August 22, 2012; 1 PM (U.S. Central Time) http://www.meetingzone.com/presenter/default.aspx?partCEC=4147918 Call-In Number: 1 877 406 7969 Access Code: 4147918 # Combustion Turbine Inlet Cooling using Direct Evaporative Cooling By Pat Zeller, Munters Corporation Sponsored by: Turbine Inlet Cooling Association (TICA)
Transcript
Page 1: Combustion Turbine Inlet Cooling using Direct Evaporative ...

August 22, 2012; 1 PM (U.S. Central Time)http://www.meetingzone.com/presenter/default.aspx?partCEC=4147918

Call-In Number: 1 877 406 7969Access Code: 4147918 #

Combustion Turbine Inlet Cooling usingDirect Evaporative Cooling

By Pat Zeller, Munters Corporation

Sponsored by:

Turbine Inlet Cooling Association (TICA)

Page 2: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Introductions

Trevor RichterChairman, TICAStellar Energy Inc.

Pat ZellerMunters Corporation

Page 3: Combustion Turbine Inlet Cooling using Direct Evaporative ...

The Turbine Inlet Cooling Association (TICA) promotesthe development and exchange of knowledge related togas turbine inlet cooling

The TICA website is one-stop source of TIC technicalinformation, including Installation Database &Performance Calculator

TICA is a non-profit organization.

Who is TICA?

Page 4: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Access to full/detailed version of TIC Installation DatabaseAccess to full/detailed version of the TIC TechnologyPerformance CalculatorGT Users get access to the TIC ForumSuppliers have access to information space on the TICAWebsite and access to booths at various electric powertrade shows

Become aMemberToday!!!

TICA Member Benefits

Page 5: Combustion Turbine Inlet Cooling using Direct Evaporative ...

August 22, 2012: Wetted-Media Evaporative Cooling

October 18, 2012: Fogging

December 19, 2012: Chiller Systems

February 13, 2013: Thermal Energy Storage

April 17, 2013: Wet Compression

June 19, 2013: Hybrid Systems

Turbine Inlet Cooling Technologies

Webinar Schedule

All Webinars start at 1 PM (U.S. Central Time)

Page 6: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Agenda:• Why Cool Turbine Inlets• How Direct Evaporative Cooling Works• Anatomy of Direct Evaporative Coolers• Things to Consider in Evaporative Cooling of CT’s• Water Quality and Usage• Quick Compare to Other Cooling Technologies• Why Direct Evaporative Cooling for Combustion Turbines

Page 7: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Unfortunate Fundamental Characteristics of AllCombustion Turbine Power Plants

During hot weather, just when power demand is at it’s peak………….1. CT Total Power output decreases up to 35% below rated capacity

(Extent of the decrease depends on the CT design)2. Efficiency decreases leading to increased fuel consumption (heat rate) and

emissions per kWh……..up to 15% more fuel consumed(Extent of the decrease depends on the CT design)

Page 8: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Why CT Power Output Capacity Decreases withIncrease in Ambient Temperature?

• Power output of a turbine is proportional to the mass flow rate of hotgases from the combustor that enter the turbine

• Mass flow rate of combustor gases is proportional to the flow rate of thecompressed air that enters the combustor

• Compressors provide compressed air and are volumetric machines,limited by the volumetric flow rate of inlet air they can pull or suck in

• As ambient temperature increases, the air density decreases. Thisresults in a decrease of the mass air flow rate

• Reduced mass flow rate of inlet air reduces the mass flow rate of thecombustor gases and hence reduced power out put of turbine

Page 9: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Why CT Efficiency Decreases with Increase in AmbientTemperature?

• Compressor of a CT system consumes almost two-third of the turbine’sgross output

• Compressor requirement increases with increase in air temperature

• Increased power required by the compressor reduces the net electricpower available from the CT system

Page 10: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Effect of Hot Weather on CT Generation Capacity Dependson CT Design

EFFECTS OF COMPRESSOR INLET AIR TEMPERATURE ON GAS TURBINE POWER OUTPUT

80%

85%

90%

95%

100%

105%

50 55 60 65 70 75 80 85 90 95 100COMPRESSOR INLET AIR TEMPERATURE, degrees F

% O

F R

ATE

D P

OW

ER

OLD "FRAME"POWER OUTPUT

Compression Ratio = 10

PERIOD OF GREATEST DEMAND

NEW AERO-DERIVATIVEPOWER OUTPUT

Compression Ratio = 30

ISODESIGNPOINT

Up to 19%capacityloss atpeakdemandfor this CT

Page 11: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Turbine Inlet Cooling Overcomes the Effects of the CT FlawsDuring Hot Weather

7 5

8 0

8 5

9 0

9 5

1 0 0

6 0 7 0 8 0 9 0 1 0 0

Am b ie n t D ry -B u lb T e m p e ra tu re , F

Net C

T Pow

er Ou

tput,%

of De

sign

No C o o lingW ith TICRa te d C a p a c ity

With Cooling

Rated Capacity

No Cooling

Page 12: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Direct Evaporative Turbine Inlet Cooling (TIC) provides a cost-effective,energy-efficient, and environmentally beneficial means to enhance powergeneration capacity and efficiency of combustion/gas turbines during hotweather.

