T&M Rev:03.12.2015
(Required on New Installs)
(Required for Cert. of Occupancy)
City of Durham Cross Connection Control 1600 Mist Lake Drive; Durham, NC 27704 Ph. (919) 560-4194 Fax. (919) 560-1744 Email: [email protected]
Backflow Prevention Assembly Test and Maintenance Report
Name of Owner: BUILDING PERMIT NO:
Mailing Address: BACKFLOW PERMIT NO:
City, State & Zip Code:
Location of Assembly:
Service Meter Number: By-pass Meter Reading:
Type: Manufacturer: Model: Size: Serial No:
Tester: Certification No: *Date: Time:
Type of Service: New Test: Recertification Test: Line Pressure:
Test Kit: Serial No: Calibration Date:
NO. 1 CHECK VALVE NO. 2 CHECK VALVE RELIEF VALVE PRESSURE VACUUM BREAKER
Leaked
Closed Tight
Diff Pressure Across
Check Valve ___.___PSID
Leaked
Closed Tight
Diff Pressure Across
Check Valve ___.___PSID
Opened at
____.____ PSID
Did not Open
Air Inlet ____.____ PSID
Did not open
Check Valve ____.____PSID
Leaked
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Closed Tight at ___.___PSID
Closed Tight at ___.___PSID
Opened at ____.____PSID Air Inlet ____.____PSID Check Valve ____.____PSID
Shut Off Valve #1 Leaked Closed Tight
Buffer:
Shut Off Valve #2 Leaked Closed Tight
Comments:
Assembly Status: PASSED **FAILED
I hereby certify that this data is accurate and reflects the proper operation and maintenance of the assembly.
(Signature of Licensed Tester and Date) (Company Name)
*Test and Maintenance Report must be submitted within 15 days. **All Repairs must be made within 10 Business Days.
1 1/2"
✔
Sep 13th 2016
18438
2
RWCT0548
✔
✔
20 Morcroft Lane
Sep 9th 2016Mid-West 845-5
irrigation
Durham, North Carolina, 27705
Unifour Fire & Safety
Matt Shambley
Pool pump room
✔
009 M2Watts
0✔
80
09141143
RP
10:52 AM
Parc at University Tower
8 2 1 8
T&M Rev:03.12.2015
(Required on New Installs)
(Required for Cert. of Occupancy)
City of Durham Cross Connection Control 1600 Mist Lake Drive; Durham, NC 27704 Ph. (919) 560-4194 Fax. (919) 560-1744 Email: [email protected]
Backflow Prevention Assembly Test and Maintenance Report
Name of Owner: BUILDING PERMIT NO:
Mailing Address: BACKFLOW PERMIT NO:
City, State & Zip Code:
Location of Assembly:
Service Meter Number: By-pass Meter Reading:
Type: Manufacturer: Model: Size: Serial No:
Tester: Certification No: *Date: Time:
Type of Service: New Test: Recertification Test: Line Pressure:
Test Kit: Serial No: Calibration Date:
NO. 1 CHECK VALVE NO. 2 CHECK VALVE RELIEF VALVE PRESSURE VACUUM BREAKER
Leaked
Closed Tight
Diff Pressure Across
Check Valve ___.___PSID
Leaked
Closed Tight
Diff Pressure Across
Check Valve ___.___PSID
Opened at
____.____ PSID
Did not Open
Air Inlet ____.____ PSID
Did not open
Check Valve ____.____PSID
Leaked
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Closed Tight at ___.___PSID
Closed Tight at ___.___PSID
Opened at ____.____PSID Air Inlet ____.____PSID Check Valve ____.____PSID
Shut Off Valve #1 Leaked Closed Tight
Buffer:
Shut Off Valve #2 Leaked Closed Tight
Comments:
Assembly Status: PASSED **FAILED
I hereby certify that this data is accurate and reflects the proper operation and maintenance of the assembly.
(Signature of Licensed Tester and Date) (Company Name)
*Test and Maintenance Report must be submitted within 15 days. **All Repairs must be made within 10 Business Days.
