Class 4141 MP Meter-Pak™ Meter Centers MP44125 MP86200 CONTENTS Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 General and Application Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Catalog 4141CT0701 2008
Transcript

Class 4141

MP Meter-Pak™ Meter Centers

MP44125

MP86200

CONTENTS

Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page

Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2General and Application Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Catalog 4141CT0701

2008

MP Meter-Pak™ Meter CentersProduct Description

2© 2008 Schneider Electric All Rights Reserved 03/2008

PRODUCT DESCRIPTIONSquare D® brand MP Meter-Pak meter centers from Schneider Electric offer a wide range of solutions for multi-metering applications:

• UL® Listed NEMA Type 3R construction

• Meets EUSERC standards

• 9-inch meter center spacing allows for more sockets per device creating lighter, more compact branch enclosures

• Meter socket jaws, constructed of tin-plated copper, are spring reinforced on MP devices

• Lever type bypass meter socket jaws are spring reinforced and equipped with jaw release

• Stainless steel cover hasps and latches meet tough coastal utility sealing requirements

• Barrel lock provisions on all ringless devices

MP Meter-Pak Meter Centers

For 2- to 6-unit apartment buildings or light commercial applications.

• Surface and semi-flush mounting

• Suitable only for use as service equipment

• Main bus ratings range from 200–800 A

• 125, 200, and 225 A (2 to 4 positions) tenant circuit breaker versions

• Four meter socket configurations available:

— Ring type four-jaw without bypass

— Ringless type with 5th jaw without bypass

— Ringless type with 5th jaw and horn bypass

— Ringless type with 5th jaw and lever bypass with jaw release

• 120/240 Vac, 1φ3W or 120/208 Vac, 1φ3W (derived from a 208Y/120 Vac, 3φ4W network)

MPH66125 with Horn Bypass

MPH33125

MP Meter-Pak™ Meter CentersProduct Description

303/2008 © 2008 Schneider Electric All Rights Reserved

Short Circuit Current Rating Selection Process

1. Review local utility requirements to ensure that metering equipment meets their standards.

2. Check with local utility to determine available fault current at the meter center.

3. Use the Short Circuit Current Ratings (SCCR) table below to:

a. Read down to select SCCR equal to or greater than desired rating.

b. Read across to select Tenant Circuit Breaker type.

4. With information obtained from Step 3, turn to the appropriate selection pages to determine catalog numbers for Meter-Pak Device and Tenant Circuit Breakers.

UL Listed Meter Center Short Circuit Current Ratings (SCCR) 10,000, 22,000, 25,000. 42,000, 65,000 and 100,000 AIR

Short Circuit Current Rating (RMS Symmetrical Amperes at 240 Vac

Maximum)1

1 Meter center short circuit current rating is equal to the lowest short circuit current rating given in the table for any circuit breaker installed in any meter panelboard in the meter center.

MP Meter-Pak Meter Centers

Tenant Circuit Breakers2

2 When slider type manual circuit closers are installed, the meter center short circuit current rating is limited to 10,000 RMS symmetrical amperes.

10,000 AIR 3

3 AIR = Amperes Interrupting Rating.

QO (125 A max., 2-pole)

QOM2-MM (200 A max., 2-pole)

QBP-TM (70–225 A max., 2-pole)

22,000 AIR 3QO-VH (125 A max., 2-pole)

QOM2-MVH (200 A max., 2-pole)

25,000 AIR 3 QDP-TM (70–225 A max., 2-pole)

42,000 AIR 3 QOH (125 A max., 2-pole)

65,000 AIR 3 QGP-TM (70–225 A max., 2-pole)

100,000 AIR 3 QJP-TM (70–225 A max, 2-pole)

MP Branch Compartments

ServiceDisconnects(6 Maximum)

Main Lugs Load Center

(Typical)

Transformer

MP Main Lugs Compartment

MP Meter-Pak™ Meter CentersTable of Contents

4© 2008 Schneider Electric All Rights Reserved 03/2008

Table of Contents

MP METER-PAK™ METER CENTERS

Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5125 A Maximum MP Meter-Pak Meter Center Configurations . . . . . . . . .6200 A Maximum MP Meter-Pak Meter Center Configurations . . . . . . . . .6225 A Maximum MP Meter-Pak Meter Center Configurations . . . . . . . . .6Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7Mains Rating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7Branch Circuit Breaker Provisions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7Meter Sockets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7Meter Socket Covers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9Utility Pull Box Cover. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11Customer/Tenant Compartment Cover . . . . . . . . . . . . . . . . . . . . . . . . . .11Mounting Channel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11Rotating Mounting Feet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11Top Endwall Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12125 A Maximum MP Meter-Pak Meter Center Top Endwalls . . . . . . . . .12200 and 225 A Maximum MP Meter-Pak Meter Center Top Endwalls . .12Semi-Flush Flange Kits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12MP Meter-Center Hub and Knockout Configurations . . . . . . . . . . . . . . .13Main Lugs Section Service Conductor Termination Data . . . . . . . . . . . .14Alternate Lug Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14NEMA/EUSERC Lug Landing Kit . . . . . . . . . . . . . . . . . . . . . . . . . . .14–15Tenant Circuit Breaker Terminal Data . . . . . . . . . . . . . . . . . . . . . . . . . . .16Service Grounding/Load Neutral and Equipment Grounding Termination Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17Hinged Rain Channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17Underground Service Wireway . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17–18Catalog Number Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19

Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20Dimensions and Knockouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31

MP Meter-Pak™ Meter CentersApplication Data

503/2008 © 2008 Schneider Electric All Rights Reserved

Application Data

MP22125 (shown)MPR22125, MPH22125

(Sealing Rings not shown) MP55125, MPR55125, MPH55125, MP66125, MPR66125, MPH66125 (shown)(Top Left Position Omitted on 5-Position Units)

MP33125, MPR33125, MPH33125 (shown)MP42200 (shown)

MPR42200, MPH42200

MP44125 (shown)MPR44125, MPH44125

MP43200, MPR43200MPH43200 (shown)

MP Meter-Pak™ Meter CentersApplication Data

6© 2008 Schneider Electric All Rights Reserved 03/2008

125 A Maximum MP Meter-Pak™ Meter Center Configurations

• Ring-type MP supplied with 4-jaw meter socket without bypass (5th jaw and manual slider type bypass kits can be ordered separately and field-installed).

• Ringless-type MPR supplied with 5-jaw meter socket without bypass (horn-type bypass kits can be ordered separately and field-installed).

• Ringless-type MPH supplied with 5-jaw meter socket with horn-type bypass.

• Both ring- and ringless-type units have provisions for mounting 2-pole, plug-on type QO®, QO-VH, or QOH circuit breakers.

200 A Maximum MP Meter-Pak Meter Center Configurations

• Ring-type MP supplied with 4-jaw meter socket without bypass (5-jaw and manual slider type bypass kits can be ordered separately and field-installed).

• Ringless-type MPR supplied with 5-jaw meter socket without bypass (horn-type bypass kits can be ordered separately and field-installed).

• Ringless-type MPH supplied with 5-jaw meter socket with horn-type bypass.

• Both ring- and ringless-type units have provisions for mounting 2-pole, bolt-on type QOM2-MM or QOM2-MVH circuit breakers.

225 A Maximum MP Meter-Pak Meter Center Configurations

• Ringless-type MPL supplied with 5-jaw meter sockets with lever bypass and jaw release.

• MPL devices have provisions for mounting QBP-TM, QDP-TM, QGP-TM, or QJP-TM 2-pole bolt-on type circuit breakers.

MP64200, MPR64200, MPH64200 (shown)

MP85200, MPR85200, MPH85200, MP86200 (shown), MPR86200, MPH86200

(Top Left Position Omitted on 5-Position Units)MPL32225, MPL53225 (shown), MPL64225

MP Meter-Pak™ Meter CentersApplication Data

703/2008 © 2008 Schneider Electric All Rights Reserved

Type

• Enclosures are indoor/rainproof NEMA Type 3R

• MP, MPH and MPR available in 2-, 3-, 4-, 5-, or 6-position configurations

• MPL available in 2-, 3-, or 4-position configurations

• Suitable only for use as service entrance equipment (cannot be fed from an upstream service disconnect)

• Designed to be wall mounted only, not suitable for use as floor standing equipment

• All unmetered conductor compartments are sealable by the utility company

• Finish: ANSI gray, baked powder coat epoxy electro-deposited over cleaned phosphatized steel

• UL Listed under File E-6294

Service

• 120/240 Vac, 1φ3W

• 120/208 Vac, 1φ3W (derived from a 208Y/120 Vac, 3φ4W network)

Mains Ratings

125 A Maximum MP Meter-Pak Meter Centers

200 A (2-position), 300 A (3-position), 400 A (4-position), 500 A (5-position), and 600 A (6-position) main bus ratings.

200 A Maximum MP Meter-Pak Meter Centers

400 A (2- and 3-position), 600 A (4-position) and 800 A (5- and 6-position) main bus ratings.

225 A Maximum MP Meter-Pak Meter Centers

350 A (2-position), 500 A (3-position), 600 A (4-position) main bus ratings.

Branch Circuit Breaker Provisions

125 A Maximum MP Meter-Pak Meter Centers

Accepts 40–125 A, 2-pole, plug-on type QO, QO-VH, or QOH circuit breakers. (Order circuit breakers separately.)

