NPM User Manual
1
NPM 4100 (Network Power Manager) User Manual
NPM User Manual
2
Contents
Ⅰ. NPM Introduction .........................................................................................................................................3
.Ⅱ Function Description ....................................................................................................................................3
.Ⅲ Applied Range ..............................................................................................................................................3
. Ⅳ Product Picture & Description ......................................................................................................................4
. Mounting MⅤ ethod .........................................................................................................................................5
Ⅵ. Hardware Introduction..................................................................................................................................5
1. Powering on & Self-check........................................................................................................................5
2. Current, Temperature & Humidity Monitoring.........................................................................................5
3. Water logging & Smog Monitoring ..........................................................................................................5
4. Outlet Fault Monitoring............................................................................................................................5
5. Individual Current, Total Current, Temperature & Humidity Over Limit Monitoring…………………..5
6. Self-checking Parameter Monitoring........................................................................................................5
7. Stopping Alarm Monitoring......................................................................................................................5
8. Master / Slave NPM Configuration ..........................................................................................................5
9. Daisy-chain Connection Method ..............................................................................................................5
10. Radialized Connection Method ..............................................................................................................6
11. Software Upgrade in Hardware...............................................................................................................6
Ⅶ. Software Introduction ...................................................................................................................................7
1. Software Overview ……………………..………………………………………………………..… ...…7
2. Software Function Description……………………………………………………………………...…...7
3. Access Method……………………………………………………… ………………………….…….....8
4. HTML Interface…………………………………………………….……………………….…..…….....8
5. NPM Daisy-chain Method………………………………………………………………….………..…17
6. FAQ and Solution ……………………………..………………………………………………….…..18
Ⅷ. Operation Steps…………………………………………………………………………………………….18
Ⅸ. Technical Parameter………………………………………………………………………..……………..18
Ⅹ. Quality warranty…………………………………………………………………………………………..19
NPM User Manual
3
Ⅰ. NPM Introduction
NPM can monitor, control and manage the power supply of many equipments in cabinets in data room all over
the world through LAN or WAN. For meeting with the restrictions and requirements in different environment,
NPM supplies many connection methods; can be connected through RJ45 in the LAN and WAN; can be accessed
and controlled through standard network management station.
Ⅱ. Function Description
1. Monitoring: Through the display interface and knob on the NPM, can monitor the total load current, individual
load current, power on/off state of individual outlet, temperature/humidity state, smog state, water logging state,
door open/close state.
2. Controlling function: Controlling the power on/off of outlet; Configuring the interval when sequential power
on/off.
3. Keeping the original state: Keeping the original state of each outlet when resetting.
4. User-defined alarming: the Min/Max limits value of total load current, individual outlet load current and
temperature/humidity.
5. System default alarming:Alarming when the total load current over limited value, or the individual outlet load
current over limited value, or individual outlet faults, or smog appears, or water logging or door opening happens.
6. Multi-alarming ways: The running indicator flashes and the buzzer alarms on the NPM controlling panel; the
problem displays (flash) on the web managing interface and the PC buzzer alarms; automatically send e-mail
to system administrator; SNMP sends alarm information.
7. Daisy-chain functions: can be daisy-chain connected at most 10 PCS using serial or radicalized connection
method.
8. User management: User right configuration
9. Access method: through IE (as Web), SNMP or Telnet (other command lines console) to access and control.
10. Support multi-user operation system and software upgrade.
Ⅲ. Applied Range
1. NPM series products can be applied to server cabinet, network cabinet etc.
2. The socket quantity (12, 16, 20, or 24) and socket standard of NPM vertical series products can be selected.
3. NPM series products conform to RoHS instruction, suitable for 110VAC and 220 VAC power supply, can meet
with the customers’ different requirements all over the world.
Ⅳ. Product Picture & Description
NPM User Manual
4
1. Mounting hole
2. Display the address and value of outlets
3. RUN: operation indicator
4. M/S: master/slave NPM indicator
5. OUTLET No.1: select outlet address (1-8way)
6. OUTLET No.2: Work with OUTLET No.1 to select the outlet address
(adds 8 ports or reduce 8 ports)
7. RESET: master or slave NPM selection; reset button
8. Water: for connecting with water logging sensor
9. Smog: for connecting with smog sensor
10. Port2:RS485 spare port
11. ND4101E12162:product model
12. Current consumption meter
13. Voltage module
14. NET: if you want to control NPM through network, this port is used to connect with
the RJ45 port of the PC, HUB, router or exchanger
15. SER: for daisy-chain
16. LINK: when daisy-chain many NPM, this port is connected with the SER port of the
next NPM
17. Port1: the software upgrading port in hardware
18. Door1 & Door2: for connecting with door opening sensor
19. T/H1&T/H2&T/H3: for connecting with temperature/humidity sensor
20. Socket quantity is 24 at most
21. Mounting hole
NPM User Manual
Ⅴ. Mounting Method
Vertical Installation.