1 1/2"
✔
Sep 13th 2016
A940818RWCT0548
✔
Shut off valve #1 needs a new handle
✔
20 Morcroft Lane
Sep 9th 2016Mid-West 845-5
fire
Durham, North Carolina, 27705
Unifour Fire & Safety
Matt Shambley
Bldg 1100 riser room
✔ ✔
805YFebco
✔
80
09141143
DC
1:21 PM
Parc at University Tower
2 4 1 2
T&M Rev:03.12.2015
(Required on New Installs)
(Required for Cert. of Occupancy)
City of Durham Cross Connection Control 1600 Mist Lake Drive; Durham, NC 27704 Ph. (919) 560-4194 Fax. (919) 560-1744 Email: [email protected]
Backflow Prevention Assembly Test and Maintenance Report
Name of Owner: BUILDING PERMIT NO:
Mailing Address: BACKFLOW PERMIT NO:
City, State & Zip Code:
Location of Assembly:
Service Meter Number: By-pass Meter Reading:
Type: Manufacturer: Model: Size: Serial No:
Tester: Certification No: *Date: Time:
Type of Service: New Test: Recertification Test: Line Pressure:
Test Kit: Serial No: Calibration Date:
NO. 1 CHECK VALVE NO. 2 CHECK VALVE RELIEF VALVE PRESSURE VACUUM BREAKER
Leaked
Closed Tight
Diff Pressure Across
Check Valve ___.___PSID
Leaked
Closed Tight
Diff Pressure Across
Check Valve ___.___PSID
Opened at
____.____ PSID
Did not Open
Air Inlet ____.____ PSID
Did not open
Check Valve ____.____PSID
Leaked
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Closed Tight at ___.___PSID
Closed Tight at ___.___PSID
Opened at ____.____PSID Air Inlet ____.____PSID Check Valve ____.____PSID
Shut Off Valve #1 Leaked Closed Tight
Buffer:
Shut Off Valve #2 Leaked Closed Tight
Comments:
Assembly Status: PASSED **FAILED
I hereby certify that this data is accurate and reflects the proper operation and maintenance of the assembly.
(Signature of Licensed Tester and Date) (Company Name)
*Test and Maintenance Report must be submitted within 15 days. **All Repairs must be made within 10 Business Days.
1 1/2"
✔
Sep 13th 2016
A100976RWCT0548
✔
✔
20 Morcroft Lane
Sep 9th 2016Mid-West 845-5
fire
Durham, North Carolina, 27705
Unifour Fire & Safety
Matt Shambley
Bldg 1000 riser room
✔ ✔
805YFebco
✔
80
09141143
DC
1:02 PM
Parc at University Tower
2 6 1 4
T&M Rev:03.12.2015
(Required on New Installs)
(Required for Cert. of Occupancy)
City of Durham Cross Connection Control 1600 Mist Lake Drive; Durham, NC 27704 Ph. (919) 560-4194 Fax. (919) 560-1744 Email: [email protected]
Backflow Prevention Assembly Test and Maintenance Report
Name of Owner: BUILDING PERMIT NO:
Mailing Address: BACKFLOW PERMIT NO:
City, State & Zip Code:
Location of Assembly:
Service Meter Number: By-pass Meter Reading:
Type: Manufacturer: Model: Size: Serial No:
Tester: Certification No: *Date: Time:
Type of Service: New Test: Recertification Test: Line Pressure:
Test Kit: Serial No: Calibration Date:
NO. 1 CHECK VALVE NO. 2 CHECK VALVE RELIEF VALVE PRESSURE VACUUM BREAKER
Leaked
Closed Tight
Diff Pressure Across
Check Valve ___.___PSID
Leaked
Closed Tight
Diff Pressure Across
Check Valve ___.___PSID
Opened at
____.____ PSID
Did not Open
Air Inlet ____.____ PSID
Did not open
Check Valve ____.____PSID
Leaked
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Closed Tight at ___.___PSID
Closed Tight at ___.___PSID
Opened at ____.____PSID Air Inlet ____.____PSID Check Valve ____.____PSID
Shut Off Valve #1 Leaked Closed Tight
Buffer:
Shut Off Valve #2 Leaked Closed Tight
Comments:
Assembly Status: PASSED **FAILED
I hereby certify that this data is accurate and reflects the proper operation and maintenance of the assembly.
