Switchgear Systems Ltd. Tel: 01788 577399 Fax: 01788 577899 E-mail: [email protected] Automatic transfer switch panels, or ATS panels, are a development of the traditional manual changeover switches. All units comply with BSEN 60947-6-1 and are designed to fulfill certain requirements for fire safety as layed down in BS9999. All changeover solutions should be chosen to suit the load of the facility; the KVA rating of a generator is not a reliable indicator for rating an ATS panel, the primary mains supply and the power requirements of the installation should always be considered when selecting an ATS panel. Choosing an Automatic Transfer Switch These ATS panels are designed specifically for advanced mains to generator applications where much more functionality is required than that which the M2B system offers. Fitted with a Deep Sea Electronics digital controller they are highly functional and adjustable; they are designed specifically for use with mains to generator systems and require a small but constant DC supply, normally taken from the battery on the GenSet. M2G - Mains To Generator These ATS units are a budget mains to generator model and include a warm up and cool down timer as well as a volt free start contact on mains failure to signal the GenSet to start the generator. They do not rely on a DC power supply to operate so will function equally well as a mains to mains system. This versatility also makes it ideal for integrating into systems with existing ATS panels which are already starting the generator, as the warm up timer prevents it from closing to load until the generator is fully up and running. M2B - Mains To Backup These ATS units are used where the backup supply is always assumed to be available. Usually this is because the secondary supply is coming from a separate transformer to the primary supply; or, for fire safety purposes, from two breakers from the same supply with alternative cable routing. They can however also be used when the secondary supply is coming from a generator where the GenSet is handling all of the supply monitoring, the start up of the generator and is able to isolate it from the ATS panel until the supply is stable. M2M - Mains To Mains We use two methods of switching in our ATS panels; dual interlocked contactors and motorised changeover switches. Both are electronically and mechanically interlocked to conform to British and European standard BSEN 60947-6-1. Typically we use contactors up to 160A and motorised changeover switches at 200A and above; this is for a number of reasons, including reliability, but the main reason is cost. We can provide motorised changeover switches at lower ratings and contactors at higher ratings as well as interlocked MCCB and ACB solutions for special requirements. Switching Devices
Transcript

Switchgear Systems Ltd. Tel: 01788 577399 Fax: 01788 577899 E-mail: [email protected]

Automatic transfer switch panels, or ATS panels, are a development of the traditional manual changeover switches. All units comply with BSEN 60947-6-1 and are designed to fulfill certain requirements for fire safety as layed down in BS9999.All changeover solutions should be chosen to suit the load of the facility; the KVA rating of a generator is nota reliable indicator for rating an ATS panel, the primary mains supply and the power requirements of theinstallation should always be considered when selecting an ATS panel.

Choosing an Automatic Transfer Switch

These ATS panels are designed specifically for advanced mains to generator applications where muchmore functionality is required than that which the M2B system offers. Fitted with a Deep Sea Electronicsdigital controller they are highly functional and adjustable; they are designed specifically for use withmains to generator systems and require a small but constant DC supply, normally taken from the batteryon the GenSet.

M2G - Mains To Generator

These ATS units are a budget mains to generator model and include a warm up and cool down timer aswell as a volt free start contact on mains failure to signal the GenSet to start the generator. They do notrely on a DC power supply to operate so will function equally well as a mains to mains system. This versatility also makes it ideal for integrating into systems with existing ATS panels which are already starting the generator, as the warm up timer prevents it from closing to load until the generator is fully up and running.

M2B - Mains To Backup

These ATS units are used where the backup supply is always assumed to be available. Usually this isbecause the secondary supply is coming from a separate transformer to the primary supply; or, for fire safety purposes, from two breakers from the same supply with alternative cable routing. They can however also be used when the secondary supply is coming from a generator where the GenSet is handling all of the supply monitoring, the start up of the generator and is able to isolate it from the ATS panel until the supply is stable.

M2M - Mains To Mains

We use two methods of switching in our ATS panels; dual interlocked contactors and motorised changeoverswitches. Both are electronically and mechanically interlocked to conform to British and European standardBSEN 60947-6-1. Typically we use contactors up to 160A and motorised changeover switches at 200A and above; this is for anumber of reasons, including reliability, but the main reason is cost. We can provide motorised changeoverswitches at lower ratings and contactors at higher ratings as well as interlocked MCCB and ACB solutionsfor special requirements.

