24 Volt DC Edition - EMerge Alliance ® Registered Products ALLIANCE REGISTERED
Transcript
Page 1: Commercial Lighting Design Guide: 24 Volt DC Edition - EMerge

24 Volt DC Edition - EMerge Alliance® Registered Products

A L L I A N C E

R E G I S T E R E D

Page 2: Commercial Lighting Design Guide: 24 Volt DC Edition - EMerge

Crestron 24 Volt DC Design Guide

2

Introduction

This design guide is intended to explain how to design a Crestron system using EMerge Alliance® standards. Before understanding how a Crestron system integrates with EMerge, it is important to know how the EMerge Alliance infrastructure differs from today’s traditional infra-

structure. This guide will touch on the features and benefits that applications of the EMerge Alliance 24 Volt DC standard bring to the table, as well as go into detail on specific Crestron products designed specifically for use with the new EMerge standard.

What is the EMerge Alliance?

The EMerge Alliance is a not-for-profit open industry association leading the rapid adoption of safe DC power distribution in commercial buildings through the development of EMerge Alliance standards. The Alliance was established in 2008 by industry leading corpora-tions including Armstrong World Industries, Johnson Controls, Nextek Power Systems, OSRAM SYLVANIA, and Worthington Armstrong Venture (WAVE). The goals of the Alliance are to create more energy efficient and flexible building spaces while improving overall sustainability.1

EMerge Technology

The Alliance developed an open standard that integrates interior infrastructures, power, controls and a wide variety of peripheral devices, such as lighting, in a common platform to reduce energy loss associated with powering the many digital DC powered devices found in today’s workplaces.1 Currently, the most common application is a low-voltage ceiling grid, capable of powering lighting fixtures. The benefit is an extremely safe and flexible power distribution system for lighting and other potential future uses. In open-plan office space, rearranging desks doesn’t require high costs of rearranging lighting fixtures. Simply relocate an EMerge Alliance Registered fixture to another spot on the grid.

Crestron and the Alliance

Crestron is currently a participating member of the EMerge Alliance. Participating members are key suppliers of products and technology that comply with EMerge standards. As a member, Crestron participates in committee proceedings and plays a role in the develop-ment of specifications. Members have total access to all EMerge specifications, which are critical in development of products.

Crestron has already developed a lighting control system for use with the 24 Volt DC EMerge standard, and plans on continued development of sustainable products which will help grow the standard platform.

1. Taken from www.emergealliance.org.

Intr

od

uctio

n

Page 3: Commercial Lighting Design Guide: 24 Volt DC Edition - EMerge

Crestron 24 Volt DC Design Guide

3

The Crestron 24 Volt DC Lighting Control System

The Crestron 24 Volt DC system is comprised of the following EMerge Alliance Registered products. As with any Crestron system, devices outside of this scope can also be inte-grated, but for the purposes of controlling a lighting system based on EMerge standards, these are the applicable devices.

Model CLC-1DIMFLV2EX-24V

TypeSwitch/0-10V dimmer with infiNET EX™ wireless communication

Details Switched 24-Volt power source feed-thru

Model INET-CBDEX

Type Cameo® Wireless Keypad

Details 2-8 button configurable, custom engravable

Model C2N-CBD-P/E

Type Cameo® Wired Keypad

Details 2-8 button configurable, custom engravable

Model GLS-OIR, GLS-ODT

Type Occupancy Sensor, with IR or Dual Technology

Details Models vary per square footage coverage, mount type and technology

Model GLS-LCL, GLS-LOL

Type Photocell

Details Models vary per square footage coverage and technology

Model MC3

Type 3-Series Control System

Details Includes integrated infiNET EX™ gateway and Ethernet

Model DIN-AP2

Type 2-Series Control System

Details Ethernet based, DIN rail form factor

Model CEN-RFGW-EX

Type infiNET EX™ Wireless Gateway

Details Use with DIN-AP2, or to expand coverage

Cre

stro

n 2

4 V

DC

Syste

m

Page 4: Commercial Lighting Design Guide: 24 Volt DC Edition - EMerge

Crestron 24 Volt DC Design Guide

4

Implementation Overview

POWER SUPPLY

(By Others)

