Mike Smid - TEC Vice President – Commercial Sales
Chilled Water Optimization Class
Agenda
• Objective • Weather • Determinants of Chiller Energy Consumption • SPLV vs. IPLV • The “Life Cycle Point” • Questions
Objective Design and implement a chilled water system that reliably delivers real and verifiable energy savings, running under the operating conditions encountered in everyday life.
Three Pillars: System Performance
Optimize total energy (not sub components)
System Reliability Under normal operating conditions Under stress
Verifiable Energy Savings Accurate, appropriate metrics
Agenda
• Objective • Weather • Determinants of Chiller Energy
Consumption • SPLV vs. IPLV • The “Life Cycle Point” • Questions
Chicago Weather 24 x 7 73.8% of hours have less than 70 F entering condenser water
0
10
20
30
40
50
60
70
80
90
0
100
200
300
400
500
600
700
800
900
95-90 85-80 75-70 65-60 55-50 45-40 <40
Ent.
Con
d W
ater
(F)
Hou
rs o
f Ope
ratio
n
Dry Bulb (F)
Ent Cond 80-85 F 75-80 F 70-75 F <70 F
Chicago Weather 12 x 5 73.3% of hours have less than 70 F entering condenser water
0
10
20
30
40
50
60
70
80
90
0
200
400
600
800
1000
1200
1400
95-90 85-80 75-70 65-60 55-50 45-40 <40
Ent.
Con
d W
ater
(F)
Hou
rs o
f Ope
ratio
n
Dry Bulb (F)
Ent Cond 80-85 F 75-80 F 70-75 F <70 F
Charlotte Weather 24 x 7
68% of hours have less than 70.4 F entering condenser water
7
Charlotte Weather 12 x 5
58% of hours have less than 70 F entering condenser water
8
Cooling Tower
• As the ambient wet bulb drops colder condenser water can be delivered to the chiller(s).
• VFD’s on centrifugal chillers track the weather.
Agenda
• Objective • Weather • Determinants of Chiller Energy
Consumption • SPLV vs. IPLV • The “Life Cycle Point” • Questions
Like pumps, chiller energy consumption is a function of mass flow and differential pressure.
kW = Tons × Lift
Compressor Input kW ~
Mass Flow X Lift
Load
Chiller
Cooling Tower
Compressor/Cycle Efficiency
Chiller Efficiency
For refrigerant to condense, it must be warmer than leaving condenser water.
95 F + 2F approach = 97F
To boil, refrigerant must be colder than leaving chilled
water.
44F – 2F approach = 42F
Refrigerant temperatures are based on leaving water temperatures!
54F 44F
85F 95F
Compressor Work (Lift)
42 F / 40 PSI 97 F / 120 PSI 82F / 90 PSI
SAT. LIQUID
SAT. VAPOR
Refrigerant Effect (Capacity)
Heat Rejection
Enthalpy
SCT
Reduced Lift
Pres
sure
42
82
97
SST
Lower Lift = Less Work = Lower kW
Compressor Work (Lift)
VFD Driven Chillers take advantage of lift and / or load reduction to reduce energy consumption.
VFD Driven Chillers take advantage of lift and / or load reduction to reduce energy consumption.
Mechanical unloading
Variable speed unloading
Chiller Efficiency
0 10 20 30 40 50 60 70 80 90
100
14% 20% 25% 31% 37% 43% 49% 56% 62% 68% 75% 81% 87% Total Building Load %
Ope
ratin
g H
ours
Individual Chiller Load %
Design Day 85°F (29.4°C) ECWT
Min Tower 55°F (12.8°C) ECWT
92% 100%
Two Chiller Plant Staging
Distribution of ton-hours
VFD Driven Chillers take advantage of lift and/or load reduction to reduce energy consumption.
VFD Driven Chillers take advantage of lift and/or load reduction to reduce energy consumption.
One chiller at 100% load
Two chillers at 100% load each
Two Chiller Plant Efficiency
Agenda
• Objective • Weather • Determinants of Chiller Energy
Consumption • SPLV vs. IPLV • The “Life Cycle Point” • Questions
Agenda
• Objective • Weather • Determinants of Chiller Energy
Consumption • SPLV vs. IPLV • The “Life Cycle Point” • Questions
19
Performance Metrics Full Load, IPLV
AHRI 550/590 IPLV
% Load Weight Condition
100% 1% 44 F / 85 F
75% 42% 44F / 75 F
50% 45% 44F / 65F
25% 12% 44F / 65F
ARI 550/590 section D2 states:
“The equation (IPLV) was derived to provide a representation of the average part load efficiency for a single chiller only. …”
Full Load has two components: 100% load and design conditions.