Switching Devices

Switchgear Systems Ltd. Tel: 01788 577399 Fax: 01788 577899 E-mail: [email protected]

Choosing an Automatic Transfer Switch

ATS Panel Remote Indication Units

The ATS panels are supplied with volt free remote indication terminals which can be used to inform remotesystems, such as a BMS, of the ATS panel’s status. We supply a range of remote indication boxes whichcan be powered from these terminals.

Version

Reference Suffix

Supply Type Mains To Mains Mains To Backup Mains To Generator

Standard Advanced Standard Advanced

M2M CS M2M CA M2M SS M2M SAM2B CS M2B SS

M2G C330&

M2G C331M2G S331

Phase failure and undervoltage monitoring ofprimary supply

Interlocked Contactor switching

Motorised Changeover switching

Manual switching override

Supply available indication

Supply in use indicationAdjustable time delay between switching

Advanced interface for GenSet control

Requires constant DC supply to operate

Test facilities & supply override

For dedicated firefighting lifts as detailedin BS9999

For Life Safety application to BS8519:2010 see ATS Bypass switches pages 22-23

Generator start signal timer and cool down timer

Suitable for standard Remote Indication Unit

Suitable for advanced Remote Indication Unit

AW D

Dimensions (mm)*see inner front cover for reference diagram

H BOType Ordering

Reference

135 160 83 602.5 cageRBOX135 160 83 602.5 cageRBOXADV

160 220 85 722.5 cageRBOX/SF160 220 85 722.5 cageRBOXADV/SF

StandardAdvanced

StandardAdvanced

Halogen free thermoplastic enclosure - IP55

Flush mounted satin finish stainless steel enclosure - IP55

Switchgear Systems Ltd. Tel: 01788 577399 Fax: 01788 577899 E-mail: [email protected]

Mains To Mains ATS Panels

500500600

400400

400

200200200

100100120

600 400 200 120

AW DH BO

40A63A80A

100A

ATS 4/2 M2MCS

OrderingReferenceStandard

ATS 6/2 M2MCSATS 8/2 M2MCSATS 10/2 M2MCS

35 cage25 cage25 cageATS 4/2 M2MCA

OrderingReferenceAdvanced

ATS 6/2 M2MCAATS 8/2 M2MCAATS 10/2 M2MCA

2 Pole for single phase supplies - Contactor Switching

35 cage

600600700

400400

500

200200200

120120150

700 500 200 150

40A63A80A

100A

ATS 4/4 M2MCSATS 6/4 M2MCSATS 8/4 M2MCSATS 10/4 M2MCS

35 cage25 cage25 cageATS 4/4 M2MCA

ATS 6/4 M2MCAATS 8/4 M2MCAATS 10/4 M2MCA

4 Pole for three phase supplies - Contactor Switching

35 cage700 500 200 150800 600 250 180

125A160A

ATS 12/4 M2MCSATS 16/4 M2MCS

70 cageATS 12/4 M2MCAATS 16/4 M2MCA 70 cage

800800800

600600

600

250300300

300300300

200A250A400A

ATS 20/4 M2MSSATS 25/4 M2MSSATS 40/4 M2MSS 30

2524ATS 20/4 M2MSA

ATS 25/4 M2MSAATS 40/4 M2MSA

4 Pole for three phase supplies - Motorised Switching with manual override

M10M10M8

AC1Rating

380-440V

AC3Rating

380-440V

40A 11kW40A 11kW40A 11kW80A 22kW

80A116A

45kW55kW

20A 11kW40A 22kW53A 30kW53A 30kW

200A250A400A

Dimensions (mm)*see inner front cover for reference diagram

80kW100kW150kW

These models are suited to applications where both supplies can beassumed to be normally available.