MC3

ELECTRICUTILITY

Color KeySensorCommon/24V0 - 10 VNetwork

LIGHTS ON

LIGHTS OFF

SHADE

SHADE

CLC-1DIM

FLV2EX-24VSetup

Chan. 1

Chan. 2

CLC-1DIM

FLV2EX-24VSetup

Chan. 1

Chan. 2

CLC-1DIM

FLV2EX-24VSetup

Chan. 1

Chan. 2

CLC-1DIM

FLV2EX-24V

GLS-LOL

GLS-OIR

Setup

Chan. 1

Chan. 2

To Other

Fixtures

To Other

Fixtures

CLC-1DIM

FLV2EX-24VSetup

Chan. 1

Chan. 2

1

2

3

4

COMPUTERPWR

NETHW-R

SW-R

ACQUIRE

ACTIVITY

MC3

This diagram illustrates multiple ways of applying the CLC-1DIMFLV2EX-24V. Each row of lighting, identified by its number, is configured differently:

1. A single CLC is powered by the Armstrong® DC FlexZone™ grid. The CLC then passes 0-10V dimming as well as 24VDC power to each lighting fixture.

2. A single CLC is powered by the Armstrong DC FlexZone grid. The CLC then passes 0-10V dimming to each fixture, but only passes 24VDC to one fixture. The second fixture is independently powered directly by the grid.

3. Each lighting fixture and the CLC are independently powered directly from the grid. The CLC passes 0-10V dimming to each fixture attached. This 0-10V signal is daisy-chained across multiple fixtures.

4. Each fixture is independently powered and controlled by a single CLC.

Note that in a typical system, photocells and occupancy sensors can be connected to the nearest CLC-1DIMFLV2EX-24V.

Cre

str

on 2

4V

DC

Syste

m

Page 5: Commercial Lighting Design Guide: 24 Volt DC Edition - EMerge

Crestron 24 Volt DC Design Guide

5

How EMerge Works

Before taking a closer look at the Crestron devices that integrate with EMerge, lets explore the basics of the EMerge system.

1. Ceiling Grid – A special ceiling grid is required for distri-bution of 24 Volts DC to all fixtures. A powered rail with-in the grid structure interconnects with the light fixture for power. The below example is of the Armstrong DC FlexZone Silhouette grid, an EMerge Alliance Registered product:

12" 24"

6'-0"

12"

DC760106 - 6' DC FLEXZONE SILHOUETTE MAIN BEAM ( DO NOT CUT)

DO NOT HANG AT THESE POINTS

760106 - 6' DC FLEXZONE BORDER MAIN BEAM (NON-POWERED) (CAN BE CUT)

DC760108 - 8' DC FLEXZONE SILHOUETTE MAIN BEAM ( DO NOT CUT)

DC760110 - 10' DC FLEXZONE SILHOUETTE MAIN BEAM ( DO NOT CUT)

DC760112 - 12' DC FLEXZONE SILHOUETTE MAIN BEAM ( DO NOT CUT)

MITERED CROSS TEE INTERSECTION

DO NOT HANG AT THESE POINTS

24"

MITERED CROSS TEE INTERSECTION

DO NOT HANG AT THESE POINTS

12" 24"

8'-0"

12"24"

DO NOT HANG AT THESE POINTS

MITERED CROSS TEE INTERSECTION

DO NOT HANG AT THESE POINTS

12" 24"

10'-0"

12"24"

DO NOT HANG AT THESE POINTS

MITERED CROSS TEE INTERSECTION

DO NOT HANG AT THESE POINTS

12" 24"

12'-0"

12"24"

12" 24"

6'-0"

12"24"

MITERED CROSS TEE INTERSECTION

POWER-IN LOCATION (BULB) ONDC FLEXZONE MAIN BEAM

POWER-IN LOCATION (BOX) ONDC FLEXZONE SILHOUETTE MAIN BEAM

ELECTRICALCONDUCTORS

ELECTRICALCONDUCTORS

Armstrong is not licensed to provide professional architecture or engineering design services.

compliance with all Legal Requirements.advised to consult with a duly licensed architect or engineer in the particular locale of the installation to assure

the drawings for a particular installation or their fitness for a particular purpose.Armstrong does not warrant, and assumes no liability for the accuracy or completeness of

applicable for a particular installation.local building codes, laws, statutes, ordinances, rules and regulations (Legal Requirements) that may be

They are not a substitute for an architect's or engineer's plan and do not reflect the unique requirements of These drawings show typical conditions in which the Armstrong product depicted is installed.