Why Use Direct Evaporative Cooling for Turbine Inlets

Page 13: Combustion Turbine Inlet Cooling using Direct Evaporative ...

How Direct Evaporative Cooling Works

Page 14: Combustion Turbine Inlet Cooling using Direct Evaporative ...

10 20 30 40 50 60 70 80 90 100 110 120

Dry Bulb Temperature, Deg. F

0.000

0.005

0.010

0.015

0.020

0.025

0.030

Hum

idityR

atio, lb Moisture/lb D

ry AirHow Direct Evaporative Cooling Works

Page 15: Combustion Turbine Inlet Cooling using Direct Evaporative ...

How Direct Evaporative Cooling Works

10 20 30 40 50 60 70 80 90 100 110 120

Dry Bulb Temperature, Deg. F

0.000

0.005

0.010

0.015

0.020

0.025

0.030

Hum

idityR

atio, lb Moisture/lb D

ry Air

Rain or Fog

Saturation Lineor

100% Relative Humidity

Page 16: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Moisture Content in Air

.022

.011

.0044

.0022

FOUR EQUAL SIZE CONTAINERS AT 80FWILL HAVE DIFFERENT MOISTURE CONTENTSAT DIFFERENT RELATIVE HUMIDITIES

20% RH 10% RH

W=.022

100% RH 50% RH

W=.011

W=.0044

10 20 30 40 50 60 70 80 90 100 110 120

Dry Bulb Temperature, Deg. F

0.000

0.005

0.010

0.015

0.020

0.025

0.030

Hum

idityR

atio, lb Moisture/lb D

ry Air

W=.0022

Page 17: Combustion Turbine Inlet Cooling using Direct Evaporative ...

As We Cool Air Close to the Wet Bulb Line

10 20 30 40 50 60 70 80 90 100 110 120

Dry Bulb Temperature, Deg. F

0.000

0.005

0.010

0.015

0.020

0.025

0.030

Hum

idityR

atio, lb Moisture/lb D

ry Air2030

40

50

60

80

70

700

1100

Page 18: Combustion Turbine Inlet Cooling using Direct Evaporative ...

10 20 30 40 50 60 70 80 90 100 110 120

Dry Bulb Temperature, Deg. F

0.000

0.005

0.010

0.015

0.020

0.025

0.030

Hum

idityR

atio, lb Moisture/lb D

ry Air

2030

40

50

60

80

7078110

Direct Evaporative Cooling of an Airstream

Page 19: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Direct Evaporative Cooling of an Airstream

10 20 30 40 50 60 70 80 90 100 110 1200.000

0.005

0.010

0.015

0.020

0.025

0.030

2030

40

50

60

80

70

74110

Page 20: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Cooling Efficiency is the Same Regardless of theStarting Point

10 20 30 40 50 60 70 80 90 100 110 120

Dry Bulb Temperature, Deg. F

0.000

0.005

0.010

0.015

0.020

0.025

0.030

Hum

idity Ratio, lb M

oisture/lb Dry

Air

2030

40

50

60

80

70

780/91.6%

950/45%

108 0/9%

70.20/81.2%

390/90%680/20%

500 /87%

500/30%

A 90% Effective Evaporative Cooler WillCool 90% of the Wet Bulb Depression

Regardless of the Starting Point

Page 21: Combustion Turbine Inlet Cooling using Direct Evaporative ...

As the Day Temp Heats Up

Shreveport, LA, July 18-31, 1993Dry-Bulb, Wet-Bulb & Relative Humidity

40

50

60

70

80

90

100Temperature, °F

3230

40

50

60

70

80

90

100Relative Humidity, %

RELATIVEHUMIDITY

WET BULB

DRY BULB

18 19 20 21 22 23 24 25 26 27 28 29 30 31Date in July

30

Page 22: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Even in Humid Areas, Direct Evaporative Cooling Works

18 19 20 21 22 23 24 25 26 27 28 29 30 31 32Date in July

60

70

80

90

100

Temperature, °F

Shreveport, LA, July 18-31

CooledAir

OutsideAir

Dry Bulb Temperatures Entering and leaving a 90% Pad

Wet Bulb

Page 23: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Tamp Florida, Month of July

60

65

70

75

80

85

90

95

100

Day of Month

DEGR

EES F

Outdoor Temperature

Cooled Air Temperature

Looking at Tampa Florida

Page 24: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Turbine Performance

70

75

80

85

90

95

100

Day of Month

MW

MW Without Cooler

MW With Cooler

Performance of 100 MW CT in Tampa, Month of July with 90% Effective Evaporative Cooler

Page 25: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Looking at Las Vegas Nevada