• Designed in compliance with BSEN 60947-6-1• For life safety requirements as detailed in BSEN 8519:2010 see page 20-21 for ATS Bypass• Electrical and mechanical interlocks between supplies• All phases on primary supply monitored to protect against total power loss, phase failure, incorrect phase sequence and under/over voltage• ‘Auto/Test’ switch• Adjustable over and under voltage trip delay• Adjustable over and under voltage limits• External LED indicators and volt free remote terminals to show the health of the supplies• (Advanced only) Adjustable switching delays between the opening of one contactor and the closing of the other• (Advanced only) External LED indicators and volt free remote terminals to show the supply in use• (Advanced only) Designed to be used for dedicated firefighting lifts as detailed in BS9999• Ingress protection IP55

Switchgear Systems Ltd. Tel: 01788 577399 Fax: 01788 577899 E-mail: [email protected]

Mains To Backup ATS Panels

These models are designed to be used in conjunction with a backup generator, but willalso operate where both supplies are coming from the mains.

• Designed in compliance with BSEN 60947-6-1• For life safety requirements as detailed in BSEN 8519:2010 see page 20-21 for ATS Bypass• Electrical and mechanical interlocks between supplies• All phases on primary supply monitored to protect against total power loss, phase failure, incorrect phase sequence and under/over voltage• ‘Auto/Off load generator test/On load generator test’ switch• Adjustable over and under voltage trip delay• Adjustable over and under voltage limits• Adjustable ‘warm up’ timer on the secondary supply for generators• Adjustable ‘cool down’ timer on the start signal for generators • Volt free mains failure indication terminals for signalling a GenSet• External LED indicators and volt free remote terminals to show the health of the supplies• External LED indicators and volt free remote terminals to show the supply in use• Ingress protection IP55

500500600

400400

400

200200200

100100120

600 400 200 120

AW DH BO

40A63A80A

100A35 cage25 cage25 cageATS 4/2 M2BC

OrderingReference

ATS 6/2 M2BCATS 8/2 M2BCATS 10/2 M2BC

2 Pole for single phase supplies - Contactor Switching

35 cage

600600700

400400

500

200200200

120120150

700 500 200 150

40A63A80A

100A35 cage25 cage25 cageATS 4/4 M2BC

ATS 6/4 M2BCATS 8/4 M2BCATS 10/4 M2BC

4 Pole for three phase supplies - Contactor Switching

35 cage700 500 200 150800 600 250 180

125A160A

70 cageATS 12/4 M2BCATS 16/4 M2BC 70 cage

800800800

600600

600

250300300

300300300

200A250A400A 30

2524ATS 20/4 M2BS

ATS 25/4 M2BSATS 40/4 M2BS

4 Pole for three phase supplies - Motorised Switching with manual override

M10M10M8

AC1Rating

380-440V

AC3Rating

380-440V

40A 11kW40A 11kW40A 11kW80A 22kW

80A116A

45kW55kW

20A 11kW40A 22kW53A 30kW53A 30kW

200A250A400A

Dimensions (mm)*see inner front cover for reference diagram

80kW100kW150kW

Switchgear Systems Ltd. Tel: 01788 577399 Fax: 01788 577899 E-mail: [email protected]

Mains To Generator ATS Panels

AW DH BOOrdering

Reference*ControlVoltage

600600600

400400

400

200200200

100100120

600 400 200 12035 cage25 cage25 cage

2 Pole for single phase supplies - Contactor Switching

35 cage

ATS 4/2 M2GC330ATS 6/2 M2GC330ATS 8/2 M2GC330ATS 10/2 M2GC330

12V DC12V DC12V DC12V DC

600600700

400400

500

200200200

120120150

700 500 200 15035 cage25 cage25 cage

35 cage700 500 200 150800 600 250 180

70 cage70 cage

ATS 4/4 M2GC331ATS 6/4 M2GC331ATS 8/4 M2GC331ATS 10/4 M2GC331ATS 12/4 M2GC331ATS 16/4 M2GC331

12V DC12V DC12V DC24V DC24V DC24V DC

4 Pole for three phase supplies - Contactor Switching

800800800

600600

600

250300300

30030030030

2524

M10M10M8

10001000

600800

300300

39035040

35M12M10

12001200

800800

300300

450450

ATS 20/4 M2GS331ATS 25/4 M2GS331ATS 40/4 M2GS331ATS 63/4 M2GS331ATS 80/4 M2GS331

ATS 100/4 M2GS331ATS 125/4 M2GS331 40

40M12M12

24V DC24V DC24V DC24V DC24V DC24V DC24V DC

4 Pole for three phase supplies - Motorised Switching with manual override

630A800A

1000A1250A

40A63A80A

100A

40A63A80A

100A125A160A

200A250A400A

AC1Rating

380-440V

AC3Rating

380-440V

40A 11kW40A 11kW40A 11kW80A 22kW

80A116A

45kW55kW

20A 11kW40A 22kW53A 30kW53A 30kW

630A800A

1000A1250A

200A250A400A

Dimensions (mm)*see inner front cover for reference diagram

300kW375kW

80kW100kW150kW250kW

450kW

These models are designed to be used in conjunction with a backup generator.