UL® Listed meter center short circuit current rating (RMS symmetrical amperes) equal to the lowest interrupting rating of installed tenant circuit breaker.

NOTE: For load center series ratings used downstream from metering equipment, refer to the following Data Bulletins: 4100DB0301 and 2700DB9901.

MPH66125

400 A Main Lugs

QO Plug-On Mounting Base

QO2100Plug-On Circuit

Breaker Installed

Ampere Rating10,000 AIR120/240 Vac

22,000 AIR120/240 Vac

42,000 AIR120/240 Vac

40 QO240 QO240VH QOH240

50 QO250 QO250VH QOH250

60 QO260 QO260VH QOH260

70 QO270 QO270VH QOH270

80 QO280 QO280VH QOH280

90 QO290 QO290VH QOH290

100 QO2100 QO2100VH QOH2100

125 QO2125 QO2125VH QOH2125

MP Meter-Pak™ Meter CentersApplication Data

8© 2008 Schneider Electric All Rights Reserved 03/2008

200 A Maximum MP Meter-Pak Meter Centers

Accepts 100–200 A, 2-pole, bolt-on type QOM2-MM or QOM2-MVH circuit breakers. (Order circuit breakers separately.)

UL Listed meter center short circuit current rating (RMS symmetrical amperes) equal to the lowest interrupting rating of tenant circuit breaker installed.

NOTE: For load center series ratings used downstream from metering equipment, refer to Data Bulletins: 4100DB0301 and 2700DB9901.

225 A Maximum MP Meter-Pak Meter Centers

Accepts 70–225 A, 2-pole, bolt-on type, QBP-TM, QDP-TM, QGP-TM, or QJP-TM circuit breakers. Also accepts 40–60 A, 2-pole, plug-on type QO, QO-VH or QOH circuit breakers; but requires the use of EZM125QOA adapter kit. (Order circuit breakers and adapter kit separately).

UL Listed meter center short circuit current rating (RMS symmetrical amperes) equal to the lowest interrupting rating of tenant circuit breaker installed.

Meter Sockets

Standard Meter Socket Configurations

• Rated 200 A continuous duty.

• Front removable spring reinforced jaws equipped with line and load side blade guides.

• Thermoset polyester with fiberglass reinforced base assembly.

• 5th jaw supplied factory-installed on ringless-type MPH and MPR in the 9 o'clock position, 5th jaw can be moved to the 3 or 6 o’clock position as required.

• Ring-type MP supplied with 4-jaw meter socket without bypass.

• Ringless-type MPR supplied with 5-jaw meter socket without bypass.

• Ringless-type MPH supplied with 5-jaw meter socket with horn-type bypass.

• Ringless-type MPL supplied with 5-jaw meter socket with lever bypass and jaw release.

QDP22200TM 2-Pole, Bolt-on Type Circuit Breaker

QOM2-MM or QOM2-MVH Bolt-On Mounting Base

QOM2200MVH Bolt-On Circuit Breaker Installed

Optional 5th Jaw Kit Installed on Ring-Type Device

Ringless-Type MPHIncludes 5-Jaw Meter Socket and Horn Bypass

Ampere Rating 10,000 AIR 120/240 Vac 22,000 AIR 120/240 Vac

100 QOM2100MM QOM2100MVH

125 QOM2125MM QOM2125MVH

150 QOM2150MM QOM2150MVH

175 QOM2175MM QOM2175MVH

200 QOM2200MM QOM2200MVH

Ampere Rating

10,000 AIR 120/240 Vac

25,000 AIR 120/240 Vac

65,000 AIR 120/240 Vac

100,000 AIR 120/240 Vac

40 QO240 1

1 Requires use of EZM125QOA adapter (order separately).

QO240VH 1 2

2 QOVH tenant circuit breakers are rated 22,000 AIR at 120/240 Vac.

QOH240 1 3

3 QOH tenant circuit breakers are rated 42,000 AIR at 120/240 Vac.

50 QO250 1 QO250VH 1 2 QOH250 1 3 —

60 QO260 1 QO260VH 1 2 QOH260 1 3 —

70 QBP22070TM QDP22070TM QGP22070TM QJP22070TM

80 QBP22080TM QDP22080TM QGP22080TM QJP22080TM

90 QBP22090TM QDP22090TM QGP22090TM QJP22090TM

100 QBP22100TM QDP22100TM QGP22100TM QJP22100TM

110 QBP22110TM QDP22110TM QGP22110TM QJP22110TM

125 QBP22125TM QDP22125TM QGP22125TM QJP22125TM

150 QBP22150TM QDP22150TM QGP22150TM QJP22150TM

175 QBP22175TM QDP22175TM QGP22175TM QJP22175TM

200 QBP22200TM QDP22200TM QGP22200TM QJP22200TM

225 QBP22225TM QDP22225TM QGP22225TM QJP22225TM

MP Meter-Pak™ Meter CentersApplication Data

903/2008 © 2008 Schneider Electric All Rights Reserved

Optional Meter Socket

• 5th jaw kit (catalog number 5J) can be field-installed on ring-type MP at the 3, 6, or 9 o’clock position and is required for 120/208 Vac, 1φ3W, service (derived from a 208Y/120 Vac 3φ4W network). One kit required per meter socket, order separately.

• Horn-type bypass kit, catalog number MMHB, can be field-installed on ringless-type MPR. One kit required per meter socket, order separately.

• Manual slider type bypass kit, catalog number MM125MB (for top position only on 125 A, 2-position ring-type MP) or MM200MB (for 125 A and 200 A ring-type MP). One kit required per meter socket, order separately for field-installation.

NOTE: Manual slider type bypass kits limit meter center equipment short circuit current rating to 10,000 RMS symmetrical amperes.

Meter Socket Covers

Optional Meter Socket Sealing Rings for Type MP

• Stainless steel snap-type sealing ring (catalog number ARP00026). Order separately for field-installation.

• Aluminum screw-type sealing ring (catalog number 29008W). Order separately for field-installation.

Ring-Type MP4-Jaw Meter Socket without Bypass

Manual Slider-Type Bypass, Closed PositionMM125MB, MM200MB (shown)

Manual Slider-Type Bypass, Open PositionMM125MB, MM200MB (shown)

Ring-Type MP Meter Socket Cover

• Individual meter socket cover provided for each meter socket.

• Cover cannot be removed with meter installed in meter socket.

• Seal ring is required to secure base of meter ontorim provided on meter socket cover.

• Aluminum snap-type seal ring (catalog number 29209-100-01) is standard on all ring-type MP meter socket covers.

Individual Ring-Type Meter Socket Cover

Snap-Type Sealing Ring Screw-Type Sealing Ring

MP Meter-Pak™ Meter CentersApplication Data

10© 2008 Schneider Electric All Rights Reserved 03/2008

Ringless-Type MPH, MPL, and MPR Meter Socket Covers

• Individual meter socket cover provided for each meter socket.

• Base of meter is supported by brackets extending from meter socket base assembly. Meter socket cover is installed over meter to seal meter base to socket.

• Ringless meter socket covers are each supplied with a stainless steel latch and hasp to accommodate utility seals including lead wire seals, barrel locks, ribbon seals, padlocks, and snap-type seals.

• Ringless meter socket covers are also supplied with a 3/4-inch knockout to accommodate front-entry barrel locks.

• Barrel lock bracket located behind 3/4-inch knockout in each ringless meter socket cover.

• Barrel lock head protector kit (catalog number MMBLC) includes ferrule, lock nut, and seal cap to accommodate 1-inch long barrel lock (barrel lock not included).