(Signature of Licensed Tester and Date) (Company Name)
*Test and Maintenance Report must be submitted within 15 days. **All Repairs must be made within 10 Business Days.
1 1/2"
✔
Sep 13th 2016
H13630RWCT0548
✔
✔
20 Morcroft Lane
Sep 9th 2016Mid-West 845-5
fire
Durham, North Carolina, 27705
Unifour Fire & Safety
Matt Shambley
Bldg 900 riser room
✔ ✔
850Febco
✔
80
09141143
DC
12:54 PM
Parc at University Tower
2 4 2 6
T&M Rev:03.12.2015
(Required on New Installs)
(Required for Cert. of Occupancy)
City of Durham Cross Connection Control 1600 Mist Lake Drive; Durham, NC 27704 Ph. (919) 560-4194 Fax. (919) 560-1744 Email: [email protected]
Backflow Prevention Assembly Test and Maintenance Report
Name of Owner: BUILDING PERMIT NO:
Mailing Address: BACKFLOW PERMIT NO:
City, State & Zip Code:
Location of Assembly:
Service Meter Number: By-pass Meter Reading:
Type: Manufacturer: Model: Size: Serial No:
Tester: Certification No: *Date: Time:
Type of Service: New Test: Recertification Test: Line Pressure:
Test Kit: Serial No: Calibration Date:
NO. 1 CHECK VALVE NO. 2 CHECK VALVE RELIEF VALVE PRESSURE VACUUM BREAKER
Leaked
Closed Tight
Diff Pressure Across
Check Valve ___.___PSID
Leaked
Closed Tight
Diff Pressure Across
Check Valve ___.___PSID
Opened at
____.____ PSID
Did not Open
Air Inlet ____.____ PSID
Did not open
Check Valve ____.____PSID
Leaked
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Closed Tight at ___.___PSID
Closed Tight at ___.___PSID
Opened at ____.____PSID Air Inlet ____.____PSID Check Valve ____.____PSID
Shut Off Valve #1 Leaked Closed Tight
Buffer:
Shut Off Valve #2 Leaked Closed Tight
Comments:
Assembly Status: PASSED **FAILED
I hereby certify that this data is accurate and reflects the proper operation and maintenance of the assembly.
(Signature of Licensed Tester and Date) (Company Name)
*Test and Maintenance Report must be submitted within 15 days. **All Repairs must be made within 10 Business Days.
1 1/2"
✔
Sep 13th 2016
A100942RWCT0548
✔
✔
20 Morcroft Lane
Sep 9th 2016Mid-West 845-5
fire
Durham, North Carolina, 27705
Unifour Fire & Safety
Matt Shambley
Bldg 800 riser room
✔ ✔
805YFebco
✔
80
09141143
DC
12:36 PM
Parc at University Tower
2 0 1 8
T&M Rev:03.12.2015
(Required on New Installs)
(Required for Cert. of Occupancy)
City of Durham Cross Connection Control 1600 Mist Lake Drive; Durham, NC 27704 Ph. (919) 560-4194 Fax. (919) 560-1744 Email: [email protected]
Backflow Prevention Assembly Test and Maintenance Report
Name of Owner: BUILDING PERMIT NO:
Mailing Address: BACKFLOW PERMIT NO:
City, State & Zip Code:
Location of Assembly:
Service Meter Number: By-pass Meter Reading:
Type: Manufacturer: Model: Size: Serial No:
Tester: Certification No: *Date: Time:
Type of Service: New Test: Recertification Test: Line Pressure:
Test Kit: Serial No: Calibration Date:
NO. 1 CHECK VALVE NO. 2 CHECK VALVE RELIEF VALVE PRESSURE VACUUM BREAKER
Leaked
Closed Tight
Diff Pressure Across
Check Valve ___.___PSID
Leaked
Closed Tight
Diff Pressure Across
Check Valve ___.___PSID
Opened at
____.____ PSID
Did not Open
Air Inlet ____.____ PSID
Did not open
Check Valve ____.____PSID
Leaked
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Closed Tight at ___.___PSID
Closed Tight at ___.___PSID
Opened at ____.____PSID Air Inlet ____.____PSID Check Valve ____.____PSID
Shut Off Valve #1 Leaked Closed Tight
Buffer:
Shut Off Valve #2 Leaked Closed Tight
Comments:
Assembly Status: PASSED **FAILED
I hereby certify that this data is accurate and reflects the proper operation and maintenance of the assembly.
