COLLECTIVE VENTILATION NOE ® RANGE 400° C - 1/2 h CMV/Collective extraction units Flow rate 400 to 11400 m 3 /h
Transcript
Page 1: COLLECTIVE VENTILATION NOE - Caladair · NOE® 10000 and 11400 dB(A) weighting -27 -18 -12 -7 -6 -5 -9 -18 • To obtain the acoustic ®power spectrum radiated in the intake duct

CALADAIR I 61 rue de Saint Véran I 71000 MÂCON LOCHÉ I Tél. 33 (0)3 85 36 82 00 – Fax 33 (0)3 85 36 82 01 I www.caladair.com P21

COLLECTIVE VENTILATION

NOE®

RANGE

400° C - 1/2 h

CMV/Collective extraction units

Flow rate 400 to 11400 m3/h

Page 2: COLLECTIVE VENTILATION NOE - Caladair · NOE® 10000 and 11400 dB(A) weighting -27 -18 -12 -7 -6 -5 -9 -18 • To obtain the acoustic ®power spectrum radiated in the intake duct

P22 CALADAIR I 61 rue de Saint Véran I 71000 MÂCON LOCHÉ I Tél. 33 (0)3 85 36 82 00 – Fax 33 (0)3 85 36 82 01 I www.caladair.com

C4 EXTRACTION UNIT DESCRIPTION NOE

®

Ventilation unit PULLEY/BELT TRANSMISSION

400 to 11400 m3/h

CTICM C4 - 400° C - 1/2 h approved

Report no. 09-E-544

CSTB technical notification for Hygro A, Hygro B and Hygro Gas usage

CMV POWER selection software

APPLICATION

• Intended mainly for air extraction in houses and public assembly buildings requiring high flow rates.

• C4, 400°C 1/2 h certified 50 Hz and 60 Hz.

RANGE

• Comprising 10 models, it covers flow rates from 400 to 11400 m3/h in a number of configurations.

INSTALLATION

• Can be installed internally or externally.

• Easy access to all internal parts.

• May be fully dismantled.

CONSTRUCTION

• Housing: galvanized steel sheet. Amply dimensioned, it offers powerful air handling and acoustic performance characteristics.

• Internal access via two removable panels.

• Bird protection grid on discharge.

• Circular nozzles with double lip seal for watertight networks (ATEC CSTB

No. 13-224-V2). s T

• Local padlockable switch on front panel.

• Pressure switch factory-fitted in the unit and set to 80 Pa (Gas CMV). Time delay possible (see MISTRAL 30 S unit option).

• External pressure tap to check air flow.

• Vibration pads incorporated under the chassis of the motorized fan unit. s SILENCE version 400°C 1/2 h certified. The insulation of the unit

using 25mm M0 mineral wool allows acoustic performance characteristics compliant with the requirements of the new regulations to be achieved.

MOTOR FAN

• Transmission by pulley and belt, motor pulley variable when stopped.

• Three-phase one-speed motor, IP55 F, 230/400V-3, 50 Hz.

• Door opening sensor available for office ventilation.

• Centrifugal impulse turbine with double opening.

• Flexible connection from turbine to unit.

• Spare belt supplied.

The units are available in two versions:

H: 1 horizontal intake Ø D1 + 1 horizontal discharge Ø D2 in-line

V: 1 horizontal intake Ø D1 + 1 horizontal intake Ø D2 + 1 vertical discharge LxL1

Reference to be given in the order:

NOE 3000 SILENCE H

1 2 3 4

1: Unit 400° C/1/2 h pulley belt transmission

2: Maximum flow rate in use

3: SILENCE version 400° C 1/2 h certified

4: Installation configuration H = in-line discharge / V = 1 or 2 horizontal intakes and vertical discharge

NOE 4800 - V

1 2 3 4

COLLECTIVE

Page 3: COLLECTIVE VENTILATION NOE - Caladair · NOE® 10000 and 11400 dB(A) weighting -27 -18 -12 -7 -6 -5 -9 -18 • To obtain the acoustic ®power spectrum radiated in the intake duct