. Hardware InⅥ troduction
1. Powering on & Self-check
The buzzer will make a sound when NPM is connected with AC power source, the panel LED is on and
sequentially display (it means digitron is normal, any different display is fault), software version number
(for example: ), baud rate (for example: ), serial number (For example: ), products series number
( ),socket quantity(for example: ), finally display the OUTLET No.1 and its value, and the running
indicator flashes, M/S indicator on means this NPM is master and off means this is slave NPM.
2. Current, Temperature & Humidity Monitoring
OUTLET No.1 and OUTLET No.2 are used to monitor the relative outlet value (OUTLET No.2 has the function
of adding 8 port or reducing 8 port when display).
3. Water logging & Smog Monitoring
3.1 When the water logging sensor monitoring the water, NPM screen displays and the buzzer alarms at the
same time.
3.2 When the smog sensor monitoring the smog, NPM screen displays ,and the buzzer alarms at the same
time.
4. Outlet Fault Monitoring
When one outlet fault (For example: A1), the NPM screen will display relative fault (for example: ), and
the buzzer alarms at the same time.
5. Individual Current, Total Current, Temperature & Humidity over Limit Monitoring
5.1 When individual load current, total load current, temperature & humidity value are lower than limited
minimum, the NPM screen displays as A.1 (that means the NO1 outlet is lower)
5.2 When individual load current, total load current, temperature & humidity value are higher than limited
maximum, the NPM screen displays as A.1.. (that means the NO1 outlet is higher)
6. Self-checking Parameter Monitoring
Make the OUTLET N0.1 display , then press reset button, the NPM screen sequentially display the NPM
self-checking parameter for one minute.
7. Stopping Alarm Monitoring
Click the RESET button to stop alarm for one minute (When NPM4101 has alarm information, the knob is not
5
NPM User Manual available, you have to stop the alarm for one minute then you can check other information. But if you don’t
modify the fault, it still alarms after one minute until you have modified the fault.)
8. Master / Slave NPM Configuration
Press the RESET button for 10-13 seconds, the indicator of M/S on indicates the NPM is the master NPM; Press
the RESET button for 5-8 seconds, the indicator of M/S off indicates the NPM is the slave NPM. Account the
time please refer to the RUN indicator (T= 2S)
9. Daisy-chain Connection Method
9.1 Each NPM owns the sole serial NO. different from others which have been locked before leaving factory and
can not be changed.
9.2 Configuring one master NPM and the others are slave NPM, can be daisy-chain 10 PCS NPM at most.
9.3 One end of the network wire connects to the LINK port of the master NPM, the other end connects to the
SER port of the first slave NPM, then use one end of another wire connects to the LINK port of the first slave
NPM, the other end connects to the SER port of the next slave NPM. Use the same way to connect other slave
NPM.
9.4 One end of the network wire connects to the net port of the PC; the other end connects to the NET port of the
NPM, then through IE to access. (Details please refers to the software introduction)
10. Radialized Connection Method
10.1 Configuring one master NPM and the others are slave NPM, can be daisy-chain 10 PCS NPM at most
10.2 One end of the network wire connects to the net port of the PC; the other end connects to the NET port of
6
NPM User Manual the NPM
10.3 One end of the network wire connects to the LINK port of the master NPM, the other end connects to the
RJ45 port of the HUB (special HUB for NPM daisy chain must from our company)
10.4 Use the end of another network wire connects to another in/out port of the HUB, the other end connects to
the SER port of the slave. Each in/out port of HUB connects to the SER port of the slave NPM, can
daisy-chain 10pcs at most.