• Designed in compliance with BSEN 60947-6-1• For life safety requirements as detailed in BSEN 8519:2010 see page 20-21 for ATS Bypass• Electrical and mechanical interlocks between supplies• All phases on primary and secondary supply monitored to protect against total power loss, phase failure, and under/over voltage• Fully controlled by either the interactive user interface or via a laptop by downloading the free of charge software• Multiple modes including auto, manual, test, start inhibit and return inhibit• Adjustable settings for voltage sensitivity, gen warm up timer, gen cool down timer, various alarms and many other features• Negative out and volt free mains failure indication terminals for signalling a GenSet• Requires a nominal but permanently available DC supply to run the controller. This is normally taken from the genset but we can supply either built in or remote solutions if this is not readily available• Volt free remote terminals to show the supply in use• Ingress protection IP55

Switchgear Systems Ltd. Tel: 01788 577399 Fax: 01788 577899 E-mail: [email protected]

M2G Control Panel Operation

Whether built in or standalone, these self-sustaining power supplies include a charger and battery to power the digital controller on the mains to generator ATS panels when an alternative source of DC power is not available.

Self-sustaining DC power supplies

Built into the panel.Suffix reference

Self MaintainedPower Supplies

12V DCOrder Reference

24V DCOrder Reference

/12V MPS /24V MPS

Stand alone MPS 160012 160024

Retro-Fit VoltageChange Kit

12V DCOrder Reference

24V DCOrder Reference

Kit of 3 relays 12VCK 24VCK

*Note: All M2G panels need a continuous DC supply to power the control panel. This is normally takenfrom the generator battery; hence the control voltage has been selected to match normal battery voltages.

If you do not wish to use thegenerator battery a built-in or stand-aloneself-maintained power source can be used.

Start Inhibit This mode prevents operation of the secondary (generator) supply when the primary supply fails. It will changeover to the primary supply to load as long as it is available and will not start or switch over to the generator supply.

Auto In this mode the controller will send the GenSet start signal on primary supply failure and switch the generator to load. When the primary supply returns the controller will return the load to the primary supply.

Prohibit Return On primary supply failure this mode allows the generator to start and switch the ATS load output over to it, as it does with the auto function but requires manual intervention to switch it back to the mains supply.

Manual This gives the user manual control of the power supplies, it will send the GenSet start signal to make both supplies available. Pressing the S1 button will close the mains supply to load and pressing the S2 button will close the generator supply to load.

Test When the panel is in test mode it will send the start signal to the GenSet and switch the load to the generator. It will continue to run in this way until switched back to a different mode.

Configuring the panel The controller can be configured from the control interface on the door or by using a configuration software free to download. A full set of configuration constructions is included with the panel and the configuration software is available on line from Deepsea electronics.

Switchgear Systems Ltd. Tel: 01788 577399 Fax: 01788 577899 E-mail: [email protected]

Sheet Steel Enclosed ATS Bypass Switches I-II

• For life safety ATS installations to BS8519:2010• Break-Before-Make operation• Door interlocked padlockable handles• Fully load rated AC23A 415-690V• Ingress protection IP55

Switchgear Systems have developed a range ofswitches that help provide bypass of Life Safety ATS panels, in a minimum number of operations, for bothsingle line and dual line switching.Designed to be fitted under our ATS switches these bypass switches combine with the ATS to provide an integrated system. This solution offers isolation in bypass mode with complete separation allowing safe working during installation, set-up, or maintainance on the ATS panel without loss of supply.

Single Line Bypass This provides bypass of one incoming supply to the ATS whilst isolating the other. It maintains continuityof supply to load while undergoing safe installation, set-up or maintainance on the ATS panel.