CALADAIR I 61 rue de Saint Véran I 71000 MÂCON LOCHÉ I Tél. 33 (0)3 85 36 82 00 – Fax 33 (0)3 85 36 82 01 I www.caladair.com P23

DIMENSIONS

CHARACTERISTICS NOE®

*Overall depth of LOBBY® unit

Dim. unit Ground Discharge version V Discharge version H Intake versions H and V Intake version V on Weight Weight of

Reference overall fixing from the top on side of local switch opposite local switch side of local switch condensate

Lenght Width Height Lenght Width Position Width Lenght Ø Floor centreline distance Ø Floor centreline distance Ø Floor centreline distance NOE® NOE® SILENCE tray

NOE®

A (mm)

B (mm)

H (mm)

X (mm)

Y (mm)

A1 (mm)

L1 (mm)

L (mm)

D2 (mm)

H1 (mm)

D1 (mm)

H1 (mm)

D2 (mm)

H1 (mm)

(kg) (kg) (kg)

2600-3000 900 585 580 940 470 370 330 271 400 320 400 320 315 320 55/57 60/62 5

3400-3800 1000 650 680 1040 520 380 360 298 450 360 450 360 400 360 72/74 78/80 6

4800-5600 1110 740 780 1150 575 400 420 355 500 375 500 375 450 375 86/88 93/95 7

6800-8000 1300 860 880 1340 670 450 500 407 630 455 630 455 500 455 119/122 129/132 10

10000-11400 1400 940 980 1440 720 410 585 490 710 485 710 485 630 485 154/159 165/170 12

ELECTRICAL

CHARACTERISTICS NOE®

Reference Motor power

(kW) Current protection

at 400 V (A) Rotation speed

(rpm) Power supply (V/phases/Hz)

NOE® 2600 0,37 1,1 865 / 1100 230-400 / 3 / 50

NOE® 3000 0,55 1,4 975 / 1240 230-400 / 3 / 50

NOE® 3400 0,55 1,4 740 / 940 230-400 / 3 / 50

NOE® 3800 0,75 1,9 880 / 1120 230-400 / 3 / 50

NOE® 4800 0,75 1,9 650 / 830 230-400 / 3 / 50

NOE® 5600 1,10 2,6 720 / 940 230-400 / 3 / 50

NOE® 6800 1,10 2,6 540 / 700 230-400 / 3 / 50

NOE® 8000 1,50 3,5 600 / 780 230-400 / 3 / 50

NOE® 10000 1,50 3,5 470 / 580 230-400 / 3 / 50

NOE® 11400 2,20 4,8 530 / 655 230-400 / 3 / 50

Page 4: COLLECTIVE VENTILATION NOE - Caladair · NOE® 10000 and 11400 dB(A) weighting -27 -18 -12 -7 -6 -5 -9 -18 • To obtain the acoustic ®power spectrum radiated in the intake duct

P24 CALADAIR I 61 rue de Saint Véran I 71000 MÂCON LOCHÉ I Tél. 33 (0)3 85 36 82 00 – Fax 33 (0)3 85 36 82 01 I www.caladair.com

ACOUSTIC

CHARACTERISTICS NOE®

• The Lp4m dB(A) ) values shown on the curves relate to the average overall acoustic pressure level radiated in a free field on a reflecting plane, unit discharge not connected. These values also enable you to obtain the spectrum for NOE® SILENCE units.

• The Lw cond dB(A) ( ) values shown on the curves relate to the average overall acoustic pressure level radiated in the intake duct for a NOE®

device.

• To obtain the overall Lw cond dB(A) for a NOE® SILENCE, ôter 5 dB(A) subtract 5 dB(A) from the overall Lw cond dB(A) ( ) value shown on the curves.