10.5 Through IE to access (Details please refers to the software introduction)
11. Software Upgrade in Hardware
11.1 We will provide you the file of software upgrade ,and please save it in your PC
11.2 Please open the software upgrade file ,then double click this file to install
the software
11.3 Operate this software after installation, see the following picture:
11.4 T grade software (special wire, it must from our company) inserts to the
PORT1 on NPM, the other DB9 inserts to the RS232 port of PC
11.5 Please select the correct series port in
he RJ45 end of the signal wire for up
, make other selection according the picture
11.6
7
Click in , add the file to the
pane
NPM User Manual
8
11.7 Power on the NPM
11.8 Click , it will show when read successfully; if fails, please check the
connection wire and the communication port
11.9 Click , it will show when erase succeeds; If fails, please
check the connection wire and the communication port
11.10 Click , it will show when uploading the file succeeds; if fails,
nnection wire and the communication port
11.12 M, the panel will show the new version, the software upgrades successfully and then it can
oduction
nection. It can help NPM to meet the strong functions of SNMP, timely monitor, control
e cabinet all over the world through the software; adopt SNMP
r monitoring, Such as: temperature/humidity sensor, door open sensor, water logging sensor and
n
terface and multi-user;
ntralized;
2.1.6 t controlling power on/off of individual outlet or several outlets at one time; (LED shows power on/off
please check the co
11.11 Power off the NPM
Power on the NP
work normally.
.Ⅶ Software Intr
1. Software Overview
This software is embedded into the SCM and connected with NPM through internet to manage the equipment. It
has the IE browser access method, WEB management interface, and multi-user operation system, compatible with
different kind network con
the network equipment.
After connect with the LAN or WAN through RJ45 port successfully, the administrator can monitor, control and
manage many pieces power equipments in th
protocol to meet simple network management.
Support senso
smog sensor.
2. Software Function Descriptio
2.1 Basic function description
2.1.1 Support the IE (Internet Explorer) browser access method, WEB in
2.1.2 Network configuration, modify IP, subnet mask, gateway, DNS;
2.1.3 Support remote network monitoring, controlling and managing;
2.1.4 Support 10pcs NPM daisy-chain, configuration and management ce
2.1.5 Support monitoring individual load current and total load current;
Suppor
state)
NPM User Manual
9
al load current;
nd total current consumption
ff the individual outlets
ater and door open sensors in the cabinet;
MP alarm function
n, CPU capacity, and software run time and hardware address;
igure the user property and edit the user information etc;
reset
3.1.1
o access, then monitor, control and manage the power supply of equipment which connect with the
mputer display resolution is 1024*768;
3.2.1 he Enabled at “SNMP Agent” dropdown box list on the SNMP page and configures other
utton to submit and save configuration
erface includes three parts: NPM system information interface, user guide menu, main controlling
2.1.7 Support resetting individual outlet or several outlets;
2.1.8 Support defining limit value of individual outlet load current, group outlet load current and tot
2.1.9 Support checking the total voltage, group current consumption a
2.1.10 Support timing power on and power o
2.1.11 Support inquiring the alarm record
2.1.12 Keep the original state of outlets after reset;
2.1.13 Support defining limit value of temperature/humidity;
2.1.14 Monitor the state of temperature/humidity, smog, w
2.1.15 Support sound, e-mail and SN
2.2 Advanced function description
2.2.1 Examine the information of NPM versio
2.2.2 HTTP/SSL configuration information;
2.2.3 SNMP network management function;
2.2.4 Support the software system upgrade function;
2.2.5 Support the hardware system upgrade function;
2.2.6 Add/delete user, conf
2.2.7 NPM system
3. Access method
3.1 IE (Internet Explorer) browser access method
User open the IE (Internet Explorer) on the computer which connects with the network, enter the IP address of
NPM t
NPM
3.1.2 Default IP: 192.168.1.163
3.1.3 User name: clever; password: clever
3.1.4 The recommended co
3.2 SNMP access method
User selects t
information
3.2.2 Click “Apply”b
4.HTML interface
HTML int
interface;
NPM User Manual
10
user’s login name, web interface to access, guide user to finish operation quickly and conveniently.
NPM system information interface: company Logo, company website, the IP of current NPM
User guide menu: show the
Current User Name
Basic function interface
Advanced function interface
Main page shows NPM current data, NPM series and version, the individual output controlling menu, total
controlling menu, the individual output name, the individual load current, the total load current of each NPM, the
of every NPM and other configurations.
the IP address, then input login name and password on the login
uously wrong for three times, the
eat the operation of step A.
