: 2” BSP 17 Low pressure gauge (optional)

8 Water OUT connection: 2” BSP 18 4-way valve

9 Power supply intake 19 Accumulator

10 Drain 20 Liquid receiver

Page 82: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–73

3

1

4

5

1.42 Outlook Drawing: EUWYP16KZW1

EUWYP16KZW1 The illustration below shows the outlook, the dimensions and the installation and service space of the unit (mm).

Components The table below lists the components.

����

FREE SPACE B1/B2

FREE SPACE MIN 3m

CAUTION FOR FAN

FIXATION4XØ15

CAUTION FOR FAN

SERVICE SPACE

No. Component No. Component

1 Air heat exchanger 14 Safety valve + pressure gauge

2 Compressor 15 Pressure port

3 Switch box 16 Ball valve

4 Main switch 17 Water filter

5 Pump Switch 18 Pump

6 Digital display controller 19 Regulation valve

7 Evaporator 20 Flow switch

8 Water IN connection: 2” BSP 21 High pressure gauge (optional)

9 Water OUT connection: 2” BSP 22 Low pressure gauge (optional)

10 Power supply intake 23 Pump drain

11 Drain 24 4-way valve

12 Air purge 25 Accumulator

13 Expansion vessel 26 Liquid receiver

Page 83: Chilere Daikin

General Outline ESIE-0302

1–74 Part 1 – System Outline

3

11

4

5

1.43 Outlook Drawing: EUWYB16KZW1

EUWYB16KZW1 The illustration below shows the outlook, the dimensions and the installation and service space of the unit (mm).

Components The table below lists the components

�����

FREE SPACE B1/B2

FREE SPACE MIN 3m

CAUTION FOR FAN

FIXATION4XØ15

CAUTION FOR FAN

SERVICE SPACE

No. Component No. Component

1 Air heat exchanger 15 Pressure port

2 Compressor 16 Ball valve

3 Switch box 17 Water filter

4 Main switch 18 Pump

5 Pump Switch 19 Regulation valve

6 Digital display controller 20 Flow switch

7 Evaporator 21 Buffer tank

8 Water IN connection: 2” BSP 22 High pressure gauge (optional)

9 Water OUT connection: 2” BSP 23 Low pressure gauge (optional)

10 Power supply intake 24 Pump drain

11 Drain 25 4-way valve

12 Air purge 26 Accumulator

13 Expansion vessel 27 Liquid receiver

14 Safety valve + pressure gauge

Page 84: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–75

3

1

4

5

1.44 Outlook Drawing: EUWYN20-24KZW1

EUWYN20-24KZW1 The illustration below shows the outlook, the dimensions and the installation and service space of the unit (mm).

Components The table below lists the components.

������

FREE SPACE B1/B2

FREE SPACE MIN 3m

CAUTION FOR FAN

FIXATION4XØ15

CAUTION FOR FAN

SERVICE SPACE

No. Component No. Component

1 Air heat exchanger 11 Air purge

2 Compressor 12 Pressure port

3 Switch box 13 Ball valve

4 Main switch 14 Water filter

5 Digital display controller 15 Flow switch

6 Evaporator 16 High pressure gauge (optional)

7 Water IN connection: 2” BSP 17 Low pressure gauge (optional)

8 Water OUT connection: 2” BSP 18 4-way valve

9 Power supply intake 19 Accumulator

10 Drain 20 Liquid receiver

Page 85: Chilere Daikin

General Outline ESIE-0302

1–76 Part 1 – System Outline

3

11

4

5

1.45 Outlook Drawing: EUWYP20-24KZW1

EUWYP20-24KZW1 The illustration below shows the outlook, the dimensions and the installation and service space of the unit (mm).

Components The table below lists the components.

����

FREE SPACE B1/B2

FREE SPACE MIN 3m

CAUTION FOR FAN

FIXATION4XØ15

CAUTION FOR FAN

SERVICE SPACE

No. Component No. Component

1 Air heat exchanger 14 Safety valve + pressure gauge

2 Compressor 15 Pressure port

3 Switch box 16 Ball valve

4 Main switch 17 Water filter

5 Pump Switch 18 Pump

6 Digital display controller 19 Regulation valve

7 Evaporator 20 Flow switch

8 Water IN connection: 2” BSP 21 High pressure gauge (optional)

9 Water OUT connection: 2” BSP 22 Low pressure gauge (optional)

10 Power supply intake 23 Pump drain

11 Drain 24 4-way valve

12 Air purge 25 Accumulator

13 Expansion vessel 26 Liquid receiver

Page 86: Chilere Daikin

ESIE-0302 General Outline

Part 1 – System Outline 1–77

3

1

4

5

1.46 Outlook Drawing: EUWYB20-24KZW1

EUWYB20-24KZW1 The illustration below shows the outlook, the dimensions and the installation and service space of the unit (mm).

Components The table below lists the components.

����

FREE SPACE B1/B2

FREE SPACE MIN 3m

CAUTION FOR FAN

FIXATION4XØ15

CAUTION FOR FAN

SERVICE SPACE

No. Component No. Component

1 Air heat exchanger 15 Pressure port

2 Compressor 16 Ball valve

3 Switch box 17 Water filter

4 Main switch 18 Pump

5 Pump Switch 19 Regulation valve

6 Digital display controller 20 Flow switch

7 Evaporator 21 Buffer tank

8 Water IN connection: 2” BSP 22 High pressure gauge (optional)

9 Water OUT connection: 2” BSP 23 Low pressure gauge (optional)

10 Power supply intake 24 Pump drain

11 Drain 25 4-way valve

12 Air purge 26 Accumulator

13 Expansion vessel 27 Liquid receiver

14 Safety valve + pressure gauge

Page 87: Chilere Daikin

General Outline ESIE-0302

1–78 Part 1 – System Outline