The user is DATE:

DRAWN BY:

DWG. NO.

PROJECT NAME:

SCALE:

CHK BY:

PATH:

DESC.:

REV:

CEILING SYSTEMS * ARMSTRONG WORLD INDUSTRIES, INC. * Lancaster, PA * Phone: 877-ARMSTRONG

DC Silhouette - Powered Mains and Non Powered Border Mains.

A1004-21-11

DLH..

Crestron is proud to be an Armstrong DC FlexZone Compatible Partner. For more info on DC FlexZone go to www.armstrong.com/dcflexzone.

2. Power Supply – A 24 Volt DC power supply is wired into AC line voltage. The power supply outputs 24 Volts to different sections on the ceiling grid.

POWER SERVER

OS

OS

S

WALL KEYPAD

OCCUPANCYSENSOR

PS PS PS PS

PHOTOCELLSENSOR

WIRELESS CONTROLLER

WIRELESS CONTROLLER

Armstrong is not licensed to provide professional architecture or engineering design services.

compliance with all Legal Requirements.advised to consult with a duly licensed architect or engineer in the particular locale of the installation to assure

the drawings for a particular installation or their fitness for a particular purpose.Armstrong does not warrant, and assumes no liability for the accuracy or completeness of

applicable for a particular installation.local building codes, laws, statutes, ordinances, rules and regulations (Legal Requirements) that may be

They are not a substitute for an architect's or engineer's plan and do not reflect the unique requirements of These drawings show typical conditions in which the Armstrong product depicted is installed.

The user is DATE:

DRAWN BY:

DWG. NO.

PROJECT NAME:

SCALE:

CHK BY:

PATH:

DESC.:

REV:

CEILING SYSTEMS * ARMSTRONG WORLD INDUSTRIES, INC. * Lancaster, PA * Phone: 877-ARMSTRONG

DC Silhouette - Large Office - Step 7 Control Solutions.

E1804-21-11

DLH..

POWER SERVER

OS

OS

S

WALL KEYPAD

OCCUPANCYSENSOR

PS PS PS PS

PHOTOCELLSENSOR

WIRELESS CONTROLLER

WIRELESS CONTROLLER

Armstrong is not licensed to provide professional architecture or engineering design services.

compliance with all Legal Requirements.advised to consult with a duly licensed architect or engineer in the particular locale of the installation to assure

the drawings for a particular installation or their fitness for a particular purpose.Armstrong does not warrant, and assumes no liability for the accuracy or completeness of

applicable for a particular installation.local building codes, laws, statutes, ordinances, rules and regulations (Legal Requirements) that may be

They are not a substitute for an architect's or engineer's plan and do not reflect the unique requirements of These drawings show typical conditions in which the Armstrong product depicted is installed.

The user is DATE:

DRAWN BY:

DWG. NO.

PROJECT NAME:

SCALE:

CHK BY:

PATH:

DESC.:

REV:

CEILING SYSTEMS * ARMSTRONG WORLD INDUSTRIES, INC. * Lancaster, PA * Phone: 877-ARMSTRONG

DC Silhouette - Large Office - Step 7 Control Solutions.

E1804-21-11

DLH..

3. Cabling – Registered cables are available for making interconnects between the power supply, grid and fixtures.

4. Light Fixture – An EMerge Registered light fixture sits in the ceiling grid like any other typical lighting fixture. Instead of wiring to high voltage, a low voltage “power tap” connects the grid to the fixture to energize it. Most fixtures use 0-10 Volt dimming ballasts.

12" 24"

6'-0"

12"

DC760106 - 6' DC FLEXZONE SILHOUETTE MAIN BEAM ( DO NOT CUT)

DO NOT HANG AT THESE POINTS

760106 - 6' DC FLEXZONE BORDER MAIN BEAM (NON-POWERED) (CAN BE CUT)

DC760108 - 8' DC FLEXZONE SILHOUETTE MAIN BEAM ( DO NOT CUT)

DC760110 - 10' DC FLEXZONE SILHOUETTE MAIN BEAM ( DO NOT CUT)

DC760112 - 12' DC FLEXZONE SILHOUETTE MAIN BEAM ( DO NOT CUT)

MITERED CROSS TEE INTERSECTION

DO NOT HANG AT THESE POINTS

24"