Individual Ringless-Type Meter Socket Cover

Barrel Lock Installed Front Entry through Knockout in Ringless Meter Socket Cover

(Reverse View)

Barrel Lock Head Protector Kit MMBLC Installed through Knockout in Ringless Meter Socket Cover

Stainless Steel Latch and Hasp, Ringless Meter Socket Cover

Support Brackets for Base of Meter

MP Meter-Pak™ Meter CentersApplication Data

1103/2008 © 2008 Schneider Electric All Rights Reserved

Utility Pull Box Cover

• Supplied with handles on 3- through 6-position 125 A maximum,2- through 6-position 200 A maximum, and 2- through 4-position 225 A maximum Meter-Pak meter center units.

• Supplied with rotating locking hasp to accommodate utility seals including lead wire seals, barrel locks, ribbon seals, padlocks, and snap-type seals.

Customer/Tenant Compartment Cover

• Removable without interfering with meter covers.

• Supplied with rotating locking hasp to accommodate a padlock (see rotating locking hasp above).

• Supplied with vertical rainproof tenant circuit breaker covers, one per meter socket.

Tenant Circuit Breaker Covers

• Constructed of impact resistant thermoplastic

• Provisions for padlocking or sealing

• Equipped with latch

Mounting Channel

• Mounting channel supplied with 3- through 6-position 125 A maximum and all 200 A and 2- through 4-position 225 A maximum units.

• Mounting flange is formed as a part of the top endwall to permit easy installation.

• Mount the channel to the wall at proper height. Hang unit on channel from mounting flange.

Rotating Mounting Bracket

• Permanently attached to save time

• Easily moved for mounting hole drilling after marking

• Accommodates slight mounting hole misalignment

• Used for permanent mounting of device to wall

Lifting Handles for Pull Box Cover

Hasp with Cover Installed

Circuit Breaker Cover, Closed

Circuit Breaker Cover, Open

Tenant Compartment Circuit Breaker Cover

Mounting Channel

Rotating Locking Hasp

Rotating Mounting Bracket

12© 2008 Schneider Electric All Rights Reserved 03/2008

MP Meter-Pak™ Meter Centers Application Data

Top Endwall Configurations

125 A Maximum MP, MPR, and MPH Meter-Pak Meter Center Top Endwalls

• 2-position unit has utility compartment provisions for mounting one type A hub for use with 1- through 2.5-inch size conduit. Closing plate (Catalog Number ACP) supplied, order hub separately.

• 3- and 4-position units have utility compartment provisions for mounting one type A-L hub for use with 2- through 4-inch size conduit. Closing plate (Catalog Number ACPL) supplied, order hub separately.

• 5- and 6-position units have utility compartment provisions for mounting two type A-L hubs for use with 2- through 4-inch size conduits. Two ACPL closing plates supplied, order hubs separately.

200 and 225 A Maximum MP, MPR, and MPH Meter-Pak Meter Center Top Endwalls

2- through 6-position units have utility compartment provisions for mounting two type A-L hubs for use with 2- through 4-inch size conduit. Two ACPL closing plates supplied, order hubs separately.

Semi-Flush Flange Kits

Prior to installation, semi-flush flange kits can be ordered separately for field modification. (Refer to instructions included in kits for complete directions.)

To drill enclosure top endwall and box sides to secure mounting flanges:

1. Drill 5/16-inch diameter clearance holes at center punched marks provided and secure flanges with 1/4-20 mounting hardware provided.

2. Secure mounting flanges of enclosure to stud wall on three sides (top, left, and right).

3. Cover mounting flanges with building paper and caulk to seal between enclosure and building paper.

225 A Maximum MPL Meter-Pak Meter Center Top Endwalls

2- through 4-position units have utility compartment provisions for mounting two type A-L hubs for use with 2- through 4-inch size conduit. Two ACPL closing plates supplied, order hubs separately.

Semi-Flush Flange Kit

Type A-L Hub Installed3- and 4-Position 125 A Top Endwall

Closing Plate ACP (supplied)2-Position 125 A Top Endwall

Type A Hub Installed2-Position 125 A Top Endwall

Closing Plate ACPL (supplied)3- and 4-Position 125 A Top Endwall

Two Type A-L Hubs Installed5- and 6-Position 125 A Top Endwall and 2- through 6-Position 200 A Top Endwall2- through 4-Position 225 A Top Endwall

Two Closing Plates ACPL (supplied)5- and 6-Position 125 A Top Endwall and 2- through 6-Position 200 A Top Endwall2- through 4-Position 225 A Top Endwall

Description Catalog Number

125 A Maximum 2-Position MPSF12

125 A Maximum 3- and 4-Position MPSF14

125 A Maximum 5- and 6-Position MPSF16

200 A Maximum 2- and 3-Position MPSF23

200 A Maximum 4-Position MPSF24

200 A Maximum 5- and 6-Position MPSF26

Semi-Flush Flange KitMPSF23

MP Meter-Pak™ Meter CentersApplication Data

1303/2008 © 2008 Schneider Electric All Rights Reserved

Knockouts

SymbolConduit Size Hole Diameter

in. [mm] in. [mm]

A 0.50 13 0.88 22

B 0.75 19 1.25 29

C 1.00 25 1.38 35

D 1.25 32 1.75 44

E 1.50 38 2.00 51

F 2.00 51 2.50 64

G 2.50 64 3.00 76

H 3.00 76 3.63 92

I 3.50 89 4.19 105

J 4.00 102 4.63 117

MP Meter-Pak Meter Center Hub and Knockout Configurations

Maximum Tenant Circuit Breaker Ampere Rating and Number of

Positions

CatalogNumber

Top Endwall Pull Box Compartment Bottom EndwallBox Back Tenant Circuit Breaker Compartment

Knockouts

Closing Plate(s) Supplied

Factory-InstalledHub Provisions

Pull Box Compartment Knockout and

Hub Provisions

Tenant Circuit Breaker

Compartment Knockouts

125 A2-Position

MP22125MPH22125MPR22125

(1) ACP (1) Type A(1) Type A Hub or(1) B300 Hub or(1) D, F, G, and (1) A

(2) C, D, F and(1) A (2) C, D, F 1

1 Same knockout pattern on side of box.

125 A3-Position

MP33125MPH33125MPR33125

(1) ACPL (1) Type A–L

(2) Type A–L Hubs or(2) E, F, G, Hand (1) A, BNote: One knockout is provided with I and J rings.

(4) C, D, Fand (1) A, B (4) C, D, F

125 A4-Position

MP44125MPH44125MPR44125

125 A5-Position

MP55125MPH55125MPR55125

(2) ACPL (2) Type A–L(2) Type A–L Hubs or(2) G, H, I, Jand (1) A

(3) C, D, F and (1) A, BProvided per compartment.

(3) C, D, FProvided per compartment.125 A

6-Position

MP66125MPH66125MPR66125

200 A2-Position

MP42200MPH42200MPR42200

(2) ACPL (2) Type A–L(2) Type A–L Hubs or(2) G, H, I, Jand (1) A

(4) C, D, F and(1) A, B (3) C, D, F

200 A3-Position

MP43200MPH43200MPR43200

200 A4-Position

MP64200MPH64200MPR64200

(2) ACPL (2) Type A–L(2) Type A–L Hubs or(2) G, H, I, Jand (1) A

(4) C, D, Fand (1) A, B (4) C, D, F

200 A5-Position

MP85200MPH85200MPR85200

(2) ACPL (2) Type A–L(2) Type A–L Hubs or(2) G, H, I, Jand (1) A, B, C

(3) C, D, Fand (1) A, BProvided per compartment.

(3) C, D, FProvided per compartment.200 A

6-Position

MP86200MPH86200MPR86200

225 A2-Position MPL32225 (2) ACPL (2) Type A–L

(2) Type A–L Hubs or(2) E, F, G, H, I, J and(1) A, B

(3) C, D, E, F and(1) A, B (3) C, D, E, F

225 A3-Position MPL53225 (2) ACPL (2) Type A–L

(2) Type A–L Hubs or(2) E, F, G, H, I, J and(1) A, B

(4) C, D, E, F and(1) A, B

(4) C, D, E, F

225 A4-Position MPL64225 (2) ACPL (2) Type A–L

(2) Type A–L Hubs or(2) E, F, G, H, I, J and(1) A, B

(5) C, D, E, F and(1) A, B (5) C, D, E, F

14© 2008 Schneider Electric All Rights Reserved 03/2008

MP Meter-Pak™ Meter Centers Application Data

Main Lugs SectionService Conductor Termination Data• Neutral bus is bonded permanently to the enclosure

• Suitable only for use as service equipment

Alternate Lug KitsAvailable for use on 3–6 position 125 A, all 200 A, and all 225 A Meter-Pak meter center units (order separately):

NEMA/EUSERC Lug Landing Kit• Catalog numbers MMSK2 and MMSK4 (order separately).