4.2 OUTPUTS controlling, see the picture below:
sensor information
4.1 Login method
A. Open IE (Internet Explorer) browser and input
frame, click “yes” button to enter the NPM system
B. User has three chance to login, if the login name and password are contin
system will automatically login out; user have to rep
NPM User Manual
A. This interface is the NPM power controlling interface, which is corresponding to “Device Control” on the
d
cting menu, user select the NPM on the menu and
n
rent and power on/off state of this individual outlet;
the d wn menu of each outl ct the ON、OFF、Reboot, then click the “Apply”
butto individual o N、OFF、Reboot of many individual outlets then click
“App trol many i
E. Select the ON、OFF、Reboo ets ” menu then click “Apply” button to
control all the outlets.
F. rent” matches wit
atches with the current consumption of each group
I. tches with the total current consumption
J. The detailed page information are as the following table:
NO. the code NO. of individual outlet
gui e menu, click it then you can open this interface
B. The submenu of “Select Device” is the daisy-chain NPM sele
ope the NPM power controlling interface to manage each NPM.
C. Interface shows the current NPM name, version and series.
D. Interface shows the individual outlet name, the load cur
rop-do et is its controlling menu, user sele
n to control this utlet; user also can select O
ly” button to con ndividual outlets at the same time.
t item in the drop-down menu of “All Outl
“Total Cur h the total current of all outlets
G. “Total Voltage” matches with the total voltage of all outlets
H. “Energy Meter” m
“Total Energy Meter” ma
Output Name the individual outlet name
Current(Amps) the individual outlet load current
Output Status(ON/OFF) the power on/off state of individual outlet
(
11
power on, power off)
NPM User Manual
12
Control the drop-down menu of individual output
K. Click “View sensors status” link to check the current NPM sensors information
4.3 Sensor monitoring
see the following picture
The interface is mainly used to monitor the NPM sensor state: environment temperature, environment humidity,
ome flashed red word to alarm.
te and
the drop-down menu of the daisy-chain equipment to examine the data
found”
idity value will
o
d “YES” to alarm
ative door value will show the red flashed “OPEN” to alarm
F. appens, the relative value will show the red flashed “YES” to alarm
G. User can click the “Refresh” button any time to refresh the page to get the updated data information
H. User can click the “Threshold value” to turn to sensor configuration interface
4.4 NPM configuration information
see the following picture
smog, water logging and door opening state; When the temperature/humidity value exceed the defined value, the
temperature/humidity value will bec
Sensor information: Sensor name, temperature/humidity value, smog, water logging, door opening sta
relative data
A. User selects each NPM from
information of each NPM sensor.
B. When the sensor is not connected normally or is not connected, the sensor state shows “Not
C. When the temperature/humidity value exceed the defined limit value, the temperature/hum
bec me flashed red word to alarm
D. When the smog happens, the state value of smog sensor will become red flashe
E. When the door is opened, the rel
When the water logging h
NPM User Manual
This interface is mainly used to configure the daisy-chain NPM information, add or modify the daisy-chain NPM
name, address, sequential interval, relative individual output name etc
A. “Select Device” frame display the NPM name
B. Input the NPM serial NO. on the right side of “NPM Address No.” frame. This serial NO. is exclusive and can
not be the same as that of other NPM. Otherwise, the daisy-chain will fail.
C “NPM name” frame is used to add NPM name, which is convenient for user’s management, the recommended
NPM name is exclusive
D. “Sequence Interval” frame is used to modify the interval of sequential power on.
“1-24” frame is used to name the individual outlet of NPM
E. The left list shows the name of current daisy-chain NPM; select any NPM to modify the relative information on
the relative input frame.
F. Click “Apply” button, save the NPM configuration information
4.5 Network configuration information
13
NPM User Manual
14
This network interface is used to configure NPM network information. The NPM administrator can configure the
NPM IP address, subnet mask, gateway address, DNS and check the network connection state and speed and other
information.
A. User can use the default IP address through selecting the button of “Obtain an IP address automatically”
B. User can configure the network information through selecting the “Use the following IP address” button
IP Address:192.168.1.n (2<n<254)
Corresponding to NPM IP address, “n” is an integer between 2 and 254.
Subnet Mask:255.255.255.0
Corresponding to NPM subnet mask, subnet mask is 255.255.255.0 when NPM IP is the third kind of IP.
Default Gateway:192.168.1.1 s
Corresponding to NPM default gateway
The NPM IP address can not be the same as the PC IP address and the NPM IP address must be in the same
network segment as the PC IP address.