Dual Line Bypass For critical installations this provides bypass of both supplies around the ATS and uses a manual changeover, on either load, to allow selection of supply in the case of a primary supply failure. It maintains continuity of either supply while undergoing safe installation, set-up or maintainance on the ATS panel.

Alternative Configurations Two position I-II Make Before Break switches can be suppied to special order.Three position I-II-III Break Before Make switches are also available. These provide a central test position. The test position bypasses the ATS while still maintaining the incoming supplies allowing it to be testedwithout affecting the rest of the installation.

When ordered alongside our ATS panels (pages 14-19) these will bemechanically and electronically fitted to the bottom of the ATS (left)

Alternative layouts are available upon request (examples seen right)

Primary Supply

Healthy On LoadSecondary Supply

On Load Healthy

16 Woodside Park, Rugby, Warwickshire, CV21 2NP

Tel: 01788 577399. Fax: 01788 577899. E: [email protected]

SwitchgearSystems Ltd

Automatic Transfer Switch

Primary Supply

Healthy On LoadSecondary Supply

On Load Healthy

16 Woodside Park, Rugby, Warwickshire, CV21 2NP

Tel: 01788 577399. Fax: 01788 577899. E: [email protected]

SwitchgearSystems Ltd

Automatic Transfer Switch

Switchgear Systems Ltd. Tel: 01788 577399 Fax: 01788 577899 E-mail: [email protected]

Sheet Steel Enclosed ATS Bypass Switches I-II

600700700

500400

500

200200200

800 600 400

AW DH O

35 cage70 cage

35 cage

Single Line 4 Pole

25

600600600

400400

400

200200200 70 cage

35 cage35 cage

Single Line 2 Pole

63A

NominalRating le

415V

100A125A250A

63A100A125A

ST BYATS 6/4 SL

OrderingReference

ST BYATS 10/4 SLST BYATS 12/4 SLST BYATS 25/4 SL

ST BYATS 6/2 SLST BYATS 10/2 SLST BYATS 12/2 SL

OperatingHandles

2221

222

800 600 400 30400A ST BYATS 40/4 SL 1M10M10

800800800

600600

600

300300300

1400 800 400

35 cage70 cage

35 cage

Dual Line 4 Pole

25

800800800

600600

600

300300300 70 cage

35 cage35 cage

Dual Line 2 Pole

63A100A125A250A

63A100A125A

ST BYATS 6/4 DLST BYATS 10/4 DLST BYATS 12/4 DLST BYATS 25/4 DL

ST BYATS 6/2 DLST BYATS 10/2 DLST BYATS 12/2 DL

4442

444

1400 800 400 30400A ST BYATS 40/4 DL 2M10M10

**

* 250A-630A dual line units come in floor standing enclosures

Dimensions (mm)*see inner front cover for reference diagram

1000 600 400 30630A ST BYATS 63/4 SL 1 M10

1400 800 400 30630A ST BYATS 63/4 DL 2 M10*

All items are sold under Switchgear Systems Limited standard terms and conditions, a copy of whichcan be found on our website (www.switchgear-systems.com).

It is the responsibility of the installer to ensure items are fitted to the requirements of BS 7671(Wiring Regulations) and best working practice.

H - Height of enclosure

W - Width of enclosure

D - Depth of enclosure (does not include handle or any other external components)

A - Width of terminal

B - Cable room measured from connection point to the end of enclosure

O - Terminal connection diameter

At Switchgear Systems Ltd. we build most of our switchgear in wall mounting sheet steel powder coated RAL 7035 enclosures. There should be no need for spreader boxes with our equipment as the enclosures are suitably sized for the spreading of typical cable sizes suitable for the switchgear’s current carrying capacity. Where larger sizes and quantities of cables are being used we can put them into bigger enclosures and manufacture bespoke extension terminals. As well as the standard enclosure we also offer a range of material options for both the enclosure and gland plate/s, as well as a number of accessories.

Enclosure material options:• Standard RAL7035 sheet steel• Alternative colour options• Stainless steel enclosures• GRP enclosures• Floor standing sheet steel

Reference diagram for dimensions shown in tables throughout catalogue

Gland plate material options:• Standard sheet steel• Aluminium• Brass• Insulation board• Brushed cable entry

Accessories:• Mounting brackets• Padlockable hasps• Metering and CT’s• Indicator lights• Castell Interlocks• And many others