• MMSK2 is available for use on 3- through 6-position 125 A and all 200 A Meter-Pak meter center units.

• MMSK4 is available for use ONLY on MPL53225 and MPL64225, Not required for MPL32225.

• Kits include three bus bar lug landing pads and mounting hardware to secure pads to main cross bus.

• Each lug landing pad with MMSK2 is supplied with two 1/2-13 studs; MMSK4 with four 1/2-13 studs; all on 1-3/4 inch center. Kits include lug mounting hardware.

• MMSK2 is rated 600A maximum when applied in EUSERC areas.

• Order one kit per Meter-Pak device, order lugs separately (refer to each device wiring diagram for lug catalog numbers).

Main Lugs Compartment

MMLK600

MMSK2

MMLK250

MMLK500

MMSK4

125 A Maximum MP Meter-Pak™ Meter Center Service Conductor Termination Data

Number of Meter Socket Positions

Main Bus Rating (Amperes)

Factory-Installed Main Lugs Capacity

(Amperes)

Line Phase and Neutral Lug Wire Size

Al/Cu AWG kcmil

2 200 A 200 A (1) #4-250

3 300 A 300 A(1) 1/0-600

or(2) 1/0-250

4 400 A 400 A

5 500 A 400 A Al or 500 A Cu

6 600 A 400 A Al or 500 A Cu

200 A Maximum MP Meter-Pak Meter Center Service Conductor Termination Data

2 400 A 400 A (1) 1/0-600or

(2) 1/0-2503 400 A 400 A

4 600 A 400 A Al or 500 A Cu

5 800 A 600 A Al or 750 A Cu(2) 3/0-500

6 800 A 600 A Al or 750 A Cu

225 A Maximum MP Meter-Pak Meter Center Service Conductor Termination Data

2 350 A 350 A (1) 1/0-600or

(2) 1/0-2503 500 A 400 A

4 600 A 400 A

Catalog Number Lug Type (Mechanical) Lug Wire Size Al/Cu AWG/kcmil

MMLK250 1

1 Standard lug kit supplied factory-installed on 3–6 position 125 A units, 2–4 position 200 A units, and 2–4 position 225 A units.

Double-Barrel (1) 1/0-600 or (2) 1/0-250

MMLK500 Double-Barrel (2) 3/0-500

MMLK600 2

2 Kit includes NEMA/EUSERC lug landing pads (MMSK2). Kit is rated 800 A maximum (600 A maximum in EUSERC areas).

Double-Barrel (2) #2-600

MP Meter-Pak™ Meter CentersApplication Data

1503/2008 © 2008 Schneider Electric All Rights Reserved

MMSK2

MMSK4

Lugs for Use with NEMA/EUSERC Lug Landing Kit MMSK2

Mains RatingLug

ManufacturerCatalog Number 1 Lug Type

Lug Wire Size AWG/kcmil

Crimping Tool or Torque

300 A

Anderson

VACL-500-12BN

Compression

4/0–500 Al/Cu VC-6FT

VCEL-060-12H2 400–600 Al, 400–500 Cu VC-6FT

VCEL-075-12H2 500 Cu VC-6FT

VHCL-500-12BN 4/0–500 Cu VC-6FT

VHCL-400-12BN 4/0–400 Cu VC-6FT

VHCL-350-12BN 3/0–350 Cu VC-6FT

ILSCOTA-600-2N 2

Mechanical#2-600 Al/Cu 375 lb-in. (42 N•m)

AU-600-2N (2) #2-600 Al/Cu 500 lb-in. (57 N•m)

400 A

Anderson VHCL-600-12BN Compression 250–600 Cu VC-6FT

ILSCOTA-600-2N 2

Mechanical#2-600 Al/Cu 375 lb-in. (42 N•m)

AU-600-2N (2) #2-600 Al/Cu 500 lb-in. (57 N•m)

500–600 AILSCO

AU-600-2NMechanical

(2) #2-600 Al/Cu 500 lb-in. (57 N•m)

800 A AU-600-2N (2) 3/0-500 Al/Cu 500 lb-in. (57 N•m)

1 Lugs are not available from Schneider Electric and must be ordered separately from Anderson or ILSCO.2 Available by ordering kit catalog number CMELK4 (kit includes 4 lugs).

Lugs for Use with NEMA Lug Landing Kit MMSK4

Catalog NumberLug

ManufacturerCatalog Number 1 Lug Type

Lug Wire Size AWG/kcmil

Crimping Tool or Torque

MPL32225 2

Anderson

L1D2-600Mechanical

#2-600 Al/Cu 550 lb-in. (62 N•m)

L1D2-800 300–800 Al/Cu 550 lb-in. (62 N•m)

VCEL-050-12H2

Compression

2/0–500 Al/Cu VC-6FT

VCEL-060-12H2 400–600 Al or 400–500 Cu VC-6FT

VCEL-075-12H2 500–750 Al or 500 Cu VC-6FT

VACL-500-12BN 4/0–500 Al/Cu VC-6FT

VACL-600-12BN 350–600 Al or 350–500 Cu VC-6FT or VC8

VACL-750-12BN 500–750 Al or 500 Cu VC-6FT or VC8

VACL-1000-12BN 750–1000 Al VC8

VHCL-500-12BN 4/0–500 Cu VC-6FT or VC-7FT

VHCL-600-12BN 3/0–350 Cu VC-6FT

ILSCO

TA-600-2N 3

Mechanical

#2-600 Al/Cu 375 lb-in. (42 N•m)

TA-800-2N 300–800 Al/Cu 500 lb-in. (57 N•m)

AU-600-2N (2) #2-600 Al/Cu 500 lb-in. (57 N•m)

Connector Manufacturing

Company

A1B2-600-2

Mechanical

#2-600 Al/Cu 375 lb-in. (42 N•m)

2AB2-600 (2) #2-600 Al/Cu 375 lb-in. (42 N•m)

3AB2-250 (3) #6-250 Al/Cu 275 lb-in. (31 N•m)

L1D2-800 300–800 Al/Cu 550 lb-in. (62 N•m)

MPL53225

Anderson

L1D2-600 Mechanical #2-600 Al/Cu 550 lb-in. (62 N•m)

VCEL-050-12H2

Compression

2/0–500 Al/Cu VC-6FT

VCEL-060-12H2 400–600 Al, 400–500 Cu VC-6FT

VACL-500-12BN 4/0–500 Al/Cu VC-6FT

VHCL-500-12BN 4/0–500 Cu VC-6FT or VC-7FT

VHCL-600-12BN 250–600 Cu VC-6FT, VC-7FT, or VC-8

ILSCO TA-600-2N 3 Mechanical #2-600 Al/Cu 375 lb-in. (42 N•m)

Connector Manufacturing

Company

A1B2-600-2Mechanical

#2-600 Al/Cu 375 lb-in. (42 N•m)

3AB2-250 (3) #6-250 Al/Cu 275 lb-in. (31 N•m)

1) Lugs are not available from Schneider Electric and must be ordered separately from Anderson or ILSCO.2) Lug landing kit is not required for this device.3) Available by ordering kit catalog number CMELK4 (kit includes 4 lugs). Continued on next page

MP Meter-Pak™ Meter CentersApplication Data

16© 2008 Schneider Electric All Rights Reserved 03/2008

Tenant Circuit Breaker Termination Data

MPL64225

Anderson

L1D2-600Mechanical

#2-600 Al/Cu 550 lb-in. (62 N•m)

L1D2-800 300–800 Al/Cu 550 lb-in. (62 N•m)

VCEL-050-12H2

Compression

2/0–500 Al/Cu VC-6FT

VCEL-060-12H2 400–600 Al or 400–500 Cu VC-6FT

VCEL-075-12H2 500–750 Al or 500 Cu VC-6FT

VACL-500-12BN 4/0–500 Al/Cu VC-6FT

VACL-600-12BN 350–600 Al or 350–500 Cu VC6-FT or VC8

VACL-750-12BN 500–750 Al or 500 Cu VC6-FT or VC8

VHCL-500-12BN 4/0–500 Cu VC6-FT or VC7-FT

VHCL-600-12BN 250–600 Cu VC6-FT, VC7-FT or VC8

ILSCO

TA-600-2N 3

Mechanical

#2-600 Al/Cu 375 lb-in. (42 N•m)

TA-800-2N 300–800 Al/Cu 500 lb-in. (57 N•m)

AU-600-2N (2) #2-600 Al/Cu 500 lb-in. (57 N•m)

Connector Manufacturing

Company

A1B2-600-2

Mechanical

#2-600 Al/Cu 375 lb-in. (42 N•m)

2AB2-600 (2) #2-600 Al/Cu 375 lb-in. (42 N•m)

3AB2-250 (3) #6-250 Al/Cu 275 lb-in. (31 N•m)

L1D2-800 300–800 Al/Cu 550 lb-in. (62 N•m)

1 Lugs are not available from Schneider Electric and must be ordered separately from Anderson or ILSCO.2 Lug landing kit is not required for this device.3 Available by ordering kit catalog number CMELK4 (kit includes 4 lugs).