C. Click “Apply” button, then power off the NPM to restart, the modified information will be valid
4.6 Timing power on/off controlling
A. User click “Timing Control” in the guide menu to open the HTML interface
B. User can choose the daisy-chain NPM in the HTML interface and configure the timing power on and power off
NPM User Manual the individual outlets
C. “Local Time” display the user’s local time, “NPM Clock” display the NPM time, When the NPM time is not the
same with the local time, user can click “Setting” button to modify the time
D. The interface detailed information as the following table
No. Individual outlet number
Output Name Individual outlet name
ON Timing(yy/mm/dd) The power on time of individual outlet
OFF Timing(yy/mm/dd) The power off time of individual outlet
E. User can configure the timing power on and power off of individual outlet following the time format under the
interface, and then click the “Apply” button, “Set success” information will show configuration successful
4.7 Alarm function and configuration
4.7.1 Current alarming function configuration
See the following picture
F.
F. User clicks the “Alarm” on the guide menu and then selects the “Threshold Value” to open relative HTML
interface.
G. User can defined the limit current alarm value on this interface through daisy-chain drop-down menu
H. The interface detailed information as the following table
NO. Individual outlet number
Output Name Individual outlet name
Current(Amps) Individual outlet load current
15
NPM User Manual
16
Overload Individual outlet max load current
Low limit Individual outlet minimal load current value
High limit Individual outlet maximal load current value
I. “Total Current” matches with the alarm value configuration of total current
J. Click “Apply” button to submit and save the defined limit current data
4.7.2 Environment alarming function configuration
A. User click the “ Alarm” from the guide menu and then select the “Threshold Value” to open relative web
interface
B. User can select the daisy-chain NPM from its drop-down menu
C. Configure the temperature/humidity threshold on the “Temperature/Humidity threshold setting” frame
D. The interface detailed information as the following table
Name sensor name
Current Temperature sensor current temperature value
Low limit sensor minimal temperature threshold
High limit sensor maximal temperature threshold
Current Humidity sensor current humidity value
Low limit sensor minimal humidity threshold
High limit sensor maximal humidity threshold
i. Click “Apply” button to submit and save temperature/humidity sensor data
When the current value of individual output and temperature/humidity value exceed their defined alarm limit value,
the NPM will make the buzzer sound to alarm and at the same time the relative current value /sensors value will
become red flashed word to alarm.
4.7.3 Alarming method configuration
There are three alarming method: sound alarm, e-mail alarm and SNMP Traps
A. Configure the sound alarm method
Select the “Enabled Sound Prompt” to enable the sound alarm function, when something goes wrong, the
administrator PC will sound to remind user.
B. Configure the e-mail alarm method
Select the “Enabled E-mail Prompt” to enable the e-mail alarm function, when something goes wrong, it will
automatically send an e-mail to the user’s defined e-mail address
C. Configure SNMP Traps alarming method
4.8 Inquiry the alarm record
NPM User Manual
17
A. User can click the “Alarm Logs” to open the relative WEB interface;
B. User can inquiry the alarm record information from the relative drop-down menu of daisy-chain NPM
C. Alarm record information include: Alarm time and alarm affair description
4.9 System information
see the following picture
User can check all the system configuration information of NPM on this interface
A. Version number
B. MAC hardware address
C. Memory capacity
D. Operation time
4.10. HTTP/SSL configuration information
4.10.1 HTTP function configuration
A. User click the “Web” on the guide menu to open the relative page
B. Select “Enable” on the drop-down menu of “Server” to enable HTTP function
C. Input HTTP port number in the corresponding input frame of “port”.
D. Click “Apply” to submit and save configuration.
HTTP protocol, hypertext transport protocols, is an application-level object-oriented protocol, because the HTTP
protocol is simple and the scale of HTTP server is small, its communication speed is fast. .NPM system adopts
HTTP protocol to make the system management, data traffic and controlling faster and more convenient.
4.10.2 SSL function configuration
A. Select “Enable” in the “Server” drop-down menu to enable SSL function.
B. Select “Optional” or “Required” in “Secure Access” drop-down menu to enable the unsafe HTTP and SSL
encryption HTTP interview; Select “Required” only to enable SSL encryption connection interview
C. Click “Apply” button to submit and save configuration
Secure Socket Layers (SSL), used to ensure the safety of transport data when user interview NPM remotely. Using
data encryption technology can ensure the data can not be intercepted and eavesdropped during network
NPM User Manual transportation. Authorized user and server ensure that the data can be sent to the proper customers’ equipment and
servers; Encrypt data to protect data from filching; maintain the data integrality, ensure the data is not changed
during transportation; SSL provides two important function: authorize user and Encrypt data
SSL Makes the NPM data system communication safer, network management more convenient.