MITERED CROSS TEE INTERSECTION

DO NOT HANG AT THESE POINTS

12" 24"

8'-0"

12"24"

DO NOT HANG AT THESE POINTS

MITERED CROSS TEE INTERSECTION

DO NOT HANG AT THESE POINTS

12" 24"

10'-0"

12"24"

DO NOT HANG AT THESE POINTS

MITERED CROSS TEE INTERSECTION

DO NOT HANG AT THESE POINTS

12" 24"

12'-0"

12"24"

12" 24"

6'-0"

12"24"

MITERED CROSS TEE INTERSECTION

POWER-IN LOCATION (BULB) ONDC FLEXZONE MAIN BEAM

POWER-IN LOCATION (BOX) ONDC FLEXZONE SILHOUETTE MAIN BEAM

ELECTRICALCONDUCTORS

ELECTRICALCONDUCTORS

Armstrong is not licensed to provide professional architecture or engineering design services.

compliance with all Legal Requirements.advised to consult with a duly licensed architect or engineer in the particular locale of the installation to assure

the drawings for a particular installation or their fitness for a particular purpose.Armstrong does not warrant, and assumes no liability for the accuracy or completeness of

applicable for a particular installation.local building codes, laws, statutes, ordinances, rules and regulations (Legal Requirements) that may be

They are not a substitute for an architect's or engineer's plan and do not reflect the unique requirements of These drawings show typical conditions in which the Armstrong product depicted is installed.

The user is DATE:

DRAWN BY:

DWG. NO.

PROJECT NAME:

SCALE:

CHK BY:

PATH:

DESC.:

REV:

CEILING SYSTEMS * ARMSTRONG WORLD INDUSTRIES, INC. * Lancaster, PA * Phone: 877-ARMSTRONG

DC Silhouette - Powered Mains and Non Powered Border Mains.

A1004-21-11

DLH..

Example: Nextek Power Server Module

Ho

w E

Me

rge

Wo

rks

Page 6: Commercial Lighting Design Guide: 24 Volt DC Edition - EMerge

Crestron 24 Volt DC Design Guide

6

Crestron Integration

Crestron 24 Volt Dimmer (CLC-1DIMFLV2EX-24V)

The Crestron 24 Volt DC dimmer is a compact device that installs on or near the lighting fixture(s) it is controlling. The CLC-1DIMFLV2EX-24V uses infinNET EX™ wireless technology to communicate to the control system. Let’s take a closer look:

MODEL: CLCI-DIMUEX-WFILE: CLCI-DIMUEX-W

Cre

str

on Inte

gra

tio

n

Page 7: Commercial Lighting Design Guide: 24 Volt DC Edition - EMerge

Crestron 24 Volt DC Design Guide

7

CLC-1DIMFLV2EX-24V Caps Removed

CLC-1DIMFLV2EX-24V Connector Detail

Chan 1

Chan 2

Setup

Sensor GroundPhoto Sensor InputOccupancy Sensor InputRemote Switch InputSensor/Switch Power FeedUnpolarized Power Input (from Armstrong® DC FlexZone™ grid)

R+ -POSensors24V

- + -SW OUT1 2

+1 20-10 V

0-10V Output*Switched Output

Input Side Output Side

-

*Half moon indicates the switched leg

As you can see, the CLC-1DIMFLV2EX-24V has an unpolorized 24VDC input for powering itself as well as fixtures that are attached to it. The output side connects switched 24VDC and 0-10VDC dimming signal to attached light fixtures. What may strike you as different are the other ports on the input side for photocell and occupancy sensor.

The CLC dimmer allows you to connect sensors directly to it, making wiring a whole lot easier (and in some cases eliminating extra or new wiring altogether).

Cre

stro

n In

teg

ratio

n

Page 8: Commercial Lighting Design Guide: 24 Volt DC Edition - EMerge

Crestron 24 Volt DC Design Guide

8

Individual Office

Lets take a look at a basic, practical application using the CLC-1DIMFLV2EX-24V.

Color KeyControlCommon/24V0 - 10 V

GLS-OIR

CLC-1DIM

FLV2EX-24V

POWER SUPPLY

ELECTRICUTILITY

GLS-LOLSetup

Chan. 1

Chan. 2

MC3COMPUTERPWR

NETHW-R

SW-R

ACQUIRE

ACTIVITY

MC3

By controlling the lighting fixtures with the CLC-1DIMFLV2EX-24V, you also get daylight harvesting and room occupancy sensing simply by adding the sensors. In this example, the fixture closer to the window will be dimmed lower than the one further from the window based on the amount of natural light. The GLS-LOL occupancy sensor measures the outdoor light while the GLS-OIR senses room occupancy.