Lugs for Use with NEMA Lug Landing Kit MMSK4

Catalog NumberLug

ManufacturerCatalog Number 1 Lug Type

Lug Wire Size AWG/kcmil

Crimping Tool or Torque

MMSK4

125 A Maximum MP Meter-Pak Meter Center Tenant Circuit Breaker Termination Data

Tenant Circuit Breaker

Type and Ampere Rating Lug Wire Size

QO, QO-VH, and QOH 2-pole, 40–70 A #8–#2 AWG Al/Cu

QO, QO-VH, and QOH 2-pole, 80–125 A #4–2/0 AWG Al/Cu

200 A Maximum MP Meter-Pak Meter Center Tenant Circuit Breaker Termination Data

Tenant Circuit Breaker

Type and Ampere Rating Lug Wire Size Wire Bending Space

QOM2-MM and QOM2-MVH2-pole, 100–200 A #4 AWG–300 kcmil Al/Cu #4 AWG–250 kcmil Al/Cu 1

1 Bottom tenant circuit breaker position has wire bending space to accommodate 300 kcmil wire, for bottom feed only.

225 A Maximum MP Meter-Pak Meter Center Tenant Circuit Breaker Termination Data

Tenant Circuit Breaker

Type and Ampere Rating Lug Wire Size Wire Bending Space

QBP-TM, QDP-TM, QGP-TM, and QJP-TM,

2-pole, 70–225 A#4 AWG–300 kcmil Al/Cu #4 AWG–300 kcmil Al/Cu

Continued from previous page

MP Meter-Pak™ Meter CentersApplication Data

1703/2008 © 2008 Schneider Electric All Rights Reserved

Service Grounding/Load Neutral and Equipment Grounding Termination Data

• Service grounding/load neutral lugs, located in the tenant compartment, are bonded to the enclosure.

• Two service grounding lugs provided per device.

• One load neutral lug and one equipment grounding lug are provided for each tenant circuit breaker position.

125 A Maximum MP, MPH, and MPR Meter-Pak Meter Centers

Load neutral and service grounding lugs will accept one #14-2/0 AWG Cu or one #12-2/0 AWG Al conductor.

200 A Maximum MP, MPH, and MPR Meter-Pak Meter Centers

Load neutral and service grounding lugs will accept one #6 AWG–300 kcmil Al/Cu conductor.

225 A Maximum MP, MPH, and MPR Meter-Pak Meter Centers

Load neutral and service grounding lugs will accept one #4 AWG–300 kcmil Al/Cu conductor.

Hinged Rain Channel

Rain channel is hinged at bottom of tenant compartment allowing easy access to wiring gutter for pulling wires.

Underground Service Wireway

Square D brand Underground Service Wireways are a convenient solution for protecting a utility's underground service conductors that terminate in MP Meter-Pak Meter Centers.

These Underground Service Wireways are not load-bearing; they are intended for use only as a means to cover and secure service entrance cables prior to entering a wall-mounted Square D MP Meter-Pak device. The units connect easily to any MP Meter-Pak Meter Center by attaching to tapped hub provisions in the bottom endwall of the metering device.

• Cover latch accommodates up to three different types of utility seals.

• All locking provisions are made of durable, corrosion-resistant stainless steel for long-lasting security.

• Mounts easily to MP Meter-Pak device’s underground, bolt-on hub provisions using supplied hardware.

• Open bottom with ½ inch srolled edge reduces possibility of cutting conductor insulation.

• Wireway covers are secured by latching means (no screws to lose).

• Gasketed, bushed openings in top provide watertight seal between the wireway and MP Meter-Pak device.

• Constructed of 14-gauge painted galvanneal steel for superior corrosion protection in all applications.

Equipment Grounding Lugs

Service Grounds and Load Neutrals

Hinged Rain Channel

MP43X11PED Shown with Cover Off (left) and

On (above)

18© 2008 Schneider Electric All Rights Reserved 03/2008

MP Meter-Pak™ Meter Centers Application Data

Underground Service Wireway Devices

Catalog Number DescriptionHeight Width

in. mm in. mm

MP43X11PED Underground Service Wireway 43 1092 11 279

MP43X8PED Underground Service Wireway 43 1092 8 203

MP35X11PED Underground Service Wireway 35 889 11 279

MP12X11PEDEXT Underground Service Wireway One-foot Extension 12 305 11 279

MP12X8PEDEXT Underground Service WirewayOne-foot Extension 12 305 8 203

Selection Chart

Wireway Catalog Number

Grade to Device Bottom

Grade to Meter

MP Meter-Pak

Device

Bottom Meter

Top Meter

in. mm in. mm

MP43X8PED 25 in. [635 mm] 42.5 1080 51.5 1308

MP22125

MPR22125

MPH22125

MP43X11PED 25 in. [635 mm]

36.0 914

54.0 1372

MP33125

MPR33125

MPH33125

63.0 1600

MP44125

MPR44125

MPH44125

54.0 1372

MP55125

MPR55125

MPH55125

MP66125

MPR66125

MPH66125

37.25 946

46.25 1175

MP42200

MPR42200

MPH42200

55.25 1403

MP43200

MPR43200

MPH43200

64.25 1632

MP64200

MPR64200

MPH64200

55.25 1403

MP85200

MPR85200

MPH85200

MP86200

MPR86200

MPH86200

MP35X11PED 16.625 in.[422 mm] 50.625 1286 64.625 1642 MPL32225

MP43X11PED 25 in.[635 mm] 38.375 975 66.375 1686 MPL43225

MP35X11PED 16.625 in.[422 mm] 30.0 762 72.0 1829 MPL64225

MP Meter-Pak

Unit

Wireway Unit

Grade

MeasurementGuideWireway

Extension

Bottom of Device

Bottom Meter Height

Top Meter Height

12 in.

18 in.

Underground Service Wireway One-Foot Extension Selection Guide*

For applications requiring additional depth, or for sloped grades, the one-foot extension can be installed to the bottom of the underground service wireway with supplied hardware.

*Selection based on Underground Service Wireway catalog numbers.

Wireway Extension Catalog Number

Wireway Catalog Number

MP12X11PEDEXT MP43X11PEDMP35X11PED

MP12X8PEDEXT MP43X8PED

MP Meter-Pak™ Meter CentersCatalog Number Description

1903/2008 © 2008 Schneider Electric All Rights Reserved

Catalog Number Description

Number Segment

Character Description MP H 4 4 125

Device Name MP Meter-Pak Meter Center

Socket/Bypass Type

Blank Ring Type

R Ringless with 5th Jaw

H Ringless with Horn Bypass and 5th Jaw

L Ringless with Lever Bypass, Jaw Release and 5th Jaw

Bus Ampacity

2 200 A

3 300 A

4 400 A

5 500 A

6 600 A

8 800 A

Number of Meter Sockets

2 2-Positions MP, MPH, MPL, and MPR

3 3-Positions MP, MPH, MPL, and MPR

4 4-Positions MP, MPH, MPL, and MPR

5 5-Positions MP, MPH, and MPR

6 6-Positions MP, MPH, MPL, and MPR

Max. Tenant Circuit Breaker Amperage

125 125 A

200 200 A

225 225 A

MP Meter-Pak™ Meter Centers

20© 2008 Schneider Electric All Rights Reserved 03/2008

Select MP Meter-Pak meter center short circuit current rating RMS symmetrical amperes from table on page 3, then make selections from the following:

Step 1: Select Ring or Ringless Type MP Meter-Pak™ Meter Centers

Ampere RatingNumber of Positions

Metering Equipment

Ring-Type, 4-Jaw Catalog Number

Ringless Type, 5-Jaw

No BypassCatalog Number

Horn BypassCatalog Number

Lever Bypass Catalog Number

125 A(Use QO® Circuit

Breakers)