4.11 SNMP function configuration
The SNMP WEB page is used to set up and renovate the entire configuration to enable the SNMP function, it is
also used to visit trap configuration page
A. Click the “SNMP” in the guide menu to open the corresponding WEB page
B. Select Enabled or Disabled in“SNMP Agent”drop-down menu to confirm whether enable the SNMP function
C. Configure the community string, input community string on the Get community frame, the string length
should be between 1 and 24 characters
D. Configure SNMP calculagraph, input one trap calculagraph value in the Error Trap Repeat Time frame, the
trap calculagraph value should be between 1-65535
E. Configure trap object, input an IP address on the Trap Destination frame then click “Apply” button
NPM support Simple Network management Protocol (SNMP), which enables administrator to use SNMP to search
network information and control individual outlets through network management system.
NPM system has SNMP function which include MIB I and MIB II; support remotely controlling function of the
power.
4.12 Update configuration
See the following picture
Administrator can upload a new version of NPM system software to NPM in the Update page, to update the NPM
software system.
A. User clicks the “Update” in the guide menu to open the corresponding WEB page.
B. Administrator clicks “browse” button to select the updated .bin file, and then click “Upload” to upload this file
to the NPM.
C. After finishing upload, the user must power off the NPM and reboot the NPM to complete the software updating.
4.13 User management
User management page is mainly used to display, delete and edit the user’s information and user rights.
18
NPM User Manual User information management
See the following picture
A. Click “User Manage” in the guide menu to open the relative WEB page.
B. This page shows all the user information of NPM system: User name, User level, control, detailed
operation etc
C. Details of user management page information are as follows:
User Name User name
Level User lever, User level include two lever, one is senior user “Administrator” and the other is common user “User”
Control Rights User rights editing, click “Edit” link to enter the user rights editing page.
Detailed operation, user click “Edit” link to enter the user information editing page to edit user password, user lever Action
Click “Remove” button to delete relative user
Senior use (Administrator) can operate all the functions of NPM system; common user (user) can only operate the
basic functions of NPM system.
D. Click “New User” link to enter new user creating page
Create a new user: see the following picture
A. When creating a user, administrator opens the new user creating page and then input a new user name on the
corresponding frame.
B. Input the user password in “Password” frame and verified password on the “Verify Password”frame.
19
NPM User Manual Password and verified password must be the same.
C. “User Level” drops-down menu is the user level, “Administrator” is the senior user and “User” is the
common user.
D. Click “Apply” button to submit data and the new user creating is finished successfully.
Edit user information
see the following picture
A. Administrator edits user information; “User Name” is the current editor’s user name.
B. Modify the user password in “Password” frame, input verified password in “Verify Password” frame,
Password and verified password must be the same.
C. “User Level” drop-down menu is the user lever, “Administrator” is the senior user and “User” is the common
user and then Click “Apply” button to finish user information editing.
4.14 Restart system
User click the “Restart” button at the guide menu to restart the system
4.15 Logout system
User click “Logout” in the guide menu, then click “Yes” button to logout NPM system
5.NPM daisy-chain
5.1 Daisy-chain method
A. Firstly configure one master NPM and some slave NPM, confirm the connection is correct.( when NPM M/S
indicator is on, it is on master NPM state; otherwise ,it is on slave NPM state)
Master NPM configuration
NPM is on slave NPM state, press RESET button for 12 seconds, M/S indicator on means configuration is successful
Slave NPM configuration
NPM is on master NPM state, press RESET button for 6 seconds, M/S indicator off means configuration is successful
B. Input the IP address, open the master NPM WEB system, and open Device Configuration page;
C. On the NPM configuration page, input the physical address of daisy-chain NPM in the corresponding frame of
NPM Address No. to name NPM.
20
NPM User Manual
21
D. Click “Apply” button to submit and save configuration information
E. Click “Device Control” in the guide menu, open NPM control page, then select the daisy-chain NPM in the
drop-down menu of “select device”. If data information is correct, the NPM daisy-chain is correct.