(Signature of Licensed Tester and Date) (Company Name)
*Test and Maintenance Report must be submitted within 15 days. **All Repairs must be made within 10 Business Days.
1 1/2"
✔
✔
Sep 13th 2016
A041929RWCT0548
✔
Check Valve #2 needs to be replaced. Shut off valve #1 needs a new handle.
✔
20 Morcroft Lane
Sep 9th 2016Mid-West 845-5
fire
Durham, North Carolina, 27705
Unifour Fire & Safety
Matt Shambley
Bldg 700 riser room
✔ ✔
805YFebco
80
09141143
DC
12:14 PM
Parc at University Tower
1 4 0 0
T&M Rev:03.12.2015
(Required on New Installs)
(Required for Cert. of Occupancy)
City of Durham Cross Connection Control 1600 Mist Lake Drive; Durham, NC 27704 Ph. (919) 560-4194 Fax. (919) 560-1744 Email: [email protected]
Backflow Prevention Assembly Test and Maintenance Report
Name of Owner: BUILDING PERMIT NO:
Mailing Address: BACKFLOW PERMIT NO:
City, State & Zip Code:
Location of Assembly:
Service Meter Number: By-pass Meter Reading:
Type: Manufacturer: Model: Size: Serial No:
Tester: Certification No: *Date: Time:
Type of Service: New Test: Recertification Test: Line Pressure:
Test Kit: Serial No: Calibration Date:
NO. 1 CHECK VALVE NO. 2 CHECK VALVE RELIEF VALVE PRESSURE VACUUM BREAKER
Leaked
Closed Tight
Diff Pressure Across
Check Valve ___.___PSID
Leaked
Closed Tight
Diff Pressure Across
Check Valve ___.___PSID
Opened at
____.____ PSID
Did not Open
Air Inlet ____.____ PSID
Did not open
Check Valve ____.____PSID
Leaked
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Closed Tight at ___.___PSID
Closed Tight at ___.___PSID
Opened at ____.____PSID Air Inlet ____.____PSID Check Valve ____.____PSID
Shut Off Valve #1 Leaked Closed Tight
Buffer:
Shut Off Valve #2 Leaked Closed Tight
Comments:
Assembly Status: PASSED **FAILED
I hereby certify that this data is accurate and reflects the proper operation and maintenance of the assembly.
(Signature of Licensed Tester and Date) (Company Name)
*Test and Maintenance Report must be submitted within 15 days. **All Repairs must be made within 10 Business Days.
1 1/2"
✔
Sep 13th 2016
A033761RWCT0548
✔
✔
20 Morcroft Lane
Sep 9th 2016Mid-West 845-5
fire
Durham, North Carolina, 27705
Unifour Fire & Safety
Matt Shambley
Bldg 600 riser room
✔ ✔
805YFebco
✔
85
09141143
DC
12:09 PM
Parc at University Tower
2 2 1 8
T&M Rev:03.12.2015
(Required on New Installs)
(Required for Cert. of Occupancy)
City of Durham Cross Connection Control 1600 Mist Lake Drive; Durham, NC 27704 Ph. (919) 560-4194 Fax. (919) 560-1744 Email: [email protected]
Backflow Prevention Assembly Test and Maintenance Report
Name of Owner: BUILDING PERMIT NO:
Mailing Address: BACKFLOW PERMIT NO:
City, State & Zip Code:
Location of Assembly:
Service Meter Number: By-pass Meter Reading:
Type: Manufacturer: Model: Size: Serial No:
Tester: Certification No: *Date: Time:
Type of Service: New Test: Recertification Test: Line Pressure:
Test Kit: Serial No: Calibration Date:
NO. 1 CHECK VALVE NO. 2 CHECK VALVE RELIEF VALVE PRESSURE VACUUM BREAKER
Leaked
Closed Tight
Diff Pressure Across
Check Valve ___.___PSID
Leaked
Closed Tight
Diff Pressure Across
Check Valve ___.___PSID
Opened at
____.____ PSID
Did not Open
Air Inlet ____.____ PSID
Did not open
Check Valve ____.____PSID
Leaked
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Closed Tight at ___.___PSID
Closed Tight at ___.___PSID
Opened at ____.____PSID Air Inlet ____.____PSID Check Valve ____.____PSID
Shut Off Valve #1 Leaked Closed Tight
Buffer:
Shut Off Valve #2 Leaked Closed Tight
Comments:
Assembly Status: PASSED **FAILED
I hereby certify that this data is accurate and reflects the proper operation and maintenance of the assembly.