2 MP22125 MPR22125 MPH22125 —

3 MP33125 1 MPR33125 MPH33125 —

4 MP44125 1 MPR44125 MPH44125 —

5 MP55125 1 MPR55125 MPH55125 —

6 MP66125 1 MPR66125 MPH66125 —

200 A(Use QOM2

Circuit Breakers)

2 MP42200 1 MPR42200 MPH42200 —

3 MP43200 1 MPR43200 MPH43200 —

4 MP64200 1 MPR64200 MPH64200 —

5 MP85200 1 MPR85200 MPH85200 —

6 MP86200 1 MPR86200 MPH86200 —

225 A(Use QB, QD, QG or QJ

Circuit Breakers)

2 — — — MPL32225

3 — — — MPL53225

4 — — — MPL64225

1 Meets EUSERC standards with addition of lug landing kit, MMSK2.

Step 2: Select Tenant Circuit Breakers

DeviceType

Ampere Rating

10,000 AIR 120/240 Vac

22,000 AIR 120/240 Vac

25,000 AIR 120/240 Vac

42,000 AIR 120/240 Vac

65,000 AIR 120/240 Vac

100,000 AIR 120/240 Vac

125 A

40 QO240 QO240VH — QOH240 — —

50 QO250 QO250VH — QOH250 — —

60 QO260 QO260VH — QOH260 — —

70 QO270 QO270VH — QOH270 — —

80 QO280 QO280VH — QOH280 — —

90 QO290 QO290VH — QOH290 — —

100 QO2100 QO2100VH — QOH2100 — —

125 QO2125 QO2125VH — QOH2125 — —

200 A

100 QOM2100MM QOM2100MVH — — — —

125 QOM2125MM QOM2125MVH — — — —

150 QOM2150MM QOM2150MVH — — — —

175 QOM2175MM QOM2175MVH — — — —

200 QOM2200MM QOM2200MVH — — — —

225 A

40 QO240 2 QO240VH 2 — QOH240 2 — —

50 QO250 2 QO250VH 2 — QOH250 3 — —

60 QO260 2 QO260VH 2 — QOH260 3 — —

70 QBP22070TM — QDP22070TM — QGP22070TM QJP22070TM

80 QBP22080TM — QDP22080TM — QGP22080TM QJP22080TM

90 QBP22090TM — QDP22090TM — QGP22090TM QJP22090TM

100 QBP22100TM — QDP22100TM — QGP22100TM QJP22100TM

110 QBP22110TM — QDP22110TM — QGP22110TM QJP22110TM

125 QBP22125TM — QDP22125TM — QGP22125TM QJP22125TM

150 QBP22150TM — QDP22150TM — QGP22150TM QJP22150TM

175 QBP22175TM — QDP22175TM — QGP22175TM QJP22175TM

200 QBP22200TM — QDP22200TM — QGP22200TM QJP22200TM

225 QBP22225TM — QDP22225TM — QGP22225TM QJP22225TM2 Requires use of EZM125QOA adapter (order separately).3 Order only. Not stocked in PDS.

MP Meter-Pak™ Meter CentersProduct Selection

2103/2008 © 2008 Schneider Electric All Rights Reserved

Step 3: Choose Accessories and / or Replacement Parts

Accessories—DescriptionCatalog Number

5th Jaw Kit (one per kit) 5J

Barrel Lock Head Protector Kit (use on MPH, MPL and MPR only; barrel lock not included) MMBLC

QO Adapter for Bolt-on QB, QD, QG and QJ Tenant Circuit Breakers (40–125 A, 2-pole) EZM125QOA

Horn Bypass Kit (use on MPR and MPH only) MMHB

Manual Slider Type Bypass:

125 A Ring Type 2-Position Top Meter (only) MM125MB 1

125 A and 200 A Ring Type MM200MB 1

Sealing Rings:

Snap-type Aluminum (standard) 29209-100-01

Screw-type Aluminum 29008W

Snap-type Stainless Steel ARP00026

LEXAN® Meter Socket Closing Plate 29007

Optional Lug Kits (3 Lugs per kit):

(1) 1/0-600 AWG/kcmil or (2) 1/0-250 per phase Al/Cu MMLK250 2 3

(2) 3/0-500 AWG/kcmil per phase Al/Cu MMLK500 3

(2) 2-600 AWG/kcmil per phase Al/Cu MMLK600 3

Semi-flush Kits:

125 A, 2-Position MPSF12

125 A, 3- and 4-Position MPSF14

125 A, 5- and 6-Position MPSF16

200 A, 2- and 3-Position MPSF23

200 A, 4-Position MPSF24

200 A, 5- and 6-Position MPSF26

NEMA/EUSERC Lug Landing Kit: For 3- through 6-position 125 A and all 200 A devices.Each pad rated 600 A maximum and includes (2) 1/2-13 studs and mounting hardware.

MMSK2 3

NEMA Lug Landing Kit:For use ONLY on MPL32225, MPL53225 and MPL64225 with optional lugs (see Table on page 16 for lugs) MMSK4

1 The meter center short circuit current rating is 10,000 RMS symmetrical amperes when manual slider-type bypass is used. Not rated for continuous duty.2 Standard lug for 3- through 6-position 125 A and 2- through 4-position 200 A devices.3 Cannot be installed on 2-position 125 A devices.

MP Meter-Pak™ Meter Centers

22© 2008 Schneider Electric All Rights Reserved 03/2008

Dimensions

Supplied with ACP Closing Plate (for Underground Service).

Order Type A Hub Separately (for Overhead Service).

3.67[93]

1.97[50]

7.10[180] 0.19

[5]

12.28[312]9.37[238]

1.38[35]

24.31[617]

2.56[65]

Embossed Mounting Holes(4 Locations)

0.25 Dia. [6]

37.50[953]

9.00[229]

LinePhaseLugs 18.50

[470]

11.25[286]

8.62[219]

C, D, F

6.97[177]

3.77[96] 4.70

[119]

LineNeutralLug

12.13[308]

1.79[45]

0.83[21]

2.09[53]

1.75[44]

C, D, F

4.70[119]

3.08[78]

8.14[207]

A or B300Hub ProvisionD, F, G

A

0.42 Dia.[11]

0.09 Dia.[2]

0.09[2] x 0.33

[8]Slot

Ringless Cover Latch

Seal Bracket

0.10[3]

Dia. 0.10[3]

x 0.40[10]

Slot

MP22125MPR22125MPH22125

Mounting Feet

2.56[65]

From Top to Center of Embossed

Mounting Holes

24.31[617]

C, D, F

1.75[44] 3.77

[96]

6.97[177]

0.42[11]

Dia.

Knockouts

SymbolConduit Size Hole Diameter

in. mm in. mm

A 0.50 13 0.88 22

B 0.75 19 1.25 32

C 1.00 25 1.38 35

D 1.25 32 1.75 44

E 1.50 38 2.00 51

F 2.00 51 2.50 64

G 2.50 64 3.00 76

H 3.00 76 3.63 92

I 3.50 89 4.13 105

J 4.00 102 4.63 118

Dimensions: in.

[mm]

2.32[60]

0.38[10]

Dia.

0.95[24]

1.73[44]

MP Meter-Pak™ Meter CentersProduct Selection

2303/2008 © 2008 Schneider Electric All Rights Reserved

Knockouts

SymbolConduit Size Hole Diameter

in. mm in. mm

A 0.50 13 0.88 22

B 0.75 19 1.25 32

C 1.00 25 1.38 35

D 1.25 32 1.75 44

E 1.50 38 2.00 51

F 2.00 51 2.50 64

G 2.50 64 3.00 76

H 3.00 76 3.63 92

I 3.50 89 4.13 105

J 4.00 102 4.63 118

Supplied with ACPL Closing Plate (for Underground Service).

Order Type A–L Hub Separately (for Overhead Service).