5.2 Daisy-chain configuration
A. Daisy-chain NPM, all the physical address of daisy-chain NPM must be exclusive;
B. Name each daisy-chain NPM, their names must be different to avoid confusion;
6.FAQ and solution
6.1 Input NPM IP then press “enter” but can not see the system login frame
Solution: Firstly please confirm whether the NPM IP and the PC IP connected with NPM are in the same network
segment, Ping NPM IP address to confirm whether the network connection is normal;
6.2 Input user name and password on the login frame but can not enter the NPM Web interface
Solution: Please confirm whether the user name and password are correct, and then submit again
6.3 Entering into NPM Web interface but can not read the NPM state;
Solution: Please open the “Device Configuration” to check whether the NPM address on the NPM Address No.
frame is correct, after confirm this address is the same as the connected NPM address, please refresh to read; If the
connected NPM address is not the same as the address on the NPM Address No. frame, please input NPM address
on the input frame then click “Apply” to save and read NPM state again.
Ⅷ Operation steps
1.Install the NPM vertically on the fixed place
2.Connect the door, water logging, smog and temperature/humidity sensors correctly
3.Select connecting method according to your requirement (details in chapter Six)
4.Connect the NPM plug to the AC power source, configure the master and slave NPM, open the IE browser to
configure correctly. (Details in chapter Seven)
Ⅸ Technical parameter No. Performance parameter Technical parameter
rated input voltage 125/250VAC 50/60HZ
input terminal type IEC60309 industrial standard plug/IP44
cable specification 3×2.5mm²、3×6.0mm²
1 Input
cable length 2M
NPM User Manual
22
the Max input current 16A、32A
socket standard IEC320 C13、C19
outlet quantity 12、16、20、24(Vertically installation)
X1 LED display power on/off state of individual outlet replaceable fuse fitting(optional)
Outlet safety protection Anti-fall protection fitting
Rated outlet voltage 125/250VAC 50/60HZ
Outlet rated current 10A
2 Outlet
the max total load current 16A、32A
Network port 1 RJ45 port
232/485 port 1 RJ45 port
daisy-chain port 1 RJ45 port
software upgrade port 1 RJ45 port
Temperature / humidity sensor port
3 RJ11 port
Smog sensor port 1 RJ11 port
Water logging sensor port 1 RJ11 port
Door open sensor port 2 RJ11 port
3 Control port
Spare sensor port 1 RJ11port
Working state 1 LED
Master/slave NPM state 1 LED
Output ,temperature/humidity address
3 LED 4 Display
Load current, temperature/humidity value
3 LED
Total current Full-scale:32A/16A Accuracy:±1﹪+2 Resolution:200mA Response time:400ms
5
Load current display
technology requirement Individual load current
Full-scale:10A Accuracy:±1﹪+1 Resolution:100mA Response time:400ms
NPM User Manual
23
Temperature Working range:-40℃~+124℃, Accuracy:±1℃,Response time:4s
6
Temperature/humidity
technology requirement Humidity Accuracy:±5﹪RH,Response time:4s
Product size(L×W×H) X2×88.8×44.4mm 7 Product size
Mounting hole X3
8 Case color Color Black
Installation bracket 1 set
Network connection wire 2M, blue
Daisy-chain connection wire 2M, yellow 9 Fittings
User manual 1 set(CD)
Temperature/humidity sensor
Smog sensor
Door sensor 10
Optional fittings
Sensor
Water logging sensor
Working temperature 0℃~55℃ 11 Environment
Relative humidity 10~90%
12 ROHS compliance
Quality WarrantyⅩ
The NPM warrants to be free for repairing in two years from the date of purchasing. During this period, our
obligation is limited to repair, replace or return to our company for repair. If the product has been beyond the
warrant for repairing time or it has been damaged by accident, negligence or misapplication, you should pay some
repair charge.
The above warranty does not apply to the following situation:
1、 The damage caused by customers’ incorrect or inadequate repair;
2、 The damage caused by unauthorized modification or misusing;
3、 The damage caused by using out of the product allowed environment.
Repairing Notice:
1、 If you want to return the product for repair, please make sure it packed in the bandbox or carton. The damage
caused during the transportation is not warranted to repair.
2、 Please give a brief description of the repairing product about the problem and its operating process.
3、 The customer should pay for the returning freight, all the tariffs and taxes.
4、 Please write down your name, address and the telephone number by which we can contact you at anytime.