In some cases a fully-automated room is acceptable (and desired), but in most cases a user will want the ability to adjust the lights manually. Another time and cost saving feature of the CLC dimmer is its ability to interface with a standard light switch. The remote switch input (R) on the CLC dimmer can be connected to a toggle (maintained) or momentary

Cre

str

on Inte

gra

tio

n

Page 9: Commercial Lighting Design Guide: 24 Volt DC Edition - EMerge

Crestron 24 Volt DC Design Guide

9

switch for basic on/off control. If more granular control is desired, a Crestron keypad can be installed in place of a traditional switch. Depending on the keypad however, it may need to be wired to the control system.

The value of this lighting system lies in the wireless communication and flexibility of the CLC-1DIMFLV2EX-24V.

Detailed Wiring of CLC for Individual Office

R+ -POSensors24V

- + -SW OUT1 2

+1 20-10 V

Input Side Output Side

-

0-10V Output*Switched Output*Half moon indicates the switched leg

24 VDCFrom Grid

Chan 1

Chan 2

Setup

Sensor Ground

- + -SW OUT1 2

+1 20-10 V

Output Side

-

GLS-LOL

GLS-OIR

- + -SW OUT1 2

+1 20-10 V

Output Side

-

2nd Fixture

Generic Maintained Toggle Switch*

*As an alternate to the maintained toggle switch, a momentary switch may be used. The behavior with a momentary switch is as follows:

• Press to toggle on/off

• Press and hold to toggle dim up/dn

Cre

stro

n In

teg

ratio

n

Page 10: Commercial Lighting Design Guide: 24 Volt DC Edition - EMerge

Crestron 24 Volt DC Design Guide

10

Entire Building Designs

Crestron EMerge systems can be deployed across entire buildings without much extra work, mostly due to the power and flexibility of infiNET EX.

• Up to 100 CLC-1DIMFLV2EX-24V devices can connect to a single control system (MC3)

• Each CLC device acts as a wireless expander, effectively increasing range whenever more infiNET EX devices are added to the wireless network

• The wireless indoor range is 100 feet from CLC device to CLC device

Optimizing Device Placement

• Each CLC-1DIMFLV2EX-24V is capable of controlling 1 or more fixtures. Since it has 2 channels, it can control 2 lighting groups independently.

• You can connect as many fixtures to each channel that you would like, as long as you do not exceed the maximum switch load rating of the CLC.

Crestron Model Load Rating (per channel)CLC-1DIMFLV2EX-24V 2.5A @ 24VDC (60W)

65mA max current sink (0-10V output)

Cre

str

on Inte

gra

tio

n

Page 11: Commercial Lighting Design Guide: 24 Volt DC Edition - EMerge

Crestron 24 Volt DC Design Guide

11

Example Applications

Open Office

Economies of scale really start to take hold when installing EMerge systems with Crestron in larger office spaces. Easier wiring across multiple units decreases installation time; the ability to move light fixtures around the grid without needing to re-run wire becomes invaluable.

POWER SUPPLY

MC3

ELECTRICUTILITY

Color KeyControlCommon/24V0 - 10 VNetworkLAN

CLC-1DIM

FLV2EX-24VSetup

Chan. 1

Chan. 2

GLS-LOL

GLS-OIR

MC3COMPUTERPWR

NETHW-R

SW-R

ACQUIRE

ACTIVITY

MC3

LAN

Setup

Chan. 1

Chan. 2

CLC-1DIM

FLV2EX-24V

In this example fixtures are controlled in groups of two. One CLC-1DIMFLV2EX-24V connects to four different light fixtures.

• Each light fixture is powered directly from the grid.

• In lieu of a keypad, Fusion EM™ Energy Management Software controls all lights according to a preset schedule. Building managers can make changes in real time from any web browser.