6.07[154]

2.76[70]

24.34[618] 12.00

[305]4.87[124]

Top Position Omitted on 3-Position Unit

7.28[185](NTS)

0.75[19]

47.37[1203]

6.53[166]

LinePhaseLugs

CoverLiftingHandles

3.44[87]

Typical

48.12[1222]

9.00[229]

TypicalC, D, F

5.58[142]

24.19[614]

1.75[44]

2.29[58]

6.85[174]10.05[255]

13.50[343]

5.25[133]

2.84[72] 11.19

[284]

23.62[600]

MP33125MPR33125MPH33125

MP44125MPR44125MPH44125

A–L Hub ProvisionE, F, G, H, I, J

A–L Hub ProvisionE, F, G, H

A, B

A, B

C, D, F

3.00[76]

9.00[229]3.20

[81]

4.75[121]

1.78[45]

1.80[46]

0.42 Dia.[11]

0.09 Dia.[2]

0.09[2] x 0.33

[8]Slot

Ringless Cover Latch

Seal Bracket

0.10[3]

Dia. 0.10[3]

x 0.40[10]

Slot

Mounting Feet

0.42[11]

Dia.

Dimensions: in.[mm]

0.38[10]

Dia.

0.95[24]

1.73[44]

24© 2008 Schneider Electric All Rights Reserved 03/2008

MP Meter-Pak™ Meter Centers Product Selection

N

Dimensions: in.

[mm]

Supplied with ACPL Closing Plate (for Underground Service).

Order Type A Hub Separately (for Overhead Service).

6.00[152]

3.00[76]

14.92[379]

2.99[76]

1.75[44]

15.23[387]

39.46[926]

4.70[119]

12.00[305]

7.36[187]

2.76[70]

Top Position Omitted on 5-Position Unit

LinePhaseLugs

CoverLiftingHandles

3.44[87]

Typical

C, D, F

2.95[75]

2.65[67]

42.37[1076]

23.62[600]

9.00[229]

Typical

11.19[284]

20.75[527]

5.85[149]

7.75[197]9.05[230] 36.31

[922]

3.02[77]

6.22[158]

9.42[239]

7.28[185](NTS)

0.75[19]

41.62[1057]

6.53[166]

0.42 Dia.[11]

0.09 Dia.[2]

0.09[2] x 0.33

[8]Slot

Ringless Cover Latch

2.61[66]

18.02[458]

3.20[81]

C, D, F

A, B

3.20[81]

A

15.07[383]

A-L Hub ProvisionG, H, I, J

Seal Bracket

0.10[3]

Dia. 0.10[3]

x 0.40[10]

Slot

0.42[11]

Dia.

1.73[44]

0.95[24]

Mounting Feet

MP55125MPR55125MPH55125

MP66125MPR66125MPH66125

0.38[10]

Dia.

Knockouts

SymbolConduit Size Hole Diameter

in. mm in. mm

A 0.50 13 0.88 22

B 0.75 19 1.25 32

C 1.00 25 1.38 35

D 1.25 32 1.75 44

E 1.50 38 2.00 51

F 2.00 51 2.50 64

G 2.50 64 3.00 76

H 3.00 76 3.63 92

I 3.50 89 4.13 105

J 4.00 102 4.63 118

MP Meter-Pak™ Meter CentersProduct Selection

2503/2008 © 2008 Schneider Electric All Rights Reserved

Knockouts

SymbolConduit Size Hole Diameter

in. mm in. mm

A 0.50 13 0.88 22

B 0.75 19 1.25 32

C 1.00 25 1.38 35

D 1.25 32 1.75 44

E 1.50 38 2.00 51

F 2.00 51 2.50 64

G 2.50 64 3.00 76

H 3.00 76 3.63 92

I 3.50 89 4.13 105

J 4.00 102 4.63 118

Supplied with ACPL Closing Plate (for Underground Service).

Order Type A Hub Separately (for Overhead Service).

9.70[246] 3.70

[94]

2.58[66]

29.44[748]

7.25[184]

8.28[210](NTS)

C, D, F

7.53[191]

LinePhaseLugs

LineNeutralLugs 9.00

[229]Typical

12.22[310]

24.62[625]

28.00[711]

31.50[800]

43.41[1103]

2.25[57]

2.70[69]

29.31[744]

12.15[309]

6.10[155]

12.55[319]

8.38[213]

MP42200MPR42200MPH42200

MP43200MPR43200MPH43200

C, D, F A, B

1.94[49]

2.66[68]

15.48[393]

3.33[85]

(Typ.) 9.20[234]

10.41[264]

3.04[77]

A-L Hub ProvisionG, H, I, J

0.75[19]

42.66[1084]

Top Position Omitted on 2-Position Unit

0.42 Dia.[11]

0.09 Dia.[2]

0.09[2] x 0.33

[8]Slot

Ringless Cover Latch

Seal Bracket

0.10[3]

Dia. 0.10[3]

x 0.40[10]

Slot

0.42[11]

Dia.

1.73[44]

0.95[24]

Mounting Feet

0.38[10]

Dia.

3.00[76]

Dimensions: in.

[mm]

26© 2008 Schneider Electric All Rights Reserved 03/2008

MP Meter-Pak™ Meter Centers Product Selection

Supplied with ACPL Closing Plate (for Underground Service). Order Type A-L Hub Separately

(for Overhead Service). 9.70[246] 3.70

[94]

0.75[19]

29.31[744]

2.58[66]

29.44[748]9.82

[249]7.36[187]

8.25[210](NTS)

LinePhaseLugs

LineNeutralLugs

C, D, F

52.00[1321]

28.00[711]

9.00[229]Typ.

12.22[310]

24.62[625]

31.50[800]

51.25[1302]

7.53[191]

8.38[213]

12.55[319]5.85

[149]

2.23[57]

5.65[144]

2.45[62] 12.15

[309]

10.37[263]

C, D, FA, B1.94

[49]

2.66[68]

3.33[85]

(Typ.)15.48[393]

3.00[76]

9.20[234]

MP64200MPR64200MPH64200

Dimensions: in.

[mm]

A-L Hub ProvisionG, H, I, J

3.04[77]

Knockouts

SymbolConduit Size Hole Diameter

in. mm in. mm

A 0.50 13 0.88 22

B 0.75 19 1.25 32

C 1.00 25 1.38 35

D 1.25 32 1.75 44

E 1.50 38 2.00 51

F 2.00 51 2.50 64

G 2.50 64 3.00 76

H 3.00 76 3.63 92

I 3.50 89 4.13 105

J 4.00 102 4.63 118

0.42 Dia.[11]

0.09 Dia.[2]

0.09[2] x 0.33

[8]Slot

Ringless Cover Latch

Seal Bracket

0.10[3]

Dia. 0.10[3]

x 0.40[10]

Slot

0.42[11]

Dia.

0.38[10]

Dia.

1.73[44]

0.95[24]

Mounting Feet

MP Meter-Pak™ Meter CentersProduct Selection

2703/2008 © 2008 Schneider Electric All Rights Reserved

20.12[511]

2.66[68]

6.20[68]

0.42 Dia.[11]

0.09 Dia.[2]

0.09[2] x 0.33

[8]Slot

Ringless Cover Latch

Seal Bracket

0.10[3]

Dia. 0.10[3]

x 0.40[10]

Slot

0.42[11]

Dia.

0.38[10]

Dia.

1.73[44]

0.95[24]

Mounting Feet

Supplied with ACPL Closing Plate (for Underground

Service). Order Type A-L Hub Separately (for Overhead Service).

26.34[669]20.34

[517]

2.58[66]

46.68[1186]

9.82[249]

7.36[187]

12.00[305]

9.82[249]Top Left

Position Omitted on 5-Position Unit

LinePhaseLugs

LineNeutral

Lugs

C, D, F

8.28[210](NTS)

0.75[19]

42.66[1084]

7.53[191]

43.41[1321]

28.25[718]

9.00[229]Typ.

12.22[310]

24.50[622]

31.50[800]

2.23[57]

2.95[75]

6.35[161]

8.60[218]

29.25[743]

46.56[1183]

5.00[127]

10.81[275]

14.20[361]

C, D, F A, B, CA-L Hub ProvisionG, H, I, J

3.33[85]

(Typ.)

4.53[115]

1.93[49]

MP85200MPR85200MPH85200

MP86200MPR86200MPH86200

3.04[77]

Knockouts

SymbolConduit Size Hole Diameter

in. mm in. mm

A 0.50 13 0.88 22

B 0.75 19 1.25 32

C 1.00 25 1.38 35

D 1.25 32 1.75 44

E 1.50 38 2.00 51

F 2.00 51 2.50 64

G 2.50 64 3.00 76

H 3.00 76 3.63 92

I 3.50 89 4.13 105

J 4.00 102 4.63 118

Dimensions: in.

[mm]

12.15[309]

28© 2008 Schneider Electric All Rights Reserved 03/2008

MP Meter-Pak™ Meter Centers Product Selection

Supplied with ACPL Closing Plate (for Underground Service). Order Type A-L Hub Separately

(for Overhead Service).