(Signature of Licensed Tester and Date) (Company Name)
*Test and Maintenance Report must be submitted within 15 days. **All Repairs must be made within 10 Business Days.
1 1/2"
✔
Sep 13th 2016
A033772RWCT0548
✔
✔
20 Morcroft Lane
Sep 9th 2016Mid-West 845-5
fire
Durham, North Carolina, 27705
Unifour Fire & Safety
Matt Shambley
Bldg 500 riser room
✔ ✔
805YFebco
✔
85
09141143
DC
11:51 AM
Parc at University Tower
2 2 2 4
T&M Rev:03.12.2015
(Required on New Installs)
(Required for Cert. of Occupancy)
City of Durham Cross Connection Control 1600 Mist Lake Drive; Durham, NC 27704 Ph. (919) 560-4194 Fax. (919) 560-1744 Email: [email protected]
Backflow Prevention Assembly Test and Maintenance Report
Name of Owner: BUILDING PERMIT NO:
Mailing Address: BACKFLOW PERMIT NO:
City, State & Zip Code:
Location of Assembly:
Service Meter Number: By-pass Meter Reading:
Type: Manufacturer: Model: Size: Serial No:
Tester: Certification No: *Date: Time:
Type of Service: New Test: Recertification Test: Line Pressure:
Test Kit: Serial No: Calibration Date:
NO. 1 CHECK VALVE NO. 2 CHECK VALVE RELIEF VALVE PRESSURE VACUUM BREAKER
Leaked
Closed Tight
Diff Pressure Across
Check Valve ___.___PSID
Leaked
Closed Tight
Diff Pressure Across
Check Valve ___.___PSID
Opened at
____.____ PSID
Did not Open
Air Inlet ____.____ PSID
Did not open
Check Valve ____.____PSID
Leaked
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Closed Tight at ___.___PSID
Closed Tight at ___.___PSID
Opened at ____.____PSID Air Inlet ____.____PSID Check Valve ____.____PSID
Shut Off Valve #1 Leaked Closed Tight
Buffer:
Shut Off Valve #2 Leaked Closed Tight
Comments:
Assembly Status: PASSED **FAILED
I hereby certify that this data is accurate and reflects the proper operation and maintenance of the assembly.
(Signature of Licensed Tester and Date) (Company Name)
*Test and Maintenance Report must be submitted within 15 days. **All Repairs must be made within 10 Business Days.
1 1/2"
✔
✔
Sep 13th 2016
A027097RWCT0548
✔
Check Valve #2 needs to be replaced.