IPLV is a weighted average of four specific operating points.
Chicago Weather 24 x 7 73.8% of hours have less than 70 F entering condenser water
0
10
20
30
40
50
60
70
80
90
0
100
200
300
400
500
600
700
800
900
95-90 85-80 75-70 65-60 55-50 45-40 <40
Ent.
Con
d W
ater
(F)
Hou
rs o
f Ope
ratio
n
Dry Bulb (F)
Ent Cond 80-85 F 75-80 F 70-75 F <70 F
21
Performance Metrics System based metrics – SPLV (System Part Load Value)
ARI 550/590 section D2 states:
“The equation (IPLV) was derived to provide a representation of the average part load efficiency for a single chiller only. However, it is best to use a comprehensive analysis that reflects the actual weather data, building load characteristics, operational hours, economizer capabilities and energy drawn by auxiliaries such as pumps and cooling towers, when calculating the chiller and system efficiency. This becomes increasingly important with multiple chiller systems because individual chillers operating within multiple chiller systems are more heavily loaded than single chillers within single chiller systems.”
Actual Local Weather Load Profile Operating Hours Economizer Pump, Tower Energy Chiller Staging
22
Chiller Staging Chicago Office Building
87.5%
62.5%
37.5%
100% Bin
75% Bin
50% Bin
25% Bin
6
1 3
4
5
3 x 400 Ton Chillers: CH-1 (black), CH-2 (Yellow), CH-3 (Blue) M
inim
um B
uild
ing
Load
2
23
Performance Metrics 100% Building Load
Design Day Weather Fully Leased Fully Occupied Full Solar Load Full Equipment and Lighting Load Full Ventilation Rates
< 1% of the operating hours – OR MAYBE NEVER
1
1
Are the chillers sized to meet the building load exactly … or were they maybe oversized … just a little.
24
Performance Metrics 100% Chiller Load
Design Leaving Chilled Water Design Entering Condenser Water No Low Delta T Syndrome! No safety factors when chillers sized Tubes fouled to AHRI selection level Assumes Chillers not oversized !!!
• Far more ton-hours occur at points 3 and 5 than at point 1
• Variable speed chillers have better 100% load efficiency at points 3 and 5 due to lower lift.
3 5 1
1
3333
5
5
55
85F 70F 60F
25
Performance Metrics SPLV vs. IPLV
Weighting significantly different. SPLV reflects multiple chiller plant staging SPLV reflects local condenser water temperatures
26
Performance Metric IPLV weighting issue (multiple chillers)
IPLV (kW/Ton) Single Chiller Plant
Actual Plant
Chiller A Chiller B Chiller C 100% 0.640 0.536 0.577 75% 0.420 0.399 0.390 50% 0.280 0.291 0.267 25% 0.260 0.341 0.301 IPLV 0.325 0.337 0.314 SPLV 0.399 0.373 0.362
2,000 Ton Hotel, with (4) 500 Ton chillers Worldwide Study
75% Load “The Life Cycle Point”
75% Load “The Life Cycle Point”
2,000 Ton Hotel, with (4) 500 Ton chillers Worldwide Study
600 Ton Office, with (2) 300 Ton chillers
Carrier Worldwide Study
75% Load “The Life Cycle Point”
30
Back Up
31
System Based Decisions Chiller Staging
Component Calculation
(1) Chiller at “full load”* 0.575
(2) Chillers at 50% load* 0.295
Delta 0.280
Capacity (tons) 300
Savings (per hour) 84 kW
Compare efficiency at the same temperatures. Compare the AHRI tolerance at the load points Compare the pump power consumption Consider the minimum evaporator flow rate
System Calculation (1) Chiller at 100% load, 65 F Condenser Water, no AHRI tolerance 0.338 x 1.05% = 0.355
(2) Chillers at 50% load, 65 F Condenser Water, no AHRI tolerance 0.295 x 1.10% = 0.325
Capacity (tons) 300
Chiller Savings 9 kW
Condenser pump power (750 gpm x 30 ft wg) 6.8 kW
Evaporator pump power (600 gpm x 20 ft wg)* 3.6 kW
Extra pump power 10.4 kW
Net Savings (per hour) -1.4 kW
* Constant flow application, use minimum flow rate calculation for variable flow systems.
*Submittal data at 100% and 50% load is often based on two different condenser water temperatures leading to unintended calculation error.
4 Steps to Optimize Chiller staging: 4
32
Questions?