40

50

60

70

80

90

100

110

DAYS

DEGR

EES

F

Outdoor Temperature

Cooled Air Temperature

Las Vegas Month of July

Page 26: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Turbine Performance

65

70

75

80

85

90

95

100

105

110

115

Day of Month

MW

MW Without Cooler

MW With Cooler

Performance of 100 MW CT in Las Vegas, Month of July with 90% Effective Evaporative Cooler

Page 27: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Direct Evaporative Cooler Anatomy

Page 28: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Construction & Examples

Page 29: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Evaporative Section LocationFilters

Mist EliminatorEvaporativeMedia

Silencers

Pump

OR

Page 30: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Construction & Examples

Page 31: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Webinar Series for Turbine Inlet Cooling Technologies

Page 32: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Webinar Series for Turbine Inlet Cooling Technologies

Page 33: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Installations

Page 34: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Installations

Page 35: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Design & Construction Considerations

•Face velocity

•Materials of construction

•Material gauge

•Media type

•Water source

•Valve function and locations

•Drains and overflows

•Air bypass

•Sump water management

Simple, but Require Engineering, Experience & Robust Design

Page 36: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Simple, But Require Engineering, Experience & Robust Design

Media is the heart of Evaporative Cooling

Page 37: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Simple, But Require Engineering, Experience & Robust Design

Page 38: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Simple, but Require Engineering, Experience & Robust Design

Areas "starved" for water will be the first to clog or soften.

Page 39: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Simple, but Require Engineering, Experience & Robust Design

Page 40: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Simple, but Require Engineering, Experience & Robust Design

Page 41: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Water Quality and Management

Continuous bleed / and or flush and dump used for scale control

• Scale inhibitors not recommended

• Bleed is major method of control

• Biocides not recommended, no oxidizing biocides allowed

• Corrosion inhibitors not recommended

• ALL SS and plastic construction

• Straight RO water is not recommended but a blend is okay

Page 42: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Water Quality and Management

• Chemicals dry out on the media each time the water is turned off,causing the chemicals to loose their effectiveness

• Some chemicals are corrosive and will harm pads and turbinecomponents.

• Some chemicals contribute to microbial growth.

• Many chemicals cause environmental problems.

• Those who use chemicals often feel they can neglect othermaintenance requirements

Page 43: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Water Quality & ManagementLIMITS FOR MAKE-UP WATER ANALYSISThe following water quality is established for evaporative cooler water make-up. This

water can then be cycled up 2 to 6 cycles to obtain the following stability indices.

Langelier Index = 0.5 + 0.25 Ryznar Index = 6.0 + 0.5Puckorius Index = 6.5 + 0.5

CONSTITUENT ALLOWABLE*Calcium Hardness (as CaCO3) 50 - 150 PPMTotal Alkalinity (as CaCO3) 50 - 150 PPMChlorides (as Cl) <50 PPMSilica (as SiO2) <25 PPMIron (as Fe) <0.2 PPMOil and Grease <2.0 PPMConductivity <750 mhosSuspended Solids <5 PPMpH 6.0 to 8.5* Need to be evaluated as a system, not in isolation

Page 44: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Water Quality & Management

Page 45: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Remote Sump Water Management

Page 46: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Water Usage

80 MW Turbine with 500,000 cfm, Arid Climate

Softened Water Moderate Water Hard WaterEvaporation, GPM 180 180 180Bleed, GPM 20 80 180

TOTAL 200 260 360

Page 47: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Utilities Example for 100 MW CT in Tampa, FL

Media Fog Mechanical Chilling

Deg of Cooling 12.6 F 13.3 F 44 F

WaterEvaporated

13 GPM 13.6 GPM 136 GPM (at CoolingTower)

Blow Down 4 GPM 6.5 GPM (atRO plant)

4.5 GPM at CoolingTower

Parasitic PowerLoss

10 kW 27 kW 3181 kW

Insertion loss 0.3”wg 0.05”wg 1.0”wg

How Direct Evaporative Cooling Compares

Page 48: Combustion Turbine Inlet Cooling using Direct Evaporative ...

How Direct Evaporative Cooling Compares

Media Fog Mechanical Chilling

Deg of Cooling 37 F 39 F 57 F

Water Evaporated 35 GPM 37 GPM 76 GPM (at CoolingTower)

Blow Down 12 GPM 18 GPM (at ROplant) 4 GPM

Parasitic PowerLoss 10 kW 75 kW 2250 kW

Insertion loss 0.3”wg 0.05”wg 1.0”wg

Utilities Example for 100 MW CT in Las Vegas

Page 49: Combustion Turbine Inlet Cooling using Direct Evaporative ...

Low Maintenance

• Flush and dump water distribution headers - quarterly

• Clean strainer - quarterly

• Drain and protect from freezing - seasonally

• Change media - 2 to 5 yrs

• Replace or service pumps - 1 to 5 yrs

Page 50: Combustion Turbine Inlet Cooling using Direct Evaporative ...

One of the most cost effective solutionsLowest first install costLow operating costsLow maintenance cost

SimpleTo understandTo designTo installTo maintain

1000’s of successful installations Worldwide

Why Use Direct Evaporative Cooling for Turbine Inlets