+ All Categories
Home > Documents > Choosing between resistor and reactor

Choosing between resistor and reactor

Date post: 15-Nov-2015
Category:
Upload: raod2
View: 41 times
Download: 0 times
Share this document with a friend
Description:
Choosing between resistor and reactor for neutral ground
Popular Tags:
8
Choosing Between Resistor and Reactor for Neutral Ground Impedance Faults involving ground produce high fault current magnitude especially when the transformer(s) neutral is solidly grounded. The neutral ground circuit in the transformer provides the return path for the fault currents. To limit this current, impedance – either in the form of a reactor or a resistor – is installed in the neutral circuit. See the figure below. Enter your email address to subscribe to this blog and receive notifications of new posts by email. Join 492 other subscribers Subscribe Power Systems Engineering Page 1 of 8 Choosing Between Resistor and Reactor for Neutral Ground Impedance | Power Syste... 02-04-2015 http://peguru.com/2013/01/choosing-between-resistor-and-reactor-for-neutral-ground...
Transcript
  • Choosing Between

    Resistor and Reactor

    for Neutral Ground

    Impedance

    Faults involving ground produce high fault

    current magnitude especially when the

    transformer(s) neutral is solidly grounded.

    The neutral ground circuit in the transformer

    provides the return path for the fault

    currents. To limit this current, impedance

    either in the form of a reactor or a resistor

    is installed in the neutral circuit. See the

    figure below.

    Enter your email

    address to

    subscribe to this

    blog and receive

    notifications of

    new posts by

    email.

    Join 492 other

    subscribers

    Subscribe

    Power Systems Engineering

    Page 1 of 8Choosing Between Resistor and Reactor for Neutral Ground Impedance | Power Syste...

    02-04-2015http://peguru.com/2013/01/choosing-between-resistor-and-reactor-for-neutral-ground...

  • Ground Fault Current Path

    The table below lists the differences between

    utilizing a resistor or reactor as the

    impedance in the transformer neutral circuit.

    Resistor

    Image

    courtesy:Postglover

    Reactor

    Image

    courtesy:Trench

    Pros

    1. It uses actual

    resistance of the

    design material

    1. It uses inductive

    reactance of the

    coil to create an

    impedance path

    Recent Posts Tags

    Cable Volt Drop Problems?

    Eliminate Voltage Drop in long cable runs and Save on cable

    costs

    Choosing

    Between

    Resistor and

    Reactor for

    Neutral Ground

    Impedance

    Power

    Cable

    Neutral

    and System

    Grounding

    Substation

    SCADA System -

    Design Guide

    Page 2 of 8Choosing Between Resistor and Reactor for Neutral Ground Impedance | Power Syste...

    02-04-2015http://peguru.com/2013/01/choosing-between-resistor-and-reactor-for-neutral-ground...

  • to limit the fault

    current.

    2. It is universally

    applied without

    any limitation.

    for the fault

    current.

    2. It is well suited

    for applications

    which require

    several thousand

    amps to flow

    through it for a

    short duration.

    Cons

    1. It is expensive to

    build since it

    must have

    enough mass to

    absorb the fault

    current energy.

    The price

    increases with

    the increase in

    fault current it

    can handle and

    time rating.

    1. It is typically

    applied in

    systems where

    there is a desire

    to limit the

    ground fault

    current to a

    magnitude that is

    25% to 60% of the

    three phase fault

    current. If the

    ground fault

    current is limited

    to less than 25%

    of the three-

    phase fault

    Per Unit

    System -

    Practice

    Problem

    Solved For

    Easy

    Understanding

    What Do

    Symmetrical,

    Asymmetrical,

    Momentary,

    Interrupting,

    Close &

    Latch

    Cable and

    Conduit

    Installation in

    Substations -

    Best Practices

    Substation Sub-

    Surface

    Engineering: An

    Overview of

    What a Geotech

    Survey Reveals

    Page 3 of 8Choosing Between Resistor and Reactor for Neutral Ground Impedance | Power Syste...

    02-04-2015http://peguru.com/2013/01/choosing-between-resistor-and-reactor-for-neutral-ground...

  • current then the

    neutral winding

    can be subjected

    to transient over-

    voltages

    (explained

    below).Therefore,

    a surge arrester

    should be

    installed in with

    the reactor to

    achieve the

    reduction in fault

    current and

    prevent transient

    over-voltages

    from damaging

    the neutral

    winding of the

    transformer.