• To obtain the acoustic power spectrum radiated in the intake duct in dB(A) for a non-insulated NOE®, device, add the correction coefficients from the table below to the Lw cond dB(A) ( ) value shown on the curves

Intake acoustic spectrum weighting for non-insulated NOE® as a function of the Lw cond dB(A) ( ) values shown on the curves

Frequency 63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz

NOE® 2600 and 3000 dB(A) weighting -35 -18 -16 -9 -5 -5 -9 -19

NOE® 3400 and 3800 dB(A) weighting -33 -18 -13 -9 -5 -5 -8 -17

NOE® 4800 and 5600 dB(A) weighting -30 -16 -14 -9 -5 -5 -9 -19

NOE® 6800 and 8000 dB(A) weighting -29 -19 -11 -8 -6 -5 -8 -17

NOE® 10000 and 11400 dB(A) weighting -27 -18 -12 -7 -6 -5 -9 -18

• To obtain the acoustic power spectrum radiated in the intake duct in dB(A) for a NOE® SILENCE device, add the correction coefficients from the table below to the acoustic spectrum of a non-insulated device dB(A) obtained using the table above.

Intake acoustic spectrum weighting for NOE® SILENCE as a function of the intake acoustic spectrum for non-insulated NOE®

Frequency 63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz

Weighting pour NOE® SILENCE dB(A) 0 -1 -2 -4 -4 -6 -6 -8

Tolerance: Overall values +/- 3 dB(A) Acoustic spectrum +/- 5 dB(A)

• Overall acoustic pressure level radiated rejection : Lw rejet dB(A) = Lp4m dB(A) ) + 20

• To define the average overall acoustic pressure level radiated at a certain distance in dB(A) in free field on a reflecting plane, discharge unit not

connected, add the value from the table below to the Lp4m dB(A) ) value shown on the curves.

Lp weighting at various distances

Distance 2 m 3 m 4 m 5 m 7 m 10 m

Distance weighting 6 2 0 -2 -5 -8

NOTA : The curves are made with a suction and discharge nozzle connected sub- woofer is not connected (C configuration according to NF N 13141-4).

COLLECTIVE

Page 5: COLLECTIVE VENTILATION NOE - Caladair · NOE® 10000 and 11400 dB(A) weighting -27 -18 -12 -7 -6 -5 -9 -18 • To obtain the acoustic ®power spectrum radiated in the intake duct

74

51

70

56

53 52 i à 1120 tr/min max

mini à 975 tr/mi

in 52

maxi à 1240 tr/

Sta

tic p

res

su

re (

Pa)

Sta

tic p

res

su

re (

Pa)

Sta

tic p

res

su

re (

Pa)

Sta

tic p

res

su

re (

Pa)

Po

wer

co

ns

um

pti

on

(W

) P

ow

er

co

ns

um

pti

on

(W

) P

ow

er

co

ns

um

pti

on

(W

) P

ow

er

co

ns

um

pti

on

(W

)

SELECTION

CURVES NOE®

320 800

700

NOE® 2600

NOE® 3000

240

160

80

00

320

240

160

80

00

maxi à 1100 tr/min 49

72 hygro à 960 tr/min

mini à 865 tr/min 44

m

n 46

49 51

72 74

44

51

74

1000 2000

Flow rate (m3/h)

5

75

77

46

1000 2000

Flow rate (m3/h)

600

500

400

300

200

100

0 3000

800

700

600

500

400

300

200

100

0 3000

320 800

700

NOE® 3400

240

160

80

00

maxi à 940 tr/min

hygro à 820 tr/min

mini à 740 tr/min

48

71

44

1000

50

73

46

69

2000

Flow rate (

m3/h)

54

77

50

73

3000

600

500

400

300

200

100

0 4000

400 1000

900

320 800

700

NOE® 3800

240 79 600

500

160 400

900

800

700

600

67

69 69

47 à 880 tr/min mini

0 tr/min 100

75

52

1040 tr/min

75

54

2

76 75

67

67

Page 6: COLLECTIVE VENTILATION NOE - Caladair · NOE® 10000 and 11400 dB(A) weighting -27 -18 -12 -7 -6 -5 -9 -18 • To obtain the acoustic ®power spectrum radiated in the intake duct

SELECTION

CURVES

NOE®

COLLECTIVE


Recommended