✔
20 Morcroft Lane
Sep 9th 2016Mid-West 845-5
fire
Durham, North Carolina, 27705
Unifour Fire & Safety
Matt Shambley
Bldg 400 riser room
✔ ✔
805YFebco
85
09141143
DC
11:37 AM
Parc at University Tower
1 6 0 0
T&M Rev:03.12.2015
(Required on New Installs)
(Required for Cert. of Occupancy)
City of Durham Cross Connection Control 1600 Mist Lake Drive; Durham, NC 27704 Ph. (919) 560-4194 Fax. (919) 560-1744 Email: [email protected]
Backflow Prevention Assembly Test and Maintenance Report
Name of Owner: BUILDING PERMIT NO:
Mailing Address: BACKFLOW PERMIT NO:
City, State & Zip Code:
Location of Assembly:
Service Meter Number: By-pass Meter Reading:
Type: Manufacturer: Model: Size: Serial No:
Tester: Certification No: *Date: Time:
Type of Service: New Test: Recertification Test: Line Pressure:
Test Kit: Serial No: Calibration Date:
NO. 1 CHECK VALVE NO. 2 CHECK VALVE RELIEF VALVE PRESSURE VACUUM BREAKER
Leaked
Closed Tight
Diff Pressure Across
Check Valve ___.___PSID
Leaked
Closed Tight
Diff Pressure Across
Check Valve ___.___PSID
Opened at
____.____ PSID
Did not Open
Air Inlet ____.____ PSID
Did not open
Check Valve ____.____PSID
Leaked
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Closed Tight at ___.___PSID
Closed Tight at ___.___PSID
Opened at ____.____PSID Air Inlet ____.____PSID Check Valve ____.____PSID
Shut Off Valve #1 Leaked Closed Tight
Buffer:
Shut Off Valve #2 Leaked Closed Tight
Comments:
Assembly Status: PASSED **FAILED
I hereby certify that this data is accurate and reflects the proper operation and maintenance of the assembly.
(Signature of Licensed Tester and Date) (Company Name)
*Test and Maintenance Report must be submitted within 15 days. **All Repairs must be made within 10 Business Days.
1 1/2"
✔
Sep 13th 2016
A033765RWCT0548
✔
✔
20 Morcroft Lane
Sep 9th 2016Mid-West 845-5
fire
Durham, North Carolina, 27705
Unifour Fire & Safety
Matt Shambley
Bldg 300 riser room
✔ ✔
805YFebco
✔
85
09141143
DC
11:20 AM
Parc at University Tower
2 0 2 2
T&M Rev:03.12.2015
(Required on New Installs)
(Required for Cert. of Occupancy)
City of Durham Cross Connection Control 1600 Mist Lake Drive; Durham, NC 27704 Ph. (919) 560-4194 Fax. (919) 560-1744 Email: [email protected]
Backflow Prevention Assembly Test and Maintenance Report
Name of Owner: BUILDING PERMIT NO:
Mailing Address: BACKFLOW PERMIT NO:
City, State & Zip Code:
Location of Assembly:
Service Meter Number: By-pass Meter Reading:
Type: Manufacturer: Model: Size: Serial No:
Tester: Certification No: *Date: Time:
Type of Service: New Test: Recertification Test: Line Pressure:
Test Kit: Serial No: Calibration Date:
NO. 1 CHECK VALVE NO. 2 CHECK VALVE RELIEF VALVE PRESSURE VACUUM BREAKER
Leaked
Closed Tight
Diff Pressure Across
Check Valve ___.___PSID
Leaked
Closed Tight
Diff Pressure Across
Check Valve ___.___PSID
Opened at
____.____ PSID
Did not Open
Air Inlet ____.____ PSID
Did not open
Check Valve ____.____PSID
Leaked
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Closed Tight at ___.___PSID
Closed Tight at ___.___PSID
Opened at ____.____PSID Air Inlet ____.____PSID Check Valve ____.____PSID
Shut Off Valve #1 Leaked Closed Tight
Buffer:
Shut Off Valve #2 Leaked Closed Tight
Comments:
Assembly Status: PASSED **FAILED
I hereby certify that this data is accurate and reflects the proper operation and maintenance of the assembly.
(Signature of Licensed Tester and Date) (Company Name)
*Test and Maintenance Report must be submitted within 15 days. **All Repairs must be made within 10 Business Days.