POWER SUPPLY

MC3

ELECTRICUTILITY

Color KeyControlCommon/24V0 - 10 VNetworkLAN

CLC-1DIM

FLV2EX-24V

Setup

Chan. 1

Chan. 2

GLS-LOL

GLS-OIR

MC3COMPUTERPWR

NETHW-R

SW-R

ACQUIRE

ACTIVITY

MC3

LAN

Setup

Chan. 1

Chan. 2

CLC-1DIM

FLV2EX-24V E

xa

mp

le A

pp

lica

tions

Page 12: Commercial Lighting Design Guide: 24 Volt DC Edition - EMerge

Crestron 24 Volt DC Design Guide

12

Conference Room

POWER SUPPLY

MC3

ELECTRICUTILITY

Color KeyControlCommon/24V0 - 10 VNetwork

LIGHTS ON

LIGHTS OFF

SHADE

SHADE

CLC-1DIM

FLV2EX-24VSetup

Chan. 1

Chan. 2

CLC-1DIM

FLV2EX-24VSetup

Chan. 1

Chan. 2

CLC-1DIM

FLV2EX-24VSetup

Chan. 1

Chan. 2

GLS-LOL

GLS-OIR

C2N-CBD-P

COMPUTERPWR

NETHW-R

SW-R

ACQUIRE

ACTIVITY

MC3MC3

This example uses one CLC-1DIMFLV2EX-24V per every 2 light fixtures to provide individual control of each light in the boardroom.

• Each light fixture is powered through the CLC. (Fixtures can also be powered directly from the grid, as long as 0-10V control lines are connected to the CLC).

• A photocell and occupancy sensor are incorporated into the system, placed in ideal locations requiring minimum wiring. (A sensor may be connected to the nearest available CLC).

• A Cameo® Keypad (C2N-CBD-P) is used to provide user control of preset lighting scenes and dim up/down control.

Exa

mp

le A

pp

lica

tio

ns

Page 13: Commercial Lighting Design Guide: 24 Volt DC Edition - EMerge

Crestron 24 Volt DC Design Guide

13

Classroom

POWER SUPPLY

GLS-LOL

GLS-OIR

ELECTRICUTILITY

Color KeyControlCommon/24V0 - 10 VNetwork

CLC-1DIM

FLV2EX-24V

MC3COMPUTERPWR

NETHW-R

SW-R

ACQUIRE

ACTIVITY

MC3

Setup

Chan. 1

Chan. 2

Standard

Toggle Switch

This example uses just a single CLC-1DIMFLV2EX-24V to control all the lights in the classroom.

• Each light fixture is powered directly from the grid.

• Each row of lights is controlled by a separate channel on the CLC. One channel dims the row closest to the windows, while the second channel dims the other row.

• Both a photocell and occupancy sensor are connected to the CLC for energy savings.

• A standard toggle switch provides user control of basic on/off operation.

Exa

mp

le A

pp

lica

tions

Page 14: Commercial Lighting Design Guide: 24 Volt DC Edition - EMerge

Crestron World Headquarters15 Volvo DriveRockleigh, NJ 07647800.237.2041201.767.3400Fax: 201.767.1903crestron.com

Crestron International HeadquartersOude Keerbergsebaan 22820RijmenamBelgium+32.15.50.99.50Fax: +32.15.50.99.40crestron.eu

Crestron Asia HeadquartersRoom 2501, 25/F, Westin CentreNo. 26 Hung To RoadKwun TongHong Kong+852.2341.2016Video Ph: +852.2373.7530Fax: +852.2344.0889crestronasia.com

Crestron Latin America HeadquartersBlvd. Manuel Avila Camacho No 37-1ACol. Lomas de ChapultepecCP 11560 México DF+55.5093.2160Fax: +55.5093.2165crestronlatin.com

Printed in USA Doc.4558 4/11

Products manufactured in the United States.Crestron, the Crestron logo, Crestron Green Light, Cameo, Cresnet, infiNET EX, Fusion EM are either trademarks or registered trademarks of Crestron Electronics, Inc. in the United States, other countries or both. EMerge Alliance is a registered trademark of the EMerge Alliance in the United States, other countries or both. Armstrong and DC FlexZone are either trademarks or registered trademarks of Armstrong World Industries, Inc. in the United States, other countries or both. Other trademarks and trade names may be used in this document to refer to either the entities claiming the marks and names or their products. Crestron disclaims proprietary interest in the marks and names of others.

Specifications subject to change without notice. Refer to www.crestron.com for detailed specifications.©2011 Crestron Electronics, Inc.