    More on transient over-voltages:

    Transient over-voltages are produced by arcing faults,

    not surges. The over-voltage occurs when the arc

    strikes due to a line-to-ground fault and charges the

    system capacitive reactance. When the arc momentarily

    extinguishes, the charge needs to dissipate. When the

    Ratings

    Mean?

    Power

    Circuit

    Breaker -

    Operation

    and Control

    Scheme

    Determining

    short-

    circuit

    rating of

    circuit

    breakers

    Direct

    Transfer

    Trip Scheme

    Page 4 of 8Choosing Between Resistor and Reactor for Neutral Ground Impedance | Power Syste...

    02-04-2015http://peguru.com/2013/01/choosing-between-resistor-and-reactor-for-neutral-ground...

  • neutral ground resistor is used as the impedance,

    its resistance is usually less than the capacitive

    reactance, thereby allowing the voltage to discharge.

    However, when the reactor is used and when its

    reactive impedance is high (to limit ground fault

    current to less than 25% of the three phase current), the

    voltage cannot discharge. As the arc re-fires, the

    charge can continually build, thus creating the over-

    voltage.

    Summary:

    If it is desired to limit the fault current to a

    really low magnitude using the actual resistance

    then a resistor is recommended. On the other

    hand, if several thousand amps of fault current

    is permissible in the system then the reactor is

    recommended. In the either case, the reactor can

    be an economical solution. Keep in mind, we

    are talking about shunt air core reactor in the

    transformer neutral for current limiting purpose.

    Series reactors, however, are expensive. The

    price of any neutral ground impedance device

    increases with the increase in the continuous

    current rating (for reactors), impedance rating,

    and time rating.

    Page 5 of 8Choosing Between Resistor and Reactor for Neutral Ground Impedance | Power Syste...

    02-04-2015http://peguru.com/2013/01/choosing-between-resistor-and-reactor-for-neutral-ground...

  • * * * * *

    grounding neutral grounding reactor

    resistor transient overvoltage

    Leave a Reply

    ARCHIVES

    January

    2013

    December

    2012

    September

    2012

    June 2012

    May 2012

    March

    2012

    January

    2012

    November

    2011

    August

    2011

    TAG CLOUD

    AC system arc

    flash study arc flash test

    asymmetrical current

    base values

    cable shield

    groundingdirect buried conduits

    direct

    transfer tripFACT generator swing

    Ground gridHVDC IEEE 1584

    John Camara Juan L.

    Bala Lewis

    Blackburn

    lockout relays modern

    power system

    momentary rating

    NCEES Professional

    Engineering

    neutral

    grounding

    BOOKS ON MY

    SHELF

    Protective

    Relaying

    NEC 2011

    Handbook

    Power System

    Analysis and

    Design

    WELCOME TO

    PE GURU

    Page 6 of 8Choosing Between Resistor and Reactor for Neutral Ground Impedance | Power Syste...

    02-04-2015http://peguru.com/2013/01/choosing-between-resistor-and-reactor-for-neutral-ground...

  • July 2011

    June 2011

    May 2011

    April 2011

    March

    2011

    September

    2010

    July 2010

    June 2010

    NFPA 70E

    OSHA 1910 Pass

    PE Exam

    permissive over reaching transfer tripper unit system PE Sample Problems

    pilot relayingpower blackout power

    flow power

    system Power

    transformers

    PPE

    protective relayingreactive power support

    short circuit

    rating steady state stability substation

    conduit details

    symmetrical components

    symmetrical current

    system frequency

    thermal limitation

    transformers

    voltage drop

    limitation Zia A.

    Yamayee

    ABOUT CONTACT TERMS & CONDITIONS PRIVACY POLICY

    SITE MAP

    Page 7 of 8Choosing Between Resistor and Reactor for Neutral Ground Impedance | Power Syste...

    02-04-2015http://peguru.com/2013/01/choosing-between-resistor-and-reactor-for-neutral-ground...

  • Page 8 of 8Choosing Between Resistor and Reactor for Neutral Ground Impedance | Power Syste...

    02-04-2015http://peguru.com/2013/01/choosing-between-resistor-and-reactor-for-neutral-ground...


Recommended