1 1/2"
✔
Sep 13th 2016
A033771RWCT0548
✔
✔
20 Morcroft Lane
Sep 9th 2016Mid-West 845-5
fire
Durham, North Carolina, 27705
Unifour Fire & Safety
Matt Shambley
Bldg 200 riser room
✔ ✔
805YFebco
✔
85
09141143
DC
11:09 AM
Parc at University Tower
1 8 1 6
T&M Rev:03.12.2015
(Required on New Installs)
(Required for Cert. of Occupancy)
City of Durham Cross Connection Control 1600 Mist Lake Drive; Durham, NC 27704 Ph. (919) 560-4194 Fax. (919) 560-1744 Email: [email protected]
Backflow Prevention Assembly Test and Maintenance Report
Name of Owner: BUILDING PERMIT NO:
Mailing Address: BACKFLOW PERMIT NO:
City, State & Zip Code:
Location of Assembly:
Service Meter Number: By-pass Meter Reading:
Type: Manufacturer: Model: Size: Serial No:
Tester: Certification No: *Date: Time:
Type of Service: New Test: Recertification Test: Line Pressure:
Test Kit: Serial No: Calibration Date:
NO. 1 CHECK VALVE NO. 2 CHECK VALVE RELIEF VALVE PRESSURE VACUUM BREAKER
Leaked
Closed Tight
Diff Pressure Across
Check Valve ___.___PSID
Leaked
Closed Tight
Diff Pressure Across
Check Valve ___.___PSID
Opened at
____.____ PSID
Did not Open
Air Inlet ____.____ PSID
Did not open
Check Valve ____.____PSID
Leaked
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Closed Tight at ___.___PSID
Closed Tight at ___.___PSID
Opened at ____.____PSID Air Inlet ____.____PSID Check Valve ____.____PSID
Shut Off Valve #1 Leaked Closed Tight
Buffer:
Shut Off Valve #2 Leaked Closed Tight
Comments:
Assembly Status: PASSED **FAILED
I hereby certify that this data is accurate and reflects the proper operation and maintenance of the assembly.
(Signature of Licensed Tester and Date) (Company Name)
*Test and Maintenance Report must be submitted within 15 days. **All Repairs must be made within 10 Business Days.
3/4"
✔
Sep 13th 2016
3613177
2
RWCT0548
✔
✔
20 Morcroft Lane
Sep 9th 2016Mid-West 845-5
irrigation
Durham, North Carolina, 27705
Unifour Fire & Safety
Matt Shambley
Hotbox at main entrance
✔
975XLWilkins
4✔
85
09141143
RP
11:01 AM
Parc at University Tower
10 6 2 8
T&M Rev:03.12.2015
(Required on New Installs)
(Required for Cert. of Occupancy)
City of Durham Cross Connection Control 1600 Mist Lake Drive; Durham, NC 27704 Ph. (919) 560-4194 Fax. (919) 560-1744 Email: [email protected]
Backflow Prevention Assembly Test and Maintenance Report
Name of Owner: BUILDING PERMIT NO:
Mailing Address: BACKFLOW PERMIT NO:
City, State & Zip Code:
Location of Assembly:
Service Meter Number: By-pass Meter Reading:
Type: Manufacturer: Model: Size: Serial No:
Tester: Certification No: *Date: Time:
Type of Service: New Test: Recertification Test: Line Pressure:
Test Kit: Serial No: Calibration Date:
NO. 1 CHECK VALVE NO. 2 CHECK VALVE RELIEF VALVE PRESSURE VACUUM BREAKER
Leaked
Closed Tight
Diff Pressure Across
Check Valve ___.___PSID
Leaked
Closed Tight
Diff Pressure Across
Check Valve ___.___PSID
Opened at
____.____ PSID
Did not Open
Air Inlet ____.____ PSID
Did not open
Check Valve ____.____PSID
Leaked
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Cleaned
Replaced
(list parts in comments)
Closed Tight at ___.___PSID
Closed Tight at ___.___PSID
Opened at ____.____PSID Air Inlet ____.____PSID Check Valve ____.____PSID
Shut Off Valve #1 Leaked Closed Tight
Buffer:
Shut Off Valve #2 Leaked Closed Tight
Comments:
Assembly Status: PASSED **FAILED
I hereby certify that this data is accurate and reflects the proper operation and maintenance of the assembly.
(Signature of Licensed Tester and Date) (Company Name)
*Test and Maintenance Report must be submitted within 15 days. **All Repairs must be made within 10 Business Days.
1 1/2"
✔
Sep 13th 2016
A027115RWCT0548
✔
✔
20 Morcroft Lane
Sep 9th 2016Mid-West 845-5
fire
Durham, North Carolina, 27705
Unifour Fire & Safety
Matt Shambley
Bldg 100 Riser Room
✔ ✔
805YFebco
✔
85
09141143
DC
10:30 AM
Parc at University Tower
2 2 1 8