8.36[212]

2.62[67]

2.81[71]

19.43[494]

Cover Knockout for use with Utility Barrel Lock

Individual Meter Socket Covers; Ringless Style (Supplied with Cover Sealing Latches)

C, D, E, F

60.25[1530]

14.00[356]

34.00[864]

26.76[680]

7.10[180]

2.20[56]

3.25[83]

4.12[105]

10.47[266]

4.43[113]

LineNeutralLugs

21.87[556]

5.72[145]

9.62[244](NTS)

0.34[9]

1.50[38]

0.75[19]

To Top of Mounting Channel

Mounting Channel Detail

0.42[11]

Dia.

0.09 Dia.[2]

0.09[2] x 0.33

[8]Slot

Ringless Cover Latch

(2) 1/2–13 Studs

1.75[44]

1.75[44]

C, D, E, FA, B

3.00[76]

8.87[225]

5.34[138]

1.89[48]

4.50[114] 1.87

[48]5.37[136]

9.00[229]

5.93[151]

2.68[68]

A-L Hub Provision E, F, G, H, I, J

Tenant Circuit Breaker Doors (Lockable)

Dimensions: in.

[mm]

Lug Detail

MPL32225

LinePhase Lugs

Knockouts

SymbolConduit Size Hole Diameter

in. mm in. mm

A 0.50 13 0.88 22

B 0.75 19 1.25 32

C 1.00 25 1.38 35

D 1.25 32 1.75 44

E 1.50 38 2.00 51

F 2.00 51 2.50 64

G 2.50 64 3.00 76

H 3.00 76 3.63 92

I 3.50 89 4.13 105

J 4.00 102 4.63 118

0.95[24]1.73

[44]

0.38[10]

Dia.

Mounting Foot

Seal Bracket

0.13[3]

Dia. 0.10[3]

x 0.50[13]

Slot

0.44[11]

Dia.

MP Meter-Pak™ Meter CentersProduct Selection

2903/2008 © 2008 Schneider Electric All Rights Reserved

Dimensions: in.

[mm]Knockouts

SymbolConduit Size Hole Diameter

in. mm in. mm

A 0.50 13 0.88 22

B 0.75 19 1.25 32

C 1.00 25 1.38 35

D 1.25 32 1.75 44

E 1.50 38 2.00 51

F 2.00 51 2.50 64

G 2.50 64 3.00 76

H 3.00 76 3.63 92

I 3.50 89 4.13 105

J 4.00 102 4.63 118

9.68[246] 0.34

[9]

1.50[38]

0.75[19]

To Top of Mounting Channel

Mounting Channel Detail

0.95[24]

1.73[44]

0.38[10]

Dia.

Mounting Foot

Seal Bracket

0.13[3]

Dia. 0.10[3]

x 0.50[13]

Slot

0.44[11]

Dia.

0.42[11]

Dia.

0.09 Dia.[2]

0.09[2] x 0.33

[8]Slot

Ringless Cover Latch

Supplied with ACPL Closing Plate (for Underground Service). Order Type A-L Hub Separately

(for Overhead Service).

11.30[287]

4.80[122]

MPL53225

2.75[70]

35.37[898]

10.87[276]

Tenant Circuit Breaker Doors (Lockable)

53.12[1349]

LinePhaseLugs

LineNeutralLugs

28.10[714]

24.10[612]

17.62[448]

14.00[356]

13.32[338]

6.32[161]

3.20[81]

C, D, E, F

Individual Meter Socket Covers: Ringless Style (Supplied with Cover Sealing Latches}

26.40[671]

4.50[114]

2.53[84]

10.10[257]

13.90[353]

C, D, E, FA-L Hub Provision E, F, G, H, I, J35.25

[895]6.00[152]

2.11[54]

2.07[53] 5.86

[149]9.65[245]

13.44[341]

2.84[72]

10.25[260]

4.05[103]

A, B 3.11[79]

Cover Knockout for use with Utility Barrel Lock

30© 2008 Schneider Electric All Rights Reserved 03/2008

MP Meter-Pak™ Meter Centers Product Selection

Supplied with ACPL Closing Plate (for Underground Service). Order Type A-L Hub Separately

(for Overhead Service)

11.30[287]

2.75[70]

4.80[122]

35.37[898]

67.37[1711]

31.62[803]

38.50[978]

41.87[1064]

Tenant Circuit Breaker Doors (Lockable)

Cover Knockout for use with Utility Barrel Lock

Individual Meter Socket Covers; Ringless Style (Supplied with Cover Sealing Latches)

2.53[64]C, D, E, F

3.20[81]

7.00[178]

LinePhaseLugs

LineNeutralLugs

14.00[356]

13.32[338]

26.40[671]

4.50[114]

13.90[353]

10.10[257]

6.32[161]

35.25[895]

C, D, E, FA–L Hub ProvisionE, F, G, H, I, J

A, B

2.11[54]

6.00[152]

2.07[53] 5.86

[149]9.65[245] 13.44

[341]2.84[72]

10.25[260]

4.05[103]

3.11[79]

1.73[44]

0.95[24]

0.38[10]

Dia.

Mounting Foot

Seal Bracket

0.13[3]

Dia.

0.44[11]

Dia. 0.10[3]

x 0.50[13]

Slot

0.42[11]

Dia.

0.09 Dia.[2]

0.09[2] x 0.33

[8]Slot

Ringless Cover Latch

9.68[246](NTS)

0.34[9]

1.50[38]

0.75[19]

To Top of Mounting Channel

Mounting Channel Detail

MPL64225

Dimensions: in.

[mm]Knockouts

SymbolConduit Size Hole Diameter

in. mm in. mm

A 0.50 13 0.88 22

B 0.75 19 1.25 32

C 1.00 25 1.38 35

D 1.25 32 1.75 44

E 1.50 38 2.00 51

F 2.00 51 2.50 64

G 2.50 64 3.00 76

H 3.00 76 3.63 92

I 3.50 89 4.13 105

J 4.00 102 4.63 118

MP Meter-Pak™ Meter CentersProduct Selection

3103/2008 © 2008 Schneider Electric All Rights Reserved

125 A DevicesFifth Jaw

Factory Installedon Ringless Device

N

Neutral,Service Groundand Equipment

Grounding Terminals

MP22125MPR22125MPH22125

Omitted on 3-Position Unit

Omitted on 5-Position Unit

MP33125MPR33125MPH33125

MP44125MPR44125MPH44125

MP55125MPR55125MPH55125

MP66125MPR66125MPH66125

NLine

EquipmentGroundingTerminals

Neutral andService Ground

N

Line

EquipmentGroundingTerminals

Neutral andService Ground

Fifth JawFactory Installed

on Ringless Device

Fifth JawFactory Installed

on Ringless Device

MP64200MPR64200MPH64200

N

Line

EquipmentGroundingTerminals

Neutral andService Ground

Fifth JawFactory Installed

on Ringless Device

Fifth JawFactory Installed

on Ringless Device

Fifth JawFactory Installed

on Ringless Device

Omitted on 2-Position Unit

Omitted on 5-Position Unit

MP42200MPR42200MPH42200

MP43200MPR43200MPH43200

MP85200MPR85200MPH85200

MP86200MPR86200MPH86200

NLine

EquipmentGroundingTerminals

Neutral andService Ground

N

Line

EquipmentGroundingTerminals

Neutral andService Ground

200 A Devices

Neutral and ServiceGrounding Terminals

Line

Equipment GroundingTerminals

Equipment GroundingTerminals

Neutral and ServiceGrounding Terminals

Line

Line

Equipment GroundingTerminals

Neutral and ServiceGrounding Terminals

225 A Devices

ø ø

ø ø

ø ø

ø

ø

ø ø

ø ø

ø ø

ø

ø

ø ø ø ø

ø ø

ø ø

ø ø

ø ø

øø

ø

ø

øø

øø

øø

øø

øø

ø

ø

øø

øø

øø

øø

ø

ø

øø

øø

øø

ø ø

ø ø

øø

øø

øø

øø

øø

øø

ø ø

øø

øø

øø

MPL32225 MPL53225MPL64225

4141CT0701 © 2008 Schneider Electric All Rights Reserved

Schneider Electric USA1601 Mercer RoadLexington, KY 40511 USA1-888-SquareD (1-888-778-2733)www.us.SquareD.com

Schneider Electric Canada19 Waterman Avenue,M4B 1 Y2Toronto, Ontario1-800-565-6699www.schneider-electric.ca

03/2008